Control & Sensor Technologygenset.co.kr/down/apecs-0250.pdf · 2018-12-28 · Control & Sensor...
Transcript of Control & Sensor Technologygenset.co.kr/down/apecs-0250.pdf · 2018-12-28 · Control & Sensor...
![Page 1: Control & Sensor Technologygenset.co.kr/down/apecs-0250.pdf · 2018-12-28 · Control & Sensor Technology Printed in the USA APECS® 0250/0250P Linkage-Free, Integral Type Actuator](https://reader033.fdocuments.us/reader033/viewer/2022060223/5f07ecd27e708231d41f7256/html5/thumbnails/1.jpg)
C o n t r o l & S e n s o r Te c h n o l o g y
Printed in the USA
APECS®
0250/0250PLinkage-Free, Integral
Type Actuator
Features
Linear Proportional Actuators
• Engine or application specific mounting brackets
• Two pin connectors
• Rod end linkages
• Position feedback
• Push or Pull actuation
• Failsafe operation using spring to returnactuator to minimum fuel position
• Polarity protected
• Corrosion resistant plated steel casing andmounting base/flange
• Engine mountable
• 100% inspected and factory tested
• Variety of options for mounting styles, plungers, terminations and springs
0250 PROPORTIONAL ACTUATOR PULL/BASE
1/4-28 THREADOR
M6 X 1 THREAD
LEAD WIRE #20 GA.COLOR:WHITE-12 VDC
RED-24 VDC(2-PLACES)
4.17 REF.[105.9]
DE-ENERGIZED
3.17 REF.[80.5]
ENERGIZED
.325 REF.[8.26]
(4-PLACES)
2.50ø REF.[63.5]
3.94 MAX.[100.1]
1.00 REF.[25.4]
1.50 REF.[38.1]
3.62 REF.[91.9]
3.25 REF.[82.6]
0250P PROPORTIONAL ACTUATOR PUSH/BASE
LEAD WIRE #20 GA.COLOR:WHITE-12 VDC
RED-24 VDC(2-PLACES)
1/4-28 THREADOR
M6 X 1 THREAD
1.50 REF.[38.1]
3.25 REF.[82.6]
3.62 REF.[91.9]
1.00 REF.[25.4]
4.90 MAX.[124.5]
.325 REF.[8.26]
(4-PLACES)
1.25 REF.[31.8]
DE-ENERGIZED2.25 REF.
[57.2]ENERGIZED
2.50ø REF.[63.5]
1/4-28 THREADOR
M6 X 1 THREAD
LEAD WIRE #20 GA.COLOR:WHITE-12 VDC
RED-24 VDC(2-PLACES)
0250P PROPORTIONAL ACTUATOR PUSH/FLANGE
5.14 MAX.[130.6]
1.76 REF.[44.7]
ENERGIZED
.76 REF.[19.3]
DE-ENERGIZED
3.62 REF.[91.9]
2.50ø REF.[63.5]
.325ø HOLE THRU REF.[8.26]
(2-PLACES)
0250 PROPORTIONAL ACTUATOR PULL/FLANGE
1/4-28 THREADOR
M6 X 1 THREAD
LEAD WIRE #20 GA.COLOR:WHITE-12 VDC
RED-24 VDC(2-PLACES)
3.62 REF.[91.9]
1.76 REF.[44.7]
DE-ENERGIZED
.76 REF.[19.3]
ENERGIZED
3.94 MAX.[100.1]
2.50ø REF.[63.5]
.325ø HOLE THRU. REF.[8.26](2-PLACES)
© 2001 Synchro-Start Products, Inc. L-SAL-037 Rev D 05/01
Options
![Page 2: Control & Sensor Technologygenset.co.kr/down/apecs-0250.pdf · 2018-12-28 · Control & Sensor Technology Printed in the USA APECS® 0250/0250P Linkage-Free, Integral Type Actuator](https://reader033.fdocuments.us/reader033/viewer/2022060223/5f07ecd27e708231d41f7256/html5/thumbnails/2.jpg)
• Stroke: • Spring Shutdown Force @ Full Stroke:1.0” maximum 1.70 pounds
• Net Force: • Temperature Range:6.0 pounds -40 deg C to 121 deg C
(-40 deg F to 250 deg F)
• Work Rating: • Vibration:0.7 foot-pounds 15 Gs
• Rated Current: • Shock:6.5 Amps (12 vdc) 200 Gs3.5 Amps (24 vdc)
• Response Time: • Shipping Weight:65 milliseconds Approx. 3.0 lbs (1.4 kg)for 10%-90% of stroke
Linear Proportional Actuators
02500250P
Specifications
To order, specify the desired features from the following chart. For example: 0250P-12A2LS1
Model Volts Mounting Style Plunger Type Termination Type Return Spring Special Options(Force @ Full Stroke)
0250 12VDC A-Flange 2-Ext.1/4-28 Threads L-Lead wire S1(pull) 24VDC E-Base 3-Ext.M-6 Threads C-Connector (1.75 lbs)
0250P 12VDC A-Flange 2-Ext.1/4-28 Threads L-Lead wire S1(push) 24VDC E-Base 3-Ext.M-6 Threads C-Connector (1.75 lbs)
Ordering Information
An overspeed shutdown device, independent of the APECS system, should be provided to preventloss of engine control which may cause personal injury or equipment damage.
WARNING
!
C o n t r o l & S e n s o r Te c h n o l o g y
Synchro-Start Products, Inc.a Knowles company6250 West Howard StreetNiles, Illinois 60714-3433 USATelephone: 847/967-7730FAX: 847/[email protected]
Synchro-Start Products Europe LimitedYork RoadBurgess HillWest Sussex RH15 9TTEnglandTelephone: (+44) (0)1444-872-836FAX: (+44) (0)[email protected]
Synchro-Start Products AsiaNo. 20 Su-Tong RoadSuzhou Singapore Industrial ParkJiangsu ProvincePRC Postal Code: 215021Telephone: (0512) 762-6727FAX: (0512) [email protected]