Control Device Technology Barrett Parker, EPA, OAQPS.
-
Upload
baldwin-long -
Category
Documents
-
view
219 -
download
0
Transcript of Control Device Technology Barrett Parker, EPA, OAQPS.
![Page 1: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/1.jpg)
Control Device Technology
Barrett Parker, EPA, OAQPS
![Page 2: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/2.jpg)
Example Control Systems
4 VOC control techniques plus capture discussion
5 PM control techniques
2 Acid gas control techniques
3 NOx control techniques
![Page 3: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/3.jpg)
VOC Control Techniques – Carbon Adsorber
General description– Gas molecules stick to the surface of a solid– Activated carbon often used as it
Has a strong attraction for organics Has a large capacity for adsorption (many pores) Is cheap
– Silica gel, activated alumina, and zeolites are also used
![Page 4: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/4.jpg)
VOC Control Techniques – Carbon Adsorber
General description (continued)– 3 types – fixed bed (most common), moving
bed, and fluidized bed– Typically appear in pairs – one adsorbing
while other desorbs– Used for control as well as recovery– Regenerated via steam, hot gas, or vacuum– Work best if molecular weight of compound
between 50 and 200
![Page 5: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/5.jpg)
VOC Control Techniques – Carbon Adsorber – Fixed Bed Schematic
![Page 6: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/6.jpg)
VOC Control Techniques – Carbon Adsorber – Fixed Bed Examples
![Page 7: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/7.jpg)
VOC Control Techniques – Carbon Adsorber
Factors affecting efficiency– Presence, polarity, and concentration of
specific compounds– Flow rate– Temperature– Relative humidity
![Page 8: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/8.jpg)
VOC Control Techniques – Carbon Adsorber
Performance indicators– Outlet VOC concentration– Regeneration cycle timing or bed
replacement frequency– Total regeneration stream flow or vacuum
profile during regeneration cycle– Carbon bed activity – Bed operating and regeneration
temperature
![Page 9: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/9.jpg)
VOC Control Techniques – Carbon Adsorber
Performance indicators (continued)– Inlet gas temperature– Gas flow rate– Inlet VOC concentration– Pressure differential– Inlet gas moisture content– Leaks
![Page 10: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/10.jpg)
VOC Control Techniques – Carbon Adsorber – Manufacturer’s Specs
![Page 11: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/11.jpg)
VOC Control Techniques – Catalytic Oxidizer
General description– Waste gas gets oxidized to water and
carbon dioxide – Catalyst causes reaction to occur faster and
at lower temperatures– Saves auxiliary fuel
![Page 12: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/12.jpg)
VOC Control Techniques – Catalytic Oxidizer
General description (continued)– Catalysts allow lower operation temperatures
(~ 650 to 1000°F)– Catalyst bed generally lasts from 2 to 5 years
Thermal aging, poisoning, and masking are concerns
– Excess air is added to assist combustion Residence time and mixing are fixed during design Only temperature and oxygen can be controlled
after construction
![Page 13: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/13.jpg)
VOC Control Techniques – Catalytic Oxidizer – Example Bricks
![Page 14: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/14.jpg)
VOC Control Techniques – Catalytic Oxidizer - Schematic
![Page 15: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/15.jpg)
VOC Control Techniques – Catalytic Oxidizer
Factors affecting efficiency– Pollutant concentration– Flow rate– Operating temperature– Excess air– Waste stream contaminants
Metals, sulfur, halogens, plastics
![Page 16: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/16.jpg)
VOC Control Techniques – Catalytic Oxidizer
Performance Indicators– Outlet VOC concentration– Catalyst bed inlet temperature– Catalyst activity– Outlet CO concentration– Temperature rise across catalyst bed– Exhaust gas flow rate
![Page 17: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/17.jpg)
VOC Control Techniques – Catalytic Oxidizer
Performance Indicators (continued)– Catalyst bed outlet temperature– Fan current– Outlet O2 or CO2 concentration
– Pressure differential across catalyst bed
![Page 18: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/18.jpg)
VOC Control Techniques - Condenser
General description – Gas or vapor turns to liquid via
Lowering temperature or Increasing pressure
– Used as pretreatment to reduce volumes– Used to collect and reuse some solvents
![Page 19: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/19.jpg)
VOC Control Techniques - Condenser
General description (continued)– Two types – contact and surface
condensers No secondary pollutants from surface type More coolant needed for contact type
– Chilled water, brines, and CFCs used as coolants
– Efficiencies range from 50 to 95 percent
![Page 20: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/20.jpg)
VOC Control Techniques – Condenser - Schematic
![Page 21: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/21.jpg)
VOC Control Techniques - Condenser
Factors affecting efficiency– Pollutant dew point– Condenser operating pressure– Gas and coolant flow rates– Tube plugging or fouling
![Page 22: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/22.jpg)
VOC Control Techniques - Condenser
Performance indicators– Outlet VOC concentration– Outlet gas temperature– Coolant inlet temperature– Coolant outlet temperature– Exhaust gas flow rate– Pressure differential across condenser
![Page 23: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/23.jpg)
VOC Control Techniques - Condenser
Performance indicators (continued)– Coolant flow rate– Pressure differential across coolant
refrigeration system– Condensate collection rate– Inspection for fouling or corrosion
![Page 24: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/24.jpg)
VOC Control Techniques – Thermal Oxidizer
General description– Waste gas turns to carbon dioxide and water– Operating temperatures between 800 and
2000°F– Good combustion requires
Adequate temperature Turbulent mixing of waste gas with oxygen Sufficient time for reactions to occur Enough oxygen to completely combust waste gas
![Page 25: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/25.jpg)
VOC Control Techniques – Thermal Oxidizer
General description (continued)– Only temperature and oxygen concentration
can be controlled after construction– Waste gas has to be heated to autoignition
temperature Typically requires auxiliary fuel
– Common design relies on 0.2 to 2 seconds residence time, 2 to 3 length to diameter ratio, and gas velocity of 10 to 50 feet per second
![Page 26: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/26.jpg)
VOC Control Techniques – Thermal Oxidizer - Schematic
![Page 27: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/27.jpg)
VOC Control Techniques – Thermal Oxidizer
Factors affecting efficiency– Waste gas flow rate– Waste gas composition and concentration– Waste gas temperature– Amount of excess air
![Page 28: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/28.jpg)
VOC Control Techniques – Thermal Oxidizer
Performance indicators– Outlet VOC concentration– Outlet combustion temperature– Outlet CO concentration– Exhaust gas flow rate– Fan current– Outlet O2 or CO2 concentration– Inspections
![Page 29: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/29.jpg)
VOC Control Techniques – Capture System
General description– Total efficiency is product of capture and
control device efficiencies– Two types of systems
Enclosures and local exhausts (hoods)
– Two types of enclosures Permanent total (M204) – 100% capture efficiency Nontotal or partial – must measure capture
efficiency
![Page 30: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/30.jpg)
VOC Control Techniques – Capture System - Schematic
![Page 31: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/31.jpg)
VOC Control Techniques – Capture System
Factors affecting efficiency– System integrity– System flow
![Page 32: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/32.jpg)
VOC Control Techniques – Capture Systems
Performance indicators– Enclosures
Face velocity Differential pressure Average face velocity and daily inspections
– Exhaust Ventilation Face velocity Exhaust flow rate in duct near hood Hood static pressure
![Page 33: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/33.jpg)
PM Control Techniqes - Cyclone
General description– Particles hit wall sides and fall out– Often used as precleaners
Especially effective for particles larger than 20 microns
– Inexpensive to build and operate– Can be combined in series or parallel
![Page 34: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/34.jpg)
PM Control Techniques – Cyclone - Schematic
![Page 35: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/35.jpg)
PM Control Techniques - Cyclone
Factors affecting efficiency– Component erosion– Inlet and outlet plugging– Acid gas corrosion– Air inleakage
![Page 36: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/36.jpg)
PM Control Techniques - Cyclone
Performance indicators– Opacity– Inlet velocity or inlet gas flow rate– Pressure differential– Inlet temperature
![Page 37: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/37.jpg)
PM Control Techniques – Electrostatic Precipitator
General Description– Charged particles are attracted to plates
and removed from exhaust gas– Two types
Dry type use mechanical action to clean plates Wet type use water to prequench and to rinse
plates– High voltages are required– Multiple sections (fields) may be used– Efficiencies up to 99% can be obtained
![Page 38: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/38.jpg)
PM Control Techniques – Electrostatic Precipitator - Schematic
![Page 39: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/39.jpg)
PM Control Techniques – Electrostatic Precipitator - Schematic
![Page 40: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/40.jpg)
PM Control Techniques – Electrostatic Precipitators
Factors affecting efficiency– Gas temperature, humidity, flow rate– Particle resistivity– Fly ash composition– Plate length– Surface area
![Page 41: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/41.jpg)
PM Control Techniques – Electrostatic Precipitator
Performance indicators– Outlet PM concentration– Opacity– Secondary corona power (current and
voltage)– Spark rate– Primary power (current and voltage)
![Page 42: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/42.jpg)
PM Control Techniques – Electrostatic Precipitator
Performance indicators (continued)– Inlet gas temperature– Gas flow rate– Rapper operation– Fields in operation– Inlet water flow rate (wet type)– Flush water solids content (wet type)
![Page 43: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/43.jpg)
PM Control Techniques – Electrified Filter Bed
General description– Charged particles are deposited on pea
gravel– Three parts
Ionizer system Filter bed Gravel cleaning and recirculation system
![Page 44: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/44.jpg)
PM Control Techniques – Electrified Filter Bed - Schematic
![Page 45: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/45.jpg)
PM Control Techniques – Electrified Filter Bed
Factors affecting efficiency– Glaze build up on ionizer or gravel– Temperature
Performance indicators– Ionizer voltage and current– Filter bed voltage, current, and
temperature– Inlet gas temperature
![Page 46: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/46.jpg)
PM Control Techniques – Electrified Filter Bed
Performance indicators (continued)– Pressure differential– Gas flow rate– Outlet PM concentration– Opacity
![Page 47: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/47.jpg)
PM Control Techniques – Fabric Filter
General description– Particles trapped on filter media, then
removed– Either interior or exterior filtration systems– Up to 99.9% efficiency– 4 types of cleaning systems
Shaker (off-line) Reverse air (low pressure, long time, off line) Pulse jet (60 to 120 psi air, on line) Sonic horn (150 to 550 Hz @ 120 to 140 dB, on line)
![Page 48: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/48.jpg)
PM Control Techniques – Fabric Filter - Schematic
![Page 49: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/49.jpg)
PM Control Techniques – Fabric Filter
Factors affecting efficiency– Filter media
Abrasion High temperature Chemical attack
– Gas flow– Broken or worn bags– Blinding
![Page 50: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/50.jpg)
PM Control Techniques – Fabric Filter
Factors affecting efficiency (continued)– Cleaning system failure– Leaks– Re-entrainment– Damper or discharge equipment
malfunction– Corrosion
![Page 51: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/51.jpg)
PM Control Techniques – Fabric Filter
Performance indicators– Outlet PM concentration– Bag leak detectors– Outlet opacity– Pressure differential– Inlet temperature– Temperature differential
![Page 52: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/52.jpg)
PM Control Techniques – Fabric Filter
Performance indicators (continued)– Exhaust gas flow rate– Cleaning mechanism operation– Fan current– Inspections and maintenance
![Page 53: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/53.jpg)
PM Control Techniques – Wet Scrubber
General description– Particles (and gases) get trapped in liquids
Inertial impaction and diffusion
– Liquids must contact pollutants and dirty liquids must be removed from exhaust gas
– Four types Spray; venturi or orifice; spray rotors; and
moving bed or packed towers
![Page 54: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/54.jpg)
PM Control Techniques – Wet Scrubber - Schematic
![Page 55: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/55.jpg)
PM Control Techniques – Wet Scrubber
Factors affecting efficiency– Gas and liquid flow rate– Condensation of aerosols– Poor liquid distribution– High dissolved solids content in liquid– Nozzle erosion or pluggage– Re-entrainment– Scaling
![Page 56: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/56.jpg)
PM Control Techniques – Wet Scrubber
Performance indicators– Pressure differential– Liquid flow rate– Gas flow rate– Scrubber outlet gas temperature– Makeup / blowdown rates– Scrubber liquid solids content (PM)
![Page 57: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/57.jpg)
PM Control Techniques – Wet Scrubber
Performance indicators (continued)– Scrubber inlet gas and process exhaust gas
temperature (PM)– Scrubber liquid outlet concentration (Acid
gas)– Scrubber liquid pH (Acid gas)– Neutralizing chemical feed rate (Acid gas)– Scrubber liquid specific gravity (Acid gas)
![Page 58: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/58.jpg)
Acid Gas Control Techniques – Dry Injection
General description– Sorbent reacts with gas to form salts that
are removed in a PM control device (fabric filter)
– Hydrated lime and sodium bicarbonate often used as sorbents
![Page 59: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/59.jpg)
Acid Gas Control Techniques – Dry Injection - Schematic
![Page 60: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/60.jpg)
Acid Gas Control Techniques – Dry Injection
Factors affecting efficiency– Dry sorbent injection rate– Emission stream gas temperature– Residence or reaction time– Degree of turbulence– Other PM control device used factors
![Page 61: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/61.jpg)
Acid Gas Control Techniques – Dry Injection
Performance indicators– Outlet acid gas concentration– Sorbent feed rate– Fabric filter inlet temperature– Sorbent carrier gas flow rate– Sorbent / carrier gas nozzle pressure
differential– Sorbent specifications
![Page 62: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/62.jpg)
Acid Gas Control Techniques – Dry Injection
Performance indicators (continued)– Inlet gas / process exhaust temperatures– Exhaust gas flow rate– Other PM control device used indicators
![Page 63: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/63.jpg)
Acid Gas Control Techniques – Spray Dryer
General description– Alkali sorbent slurry turns acid gas into PM
that is collected by a control device– Slurry is usually lime and water
![Page 64: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/64.jpg)
Acid Gas Control Techniques – Spray Dryer - Schematic
![Page 65: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/65.jpg)
Acid Gas Control Techniques – Spray Dryer
Factors affecting efficiency– Slurry feed rate– Residence or reaction time– Emission stream gas temperature– Slurry reactor outlet temperature– Slurry droplet size– Other PM control device used factors
![Page 66: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/66.jpg)
Acid Gas Control Techniques – Spray Dryer
Performance indicators– Outlet acid gas concentration– Alkali feed rate to slurry mix tank– Water feed rate to slurry mix tank– Slurry feed rate and droplet size– Spray dryer inlet gas / process exhaust
temperature– Other PM control device indicators
![Page 67: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/67.jpg)
NOx Control Techniques – Selective Catalytic Reduction
General description– Ammonia or urea is injected into exhaust
streams with plenty of oxygen to reduce nitrogen oxide to nitrogen and oxygen
– Efficiency ranges from 70 to 90 percent– Catalysts made from base and precious
metals and zeolites– Operating temperatures range from 600 to
1100°F
![Page 68: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/68.jpg)
NOx Control Techniques – Selective Catalytic Reduction - Schematic
![Page 69: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/69.jpg)
NOx Control Techniques – Selective Catalytic Reduction
Factors affecting efficiency– Catalyst activity– Masking or poisoning– Space velocity (gas flow rate divided by
bed volume)– Excess ammonia or urea slip
![Page 70: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/70.jpg)
NOx Control Techniques – Selective Catalytic Reduction
Performance indicators– Outlet nitrogen oxide concentration– Ammonia / urea injection rate– Catalyst bed inlet temperature– Catalyst activity– Outlet ammonia / urea concentration– Catalyst bed outlet temperature
![Page 71: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/71.jpg)
NOx Control Techniques – Selective Catalytic Reduction
Performance indicators (continued)– Inlet gas flow rate– Fuel sulfur content– Pressure differential across catalyst bed
![Page 72: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/72.jpg)
NOx Control Techniques – Non Selective Catalytic Reduction
General description– Low oxygen exhaust gas transforms via
catalytic reaction to water, carbon dioxide, and nitrogen
– Catalysts made from noble metals– Efficiency ranges from 80 to 90 percent– Operating temperatures range from 700 to
1500°F
![Page 73: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/73.jpg)
NOx Control Techniques – Non Selective Catalytic Reduction
Factors affecting efficiency– Catalyst activity– Masking or poisoning– Space velocity (gas flow rate divided by
bed volume)– Catalyst material
![Page 74: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/74.jpg)
NOx Control Techniques – Non Selective Catalytic Reduction
Performance indicators– Outlet nitrogen oxide concentration– Catalyst bed inlet temperature– Catalyst activity– Catalyst bed outlet temperature– Inlet gas flow rate– Pressure differential across catalyst bed– Outlet oxygen concentration
![Page 75: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/75.jpg)
NOx Control Techniques – Water or Steam Injection
General description– Water or steam injected in combustion
zone reduces temperature and nitrogen oxide formation
– Only thermal nitrogen oxides reduced– Reductions range from 60 to 80 percent– Water must be atomized
![Page 76: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/76.jpg)
NOx Control Techniques – Water or Steam Injection - Schematic
![Page 77: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/77.jpg)
NOx Control Techniques – Water or Steam Injection
Factors affecting efficiency– Water quality– Quantity of water injected– Combustor design– Combustor materials– Turbine load cycle
![Page 78: Control Device Technology Barrett Parker, EPA, OAQPS.](https://reader030.fdocuments.us/reader030/viewer/2022033104/56649cfa5503460f949ccac8/html5/thumbnails/78.jpg)
NOx Control Techniques – Water or Steam Injection
Performance indicators– Outlet nitrogen oxide concentration– Water to fuel ratio– Fuel bound nitrogen concentration