    CalculationofMakeupWater

    Circulatingwaterquantity R 200 m3/h

    Temperaturedrop T 10 O

    C

    Latentheatofwater HL 2260 kJ/kg

    Sp.Heatofwater C 4200 kJ/kgK

    Cycleofconcentration 8

    A. Eveporationloss,E= RHL/CT

    = 10.76 m3/h

    B. Windageloss,W = 0.2%ofR

    = 0.40 m3/h

    C. Blowdownwaterquantity,B

    = [E/(COC1)] W

    = 1.14 m3/h

    Makeupofwater= E+W+B

    = 12.30 m3/h

    SomakeupwaterprovidedbySINOMAisok