Rhode Island Convention Center • Providence, Rhode Island Continuous Commissioning at Sandia National Laboratories Session: Why Ongoing Commissioning Can Lead to Better Performing Buildings Jack Mizner Sandia National Laboratories August 10, 2016 Sandia National Laboratories is a multi-program laboratory managed and operated by Sandia Corporation, a wholly owned subsidiary of Lockheed Martin Corporation, for the U.S. Department of Energy’s National Nuclear Security Administration under contract DE-AC04-94AL85000.

Transcript of Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation...

Page 1: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Rhode Island Convention Center • Providence, Rhode Island

Continuous Commissioning at Sandia National Laboratories

Session: Why On‐going Commissioning Can Lead to Better Performing Buildings

Jack MiznerSandia National Laboratories

August 10, 2016Sandia National Laboratories is a multi-program laboratory managed and operated by Sandia Corporation, a wholly owned subsidiary of Lockheed Martin Corporation, for the U.S. Department of Energy’s National Nuclear Security Administration under contract DE-AC04-94AL85000.

Page 2: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Sandia’s Sites

2

Albuquerque, New Mexico Livermore, California

Waste Isolation Pilot Plant,Carlsbad, New Mexico

Kauai, Hawaii Pantex Plant,Amarillo, Texas

Tonopah, Nevada

LEED Buildings: 11 Avg. Bldg. Age: 38 yrs.

Workforce:  >12,000 Major buildings:  225Space:  7.4 million GSF

Physical area :188,000 acres Paved roads: 49 milesUnpaved roads: 38 miles 

Page 3: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade3

Energy Use Breakdown

Electric:  284,410,778 kWh 

Natural gas:  340,278,252 SCF

Total Energy Use:  1,310,730 MBTUs

Total utility costs:  over $19M

Page 4: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

• Building types: – Semi‐conductor fabrication; – Pulsed power reactors; – Data centers; – High security;– Cafeteria; – Auditorium; – Warehouse; – Nuclear facilities– Explosive facilities 

Buildings and Space

• Space types: – Offices– Laboratories:

• chemistry, • biology, • electronic, • laser labs; • computer

– Clean rooms; – High‐bays; – Computer rooms

Page 5: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Energy Audits & Retro‐commissioning

Conduct Audit

Maintenance

Complete Report

CapitalImprovements

Building AutomationSystem

Types of ECMs

UFN

Correct Code

Service Request

Energy & Water Audits 4‐year schedule top Energy 

Consumers Led by Operations team per 

process using checklist ASHRAE Level II

Retro‐commissioning or Energy Conservation Measures (ECM) Identified & implemented per SNL 

Facilities processes

Correct per Maintenance Schedule

Fund based on ROI & Criteria

Load Profile & Energy‐Use Baseline Annual Load Profiles & Energy Use to 

verify savings Energy Models

Facility Management System

ServiceRequest

Page 6: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Energy Data Warehouse

6

SQL Data Warehouse

Analytic  Software

EnergyDashboard

EnergyModeling

R&DOptimization

BASServers

Data TransferServer 

MetersElectric

Natural GasBTU

NM PSEL WeatherSolar

PV Generation

Page 7: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Energy Dashboard

Graphs are displayed in kWh Graphs are displayed in MCF

The average use per day in kWh was The average use per day in MCF was13,018 32.06

Building 701

Electrical Use Awareness Bulletin Gas Use Awareness Bulletin

Building 701

0200000400000600000

kWh

Month

Building 701 Electric Use History

FY15

FY16

0

100,000

200,000

300,000

400,000

500,000

This Month,March 2016

Last Month,February

2016

This MonthLast Year,

March 2015

Building 701 Electric Use

kWh

0.00400.00800.00

1,200.001,600.002,000.00

MC

F

Month

Building 701 Gas Use History

FY15

FY16

0.00

200.00

400.00

600.00

800.00

1,000.00

1,200.00

This Month,March 2016

Last Month,February

2016

This MonthLast Year,

March 2015

Building 701 Gas Use

MCF

Page 8: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

IX Building Module Architecture

2. User Interface ; Create a Scenario

SelectBuildings

SelectECMs/OCMs

3. Run Scenario

Sim

ulat

ion

Eng

ine

Energy savings of one or many ECMs for one or many years by:

• ECM• Building• Building type• Groups of

buildings (TAs)• Site (NM or CA)• Whole lab

Dat

abas

e

SelectYears

Background data such as central plant network information

VBA Wrapper in Microsoft ExcelVBA Wrapper in Microsoft Excel1. Design ECMs and Assemble

Building Models4. View Results

5. Cost Analysis

Building Models

8

EnergyModeling

Page 9: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

eQUEST

EnergyModeling

Page 10: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

IX Software EnergyModeling

Page 11: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Results

IX uses a pivot table of the results database to make reducing to specific results or aggregating to site‐wide results easy.

EnergyModeling

Page 12: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Initiative Savings 

Lighting retrofits 0.5%

Digital Control Conversions

6‐10%Free‐cooling heat exchangers

Central Plant Upgrades

Clean Room modifications (filters and reduced air flow)

12

Energy Saving Opportunities

Energy Conservation Measures Operational Conservation Measures

Initiative Savings 

Office (T Set and Operating hours)

1‐1.5%

Lab (T Set and Operating hours)

3‐7%

Ventilation setback (labs) 2‐3%

Eliminate 24/7 operations 2‐3%

Retro‐commissioning, Analytics

1‐2%

EnergyModeling

Page 13: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Cool Roofs ‐ Percentage Savings

• Site‐wide energy savings for this ECM is only 0.4%

• If cool roof and insulation costs are high, other ECMs may be more desirable  

13

‐0.10%

0.00%

0.10%

0.20%

0.30%

0.40%

0.50%

2012 2017 2022 2027 2032 2037

SNL NM/CA Site‐wide Percent Energy Savings

Optimal

Average of 4 Random Cases

EnergyModeling

Page 14: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Institutional Transformation (IX)

• Parameter studies of many– Buildings– Energy conservation measures (ECM)

– Years

• Climate• Current version 2.5• Future version 3.0 

‐60.0

‐40.0

‐20.0

0.0

20.0

40.0

60.0

80.0

100.0

2020 2050 2080

Energy Savings (B

illion BT

U)

IX SNL CA/NM Energy Savings HAD CM3 A2 Climate Scenarios

Total Electricity

Total Gas

0.000.200.400.600.801.001.201.401.60

0.7 0.6 0.5 0.4

Site‐W

ide % Ene

rgy Savings

Site‐wide Maximum Chiller Efficiency at Full Load (kW/ton)

SNL Chiller Efficiency Study

EnergyModeling

Page 15: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Basic Central Air System Analytic  Software

Page 16: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

DIGITAL CONTROL OUTCOME [70 Degree Air]

Manner of delivery is as important as outcome … ‐ Automatically Driven‐ Stability via Tested Programming‐ Optimized Sequencing ‐ Proven Efficiency Using Employed Metrics‐ Self Diagnosing Reliability

Purely End Result Oriented… ‐ Operator Driven‐ Reliable‐Metrics: Non Existent‐ Field Efficiency is Subordinated‐ Unrealized Design Intent

TWO METHODS: SAME OUTCOMEDIFFERING ENERGY IMPACT

Building Operations Analytic  Software

Page 17: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Case Study – Sensor Disturbance

• Office/Lab Building • Cooling options: chiller and evaporative cooling• Fall day

– 75 degrees F; 15% Relative Humidity• Building temperature is with limits and occupants are not complaining.• Chilled water valve is open, electric chiller is running and economizer/evaporative 

cooling system is off.• WHAT WENT WRONG?

Analytic  Software

Page 18: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Case Study – Human Disturbance

• Office Building: carpet was cleaned during the weekend.

• HVAC system was placed in 24/7 operations to remove carpet cleaning odors.

• eQuest model; encountered difficulty in calibration process.

• WHAT WENT WRONG?

Analytic  Software

Page 19: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

• ONE BUILDING ‐ ALBUQUERQUE SITE• 25 RULE BASED ANALYTICS

Analytics Pilot ProjecteQuest Runs to calculate savings based on Findings from Pilot Project:

• AHU Start Time Not Optimized (1.5 hour excess run time)

• AHU Fan Speed Fixed• AHU Supply Air Temperature Fixed• AHU Economizer Not Implemented• Hot Water Supply Temperature Fixed

Analytic  Software

Page 20: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Building 899A 150 ton screw chiller fault detection

Advanced Fault Detection

• Fault criteria which vary with time• Rules based on gray‐box model parameters• Parameters estimated by Kalman filtering

R&DOptimization

Page 21: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

Big Modeling and Data

Capability to approach sustainability with an unprecedented level of detailRobustly detect faults

119 Doe2 Models and IX 250,000 Data streams

+

Model Parser

+

=+Advanced Analytics

R&DOptimization

Page 22: Continuous Commissioning at Sandia National Laboratories · BTU NM PSEL Weather Solar PV Generation ... 500,000 This Month, March 2016 Last Month, February 2016 This Month Last Year,

Energy Exchange: Federal Sustainability for the Next Decade

• Jerry Gallegos• Daniel Villa• Marlin Addison• Birk Jones• Mary Bultmann• Jim Sweeney• LaTonya Walker

22

QUESTIONS