Connection of EarThing Circuits in Hv Systems
-
Upload
anonymous-wk6qxd -
Category
Documents
-
view
5 -
download
2
description
Transcript of Connection of EarThing Circuits in Hv Systems
-
0. Introduction 3
1. General screen connection principles 5
2. Earthing circuit conditions and tests 13
3. Standardized screen connection diagrams 15
4. Elements making up the screen circuit 18
5. Multiple circuits 43
6. Tests 44
7. Earthing of lightning arresters 49
1
CONTENTS
-
This Engineering Recommendation deals with the earthing of cable screens which constitute
an insulated three phase line, installed either in a service gallery, in an indoor installation
or directly buried. To reduce the losses on the line and optimize the transport capacity,
connection systems tend to be adopted which reduce the intensity of the currents induced
on the screens. These systems involve specific connections of the screens to each other
and to earth and give rise to permanent current and current surges on the screen circuits
which must be considered.
0.1 SCOPE
This Recommendation describes the systems and components used in the connections
of the screen circuits of three phase power lines for voltages equal to or greater than 66
kV, made up of single-core cables with metallic screen and insulating sheath. Specific
means may be required to withstand the permanent current and current surges which can
occur between different parts of the screen circuit, and between the same and the earth,
and the testing and checking of the continuity of this circuit should be allowed.
0.2 DEFINITIONS
This Recommendation uses the definitions of the International Electrotechnical Vocabulary
(publication CEI 50), and in Appendix A of "The Design of Specially Bonded Cable Systems,
(part 1)" of Electra no. 28, of May 1973.
The following definitions are moreover added:
Screen. Continuous concentric conductor which surrounds the main conductor and
insulation, aimed at confining the electric field and at conducting the possible short-
circuit currents. It can be made up of a continuous metallic covering or a corona of
wires possibly complemented with metallic tapes. It should be connected to earth
directly or indirectly.
Sheath Voltage Limiters (SVL). Devices with two terminals of strongly non-linear
voltage-current characteristic, aimed at limiting the differences of transitory potential
which, on the occasion of impulse, atmospheric or manoeuvring surges, can appear
between elements of the screen circuit with limited dielectric strength.
Connection box. Blockable box(1), built to house the connections of the screens, of
the earthing cables and the associated SVL when they exist. It should be connected
to earth if it is metallic.
0. INTRODUCTION
(1) Which requires a tool or a key to open it
3
-
Indirect earthing Earthing of the screens of the cables, or of a section of them, so that
the screen circulation currents that would otherwise occur are reduced or eliminated.
Other sections of screen from the same or another phase may be involved in series in
this connection between a screen and an earth electrode. Indirect earthing causes small
permanent current at some points of the screens or at the terminal.
4
-
In an alternating current line, the whole formed by the screens and their connections
constitutes a secondary circuit strongly coupled to the primary circuit, formed by the main
conductors subjected to mains voltage. For this reason, considerable intensities can
appear on the screen circuit during the normal operation of the line. The added losses
and heating for this reason should be taken into account, and in many cases measures
should be taken to minimize them. This Recommendation distinguishes between two
screen earthing diagram types:
Rigid earthing systems
Special earthing systems
The following conditions should be fulfilled in both systems:
During the normal operation the capacitive currents should be conducted to earth,
maintaining the screens at a potential close to that of earth.
During the time a short-circuit lasts, both external to the line and occurring in the same
or on one of its elements, the fault currents which can travel along the screen circuit
should not cause excessive voltage between screens and earth and between parts of
the screen circuit. The strength of the insulation between screen and earth (cable sheath)
and of the separation insulation between sections of screen should be sufficient to
withstand these voltages.
At the points in which the current surges of atmospheric or manoeuvring origin could
cause inadmissible dielectric stress on the screen circuit, there should be adequately
sized voltage limiting devices.
The adoption of measures to cancel or minimize the permanent intensities on the screens
associated with the operation of the line under normal conditions can cause another type
of problem, mainly the appearance on the screen circuit of high voltages during short-
circuits or current surges on the mains. This Recommendation regulates the procedures
to maintain these surges within acceptable limits.
5
1. MAIN SCREEN CONNECTION PRINCIPLES
-
1.1 RIGID EARTHING SYSTEMS
In these systems the screens of the three phases are connected together directly and to
earth so that, at all points of the line, the voltages of the screens between each other and
in relation to earth are maintained close to zero. No provision is adopted to prevent the
circulation of currents along the screens under a permanent regime. These currents, induced
by the main conductors, will give rise to an additional production of heat, with the consequent
reduction of the lines transport capacity.
The screens should be joined together and to earth at both ends of the lines. If necessary,
with the aim of limiting the screen voltages which could appear in the event of a defect on
the line itself, the screens will be joined together at other points, which can also be earthed.(2)
Generally speaking, single-core cables which constitute a three phase line are arranged
in a triangle as close as possible, to reduce the currents on the screens, which increase
on increasing the separation between phases.
With this arrangement, the transpositions of phases along the line are only useful to reduce
their inductive influence on adjacent cables. When the arrangement is flat, or in some other
way asymmetric, the transposition of conductors can moreover achieve the equality of
currents on the screens, and thus obtain the minimum value of losses in this type of
connection. Under no circumstances can the transposition of conductors be used to cancel
the currents on the screens.
Joints
Fig. 1Rigid earthing system
6
(2) It is prudent to connect the screens together and to earth every 2 to 3 km, but this is only requiredif the voltages generated between phases or between phase and earth due to voltage drop becauseof the circulation of fault current exceeds the perforation voltage of the sheath.
-
1.2.5 Sheath voltage limiters (SVL)
The limiting devices indicated in the previous section, also called surges dischargers, are
strongly non-linear zinc oxide conductor elements. They present a very high resistance to
the reduced voltages that appear under normal operating conditions, and they do not
therefore modify the screen circuit diagram. They weakly conduct the industrial frequency
voltages originated during mains failures, without having any limiting effect on these voltages.
On the other hand, they conduct intensely for the short disturbances of atmospheric or
manoeuvring origin which would cause very high voltages at the ends and at the discontinuity
points, limiting these voltages to admissible values. This conduction is accompanied by
production of heat in the discharger, for which the latter has a reduced storage capacity.
For this reason, they are only adequate to limit surges of an order of duration lower than
1 ms, being able to be destroyed if an industrial frequency voltage, even of short duration,
exceeds their free conduction threshold.
It is necessary to limit the voltages which appear between screens and the local earth and
which subject the insulating sheath of the cable and the supporting insulators of the
terminals to dielectric stress, and the voltages that are presented between the two ends
of the screen which concur at the same joint with screen discontinuity, which must be
withstood by a very small thickness of insulating material inside the joint.
1.3 SCREEN CONNECTIONS
To allow periodic verifications of insulation and continuity of the screen circuit, the connections
between screens, to earth and to the SVL are carried out using detachable elements(3). The
connection of the SVL must also be detachable.
These connections and the SVL must be placed out of reach of unauthorized people, either
in adequate boxes, with insertion of physical barriers, or next to the external terminal base
if they are not accessible from the ground.
12
(3) The detachable connections are connected by means of blades or screws and can easily beremoved and replaced, without subjecting the elements of the circuit to stress or bending.
-
2.1 GENERAL CONDITIONS
All the direct connections between screens and between the latter and earth must be
carried out using detachable links. The connections between screens and between the
latter and earth carried out using SVL must be disconnectable. During the operation of the
line, these elements must be considered as live elements and the same precautions shall
be established to access them as for the live parts of the installation.
2.2 SCREEN EARTHING POINTS
The direct earthing of the screens shall be carried out taking into account the following
instructions:
In the cases in which the screens must be earthed at one of the ends of the line, the
connection will be carried out to the general earth electrode of the substation and at the
same point where the earth bonding conductor, if it exists, is connected.
In the cases in which the screens are earthed at intermediate points of the line, they will
also be connected to the bonding conductor, if it exists.
If there is no bonding conductor, and in the location there is a local earth system intended
for other uses, to carry out the connection of the screens to this system at intermediate
points of the line it will be necessary to justify that it can accept the impulses of intensity
which would originate in the event of atmospheric or manoeuvring discharge, the industrial
frequency intensities that would appear in the event of short-circuit at any point of the
line or external to it and the permanent industrial frequency intensities that may occur
due to asymmetries of the line or other causes, always ensuring the safety of people and
equipment.
2.3 EARTHING POINTS OF THE SVL
In the situations in which the SVL devices are connected in a star, the centre of the star
can be earthed in the following cases:
In the cases in which the SVL must be connected at one of the ends of the line, the
connection will be carried out to the general earth electrode of the substation and at the
same point where the earth continuity conductor, if it exists, is connected.
To the earth continuity conductor, if it exists.
If there is no earth continuity conductor, and there is no adequate earth network, the
connection may be carried out to an electrode formed by four earth rods with a length
no shorter than 1.2 m, connected parallel and situated in the four corners of the enclosure
where the SVL are housed, provided that this electrode is electrically independent from
any other local earth system of the installation.
2. EARTHING CIRCUIT CONDITIONS AND TESTS
13
-
If there is no earth continuity conductor, and in the location there is a local earth system
intended for other uses, to carry out the connection to this system it will be necessary
to justify that it can accept the impulses of intensity which would originate in the event
of atmospheric or manoeuvring discharge and the industrial frequency intensities that
would appear in the event of action of one of the SVL ensuring the safety of people and
equipment.
If none of the possibilities indicated in the above hypotheses is available, the centre of
the star of the SVL will not be earthed. In these cases, the connection of the SVL in a
triangle is preferred.
14
-
3.1 RIGID EARTHING SYSTEMS
With this system the screens are directly joined to each other and to earth at both ends
and, possibly, at some intermediate point, without there being any interruption in their
continuity. Fig.1 illustrates the general case, in which both ends of the line and possibly
the joint points are directly earthed.
3. STANDARDIZED SCREEN CONNECTION DIAGRAMS
Joints
Fig. 1Rigid earthing system
3.2 CROSS BONDED CONNECTION SYSTEMS
Fig. 2 describes the diagram to be used in the event of a major single section and Fig. 5
in the event of two major sections. With this system surge limiting devices are only necessary
at the intermediate points of discontinuity of the screens.
Fig. 2Cross bonting system
(1 Major section, 3 minor sections)
Minor sectionMinor section Minor section
Major section
15
Cross bondinglink boxeswith SVL
-
The SVL can be connected in the following manners (see Fig 9):
In a triangle, each of them being parallel with the continuity interruption space of each
screen.
In a star, with its centre connected to a local earth system or to the bonding conductor
(or to one of the conductors), if it exists (see section 2.3).
In a star, with its centre insulated.
Major section Major section
Fig. 3Continuous cross bonding system
(2 major sections, 6 minor sections)
16
Cross bonding link boxes with SVL
Fig. 9Detail of SVL box and screen crossing
Cross bondinglink boxwith SVL
SVL instar
SVL intriangle
-
3.3 SINGLE POINT EARTHING SYSTEMS
These systems, which can be made up of one or several sections, are characterized by the
discontinuity of the screens in some (or in all) the changes of section and by the joining
of the screens to each other and to earth in a single point within each section. Surge limiting
devices assembled in a star with centre earthed must be installed at each end of section
which does not coincide with the point of its earthing. There must be an earth continuity
conductor, and the earth connections, both of the screens and of the surge limiting devices,
must be carried out directly to this conductor (Figs. 6, 7 and 8).
17
Fig. 6Single point bonded system
(Earthing at one end)
Fig. 7Single point bonded system(Earthing at the middle point)
Earth continuity conductor
SVLlink boxes
Earth continuity conductor
Fig. 8Single point bonded system
(Earthing at both ends with interruptionof screen at the middle point)
SVLlink box
SVLlink box
Earth continuity conductor SVLlink box
-
4. ELEMENTS MAKING UP THE SCREEN CIRCUIT
(4) The connection boxes are of a watertight horizontal type, and are used in chests or galleries.The cupboards are of vertical type protected against the elements and used fastened to walls ofsubstations or metallic structures (pylons or towers).(5) An internal short-circuit generates a very considerable excess pressure. If the box breaks, thisexcess pressure will be transmitted to the chest (of small volume) and may be sufficient to pull offthe cover and cause an accident.
18
The elements necessary to establish the connections between the elements of the screen
circuit that each system requires, and for the subsequent verification of the screens, are
described below.
4.1 CONNECTION BOXES OR CUPBOARDS (4)
The ends of the junction cables and of the SVL (except the SVL connected directly between
sectioning insulation on terminals of equipment with metallic casing or on external terminals
see section 4.5.1), will be enclosed in connection boxes capable of containing the effects
of thermal or electric failure of any of the elements housed without damage being caused
to neighbouring external elements. In the cases of boxes installed in chests or enclosures
of small volume it is recommended that they should be capable of containing the effects
of an internal short-circuit.(5)
In the case of voltages of 245 kV upwards, with their corresponding high fault levels, it is
accepted that, in certain situations, the insulation of the SVL and of the connections may
not be capable of withstanding the conditions to which they are subjected in the event of
an internal fault of the line itself. When this situation is foreseen, additional measures should
be adopted to confine the consequences of this type of fault.
Metallic connection boxes should always be earthed, by means of a connection independent
from the earthing of the elements contained inside them (connections of the screens or of
the SVL) with a sufficient level of insulation. The internal insulation of the connection boxes
should fulfil the conditions of section 6.3.
The boxes or cupboards should be equipped with some means to prevent incorrect
connection positions and shall be equipped with a label which shows the normal connection
arrangement.
The connections of the terminals, junction cables and SVL must be designed so that they
can achieve and easily maintain the contact resistances of section 6.6 (d). The terminals
and junction cables must also fulfil the short-circuit resistance conditions given in the Table
of section 4.2.
-
4.1.1 Watertight connection boxes
They must fulfil protection grade IP68. Those which contain SVL and which are assembled
at ground level must be of a horizontal type, with covers equipped with adequate bolts for
installation in not very deep chests under the surface of the ground. The highest point of
the box assembled in a chest (without considering the lifting eyes) should not be more than
1 m below the level of the ground, to aid handling.
The boxes foreseen for external installation must be weatherproof and adequate for assembly
on watertight terminal support structures.
The metallic boxes must be earthed by means of connection to adjacent main earth
electrodes or to the earth bonding conductor. They can also be connected just to a local
earth system, independent from the main system, if the internal insulation of the box
guarantees an adequate safety level.
Each box should contain the elements of just one circuit.
4.1.2 Protected connection cupboards or boxes
All these boxes should fulfil protection grade IP54. When they are in vertical position they
are called cupboards. The cupboards should fulfil the following conditions:
(1) The back part of the cupboard should be a fixed panel.
(2) The door(s) should be closed by means of a security lock or an alternative method. When
the cupboard has two doors, only one of them needs to be blockable; the other door can
be secured by means of internal espagnolette bolts on the upper and lower part.
(3) Each circuit should have its own cables for connection to screens and to earth, SVL
and earth cables. These elements cannot be shared by two circuits.
When the cupboard is situated within the area of an important earth network (for example
of a substation), the internal earth bar should be connected to this network. If the cupboard
is metallic, it should also be connected to this earth network, it being possible to carry out
this connection to the earth bar inside it.
When the box is not situated thus (for example at joint points all along the cable run), the
earth bar to which the connecting cables are connected (by SVL, in the appropriate cases)
in normal operation should be connected to the earthing system of the location of the joint.
The box, if it is metallic, should be connected to its own local earth. The insulation between
the internal earth bar and the box should be adequate to resist the test level between
junction cable and earth specified under Point 6.3. The insulation between the casing of
the SVL and the box should also fulfil this condition.
When the box is metallic, its earth connection terminal shall be independent from the
elements housed in it. The set of connection devices may be covered by a transparent
methyl methacrylate insulating screen, or by another suitable material.
19
-
If higher values are foreseen in a specific installation, suitable larger sections should be adopted.
The connecting cables to be used should be:
In cable systems with rigid connection: All the connecting cables will be single-core.
In cable systems with special connection: Except in the cases which are indicated below,
all the connecting cables shall be concentric. In a joint with screen sectioning, the conductors
on both sides of the sectioning shall be the inside and the outside of the connecting cable.
In the terminals, the junction cables connected to the screens of the cables should be the
interior conductors of the concentric cables; the exterior conductors of the aforementioned
cables shall be connected in all cases to the metallic parts of the terminal support structures.
If metallic connection boxes are used, the exterior conductors of the concentric cables of
the terminals shall be connected in all cases to the metallic box.
4.2 JUNCTION CABLES BETWEEN SCREENS AND CONNECTION BOXESAND/OR SVL HOUSING
These cables must be made up of stranded copper conductors insulated with XLPE, andshould be one of the following types:
(i ) Single-core construction, in accordance with Table 1A.(ii) Concentric construction, in accordance with Table 1B.Tables 1A and 1B show the minimum section of connecting conductor associated with thenominal voltages and with the systems short-circuit current levels. The connecting cablesmust comply with the conditions of UNE-HD-603 in everything which is applicable to them,except as regards the testing voltages, which shall be those indicated under Point 6.4 ofthis recommendation.
The section of the connecting cables, both for the interior and exterior conductors of theconcentric cables and for the single-core cables in any type of connection, shall be determinedby the maximum value of the short-circuit current foreseen for the installation. Dependingon the highest voltage for the material, the minimum levels of this current to be taken intoaccount in the design of the connecting conductors are established in Tables 1A and 1B,as follows:
20
U 72,5 kV 16 kA for 1 second
72,5 kV < U 145 kV 25 kA for 1 second
145 kV < U 245 kV 40 kA for 1 second
245 kV < U 63 kA for 1 second
-
The SVL and their detachable connections can be situated directly on the pylon or metallic
support structure.
The connections should be designed to minimize the length of the cables. Whenever
possible, no concentric type connecting cable should be more than 10 m long.
Joints will not be accepted in the connecting conductors in new installations, but they can
be accepted in subsequent interventions, for example in maintenance or repair work.
The exceptional cases in which single-core connecting cables can be used in systems with
special screen connection are:
Junction cables used for the earthing of the screens of the cables at the common earthing
point of two sections with single-point connection, as shown in Fig. 7.
21
Fig. 7Single point bonded system(Earthing at the middle point)
Earth continuity conductor
Junction cables used in terminals normally earthed.
Junction cables used for earthing or other connections in the terminals in equipment
with metallic casings, as in Figs. 20, 21 and 22.
SVLlink box
SVLlink box
-
Fig. 10 Screen connection diagram in terminals with metallic casing
(Direct earthing)
22
Connections close to metallic casings
Blockableconnection box
assembledon frame
Main earth of the system orearth continuity conductor
The bridges must be connected directly to both sides of theseparation insulation and the metallic casings must beconnected to the main earth of the system.
NOTE:
Connection function:Element:Applicable to:
Direct earthingTerminal of the cableFor direct earthing in systems with class SF61insulated screen.
-
23
Fig. 11Screen connection diagram in terminals with metallic casing
(Direct earthing)
Connections far from metallic casings
Blockableconnection box
on frame
Connecting cableto pass through theCT (if appropriate)
Main earth of the system orearth continuity conductor
The SVL must be connected directly to both sides of theseparation insulation and the metallic casings must beconnected to the main earth of the system.
NOTE:
Connection function:Element:Applicable to:
Direct earthingTerminal of the cableDirect earthing in systems with class SF62insulated screen.
-
46
6.5 SHEATH VOLTAGE LIMITERS
The routine and maintenance tests on finished assemblies shall be as follows:
Zinc oxide units
The voltage test at AC 50Hz must be adapted to give a peak test intensity of
1.6 mA and the voltage measured must be within the range given below.
In the finished installation tests the visual examination must show that the junction cables
and the external surface of the unit or of the container are free from important protuberances
or from other signs of deterioration.
(a) Internal insulation resistances for SVL enclosures with earth cables.
The resistance between the earth cables and any metallic case should not be less than
10 M measured with a 1000 V megaohmmeter.
Type of limiter Peak voltage Peak voltage/2
(kV) (kV)
CPA-03 5,05 5,56 3,57 3,93
CPA-06 10,10 11,12 7,14 7,86
-
6.6 COMPLETE CIRCUITS ONCE INSTALLED
(a ) After installing a complete circuit tests shall be performed to ensure that the
screen and the sectioning insulation of the screen at all points are capable of
withstanding a rigidity test at direct voltage of 10 kV for 1 minute. The SVL should
be disconnected on performing these tests.
The connections and the earthing of the screens should also be checked.
(b ) It is recommended, at regular intervals, to test the integrity of the screen-earth
insulation at a direct voltage of 5 kV for 1 minute. The SVL should be checked
at the same time, in accordance with Point 6.5.
(c ) If there is an internal defect in a cable system with special connection, the tests
referred to in section (b) above should be carried out and the continuity of the
screen-earth metallic path should be checked before putting the cable back in
service.
(d ) After the installation a measurement should be taken of the resistance of all the
contacts of the junction cables of the screens in each connection box or cupboard,
using a digital microhmmeter. The contact resistance should not be greater than
20 .
The contact resistance of the SVL connections in the boxes or cupboards should
be measured in a similar manner and should not be greater than 50 .
When possible the contact resistance of the external earth cable should be
measured in a similar manner, and should not be greater than 50 .
Note
If a fault current has circulated through a cable system with special connection,
it is recommended at the first opportunity available to check the integrity of the
screen-earth insulation, the integrity of the connection cables and the characteristics
of the SVL.
47
-
48
Table 1A
CONSTRUCTION OF SCREEN CONNECTION SINGLE-CORE CABLES
*Also for connections of 132kV and 275kV systems not subjected to the short-circuit current, for example connections to SVL.
Table 1B
CONSTRUCTION OF SCREEN CONNECTION CONCENTRIC CABLES
12,8 13,3 17,8 18,7 20,2 21,0 26,4 28,0
1,2+2,0 19,2 20,7 1,7+1,0 23,4 25,3 1,8+1,0 25,8 27,9 2,2+3,0 36,8 39,7
24,4 26,4 33,6 36,3 36,0 38,9 47,4 51,2
1,8 28,4 30,7 1,8 37,6 40,6 2,1 40,6 43,8 2,4 52,6 56,8
Dimensions(mm)
Nominal sectionof the conductor
Voltage of the as-sociated system
Central conductor
XLPE Insul. +PVC internal sheath
30 up to 66 kV 132 kV 275 kV 400 kV
120* mm2 240 mm2 300 mm2 500 mm2
Concentricconductor
PE external sheath
Thickness Diameter
Min Max
Thickness Diameter
Min Max
Thickness Diameter
Min Max
Thickness Diameter
Min Max
12,8 13,3 17,8 18,7 20,2 21,0 26,4 28,0
1,2+1,5 18,2 19,7 1,7+1,7 24,6 26,6 1,8+1,8 27,4 29,6 2,2+2,0 35,3 38,1
Thickness Diameter
Min
Dimensions(mm)
Nominal sectionof the conductor
Voltage of the as-sociated system
Conductor
XLPE Insul. +PVC Sheath
Max
30 up to 66 kV 132 kV 275 kV 400 kV
120 mm2 240 mm2 300 mm2 500 mm2
Thickness Diameter
Min Max
Thickness Diameter
Min Max
Thickness Diameter
Min Max
-
49
7. EARTHING OF LIGHTNING ARRESTERS
7.1. INTRODUCTION.
The object of this chapter is to determine how lightning arresters should be connected to
earth in high voltage circuits.
The earthing is standardized by the substation regulation MIE RAT 13 Earthing installations
of the Regulation on Technical Conditions and Safety Guarantees in Electric Power Plants,
Transformer Stations and Substations. To summarize, this regulation says:
- In an installation there cannot be a live accessible point which can damage people,
whether under conditions of normal operation or in short-circuit. Consequently, any
cable which conducts current should be insulated.
- The earthing circuit cables which connect the electrodes should be bare, resistant
to corrosion and preferably visible.
- The dischargers have to be connected to the earth of the accessory that they
protect.
- The earth circuits should be straight without forced bends and as short as possible.
The earthing of lightning arresters (insulated cable or bare conductor) is not determined.
There is no reason to use one or another type of conductor.
Taking the case of a lightning arrester at the top of a support. The earth connection can
be carried out with an insulated cable or with a bare conductor, and in actual fact is carried
out in both ways depending on what the customer decides. It should be taken into account
that:
- It is preferable to use an insulated cable, which is on the safety side.
- In any case the customer can make any decision without it affecting the safety of
the circuit.
- We can opt for a bare cable, linked electrically and mechanically to the support
in short sections, which will not have problems of perforation of insulation in the event
of an important impulse.
-
50
7.2. CONNECTION TO THE EARTH CIRCUIT.
The connection of the different earthings indicated (direct earthing, earthing of the
discharger, earthing of the lightning arresters) will be carried out as follows:
The lightning arrester earthing cable can be the same for the three lightning arresters of
a circuit.
The same cable cannot be used for lightning arresters of different circuits.
The earth connection will be carried out to the earth cable indicated by the customer.
The connection elements must be suitable for the section of the conductor connected.
The project completion documentation must indicate where the connection of each circuit
is carried out.