Andrea Pitto RSE Control of HVDC grid converters and offshore wind farms for the provision of ancillary services and grid code compliance HVDC International Workshop “Operational experience and technological development for applications worldwide” Venice, Italy, March 28-30, 2017

Transcript of Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to...

Page 1: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Andrea Pitto – RSE

Control of HVDC grid converters and offshore wind farms for the provision of

ancillary services and grid code compliance

HVDC International Workshop “Operational experience and technological development for applications worldwide”

Venice, Italy, March 28-30, 2017

Page 2: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Outline

• Multi-terminal HVDC (MTDC) Grids for offshore windpower integration

• Converters for HVDC grids: the requirements

• Grid code compliance

• Ancillary services provision

• Models & Examples

•Conclusions

2

Page 3: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Multi-terminal HVDC (MTDC) Grids for offshore wind power integration: why?

• Compared with on-shore wind farms, off-shore ones have generally higher wind speed and larger power generating capability, which can enhance the wind turbine efficiency by 5-6%

• Development of such large-scale wind farms in Swedish, Danish, German, Dutch, French, Belgian, British and Irish waters

• Depending mainly on the transmission distance and required capacity, these radial connections are either Alternating Current (AC) or Direct Current (DC).

• A DC solution becomes mandatory in case of far and/or high-capacity offshore wind farms

3

Page 4: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Multi-terminal HVDC (MTDC) Grids for offshore wind power integration: perspectives

• Currently under investigation combined solutions for off-shore interconnection and wind generation transmission based on mainly three-legged multi-terminal HVDC

o such as Kriegers Flak (600 MW - 2020), COBRA and Caithness-Moray HVDC link (800÷1200 MW – 2018, with hub option),

• The North Seas Offshore Grid Infrastructure (NSCOGI) scheme at 2030 includes 19 projects where, on the whole, about 10000 km of new DC subsea cables should integrate up to 112 GW of offshore wind power.

• The NSCOGI study emphasizes the role of multi-terminal, meshed DC grid design versus the radial option in terms of lower grid investment.

4

Page 5: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Multi-terminal HVDC (MTDC) Grids for offshore wind power integration: how?

• The future offshore grid can be realised adopting two types of HVDC technologies:

o Line Commutated Converter (LCC) and Capacitor Commutated Converter (CCC)

oVoltage Source Converters (VSCs).

• LCCs are more mature (very high voltage and power levels, up to ±800 kV DC and 7.2 GW respectively, low losses), but VSCs appear more suitable for the Offshore DC grid concept itself.

• Currently the maximum rated DC voltage of the VSC technology is ±640 kV DC and the maximum power transmitted is 1200 MW.

5

Page 6: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

LCC, CCC and VSCs

6

AC bus

Tuned ac

filters

Switched capacitors

YY

Δ

Passive dc filters, this

can also be active

filters

Smoothing

reactor

Thyristor valves the of

twelve pulse converter

Converter transformer

AC bus

Tuned ac

filters

YY

Δ

Passive dc filters, this

can also be active

filters

Smoothing

reactor

Thyristor valves of the

twelve pulse converter

Converter transformer

LCC: Line

commutated

converter

CCC: Capacitor

commutated

converter

Vc

½Vdc

-½Vdc

0 wt

Vg

Io

Va0

Vdc

Interfacing

transformerPhase reactors

ac filters

0 a

VSC: One phase of two-level converter

weak AC networks with a short circuit ratio (SCR) up to 1CCC can change the DC current faster than LCC, without causing significant over-voltages on the inverter AC side CCC less susceptible to commutation failure at inverter terminals than LCC.

weak AC networks with a short circuit ratio (SCR) up to 1CCC can change the DC current faster than LCC, without causing significant over-voltages on the inverter AC side CCC less susceptible to commutation failure at inverter terminals than LCC.

Page 7: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Converter technology vs grid requirements

• VSCs have several advantages with respect to conventional LCC or CCC‟s:

o VSCs can operate stand-alone or in synchronized manner with the AC grid.

o VSC can contribute to control grid voltage, instead of being a reactive load that needs compensation devices.

o VSC has no short circuit power requirements to operate, i.e. it can “switch on” a de-energised network.

• VSC-HVDC transmission systems are based around self-commutation power semiconductor devices and operate from a regulated DC-bus voltage, which is common to all nodes.

o This allows fast modulation of the HVDC converter terminal AC voltage (phase and magnitude),

• In recent years, power system industry has recognized that the Voltage Source Converter (VSC) technology is the most suitable converter solution for the development of offshore DC connections.

7

Page 8: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Multi-terminal HVDC (MTDC) Grids for offshore wind power integration: barriers

• The realisation of effective DC protection systems, which are mandatory to guarantee that a fault does not imply either damage to the electrical infrastructure or service interruption.

o In this regard, the DC breaker, i.e. one of the key elements of complex DC grids, is not yet a mature component and has currently no full-scale installation in operation.

• the implementation of DC grids will require future specific market rules and regulatory frameworks within the vision of the single European Internal Energy Market (IEM)

o Currently, very few radial HVDC multi-terminal connections exist, and no meshed HVDC grids.

8

Page 9: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

HVDC grid topologies• Point to point grids

o Low reliability and flexibility

• Tree-like (backbone) grids

o Possible to re-route powerflows among onshoreterminals

o Losing the DC cable from offshore conv. meanslosing the wind park production

• Meshed grids: max reliability and flexibility

o Energy may use many pathways to go from the wind turbines to the shore, and the same for power exchanges.

o N-1 on the DC grid may have a limited impact on the transmission capacity.

o A meshed grid will add flexible interconnection capacity between different countries.

o A large amount of power can be connected to this grid; however, it has to be able to handle a fault without losing the entire generation.

9

Page 10: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

HVDC grid functions (I)• A major motivation for a grid lies in reliability requirements.

These in turn derive from the need to ensure the maximum exploitation of wind energy delivered in electricity market so that the economic investment made for the wind farms brings revenues.

o Reliability is meant here as the property of being able to assure (at least, partially) the power transfer from offshore wind farms to shore also in case of outage of some components in the offshore grid, thanks to the availability of alternative paths.

o Reliability requirements concern DC transmission lines and converter stations. For example, in case of point-to-point connection, the loss of one converter station or DC line would imply losing the whole wind farm production. Currently this issue can be partially solved by adopting a bipolar configuration in the converter station.

10

Page 11: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

HVDC grid functions (II)• Another driver related to economic and environmental considerations

consists of maximisation of wind energy harvesting and market opportunities.

o In case of radial connection of Offshore Wind Farms (OWF), under current market arrangements the only electricity market or market zone to which the OWF can, in the first instance, sell its energy or realise income from a renewables support mechanism is the one operating at the location to which the OWF is connected (the so called „home‟ market). If energy is to be sold into a different market, the OWF owner must procure access rights to an interconnector between the „home‟ market and the second market. If a price in a remote market zone is to be obtained rather than the local price, financial transmission rights should have been bought.

o In contrast, if the OWF is connected to a DC grid and two or more of the terminals are connected into different electricity markets or market zones, the controllability of a DC grid allows power to be directed to a chosen AC system location and the maximum power that can be transmitted via any one terminal is limited by both the rating of the connection and the capacity of the AC system to which it is connected. Wind power spilling would thus be minimised and best opportunities from the market viewpoint could be exploited.

11

Page 12: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

HVDC grid functions (III)• The use of DC grids connecting wind farms far away from each

other may smooth out the variability of the wind power, hence achieving steadier power injection into AC grids (mitigation effect) with positive impact on efficiency and security of operation, as well as on the environment.

o In fact, due to the variable nature of wind, the corresponding power output fluctuates independently from the load. Since the capacity of the off-shore wind farm is large, the magnitude of the fluctuating power is large as well. This might affect the demand-generation balance, leading to the need for procuring large, high-cost power reserve, provided by conventional generators. Some of them could otherwise be kept offline.

o The mitigation effect may contribute to keep the frequency stability of the AC grid. Of course, statistical studies of wind behaviour are needed in order to make sure that a certain mitigation effect would exist. Such information may support the design and sizing of the DC grid.

12

Page 13: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

HVDC grid functions (IV)• Security of operation (i.e. continuity of power supply to the users) could

also benefit from offshore grids.

o A wind farm or onshore converter failure results in the loss of power injection into the AC grid. In case of point-to-point connection, stability may be severely affected. In case of DC grid connected to different AC grids, the disturbance may be “allocated” to the individual AC grids, thus reducing the magnitude of the disturbance each AC grid has to cope with. Moreover, the DC grid injections can be dispatched in such a way as to enhance security in case of AC grid faults.

• In conjunction with wind power production, DC grids could be used to exchange power between the AC grids, thus acting as interconnectors. In this case, some onshore DC terminals could be withdrawing power, while others could be injecting power into the DC system utilizing bi-directional power flow capability of VSC.

o Power transfer capacity between countries could therefore be enhanced (though the available capacity would be the residual one from wind power, in case of wind priority). Again, this solution would assure greater efficiency of operation and environmental benefits.

13

Page 14: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

HVDC grid functions (V)• The interconnection function could also be utilized to provide mutual

support between areas of an AC grid, or even between different (i.e. not synchronously connected) AC grids, for enhanced security of operation with respect to frequency stability and to share power balancingresources.

o In this case the DC grid would act as the means that allows implementation of the support between AC areas, while the offshore wind farms might not be directly involved. In this way, DC systems may partially relieve the requirements for ancillary services (e.g. for some kinds of reserve) to be provided by conventional generators.

o By this vision, overall operational costs might decrease while at the same time complying with “DC grid code requirements”.

o The above function can be enhanced by making the wind farms contribute to ancillary services, as (downward or even upward) reserve (for frequency stability or balancing) can be shared among the offshore wind generators.

14

Page 15: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

HVDC grid functions (VI)• In addition to the previous ones, more ancillary services can be provided

from the DC grid to the AC grid. The DC grid with wind generation can be seen from the AC grid as a VPP (Virtual Power Plant) able to perform in such a way that the global operation of the integrated DC/AC power system is secure and optimal.

o Ancillary services are classified and regulated in different ways by the different grid codes and market structures. However, some of them have become common in most grid codes.

o Conventional control systems of the wind generators and of VSCs are generally required to perform functions such as fault ride through and voltage support during AC network faults; therefore the wind farm grid codes could be adapted to the DCG.

15

Page 16: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Ability to provide ancillary services such as:

o Frequency support

o Fault Ride Through capability

o Fast voltage support

• critical for operation of weak AC networks such as offshore wind farms, but also essential to aid recovery of the AC grids from AC faults. In addition, this feature has the potential to improve utilization of the AC power network in terms of increased steady-state and transient stability limits, and loss minimization.

o Fast power run-back and run-up

• This feature could be exploited during AC network faults or loss of major generation or load to minimize or eliminate active power mismatch (provide retarding power) to limit rotor acceleration of the generators. Also it can be used to provide fast acting frequency support to AC networks.

o Black start capability

• This feature could be used to eliminate the need for an offshore start-up generator or STATCOM, hence reduces cost. It could be used to restore the power to the AC grid following a blackout, and in general to supply passive AC networks.

16

HVDC converters: potential requirements (I)

Page 17: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

HVDC converters: potential requirements (II)

•Power flow control, including:

oControl of power exchange between the mainland AC grids

oDC power management:

• this may include fast power reversal in some terminals in order to achieve specific objectives such as addressing loop flow and congestion in nearby AC network sections, minimizing total power loss in AC/DC corridors, and redirecting DC power to minimize the loss of power in-feed during a fault in a section of the DC grid.

•Resilience to AC and DC network faults: this is essential in order to ensure overall system stability during major AC and DC network disturbances.

17

Page 18: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

GRID CODE REQUIREMENTS

18

Page 19: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

HVDC converters: what do grid codesrequire?

• Requirements to HVDC converters are set by:

oENTSO-E Grid code (GC)

oNational Grid (UK) Grid code

• The focus will be on:

oFrequency support

oVoltage/reactive powersupport

oFault Ride Through Capability

19

DC converters to whichGC requirements apply

Title II of GC Title III of GC

Page 20: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Frequency support requirements

Both grid codes identify two main control modes:

oFrequency sensitive mode: in case of over- / under-frequencies within a limited frequency range

oLimited Frequency Sensitive Mode: in case of over- / under-frequencies for larger frequency excursions

20

Page 21: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Frequency Sensitive Mode for HVDC converters

21

ENTSO-E solution for FSM:Different droops for over- /and under-frequencies

Limitation of the FSM contribution for bothhigh and lowfrequencies

Parameters IntervalsFrequency response range 0-+/-500 mHzDroop s1 (upward regulation) >= 0,1%Droop s2 (downward regulation) >= 0,1%Frequency insensibility deadband Max 30 mHz

Page 22: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Frequency Sensitive Mode for HVDC converters

22

UK National Grid solution for FSM:different droopsfor over and under frequencies

LFSM applies

Page 23: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Limited Frequency Sensitive Mode for HVDC converters

23

LFSM – O: f1 freq. Threshold between50.2 Hz and 50.5 Hz a droopS3 which can be set equal or higher than 0,1%;

LFSM – U:f2 freq. Threshold between49.8 Hz and 49.5 Hz a droopS4 which can be set equalor higher than 0,1%;

ENTSO-E solution for LFSM:

Page 24: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Limited Frequency Sensitive Mode for HVDC converters

24

NG (UK) solution for LFSM:for over-frequencies2% power reduction foreach 0.1 Hz above 50.4 Hz in Inverter mode

Inverter mode (power intoGB)

Rectifier mode (power from GB)

Page 25: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Voltage Support Requirements

Both GCs identify threemodes of control for DC converters:

o Constant Q

o Constant power factor

o Vac-Q droop

• Vac setpoint in the range +/-5% of nominal value

• 90% of Q variationwithin t1 = 0.1-10s

• Settling time within1 - 60 seconds

25

Page 26: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

FRT requirements for HVDC converters

26

U [p.u.]

1

Urec2

Urec1

Ublock

Uret

Voltage parameters [pu] Time parameters [s]Uret 0.00-0.30 tclear 0.14-0.25Urec1 0.25-0.85 trec1 1.5-2.5Urec2 0.85-0.90 trec2 trec1-10.0

Time-voltage curve = lower limit of time-voltage profile during and afterfault clearance

U = ratio «actual voltage/pre-fault voltage»

Blocking = remaining connected with ZERO active and reactive powers

0 tclear trec1 trec2

Page 27: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Offshore DC connected wind parks: whatdo grid codes require?

• Requirements for DC connected wind parks are reported in Articles 20 thru 22 of «Network code on requirements for grid connection of generators» (latest update April 2016)

• Main focus on:

oFrequency support

oVoltage support

oFault ride through capability

27

Page 28: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

DC connected parks: «f» requirements

Frequency support requirements for ratings > 50 MW:

oLFSM-O (2-12% droop, deadband 0.2-0.5 Hz)

oLFSM-U (feasible in case of deloaded operation)

oFSM

28

Parameters FSM Intervals

Power range in % of maximumcapacity

1.5-10 %

Droop 2-12%Frequency responseinsensitivity

10-30 mHz

Frequency response range 0-500 mHzMax initial delay t1 2 sMax time for full activation t2 30 s

Page 29: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

DC connected parks: «v/Q» requirements

29

Three modes:Q control

Power factor control

Voltage control: 2-7% droopwith a Vac setpoint whichcan be set within 0.95 and 1.05 p.u.

Page 30: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

DC connected parks: FRT requirements

30

Main differences between ENTSO-E and UK grid codes in on-fault responserequired to WT’s:For ENTSO-E grid code, priority must be given to reactive power support (thus, active power can go to zero in «on-fault period»)In UK grid code, in «on-fault» period the WT must deliver at least an activepower proportional to residual voltage

Page 31: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

HVDC converters for MTDC grids: modeling framework

31

Offshore WTsOffshore VSCsOnshore VSCs

MTDC grid

Reference gridcode: UK National Grid code because it’sused to set KPIsin Demo 1 in Best EU FP7 Paths Project

Page 32: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

32

MODELS

Page 33: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Control models for HVDC converters: grid code compliance• Focus on VSCs

• In the proposed modeling framework, VSC links are endowed with:

o«Basic» controllers, which control some operatingquantities of interest (P, Vac, Vdc, Q)

oGrid code compliance controllers, which allow the localcontrollers to fulfill GC requirements in terms of reactivepower and frequency support. They act on the setpoints of P and Q sent to local controllers

33

VSC «basic»controllers

GRID CODE COMPLIANCE

controllersQref

Pref

Page 34: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Basic controllers• Based on Park‟s transformation

oTwo cascaded PI‟s for each control channel

oCurrent limitation with d-axis or q-axis priority

• Allowing independent control of two operatingquantitites (e.g. P/Q, P/Vac, Vdc/Q, Vdc/Vac)

34

FRAME Control Q-Vdc_GC_GridCode_pm:

Q controlElmDsl*

0

1

VdcN*

VdcP*

VdcPdro..*

0

1

2

3

Curren..ElmDsl..

0

1

2

3

0

1

Idc measStaImea*

P-Q measStaPqmea*

0

1

transformation phase..ElmDsl*

iq

0

1

2

3

0

1

PLLElmPhi*

0

1

VSC-1ElmVsc*

0

1

2

3

0

1

Vac measStaVmea*

0

1

Vdc Control*

0

1

2

3

0

1

4

FRAME Control Q-Vdc_GC_GridCode_pm:

1

0

Vdc_r..Vdcm

p

Vdc

p

Qref

Pref Pmq

Pmd

idiq

Idc

idref

iqrefQ

ui

ud

ur

sinref

cosre..

DIg

SIL

EN

T

d axis channel

q axis channel

Pref and Qref setpointscoming from GC controller!!

Page 35: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

DC voltage controllability on MTDC network

• Only one VSC controlling DC voltage in MTDC grid is veryrisky:

o Losing this VSC means losingDC voltage controllability

• To share voltage control, two alternatives are proposed:

o Voltage margin control (adequate for DC grids with few terminals)

o Voltage droop control applied to onshore VSCs!

35

Linear relationship between DC voltage and P flowing through the onshore VSC:V = Vref + k (P - Pref)

P>0 when injected into AC system

Page 36: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Grid Compliance (GC) Control Block

• Establishes the corresponding active and reactive power references of the associated HVDC terminal in order to satisfy grid connection requirements established by Grid Code in terms of active-reactive control and Low Voltage Ride Trough (LVRT).

• The GC controller is divided in two parts:

1. active power/frequency controller,

2. reactive power/AC voltage controller

•Models developed both in MATLAB/Simulink and in DigSILENT PowerFactory

36

Page 37: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

-

Iq_ref+

Qmeas

ΣQref

-Vdc_meas

Pref

Pmeas

Id_refPref0

-PIΣ

Kvdc_p

PI

Vdc_ref

Σ

Σ

+

+

+

Σ

Σ

I

Pmeas

ΔPint

Pref0

Pref_gc

ΔPFSM

ΔPLFSM

Pref’

Pmeas

Pref_ext

fmeas

fmeas

PFref

PmeasQref_PF

Qext

Qvac_droopVac_meas

Qref_gc

Qmode_selector

FSM

LFSM

Pcompensation

Plimiter

Integral Block

VAC DROOP

PFcalc

-

GC compliance controller applied to P-Q Terminal (with Vdc-P droop)

VSC CONTROLLER

GC CONTROLLER

OR

P>0 if power imported from AC system(Rectifier mode)

Source: Technalia within Best Paths

Page 38: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Iq_ref

-

+

Qmeas

ΣQref

-Pmeas

Vdc_ref

Vdc_meas

Id_refVdc_ref0

-PIΣ

PI

Vdc_ref0 Σ

Σ

+

+

+

+

PrefKp_vdc

Σ

Σ

Σ

I

Pmeas

ΔPint

Pref0

Pref_gc

ΔPFSM

ΔPLFSM

Pref’

Pmeas

Pref_ext

fmeas

fmeas

PFref

PmeasQref_PF

Qext

Qvac_droopVac_meas

Qref_gc

Qmode_selector

FSM

LFSM

Pcompensation

Plimiter

Integral Block

VAC DROOP

PFcalc

-

GC CONTROLLER APPLIED TO Vdc-Q Terminal (with P-Vdc droop)

VSC CONTROLLER

GC CONTROLLER

OR

P>0 if power imported from AC system(Rectifier mode)

Source: Technalia within Best Paths

Page 39: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Frequency controller: why?• Simulates both FSM and LFSM modes

o LFSM must be always enabled but only acts when frequency goes beyond a certain range depending on if the terminal is working in rectifier or inverter mode. In rectifier mode, terminal only must limit power extracted from grid in case of low frequency (<49.5Hz), while in inverter mode power yielded to the grid must be only limited in case of high-frequency (>50.4Hz).

o When selected FSM mode, the DC Converter Station must adjust the active power output in response to any frequency change (within the range 49.5 Hz to 50.5 Hz) according to the configured droop characteristic. When the system frequency moves outside the interval [49.5 Hz, 50.5 Hz] the requirements of LFSM apply.

• Final Active power reference of a terminal is calculated adding up the contributions of several controllers, among which the GC controller

o in case of P/Q Terminal, the output of the GC controller is considered as the active power reference of the terminal only when no P-Vdc droop control is enabled.

o if a P-Vdc droop control is activated, the output of the GC control block is modified by the P-Vdc droop control loop and cannot be considered anymore as the active power reference. In this case, the active power reference is calculated through the addition of the P-Vdc control output plus the GC control output.

o for Vdc/Q terminals, the output of the GC controller is only used if the Vdc-P droop control is enabled to modify the nominal voltage reference in case of power deviation.

39

Page 40: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

40Source: Technalia within Best Paths

GC compliance controller: MATLAB/Simulink insight

Page 41: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Integral control inside GC controller• Active power set by the converter not only depends on the reference

established by GC Block but also on droop controls included for ensuring DC grid stability.

o This means that the minimum change in the active power required by the grid code might not be satisfied because it can be modified by the droop controllers.

• For solving this issue an integral loop is added at the frequency controller output. The integral controller ensures that, no matter the droop controllers used, the minimum required change on the active power established by the grid code is achieved. Therefore, the power reference will be modified as follows:

Pref_GC_mod = Pref_GC + ΔPIntegral

• This integral control must include some limitations to ensure correct performance. Integral control acts without limits if the active power change registered is less than the required one. In reverse, the integral term will try to adjust exactly the desired active power change but it will be saturated at Pref_GC_mod = Pref_GC.

o if two terminals are trying to change active power in the same direction but with a different magnitude, the objective is to reach the biggest change.

41

Page 42: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Integral control inside GC controller

42

P>0 if power imported from AC system (Rectifier mode)

Enabled only in LFSM mode, where the frequency changes against which the terminals have to react are in opposite direction in the rectifier and inverter stations (the inverters have to react to over-frequencies while rectifiers have to react to under-frequencies)

Source: Technaliawithin Best Paths

Page 43: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

GC compliance controller: DigSILENTModel

43

GridCode_freqVoltageReg:

PQmeas*

0

1

Qregulator*

0

1

2

3

f req_reg*

0

1

Vmeas_ac*

Fmeasure*

GridCode_freqVoltageReg:

0

11Qref

p

q

us

Preff req

DIg

SIL

EN

T

Pref and Qref setpointsmodified by GC controller to be sent to basic controllers

Pref and Qref setpointsmodified by GC controller to be sent to basic controllers

Page 44: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Frequency support control in GC Controller: DIgSILENT model

44

Controller for frequencysupport

Freq_reg_GridCode:

checkVac_forR..Ublock_regf

Pcompensation0

1

2

ratioPmaxSbRC,Sb

ConstC2

dead band LFS..dLFSM_HF,dLFS..

0

1

ratioSbPmaxRC,Sb

ratioSbPmaxRC,Sb

limit..0

1

regP_activati..

0

1 0

1

2

Limits_FS..Flim_FSM_..

ConstC1

KK

gain

_in

t

Constenabling_FSM

KKco

nve

nzi

one

KKconvenzione

KKconvenzione

and_nand_acti..0

1

KKgain_int -

Limiter sig2

P_max

P_min

K/sKuno

--

swtchcedparam..K_HF_LFSM,K_L..

LFSM_activati..dLFSM_LF,dLFS..

0

1

swtchcedparam..K_HF_FSM,K_LF..

semiDBanddb_FSM-

Freq_reg_GridCode:

0

1

2

3

4o17us

o16

o3

o2

o1

Pref

yi7

o10

y i11pref 0

y i9p

Pref_ctrpre_f..dP_FSM

o5

o14

o13

y i6

y i2

o15

pre

f

inp1

yhigh

y low

o6

o12

o11

o9

y i5

y i4o8 o7 y i3o4y i1inp

y i

f ref

f req

DIg

SIL

EN

T

Able to simulate:FSM (Frequency Sensitive Mode)LFSM (Limited FrequencySensitive Mode)

A blocking signal may set Pref to zero in case of toolow AC voltages

Page 45: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Voltage/Reactive Power Controller: DIgSILENT model

45

Controller for reactivepower support

Potential control modes: Constant power

factor Constant Q Vac-Q droop

A blocking signal may set Qref to zero in case of too low AC voltages

Qreq_reg_GridCode:

Constenabling_Vctrl

logic or0

1LVRT_V

lvrt

-

DBanddb_vlrt

selettore_LVRTKvac_droop_up,Kvac_droop_down

Constenabling_Qctrl

Constenabling_PFctrl

log

ic n

ot

logic and0

1

logic and0

1

fromPFtoratio

end

Qreq_reg_GridCode:

2

3

4

6

8

7

9

00

5

Vctrl_sig

Vctrl_enabl

uref

err_uus err_u_db

Qc

trl_

sig

PFctrl_sig

LVRTtrigo

utp

Qctrl_enabl

Qref

PF

ou

t

qset

PFenabl

ratio

p

PFref

Qo

ut

Vo

ut

qre

q

DIg

SIL

EN

T

Page 46: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

How does the Frequency controller work?

46

Terminal Pref_GC(pu) Pdc (pu) Vdc ΔPdc (pu)

T1 (Rectifier) 0.5 0.625 0.995 -0.375

T2 (Inverter) -0.75 -0.625 0.995 +0.375

Terminal Pref0 (pu) Vdc_ref Kf Kvdc Δf (pu) ΔPdc (pu)

T1 (Rectifier) 1 1 0,04 25 -0,02 <=-0,50

T2 (Inverter) -1 1 0,04 25 0,01 >=0,25

T1 T2with no integral control (only Kf droop action)

this operation point does not fulfill the active power change required for terminal T1 (<=-0,5 see Table above)!

Frequency shifts imposed

with integral control

0.5 achieved!

ΔPintegral (pu)= -0.5+0.25=-0.25!Pdc = Pref0+∆f/Kf +Kvdc (Vdc_ref-Vdc)

Page 47: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

How does the Frequency controller work?

47

Terminal Pref_GC(pu) Pdc (pu) Vdc ΔPdc (pu)

T1 (Rectifier) 0.5 0.625 0.995 -0.375

T2 (Inverter) -0.75 -0.625 0.995 +0.375

Terminal Pref0 (pu) Vdc_ref Kf Kvdc Δf (pu) ΔPdc (pu)

T1 (Rectifier) 1 1 0,04 25 -0,02 <=-0,50

T2 (Inverter) -1 1 0,04 25 0,01 >=0,25

T1 T2with no integral control (only Kf droop action)

this operation point does not fulfill the active power change required for terminal T1 (<=-0,5 see Table above)!

Frequency shifts imposed

If f1 recovers up to f1=0.995pu ….

T1 saturates !

Action of T2 integral control!

with integral control

Pdc = Pref0+∆f/Kf +Kvdc (Vdc_ref-Vdc)

Page 48: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Control scheme of MTDC grid for offshore wind parks for providing frequency support

48

Rationale: to translatefrequency deviation in onshore AC systems intovariations of frequency in offshore islands exploiting the variations of DC voltage on MTDC grid

Communication free control architectureExploits:• FSM of onshore VSCs• Freq-Vdc dependence in

offshore VSC control• FSM of WTs

Page 49: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

VSC controls to enableancillary service provision

• WTs endowed with LFSM and FSM (this is feasible in case of deloaded operation)

• Basic onshore VSC controls: P-Vdc control with P-f dependence(FSM or LFSM for larger variations)

• Basic offshore VSC control: |V|/f control,

o by controlling d-axis and q-axis components of AC voltage

o still Park‟s transf. based scheme with current limitation in case of offshore AC faults

o Dependence between DC voltage and offshore frequency (a deadbandis added to avoid triggering offshore frequency variations due to DC voltage oscillations caused by wind power fluctuations)

49

dfKPPKuu FSMrefvdcPdcrefdcref 00

df = fref – f – dbFSM sign(fref-f) for |fref - f| > dbFSM and df = 0 for |fref - f| < dbFSM.

0_0__ dcdcfvdcrefoffrefoff uuKff

Page 50: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Example of MTDC grid providingfrequency support

50

10.08.006.004.002.000.00 [s]

50.115

50.090

50.065

50.040

50.015

49.990

KAS\KAS_400_S1: onshore AC freq., Hz

FSM_WF: offshore AC island freq., Hz

10.08.006.004.002.000.00 [s]

0.95

0.93

0.91

0.89

0.87

0.85

[-]

Dr_ONSH1: P onshore VSC1, p.u.

Dr_ONSH1: Pref onshore VSC 1, p.u.

10.08.006.004.002.000.00 [s]

1.0520

1.0515

1.0510

1.0505

1.0500

1.0495

[-]

Dr_ONSH1: Vdc onshore VSC1, p.u.

Dr_ONSH1: Vdcref onshore VSC1, p.u.

10.08.006.004.002.000.00 [s]

-721.50

-724.00

-726.50

-729.00

-731.50

-734.00

[MW]

VScoffshore1: P output, MW

DIg

SIL

EN

T

Study case: Six-terminal «tree-like» MTDC grid connectedto a real-world AC system

Loss of a very large power export (about1700 MW)

Same curve for onshore/offshore VSC #2 and 3

Onshore Frequency

Offshore Frequency

DC voltage increase

Offshore WFsreduce theiroutputs

Page 51: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

FRT of a MTDC grid for the integration of offshore wind parks

• Onshore AC faults cause a drastic drop of active ower output

a large power unbalance on DC grid

overvoltages which may become unacceptable for DC components

• To limit DC voltage two alternatives are possible:

o Locating a lumped chopper controlled resistor on the DC side of onshoreVSCs

o Using decentralized choppers on the DC links of WTs

• Offshore AC faults:

o Current limitation in offshore VSC control is required to reduce itscontribution to the fault

o Fulfill FRT requirements for WTs

51

Page 52: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Chopper-based solution to enable FRT

52

MT- HVDC

NetworkVDC

Offshore VSC

VAC

VminFRT

KWT DC

resistor

DC Chopper

VDCref

VD

C

time

VACref

VA

C

time

WGSVSC

AC

offs

ho

re

ne

two

rk

VFRT

chop

VDCref

VDC

KDC/AC

VACref

VAC

GSVSC

VAC

VDC

MT- HVDC

Network

...

...

VDC

VDCmax

Kchop DC

resistor

Onshore VSC

DC Chopper

0

Pmax

Dead-band

From: TWENTIES Project

Page 53: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

MTDC grid response to onshoreAC faults

53

• Study case: Six-terminal «tree-like» MTDC grid connected to a real-world AC system

• Assuming «lumped» DC chopper on all the DC sides of onshore VSCs

• AC fault close to AC terminal of onshore VSC #3

2,001,601,200,800,400,00 [s]

200,00

150,00

100,00

50,00

0,00

-50,00

[MW]

Chopper resistor: Active power, MW

Chopper resistor2: Active power, MW

Chopper resistor3: Active power, MW

2,001,601,200,800,400,00 [s]

-728,00

-729,00

-730,00

-731,00

-732,00

-733,00

[MW]

VScoffshore1: Active power, MW

VScoffshore2: Active power, MW

VScoffshore3: Active power, MW

2,001,601,200,800,400,00 [s]

1,19

1,15

1,11

1,07

1,03

0,99

udc1: Vdc for onshore VSC 1, p.u.

udc2: Vdc for onshore VSC 2, p.u.

udc3: Vdc for onshore VSC 3, p.u.

Vdc_droopONSH1: Vref of VSC 1, p.u.

Vdc_droopONSH2: Vref of VSC 2, p.u.

Vdc_droopONSH3: Vref of VSC 3, p.u.

2,001,601,200,800,400,00 [s]

1,25

1,00

0,75

0,50

0,25

0,00

[-]

Vdc_droopONSH1: P of VSC 1, p.u.

Vdc_droopONSH1: Pref of VSC 1, p.u.

Vdc_droopONSH2: P of VSC 2, p.u.

Vdc_droopONSH2: Pref of VSC 2, p.u.

Vdc_droopONSH3: P of VSC 3, p.u.

Vdc_droopONSH3: Pref of VSC 3, p.u.

DIg

SIL

EN

T

DC voltage islimited at 1.15 p.u.

Choppers #1 2 and 3 intervene!

Active power dropat AC terminal of onshore VSC #3

WF slight reduction due to f-Vdc dependence in offshore VSC control and LFSM mode on WTs

Page 54: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Wind turbine power responsein case of offshore AC faults

54

ENTSO-E GC: priority to reactive powersupport, P goesto zero in «on fault» period

UK National Grid GC: activepowerproportional to residual voltage

1.000.800.600.400.200.00 [s]

1.50

1.00

0.50

0.00

-0.50

-1.00

PQ controller UK: Q output

PQ controller UK: iqr

PQ controller UK: u

PQ controller UK: limited iqr

0.212 s 0.537

1.000.800.600.400.200.00 [s]

1.30

1.10

0.90

0.70

0.50

0.30

PQ controller UK: P output

PQ controller UK: idr

PQ controller UK: idrf_max

PQ controller UK: idrf_min

PQ controller UK: limited idr

0.212 s 0.537

DIg

SIL

EN

T

Page 55: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Bibliography (1)•Grid CodesoNational Grid, «The Grid Code», latest update March 2017oENTSO-E, «Network code on requirements for grid connection of high

voltage direct current systems and direct current-connected power park modules», latest update August 2016

•Papers on HVDC modeling:oS. I. Nanou, G. N. Patsakis, and S. A. Papathanassiou, “Assessment of

communication-independent grid code compatibility solutions for VSC–HVDC connected offshore wind farms,” Electr. Power Syst. Res., vol. 121, pp. 38–51, Apr. 2015.

oC. Feltes, H. Wrede, F. W. Koch, and I. Erlich, “Enhanced Fault Ride-Through Method for Wind Farms Connected to the Grid Through VSC-Based HVDC Transmission,” IEEE Trans. Power Syst., vol. 24, no. 3, pp. 1537–1546, Aug. 2009.

oE. Ciapessoni, D. Cirio, A. Gatti, A. Pitto, A. M. Denis, O. Despouys, Y. Phulpin, L. He, C.-C. Liu, C. Moreira, B. Silva, “Dynamics and control of Multi-Terminal High Voltage Direct Current networks for integration of large offshore wind parks into AC grids”, paper C4-102, CIGRE Session, Paris, Aug 2012. 55

Page 56: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Bibliography (2)

Papers on HVDC modeling:oE. Ciapessoni, D. Cirio, A. Gatti, A. Pitto, A. M. Denis, L. He, C.-C. Liu, C.

Moreira, B. Silva, “Impact of multi-terminal HVDC grids on AC system stability and operation”, 2014 CIGRE Session, Paris, Aug „14.

oC. E. Ugalde-Loo et al. “Open access simulation toolbox for the grid connection of offshore wind farms using multi-terminal HVDC networks”, AC/DC UK conf., Manchester, Feb 14-16, 2017.

oE. Ciapessoni, D. Cirio, A. Gatti, A. Pitto, M. Rapizza, I. Azpiri Irazabal, P. Lund, J. Glasdam, “Assessing the impact of Multi-terminal HVDC grids for wind integration on future scenarios of a real-world AC power system using Grid Code compliant open models”, Powertech 2017, Manchester, UK, June 2017.

oB Silva, C.L. Moreira, L. Seca, Y Phulpin, J.A. Peças Lopes, “Provision of inertial and primary frequency control services using offshore multiterminal HVDC networks”, IEEE Trans. on Sustainable Energy, Vol. 3, no. 4, pp. 800-808, Oct 2012.

oB. Silva, C. Moreira, H. Leite, J.A. Peças Lopes, “Control Strategies for AC Fault Ride-Through in Multi-terminal HVDC Grids”, IEEE Transactions on Power Delivery, vol.29, no.1, pp.395,405, Feb. 2014.

56

Page 57: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Conclusions (1)

• Control functions of MTDC grid converters and WFs, compliant with GC requirements

• Models mainly address the aspects of FRT, ancillaryservice provision

oOther topics may be tackled e.g. requirements concerningprotection, restoration etc.

• Further work consists in tuning the available open models to match the response of «black box» modelsprovided by manufacturers

57

Page 58: Control of HVDC grid converters and offshore wind farms ... · HVDC grid topologies •Point to point grids o Low reliability and flexibility •Tree-like (backbone) grids o Possible

Many of the presented models have been developed in the context of Demo 1 of the EU FP7 Project Best Paths

A library of open models is available on the website:

http://www.bestpaths-project.eu/

Attend the Demo 1 presentation at the Workshop!

For any information, feel free to contact me!

Dr. Andrea Pitto – Email: [email protected]

58