Confidential Inspection Report LOCATED AT: 7555 E Morgan Battle Creek, Michigan PREPARED EXCLUSIVELY FOR: Option One Properties INSPECTED ON: Tuesday, July 16, 2013 Inspector, Edward Dunning Morgan Home Inspection LLC

Transcript of Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper...

Page 1: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

Confidential Inspection Report

LOCATED AT:

7555 E Morgan

Battle Creek, Michigan

PREPARED EXCLUSIVELY FOR:

Option One Properties

INSPECTED ON:

Tuesday, July 16, 2013

Inspector, Edward Dunning

Morgan Home Inspection LLC

Edward Dunning
Edward Dunning
Page 2: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

Executive Summary

This is a summary review of the inspector's findings during this inspection. However, it does not contain every

detailed observation. This is provided as an additional service to our client, and is presented in the form of a

listing of the items which, in the opinion of your inspector, merit further attention, investigation, or

improvement. Some of these conditions are of such a nature as to require repair or modification by a skilled

craftsman, technician, or specialist. Others can be easily handled by a homeowner such as yourself.

Often, following the inspector's advice will result in improved performance and/or extended life of the

component(s) in question. In listing these items, your inspector is not offering any opinion as to who, among

the parties to this transaction, should take responsibility for addressing any of these concerns. As with most of

the facets of your transaction, we recommend consultation with your Real Estate Professional for further

advice with regards to the following items:

Electrical System

GFI PROTECTION

Item #1: - No GFCI protection is installed. We recommend upgrading by installing ground fault receptacles in

all locations required by present standards. These include receptacles near sink basins, in bathrooms,

garages, crawl spaces, and the exterior. Pictures are as follows: kitchen, bath next to dining rm, bath room on

north wall next to bedroom, bathroom in between bedrooms east side. Bar sink in basement and outlet at

service panel.

� �

Page i

Page 3: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

� �

� �

Page ii

Page 4: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

Tuesday, July 16, 2013

Option One Properties

7555 E Morgan

Battle Creek, Michigan

Dear Option One Properties,

We have enclosed the report for the property inspection we conducted for you on Tuesday, July 16, 2013 at:

7555 E Morgan

Battle Creek, Michigan

Our report is designed to be clear, easy to understand, and helpful. Please take the time to review it carefully.

If there is anything you would like us to explain, or if there is other information you would like, please feel free

to call us. We would be happy to answer any questions you may have.

Throughout the report, you'll find special symbols at the front of certain comments. Below are the symbols and

their meanings:

� = Potentially serious issue that should be addressed.

� = Upgrade recommended, but not required

We thank you for the opportunity to be of service to you.

Sincerely,

Inspector, Edward Dunning

Morgan Home Inspection LLC

Edward Dunning
Edward Dunning
Edward Dunning
Edward Dunning
Page 5: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

Table of Contents ♾

Introduction......................................................................................................................................1

Introductory Notes............................................................................................................................2

Air Conditioning................................................................................................................................2

Heat..................................................................................................................................................3

Electrical System..............................................................................................................................6

Interior............................................................................................................................................10

Insulation/Energy............................................................................................................................15

Plumbing.........................................................................................................................................15

Roofing...........................................................................................................................................17

Structure.........................................................................................................................................19

Water Heater..................................................................................................................................20

Exterior/Site/Ground.......................................................................................................................21

Attic................................................................................................................................................25

Basement.......................................................................................................................................26

Bathroom........................................................................................................................................29

Bedroom.........................................................................................................................................31

Garage............................................................................................................................................32

Kitchen............................................................................................................................................33

Locations of Emergency Controls..................................................................................................33

Environmental Concerns................................................................................................................34

Conclusion......................................................................................................................................35

Page 6: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

Introduction

We have inspected the major structural components and mechanical systems for signs of significant non-

performance, excessive or unusual wear and general state of repair. The following report is an overview of

the conditions observed.

In the report, there may be specific references to areas and items that were inaccessible. We can make no

representations regarding conditions that may be present but were concealed or inaccessible for review. With

access and an opportunity for inspection, reportable conditions may be discovered. Inspection of the

inaccessible areas will be performed upon arrangement and at additional cost after access is provided.

We do not review plans, permits, recall lists, and/or government or local municipality documents. Information

regarding recalled appliances, fixtures and any other items in this property can be found on the Consumer

Product Safety website. These items may be present but are not reviewed.

Our recommendations are not intended as criticisms of the building, but as professional opinions regarding

conditions present. As a courtesy, the inspector may list items that they feel have priority in the Executive

Summary portion of the report. Although the items listed in this section may be of higher priority in the opinion

of the inspector, it is ultimately the client's responsibility to review the entire report. If the client has questions

regarding any of the items listed, please contact the inspector for further consultation.

Lower priority conditions contained in the body of the report that are neglected may become higher priority

conditions. Do not equate low cost with low priority. Cost should not be the primary motivation for performing

repairs. All repair and upgrade recommendations are important and need attention.

This report is a "snapshot" of the property on the date of the inspection. The structure and all related

components will continue to deteriorate/wear out with time and may not be in the same condition at the close

of escrow.

Anywhere in the report that the inspector recommends further review, it is strongly recommended that this be

done PRIOR TO THE CLOSE OF ESCROW. This report is not intended for use by anyone other than the

client named herein. No other persons should rely upon the information in this report. Client agrees to

indemnify, defend and hold inspector harmless from any third party claims arising out of client's unauthorized

distribution of the inspection report.

By accepting this inspection report, you acknowledge that you have reviewed and are in agreement with all of

the terms contained in the standard contract provided by the inspector who prepared this

report.

Page 1

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 7: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

Introductory Notes

ORIENTATION

For purposes of identification and reporting, the front of this building faces south.

NOTES

The house was estimated to be approximately 55 years old.

Over the course of this inspection the temperature was estimated to be between 80 and 100 degrees.

The weather was sunny at the time of our inspection.

Air Conditioning

An air conditioning system consists of the cooling equipment operating and safety controls and a means of

distribution. These items are visually examined for proper function, excessive or unusual wear, and general

state of repair. Air conditioning systems are not tested if the outside temperature is too cold for proper

operation. Detailed testing of the components of the cooling equipment or predicting their life expectancy

requires special equipment and training and is beyond the scope of this inspection. This is a non-evasive,

basic function review only. We do not dismantle, uncover or calculate efficiency of any system. Regular

servicing and inspection of air conditioning equipment is encouraged.

BASIC INFORMATION

Method of cooling: Evaporative cooling

Type of system: Gas heat with air conditioning

Number of units: 1

Condenser location: Rear of structure

HVAC WIRING

All accessible wiring appears in good condition. Electricity off to house

HVAC DISCONNECT

The local disconnect appears properly installed and in good condition.

CONDENSING UNIT

The condensing unit appears to be properly installed and in serviceable condition.

Shrubs are blocking the air circulation around the condensing unit. We recommend all shrubs be cut back to

provide three feet of clearance from the unit.

Page 2

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 8: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

DUCTS

Both the heating system and the central air conditioning system share the same duct work. Please see the

heating system for any comments regarding the duct work.

The ducts appear to be properly installed and are in serviceable condition.

THERMOSTAT

The thermostat appears to be properly installed and the unit responded to the user controls.

Heat

A heating system consists of the heating equipment, operating and safety controls, venting and the means of

distribution. These items are visually examined for proper function, excessive or unusual wear and general

state of repair. This is a non-evasive, basic function review only. We do not dismantle, uncover or calculate

efficiency of any system. Regular servicing and inspection of heating systems is encouraged.

Forced Hot Air

BASIC INFORMATION

Furnace location: Basement

Energy source: Natural gas

Furnace btu input rating: 125,000 btu's

Page 3

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 9: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

HEAT EXCHANGER

The heat exchanger was visually examined and we observed no cracks, holes or other conditions that would

indicate it is at the end of its service life.

BLOWER/MOTOR

The fan belt is deteriorated. We recommend it be replaced.

The fan belt is broken. We recommend it be replaced.

DUCTS

The ducts appear to be properly installed and are in serviceable condition.

Page 4

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 10: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

The ducts appear to be generally properly installed and are in serviceable condition, with exceptions noted

below. Small duct on right rear of furnace sub standard installation. See picture.

THERMOSTAT

The unit responded to the thermostat and it is generally properly installed, with exceptions noted below. Can

not operate no power in house.

HVAC DISCONNECT

We found underfusing in the local disconnect. There is no hazard but this condition may prove to be an

annoyance because of frequent and unnecessary tripping of the circuit. We recommend installation of proper

fuses. Furnace supply not fused at furnace.

Page 5

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 11: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

Electrical System

An electrical system consists of the service, distribution, wiring and convenience outlets (switches, lights, and

receptacles). Our examination of the electrical system includes the exposed and accessible conductors,

branch circuitry, panels, overcurrent protection devices, and a random sampling of convenience outlets. We

look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity

and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature of

the electrical wiring prevents inspection of every length of wire.

BASIC INFORMATION

Service entry into building: Overhead service drop

Voltage supplied by utility: 120/240 volts

Capacity (available amperage): 200 amperes

System grounding source: Driven copper rod

Branch circuit protection: Circuit breakers

Wiring material: Copper wiring where seen

Wiring method: Non-metallic sheathed cable or 'romex'

METER & MAIN

The meter and main electrical service panel are outside on the rear of the building.

ELECTRIC METER

The electric meter is outside on the rear of the building.

MAIN SERVICE

The main electrical service panel is outside on the rear of the building.

MAIN DISCONNECT

The main electrical service disconnect is outside the building in the rear.

SERVICE DROP

The service drop appears to be properly installed and in good condition.

CB MAIN PANEL

The main service panel is in good condition with circuitry installed and fused correctly.

Page 6

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 12: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

SERVICE GROUNDING

The system and equipment grounding appears to be correct.

BRANCH CIRCUITRY

The accessible branch circuitry was examined and appeared properly installed and in serviceable condition.

CONDUCTOR MATERIAL

The accessible branch circuit wiring in this building is copper.

RECEPTACLES: OVERALL

Based upon our inspection of a representative number, the receptacles were generally found to be in

serviceable condition and operating properly, with exceptions noted elsewhere. Missing cover plate in kitchen.

SWITCHES: OVERALL

We checked a representative number of switches and found they were operating and in serviceable condition.

Page 7

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 13: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

We checked a representative number of switches and found them operating and generally in serviceable

condition, with exceptions noted below. Missing cover plate in utility room.

LIGHTS: OVERALL

The light fixtures in this building are generally in serviceable condition, with exceptions noted below. Light in

front hall missing glass. Light fan in first bedroom to right broken globe.

� �

Page 8

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 14: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

GFI PROTECTION

No GFCI protection is installed. We recommend upgrading by installing ground fault receptacles in all

locations required by present standards. These include receptacles near sink basins, in bathrooms, garages,

crawl spaces, and the exterior. Pictures are as follows: kitchen, bath next to dining rm, bath room on north

wall next to bedroom, bathroom in between bedrooms east side. Bar sink in basement and outlet at service

panel.

� �

� �

Page 9

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 15: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

� �

GENERAL COMMENT

The electrical system is in good condition and the components are properly installed. No unsafe conditions

were observed in the readily accessible portions of the installation.

Interior

Our review of the interior includes inspection of walls, ceilings, floors, doors, windows, steps, stairways,

balconies and railings. These features are visually examined for proper function, excessive wear and general

state of repair. Some of these components may not be visible/accessible because of furnishings and/or

storage. In such cases these items are not inspected.

Page 10

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 16: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

SURFACES: OVERALL

The interior wall, floor, and ceiling surfaces were properly installed and generally in serviceable condition,

taking into consideration normal wear and tear. However curtains have been removed leaving damage to

walls.

� �

FLOORS: OVERALL

The floors have a good appearance and are in serviceable condition, with exceptions noted below. Most

carpet has stains or has reached the end of its serviceable life with the exception of the basement carpet that

contains foreign growth (mold). Floor in laundry 1/2 bath next to kitchen peeling and cracking.

� �

Page 11

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 17: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

� �

STAIRS

The stairs were used several times during the inspection. The various components appear to be properly

installed and no deficiencies were noted during use. The handrails were securely attached.

RAILINGS

The railings appear to properly installed and are in serviceable condition.

DOORS: OVERALL

The interior doors appear to be properly installed and in good condition, with exceptions noted below. Back

door missing correct window.

Page 12

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 18: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

� � The interior doors appear to be properly installed and in good condition, with the exception of the door

at the screen porch to kitchen entrance. This door should be replace due to blunt force.

WINDOWS: OVERALL

The windows tested appear to be properly installed and generally in serviceable condition, with exceptions

noted below or elsewhere in this report. Two screen porch windows broken or missing. Garage window

broken. Back bedroom windows cracked. Windows on south side or front of house have interior moisture

damage and need reglazing.

� �

Page 13

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 19: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

� �

� �

� �

Page 14

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 20: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

FIREPLACE

The fireplaces appear to be properly installed and in serviceable condition with no signs of excessive or

unusual wear.

DETECTORS: OVERALL

Only one detector found replacement needed for it. Remaining house needs detectors.

Insulation/Energy

Insulation, weatherstripping, dampers, double-glazed glass and set-back thermostats are features that help

reduce heat loss and/or gain and increase system and appliance efficiency. Our visual inspection includes

review to determine if these features are present in representative locations and we may offer suggestions for

upgrading. Our review of insulation is based upon uniformly insulated or are insulated to current standards. It

is our opinion that all homes could benefit from energy conservation upgrades, and we suggest that you

consult professionals.

ATTIC INSULATION

Due to access limitations, the insulation was only spot checked.

The level of insulation would appear to provide an R-19 insulating value. This provides only moderate

resistance to heat transfer and was the standard until recently. An insulation contractor could be consulted

regarding upgrading.

Plumbing

A plumbing system consists of the domestic water supply lines, drain, waste and vent lines and gas lines.

Inspection of the plumbing system is limited to visible faucets, fixtures, valves, drains, traps, exposed pipes

and fittings. These items are examined for proper function, excessive or unusual wear, leakage, and general

state of repair. The hidden nature of piping prevents inspection of every pipe and joint. A sewer lateral test,

necessary to determine the condition of the underground sewer lines, is beyond the scope of this inspection If

desired, a qualified individual could be retained for such a test. Our review of the plumbing system does not

include landscape watering, fire suppression systems, private water supply/waste disposal systems, or

recalled plumbing supplies. Review of these systems requires a qualified and licensed specialist.

BASIC INFORMATION

Domestic water source: Private well water

Landscape water source: Private well water

Main water line: Copper

Main water line: Galvanized steel

Page 15

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 21: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

Supply piping: Copper where seen

Waste disposal: Private on-site disposal

Waste disposal: Indeterminate

Waste piping: Cast iron and copper

Water pressure: Mid-range of normal water pressure

WATER SHUTOFF LOCATION

The domestic water supply main shut-off valve is on the front wall in the basement.

MAIN SUPPLY

There was no evidence of surface corrosion or leakage at the exposed and accessible main supply.

INTERIOR SUPPLY

The exposed and accessible supply piping generally appears to be properly installed and in good condition.

WATER PRESSURE

The system water pressure, as measured at the exterior hose bibs, is within the range of normal.

DRAIN LINES

The visible drain piping appears to be properly installed and in serviceable condition.

GAS METER COMMENT

There is no gas meter. This property is not served by a gas utility.

Page 16

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 22: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

GENERAL COMMENT

The plumbing system appears to be in good condition, with the exceptions noted above. Unusual drain

system for condensate from condenser which includes sump pump and trash can (pics 1 and 2). Substandard

piping connections below kitchen.

� �

Roofing

A roof system consists of the surface materials, connections, penetrations and drainage (gutters and

downspouts). We visually review these components for damage and deterioration and do not perform any

destructive testing. If we find conditions suggesting damage, improper application, or limited remaining service

life, these will be noted. We may also offer opinions concerning repair and replacement. Opinions stated

herein concerning the roof are based on a limited visual inspection. These do not constitute a warranty that

the roof is, or will remain, free of leaks.

Page 17

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 23: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

Composition Shingle

BASIC INFORMATION

Location: Covers whole building

Roof slope: Low pitch

Material: Asphalt composition shingle

Layers: Single layer

Roof drainage system: Gutters and downspouts

INSPECTION METHOD

Our inspection of this roof was conducted from the roof surface. The inspector walked upon the surface and

visually examined the accessible roofing components.

SURFACE

The roofing surface appears to have been properly installed and is in serviceable condition, with exceptions

noted below. Attention to the items listed, together with routine maintenance, will keep it functional and

maximize its useful life. One cap shingle above garage missing, see photo.

FLASHINGS: OVERALL

Metal flashing has been used to seal the connections and penetrations.

The accessible connection and penetration flashings appear to be properly installed and in serviceable

condition. All of the connections and penetrations should be periodically examined for signs of leakage and

repairs performed if necessary.

Page 18

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 24: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

CHIMNEY AT ROOF

The chimney appears to be properly installed and in serviceable condition.

There are no spark arrestors or rain caps above the flues to prevent the escape of hot embers or rain entry. As

an upgrade, we recommend that chimney cap/spark arrestors be installed.

The mortar cap shows signs of deterioration and should be replaced during routine property maintenance.

This deterioration will lead to moisture intrusion.

� �

SERVICE DROP

The service drop appears to be properly installed and in good condition.

DOWNSPOUTS

The downspouts appear to be properly installed and in serviceable condition.

Structure

The structural elements of a building include foundation, footings, all lower support framing and components,

wall framing and roof framing. These items are examined, where visible, for proper function, excessive or

unusual wear and general state of repair. Many structural components are inaccessible because they are

buried below grade or behind finishes. Therefore, much of the structural inspection is performed by identifying

resultant symptoms of movement, damage and deterioration. Where there are no visible symptoms, conditions

requiring further review or repair may go undetected and identification will not be possible. We make no

representations as to the internal conditions or stabilities of soils, concrete footings and foundations, except as

exhibited by their performance.

Page 19

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 25: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

BASIC INFORMATION

Exterior wall support: Concrete block

FOUNDATION

Due to the installation of finished surfaces, the slab is mostly inaccessible and could not be thoroughly

inspected. However, we observed no signs of significant settlement or related interior cracking to suggest a

major problem.

MOISTURE

We observed evidence of major seepage at the front (south) wall in basement below first bedroom to right. We

recommend a licensed engineer be retained to evaluate this condition and determine what corrective

measures are necessary. Photos are at corner above problem and resulting interior moisture.

� �

GENERAL COMMENT

All the visible structural elements appear to be in generally good condition and are performing as would be

expected for a building of this age and type of construction.

Water Heater

Our review of water heaters includes the tank, water and gas connections, electrical connections, venting and

safety valves. These items are examined for proper function, excessive or unusual wear, leakage and general

state of repair. We do not fully review tankless/on-demand systems and suggest you consult a specialist. The

hidden nature of piping and venting prevents inspection of every pipe, joint, vent and connection.

Page 20

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 26: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

BASIC INFORMATION

Location: In the basement

Energy source: Natural gas

Capacity: 40 gallons

Unit type: Free standing tank

Insulation: None present

T/P RELEASE VALVE

The water heater is equipped with a temperature and pressure relief valve. This device is an important safety

device and should not be altered or tampered with. We observed no adverse conditions.

GAS SUPPLY

The gas piping for the appliance includes a local 90 degree shut-off valve for use in an emergency or in case

of repair. The valve was not tested at the time of inspection, but is of a type usually found to be serviceable.

VENTING

The water heater vent is properly installed and appears in serviceable condition.

WATER CONNECTORS

The cold water inlet and hot water outlet connections appear properly installed and in serviceable condition.

Exterior/Site/Ground

FOUNDATION

The foundation and other visible elements of the support structure have performed well and are in good

condition for the age of the structure.

SERVICE DROP

The service drop appears to be properly installed and in good condition.

Page 21

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 27: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

MASONRY WALLS

The masonry walls appear to be properly installed and in good condition. Plants and bushes should be

trimmed back to at least one foot from walls to reduce moisture intrusion.

DOORS

The exterior doors appear to be properly installed and generally in serviceable condition, with exceptions

noted below. Doors need touch up painting.

� �

Page 22

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 28: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

WINDOWS

The windows appear to be properly installed and generally in serviceable condition. Some windows need paint

refreshed.

� �

GRADING

The grading of the lot appears to properly and adequately drain excess surface water and roof runoff away

from the structure.

Page 23

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 29: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

GUTTERS

Roof runoff water is channeled to the downspouts by a metal gutter system attached to the fascia boards or to

the ends of the rafters along the edge of the roof.

DRIVEWAY

The driveway is generally in good condition, however there is cracking caused by roots from adjacent

vegetation. To reduce the risk of driveway damage, pruning of the roots or removal of the vegetation may be

considered.

The minor cracks in the driveway are of a cosmetic nature only. No action is indicated.

DECK

The deck appears to be properly constructed and generally in serviceable condition, with exceptions noted

below. Deck nearing end of service period some board need to be replaced.

� �

Page 24

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 30: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

VEGETATION

We recommend the trees overhanging the roof be trimmed to prevent damage of the roofing surface, and

allow free flow of roof runoff.

Attic

The attic contains the roof framing and serves as a raceway for components of the mechanical systems.

There are often heating ducts, electrical wiring and appliance vents in the attic. We visually examine the attic

components for proper function, excessive or unusual wear, general state of repair, leakage, venting and

misguided improvements. Where walking in an unfinished attic can result in damage to the ceiling, inspection

is from the access opening only.

RAFTERS

The rafters are 2 x 6 placed 24 inches on center.

SHEATHING

The roof sheathing is plywood nailed solidly across the rafters.

ROOF TRUSSES

The trusses are generally in good condition, where seen, and have performed adequately since their

installation.

Page 25

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 31: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

VENT LINES

The vent piping for the waste system appears to be properly installed and in good condition.

DUCTS

The ducts appear to be properly installed and are in serviceable condition.

VENTILATION

The attic is adequately vented. Good ventilation helps reduce attic moisture levels and prevents condensation

on the underside of the roof. In addition, it reduces heat build-up in the attic, making the house more

comfortable.

Basement

The basement is where much of the building's structural elements and many of its mechanical systems are

located. These include foundation, structural framing, electrical, plumbing and heating. Each accessible

component and system is examined for proper function, excessive, or unusual wear and general state of

repair. It is not unusual to find occasional moisture in basements. Substantial and/or frequent water

accumulation can adversely affect the building foundation and support system and would indicate the need for

further evaluation by a specialist. Although observed in the basement, some items will be reported under the

individual systems to which the belong.

BASIC INFORMATION

Foundation material: Concrete block

Wall system: Wood stud walls

Page 26

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 32: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

WALLS

� There are stains from leakage on the basement walls. This appears to be a minor condition that may be

an annoyance but, in our opinion, is not structurally significant. We recommend monitoring during periods of

heavy rain. In addition moisture high on north block wall in utility area.

� �

MOISTURE

The basement was damp at the time of our inspection, however, there were no adverse conditions or damage

observed resulting from the moisture present to date.

To keep the moisture infiltration to a minimum, we recommend that all exterior surface drainage, including

water from the downspouts, be directed as far away from the building as possible. Watering landscaping

should be minimized and controlled.

Page 27

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 33: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

HOT WATER SHUTOFF

The domestic water supply main shut-off valve is on the front wall in the basement.

INTERIOR SUPPLY

The exposed and accessible supply piping generally appears to be properly installed and in good condition.

DRAIN LINES

The visible drain piping appears to be properly installed and in serviceable condition.

GAS PIPING

The gas piping appears to be properly installed and in serviceable condition. We detected no evidence of

leakage at any of the exposed gas piping. Pressure testing may reveal leaks, but this procedure is beyond the

scope of our inspection.

WIRING

There is an uncovered junction box in finished area north wall. In addition two open boxes on ceiling in utility

area. We recommend the box be covered to protect the wiring connections.

� �

Page 28

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 34: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

DUCTS

The ducts appear to be properly installed and are in serviceable condition.

A/C DUCTS

Both the heating system and the central air conditioning system share the same duct work. Please see the

heating system for any comments regarding the duct work.

Bathroom

Bathrooms are visually inspected for proper function of components, active leakage, excessive or unusual

wear and general state of repair. Fixtures are tested using normal operating features and controls. Due to

finished surfaces such as drywall/plaster, tile, and flooring, much of the bathroom is considered inaccessible.

We do not test or confirm proper application of secondary equipment including but not limited to steam units,

spa tubs, heated towel bars, etc.

Main Floor / Right

BASIC INFORMATION

Toilet: Ceramic unit with a porcelain finish

Page 29

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 35: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

INTERIOR WALLS

The walls are damaged behind toilet in first bathroom to right as you enter the house. We recommend repair

or refinishing. Same bathroom has substandard overflow drain putty.

� �

SHOWER WALLS

The shower walls appear to be properly installed and in serviceable condition.

GLASS ENCLOSURE

The glass shower enclosure is safety labeled and appears to be in good condition.

Main Floor / Rear

BASIC INFORMATION

Toilet: Ceramic unit with a porcelain finish

SHOWER

The shower was operated for the inspection and appeared to be in serviceable condition.

GLASS ENCLOSURE

The glass shower enclosure is safety labeled and appears to be in good condition.

Main Floor / Kitchen

Page 30

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 36: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

LIGHTS

The light fixture is damaged. We recommend it be replaced.

Basement

BASIC INFORMATION

Toilet: Ceramic unit with a porcelain finish

TOILET

The toilet may be leaking. We recommend that it be repaired or replaced.

Bedroom

Page 31

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 37: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

Bedroom

RECEPTACLES

The receptacles were found to be properly installed and in serviceable condition. The number of receptacles is

considered adequate for the size of the room.

SMOKE DETECTOR

There is no smoke detector in this area, as required. We recommend one be installed.

Garage

Garages and/or vehicle storage areas are visually inspected for general state of repair. Due to the presence of

the storage and personal property, our review of these areas is limited.

WIRING

Improper wiring methods have been employed. We recommend all substandard wiring be abandoned or

removed and properly installed using approved materials. Exterior wiring through window.

WALLS

The walls are drywall.

Page 32

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 38: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

The walls are damaged at the base between house and garage. We recommend repair or refinishing.

FIRE SEPARATION

The wall between the garage and the living space is of fire resistive construction as required by today's

building standards.

Kitchen

The kitchen is visually inspected for proper function of components, active leakage, excessive or unusual

wear, and general state of repair. We inspect built-in appliances to the extent possible using normal operating

controls. Freestanding stoves are operated, but refrigerators, small appliances, portable dishwashers, and

microwave ovens are not tested.

BASIC INFORMATION

Ventilation: None other than typical window

APPLIANCES: OVERALL

The secondary kitchen appliances (toasters, blenders, etc.) were not inspected and are not included in this

report. A qualified individual would have to be retained to provide detailed information concerning their

condition. Power not on.

Locations of Emergency Controls

In an emergency, you may need to know where to shut off the gas, the water and/or the electrical system. We

Page 33

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 39: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

have listed below these controls and their location for your convenience. We urge that you familiarize yourself

with their location and operation.

METER & MAIN

ELECTRICAL SYSTEM

The meter and main electrical service panel are outside on the rear of the building.

ELECTRIC METER

ELECTRICAL SYSTEM

The electric meter is outside on the rear of the building.

MAIN SERVICE

ELECTRICAL SYSTEM

The main electrical service panel is outside on the rear of the building.

MAIN DISCONNECT

ELECTRICAL SYSTEM

The main electrical service disconnect is outside the building in the rear.

WATER SHUTOFF LOCATION

PLUMBING

The domestic water supply main shut-off valve is on the front wall in the basement.

HOT WATER SHUTOFF

BASEMENT

The domestic water supply main shut-off valve is on the front wall in the basement.

Environmental Concerns

Environmental issues include but are not limited to radon, fungi/mold, asbestos, lead paint, lead

contamination, toxic waste, formaldehyde, electromagnetic radiation, buried fuel oil tanks, ground water

contamination and soil contamination. We are not trained or licensed to recognize or discuss any of these

materials. We may make reference to one of more of these materials in this report when we recognize one of

Page 34

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning
Page 40: Confidential Inspection Report · 2016-02-08 · look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection

the common forms of these substances. If further study or analysis seems prudent, the advice and services of

the appropriate specialists are advised.

Conclusion

COMMENTS

This structure appears to be very well built utilizing quality materials and professional workmanship. It is in

need of only typical maintenance and upgrading.

Page 35

The Report

7555 E Morgan

Battle Creek, Michigan

Tuesday, July 16, 2013

Copyright© 2010-2013, SPECTACULAR, Morgan Home Inspection LLC, Edward Dunning 1307-1

Edward Dunning