Cooling Path Case Study Whitepaper
-
Upload
bangalore79 -
Category
Documents
-
view
220 -
download
0
Transcript of Cooling Path Case Study Whitepaper
-
8/8/2019 Cooling Path Case Study Whitepaper
1/18
A WHITE PAPER FROM
FUTURE FACILITIES INCORPORATED
Cooling Path Management for the Mission
Critical Facility (MCF): A Case Study
A simulation-based methodology to maximize equipmentresilience and cooling energy efficiency
Akhil Docca and Sherman Ikemoto
2/28/2008
Executive summary
The proliferation of modern, high-powered IT equipment is creating a new set of coolingchallenges in the data center that can reduce equipment resilience well before the coolingcapacity of the room is reached. This is forcing owner/operators to take a conservativeapproach by overcooling the data center paying more excessively to operate the coolingsystems. This paper is a case study for cooling path management; a simulation basedmethodology to maximize IT equipment resilience and cooling energy efficiency.
-
8/8/2019 Cooling Path Case Study Whitepaper
2/18
2 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
A Case Study for Cooling Path ManagementThe Cooling PathCooling path management is a simulation-based methodology for data center cooling system
management. The methodology is based on the Virtual Facility approach to data center
modeling which takes all of the major elements of the data center into full account, including theinfrastructure, cooling components, cabinets and IT equipment. The cooling path is defined as
the route taken by the cooling air from the ACU supplies, to the inlets of each individual unit of
IT equipment and back to the ACU returns. Cooling paths are intricate and complex as they
exist in the data center but are intuitive as a management methodology and straightforward to
control within the Virtual Facility model to achieve operational objectives for the cooling system.
Cooling path management is the process of stepping through the full route taken by the cooling
air and systematically minimizing or eliminating cooling breakdowns and inefficiencies with the
ultimate goal of meeting the air intake requirement for each unit of IT equipment. Strict
adherence to the methodology eliminates the need to know in advance where to look for
problems and enables design options to be addressed holistically over the full scale of the roomfrom the equipment inlets and exhausts to the room itself.
The cooling path can be split into three primary segments that simplify the methodology as
shown in Figure 1.
Figure 1: The Cooling Path is the route taken by the cooling air from the ACU supply to the
perforated tiles, to the equipment inlets and back to the ACU return
Each segment has its own specific objectives for improvement and associated set of change
options for achieving the objectives. This makes the methodology easy to use, repeatable and
applicable to all combinations of IT equipment, cabinets and rooms. The objectives and
associated change options are shown in Table 1.
-
8/8/2019 Cooling Path Case Study Whitepaper
3/18
3 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
Segment Description Design Objective Problem areas Design Options1 ACU supply to
perforated tile Meet flow rate andtemperaturespecification for
each perforated tile
Low pressures
zones due to low
airflow or flow
vortices
ACU selection andplacement
Blockage relocation
Tile placement Baffles/diffusers
2 Perforated tileto equipment
inlets Meet flow rate andtemperaturespecification foreach piece ofequipment
Bypass flow from
perforated tiles to
ACUs Blanking ACU controls Equipment redistribution Hot/cold aisle Ducting Hot/cold aisle
containment
3 Equipmentexhausts to
ACU returnRecirculation from
equipment
exhausts to inlets
Table 1: The Cooling Path is divided into three segments to simplify the methodologyThe cooling paths are influenced by the room configuration, the IT equipment and how they are
arranged relative to each other. Any changes to the facility including ACU settings, cabinet
arrangement and equipment placement will change fundamentally the cooling paths. Cooling
path management, therefore, is appropriate to initial design of the room and to configuration
management throughout the data center life span in order to manage cooling problems or
inefficiencies that creep in over time.
More information on cooling path management and the Virtual Facility can be found on the
Future Facilities website (www.futurefacilities.com).
Case Study DescriptionCooling path management with the Virtual Facility is best illustrated with a case study. Figure 2
shows a small but representative Virtual Facility that was built in the 6SigmaRoom design
software. The main objective of the methodology is to minimize cooling problems and maximize
cooling system efficiency by managing the cooling path for each unit of IT equipment in
accordance with design objectives. The process should be re-applied for every major change to
the room configuration or IT equipment.
http://www.futurefacilities.com/http://www.futurefacilities.com/http://www.futurefacilities.com/http://www.futurefacilities.com/ -
8/8/2019 Cooling Path Case Study Whitepaper
4/18
4 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
Figure 2: Isometric view of the data center case study
The case study room is designed to the following specifications:
1000 sq.ft
23 cabinets, 3.75 kW/cabinet
90 kW total load, 90 W/sq.ft
4 ACUs , 120 kW total cooling capacity, n+1
Three IT equipment configurations were studied to illustrate how cooling path management is
performed as part of the inventory management process. The configurations selected for studyare:
Initial design or pre-commissioning
Loaded to 30% of cooling capacity
Loaded to 80% of cooling capacity
Now, lets take a detailed look at each section of the facility starting from the raised floor.
Raised Floor:The raised floor stands 2 feet off the ground and is non-rectangular to accommodate an
entrance ramp. The ACUs reside within the room and the chilled water supply plumbing lieunder the raised floor alongside the data and power cables. These must be included the Virtual
Facility model as they have a significant impact on Segment #1 of the cooling path.
ACU 01PDU 01
PDU 02
PDU 03
ACU 02
ACU 03
ACU 04
Perforated tiles
Raised Floor
Cutout
-
8/8/2019 Cooling Path Case Study Whitepaper
5/18
5 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
Figure 3: Under floor obstructions
Air Conditioner Unit (ACU):There are 4 ACUs in the room capable of providing 30 kW of cooling and 4,200 CFM of air at
maximum return air temperature of the 20 C. The set point for each is 22 oC. The ACU control
system is important to model properly in the Virtual Facility to simulate the actual behavior of the
ACU in the data center. The ACU libraries and generic models that are available within
6SigmaRoom model the controls properly and can accurately predict the potential cooling and
efficiency problems that can occur at any point along the cooling path.
Figure 4: ACUs are rated at 30 kW of cooling at a maximum return air temperature of 20
Cable Trays
Chilled WaterPipes
Power Cables
-
8/8/2019 Cooling Path Case Study Whitepaper
6/18
6 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
Cabinets:There are a total of 23 Cabinets in the room. 20 of these have been specified to house servers
and storage equipment (2000 mm height x 600 mm width x 900 mm depth) and the remaining
three have been specified to house networking equipment (2000 mm height x 800 mm width x
900 mm depth). All the cabinets are on casters and are 50 mm (2) above the raised floor. The
cable penetrations at the rear of the cabinets have cold-locks and have a sealing efficiency of80%. The cabinet libraries available within 6SigmaRoom contain all of the detail necessary to
predict with a high level of accuracy potential cooling and efficiency problems that can occur
along cooling path Segments #2 and #3.
Figure 5: Cabinet & Equipment View
Cooling Path Design at Three Stages of LifeInitial design or pre-commissioning:The initial design of the data center is done often without specific knowledge of the equipment
that will eventually populate the cabinets. At this stage, the focus of cooling path design is
limited to Segment #1 as design of Segments #2 and #3 have little meaning given the lack of
information about the IT equipment that will eventual be deployed. Here, simple 3.75 kW of
load evenly distributed over the vertical height of each cabinet is used to approximate the fully
loaded condition. In reality, this is far from the worst case thermal loading condition, but has
become the standard configuration for cooling design at the pre-commissioning stage.
Segment #1 is the path from the ACU supplies to the perforated tiles. The design goal is to
supply a minimum of 450 CFM of cooling air to each perforated tile; an amount, in theory,
sufficient to hold the 3.75kW cabinets to a temperature rise of 15 C. The ACUs, tiles and
under-floor obstructions (chilled water pipes, data cables & power cables) can be configured in
the room to achieve the design goal.
Cabinet Exterior Shell
Cabinet Interior Shell (Mounting Rails,
Equipment & Empty U Slots
-
8/8/2019 Cooling Path Case Study Whitepaper
7/18
7 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
The Virtual Facility reveals a breakdown in Segment #1 of the cooling path in the form of low
flow by 100 CFM at tile O8 as shown in Figure 6.
Figure 6: Airflow rate coded by color at each perforated tile
The under-floor airflow and pressure distribution reveals the root of the problem as shown in
Figure 7.
Figure 7: Velocity vector plot of airflow under the raised floor. Note the indicated airflow vortex.
Airflow vortex Low pressure zone
Flow from tile O8 is
below specification
by 100 cfm
-
8/8/2019 Cooling Path Case Study Whitepaper
8/18
8 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
The vortex creates a low pressure zone that reduces the airflow at the corresponding perforated
tile (O8) to 450 CFM. This vortex has to be minimized or eliminated to bring Segment #1 to
specification. Referring to Table 1, under floor problems can be addressed by four methods.
We start by examining the location of ACU 04 which is supplying the air that is swirling under tile
O8. After testing a few different locations, the Virtual Facility revealed that a 2 foot shift to the
left of ACU 04 (Figure 8) reduces the vortex enough to meet the airflow specification.
Figure 8: ACU 04 was shifted by 2 feet to the left to reduce the vortex generated on the
downstream side of the floor cutout.
This design change resulted in a 30% increase in flow rate at tile O8 from 450 to 586 CFM
above the required 550 CFM specification as shown in Figure 9.
Figure 9: Reducing the under-floor vortex increases the flow to the corresponding perforated tile
Tile flow rate at 450 CFM originally Tile flow rate at 600 CFM after the design change
2 shiftACU 04
-
8/8/2019 Cooling Path Case Study Whitepaper
9/18
9 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
More optimization can be done, but given that specifications are met, cooling path design for the
pre-commissioning stage is complete. Without knowledge of the equipment, Segments #2 (tile
to equipment inlet) and #3 (equipment exhaust to ACU) of the cooling path are undefined which
makes cooling path design for these segments ineffectual.
In addition to the tile flow rate specification, a hot aisle/ cold aisle arrangement is specified to
further ensure the resilience of equipment that will eventually populate the room. As we will see
later in the case study, room-side thermal design guidelines like the hot aisle/cold aisle can be
defeated easily by high power IT equipment.
Loaded to 30% of cooling capacityThe case study continues at the stage when the first wave of equipment is deployed and cooling
path Segments #2 (from the tiles to the equipment inlets) and #3 (from the equipment exhausts
to the ACUs) come into play for the first time. The room is loaded to 30% of its cooling capacity
as shown in Figure 10.
Figure 10: Data center loaded to 30% of cooling capacity
The Virtual Facility reveals a cooling path problem for a networking unit as shown in Figure 11.
Figure 11: The color plot shows an over temperature problem within the networking cabinet
Overheated
networking unit
4 networking units
in two cabinets
36 storage units in 3
cabinets
27 computing units in 7
cabinets
-
8/8/2019 Cooling Path Case Study Whitepaper
10/18
10 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
We know from the design of Segment #1 that sufficient air is being supplied to the tile in front of
the cabinet, therefore the problem must exist in cooling path Segments #2 or #3 for this piece of
equipment. Lets start with Segment #2 where bypass air is the problem to be examined.
6SigmaRoom can calculate a useful metric called ACU Supply Effectiveness Indexto quantify
the amount of air that bypasses the equipment and returns directly to the ACUs.
ACU Supply Effectiveness: the overall percentage of cooling air supplied by the ACUs that
enters the equipment intake vents (as opposed to returns directly to ACU)
In the current configuration, only 24% of the cooling air supplied enters the equipment. This
value can be confirmed graphically by the airflow patterns in front of the networking cabinets as
shown in Figure 12.
Figure 12: 76% of the cooling air supplied by the perforated tiles bypasses completely theequipment inlets and returns directly to the ACUs
A secondary effect of the bypass is poor operating efficiency for ACUs 01 and 02 as shown in
Figure 13 on the right. The air returns at a relatively cool temperature of 20 C which reduces
the cooling effect of ACUs 01 and 02 according to the cooling profile shown in Figure 4. As a
result, ACUs 01 and 02 supply the networking equipment with air that is warmer than desired as
shown in Figure 13 on the left.
The amount of bypass air is
significant in the current
configuration
-
8/8/2019 Cooling Path Case Study Whitepaper
11/18
11 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
Figure 13: Non-uniform supply temperature is shown on the left that is dictated primarily by ACU
operating efficiency that is show on the right
Both the effectiveness index and the non-uniform supply temperature strongly indicate that
reducing bypass will improve the cooling problem for the networking unit. At the very least, a
significant amount of cooling energy could be saved.
Referring to Table 1, bypass reduction for Segment #2 can be accomplished in this case by four
methods:
Shutting down ACU 01 and 02 (this option has the added benefit of reducing cooling
costs) and making the remaining 3 ACUs to operate at a higher efficiency
Reducing the supply flow rate from the ACUs by 50% (assuming variable speed drives
are in use)
Shutting off floor grilles in front of cabinets without any equipment to force the air to
reach the cabinets with equipment in them
Redistributing the networking equipment equally in 4 cabinets instead of two
The options were implemented one at a time to assess the impact individually. Eventually all
the four options had to be implemented to achieve the best possible result on the resilience of
the networking equipment without incurring a lot of cost. The resulting overheat plot in Figure
14 shows that all the networking units that were originally operating above the specifiedtemperature limit are now below the limit.
ACU 02
ACU 01
ACU 03
ACU 04Warm air being supplied
by ACUs 01 and 02
-
8/8/2019 Cooling Path Case Study Whitepaper
12/18
12 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
Figure 14: The over temperature condition has been eliminated as a result of reducing bypass
air associated with the networking equipment
This result is somewhat counterintuitive in that the over temperature condition was eliminated by
cutting the cooling supply in half. Figure 15 illustrates why this happened.
Figure15: Segment #2 cooling path before and after shutting off ACUs 01 and 02.With all the changes made, less cooling air is being supplied, but the supply temperature is
lower by 5 C. Also, the ACU supply effectiveness has increased from 24% to 47%, which is a
marked improvement over the original facility layout. These combine to solve the temperatureproblem and reduce the cooling system operating cost by 50%.
Cooling path design summary at 30% loading:
IT equipment cooling problems can occur in a partially loaded data center
Bypass is high before proposed changes Bypass is reduced after implementing the changes
-
8/8/2019 Cooling Path Case Study Whitepaper
13/18
13 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
IT equipment cooling problems are most often associated with cooling path Segments
#2 and #3 as Segment #1 is typically within specification when the room is
commissioned
In this case, the problem was too much bypass air in Segment #2.
The problem was fixed by shutting down two ACUs, closing the floor grilles in front of
empty cabinets and distributing the networking equipment evenly in networking row ofcabinets.
Loaded to 80% of cooling capacityOur case study continues with the introduction of new equipment that loads the room to 80% of
its cooling capacity as shown in Figure 16. 80 units have been added and the room power
dissipation has increased from 40 kW to 77 kW. All four ACUs are now operational to
accomodate the increased equipment load; damper settings have been removed from the
perforated floor tiles to faciliate maximum airflow to all cabinets.
Figure 16: 58 servers, 84 storage units and 8 networking units are added to the room.
8 networking units
in 4 cabinets
84 storage units in 7
cabinets
58 computing units in
13 cabinets
-
8/8/2019 Cooling Path Case Study Whitepaper
14/18
14 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
Thermal problems are expected to reappear with the change, and they do as shown in Figure
17.
Figure 17: New over temperature problems within one computing and networking cabinet
The equipment within cabinets C5 and N6 are receiving cooling air that is above their specified
maximum. A look inside the Cabinets C5 and N6 (Figure 18) shows the specific units that areoverheating.
Figure 18: Equipment overheat plot C5 and N6 cabinets
A walk through of the cooling path in the Virtual Facility shows that Segments #1 and #2 are fine
for both the blade server and networking switch. However, the Virtual Facility reveals that
Segment #3 problems exist for both units as a significant amount of hot air is being re-circulated
from the exhausts to the inlets as shown in Figures 19 and 20. At this stage, the concept ofeffectivness indices will be used again as a metric to improve the design. This time, the
efficiency index will be associated with the equipment inlets.
Equipment Supply Effectivness - the percentage of cooling air entering a specific piece of
equipment that comes directly from an ACU supply (as opposed to the exhaust of a neighboring
piece of equipment)
IBM Blade
Center 1
Rackable C3106
C5 Cabinet N6 Cabinet
Cisco 6509
networking
switches
Cabinet C5Cabinet N6
-
8/8/2019 Cooling Path Case Study Whitepaper
15/18
15 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
In the current configuration, only 51% of the air enters the IBM Blade Center 1 comes from the
ACU supply as shown in Figure 20.
Figure 20: Hot air from the server across the hot aisle and from its own exhaust is re-ingested
Specifically, the IBM Blade Center 1 ingests warm exhaust air from two locations a) from its own
exhaust and b) from the HP DL360 G5 server that sits across the hot aisle. In this case, the hot
aisle/cold aisle arrangement was defeated by the equipment it was implemented to protect.
The remaining cabinets in row C house HP DL 360 G4 servers that have a different fan
characteristic from the G5 servers and blow air into the hot aisle at a lower velocity. Without the
additional hot air from across the aisle, the IBM Blade Center servers in the remaining cabinets
(C4, C7, C8, C9 & C10) do not overheat.
For the Cisco unit, 52% of its cooling air comes directly from an ACU as shown in Figure 21.
Figure 21: Hot air from the exhaust re-circulates into the intake of the Cisco 6509
-
8/8/2019 Cooling Path Case Study Whitepaper
16/18
16 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
Specifically, the Cisco 6509 power supply at the bottom of the unit is ingesting air that is
exhausted from the line cards that sit above in the same chassis.
The re-circulating exhaust air must be reduced to improve the Segment #3 cooling paths for the
overheating IBM Blade Center 1 and Cisco 6509 units. Referring to Table 1, a simple and cost-
effective way of reducing re-circulation is to install blanking panels in the empty slots of the
cabinet. For the IBM unit, most of the exhaust air is prevented from flowing to the front of the
cabinet where it can be entrained into the inlets as shown in Figure 22.
Figure 22: Blanking solves the cooling problem for the IBM Blade Center 1 by preventing
enough exhaust air from re-circulating to the intake
However, more must be done to solve the cooling problem for the Cisco unit. Here, internal
cabinet baffling is installed within the cabinet to segregate the intake and exhaust air as shownin Figure 23.
Figure 23: Internal baffling solves the cooling problem for the Cisco 6509 by segregating the
intake and exhaust air between the PSU and the Line Cards
-
8/8/2019 Cooling Path Case Study Whitepaper
17/18
17 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
The resulting overheat plot in Figure 24 shows that all the equipment in the data center is
operating under maximum allowable inlet temperature for the room at 80% cooling load. In
other words, the full cooling path for each unit of equipment has been designed and
implemented properly.
Figure 24: The cooling problems have been fixed for the room at 80% of cooling capacity
It is important to emphasize once again that each individual unit of equipment in the Virtual
Facility is modeled explicitly to attain sufficient modeling resolution for full cooling path design.
Equipments from different vendors have unique power dissipation and air flow characteristics
such as intake and exhaust size and location and fan flow rates. Capturing these details is
critical to defining fully cooling path Segments #2 and #3 in the Virtual Facility. Lacking thesedetails would have prevented in this case the insight necessary to solve the cooling problems,
maximize equipment resilience and improve cooling system efficiency.
Summary Points High power dissipation and power cooling fans within the IT equipment are driving the
need for a new simulation-based methodology called cooling path design
Room-side design guidelines such as specified tile flow rates and hot aisle/cold aisles do
not ensure resilience for modern IT equipment
Cooling path design is the systematic improvement of the entire cooling path for every
unit of equipment in the data center
Cooling path design must be performed for every change in inventory or room
configuration as these have a fundamental impact on the cooling path definition for the
affected equipment
The Virtual Facility, with its ability to model and track changes to the inventory explicitly,
provides an effective platform for cooling path design
In this case study, the follow objectives were achieved:
-
8/8/2019 Cooling Path Case Study Whitepaper
18/18
18 Future Facilities Incorporated. All rights reserved. No part of this publication may be used reproduced or photocopied, transmitted, or stored in a retrievalsystem of any nature, without the permission of the copyright owner. www.futurefacilities.com | A White Paper from FUTURE FACILITIES INCORPORATED
Stage Problem area Design achievementPre-commissioning Swirling flow under perforatedtile leading to low flow Met the tile flow ratespecification for the room30% loaded to
capacity Overheating equipment Wasted cooling capacity
Solved cooling problem for
networking equipment
Reduced cooling cost by 50%
80% loaded to
capacity Overheating equipment Solved complex coolingproblem for networking andblade server
References1. ASHRAE. (2005) Datacom Equipment Power Trends and Cooling Applications. Atlanta:
ASHRAE
2. ASHRAE. (2006) Design Consideration for Datacom Equipment Centers. Atlanta: ASHRAE
3. Garday, D and Costello, D. (2006) Air-Cooled High-Performance Data Centers: Case
Studies and Best Methods.http://www.intel.com/it/pdf/air-cooled-data-centers.pdf
4. Malone, C. and Belady, C. (2006) Data Center Power Projections to 2014. iTHERM 2006,
San Diego, CA
5. Malone, C. and Belady, C. (2006) Metrics to Characterize Data Center IT Equipment Energy
Use. Proceedings of 2006 Digital Power Forum, Richardson, TX
6. Patel, C.D., Sharma, R, Bash, C.E., Beitelmal, A. (2002) Thermal Considerations in Cooling
Large Scale High Compute Density Data Centers, (2002) Inter Society Conference on
Thermal Phenomena, pg 767-776
7. Patterson, M., Costello, D., and Grimm, P. (2007) Data Center TCO, A Comparison of High-
Density and Low-Density Spaces, Hillsboro, Thermes 2007, Santa Fe, NM
8. VanGilder, J.W. and Schmidt, R.R. (2005) Airflow Uniformity through perforated tiles in a
raised-floor Data Center. ASME Interpack 05, San Francisco, CA
AuthorsAkhil Docca is the Engineering Services Manager at Future Facilities Inc.
Sherman Ikemoto is the General Manager of Future Facilities Inc.
http://www.intel.com/it/pdf/air-cooled-data-centers.pdfhttp://www.intel.com/it/pdf/air-cooled-data-centers.pdfhttp://www.intel.com/it/pdf/air-cooled-data-centers.pdfhttp://www.intel.com/it/pdf/air-cooled-data-centers.pdf