CalculationofMakeupWater
Circulatingwaterquantity R 200 m3/h
Temperaturedrop T 10 O
C
Latentheatofwater HL 2260 kJ/kg
Sp.Heatofwater C 4200 kJ/kgK
Cycleofconcentration 8
A. Eveporationloss,E= RHL/CT
= 10.76 m3/h
B. Windageloss,W = 0.2%ofR
= 0.40 m3/h
C. Blowdownwaterquantity,B
= [E/(COC1)] W
= 1.14 m3/h
Makeupofwater= E+W+B
= 12.30 m3/h
SomakeupwaterprovidedbySINOMAisok