Contents IllustrationsSafety Instructions: Installation Special ConditionsMountingApplicationTechnical CharacteristicsCommon SpecificationsInput: RTD T/COutput: Current Sensor Error DetectionApprovals Ex / I.S. Data Observed Authority RequirementsProgramming General TP05 Module HART® Modem HART® Communicator
Drawings CSA Installation FM InstallationFigures Connections (Figure 1) Installation (Figure 2) Block Diagram (Figure 3) TP05 Programming Module (Figure 4) HART® Modem (Figure 5) Multi Drop Connection (Figure 6) HART® Controller (Figure 7) Mounting of Sensor Wires (Figure 8) Mechanical Specifications (Figure 9)
Tables Accuracy General Values (Table A) Accuracy Basic Values (Table B) Input Range (Table C)
Burns Engineering, Inc.10201 Bren Road East Minnetonka, Minnesota 55343
Form 07075507/07
While this information is presented in good faith and is believed to be accu-rate, Burns Engineering cannot guarantee satisfactory results from reliance upon this information. For complete warranty information, please request a copy of Burns Engineering form #0475143 “Terms and Conditions of Sale”
222233
33
44
44
89
1011
56 & 7
4489
1011111212
333
Model T552-wire HART® Programmable
Temperature TransmitterInstruction Manual
2
Model T55, 2-wire HART® Programmable Temperature Transmitter Instruction Manual
Bur ns Eng ine e r i ng I nc .
Safety Instructions: Installation For a safe installation of the T55 in a hazardous area the following must be observed. • The module must only be installed by qualified per-sonnel who are familiar with the national and interna-tional laws, directives and standards that apply to this area.• Year of manufacture can be taken from the first two digits in the serial number.• The sensor circuit is not infallibly galvanically isolated from the input circuit. However, the galvanic isolation between the circuits is capable of withstanding a test voltage of 500 Vac during 1 minute.• The transmitter must be mounted in an enclosure in order to provide a degree of ingress protection of at least IP20.• For use in explosive atmosphere Install per CSA and FM installation drawings.• Cable entries and blanking elements shall be used that are suitable for the application and correctly in-stalled.• For an ambient temperature ≥ 60°C, heat resistant cables shall be used with a rating of at least 20 K above the ambient temperature.• The surface temperature of the enclosure is equal to the ambient temperature plus 20K, for a dust layer with a thickness up to 5 mm.
Safety Instructions: Special Conditions Special conditions for use:• For use in potentially explosive atmospheres of flam-mable gasses, vaporous and mists, the transmitter shall be mounted in an enclosure providing a degree of ingress protection of at least IP 54 in accordance with EN 60529.
• For use in the presence of combustible dusts, the transmitter shall be mounted in an enclosure provid-ing a degree of ingress protection of at least IP 6X in accordance with EN 60529. The surface temperature of the enclosure shall be determined after installation of the units.• Provisions shall be made to prevent the rated supply voltage being exceeded by transient disturbances of more than 40%.• If the enclosure in which the transmitter is mounted is made of Aluminum and installed in Zone 0, 1 or Zone20, 21 or 22 it shall not contain by weight more than 6% in total of magnesium and titanium. • The additional enclosure of the apparatus shall be designed and/or installed in such a way that, even in the event of rare incidents, ignition sources due to im-pact and friction sparks are excluded.
Mounting• For sensor head mounting. In non-hazardous areas the T55 can be mounted on a DIN rail.
Application• Linearized temperature measurement with Pt100...Pt1000, Ni100...Ni1000, or TC sensor.• Difference or average temperature measurement of 2 resistance or TC sensors.• Conversion of linear resistance variation to a stan- dard analogue current signal, for instance from valves or Ohmic level sensors.• Amplification of a bipolar mV signal to a standard 4...20 mA current signal. • Connection of up to 15 transmitters to a digital 2-wire signal with HART® communication.
For assistance call (800) 328-3871 (952) 935-4400 3
Technical characteristics• Within a few seconds the user can program T55 to measure temperatures within all ranges defined by the norms.• The RTD and resistance inputs have cable compen-sation for 2-, 3- and 4-wire connection.• Continuous check of vital stored data for safety rea-sons.• Sensor error detection according to the guidelines in NAMUR NE 89.
Effect of supply voltage variation:* < 0.005% of span/ VDCVibration: IEC 60068-2-6 Test FCLloyd’s specification no. 1: 4 g / 2...100 HzMax. wire size: 1 x 16 AWG stranded wireHumidity: < 95% RH (non-cond.)Dimensions: Ø 1.73 x 0.8 inTightness (enclosure / terminal): IP68 / IP00Weight: 1.8 oz.
*Of span = Of the presently selected range
Input: RTDMax. offset: 50% of select. max. valueCable resistance per wire (max.): 5 ΩSensor current: Nom. 0.2 mAEffect of sensor cable resistance (3- / 4-wire): < 0.002 Ω/ΩSensor error detection: YesShort circuit detection: if 0% > 30 Ω
Input: ThermocoupleMax. offset: 50% of select. max. valueCold junction compensation: < ±1.0°CExternal CJC with Ni100 or Pt100: -40 ≤ Tamb. ≤ 135°CSensor error detection: YesSensor error current: When detecting: Nom. 33 mA Else: 0 mAShort circuit detection: If 0% > 5 mV
Common SpecificationsSpecifications range: 40°C to +85°CSupply voltage, DC Standard: 8.0...35 V ATEX, FM and CSA: 8.0...30 VDCIsolation voltage, test / operation: 1.5 kVAC / 50 VACWarm-up time : 30 s.Communications interface: Programming Module and HART®
Signal / noise ratio: Min. 60 dB Response time (programmable): 1...60 sEEprom error check: < 10 sSignal dynamics, input: 22 bitSignal dynamics, output: 16 bitCalibration temperature: 20...28°CAccuracy: the greater of general and basic values given in Tables A and B
Input Type Absolute Accuracy
Temperature Coefficient
All ≤ ±0.05% of span* ≤ ±0.005% of span* / ºC
Table A. Accuracy General Values
EMC immunity influence ........................................... < ±0.1% of span Extended EMC immunity: NAMUR NE 21, A criterion, burst ............................. < ±1% of span
Temperature coefficient
Basic accuracy
Input type
RTD TC type: E, J, K, L, N, T, U TC type: B, R, S, W3, W5, LR
≤ ±0.1°C
≤ ±0.5°C
≤ ±1°C
≤ ±0.005°C/°C
≤ ±0.025°C/°C
≤ ±0.1°C/°C
Table B. Accuracy Basic Values
Type
Min. Value
Max. value
Min. span
Standard
Pt100Ni100
B E J K L N R S T U
W3 W5 LR
-200°C -60°C
+400°C -100°C -100°C -180°C -100°C -180°C -50°C -50°C
-200°C -200°C
0°C 0°C
-200°C
+850°C +250°C
+1820°C +1000°C +1200°C +1372°C +900°C
+1300°C +1760°C +1760°C +400°C +600°C
+2300°C +2300°C +800°C
25°C 25°C
200°C 50°C 50°C 50°C 50°C
100°C 200°C 200°C 50°C 75°C
200°C 200°C 50°C
IEC 60751DIN 43760
IEC584 IEC584 IEC584 IEC584
DIN 43710 IEC584 IEC584 IEC584 IEC584
DIN 43710 ASTM E988-90 ASTM E988-90 GOST 3044-84
Table C. Input Range
4
Model T55, 2-wire HART® Programmable Temperature Transmitter Instruction Manual
Bur ns Eng ine e r i ng I nc .
Output: CurrentSignal range: 4...20 mAMin. signal range: 16 mAUpdating time: 440 ms (660 ms for diff.)Fixed output signal: Between 4 and 20 mAOutput signal at EEprom error: ≤ 3.5 mALoad resistance: ≤ (Vsupply - 8) / 0.023 [Ω]Load stability: < ±0.01% of span* / 100 Ω
Output: Sensor Error Detection*Programmable: 3.5...23 mANamur NE43 Upscale: 23 mANamur NE43 Downscale: 3.5 mA
Approvals: Ex / I.S. Data• Signal output / supply, terminal 1 to 2: Ui: 30 VDC Ii: 120 mADC Pi: 0.84 W Li: 10 µH Ci: 1.0 nF• Sensor input, terminal 3, 4, 5 and 6 Uo: 9.6 VDC Io: 28 mA Po: 67 mW Lo: 35 mH Co: 3.5 µF
• FM, applicable in: IS, Class I, Div. 1, Group A, B, C, D, IS, Class I, Zone 0, AEx ia IIC FM Installation Drawing No.: FM-T5-212
• CSA, applicable in: IS, Class I, Div. 1, Group A, B, C, D, IS, Class I, Zone 0, Ex ia IIC CSA Installation Drawing No.: CSA-T5-212
Observed Authority Requirements:EMC2004/108/EC Emission and immunity: EN 61326ATEX 94/9/EC: EN 50014, EN 50020, EN 60079-15, EN 50284 and EN 50281-1-1FM: 3600, 3611, 3610, 3810CSA, CAN / CSA: C22.2 No. 157, E60079-11, UL 913
Figure 1. Connections
3 4 65 3 4 65 3 4 65
3 4 65
+-
3 4 65
+-
3 4 65
12
3 4 65
+
-1
+
-2
3 4 65
+
-
+
-
12
3 4 65
+
-
1
+
-
2
1 2
mA -+
Output :2-wire installation
Input :R TD, 2-wire R TD, 3-wire R TD, 4-wire
TC, internal CJC TC, external CJC
TC, differenceor average,
with external CJCmV, difference
or average
R TD, differenceor average
TC, differenceor average,
with internal CJC
Figure 2. Installation
+-
+-
V+
mA
V+
mA
V+
mA
+-
+-
+
-
+-
+-
+- 1
+- 2
+-
+-
12
12
TC to 4...20 mA
RTD to 4...20 mA
Difference or AverageRTD or TC
2-wire intallationin control room
2-wire intallationin control room
2-wire intallationin control room
For assistance call (800) 328-3871 (952) 935-4400 5
Burns Engineering CSA Installation Drawing .
Model Drawing Revision Date Appr. Page
T51 / T55 CSA-T5-212 A April 11-2007 PB 1/1
Model T51
Model T55
Warning:Substitution of components may impair intrinsic safety. The transmitters must be installed in a suitable enclosure to meet installation codes stipulated in the Canadian Electrical Code (CEC).
Non Hazardous LocationHazardous (Classified) Location
Associated Apparatusor Barrier
withentity Parameters:
SENSOR
1 2
345
6
UM < 250VVoc or Uo < Vmax or UiIsc or Io < Imax or IiPo < PiCa or Co > Ci + CcableLa or Lo > Li + Lcable
This device must not be connected to any associated apparatus which uses or generates more than 250 VRMS
+
-Terminal 1 , 2Ui (Vmax): 30 VIi (Imax)i: 120 mAPi: 0.84 WCi: 1 nFLi:10 uH
Terminal 3,4,5,6Only passive, or non-energy storing devices such as RTD's and Thermocouples may be connected.
Ambient temperature limitsT4: -40 to + 85 deg. CelciusT6: -40 to + 60 deg. Celcius
Class I,Division1, Groups, A,B,C,DClass I, Zone 0, IIC
Non Hazardous LocationHazardous (Classified) Location
Associated Apparatusor Barrier
withentity Parameters:
SENSOR
1 2
345
6
UM < 250VVoc or Uo < Vmax or UiIsc or Io < Imax or IiPo < PiCa or Co > Ci + CcableLa or Lo > Li + Lcable
This device must not be connected to any associated apparatus which uses or generates more than 250 VRMS
+
-Terminal 1 , 2Ui (Vmax): 30 VIi (Imax): 120 mAPi: 0.84 WCi: 1 nFLi:10 uH
Terminal 3,4,5,6 Uo(Voc) : 9.6 VIo (Isc): 28 mAPo: 67.2 mWCo (Ca): 3.5 uFLo (La): 35 mH
Ambient temperature limitsT4: -40 to + 85 deg. CelciusT6: -40 to + 60 deg. Celcius
Class I,Division1, Groups, A,B,C,DClass I, Zone 0, IIC
6
Model T55, 2-wire HART® Programmable Temperature Transmitter Instruction Manual
Bur ns Eng ine e r i ng I nc .
Model Drawing Revision Date Appr. Page
T51 / T55 FM-T5-212 A April 23-2007 PB 1/2
Non Hazardous LocationHazardous (Classified) Location
Associated Apparatusor Barrier
withentity Parameters:
SENSOR
1 2
3
45
6
UM < 250VVoc or Uo < Vmax or UiIsc or Io < Imax or IiPo < PiCa or Co > Ci + CcableLa or Lo > Li + Lcable
This device must not beconnected to any associatedapparatus which uses orgenerates more than 250 VRMS
+
-Terminal 1 , 2Vmax or Ui: 30 VImax or Ii: 120 mAPmax or Pi: 0.84 WCi: 1 nFLi:10 uH
Terminal 3,4,5,6Only passive, or non-energystoring devices such as RTD'sand Thermocouples may beconnected.
Ambient temperature limitsT4: -40 to + 85 deg. CelciusT6: -40 to + 60 deg. Celcius
Class I,Division1, Groups, A,B,C,DClass I, Zone 0, IIC
Non Hazardous LocationHazardous (Classified) Location
Associated Apparatusor Barrier
withentity Parameters:
SENSOR
1 2
3
45
6
UM < 250VVoc or Uo < Vmax or UiIsc or Io < Imax or IiPo < PiCa or Co > Ci + CcableLa or Lo > Li + Lcable
This device must not beconnected to any associatedapparatus which uses orgenerates more than 250 VRMS
+
-Terminal 1 , 2Vmax or Ui: 30 VImax or Ii: 120 mAPmax or Pi: 0.84 WCi: 1 nFLi:10 uH
Terminal 3,4,5,6Vt or Uo: 9.6 VIt or Io: 28 mAPt or Po: 67.2 mWCa or Co: 3.5 uFLa or Lo: 35 mH
Ambient temperature limitsT4: -40 to + 85 deg. CelciusT6: -40 to + 60 deg. Celcius
Class I,Division1, Groups, A,B,C,DClass I, Zone 0, IIC
For assistance call (800) 328-3871 (952) 935-4400 7
Model Drawing Revision Date Appr. Page
T51 / T55 FM-T5-212 A April 23-2007 PB 2/2
8
Model T55, 2-wire HART® Programmable Temperature Transmitter Instruction Manual
Bur ns Eng ine e r i ng I nc .
Figure 3. Block Diagram
T55
Programming: General
The T55 Transmitter can be cofigured in the following ways:
• With the Burns Engineering TP05 Programming Module and PC configuration software. • With a HART® modem and PC configuration software.
• With a HART® communicator with a Burns Engineering DDL driver.
For assistance call (800) 328-3871 (952) 935-4400 9
Programming: TP05 Module
For programming please refer to the Programming Module Figure 4 on sheet #9 and the help functions in TP05.Please note the Programming Module set up is not approved for communication with modules installed in haz-ardous (Ex) areas.
T55
Burns Enginnering, Inc.
2007-07-07
073201594
TP05 Programming Module
Programming ModuleTP05
PNR
TXD
RXD
Connector
Figure 4. TP05 Programming Module
10
Model T55, 2-wire HART® Programmable Temperature Transmitter Instruction Manual
Bur ns Eng ine e r i ng I nc .
Programming: HART® modem:
For programming please refer to the HART®Modem Figure 5 on sheet #9 and the help functions in TP05.
T55
Burns Engineering, Inc.
2007-07-07
073201507
TP05 Programming Module
Figure 5. HART® modem
For assistance call (800) 328-3871 (952) 935-4400 11
Programming: HART® communicator
For programming please refer to the note below and the HART® Communicator Figures 6 & 7 on Sheet #11. To gain access to product-specific commands, the HART® communicator must be loaded with the Burns Engineering DDL driver. This can be ordered either at the HART® Communication Foundation or at Burns Engineering.• The HART® communicator or a PC modem can be connected across AB or BC.• The outputs of max. 15 transmitters can be connected in parallel for a digital HART® communication on 2-wires. • Before it is connected, each transmitter must be configured with a unique number from 1 to 15. If 2 transmitters are configured with the same number, both will be excluded. • The transmitters must be programmed for multidrop mode (with a fixed output signal of 4 mA). Maximum current in the loop is therefore 60 mA. • The communication is either by means of a HART® communicator or a HART® modem. • The TP05 Programming Module can configure the individual transmitter for multidrop mode and provide it with a unique polling address.
T55
Figure 6. Multi Drop Connection
Figure 7. HART® Communicator
T55 T55T55
12
Model T55, 2-wire HART® Programmable Temperature Transmitter Instruction Manual
Bur ns Eng ine e r i ng I nc .
Notes:
Burns Engineering is available to answer your questions regarding T55 Transmitter applications. Call toll free 1-800-328-3871.
Figure 8. Mounting of Sensor Wires
Figure 9. Mechanical Specifications
0.8 in
0.24 in
1.73 in
1.30 in (33mm)
1 2
3
45
6