construction technologg laboratoriesFor wet grout interface and normal stress of 60 psi, both...

30
construction technologg laboratories = . . . . . . '' $EK;-;- . ~ ~ ' . s. e .= ^' . . ,#4s ; . . se- '' ; :. e ** _ +* % N, . f .g - <# " , .* , - ,4 " ... )s . -s ' - , , 3 $v g. ? ' y - ~" ; ; ~ , - , , c , ,, . , 'g i , g.1 l

Transcript of construction technologg laboratoriesFor wet grout interface and normal stress of 60 psi, both...

  • construction technologg laboratories= . . . ..

    .

    '' $EK;-;-. ~ ~ '.s. e.=

    ^' . . ,#4s; . . se-'' ; :. e ** _

    +*% - - N,

    . f .g-

  • Report to

    FLUOR POWER SERVICES, INC. TENNESSEE VALLEY AUTHORITYChicago, Illinois Knoxville, Tennessee

    DUKE POWER COMPANYCharlotte, N. C.

    TESTS TO EVALUATECOEFFICIENT OF STATIC FRICTION

    BETWEEN STEEL AND CONCRETE

    by

    B. G. Rabbat and H. G. Russell

    .

    Submitted byCONSTRUCTION TECHNOLOGY LABORATORIES

    A Division of the Portland Cement Association5420 Old Orchard Road

    Skokie, Illinois 60077February 1979

    7902080A3&.

  • TESTS TO EVALUATE COEFFICIENT OF

    STATIC FRICTION BETWEEN STEEL AND CONCRETE

    by

    B. G. Rabbat and H. G. Russell *

    HIGHLIGHTS

    An experimental investigation was conducted to determine

    the coefficient of static friction betwean cast-in-place

    concrete or grout and rolled steel plate. Push-off tests were

    performed under conditions that represe t the interior and

    exterior bearing surfaces of a containment vessel.

    Test Program

    Five sets of three similar push-off tests were conducted.

    Specimens consisted of either concrete cast on top of, or grout

    cast under a flat steel plate. Three sets of concrete speci-

    mens were tested with a wet interface at normal stress levels

    of 20, 60, and 100 psi. One set of concrete specimens was

    tested with a dry interface at a normal stress of 60 psi. One

    set of grout specimens was tested with wet interface at a nor-

    mal stress of 60 psi. For each specimen, nominal bond stress

    and coefficient of static friction at interface were measured.

    Conclusions

    Results of this investigation have shown the following:

    *Respectively, Structural Engineer and Manager, StructuralDevelopment Section, Portland Cement Association, Skokie,Illinois

    -1-

  • 1. Bond strength for concrete specimens varied between 25

    and 89 psi. For grout specimens, bond strength was

    negligible.

    2. For wet concrete interface specimens average effective *

    coefficients of static friction were 0.67, 0.65, and

    0.64, at normal stresses of 20, 60, and 100 psi,

    respectively. The corresponding average peak *

    coefficients of static friction were 0.70, 0.68 and

    0.64, respectively.

    3. For dry concrete interface specimens with a normal

    stress of 60 psi, the average effective and average

    peak coefficiends of static friction were 0.57 and

    0.69, respectively.

    4. For wet grout interface and normal stress of 60 psi,

    both average effective and average peak coefficients

    of static friction were 0.68.

    INTRODUCTION

    The purpose of this investigation was to determine exper-imentally the coefficient of static friction between cast-in-

    place concrete or grout and rolled steel plate. For concrete

    specimens, wet and dry interface conditions were tested. For

    grout specimens, wet interface condition only was tested. The

    work described in this report complie.e with Fluor Power Services

    Inc. Purchase Order No. B-1394 dated January 31, 1978.

    * Definitions of effective and peak coefficients of staticfriction are given under heading " Shear Stress - SlipRelationship".

    -2-

  • EXPERIMEN'.aL PROGRAM

    This section describes the test specimens, test variables,

    manufacturing procedure, test setup, instrumentation, and

    testing procedure.

    Test Specimens

    Test specimens represented conditio.1s at either steel-

    concrete or steel-grout interface in the lower support region

    of a containment vessel. To simplify testing, the friction

    surface was simulated as a flat plare.

    A test specimen is shown in Fig. 1. The test surface was

    13.5 in, wide and 24 in, long. These dimensions give a test

    area of 324 sq.in.

    Test variables

    Fifteen specimens were tested in tnis investigation. All

    specimens were tested in sets of three. Test variables inclu6ud

    1. Concrete blocks with wet and dry interface

    2. Grout blocks with wet interface

    3. Level of normal compressive stress

    Experimental program as summarized in Table 1 comprised the

    following three series.

    Series I - Wet Concrete-to-Steel Interface

    Series I consisted of nine tests. Three tests were per-

    formed at each of three levels of normal compressive stress.

    After breaking the bond, the concrete-to-steel interface was

    intentionally saturated with water for the friction tests.

    -3-

  • C~oncrete or Grout Block

    /7 Steel PlateI/,/ /

    ' i 14 "

    $| / /// /v

    24" 7 |a/'

    4 28" y,

    .

    Fig. 1 Test Specimen

    -4-

  • TABLE 1 - EXPERIMENTAL PROGRAM

    NormalTest Compressive Interface

    Number Series Specimen * Stress Condition(psi)

    1 I CWB-1 602 CWA-1 100 Concrete to Steel3 CWC-1 20 (we t)4 CWB-2 605 CWA-2 1006 CWC-2 207 CWB-3 608 CWA-3 1009 CWC-3 20

    10 II CDB-1 60 Concrete To Steel11 CDB-2 60 (dry)12 CDB-3 60

    13 III GWB-1 60 Grout to Steel14 GWB-2 60 (we t)15 GWB-3 60

    * Specimen Identification is as follows:

    First Letter: C is for Concrete, G is for GroutSecond letter: W is for Wet, D is for DryThird letter is the Load Level: A= 100 psi, B 60 psi,=

    C = 20 psiLast digit is for first, second or third test of each set.

    -5-

  • Series II - Dry Concrete-to-Steel Interface

    Three tests were performed in Series II. Normal compres-

    sive stress was held constant at an intermediate level. The

    concrete-to-steel interface was not wetted after breaking the

    bond.

    Series III - Wet Grout-to-Steel Interface

    Series III consisted of three tests at the same level of

    compressive stress as in Series II. However, after breaking

    the bond the grout-to-steel interface was completely wetted.

    Manufacture of Specimens

    Concrete and grout specimens were manufactured according to

    different procedures discussed below. In all specimens, the

    steel plate was as rolled SA 516 Grade 70 steel, one inch thick

    and 14x28 in, in size.

    Steel Plate Cleaning

    The steel plate was cleaned in accordance with the Steel

    Structures Council Specifications SSPC-SP2-63, Hand Tool

    III *Cleaning Oil and grease were removed using acetone.

    solvent. Rust scale was removed by hand hammering. Loose mill

    scale was removed by hand wire brushing.

    Concrete-to-Steel Specimens

    After cleaning the steel plate, wood formwork was clamped

    to the top of the steel plate. The concrete mix was designed

    to yield a compressive strength between 3000 and 5000 psi at 28

    * Number in parenthesis denote references listed at the end ofthe report.

    -6-

  • days. The mix was made using Type I Portland Cement, Elgin

    Sand and Elgin Gravel with a maximum aggregate size of 1-1/2 in.

    Concrete was compacted using an internal vibrator. From

    each batch, six 6x12 in. standard concrete cylinders weretaken. These cylinders were used to determine the concrete

    compressive strength.

    Concrete was cured for 7 days under plastic - re ting .

    Formwork was then stripped and specimens kept i n t.. . . labora-

    tory at a temperature of 73 F and a relative humidity of 50%until test time at 28 to 30 days.

    Grout-to-Steel Specimens

    Grout-to-steel specimens were prepared in a setup as shownin Fig. 2. The setup was designed to simulate field conditions

    of placing grout at the exterior bearing surface of acontainment vessel. Formwork was clamped t7 the underside ofthe steel plate. The specimen was inclined during grouting.

    The difference in height between the bottom horizontal edges ofthe grout block was 4 in.

    The grout mix specifications called for

    Cement: Type 2, ASTM C-150, no admixtures

    Fine Aggregate: Natural Elgin Sand, ASTM C33

    Cement to Sand katio: 1 to 2 by Volume

    Water to Cement Ratio: 0.5 by weight

    Flow of this mix was measured after five drops in three secondson a flow table.

    Grout was placed through a funnel secured to the top of theright-hand side pipe shown in Fig. 2. This pipe had a 2 in.

    -7-

  • - - - ,_

    * ?] ' *[j,; 2 | 5 ' ' ~~4 9.-y, , ,

    my-

    . i , , . , 'c , Lj .-- JP.i 3-,. ",

    ?. $;.} pig %

    '~ - i=;Y. .hf

    ,'

    . D:. s:.N- * -

    pjf''.$n zif~~f';I &

    ~

    f-, ,,:'' ' ' ' '

    -,

    . .,y g . :. '- . :f'Nf5' .* $:

    _g.r . - ''4[ ? d' :.m- je. |8p;8

    %,A '.cf- j ,,

    .

    .s. ..m.., ,. . ;o ,t4

    - ;.

    |*

    ..,o F.sdej ', ' bt)- y, : ',

    Y-) $ ,$''''' ,..

    *

    ?)'

    i-

    -

    - '

    x 'y. o-

    1 . ,9]f.-ap .' ,_

    - <

    ' . ' s..R'~ -' 3: ,I N *.) -

    ' ~r - -;s. , , *

    t ;.t ,%; __ -

    wg

    . ,

    ,

    .. ~,. :. - _,

    =- =a . , -_ _M :;- - - ,- ~ -

    Setup for Preparation of Grout S ecimensP-

    -8-

  • diameter. Because of its consistency, the grout filled the

    form and flowed upward in the lef t-hand pipe. The height ofthe left-hand side pipe corresponded to 5-ft head measured from

    the center of the grout block.

    To permit bleeding of air trapped under the plate, holes

    were provided around the top perimeter of the f orm. These

    holes were sealed as soon as air bleeding was completed.

    The tubing was sawed off af ter 7 days. The specimens were

    then stripped and turned upside down. They were kept in the

    laboratory at a temperature of 73 F and a relative humidity of50% until test time. Grout compressive strength was measured

    using six 2-in. cubes.

    Test Setup

    The test setup is shown in the photograph of Fig. 3 andschematically in Fig. 4. This setup is capable of applying

    vertical loads normal to the shear plane and horizontal loads

    parallel to the shear plane. The main components of the setup

    are shown in Fig. 5. They were assembled as follows:

    Test specimen was grouted to the lower block shown in Fig.5. Brackets clamped to the lower block served as guides toposition the steel plate. During testing, the brackets pre-

    vented slip of the test specimen with respect to the lower

    bloc k .

    The upper block shown in Fig. 5 was grouted on top of thetest spec imen. Brackets embedded in the upper block served as

    guides to place it. During testing, the brackets also helped

    prevent slip of the specimen with respect to the upper block.

    -9-

  • 75 w aw fg

    '

    .

    44

    :

    .

    -\ n,.t m

    *

    a.

    4 'l,

    A 4

    C'

    ,,

    s *, ,' ' -

    5 * ' le,_*

    'M 1potentio ig!

    . >* *? 5;

    . ,.

    , >, ,n

    . .* -

    *m yy ..,,

    %,

    , ~* ~e, %,:

    sem ,s

    ...~-

    .

    l

    S,M .' .-

    .- - . *N . -

    -10-

  • ,-*-C B* A*,

    A a E dp Load Cells n i-H- it-

    1 ['

    * Rams for Normal Stress

    f h p -Structural Tubes ||'

    Potentiometers

    4- Load Cells

    e /,

    'I- i L__ ]_

    ||# 6|,|%, 'N x */ 11 ||

    Rams for 11 - 11.Push-Off 'Y ' Y Y*Load LO B* AHALF-SECTION A-A HALF-SECTION B-B SECTION C-C

    Fig. 4 Schematic of Test Setup

  • -*-B A+

    UPPER BLOCK- _t ,, --

    I"|+-- 24 /g H

    "24" i| |*- 13 '/ M2

    MConcrete Block TEST SPECIMEN ',',

    SA 516 Grade 70) T,,Steel Plate 2 8,, _*

    ?.8 '/ " ~8

    LOWER BLOCK

    -+ B A+SECTION AA SECTION BB

    Fig. 5 Test Setup Components

  • Horizontal rams were used to apply in-plane shear loads.

    Vertical rams were used to apply normal stresses. All ramswere loaded using hydraulic oil pressure.

    Instrumentation

    All loads were measured using calibrated load cells }

    acting in series with the hydraulic rams.

    Slip of the concrete test block relative to the steel platewas measured with two potentiometers as shown in Fig. 6. Eachpotentiometer was attached to a bracket secured to the steel

    plate. The potentiometer's plunger was attached to a bracket

    on the concrete test block.

    An X-Y plotter was used to obtain a continuous record of

    the in-plane shear versus slip at the friction interface. The

    Y-axis of the plotter was calibrated to indicate the in-plane, shear stress. This consisted of the sum of loads from two loadcells divided by the interface area. The X-axis indicated theaverage slip measured by two potentiometers.

    Test Procedure

    Bond between concrete and steel was broken by application

    of an in-plane shear force applied at the shear-friction inter-face. No normal compressive stress other than the weight of

    the upper block was applied at this stage. This weight wasequivalent to a nominal stress of 8.18 psi. The shear stressrequired to cause first slip was noted. The concrete block was

    then moved back to its original position on the steel plate.

    -13-

  • Concrete orGrout Block

    ._ Brocket securedto Block

    p Potentiometer.

    IJ /\ Steel Brocket secured to

    Plate Steel Plate

    Fig. 6 Attachments to Measure Slip

    -14-

  • For tests requiring a wet friction surface, the iaterfaces

    were separated af ter bond was broken. The interfaces were then

    saturated with water to ensure a wet sur f ace during testing.

    Interfaces remained saturated during subsequent testing.

    During each test, normal stress was held constant.

    Af ter application of normal compressive f orce, the shear

    load was applied slowly. A continuous record of the horizontal

    load versus slip at the shear-friction interface wac obtained.

    A representative shear stress versus slip curve is shown in

    Fig. 7. It can bee seen that slip occurred in increments.

    Each slip increment occurred within a fraction of a second and

    was accompanied by a drop in shear stress. The drop was a

    result of the stif f ness of the loading system. To eliminate

    the eff ect of stiff ness of the loading system, the shear stress

    versus slip curves reported under test results were idealized

    by a curve joining the peaks of the saw teeth of Fig. 7. Note

    tha t the testing rate was adjusted to obtain 0.1 in. slip

    within three to five minu tes. The test was stopped when 0.5

    in. slip was reached.

    TEST RESULTS

    Results presented in this section include material

    properties, bond strengchs at interface, shear stress versus

    slip relationships, and coefficients of static f riction. The

    eff ects of normal stresses, wet interface, grout versus

    concrete, and concrete strength on the coefficient of static

    f riction are discussed.

    -15-

  • .

    60 -

    . #1NNS\\\iN\\\\\\\\\\\'4 ~ \Shear N \ .Stress,psi

    20 -

    O ' '

    O 0.1 0.2

    Slip, inch

    Fig. 7 Representative Continuous Record of ShearStress versus Slip

    -16-

  • Concrete Strength

    At test age, six concrete cylinders were loaded to deter-

    mine concrete compressive strength. The average concrete

    strength is listed in Table 2. Age of concrete at time of

    testing is also listed.

    Grout Properties

    Grout strength was measured using 2 in. cubes. The average

    cube strength is listed in Table 3. The flow measured on the

    flow table after five drops in three seconds is also listed.

    Bond Strength at Interface

    Bond strength is the nominal shear stress required to break

    the bond between the concrete or grout block and the steel

    plate. It is equal to the in-plane shear force that broke the

    bond divided by the area of the interface (324 sq. in.).

    Measured bond strengths are listed in Table 4 where the

    specimens have been grouped in sets of three similar tests.

    For concrete specimens, the bond strength varied between 25 and

    89 psi.

    For grout specimens, bond strength was negligible.

    Inspection of the interface after testing indicated that after

    placing the grout, bleeding occurred inside the formwork. Sand

    particles settled and water laitance moved up, with a larger

    accumulation at the highest point of the formwork. As cement

    hydrated, water was absorbed. As a result, air gaps formed

    between the steel plate and grout block. Moreover, air bubbles

    -17-

  • TABLE 2 - CONCRETE STRENGTH

    AverageTest Test Age Concrete Strength

    Number Specimen (days) (psi)

    1 CWB-1 28 37702 CWA-1 29 35103 CWC-1 28 32754 CWL-2 28 35105 CWA-2 28 37806 CWC-2 28 35257 CNB-3 28 30308 CWA-3 28 38009 CWC-3 28 3270

    10 CDB-1 28 362011 CDB-2 28 372012 CDB-3 28 3710

    TABLE 3 - GROUT PROPERTIES

    Test Specimen Test Age Average CubeNumber (days) Days Strength (psi) Flow *

    13 GWB-1 28 7680 14214 GWB-2 30 7655 12115 GWB-3 28 8390 120

    1

    * ASTM C230 (3)

    .

    -18-

  • TABLE 4 - BOND STRENGTH AND COEFFICIENT OF FRICTION

    Bond Shear Stress (psi) Coefficient of FrictionSpecimen Strength

    (psi) Peak Effective Peak Effective

    CWA-1 52.8 62.0 62.0 0.62l 0.62CWA-2 48.6 63.5 63.5 0.63 0.64* 0.63 0.64CWA-3 51.4 68.0 67.8 0.681 0.68

    CWB-1 55.0 42.0 40.7 0.70) 0.68CW2-2 25.0 40.4 39.6 0.67 ( 0.68 0.66 0.65CWB-3 89.0 40.5 36.1 0.68? 0.60

    CWC-1 61.2 13.8 12.3 0.69| 0.64iCWC-2 83.6 14.2 14.0 0.71| 0.70 0.70f 0.67CWC-3 78.4 13.9 13.5 0.69? 0.671

    CDB-1 67.3 40.5 33.7 0.68 0.56lCDB-2 53.0 46.2 35.0 0.77 0.69 0.58 0.57-CDB-3 58.2 36.9 34.0 0.62 0.57l

    GWB-1 8.0 41.2 41.2 0.69l 0.69

    0.68|1GWB-2 - 40.9 40.9 0.68 0.68 0.68GWB-3 - 40.0 40.0 0.67 0.67

    * Average of each set

    .

    -19-

    .

  • had formed at the interface as shown in Fig. 8. The left hand

    side was the highest point as cast. In Specimens GWB-2 and

    GWB-3, the bond had broken during handling of the specimens

    before testing.

    Shear Stress - Slip Relationship

    Shear stress versus slip curves for Series I, II, and III

    are plotted in Figs. 9, 10, and 11, respectively.

    Peak and effective shear stresses are listed in Table 4.Peak shear stress is defined as the highest shear recorded on

    shear stress versus slip curve. Where the peak shear stress

    occurred at a slip less than 0.5 in., an effective shear stress

    was determined. Effective shear stress is defined as the

    lowest shear stress occurring after the peak shear stress.

    Where the peak shear stress occurred at 0.5-in, slip, the

    effective shear stress was considered equal to the peak shear

    stress.

    Coefficient of Friction

    Coefficient of frictinn is defined as the shear stress

    divided by the normal stress. Coefficients of friction

    corresponding to each of the peak and effective shear stresses

    are listea in Table 4. An average coefficient of friction for

    each set is given in the same table.

    -20-

  • f|f ',, kj, , .j' /;; - | i

    '

    ,.. ~, ,1 j !!; : .i.

    .,u

    (' L*5 + =7w-

    1

    1

    [' ,,!

    _. ,_

    ...

    ._

    .,

    . _ ..

    ~- -- ,__

    'N '. - N 3j ,, n D .'' s bl*.f.ld?i __. 2 1

    Fig. 8 Friction interface ofSpecimen GiB-1 af ter Testing

    -21-

  • i

    80 -

    NormalCompressive Stress

    , _ _ . . . CWA.3100 psi

    .- - -.. .-

    .

    A-2f CWK-l

    ~ ~

    60 _ _ _ _ -/ p , _ ___ _ShearStress,psi

    CWB-l 60 psi ,^

    =7[N.~40 _ --CWB-2- '.s . _ _ _ _ . . _ . _ . , '0, CWB-3

    20 -

    --

    FCWC-2 CWC-3 2 20 psi'

    r ___.- -

    L CWCT ~~-~

    I iO0.1 0.2 03 o4 0.5

    Slip, inch.

    Fig. 9 Shear-Stress versus Slip of Series I

  • 80 -

    60 -

    ShearStress,

    .

    -

    40 J__

    s ive Stressi / 60 ps1

    EDh3''

    ' " * - ~ ~- - - - -

    =a--

    ,

    20 -

    '' ' ' '0O 0.1 0.2 0.3 0.4 0.5

    Slip, inch.

    Fig. 10 She ar-S tre s s versus Slip of Series II

  • 80-

    60 -

    SlieorStress, Normal

    " "'" ""PSI 00 psiM B-3 GWB-l40

    f_Y2- -

    t

    20 -

    Oo'4

    ,

    l O.2 03 0.5Si,lp, inch.

    ,

    Fig ,11 Shear-Stress versus Slip Of Series III

  • Effect of Normal Stresses

    The effect of normal stress on coefficient of friction is

    shown in the results of Series I, concrete-to-concrete

    specimens with wet interface. At normal stresses of 20, 60,

    and 100 psi, the average peak coefficients of static friction

    were 0.70, 0.68 and 0.64, respectively. The corresponding

    average effective shear stresses were 0.67, 0.65, and 0.64,

    respectively. These average coefficients of static friction

    tended to decrease as normal compressive stress increased.

    Effect of Wetting Interface

    The effect of wet interface on coefficient of static

    friction can be seen when comparing average results of CWB and

    CDB tests in Table 4. Corresponding to peak shear stress, the

    average coefficients of static friction are 0.68 and 0.69 for

    wet and dry interfaces, respectively. These coefficients are

    fairly close. However, the average coefficients corresponding

    to effective shear stress, are 0.65 and 0.57 for wet and dryinterfaces, respectively. Therefore, it appears that the

    'verage coefficient of friction corresponding to effective

    .thear stress is about 12% lower for the case of dry interface.

    Grout Versus Concrete Interface

    Comparisons between coef ficient of static friction for

    grout or concrete against rolled steel is obtained from the GWB

    and CWB sets of specimens. The average peak coefficient of

    static friction was the same in both cases a1though in the

    -25-

  • grout series not all of the interface area was in contact with

    the steel p_ ate. This interface condition with air gaps and

    bubbles can be expected in the field. However, variation of

    the grout surface condition did not appear to affect the

    measured coefficient of friction.

    The average effective coefficient of static friction for

    concrete and grout specimens were 0.65 and 0.68, respectively.

    The observed coefficient for the grout specimens was about 5%

    higher than for the concrete specimens.

    Effect of Concrete Strength

    Concrete strengths are listed in Table 2, and coefficients

    of static friction are listed in Table 4. Based on the test

    results of Series I, the coefficient of static friction appar-

    ently increased with increased concrete strength. However, the

    range of concrete strengths is tco small to state positivelywhat the effect of concrete strength is on the coefficient of

    static friction.

    Concluding Remarks

    Fif teen specimens were tested to determine the coefficient

    of static friction between cast-in-place concrete or groutedmortar and rolled steel plate. The specimens simulated the

    condition that could exist at the interior and exterior bearingsurfaces of a containment vessel. A detailed summary of the

    test program, and conclusions appear under " HIGHLIGHTS" at the

    beginning of this report.

    -26-

  • ACKNOWLEDGMENTS

    This investigation was carried out in the Structural

    Development Section of the Construction Technology Laboratories

    under Dr. W. G. Corley, Director, Engineering Development

    Department. Particular credit is due to W. T. Fasig and W.

    Hummerich, Jr. for their assistance in manufacture and testing

    of the specimens.

    CAVEAT

    This report has been prepared for the exclusive use of

    Fluor Power Services, Inc., Duke Power Company, and Tennessee

    Valley Authority and their related entities. The use of the

    report by others will be permitted only on the understanding

    that there are no representations or warranties, expressed or

    implied as to the accuracy and validity of the data and

    information or conclusions contained therein.

    -27-

  • REFERENCES

    1. " Surface Preparation Specifications - No.2 Hand ToolCleaning", SSPC-SP2-63, Steel Structures Painting Council,October 1963.

    2. Hognestad, E., Hanson, N.W., Kriz, L.B. and Kurvits, O.A.," Facilities and Test Methods of PCA Structural Laboratory",Journal of the PCA Research and Development Laboratories,Vol. 1, No. 1, pp. 12-20 and pp. 40-45, January 1959; Vol.1, No . 2, pp. 30-37, May 1959; Vol. 1, No. 3, pp. 35-41,No. 3, pp. 35-41, September 1959. Reprinted as DevelopmentDepartment Bulletin D33, Portland Cement Association,Skokie, Illinois.

    3. Standard Specification for Flow Table for Use in Tests ofHydraulic Cement", ASTM C230-74, American Society forTesting and Materials, Philadelphia.

    -28-