Control Principles Instruction of WGF44013.7_2 Style Boiler

download Control Principles Instruction of WGF44013.7_2 Style Boiler

of 38

Transcript of Control Principles Instruction of WGF44013.7_2 Style Boiler

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    1/38

    WBC

    WGF440/13.7-2 Style Boiler

    Control Principles Instruction

    SS505-22

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    2/38

    WBC Control Principles Instruction SS505-22

    Preface

    India MPPL1135MW CFB boiler which is a single drum natural circulation boiler with

    high temperature and super high pressure, single middle reheating, a high temperature

    insulated cyclone, balanced air draft, coal feeding on front wall, outdoor arrangement. It burns

    high moisture and high sulfur lignite and it is designed by Wuhan Boiler Company Ltd. and

    Thermophysics Engineering Institute of Chinese Academy of Sciences and made by WuhanBoiler Company Ltd.

    The instruction specifies attentive items in boiler on-off process and normal operation

    according to design characteristics of this boiler. In accordance with the features of circulating

    fluidized bed boiler of this type it also gives alarm value of the main control parameters, MFT

    acting values that provide references for the power plant and design institute when carrying

    on DCS program, compiling operating rules, running and controlling of the boiler.When reading this instruction, please refer to the following correlative instructions

    simultaneously:

    1. Boiler Product Specification (SS505-1):

    2. Boiler Operating Instruction (SS505-7):

    3. Other instructions (such as ash cooler, ignition, soot-blowing, regular blow through,

    etc ):

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    3/38

    WBC Control Principles Instruction SS505-22

    CONTENTS

    1. GENERAL RULES.........................................................................................1

    2. SAFETY MEASURES OF RUNNING .........................................................1

    2.1 Basic requirements.......................................................................................................................................... ..1

    2.2 Measuring points description...........................................................................................................................1

    2.3 Limitations of subatmospheric pressure in the furnace................................................................................1

    2.4 Drum water level and temperature difference requirements .......................................................................2

    2.5 Excess air requirements ................................................................................................................................ ...2

    2.6 Furnace bed temperature limitations..............................................................................................................2

    2.7 Limitations of air flow and air pressure in the air chamber in the furnace ................................................3

    2.8 Protection of reheater pipes .............................................................................................................................3

    2.9 Safety valve regulation......................................................................................................................................3

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    4/38

    WBC Control Principles Instruction SS505-22

    1. General rules

    (1) The contents in the following sections can not be regarded as operating regulations of

    the boiler unit. When the power plant compiles and improves its operating regulations

    instructions about the boiler, auxiliary equipment and the instruction of initial operation of the

    boiler could be used to referring as a instructing datum.

    (2) Security of the boiler should be paid attention to in the operating and running.

    Circulating fluidized bed combustion technology is different from pulverized coal combustion

    technology and other combustion technologies. Circulating fluidized bed boiler doesnt have

    obvious fireballs in the furnace. It contains plentiful circulated solids that carrying a lot of

    heat.

    (3) Before start-up boiler unit the operating workers should be fully familiar with

    structure and function of the boiler, assemblies, control system and auxiliary equipments.

    (4) Operating workers should be know the working conditions of each assemblies andauxiliary equipments as well as pay attention to actual operating conditions when star-up and

    in operation of the boiler according to system requirements.

    2. Safety measures of running

    2.1 Basic requirements

    (1) O ti k t b d b d t ti d f t th t

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    5/38

    WBC Control Principles Instruction SS505-22(3) MFT (main fuel trip) should be set in the furnace outlet pressure value of 2500Pa

    and with 5 seconds delay.

    (4) Forced and induced draft fans trip should be set in the furnace outlet pressure value

    of 3500Pa (without delay).

    (5) After forced fans, induced draft fans and all of the loop seal high pressure blowers

    shut off (using MFT action to make fans shut off) the collapsed bed materials still occur

    combustion. So access door must keep closed .When start-up again the air flow should be

    entered in slowly in order to blow combustible in the boiler out of the unit.2.4 Drum water level and temperature difference requirements

    (1) Normal water level of the drum is below drum centerline 150mm.Alarm water level

    is set in 100mm relative to normal water level. Shutdown water level is set in 175mm and

    -200mm relation to the normal water level.

    (2) When the drum is at the lowest water level (water level lower than normal water level

    200mm) or at the highest water level (water level higher than normal water level 175mm)should carry on MFT and cut off forced fans and induced draft fans.

    (3) To prevent the drum from excessive thermal stress variation ratio of the steam drum

    metal wall-temperature should be lower than 55 /h. The temperature difference between the

    up wall temperature and the down wall temperature of the drum should be controlled less than

    40 .The up wall temperature and the down wall temperature of the drum should be

    i t d d th t t diff i t ti h ld b t i th t t l

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    6/38

    WBC Control Principles Instruction SS505-22temperature as low as 550 automatically MFT should be carried out or dive into above-bed

    assisted combustion or off-bed auxiliary burners. But when bed temperature below 550

    whether auxiliary and air duct ignition combustion is operating or not MFT should be carried

    out.

    According to the accumulated operating experiences and different emphasis between

    combustion efficiency of the boiler and desulfurization and nitrogen efficiency in the case of

    ensuring the boiler without slag bed temperature could properly regulate according to actual

    running bed temperature of the boiler. In the running if the local bed temperature appearsrising it should increase primary air mass flow of the furnace bottom to improve local bad

    fluidizing conditions.

    2.7 Limitations of air flow and air pressure in the air chamber in the furnace

    (1) When the boiler operates normally the air chamber static pressure below the furnace

    distributor should maintain between 8000 and 16000Pa.When air chamber static pressure is

    below 6000Pa low limitation alarm of the air pressure will be sent out. If air chamber staticpressure is over 18000Pa high limitation alarm of the air pressure will be sent out

    (2) When the primary air flow of distributor is below 10104Nm3/h air flux low

    limitation alarm will be sent out.

    (3) Carry out MFT if it happened following situations:

    a. Air chamber pressure in the furnace is above 20000Pa and delays 10 seconds;

    b Ai i th i h b i b l 6000P d d l 10 d

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    7/38

    WBC Control Principles Instruction SS505-22

    MPa t/h

    Drum safety valve 1# 15.74 172.17

    Drum safety valve 2# 16.21 177.25Superheater safety valve 1# 14.30 49.51

    Superheater safety valve 2# 14.44 49.99

    Reheater safety valve at inlet 1# 3.07 139.25

    Reheater safety valve at inlet 2# 3.15 142.60

    Reheater safety valve at outlet 1# 2.80 47.01

    Reheater safety valve at outlet 2# 2.99 37.90

    2.10 Control of steam temperatureIn order to monitor start-up conditions we set up wall- thermocouple to measure steam

    temperature at the relational components of stream circuitry to confirm allowable heating-up

    velocity.

    Component Position NO. Alarm temperature value

    Drum Top and bottom parts Up-down 6apiece

    Temperature difference

    between 40

    temperature variety 55 /h

    Platen

    superheater

    Upwards platen: top parts 8 /

    Downwards platen: at subjacent

    outlet of platen8 495

    Low temp.

    h t

    Outlet pipeloop

    (even distribution in furnace

    idth)

    22 430

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    8/38

    WBC Control Principles Instruction SS505-223.1. Strategies and requirements of the furnace safety monitor system

    The primary function of the furnace safety monitor system is to implement orderly

    management of boiler combustion system. When permission conditions are satisfied the

    program controls burners to start-up and shutdown the boiler as well as to maintain burners

    operating steadily. When permission conditions are not satisfied we should carry on safe logic

    which is designed advanced and essential safeguards for boiler to protect safety of workers

    and equipments. These safeguards consist of rapid drop of load, shutdown of the boiler, soot-

    blowing of the furnace after shutdown and so on.Primary functions of the furnace safety monitor system are:

    (1) The flame monitoring;

    (2) The furnace pressure monitoring;

    (3) Burners management;

    (4) MFT;

    (5) Furnace soot-blowing;(6) Other interlock and monitor items.

    Primary conditions joined in boiler protection interlock are:

    (1) Boiler temperature permitted range;

    (2) Steam drum water level is not low;

    (3) Steam drum water level is not high;

    (4) Ai f hi h i t l

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    9/38

    WBC Control Principles Instruction SS505-22When the MFT occurs it will appears following actions:

    (1) Stop flue burner (under-bed burner);

    (2) Stop above-bed start-up burner;

    (3) Stop coal feeder and rotary valve;

    (4) Stop limestone feeder and rotary valve;

    (5) Close latch valves of first and secondary spray water;

    (6) Close main oil trip valves;

    (7) Set total air flow in minimum;(8) Turn the secondary air spray nozzle control to manual actuated.

    The main conditions joined in flue and above-bed burner interlock are:

    (1) Main oil piping trip valve is open;

    (2) Main oil piping trip valve is close;

    (3) Main oil piping pressure is low;

    (4) Main oil piping pressure is high;(5) Ignition is permitted;

    (6) Main oil piping trip valve conditions is satisfied;

    (7) Single burner ignition is permitted;

    (8) Air flow of the single burner is more than the minimum value;

    (9) Oil pressure of the single burner is low;

    (10) Oil f th i l b i i l

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    10/38

    WBC Control Principles Instruction SS505-22

    Purge logic

    (see Chart 2)

    MFT logic

    [see Chart 1(b)]

    Finish the purge

    Permit to release MFT relay

    N

    O

    T

    A

    N

    D

    A

    N

    D

    Burner logic

    in flue

    Solid fuel logic

    (see Chart4)Main fuel trip(MFT)

    Chart 1(a) Interlock system program

    Loose induceddraft fan

    Loose forceddraught an

    Drum water level

    is low

    Furnace pressure ishigh

    Ai fl

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    11/38

    WBC Control Principles Instruction SS505-22

    Conditions of the

    boiler trip have

    b d

    All the fuel feeding

    equipments havetripped and all the

    safty valves have

    closed

    All the required air

    regimes is operating

    All the air paths in

    purge position

    AN

    D

    Boiler air flow more

    than purge air flow

    A

    It has been startedand completed 5

    times volume or

    purged for 5minutes(bed hasbeen

    fluidized)

    O

    R

    Purge of the

    i f l d

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    12/38

    WBC Control Principles Instruction SS505-22

    Air used forcobustion of

    burnerin flue is notsufficient

    Pressure of burner

    in flue is dissatisfied

    burning source

    Burner in

    flue"Flameless"

    Igniter "Sparkless"

    MFT(see Chart 1(b))

    MFT relay

    (see Chart1 (b))

    OR

    O

    R

    Close saftysidengaging valve

    of single burner

    in flue

    Stop striking fire

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    13/38

    WBC Control Principles Instruction SS505-22

    Trip of superiorfeeding system

    equipment

    Parts of solid fuelfeeding system is

    in trouble

    Bed has not

    fluidized

    Withourconfirmation ofburner in flue

    Permissions of solidfuels bed

    temperature aredissatisfied

    Bed temperature islow

    MFT(see chart 1 (b))

    MFT relay

    (see Chart 1(b))

    A

    N

    D

    OR Trip of solid fuel

    feeding system

    Chart 4 Solid fuel safety subsystem

    3.2 Strategies and requirements of regulation and control

    Th i f ti f l ti d t l t (Th d t b l t

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    14/38

    WBC Control Principles Instruction SS505-22transfer process.

    (2) Mass flow compensation control circuit

    Measuring value of total fuel mass flow (coal and fuel oil) regards as feedback signal of

    the coal mass flow control circuit and required amount signal of the air flow control circuit

    must consider some changes of the boiler heat transfer status and fuel heat value. Therefore,

    total fuel flow must be compensated.

    (3) Feed water mass flow control circuit

    This circuit design must ensure that balance between feed water flow of the boiler and

    that of steam flow in order to maintain the required water level in drum. During the start-up

    period above process is realized by controlling the opening degree of the start-up feed water

    regulate valve. In normal operating period above process is realized by controlling the

    opening degree of the main feed water regulate valve. These two valves receive their control

    signals respectively from single momentum controller or three- momentum controller. The

    single momentum control could control automatically but also could control manually. Three-momentum control could cascade control but also could control manually in operation. Single

    momentum control inspects steam drum only and is used in start-up. Three- momentum

    control inspects drum water level, steam mass flow and feed water mass flow. It has high

    control level and is used in the steady heavy load condition.

    (4) Primary air heater control circuit

    Th t l t i d t t l th ld d t t f i h t t

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    15/38

    WBC Control Principles Instruction SS505-22adjustment. The main controller responds according to temperature difference between the

    temperature at SH3 outlet and the setting value of the manual actuated. Assistant controller

    responds according to temperature difference between modified temperature by main

    controller and temperature at SH2 outlet. The final main steam temperature left boiler controls

    in 540 .

    (6) Steam temperature of reheater control circuit

    The whole steam temperature control is realized by spraying water of desuperheater to

    control temperature of steam left reheater. This control is based on cascade adjustment. The

    main controller responds according to temperature difference between temperature at RH2

    outlet and the setting value of the manual actuated. Assistant controller responds according to

    temperature difference between temperature modified by main controller and temperature at

    RH1 outlet. The final temperature of steam left reheater is controlled in 540 .

    (7) Bed temperature control circuit

    The purpose of this circuit is to keep bed temperature at setting value according to loaddemands. The setting value is 870 . Operating in this temperature could ensure optimal

    combustion efficiency and optimal desulfuration efficiency. For controlling bed temperature

    at this level the ratio of the primary air and the secondary air should change with bed

    temperature.

    (8) Primary air flow control circuit

    Th i id d b i i f h f ll i f ti

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    16/38

    WBC Control Principles Instruction SS505-22damper is controlled. During start-up burner exit operation the damper should be set at a fixed

    opening degree. Cold air flow of the single burner can not lower than 8788 Nm 3/h to protect

    the burner injections from burnout.

    Air distribution of the off-bed burner: There are 2 off-bed burners. Every start-up burner

    has 3 damper regulators. They are a damper used for oil burner combustion, a cooling air

    dampers and a main fluidizing air damper. At start-up the main fluidizing air damper is

    closed. After converting the oil mass flow of the burner into combustion air flow (excess air

    ratio 1.1) and cooling air flow (excess air ratio 3), then comparing with actual measured

    air flow. Consequently opening degree of the air damper is controlled. During the initial start-

    up period the damper could reduce gradually to protect temperature excursion of

    precombustion pot after cooling air dampers opened entirely. After burner outage the main

    fluidizing dampers opened gradually, air dampers for combustion and dampers for cooling are

    closed gradually to maintain total primary air s flow at the bottom of furnace.

    (11) Furnace draft (subatmospheric pressure) control circuitThe boiler is balance draft boiler which is defined as by controlling the discharge amount

    of combustion product and excess air amount relative to feeding in order to maintain the

    pressure of a certain characteristic point constant in the furnace. The pressure balance point of

    this boiler is set at furnace outlet. Induced draft fan sucks flue gas from dust separator and

    vents cleanly flue gas to stack. Subatmospheric pressure of furnace could be realized by

    lli h d i d f h i d d d f

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    17/38

    WBC Control Principles Instruction SS505-22(15) An attachment of Control circuit

    Control circuit Regulated parameter Control variable Control components

    Boiler load controlMain steam mass flow

    and pressure

    coal feed mass

    flow, oil mass flow

    Feeder revolution

    numbers, oil-firing

    regulator valve

    Feed water mass

    flow control Drum water level

    Feed water

    mass flow

    feed water regulator valve

    Speed governing feedpump

    Superheater

    temperature control

    Superheater

    temperature

    desuperheated

    water mass flow

    desuperheat water

    regulator valve

    Bed

    temperature controlBed temperature

    ratio of primary air

    and secondary air

    primary air and secondary

    air control dampers

    bed pressure control Bed pressure Tapping mass flow

    Roller ash cooler rate

    rotational speed control

    Furnace draft control Furnace draft Flue gas mass flowdamper at

    induced draft fan inlet

    primary air

    flow control

    Primary air mass flow,

    bed temperature

    Primary air

    mass flow

    Guide vane at

    primary air fan inlet

    secondary air

    fl l

    Oxygen content in flue,

    b d

    secondary air flowTotal damper of

    d i fl

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    18/38

    WBC Control Principles Instruction SS505-22

    4. Boiler function curves

    This section provides function curves of the boiler. It is only a reference for designing

    boiler control system.

    1 3

    1.4

    Correctionfact

    orofmans t

    eam

    massfl o

    w

    Temperature correction factor of the main steam mass flow

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    19/38

    WBC Control Principles Instruction SS505-22

    Temperature correction factor of feed water mass flow

    0.8

    0.9

    1.0

    1.1

    1.2

    0 100 200 300 400

    Temperature of feed water

    Correct

    ion

    factor

    offeed

    water

    massflow

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    20/38

    WBC Control Principles Instruction SS505-22

    Pressure correction factor of main steam mass flow

    0.0

    0.2

    0.4

    0.6

    0.8

    1.0

    1.2

    0.0 5.0 10.0 15.0 20.0

    Pressure of main steam MPa

    Correct

    ion

    factor

    ofmain

    steam

    mass

    flow

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    21/38

    WBC Control Principles Instruction SS505-22

    Drum pressureMPa Gain1 0.00 1.0000

    2 1.50 1.1206

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    22/38

    WBC Control Principles Instruction SS505-22

    Drum pressureMPa Deviationmm1 0.00 0.00002 1.50 38.9471

    3 3.00 60.5434

    4 4.50 79.5728

    5 6.00 98.1170

    6 9.00 137.4645

    7 11.00 167.8156

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    23/38

    WBC Control Principles Instruction SS505-22

    Total secondary airtemperature ( )

    Correction factor ofair mass flow

    1 0.0 1.0622

    2 10.0 1.0432

    3 20.0 1.0253

    4 32.0 1.0000

    5 40.0 0.9920

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    24/38

    WBC Control Principles Instruction SS505-22

    Primary air temperature

    Correction factor of

    air mass flow

    1 0.0 1.3693

    2 100.0 1.1715

    3 150.0 1.1001

    4 200.0 1.04035 250.0 1.0000

    6 300.0 0.9452

    7 350.0 0.9065

    8 400.0 0.8721

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    25/38

    WBC Control Principles Instruction SS505-22

    Secondary air

    temperature ( )

    Correction factor of

    air flow

    1 0.0 1.3693

    2 100.0 1.1715

    3 150.0 1.1001

    4 200.0 1.0403

    5 250.0 1.0000

    6 300.0 0.9452

    7 350.0 0.9065

    8 400.0 0.8721

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    26/38

    WBC Control Principles Instruction SS505-22

    Fuel spreading air

    temperature ( )

    Correction factor of

    air flow

    1 0.0 1.3693

    2 100.0 1.1715

    3 150.0 1.10014 200.0 1.0403

    5 250.0 1.0000

    6 300.0 0.9452

    7 350.0 0.9065

    8 400.0 0.8721

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    27/38

    WBC Control Principles Instruction SS505-22

    Steam mass flow Excess oxygen content

    t/h %

    1 65.0 14.3000

    2 123.8 9.7000

    3 200.0 4.0000

    4 220.0 2.7000

    5 303.0 2.7000

    6 398.0 2.70007 440.0 2.7000

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    28/38

    WBC Control Principles Instruction SS505-22

    Controller output of

    oxygen content %

    Correction factor of

    oxygen content

    1 0.0 0.802 50.0 1.00

    3 100.0 1.20

    Relation of deviation amount of bed temperature manual actuated and primary air flow

    15.0

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    29/38

    WBC Control Principles Instruction SS505-22

    % KNm3/h

    1-50.0 -10.00

    20.0 0.00

    350.0 10.00

    Relation of deviation amount of bed temperature manual actuated and upper secondary air flow

    10.0

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    30/38

    WBC Control Principles Instruction SS505-22

    % KNm3/h

    1 -50.0 -5.00

    2 0.0 0.00

    3 50.0 5.00

    0.0

    5.0

    10.0

    second

    aryair

    flow

    Km3

    /h

    Relation of deviation amount of bed temperature manual actuated

    and middle and lower secondary air flow

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    31/38

    WBC Control Principles Instruction SS505-22

    3 50.0 5.00

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    32/38

    Table 1 Measuring point description

    No. Measuring name Qty FunctionRunning

    value

    Range of

    measuring

    (a reference)

    Arranging

    locationRemarks

    1 Feed water mass flow 1Regulate feed water

    flow440t/h 0550t/h

    Feed water

    pipeline

    2Total desuperheated water

    mass flow of superheater1 Monitor 21.94t/h 050t/h

    Superheater

    desuperheated

    water total pipe

    Maximum 32t/h

    3Feed water temperature in

    front of operation floor1

    Correction of

    feed water flow248 0400

    Feed water

    pipeline

    4Pressure at

    economizer inlet2

    Monitor for spot,

    remote transmission

    monitor

    15.35MPa 025MPaFeed water

    pipeline

    5Temperature at economizer

    inlet1 BTU compensation 248 0400

    Feed water

    pipeline

    6Temperature at economizer

    outlet2 Monitor 300 0400

    Economizer

    outlet header

    7Drum up and down wall-

    temperature measuring point

    6

    pairsMonitor

    342 ,

    temperature

    difference is

    40

    0400 Drum

    8 Drum water level alarm 2 Interlock protection 100 300 Drum

    Acting value: 175mm

    9Drum water level automatic

    regulating3

    Water level

    regaulatingDrum

    W

    BC

    ControlPrinciplesInstruc

    tion

    SS505-

    22

    29

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    33/38

    Table 1 Measuring point description

    No. Measuring name Qty FunctionRunning

    value

    Range of

    measuring

    (a reference)

    Arranging

    locationRemarks

    10Connect with spring safety

    valve2 Protection 14.99MPa Drum

    Acting value

    14.991.08MPa

    Acting value

    14.991.05MPa

    11Drum pressure measuring

    point5

    Monitor, correct

    stream drum water

    level pressure

    14.99MPa 025MPa Drum

    12Metal wall-temperature at

    SH1 outlet tube22 Monitor 430 0800 At SH1 outlet

    13Steam temperature at

    SH1 outlet4 Monitor 410 0600

    At SH1 outlet

    pipe

    14Steam temperature at

    SH2 inlet6

    Monitor, correct spay

    water mass flow394 0600

    At SH2 inlet

    pipe

    15Metal wall-temperature of

    SH2 upwards panels tube8 Monitor 455 0800

    Upper parts of

    SH2 upwards

    panel

    16Metal wall-temperature of

    SH2 upwards panels tube8 Monitor 495 0800 At SH2 outlet

    17 SH2 outlet steam temperature 4Regulate spay water

    mass flow473 0600

    At SH2 outlet

    pipe

    18 SH3 inlet steam temperature 6monitor, correct spay

    water mass flow 452 0600At SH3 inlet

    pipe

    19Metal wall-temperature of

    SH3 outlet tube22 Monitor 550 0800 At SH3 outlet

    20 SH3 outlet steam temperature 4 Monitor and Regulate

    spay water mass

    540 0~600 Main steam

    outlet pipeline

    W

    BC

    ControlPrinciplesInstruc

    tion

    SS505-

    22

    30

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    34/38

    Table 1 Measuring point description

    No. Measuring name Qty FunctionRunning

    value

    Range of

    measuring

    (a reference)

    Arranging

    locationRemarks

    flow

    21Connect with spring safety

    valve2 Protection 13.70MPa

    SH3 outlet

    header

    Acting value

    14.30MPa

    Acting value

    14.44MPa

    22Connect with spring safety

    valve2 Protection 2.454MPa

    Reheater outlet

    header

    Acting value

    2.80MPa

    Acting value

    2.99MPa

    23Connect with spring safety

    valve2 Protection 2.605MPa

    Reheater inlet

    header

    Acting value

    3.07MPa

    Acting value

    3.15MPa

    24Reheater inlet steam

    temperature4 Protection 326 0600

    Reheater inlet

    header

    Acting value

    366

    25Low temp. reheater inlet

    steam temperature6 Monitor 326 0600

    Pipeline at

    reheater steam

    inlet

    26Metal wall-temperature of

    low temp.reheater22 Monitor 480 0800 RH1

    27Low temp. reheater outlet

    steam temperature4 Monitor 459 0~600

    RH1 outlet

    pipeline

    28High temp. reheater inlet

    steam temperature6 Monitor and regulate 452 0~600

    RH2 inlet

    pipeline

    W

    BC

    ControlPrinciplesInstruc

    tion

    SS505-

    22

    31

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    35/38

    Table 1 Measuring point description

    No. Measuring name Qty FunctionRunning

    value

    Range of

    measuring

    (a reference)

    Arranging

    locationRemarks

    29

    High temp. reheater outside

    track pipe metal wall-

    temperature

    12 Monitor 550 0800 RH2

    30High temp. reheater outlet

    steam temperature4 Monitor and regulate 540 0600

    RH2 outlet

    pipeline

    31Reheater desuperheated water

    mass flow2 Monitor 2.78t/h 08t/h

    Reheater

    desuperheater

    Maximum

    3t/h

    32Superheater desuperheat

    water mass flow2 Monitor 8.3t/h 015t/h

    Superheater

    desuperheater

    Maximum

    11.5t/h

    33Superheater desuperheat

    water mass flow2 Monitor 2.8t/h 08t/h

    Superheater

    desuperheater

    Maximum

    4.5t/h

    34

    Reheater

    Accidental spay water mass

    flow

    2 Monitor 0t/h 010t/hAccidental

    desuperheaterMaximum 10t/h

    35Wall-temperature measuring

    point of off-bed burner6 Monitor and control 900 01300

    On the burner

    precombustion

    pot inside wall

    Acting value

    >1100

    36

    Outlet flue gas temperature

    measuring point of off-bed

    burner

    4 Monitor and control 850 01300 At burner outletActing value

    >900

    37

    Furnace compartment

    pressure 4

    Regulate ash

    discharge 14500Pa 022000PaFurnace

    compartment

    Operating range

    800016000Pa

    38

    Water-cooling air box

    temperature measuring

    point

    2 Monitor 260 01300Water-cooling air

    box

    W

    BC

    ControlPrinciplesInstruc

    tion

    SS505-

    22

    32

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    36/38

    Table 1 Measuring point description

    No. Measuring name Qty FunctionRunning

    value

    Range of

    measuring

    (a reference)

    Arranging

    locationRemarks

    39 Pressure of combustoremulsion zone lower parts

    10 Monitor and regulateash discharge

    7000Pa 015000Pa

    Combustor

    emulsion zone

    lower parts

    40Pressure of combustor

    emulsion zone middle parts6 Monitor 4000Pa 06000Pa

    Combustor

    emulsion zone

    middle parts

    41Pressure of combustor

    emulsion zone upper parts6 Monitor 2000Pa 04000Pa

    Combustor

    emulsion zone

    upper parts

    42Bed temperature of combustor

    emulsion zone lower parts

    10 Control and monitor 870 01300Combustor

    emulsion zone

    lower parts

    43Bed temperature of combustor

    emulsion zone middle parts10 Control and monitor 870 01300

    Combustor

    emulsion zone

    middle parts

    44Bed temperature of combustor

    emulsion zone upper parts10 Monitor 870 01300

    Combustor

    emulsion zone

    upper parts

    45 Combustor outlet pressure 10Monitor, protect

    and regulate0 200Pa Combustor outlet

    Acting value

    >3500Pa

    46 SH3 inlet flue gas temperature 2 Monitor 820 01300 At SH3 inlet

    47 SH1 inlet flue gas temperature 2 Monitor 690 0~800Cagewall

    superheater

    48SH1 outlet flue gas

    temperature2 Monitor 551 0800

    Cagewall

    superheater

    W

    BC

    ControlPrinciplesInstruc

    tion

    SS505-

    22

    33

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    37/38

    Table 1 Measuring point description

    No. Measuring name Qty FunctionRunning

    value

    Range of

    measuring

    (a reference)

    Arranging

    locationRemarks

    49

    Economizer inlet flue gas

    temperature 2 Monitor 420

    0800

    Economizer

    casing

    50Economizer outlet flue gas

    temperature2 Monitor 293 0800

    Economizer

    casing

    51Oxygen content measuring

    point at economizer inlet flue2 Air flow regulating 2.70% 020%

    Economizer

    casing

    52Temperature measuring point

    at air preheater outlet flue2 Monitor 146 0800

    Air preheater

    casing

    53Temperature measuring point

    at cyclone inlet flue4 Monitor 870 01300

    Cyclone inlet

    flue

    54

    Temperature measuring point

    at cyclone outlet flue 4 Monitor 870 01300

    Cyclone outlet

    flue

    55Pressure measuring point at

    cyclone inlet flue2 Monitor -200Pa 4000Pa

    Cyclone inlet

    flue

    56Pressure measuring point at

    cyclone outlet flue2 Monitor -1900Pa 4000Pa

    Cyclone outlet

    flue

    57Temperature measuring point

    on the loop seal lift line2 Monitor 880 01300

    Cyclone lower

    parts

    58Pressure measuring point on

    the loop seal lift line2 Monitor -1000Pa 4000Pa

    Cyclone lower

    parts

    59

    Temperature measuring point

    at loop seal inlet 2 Monitor 870 01300 At loop seal inlet

    60Pressure measuring point at

    loop seal inlet2 Monitor 6000Pa 010000Pa At loop seal inlet

    61Pressure measuring point at

    loop seal compartment4 Protect 42000Pa 050000Pa Loop seal air box

    Acting value

  • 8/3/2019 Control Principles Instruction of WGF44013.7_2 Style Boiler

    38/38

    Table 1 Measuring point description

    No. Measuring name Qty FunctionRunning

    value

    Range of

    measuring

    (a reference)

    Arranging

    locationRemarks

    62

    Temperature measuring point

    of loop seal 2 Monitor 870

    01300

    Loop seal

    gradient leg

    63Pressure measuring point of

    loop seal2 Monitor 6000Pa 012000Pa

    Loop seal

    gradient leg

    Note: Other measuring points refer to arrangement drawing of measuring point and combustion system drawing.

    W

    BC

    ControlPrinciplesInstruc

    tion

    SS505-

    22

    35