ELCOS- Parma- Italy - GB - CAM -684 1Valid for firmware revisions higher than or equal to 1.24
CONTROL UNIT FOR GENERATING SETTYPE CAM-684
Made for the preparation of automatic emergency intervention switchboards.This controls and commands the genset unit. It commands the mains and generator contactors tosupply the user.
MAI
NS
GEN
ERAT
OR
INST
RU
CTI
ON
AN
D U
SE M
ANU
ALIt is equipped with display to showthe INSTRUMENTS:- three mains voltmeters- three generator voltmeters- delta voltages phase/phase- star voltages- three mains/generator ammeters- frequency meter- wattmeter total and per phase- varmeter “- voltammeter “- kilowatt-hour- cosphimeter per phase- partial hour-meter- total hour-meter- starting counter- starting failure counter- tachometer- battery voltmeter- battery charger current
(with battery charger type CBS)- fuel level gauge- water oil thermometer- oil pressure gauge
• Automatic supervision of faults with messages on the display• Texts in 6 languages: Italian, English, French, German, Spanish and Portuguese• Information on 4 programmable preventive maintenance operations with display of the hours
remaining before the maintenance work is due• Remote controls (starting, stop and test)• EJP function• Preheating glow plugs management• Management of refuelling of working tank from storage tank• Clock to program starting or stopping the generating set• Generator start/stop on request for power• Possibility of starting the generating set in case of low battery-charge• Programmable weekly selftest.• Available inputs for fully programmable anomalies (times, polarities, stopping possibility and message
about the anomaly)• Three-phase voltmetric control, voltage failure, undervoltage, overvoltage, asymmetryc voltage and
not correct phase sequence of the mains and of the generator.• Anomaly historical log (including data from the last 50 occurred anomalies)• Displaying of the most serious faults with both led and messages on the display• Possibility of password protected programming.
• CAN Bus Connection (SAE J1939)• Serial ports RS232 and RS485• Connection with a remote panel (Type PRE-685) to display the instruments and errors managed
by the CAM-684• GSM Modem (to be mounted externally), possibility of displaying the control unit instruments with a
mobile phone, operating the starting and stopping and notifying with an SMS message when the generating set is in alarm state• MODBus protocol through port RS232, RS485 and the serial port via USB• Remote operation with personal computer (on request):
- reading of the instruments shown on the display of the control unit- anomaly historical record- displaying of anomalies and operating status of the generating set.- start stop controls
MODES OF COMMUNICATION OF CAM-684
®PARMA ITALY
E-mail: [email protected] - HTTP://www.elcos.it Fax +39 0521/270218Tel. +39 0521/772021
ELCOS- Parma- Italy - GB - CAM -6842 Valid for firmware revisions higher than or equal to 1.24
TECHNICAL DATA Supply by battery 12 Vdc 24 Vdc Supply voltage 8 ÷ 32V Selfconsumption with stopped engine and pressed emergency button
350 mA 12V 180 mA 24V
Suitable for three-phase generators having the following voltage range:
80 ÷ 430Vac ±10%; frequency 50 ÷ 60Hz
Dielectric withstand voltage between battery powered circuits and mains/group powered circuits
3750 Vac 50Hz 1 sec
Voltage sag in power line from battery
65msec
0V
10V
Rated insulation voltage: • Terminal board at mains voltage
600V
• Terminal board at genset voltage 600V • Terminal board at battery voltage 32V Capacity of contact for control of the genset contactor 250V 3A (AC1) Max load on the outputs 15 (starting) 0,25A,
17 (stop) 1,5A, 19 (key) 0,25A, 6 (glow plugs) 0,25A 70 (general alarm) 0,25A
Degree of rear protection IP 20 Degree of front protection IP 64 Temperature range - 20 ÷ + 60°C W eight 1120g Dimensions with terminals disconnected (LxHxP)mm 290x200x62 Hole mm 274x185 Tachometer 5 digits Instruments accuracy: oil pressure gauge, water thermometer, fuel level
±2%
Mains/generator voltmeter Max 570V accuracy ±1% field of measurement 50 ÷ 570Vac
Rated current of the ammeters 5 A ac Ammeter Max 4800A, accuracy ±1%
field of measurement 0,02 (20mA) ÷ 6A Frequency meter: 0-85 Hz, accuracy ±0,1 Hz
frequency field 45 ÷ 85Hz Precision of the wattmeter, varmeter, voltammeter, kilowatt-hour and cosphimeter
±2%
Tachometer Max 4000 RPM accuracy ± 10 RPM Serial output parameters 9600 baud, 8 bit data, 1 bit stop; even parity Rechargeable batteries (excluded from supply) 1,2V Type AAA
S U M M A R Y S u m m a ry – T e c h n ic a l d a ta - H is to ry o f re v is io n s P a g e 2 B r ie f in s tru c t io n s – In s tru m e n ts – M o d e s o f c o m m u n ic a tio n o f th e c o n tro l u n it “ 3
O p e ra tio n : F u n c tio n s s e le c tio n – M a n u a l – A u to m a tic – T e s t – O ff – G lo w p lu g s p re h e a t in g – S ta r t in g – S ta r tin g F a ilu re
“ 4
O p e ra tio n : D e te c t io n o f ru n n in g e n g in e – S to p – G e n e ra to r s e t p ro te c t io n d e v ic e s – G e n e ra l a la rm – P re v e n tiv e m a in te n a n c e – E m e rg e n c y s to p – S to p p in g fa ilu re – G e n e ra to r s e t s ta r tin g w ith lo w c h a rg e o f th e b a tte ry - S ta r t in g o n re q u e s t fo r p o w e r – C lo c k
“ 5
W ir in g d ia g ra m “ 6 -7 M e s s a g e s a n d in s tru m e n ts – A n o m a ly m e s s a g e s – C A N B u s in s tru m e n ts – C u m u la t iv e a la rm s “ 8
S ta r t u p , s to p a n d te s t c a l l re m o te c o n tro ls a n d E J P fu n c t io n s – M a in s g e n e ra to r v o ltm e tr ic re la y s “ 9
U s e r p ro g ra m m in g “ 1 0
N o tic e s “ 1 1
B a tte ry c h a rg e r – O rd e r in g d a ta – A c c e s s o r ie s s u p p lie d -D e c la ra t io n C E “ 1 2
HISTORY OF REVISIONSDate Description Page
VM . motor management inserted 3-5-9-20programming manual
4-1210-13-20
programming manual
Password management inserted.Minimum temperature read by the transmitter brought to 0°C.Disconnected temperature and pressure transmitter fault management removed.Stop time extended to 120 seconds.New Scania motor management inserted.
Level of theREVISION
Cummins .motor management insertedThe over-temperature error is delayed by the thermostat by 5 seconds.
GSM stop function enabled.
1.24 MODBus protocol through port RS232, RS485 and the serial port via USBFebruary 2014
ELCOS- Parma- Italy - GB - CAM -684 3Valid for firmware revisions higher than or equal to 1.24
With the running
engine the
generator set
instruments are
shown. In the
event of a fault,
instead of the
measurement,
the display
shows the
message of
the occurred
fault.
INSTRUMENTS
BRIEF INSTRUCTIONS
" " " "
With battery charger type CBS
• THREE MAINS AND GEN- ERATOR VOLTMETERS up to 570V
• THREE MAINS/ 30/5, 40/5, GENERATOR 80/5, 100/5, 150/5, 200/5, 250/5, 300/5, 600/5, 800/5, 1000/5, AMMETERS 1200/5, 1500/5, 2000/5, 2500/5, 3000/5, 4000/5.
• FREQUENCY METER greater than 30 V~.• WATTMETER (Total and per phase) • VARMETER • VOLTAMMETER
• COSPHIMETER (Per phase)
• 65535.• FAILURE COUNTER 9999• 8500 rpm.• • BATTERY CHARGER CURRENT
For three-phase voltages and nominal value ~.• DELTA VOLTAGES PHASE/PHASE• STAR VOLTAGES
Compatible with the amperemetric transformer type 50/5, 60/5, 400/5, 500/5,
Maximum reading of 4000A or 110% of the full-scale current of the chosen transformer.From 0Hz to 85Hz for alternating voltages with amplitude
• KILOWATT-HOUR (Total)
• PARTIAL HOUR-METER With four digits and a maximum reading of 9999 (hours and minutes). (The hours indicated are zeroset the next time the genset is started up.)
• TOTAL HOUR-METER Displays five digits and a maximum reading of 59999 (hours and minutes). STARTING COUNTER Displays the number of occurred startings up toSTARTING
Displays the number of failure startings up toTACHOMETER Displays the number of engine revs up toBATTERY VOLTMETER
• FUEL LEVEL GAUGE Displays the percentage of fuel present in the tank
• WATER OR OIL THERMOMETER Displays the water and oil temperature of the engine up to 140°C• OIL PRESSURE GAUGE Displays the oil pressure of the engine up to 9 bar
C
MODEM
ENGINEEquipped with control unitfor the electronic control ofthe injection system
10m max500m maxRS232/
RS485RS232/RS485
MODEM GSMELCOS
CAN Bus
RS232
RS485
I/0 EXTENSION
REMOTE PANEL
I/0 EXTENSION
MOD BUS
" " MASTER
" " MOD BUS
ELCOS- Parma- Italy - GB - CAM -6844 Valid for firmware revisions higher than or equal to 1.24
ENABLED WITH CONTROL UNIT IN AUTOMATIC MODE (For programming see page 10)after a pause of 3 seconds, the engine starts and continues to run for the WEEKLY TEST TIME (programmed to 3 minutes).This test will be repeated automatically every week on the exact day and at the hour to which it has been programmed. During the automatic test cycle, WEEKLY AUTOMATIC TEST is shown on the display.
Press key
STOPPING OF ENGINE DURING THE TEST
WEEKLY TEST STOP:The weekly test is stopped when an anomaly is displayed on the display
The function selectedwith the key is shown bythe associated warning light.
The control unit commands are enabledStarting with key stopping with key (it is obtained by pressing once the key
.).
MANUAL
OPERATIONFUNCTIONS SELECTION
STOPSTART
When key is pressed until Led comes onThe engine cannot be started in any way and, if running, the engine is stopped without carrying out engine cooling
..
OFF
- .- .
In with key (it is obtained by pressing once the key)In it is activated automatically before starting
The preheating action time can be adjusted, the preheating action stops before startup start. The factory preheating command is inhibited as it has been programmed to zero seconds.
manualautomatic
GLOW PLUGS PREHEATING
PROTECTIONSThe generator set protection function in manual mode can be programmed in two ways:· Display only of the fault that has intervened WITHOUT STOPPING the engine. The faults overfrequency, overspeed and emergency of the generator are programmed with stopping of the engine. It cannot be programmed without stopping of the engine.· Display of the fault that has intervened WITH ENGINE STOPPING. (The control unit is programmed in this way).
START
TEST
WEEKLY AUTOMATIC TEST
When a fault occurs on the mains, (detected by the internal voltmetric relay, or by the external call), once the ime have elapsed, the control unit commands the opening of the mains
contactor, and starts the generator set.With engine running and generator voltage normal and once the GENERATOR TO POWER USERS CONNECTION DELAY has elapsed, the generator contactor closes. While it is running the generator set is protected from possible faults.When the mains voltage is restored and the MAINS ACCEPTANCE time has elapsed, the control unit commands the opening of the generator contactor, after the GENERATOR-MAINS INTERLOCK time the mains contactor closes The COOLING TIME allows and facilitates subsequent cooling of the engine before stopping it.
tSTARTUP DELAY AFTER MAINS FAULT
AUTOMATIC
On pressing key , we obtain the engine startup cycle as in automatic, and the power users remain supplied by the mains. If a mains fault occurs during the test, the control unit remains in test mode, positions itself as in automatic operation and commands the closing of the generator contactor.
STOP
CONTROL FOR MAINS/GENERATOR CONTACTORS
It is left to the keys By pressing on the keys, the load is switched from the mains to the generator and vice versa.
STARTING
- .
. Engine start-up is stopped if the starter pinion does not couple with the flywheel ring gear. After the first missedcoupling, the starter motor makes five more attempts. When coupling is missed for the sixth time, the starter motor continues running for 5 seconds.
.
In mode or if a mains anomaly is detected by the internal voltmetric relay, or an external call, and after
To make starting easier, a special circuit establishes a series of programmable startups (programmed to 4STARTUPS); the number of startups, the length of the pause time and the startup time can be programmed
If the whole series of attempts is unable to start the engine, at the end of this cycle STARTING FAILUREis shown on the display and the stop signal is activated
automaticthe STARTUP DELAY AFTER MAINS FAULT time has elapsed
START-UP WITH PINION CONTROL ENGAGED
STARTING FAILURE
- In mode with key , in Test and with the remote control, it comes on immediately after the PREHEATING TIME.
manual START
ELCOS- Parma- Italy - GB - CAM -684 5Valid for firmware revisions higher than or equal to 1.24
OPERATION
GENERATOR SET STARTING WITH LOW BATTERY CHARGE(with control unit in automatic mode)
STARTS OR STOPS the generator set depending on the voltage measured on the battery terminalsBefore starting automatically, the generator set activates the intermittent general alarm for 8 seconds, followed by a pause of 3 seconds.
12.
When the voltage measured on the battery is lower than the minimum threshold, THE ENGINE STARTS. When the voltage exceeds the maximum threshold after the intervention delay, THE ENGINE STOPS. To change the programming of the thresholds and of the delay see the basic table of the TECHNICAL PROGRAMMING OPERATIONS manual on page
The intervention of the fault is displayed; it can cause the engine to be stopped and activates the general alarm see BASIC TABLE at pages 10-11 of the TECHNICAL PROGRAMMING manual.
When the engine is running the generator set instruments are shown.When there is a fault, instead of the reading, the display shows the intervened fault message, and the associated yellow LED flashes.
FAULT DISPLAY
FAULT RESET
It is possible to access the reading of the measurements and at the same time to silencing the general alarm,by pressing key for 1 second.
The display will resume showing the previous fault 20 seconds after the last pressing of the key.
On pressing the key , the protection devices and all the locked functions are reactivated.
HOW TO SEE THE INSTRUMENT READINGS AGAIN
GENERATOR SET PROTECTION DEVICES AND USER
GENERAL ALARMThis is produced by mounting an acoustic signal, linked to the appropriate terminalIt can be arranged so that it is activated continually or for a set timeWhen key is pressed the general alarm is silenced.
..
PREVENTIVE MAINTENANCEWhen preventive maintenance operations need to be carried out, the yellow LED flashes while the number of the intervened maintenance appearsThe timing for the maintenance operations and the procedure for zeroing the time up maintenance indication can be programmed by the manufacturer of the generator set unit
.
.EMERGENCY STOP
The emergency stop can be activated in all working conditions, by mounting one or more click down push-button. The stop is immediate (without engine cooling), does enable the general alarm and EMERGENCY STOP is shown on the display.
STOPPING FAILEDThis intervenes if the running engine signal is detected 120 seconds after the stop command. STOPPING FAILURE will be read on the display.
Do not use the emergency button combined with a stopping system that is not energized in run mode.
DETECTION OF RUNNING ENGINEIt is obtained by detecting generator frequency and residual voltage or by detecting battery charger alternator (permanent magnets or pre-excitation) voltage and frequency. It is also possible to use a pick-up device in place of the alternator. In case of engine equipped with electronic injection controller (CAN Bus) it is not necessary any pick-up and the alternator is used only to detect belt breakage.When the running engine signal has been detected the unit disconnects the starter and switches on the led .
STOP- ).- .- .
:• w
•.
In mode using key (it is obtained by pressing once the keyIn mode when the protection systems and the remote controls interveneIn mode when the mains power returns, or when the protection systems or remote controls intervene
Stopping can occur in two waysith the solenoid deactivated while the engine is running and activated when stopped. This condition is maintained
during the STOP TIME after the engine stopped detection.
manualTestAutomatic
with solenoid or electro-valve activated while the engine is running and deactivated when stopped, remaining in this condition even when the engine is stationary
STOP
This starts or stops the generator set according to the power detected by the control unit.A general alarm triggers for 8 seconds followed by a 3-second pause before automatic start-up of the generator set.As soon as the power value of the power user is above the programmed threshold during the entire engagement delay, the control unit starts the generator set and controls opening of the network contactor. With engine running the generator contactor closes when the generator voltage is regular and the generator engagement delay to the power user has elapsed. As soon as the power value of the power user is below the programmed threshold during the entire engagement delay, the control unit opens the generator contactor, after the generator mains interlock time the mains contactor closes. The cooling time allows for and facilitates cooling of the engine before it is stopped.
STARTING ON REQUEST FOR POWER
CLOCKThe TIMER permits to programme the operation or the block of the generator set AUT
Operation obtained as during mains failure
Stops starting or running of generator set.
. In operation.STARTING
.STOP
ELCOS- Parma- Italy - GB - CAM -6846 Valid for firmware revisions higher than or equal to 1.24
TWISTEDCABLES
MAGNETICTRANSDUCER
EMERGENCYPUSH-BUTTON
30 85
87 86PREHEATING
30 85
86STOP
79
80
87
525150334 17154A21 6 313019
+ SUP
PLY
CO
NN
EC
T IF
TH
E
PRE
HE
ATIN
G O
F G
LOW
PLU
GS
STAR
TUP
STO
P
ENA
BLE
D W
ITH
EN
GIN
E S
TAR
TIN
G O
R R
UN
NIN
GD
ISA
BLE
D W
ITH
EN
GIN
E O
FF
OUTPUTS (+)0,25A MAX
FUEL
LEV
EL F
LOAT
PR
OG
RAM
MED
WIT
H V
ARIA
BLE
RE
SIS
TAN
CE
IND
ICAT
OR
5
OIL
PR
ESSU
RE
SW
ITC
H
ENG
INE
TH
ER
MO
STA
TIC
SW
ITC
H
G
EN
ER
ATO
R O
VER
LOAD
SW
ITC
H
WAT
ER O
IL T
EMP
ER
ATU
RE
TR
ANSM
ITTE
R
OIL
PR
ESSU
RE
TR
AN
SM
ITTE
R
63
585756
RS485+
RS485-GND
37 39
FUEL
LEV
EL
FLO
AT (
leve
l in
dica
tor w
ith c
onta
ct)M
AX
. SA
FETY
LE
VE
L
CA
LL
TEST
Or E
JP s
tarti
ng
STO
P
REMOTECONTROLSWITH CONTROLUNIT INAUTOMATIC10m MAX
+ -
30
STARTING
Connect to the terminal of the braid
PERMANENT MAGNETALTERNATOR
PRE-EXCITATIONALTER-NATOR
REGULATOR
CLB+
+
G
D+B+
R
RG
YELLOW REDYELLOW
NEVER INSTALL THE EMERGENCY PUSHBUTTON LINKED TO ASTOP SYSTEM WHICH ISNOT ENERGIZED WHENTHE UNIT IS RUNNING
YOUR ELECTRICAL TECHNICIAN CAN ASK US ANYTHING ABOUT THIS PRODUCT BY TELEPHONING ONE OF OUR TECHNICIANS
CONTACTOR CONTROL
MAI
NS
CO
NTA
CTO
R A
UX
ILIA
RY
CO
NTA
CT
GE
NE
RAT
OR
CO
NTA
CTO
R A
UX
ILIA
RY
CO
NTA
CT
2221
13
in th
e Te
chni
cal P
rogr
amm
ing
Man
ual)
(see
pag
e
WIRING
3632
75
76 L1
77 L2
78 L3
64
65
66
848586
FOR THE CONNECTIONOF A SINGLE AMMETERUSE TERMINALS 75-77
GENERATORMAINS
AMMETERS
DETECTIONOF RUNNING ENGINE
AND TACHOMETER
DETECTIONOF RUNNING ENGINE
AND TACHOMETER DETECTION OF RUNNING ENG- INE AND CHARGING ALTERNA- TOR PRE-EXCITATION (WITH- OUT THIS CONNECTION THE AL- TERNATOR DOES NOT CHARGE)
DE
TEC
TION
OF
RU
NN
ING
EN
GIN
EW
HEN TERMINALS 63 AND 64 ARE CONNECTED, TERMINAL 65M
UST NOT BE CONNECTEDCOMMUNICATION PORT RS485
FOR DETEC-TION OF RUN-NING ENGINEWITH PRE-EXCITATIONALTERNATORTHISCONNECTIONIS SUFFICIENT
FU134A
Mai
ns d
etec
tion
on p
age
5in
the
Tech
nica
l
STA
RTU
P O
r EJP
sw
itchi
ng c
onse
nt
WAT
ER
OR
OIL
HEA
TER
TH
ERM
OS
TATI
C S
WIT
CH
FAU
LT IN
DIC
ATIN
G
RA
DIA
TOR
CO
OLA
NT
LEVE
L PR
OB
E
W
IF THEINDICATOR (WITHCONTACT) IS NOTUSED, CONNECT THE TERMINAL (36)TO GROUND
RELAY
KM-R KM-G
CONNECT DIRECT-LY TO THE ( )BATTERYTERMINAL
RELAY
RELAY
FU1
4A
Fuse 1A
The blownfuse doesnot stop theengine fromstarting
2,5 mm min50m MAX
50
See remotecontrols onpage 9
COMMUNICATIONPORTUSB
NO
T U
SED
ON PAGE 7OF THE TECHNICAL PROGRAM-MING MANUAL.
SEE
NECESS-ARY PRO- GRAMMING
INST
RU
MEN
T SU
PPLY
(
)
Prog
ram
min
g M
anua
l
CONTACT CAPACITY3A 275VAC MAX
FUELPUMP
EM
ER
GE
NC
YP
US
HB
UTT
ON
IS
NO
T FI
TTE
D
(1,5
A m
ax)
CAM-684
21
ELCOS- Parma- Italy - GB - CAM -684 7Valid for firmware revisions higher than or equal to 1.24
87 86PREHEATING
STOP
63
585756
RS485+
RS485-
REMOTECONTROLSWITH CONTROL
30
STARTING
Connect to thePERMANENT MAGNET
EVER INSTALL THE EMERGENCY PUSH
YOUR ELECTRICAL TECHNICIAN CAN ASK US ANYTHING ABOUT
3632
IF THE
RELAY
KM-R KM-G
CONNECT DIRECT-LY TO THE ( )
RELAY
RELAY
Fusenot stop the
2,5 mm min
50
See remote
FLAT
CA
BLE
U N
1 2
75 76
FU12
10
A
AUTOMATIC
TYPE CBS-030 CBS-060
BATTERYCHARGER
FU7 1A
FU8 1A
74
72
73
71
GENERATOR
MAINS
CONTACTORSCONTROL:
CONTACTSCAPACITY MAX3A 275VAC
FU6 1A
FU9 1A
FU5 1A
CONNECT THE TERMINALS95N 97V FOR SINGLE-PHASE DETECTION
97
98
96
95
THREE-PHASE DETECTIONOF RUNNING ENGINE MAX 475VAC 50÷60Hz
CONNECT THE TERMINALSFOR SINGLE-
PHASE DETECTION 90N 92V
92
93
91
90
THREE-PHASE DETECTION OF MAINS
MAX 475VAC50÷60Hz
CO
MM
UN
ICAT
ION
POR
T:• • A
MM
ETE
R• V
OLT
ME
TER
BAT
TER
Y C
HAR
GE
R S
TATU
S
CONSULT STANDARDS CEI 44-5 (EN 60204) FOR INFORMATION CONCERNING PROTECTION AGAINST OVERLOAD CURRENTS IN THE ELECTRICAL EQUIPMENT USING BATTERY VOLTAGE
STAR
TER
MOTO
R PI
NION
.NO
T CO
UPLE
D
70
OUTP
UT (+
)0,2
5A M
AX 10
0m M
AXGE
NERA
L ALA
RM
69
COMMUNICA-TION PORT
RS 232
FU14 2A
B.M.KM-R
TA1
TA2
TA3
FUELFLOAT
If only one levelindicator (float)with severalcontacts is usedASK FOR ASEPARATEDIAGRAM
GENER-ATOROVER-LOADSWITCH
OIL PRESS-URETRANS-MITTER
TEMPER-ATURETRANS-MITTER
THERMO-STATICSWITCH
OIL URESWITCH
PRESS-
GENERALALARM
FU2 4A
FU3 4A
KM-P
FUEL LOADING SAFETYSOLENOID VALVE
FUELPUMPTHER.
KM-G
SCREWELECTRODES
RODELECTRODE
COOLANT LEVEL PROBEFOR RADIATORS WITH
PLASTIC EXPANSION TANKFOR RADIATORS WITH
METAL EXPANSION TANK
- 4.
HAVING MADE THE CONNECTIONS, THE CONTROL UNIT IS IN OFF MODE. TO SELECT OTHER OPERATING MODES, SEE PAGE
CABLES FOR CONNECTION OF THE AMMETERIC TRANSFORMERS
LENGTH m SECTION mm2
25
8
1,52,54
W1V1U1N1
X-MAINS 400V
N2U2V2W2
X-USER 400V
U4V4W4
FUE
LPU
MP
FU12
FU13
FU14
V5N53940
(1)
(2)
WATER OR OILHEATER
(1) WORKING THERMO-STATIC SWITCH(2) INDICATINGTHERMOSTATICSWITCH.
IF THE FUNCTION LOWCOOLING LIQUID LEVELIS NOT USED, CONNECTTERMINAL 50 TO GROUND
FU10 10A
FU11 10A
KM-P
FU4 1A
GE
NE
RAT
OR
INP
UT
DIAGRAM
KM-P
8786
3085
RELAY
CAN Bus
CAN H
CANL
KM-R
KM-G
KM-G
KM-R
W
VU
N
W
VU
N
CONN
ECT
USIN
G TW
ISTE
DOR
SHI
ELDE
D CA
BLES
MAX
10m
LONG
.
TERMINATION RESISTANCE (120 Ohm)Check in the control unit manual (ECM/ECU)if the resistance must be inserted (engineside) between the CAN-H and CAN-L wires(CAN Bus J1939)
ELCOS- Parma- Italy - GB - CAM -6848 Valid for firmware revisions higher than or equal to 1.24
MESSAGES AND INSTRUMENTSSent (SAE J1939 protocol Bus) from the engine equipped with control unit for electronic control of the injection system.All the messages or instruments displayed on the display regarding the injection control unit and the CAN Bus, are identified by the presence of the characters at bottom right.
ANOMALY MESSAGESThe anomaly messages managed by the injection control unit are indicated on the display. SPN...............................
FMI.........ANOMALYCAN BusANOMALY
Problems with connection to theCAN Bus
CAN Bus INSTRUMENTSThese are read by the injection control unit and shown on the display when the engine is running.
SOME MAKES OF ENGINE DO NOT PROVIDE FOR THE DISPLAY OF ALL THE LISTED INSTRUMENTS
All anomalies regarding these instruments are managed by the injection control unit.
CUMULATIVE ALARMSLED (red) STEADY LIGHT: anomaly managed by the injection control unit the engine . will cause to stop
LED (yellow) STEADY LIGHT: anomaly managed by the injection control unit the engine will NOT cause to stop. LED (red) FLASHING LIGHT: anomaly managed by the control unit CAM-684 the engine .will cause to stop .
LED (yellow) FLASHING LIGHT: anomaly managed by the control unit CAM-684 the engine LEDS OFF ALL OK.
will NOT cause to stop.
INSTRUMENTS DESCRIPTIONUNIT OFMEASURE-MENT
TACHOMETER Displays the number of engine revolutions rpmOIL PRESSUREGAUGE
Displays the pressure of the engine oil bar kPaTHERMOMETER Displays the engine water or oil temperature °C °FUSEDFUEL
Amount of fuel consumed by the engine per unit of time(l/h)
l/hFUELTEMPERATURE
Temperature of the fuel from the inlet of the injectors °C °FTURBO-CHARGERTEMPERATURE
Temperature of turbocharger lubricant °C °F
OILTEMPERATURE
Temperature of the engine lubricant oil °C °FINTERCOOLERTEMPERATURE
Temperature of intercooler liquid after the turbocharger °C °FINTAKETEMPERATURE
Temperature of the pre-combustion air °C °FCOOLANT LEVEL Level of the coolant expressed in % %FUELPRESSURE
Pressure of the fuel between the supply pump and theinjection pump
bar kPaCOOLANTPRESSURE
Pressure of the liquid in the cooling system bar kPaENGINETORQUE
Torque percentage at engine outlet NmENGINE POWER Power developed by the engine kW
ELCOS- Parma- Italy - GB - CAM -684 9Valid for firmware revisions higher than or equal to 1.24
REMOTE CONTROLS START, STOP, TEST AND EJP FUNCTIONS ENABLED WITH CONTROL UNIT IN AUTOMATIC AND IN TEST MODE
CALL
On closing the call contact operation is as with mains fault.
ENABLED WITH CONTROL UNIT IN AUTOMATIC
STARTING
When the start up contact (see page 6) is closed REMOTE STARTING is shown on the display. After the REMOTE STARTUP DELAY time (programmed to 1 sec.) has elapsed, the start up begins, the general alarm is activated intermittently (for 8 seconds), then the general alarm is deactivated and after a pause of 3 seconds the start up cycle begins and operation is as with mains fault. When the startup contact is opened operation is as with mains return.
TEST When the test contact is closed (see page 8) REMOTE TEST is shown on the display. The general alarm is activated intermittently (for 8 seconds). When the general alarm is deactivated, after a pause of 3 seconds the start up cycle begins. If there is a mains fault during the test, the control unit remains in test mode and, as in automatic, commands the closing of the generator contactor that will reopen when the mains returns. When the test contact is opened operation is as with mains return. If the automatic test is in progress the engine continues to run until the end of the automatic test.
STOP When the stop contact is closed, REMOTE STOP is shown on the display. The control unit does not allow any startup operation, and if the generator set is running, it is stopped. The intervention of the remote control is shown on the display.
EJP FUNCTION Choose EJP function (see TECHNICAL PROGRAMMING manual on page 18). When the START UP contact, connected to terminal 31, closes, EJP STARTUP is seen on the display. After the EJP STARTUP DELAY time (programmed to 25 min.) has elapsed , the start up procedure begins. When the switching contact (terminal 32) closes, EJP SWITCHING CONSENT is seen on the display and the operation is as when there is a mains fault. When the two EJP contacts are opened functioning is as when the mains power returns.
VOLTMETRIC MAINS AND GENERATOR RELAYS INSIDE THE CONTROL UNIT
These check the mains and generator set voltage. They intervene in the event of: voltage failure, undervoltage, overvoltage, asymmetrical voltage and incorrect phase sequence
MAINS RELAY When voltage has been detected on the three phases, with a value within the preset limits, after the MAINS ACCEPTANCE delay (programmed to 100 sec.) the generator set stops (for the starting and stopping procedures see automatic operation on page 4).
GENERATOR RELAY When a voltage value is detected on the three phases of the operating generator set within the expected range, the generator contactor closes after the delay (setpoint equal to 7 seconds) for “GENERATOR TO POWER USERS CONNECTION”. When the voltage value detected is inferior or superior to the normally expected range, the generator contactor is de-energised.
ELCOS- Parma- Italy - GB - CAM -68410 Valid for firmware revisions higher than or equal to 1.24
STARTING CONSENT. Operation obtained as during automatic mode.
Programming of telephone numbers of the users to inform when alarm.Refer to “Sending SMS messages” in the Modem Manual
the generator set is in
ADJUST THE CALENDAR CLOCK. The TIMER permits to programme the operation or the block of the generating set.
WEEKLY AUTOMATIC TEST. When WEEKLY AUTOMATIC TEST ENGAGED programming is finished, withcontrol unit in automatic mode, the generator set executes the test cycle.
12:15
TO 15:20
FROM
333
333123456
12:15
TO 15:20
FROMDAILY STARTTIMER
WEEKLY AUTOMATICTEST
Decreases
Decreases
Increases
Increases
Press and wait forPROGRAMMED to be written
Press and wait forPROGRAMMED to be written
Press and wait forPROGRAMMED to be written
Press when the arrow is nextto the time to be corrected
Press to write number
Press to choose
USER PROGRAMMING
STOP
Press to
exit theprogramming
Press to select: PROGRAMMINGOPERATIONS
USERPROGRAMMING
LANGUAGE CHOICE
WEEKLY AUTOMATICTEST
DAILY STOPTIMER
DAILY STARTTIMER
PRESS TO DISPLAY THEREQUIRED PROGRAMMING
Decreases
LANGUAGE CHOICE. The language set up in the factory is ITALIAN the languages that can be selected areSPANISH
, : ENGLISH - FRENCH - GERMAN - - PORTOGUESE.
LANGUAGE CHOICE
Press and wait forPROGRAMMED to be writtenPress to select
Press to display
EXCLU
ENGAGED
EXCLUFactory setting
Press to display
STOP
STOP
Press to display
STOP
ACCESS TO PROGRAMMING MODE
( ) led off
CALENDAR CLOCK ADJUSTMENT
ADJUSTMENT IS RECOMMENDED.The time and date are used when the anomalylog events are displayed.
CALENDAR CLOCK ADJUSTMENT
ADJUSTMENTDAY MONTH YEAR
HOUR MINUTES
Press for 2 secondsuntil the number requiring editing flashes
If the power is cut off, adjustment of thecalendar clock must be repeated. Installation of tworechargeable batteries in the control unit shall preventa new setup.WARNING: USE RECHARGEABLE BATTERIES ONLY. Non-rechargeable batteries may damage the control unit.
STOP
Movesthe cursor
Increases
TELEPHONE 1
TELEPHONE 3
TELEPHONE 2
STOP. Stops starting or running of generator set. 23:00
TO 07:30
FROM
23:00
TO 07:30
FROMDAILY STOPTIMER Decreases Increases
Press and wait forPROGRAMMED to be written
Press when the arrow is nextto the time to be corrected.
STOP
Press to display
exam
ple
exam
ple
exam
ple No. user
No. mobile phone
Press to move the cursor
cursor
- - 2 3Or
TELEPHONE 1
TELEPHONE 1
TELEPHONE 1
LANGUAGE CHOICEENGLISH
TEST
CancelsC
ELCOS- Parma- Italy - GB - CAM -684 11Valid for firmware revisions higher than or equal to 1.24
NOTICES Used only to check and command a genset unit. It commands the mains and generator contactors to supply the user. It has been designed to be installed only inside on an electrical panel as a single unit and so that it can be connected to other components (contactors, fuses, thermo-magnetic switches, etc.) which the installer will have available to complete the plant.
Warning: Components carrying dangerous voltage levels Only assigned and suitably trained personnel are allowed access to the control unit. No maintenance operations are permitted unless the plant is disconnected from the mains and the battery. As an additional safety measure, the plant phases should be short-circuited and earthed. Not withstanding the above, only assigned and trained personnel can perform the following
operations with the plant on: - make a visual inspection of the control unit, the connections and their markings; - measure the voltage and/or current values; - programming of the functions. These interventions, however, must be performed using equipment which ensures appropriate levels of electrical protection.
Warning: Adhere closely to the following advice
- When making connections always follow the instructions and the Wiring Diagram on pages 6-7. - Any interventions on the unit must be performed with the motor stationary and terminal 50 of the starting motor disconnected. - Check that the consumption of the connected equipment are compatible with the described technical characteristics. - Install in such a way that there is always adequate heat disposal. - Always install under other equipment which produces or spreads heat. - Handle and connect without mechanically stressing the electronic board. - Make sure that no copper conductor cuttings or other waste material fall inside the control panel. - Never disconnect the terminals of the battery with running engine. - Never use a battery charger for the emergency start-up; the control unit could be damaged. - In order to safeguard people and equipment, before connecting an external battery charger, disconnect the electrical system terminals from the battery poles. THIS CONTROL UNIT IS NOT SUITABLE FOR OPERATING IN THE FOLLOWING CONDITIONS: - Where the environmental temperature is outside the limits indicated in the technical data. - Where the air pressure and temperature variations are so rapid as to produce exceptional condensation. - Where there are high levels of pollution caused by dust, smoke, vapour, salts and corrosive or radioactive particles. - Where there are high levels or heat from radiation caused by the sun, ovens or the like. - Where attacks from mould or small animals are possible. - Where there is the risk of fire or explosions. - Where the control panel can receive strong vibrations or knocks. - Where the control panel is protected by barriers or casing with protection level less than IP40. ELECTROMAGNETIC COMPATIBILITY This control unit functions correctly only if inserted in plants which conform with the CE marking standards; it meets the exemption requirements of the standard EN61326-1 but it cannot be excluded that malfunctions could occur in extreme cases due to particular situations. The installer has the task of checking that the disturbance levels are within the requirements of the standards. CONDUCTION AND MAINTENANCE The following maintenance operations should be performed every week: - check that the indicators function; - check the condition of the batteries; - check that the conductors are tight, check the condition of the terminals. UNLESS WE MAKE A WRITTEN DECLARATION STATING THE CONTRARY, THIS CONTROL UNIT IS NOT SUITABLE FOR USE AS A CRITICAL COMPONENT IN EQUIPMENT OR PLANTS RESPONSIBLE FOR KEEPING PERSONS OR OTHER LIVING BEINGS ALIVE.
YOUR ELECTRICAL TECHNICIAN CAN ASK ANY QUESTIONS ABOUT THIS CONTROL UNIT BY TELEPHONING OUR TECHNICIAN
ELCOS- Parma- Italy - GB - CAM -68412 Valid for firmware revisions higher than or equal to 1.24
ELCOS s.r.l. assumes full responsability for declaring that the control unit:
type CAM-684installed and used in the ways and for the purposes described in theinstruction and use manual, is in conformity with the following directives:- 2006/95/CE related to the electrical materials destined to be used
within certain voltages limits- 2004/108/CE related to the electromagnetic compatibility and that repeals
the directive 89/336/CEE- 2011/65/UE on the restriction of the use of certain hazardous substances in
electrical and electronic equipment,because it is built and functions in accordance with the harmonized Standards:EN61010-1, EN61326-1, EN61326/A1, EN61000-4-2,EN61000-4-3,EN61000-4-4, EN61000-4-5, EN61000-4-6, EN60529.
CONFORMITY DECLARATION
BATTERY CHARGERWe recommend fitting the plant with battery chargers
compliant with DIN41773 standards.
BATTERY CHARGER OPERATIONTHREE CHARGING LEVELS
- RAPID WITH CURRENT CONTROL- INTERMEDIATE- MAINTENANCE
WITH VOLTAGE CONTROL} WHEN THE BATTERY CHARGER IS CONNECTED TO THE CAM-684 CONTROL UNIT, THE DISPLAY SHOWS THE FOLLOWING:
• CHARGING CURRENT• BATTERY VOLTAGEANOMALIES
• DETACHMENT OF BATTERY CABLES (with engine stopped)• SHORT CIRCUITING OF BATTERY CABLES
ORDERING DATA
ACCESSORIES SUPPLIED
Type CodeCAM-684 00242283
Type CodeKIT MU CAM-684 40804469
ACCESSORIES ON REQUESTType CodeTHE REMOTE PANEL Type PRE-685 00242282(Displays the instruments and errorsmanaged by the CAM-684)
®