Coolex Rooftop Package 48120 r 407 c

24
 www .coolex.com.kw Rooftop Package Series R-407C 48-120 MBH Packag ed Air Conditioning Units With Hermetic Compressor Tropical 50 Hz  For more technical information please visit  www .coolex.com.kw 

description

Coolex Rooftop PackageModel_ 48120 r 407 cSelection of Units and Design data Selection Procedure

Transcript of Coolex Rooftop Package 48120 r 407 c

Page 1: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 1/24

 www.coolex.com.kw 

Rooftop Package SeriesR-407C 48-120 MBH

Packaged Air Conditioning UnitsWith Hermetic Compressor Tropical

50 Hz

 For more technical information please visit  www.coolex.com.kw 

Page 2: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 2/24

 www.coolex.com.kw 1

Table of Contents

INTRODUCTION 2

NOMENCLATURE 2

UNIT RATING SUMMARY 3

OUT STANDING FEATURES 3

STANDARD SPECIFICATIONS 5

OPTIONAL SPECIFICATIONS 6

SELECTION PROCEDURE 7

GENERAL DATA 8

PERFORMANCE DATA TABLES 9

UNIT ELECTRICAL DATA 12

SUPPLY AIR PERFORMANCE 13UNIT DIMENSIONS 14

TYPICAL WIRING DIAGRAMS 17

LOAD DISTRIBUTION 18

NOTES 19

1. Air Cooled Screw Water Chillers

2. Air Handling Units

3. Ducted Split Units

4. Concealed Split Units

5. Fan Coil Units

OTHER COOLEX PRODUCTS

Page 3: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 3/24

 www.coolex.com.kw 2

NOMENCLATURE

Unit Series Description PNGc Package New Generation,

R-407C Refrigerant

A

B

C

D

E

F

G

H

I

J

External Overload for each condenser fan motor External overload for evaporator fan motor Circuit breaker for each compressor circuit breaker for each condenser fan motor circuit breaker for evaporator fan motorA, BC, DA, C, DC, D, EA, B, C, D, E

A

BCDEFGHIJKLMNO

PQ 

Double skin

2 in aluminum filter Sight glassstainless steel drain pancondenser coatingEvaporator coatingcopper finsModulating High and Low pressure switchesHigh and Low Pressure Gaugesair flow switchA, BA, B, DH, IE, FE, F, G

D, E, FOther Combination and options to be assignedin the quotation

Cooling CapacityNominal MBH48 - 6076 - 90100 - 110120

Code DescriptionA First SeriesB Second SeriesC Third Series

Electrical Specifications

2 415/3Ph/50Hz

Electric HeaterX X kW value

INTRODUCTION

COOLEX UL listed, High Efficiency ResidentialPackage Units (PNGc) are designed specificallyfor tropical operation with high performance, lowpower consumption, easy installation and low noiseoperations.PNGc Residentiall units are available from 48 to 120nominal MBH at 50Hz.

Quality and Efficiency make COOLEX aircooled package units the preferred choicefor DX cooling systems in Residentialapplications.Coolex Packaged Units can be used forcooling or heating with optional electricheater.

PNGc 076 C 2 H10 A A

Page 4: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 4/24

 www.coolex.com.kw 3

Rating Conditions: Indoor Temperature DB = 800 F (26.7 0 C).  WB 67 0 F (19.40 C).

UNIT RATING SUMMARY

OUT STANDING FEATURES

Controls• Single point power supply

• Color coded wires

• Weather proof Control panel

Options & Accessories

• Microprocessor based control

• Totally Enclosed Fan cooled (TEFC) Blower Motor

• Intelligent air Quality System by Economizer control

• Ultra Violet (UV) lamps

Superior Efficiency• High EER (Energy Efficiency Ratio)

• Low power consumption

• High volumetric efficiency scroll compressors

• Designed to operate at severe ambient temperature

up to 52°C without tripping

Quiet operation

• Low noise level compressors, condenser fans

and evaporator blower

• Compact physical footprint

 

Model

 Air 

Flow

(CFM)

Cooling

Capacity

(Btu/h)

Total

Power

(kW)kW/Ton EER

Cooling

Capacity

(Btu/h)

 Ambient temp 95°F Ambient temp 115°F Ambient temp 118.4°F Ambient temp 122°F

Total

Power

(kW)kW/Ton EER

Cooling

Capacity

(Btu/h)

Total

Power

(kW)kW/Ton EER

Cooling

Capacity

(Btu/h)

Total

Power

(kW)kW/Ton EER

PNGc-048 C2

PNGc-060 C2

PNGc-076 C2

PNGc-090 C2

PNGc-100 C2

PNGc-110 C2

PNGc-120 C2

1800

2200

2600

2800

3300

3600

4200

50725

59920

74234

89468

99643

106696

116616

4.91

5.52

7.25

8.35

8.88

9.60

11.04

1.16

1.10

1.17

1.12

1.07

1.08

1.14

10.34

10.86

10.24

10.72

11.22

11.11

10.56

45630

54911

66122

84034

91524

98669

109915

5.83

6.44

8.58

9.69

10.63

11.30

13.13

1.53

1.41

1.56

1.38

1.39

1.37

1.43

7.83

8.53

7.71

8.68

8.61

8.74

8.37

44765

53420

64774

77397

88345

97706

101776

6.03

6.64

8.79

9.91

10.83

11.65

13.48

1.62

1.49

1.63

1.54

1.47

1.43

1.59

7.42

8.04

7.37

7.81

8.16

8.38

7.55

43640

51593

63044

74778

84977

96222

99038

6.27

6.89

8.99

10.21

11.14

12.06

13.97

1.72

1.6

1.71

1.64

1.57

1.50

1.69

6.96

7.49

7.01

7.32

7.63

7.98

7.09

Page 5: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 5/24

 www.coolex.com.kw 4

OUT STANDING FEATURES

Evaporator’s Side• Easy access to the evaporator side with removable panel for

maintenance purpose for the fan, motor, belt, pulleys, andexpansion device

• Easy access to drain pan for cleaning

Compressor’s Side• Easy access to the compressor side with removable panel

for maintenance purpose for the compressor, and filter drier• Easy access to condenser fans, and motors

Electrical Panel

• Easy access to the electrical panel with removable panel formicroprocessor access and electrical parts

Page 6: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 6/24

 www.coolex.com.kw 5

STANDARD SPECIFICATIONSGeneral

• The Package New Generation units (PNGc) are factory assembled cooling or combination of cooling and heating with electric heater, suitablefor outdoor installation mounting on the roof or ground.

• The packaged unit consists of scroll compressors, cooling coil, condenser coil, fans, electric heater (optional), control wiring and interconnectingpiping-all factory assembled.

• The units are rated and tested in accordance with ARI 340/360 standard.• The units are UL listed, in accordance to UL 1995 & CSA C22.2 No.236-11.Certificate Number 20130301-SA33594• The units cooling coils are AHRI certified (Reference Number 6742831) and rated according AHRI standard 410-2005

Condenser CoilsThe coils are built up seamlesscopper tubes and mechanicallybonded to scientifically designedlouvered fins.

The assembled coils are factoryleak tested under water at apressure of 450 psig for qualityand leak free unit.

Condenser FansThe fans are selected for optimumefficiency and maximum soundpower reduction, propeller type anddirect driven, upward discharge andprovided with fan grille mounted on

 the casing.

Unit CasingThe casing sheet metal isfabricated from hot dipped G90,Zinc coating and zero spanglegalvanized steel, oven-baked

powder coated.The unit is provided with anintegral weather resistant controlpanel for outdoor application.

Evaporator CoilsThe coils are built up of ripple finned seamless copper

 tubes and mechanically bonded to scientifically designedlouvered fins.The assembled coils are factory leak tested under waterat a pressure of 350 psig for quality and leak free units.

Drain PanThe drain pan isfabricated of galvanizedsteel. The drain pan ispowder coat paintedand the outer surface is

 thermally insulated.

Condenser Fan MotorCondenser fan motors are

 totally enclosed air-over type with class F insulation. Themotors are provided withinherent thermal protectionand auto rest type.

Evaporator FanThe units are provided withcentrifugal fans which arestatically and dynamicallybalanced, designed for low

sound level operationDirect drive motors forPNG048/060 models andremaining models PNG076 to120 are belt driven.

CompressorThe compressors are scroll type

 with crankcase heater, internalpressure relief valve which provideshigh pressure protection to the

refrigerant system and rubber vibration isolators for quiet andefficient operation.The compressors are equipped

 with internal motor protector forsafe operation. The compressorsare built to NF, VPE, CSA, & ULcertification.

Page 7: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 7/24

 www.coolex.com.kw 6

Microprocessor Based Controller

The Package New Generation units are provided with technologically advanced

Microprocessor based controller, incorporating the following benefits and features:

• Compressor lock out function

• Balance loading of compressors• Compressors lead-lag operation

• Pump down option.

• Fault diagnostics

• Indicator lights for high & low pressure Safeties

Electrical

• Electric heaters (open coil type)

• Electric heaters (fin type)

• Compressor circuit breaker

• Mild ambient (fan cycling) control

• Duct sensor

• Anti - ice thermostat

• Volt free contacts

• External overload

• Ultra violet light

• Dirty filter indication

• Fire alarm connection

• Economizer controller

Construction & Refrigeration

• Pump down solenoid valve (pds)

• Hot gas bypass valve

• Condenser coil guard

• Adjustable high pressure switch

• Adjustable low pressure switch

• Muffler

• Replaceable filter drier with mechanical shut-off valve

• Coil coat, tinned copper fins

• Filter and filter box

• Double side drain connections

• Stainless steel drain pan

• Lockable door for the control panel

• Mixing box

OPTIONAL SPECIFICATIONS

MICROPROCESSOR CONTROLLER

Page 8: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 8/24

 www.coolex.com.kw 7

The below example illustrates the selection procedure to assist using this catalog toselect the appropriate PNGc unit that meets the design requirements.

SELECTION PROCEDURE

Sea level

1000

2000

3000

4000

5000

6000

7000

Altitude[ft]

Correctionfactor

1

0.996

0.990

0.984

0.980

0.974

0.965

0.960

Example :

Design requirements

• Total cooling capacity 64 [MBH]

• Sensible cooling capacity 47 [MBH]

• Design ambient temperature 115 [°F]

• Evaporator air flow 2400 [CFM]

• Evaporator entering temperature DB/WB 80/67 [°F/°F]

• External static pressure 0.2 [in.wg]

• Altitude 2000 [ft]

• Power supply 415V / 3Ph / 50Hz

*Using the correction factor table at the specified altitude, thereby the

required capacity will be:

Corrected capacity  = Required capacity

  /corr. factor

Corrected total capacity  = 64 [MBH]/0.99

  = 64.64 MBH

Corrected sensible capacity  = 47 [MBH]/0.99

  = 47.47 MBH

From the cooling capacity at performance data tables (page 10), the

closest selection model to the required capacity is PNGc 076. From

 the performance table:

Total capacity = 65.13 [MBH]

Sensible capacity  = 48.5 [MBH]

Page 9: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 9/24

 www.coolex.com.kw 8

GENERAL DATA

PNGc-048 PNGc-060 PNGc-076 PNGc-090 PNGc-100 PNGc-110 PNGc-120

Compressor 

Condenser Fan

Condenser Coil

Evaporator Blower 

Size of Pulley

V-Belt

Evaporator Coil

Expansion Device

Refrigerant Charge

Weight

Type

Quantity

Refrigerant

Oil recharge (OZ)

Type

Diameter, mm

 Air Flow, m3 /min. (CFM)

Motor Enclosure/Ins Class

Nominal kW (HP)

RPM

Type

Rows - FPI

Total Face area, m² (ft²)

Type

Size (D x W), mm*

Motor Enclosure/Ins Class

Motor Frame

Nominal kW (HP)

RPM Range

Blower (PD x Bore), mm**

Motor (PD x Bore), mm**

Type & Section

Type

Rows - FPI

Total Face area, m² (ft²)

Type

kg

kg

Scroll Hermetic

1 2

R - 407C

62 56 85 42 Each 62 Each

Propeller 

610 762

95 (3360) 102 (3605) 198 (6995)

Totally Enclosed Air Cooled, Class F

0.56 (3/4) 0.56 (3/4) 0.56 (3/4) 1.12 (1.5)0.75 (1)

900

Enhanced Fins & Tubes

1-15 2-14 3-16 3-162-132-15

1.40 (15.07) 1.60 (17.22) 1.53 (16.96) 2.15 (23.14)1.38 (14.85)

Centrifugal

280x254 305x280 305x381

Open Drip-Proof, Class B

48 56 182T/184T

0.56 (3/4) 0.75 (1) 1.12 (1.5)

930-1117

1.5 (2)

686-1300

2.2 (3)

729-1250

226.1 X 25.4

139.7 –165 x 22.2

B 43

700-900 800-1090

-

-

-

167.6 x 25.4

93.9 - 119.4 x 22.2

B 39B 35B 44

Enhanced Fins & Tubes

3-14

0.59 (6.35 )

Thermostatic

4.8

233

4-12

0.55 (6.07)

Thermostatic

7

277

2-13 3-13 3-12 3-12 3-14

0.49 (5.28)

Capillary

0.91 (9.79)

3.2

180

4.6

196

3.5 (each)

361

3.4-3.8

369

3.6(each)

375

-

-

-

Capillary Thermostatic

Page 10: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 10/24

 www.coolex.com.kw 9

PERFORMANCE DATA TABLES 

      P      N      G     c   -      0      4      8      C      2

 52,736

49,023

43,507

38,206

54,038

50,254

44,584

39,139

54,571

50,725

45,015

39,518

86

80

74

68

86

80

74

68

86

80

74

68

72

67

62

57

72

67

62

57

72

67

62

57

 34,729

34,805

33,596

31,858

35,560

35,647

34,416

32,624

35,906

35,993

34,740

32,937

4.34

4.21

4.03

3.83

4.46

4.34

4.14

3.94

4.52

4.39

4.19

3.99

 50,824

44,092

36,832

26,530

52,080

45,172

37,724

30,552

52,587

45,630

38,087

30,838

34,667

32,352

30,027

27,014

35,492

33,131

30,749

27,678

35,835

33,578

31,035

27,907

5.43

5.10

4.78

4.55

5.59

5.25

4.92

4.68

5.65

5.30

4.97

4.74

 49,757

43,167

36,058

25,973

50,987

44,224

36,932

29,910

51,483

44,765

37,288

30,191

5.64

5.30

4.96

4.73

5.79

5.44

5.10

4.86

5.86

5.49

5.16

4.91

 48,628

42,187

35,240

25,384

49,830

43,221

36,095

29,231

50,315

43,640

36,443

29,505

 33,911

31,648

29,372

26,424

34,718

32,409

30,078

27,075

35,054

32,846

30,359

27,299

5.85

5.50

5.15

4.90

6.02

5.66

5.30

5.04

6.09

5.71

5.36

5.10

1360

1530

1800

63,272

59,356

56,904

52,385

63,574

59,637

57,174

52,635

63,874

59,920

57,444

52,885

86

80

74

68

86

80

74

68

86

80

74

68

72

67

62

57

72

67

62

57

72

67

62

57

  39,149

40,897

42,460

41,103

39,540

41,092

42,655

41,298

39,519

41,288

42,850

41,493

4.62

4.66

4.49

4.41

4.65

4.69

4.52

4.44

4.67

4.73

4.55

4.46

 60,810

54,382

49,511

42,853

61,102

54,643

49,741

43,052

61,395

54,911

49,971

43,250

  40,146

40,146

38,949

35,016

40,523

40,785

39,128

35,173

40,523

40,523

39,306

35,330

5.70

5.60

5.40

5.24

5.73

5.63

5.43

5.27

5.92

5.66

5.46

5.30

59,031

52,791

48,064

41,600

59,316

53,045

48,287

41,793

59,600

53,420

48,510

41,985

5.90

5.80

5.60

5.42

5.93

5.83

5.63

5.45

6.14

5.86

5.66

5.48

57,149

51,108

46,531

40,273

57,424

51,353

46,746

40,461

57,700

51,593

46,963

40,647

 38,515

38,515

37,368

33,594

38,878

39,130

37,539

33,745

38,878

38,878

37,710

33,896

6.12

6.02

5.80

5.63

6.15

6.05

5.83

5.66

6.37

6.08

5.86

5.69

1890

2000

2200

  79,451

72,403

66,120

60,373

80,255

73,137

66,785

60,988

81,456

74,234

67,788

61,901

86

80

74

68

86

80

74

68

86

80

74

68

72

67

62

57

72

67

62

57

72

67

62

57

 54,024

52,420

50,724

49,059

54,569

52,955

51,239

49,553

55,387

53,742

52,006

50,300

6.03

5.96

5.82

5.73

6.08

6.02

5.88

5.79

6.17

6.10

5.98

5.87

  70,780

64,495

58,897

53,777

71,487

65,143

59,495

54,325

72,563

66,122

60,381

55,142

49,488

48,027

46,474

44,944

49,988

48,506

46,936

45,404

50,739

49,238

47,646

46,084

7.32

7.24

7.07

6.96

7.39

7.31

7.15

7.03

7.50

7.41

7.26

7.14

69,181

63,039

57,567

52,562

69,872

63,671

58,151

53,099

70,924

64,774

59,018

53,896

7.53

7.45

7.29

7.16

7.61

7.52

7.36

7.25

7.73

7.63

7.47

7.35

67,489

61,496

56,158

51,276

68,163

62,113

56,728

51,799

69,189

63,044

57,574

52,578

46,097

44,736

43,291

41,864

46,563

45,183

43,719

42,293

47,262

45,864

44,381

42,927

7.76

7.68

7.50

7.39

7.84

7.75

7.59

7.46

7.96

7.86

7.70

7.57

2160

2400

2600

 34,300

32,010

29,709

26,728

35,116

32,780

30,423

27,385

35,456

33,223

30,707

27,612

47,840

46,428

44,928

43,448

48,325

46,893

45,374

43,893

49,050

47,599

46,060

44,551

39,354

39,354

38,181

34,325

39,723

39,981

38,357

34,480

39,723

39,723

38,531

34,634

Model

Air

Flow

CFM

Temp (°F) 95 °F 115 °F 118.4 °F 122 °F

Condenser Ambient Temperature [ºF]

DB WBCapacity Btu/Hr kw

InputTotal Sen.

kwInputTotal Sen.

kw

InputTotal Sen.

kwInputTotal Sen.

Capacity Btu/Hr Capacity Btu/Hr Capacity Btu/Hr

      P      N      G     c   -      0      6      0      C      2

      P      N

      G     c   -      0      7      6      C      2

Page 11: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 11/24

 www.coolex.com.kw 10

PERFORMANCE DATA TABLES 

      P      N      G     c   -      0      9      0      C      2

 98,305

87,268

79,552

71,235

99,300

88,149

80,353

71,958

100,787

89,468

81,559

73,033

86

80

74

68

86

80

74

68

86

80

74

68

72

67

62

57

72

67

62

57

72

67

62

57

 63,345

56,233

51,261

45,901

63,986

56,800

51,777

46,368

64,944

57,650

52,554

47,060

7.90

7.01

6.39

5.73

7.98

7.08

6.46

5.78

8.10

7.19

6.56

5.87

 92,335

81,968

74,721

66,908

93,269

82,795

75,473

67,588

94,666

84,034

76,605

68,598

 59,988

53,253

48,544

43,469

60,595

53,790

49,033

43,910

61,502

54,595

49,769

44,566

9.40

8.34

7.61

6.81

9.49

8.43

7.68

6.88

9.64

8.55

7.80

6.98

 85,042

75,494

68,819

61,624

85,903

76,256

69,512

62,250

87,189

77,397

70,555

63,180

9.65

8.57

7.81

7.00

9.75

8.66

7.89

7.07

9.90

8.79

8.01

7.17

 82,164

72,939

66,490

59,538

82,996

73,676

67,160

60,143

84,238

74,778

68,168

61,042

 55,066

48,883

44,561

39,902

55,623

49,376

45,010

40,307

56,456

50,115

45,685

40,909

9.87

8.76

7.99

7.15

9.97

8.85

8.07

7.23

10.12

8.98

8.19

7.33

2500

2700

2900

  112,323

97,199

88,446

77,634

113,460

98,176

89,339

78,420

115,160

99,642

90,677

79,588

86

80

74

68

86

80

74

68

86

80

74

68

72

67

62

57

72

67

62

57

72

67

62

57

 75,838

70,185

68,359

66,012

76,601

70,890

69,052

66,683

77,758

71,954

70,093

67,676

7.77

7.39

7.11

6.78

7.86

7.46

7.19

6.85

7.96

7.57

7.29

6.95

103,162

89,266

81,231

71,300

104,206

90,172

82,052

72,024

105,761

91,525

83,277

73,101

71,524

66,191

64,476

62,259

72,248

66,856

65,129

62,888

73,333

67,860

66,097

63,833

9.52

9.05

8.70

8.31

9.61

9.14

8.79

8.39

9.77

9.28

8.94

8.52

 99,577

86,164

78,409

68,822

100,585

87,038

79,200

69,521

102,086

88,345

80,384

70,561

9.78

9.30

8.95

8.54

9.88

9.39

9.04

8.62

10.03

9.53

9.17

8.75

 95,781

82,880

75,420

66,199

96,751

83,720

76,182

66,871

98,195

84,977

77,319

67,871

 68,492

63,385

61,742

59,618

69,184

64,021

62,368

60,222

70,223

64,983

63,295

61,127

10.06

9.56

9.19

8.77

10.16

9.66

9.30

8.87

10.31

9.80

9.44

9.00

2700

3000

3300

108,478

103,110

97,170

88,581

111,188

105,691

99,587

90,766

112,255

106,696

100,531

91,628

86

80

74

68

86

80

74

68

86

80

74

68

72

67

62

57

72

67

62

57

72

67

62

57

 69,196

71,245

71,659

70,260

70,559

72,965

73,391

71,955

71,213

73,648

74,074

72,628

8.62

8.51

8.21

7.94

8.89

8.28

8.00

7.74

8.50

8.38

8.10

7.83

 103,721

95,755

85,781

73,954

106,283

98,100

87,863

75,723

107,294

98,669

88,691

76,432

68,552

67,646

64,496

60,226

70,214

69,268

66,029

61,663

70,867

70,093

66,642

62,226

9.76

9.66

9.23

8.84

10.06

9.95

9.51

9.10

11.11

10.07

9.62

9.20

  103,448

94,965

84,211

71,721

105,003

96,918

86,805

74,811

106,001

97,706

87,623

75,512

9.78

9.67

9.24

8.82

10.43

10.33

9.87

9.45

11.54

10.44

9.98

9.55

 101,605

92,635

81,266

68,250

103,647

95,667

85,684

73,846

104,633

96,222

86,491

74,537

68,562

66,602

62,156

56,852

69,722

68,783

65,567

61,231

70,372

69,602

66,176

61,791

9.99

9.88

9.43

8.99

10.84

10.73

10.25

9.82

11.98

10.85

10.37

9.93

2880

3240

3600

 56,351

50,024

45,601

40,833

56,921

50,529

46,061

41,248

57,774

51,285

46,752

41,864

 68,894

67,470

63,677

58,880

69,975

69,032

65,805

61,453

70,626

69,855

66,416

62,015

70,051

64,828

63,148

60,977

70,760

65,479

63,787

61,594

71,822

66,462

64,736

62,519

Model

Air

Flow

CFM

Temp (°F) 95 °F 115 °F 118.4 °F 122 °F

Condenser Ambient Temperature [ºF]

DB WBCapacity Btu/Hr kw

InputTotal Sen.

kwInputTotal Sen.

kw

InputTotal Sen.

kwInputTotal Sen.

Capacity Btu/Hr Capacity Btu/Hr Capacity Btu/Hr

      P      N      G     c      C   -      1      0      0      2

      P      N

      G     c   -      1      1      0      C      2

Page 12: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 12/24

 www.coolex.com.kw 11

PERFORMANCE DATA TABLES 

LEGEND:

CFM : Air flow rate ( Ft3/minute)DB : Dry bulb temperature (°F)

 WB : Wet bulb temperature (°F)P.I : Power input for (compressor +condenser fan only) (kW)

Note: Capacity in kW= (Btu/hr/12000)*3.517 

 

      P      N      G     c   -      1      2      0      C      2

 125,817

113,748

102,130

87,347

127,084

114,897

103,163

88,224

128,993

116,616

104,709

89,554

86

80

74

68

86

80

74

68

86

80

74

68

72

67

62

57

72

67

62

57

72

67

62

57

 87,650

79,242

71,149

60,850

88,533

80,043

71,868

61,461

89,863

81,240

72,945

62,388

10.53

9.52

8.55

7.31

10.64

9.62

8.64

7.38

10.80

9.76

8.76

7.50

 118,588

107,213

96,262

82,328

119,783

108,296

97,235

83,155

121,582

109,915

98,693

84,409

82,003

74,137

66,565

56,929

82,829

74,886

67,238

57,501

84,073

76,006

68,246

58,368

12.84

11.61

10.42

8.91

12.97

11.73

10.53

9.00

13.16

11.90

10.69

9.14

 109,807

99,274

89,134

76,232

110,913

100,277

90,035

76,998

112,579

101,776

91,385

78,158

13.23

11.96

10.74

9.19

13.37

12.08

10.85

9.28

13.57

12.26

11.01

9.42

 106,853

96,603

86,736

74,181

107,929

97,579

87,613

74,926

109,550

99,038

88,927

76,056

80,103

72,419

65,023

55,610

80,910

73,151

65,680

56,169

82,125

74,245

66,664

57,016

13.72

12.41

11.14

9.53

13.86

12.53

11.25

9.62

14.07

12.72

11.42

9.77

3200

3600

4200

 81,194

73,406

65,908

56,368

82,012

74,147

66,574

56,934

83,244

75,256

67,572

57,792

Model

Air

Flow

CFM

Temp (°F) 95 °F 115 °F 118.4 °F 122 °F

Condenser Ambient Temperature [ºF]

DB WBCapacity Btu/Hr kw

InputTotal Sen.

kwInputTotal Sen.

kw

InputTotal Sen.

kwInputTotal Sen.

Capacity Btu/Hr Capacity Btu/Hr Capacity Btu/Hr

Page 13: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 13/24

 www.coolex.com.kw 12

UNIT ELECTRICAL DATA

LEGEND:

FLA - Full Load Amps RLA - Rated Load AmpsHP - Horse Power MCA - Minimum Circuit AmpsLRA - Locked Rotor Amps MOCP - Maximum Over Current Protection

Model

-

5

7.5

10

-

5

7.5

10

-

5

7.5

10

-

5

7.5

10

15

-

10/12

15/20

25/30

35/40

-

10/12

15/20

25/30

35/40

-

10/12

15/20

25/30

35/40

PowerSupply 

415-3-50

415-3-50

415-3-50

415-3-50

415-3-50

415-3-50

415-3-50

PNGc-048

PNGc-060

PNGc-076

PNGc-090

PNGc-100

PNGc-110

PNGc-120

 VOLTAGE RANGE Compressor   Evaporator BlowerMotror

FM Electric Heater

(V-PH-Hz)   Min. Max. FLA RLA LRA HP FLA KW FLA

MCA MOC

374

374

374

374

374

374

374

457

457

457

457

457

457

457

1.3

1.3

1.3

1.3

2

2

3

8.3

10

12.1

16.4

7.9

8.3

10

61.8

65.5

101

95

50

61.8

65.5

0.75

1

1

1.5

2

2

3

2.5

3.3

2.4

2.9

4.3

4.3

4.6

-

7

10.4

13.9

-

7

10.4

13.9

-

7

10.4

13.9

-

7

10.4

13.9

20.9

-

13.9/16.7

20.9/27.8

34.8/41.7

48.7/55.6

-

13.9/16.7

20.9/27.8

34.8/41.7

48.7/55.6

-

13.9/16.7

20.9/27.8

34.8/41.7

48.7/55.6

14.2

14.2

16.1

20.5

17.1

17.1

17.1

21.5

18.8

18.8

18.8

20.4

24.7

24.7

24.7

24.7

29.8

24.1

24.1/26.3

31.5/40.1

48.9/57.5

66.3/74.9

25

25/26.3

31.5/40.1

48.9/57.5

66.3/74.9

30.1

30.1/30.1

31.9/40.5

49.3/57.9

66.6/75.3

20

20

20

25

25

25

25

25

30

30

30

30

40

40

40

40

40

30

30/30

35/45

50/60

70/80

30

30/30

35/45

50/60

70/80

40

40/40

40/45

50/60

70/80

Page 14: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 14/24

 www.coolex.com.kw 13

SUPPLY AIR PERFORMANCE

CFM Values, PNG 048 & PNG 060 (Direct driven motor)

RPM Values, PNG 076 - 120 (Belt Driven)

MODEL

PNGc-048

PNGc-060

940

932

920

966

959

947

External Static Pressure [in.wg]

0.1

1800

1700

1630

2200

2075

2000

RPM0.2

1690

1530

1490

2100

2000

1940

0.3

1580

1420

1380

1990

1946

1900

0.4

1460

1390

-

1960

1895

-

0.5

1360

-

-

1890

-

-

External Static Pressure [in.wg]

Model

PNGc-076

PNGc-090

PNGc-100

PNGc-110

PNGc-120

2160

2400

2600

2500

2700

2900

2700

3000

3300

3240

3400

3600

3200

3600

4200

CFM0.1 0.2 0.3 0.4 0.5 0.6 0.7

826

900

992

930

957

984

-

-

1057

843

886

920

-

889

907

845

946

1022

953

979

1006

-

1045

1109

882

924

942

893

907

925

932

984

1122

977

1002

1027

942

1076

1155

921

952

989

904

918

955

984

1022

1222

1001

1025

1049

980

1106

1212

949

983

1021

915

928

986

1042

1060

1322

1025

1048

1072

1017

1137

1278

989

1019

1055

926

963

1025

1076

1098

1422

1050

1072

1094

1055

1167

1300

1017

1053

1090

936

997

1064

1114

1136

1522

1075

1096

1117

1092

1198

-

1054

1086

1126

947

1031

1103

Page 15: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 15/24

 www.coolex.com.kw 14

Page 16: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 16/24

 www.coolex.com.kw 15

Page 17: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 17/24

 www.coolex.com.kw 16

Page 18: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 18/24

 www.coolex.com.kw 17

Page 19: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 19/24

 www.coolex.com.kw 18

LOAD DISTRIBUTION

X1 (kg)

47

51

61

71

94

96

98

 A (mm)

75

75

75

75

75

75

75

W (mm)

1130

1130

1130

1130

1405

1405

1405

L (mm)

1290

1290

1290

1290

1740

1740

1740

MODEL

PNGc-048

PNGc-060

PNGc-076

PNGc-090

PNGc-100

PNGc-110

PNGc-120

LOAD DISTRIBUTION

X2 (kg)

43

47

56

68

87

89

90

Page 20: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 20/24

 www.coolex.com.kw 19

NOTES

Page 21: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 21/24

 www.coolex.com.kw 20

NOTES

Page 22: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 22/24

 www.coolex.com.kw 21

NOTES

Page 23: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 23/24

 www.coolex.com.kw 22

CENTRAL AIR CONDITIONING AND SPLIT UNITCoolex continuously works towards the improvement of

its products. Hence, the design and specifications of theordered product may vary without prior notice.

Please contact Sales and Marketing Department

[email protected] or www.coolex.com.kw for

specific information on the current design andspecifications. Ref no.: CPRC13-5-000

COOLEX is a subsidiary of the RIC Group

 www.ric.com.kw 

Page 24: Coolex Rooftop Package 48120 r 407 c

7/17/2019 Coolex Rooftop Package 48120 r 407 c

http://slidepdf.com/reader/full/coolex-rooftop-package-48120-r-407-c 24/24

 www.coolex.com.kw