Cooling Tower 6MW

download Cooling Tower 6MW

of 6

Transcript of Cooling Tower 6MW

  • 7/27/2019 Cooling Tower 6MW

    1/6

    FIRST METHOD

    Input parametersHot water temperature 40.5 C

    Cold water temperature 29.5 C

    Wet bulb temperature 26 C

    Range of cooling tower 11 C

    Approach 3.5 C

    Diameter of fan 3.8 m

    Diameter of fan hood 3.9 m

    Avarage air velocity at exit 6 m/s

    Density of water 1000 Kg/m^3

    Density of air 1.2 Kg/m^3

    Specific heat capacity of water 4.178 kj/kgK

    Air mass flow rate of fan hood (G) 86.1202368 kg/s

    Water mass flow rate( L) 111 kg/s/cell

    Water mass flow rate/air mass flow rate 1.288895666

    Enthalpy pick up water

    (H2-H1) = L/G(t2-t1)[1+0.0008(t2-32)]

    H2-H1 26.6042295 BTU/lb of a

    Heat balance calculation

    G(H2-H1) = L(T1-T2)+Ev x cold water temperature

    Heat removing capacity of water = Heat rejection rate in the process

    Heat removing capacity of the tower 1260.139399 Kcal/sec

    Heat rejection rate in the process 18184118.35 BTU/Hr

    Is almost equal Hence Heat balance is establishedOther ParametersAir flow calculation 71.766864 m^3/sec

    Approach 3.5 C

    Range 11 C

    Drift loss 0.3996 m^3/hr

    Evaporation loss 6.725268 m^3/hr

  • 7/27/2019 Cooling Tower 6MW

    2/6

    Dry bulb teperature 30 C

    Wet bulb temerature 26 C

    Relative humidity 72 %

    If fan RPM reduced to 50%(an approximately 40% reduction in air flow rate)

    0.1 bar at

    45.8 C

    29.5 C

  • 7/27/2019 Cooling Tower 6MW

    3/6

    COOLING TOWER DESIGN

    Second me

    104.9 F Estimate outlet85.1 F Enthalpy of air outlet

    78.8 F Enthapy of air inlet at

    19.8 F

    6.3 F

    L/G

    Air mass flow rate

    Calculate towedelta ha

    1 BTU/Lb F

    T has

    85.1 53.1

    87.08 55.13

    71.766864 m^3/sec 95 63.04

    880966.3645 lb/hr/cell 0.111 m^3/sec/cell 399.6 m^3/hr/cell 96.98 64.83

    102.92 70.94

    104.9 73.02

    ir 14.63233 Kcal/kg of air

    (Ka*V)/L

    Determine the loading

    Ka

    4536501.837 Kcal/Hr

    4580579.413 Kcal/Hr

    This Tower characteristic Graph

  • 7/27/2019 Cooling Tower 6MW

    4/6

    86 F

    78.8 F

    Determine

    40.5 C

  • 7/27/2019 Cooling Tower 6MW

    5/6

    hod

    air temperature 35 C 95 Ft 37.5 C or 99.5 F saturated 145 kj/kg 62.35 BTU/lb

    et bulb tem 26 C or 78.8 F 80 kj/kg 34.4 BTU/lb

    1.411616

    78.63327 Kg/s

    characteristic by the simpsion rule13 kj/kg 5.59 BTU/lb

    ha has-ha 1/(has-ha)

    34.4 18.7 0.053476

    37.195 17.935 0.055757

    48.375 14.665 0.06819

    51.17 13.66 0.073206

    59.555 11.385 0.087835

    62.35 10.67 0.093721

    0.071247

    1.41069

    factor as per graph 2.5 GPM/ft^2 1111.5 lbs/hr/ft^2

    100

    cooling water temperature 10F above wet bulb temperature

  • 7/27/2019 Cooling Tower 6MW

    6/6

    the tower dimentions

    Tower hight 15.67981 ft 4.779207 m

    Area of tower 121345.6 ft^2 11273 m^2