Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to...

106
Confidential Inspection Report LOCATED AT: 5410 Kendra Ct SE Lacey, Washington 98513 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON: Monday, May 6, 2019 Inspector, Isaac McPhee 1411 Strong Foundations Home Inspection

Transcript of Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to...

Page 1: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Confidential Inspection Report

LOCATED AT:5410 Kendra Ct SE

Lacey, Washington 98513

PREPARED EXCLUSIVELY FOR:Faira.com

INSPECTED ON:Monday, May 6, 2019

Inspector, Isaac McPhee 1411Strong Foundations Home Inspection

Page 2: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 2 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Executive Summary

This is a summary review of the inspectors' findings during this inspection. However, it does not contain every detailed observation. This is provided as an additional service to our client, and is presented in the form of a listing of the items which, in the opinion of your inspector, merit further attention, investigation, or improvement. Some of these conditions are of such a nature as to require repair or modification by a skilled craftsman, technician, or specialist. Others can be easily handled by a homeowner such as yourself.

Often, following the inspector's advice will result in improved performance and/or extended life of the component(s) in question. In listing these items, your inspector is not offering any opinion as to who, among the parties to this transaction, should take responsibility for addressing any of these concerns. As with most of the facets of your transaction, we recommend consultation with your Real Estate Professional for further advice with regards to the following items:

NOTESINTRODUCTORY NOTES

1: The home was occupied at the time of the inspection, with personal possessions in every room of the home. The presence of personal possessions limited the inspection. Access was denied to a number of wall and floor surfaces, electrical outlets, heat registers, and other items. We recommend a full walkthrough of the home after all items have been removed in order to provide a more thorough evaluation.

EXTERIOR PLUMBINGEXTERIOR/SITE/GROUND

2: One or more of the hose bib handles is damaged/missing. We recommend replacement for full usage of this feature.

3: The front hose bib appears to have been repaired in an unusual way, and may be prone to leaking. Recommend properly repairing or replacing the hose bib.

OUTDOOR RECEPTACLESEXTERIOR/SITE/GROUND

4: A receptacle cover plate at the front of the home is damaged. We recommend it be replaced during the course of normal maintenance.

PLYWOOD SIDINGEXTERIOR/SITE/GROUND

5: The plywood siding shows routine wear and some minor damage (primarily along lower edges) but is generally in serviceable condition. We recommend minor maintenance, including painting and caulking, to ensure maximum service life.

Page 3: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 3 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

HARDBOARD SIDINGEXTERIOR/SITE/GROUND

6: The siding (skin) on portions of this home is a hardboard/composite style system. Louisiana-Pacific, Weyerhaeuser, Masonite, Georgia-Pacific, and several others have a long history of problems. In this case, the siding on the home appears to be generally in functional condition, though with some indications of splitting or swelling that indicate maintenance may be necessary, as well as some surface damage, primarily along lower edges.

Even in areas where deterioration may not be present, ensure that the siding is properly painted and caulked, with specific focus on the bottom edges, which are prone to swelling.

The expected deterioration due to product defects may be reduced and even arrested by extensive preparation (wire brushing the leading edges), caulking, proper priming (elastomeric primers) and painting (mildew treatment added). Have the siding evaluated by a licensed painting contractor familiar with composite siding issues for a full cost estimate.

The limits of a physical/visual home inspection may necessitate the removal of a localized section of siding in order to determine if, or the extent of any moisture intrusion that may have occurred. The conditions reported are the result of a careful visual inspection. There is a possibility that other damage or conditions conducive to damage may be present that are not readily identifiable at visual means at the time of inspection. The home inspection report is not a warranty or guarantee that all damage or conducive conditions associated with the composition siding have been identified.

DOWNSPOUTSEXTERIOR/SITE/GROUND

7: Runoff water from the roof discharges next to the house in one or more locations. We recommend the downspouts be routed sufficiently away from the structure to prevent puddling, pooling, and saturation of the soil around the building.

DRIVEWAYEXTERIOR/SITE/GROUND

8: The minor cracks in the driveway are of a cosmetic nature. However, they do indicate movement in the soil and, over time, may develop into an aesthetic issue and/or a safety concern because of tripping hazards.

GATESEXTERIOR/SITE/GROUND

9: The gate at the front of the home is difficult to operate. We recommend repair or maintenance.

VEGETATIONEXTERIOR/SITE/GROUND

10: Some trees or shrubs were near or in contact with the home's siding. This can lead to moisture or pest damage. Recommend ensuring all trees and shrubs are trimmed away from the side of the home, at least 6 inches, in order to preserve the siding materials.

PAINT/STAINEXTERIOR/SITE/GROUND

11: Caulking was needed at several locations at the exterior. Recommend caulking as needed as part of regular maintenance.

Page 4: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 4 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

SURFACECOMPOSITION SHINGLE ROOFING

12: Some moss was observed growing on the roof surface. Moss tends to retain moisture and can damage the roof over a long period of time. Cleaning and treating the roof regularly will minimize damage to the sheathing. Moss treatments are most effective when performed during the wetter, growing seasons, such as spring and fall.

13: The roof is older and we observed evidence of cracked and/or deteriorated shingles on the ridge and throughout the field. In general, the roof appears to be nearing the end of its expected service life, and, though presently watertight, we advise budgeting for eventual roof replacement. Until roof is replaced, continue to monitor the roof surface for signs of unusual wear or tear that would indicate repairs are needed.

PLUMBING VENTSCOMPOSITION SHINGLE ROOFING

14: The neoprene "boot" flashings around one or more plumbing vents are showing signs of warping or cracking. This can lead to moisture entry into the attic. Recommend replacing all damaged plumbing boots.

RECEPTACLESGARAGE

15: Several of the receptacles are missing cover plates. We recommend they be replaced to reduce the risk of electrical shorts and hazardous shocks.

GARAGE DOORSGARAGE

16: Gaps in the weatherstripping at the base of the garage door were observed, which can allow pest entry into the garage. Recommend upgrading this seal.

LIGHTSKITCHEN

17: One of the stove-top lights beneath the microwave was not working at the time of the inspection. It is likely that the bulb is burned out. Replace the bulb and retest.

CABINETSKITCHEN

18: One cabinet door is damaged/disconnected. We recommend it be repaired or replaced.

DRAIN TRAPMAIN FLOOR MASTER BATHROOM

19: The flexible rubber or plastic fitting used in the drain trap is nonconforming. The system is functional, though flexible piping can be prone to clogging and can trap bacteria and other harmful substances. However, modification would be considered optional.

BATHTUBMAIN FLOOR MASTER BATHROOM

20: The bathtub is worn and the surface is chipped, suggesting its useful life is limited.

Page 5: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 5 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

SHOWERMAIN FLOOR MASTER BATHROOM

21: The showerhead fitting leaks and is in need of tightening.

SHOWER WALLSMAIN FLOOR MASTER BATHROOM

22: There was a gap behind the tub spout at the wall that could allow moisture entry. Recommend caulking this gap to prevent damage.

BATHROOM FLOORMAIN FLOOR MASTER BATHROOM

23: Caulking at the base of the tub or shower is in marginal condition. It is important to maintain the caulking around bathtubs and showers, especially at the intersection between the tub or shower and the floor. Failure to maintain this seal will often result in damage to flooring materials, subflooring and framing.

COUNTERTOPSMAIN FLOOR MASTER BATHROOM

24: The joint between the countertop and the backsplash is open and subject to moisture damage from water penetration. We recommend this joint be caulked and maintained to prevent water entry and subsequent damage.

DRAIN TRAPMAIN FLOOR HALLWAY BATHROOM

25: The flexible rubber or plastic fitting used in the drain trap is nonconforming. The system is functional, though flexible piping can be prone to clogging and can trap bacteria and other harmful substances. However, modification would be considered optional.

VENTILATIONMAIN FLOOR HALLWAY BATHROOM

26: The bathroom exhaust fan is visibly dirty. This can impede airflow and cause damage to the fan motor. Recommend cleaning fan.

VENTILATIONLAUNDRY AREA

27: The bathroom exhaust fan is visibly dirty. This can impede airflow and cause damage to the fan motor. Recommend cleaning fan.

SWITCHESMAIN FLOOR MASTER BEDROOM

28: There are switches for which no purpose was immediately obvious. We recommend inquiries of the owner to determine what is controlled by these switches.

DOORSMAIN FLOOR MASTER BEDROOM

29: The closet door rubs on the frame. We recommend it be planed or sanded for smoother operation.

30: The exterior door has a poor fit and is difficult to operate. We recommend the door be planed or sanded for smoother operation. After adjustment, all six sides must be sealed to prevent moisture intrusion and additional distortion.

Page 6: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 6 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

CLOSET DOORSMAIN FLOOR NORTHEAST BEDROOM

31: No closet door is installed in this area. We recommend a closet door be installed as an upgrade.

CLOSET DOORSMAIN FLOOR NORTH MIDDLE BEDROOM

32: No closet door is installed in this area. We recommend a closet door be installed as an upgrade.

WINDOWSMAIN FLOOR NORTH MIDDLE BEDROOM

33: There is condensation between the panes of glass of one double pane window. This indicates a failed seal. We recommend the lens assembly be replaced, which is the only method for correcting this deficiency.

SMOKE DETECTORMAIN FLOOR NORTH MIDDLE BEDROOM

34: There is no smoke detector in this area, as required. We recommend one be installed.

SWITCHESMAIN FLOOR LIVING ROOM ADDITIONAL ROOMS

35: There are switches for which no purpose was immediately obvious. We recommend inquiries of the owner to determine what is controlled by these switches.

DETECTORS: OVERALLINTERIOR

36: Several smoke or carbon monoxide detectors have been removed or have missing batteries. We recommend ensuring smoke/CO detectors are installed and operable throughout the home per modern building safety standards.

VENT LINESATTIC

37: Minor moisture entry was observed around one or more plumbing vents due to deteriorated flashings (see "Roof" section for more information). This condition should be resolved by replacing the plumbing flashing as needed.

VENTILATIONATTIC

38: There is evidence of improper or incomplete ventilation in portions of the attic. The lack of adequate ventilation, when combined with cold weather and high indoor relative humidity, causes water vapor produced inside the house to rise into the attic, causing condensation on the cold surfaces.

Staining/discoloration was observed on the attic sheathing in numerous locations. This is an indication of excess moisture and can be caused by many conditions such as current or prior leaks, condensation/humidity from lack of adequate ventilation, poorly sealed penetrations from the building envelope, such as attic hatches, light fixtures, fan units terminating into the attic, prior or current excessive moss, etc. Proper removal/remediation of the stained materials is recommended. The actual presence of mold can only be determined by proper testing, which is not part of this inspection.

Page 7: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 7 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

FOUNDATIONCRAWL SPACE

39: Hairline and/or small cracks, within normal tolerances, are visible. This type of cracking is often a result of shrinkage of materials and/or minor settlement and usually does not affect the strength of the foundation. No action is indicated.

VAPORT BARRIERCRAWL SPACE

40: The vapor barrier in the crawlspace is properly installed, but is torn in several areas, and dirty, with construction debris, rodent droppings, and other detritus. We recommend removing the existing vapor barrier and replacing with new black 6mm plastic to ensure a clean environment.

VENTILATIONCRAWL SPACE

41: One or more of the crawl space vent screens is torn; additionally, a very large gap was observed around the drain piping as it exits the crawlspace. We recommend any damaged screens be repaired or replaced and gaps be properly filled to prevent access by rodents or other pests.

PEST CONTROLCRAWL SPACE

42: Rodents, and possibly larger animals, have been active in the crawlspace. We recommend the crawlspace be cleaned by a qualified specialist, and that any gaps to the exterior be sealed and that bait or traps be set and monitored. The advice and services of a licensed exterminator would be recommended if problems persist.

BURNERSWATER HEATER

43: The burner flame is yellow tipped, suggesting too little primary air, clogged burner ports, misaligned burner orifices, and/or a clogged draft hood. We recommend that the unit be serviced, cleaned and tuned.

GENERAL COMMENTWATER HEATER

44: This water heater is near the end of its expected service life. Although operating, the need for replacement should be expected within the next few years.

HEAT EXCHANGERFORCED HOT AIR HEAT

45: There was limited access for visual inspection of the heat exchanger. Though the furnace was operating, based on the age of the unit, it is very important that the heat exchanger be more fully evaluated by a licensed HVAC technician. Even if no adverse conditions are noted, it is important that proper carbon monoxide detectors be installed in order to ensure notification if any damage occurs to the heat exchanger.

AIR FILTERSFORCED HOT AIR HEAT

46: The filter has accumulated debris which decreases its effectiveness and blocks air flow. This can dramatically decrease the efficiency of the heating system. We recommend the filter be removed, cleaned and replaced if necessary.

Page 8: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 8 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

HVAC DISCONNECTFORCED HOT AIR HEAT

47: There is no local disconnect in view of the equipment. We recommend that one be installed as required by present standards.

GENERAL COMMENTFORCED HOT AIR HEAT

48: The heating system responded to normal operating controls. Components appear to be properly installed and serviceable. This is an older system showing normal wear and tear, but we noted no conditions considered to be out of the ordinary. It is important to continue to monitor the furnace regularly as the unit ages, along with budgeting for eventual replacement.

49: The last service date of the gas forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if last service date was more than one year ago, recommend that a qualified HVAC technician inspect, clean, and service the system, and make repairs if necessary. For safety reasons, and because the system is fueled by gas, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC technician when it is serviced.

SWITCHES: OVERALLELECTRICAL SYSTEM

50: We tested a representative number of switches and found several to be without an obvious function. This is not necessarily a deficiency, but we suggest consultation with the owner as to their purpose.

FLOOR INSULATIONINSULATION/ENERGY

51: There are numerous fiberglass batts that have fallen out of place or been damaged by rodent activity. We recommend this material be secured back in place and any damaged material be replaced.

Page 9: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 9 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Monday, May 6, 2019Faira.com

5410 Kendra Ct SELacey, Washington 98513

Dear Faira.com,

We have enclosed the report for the property inspection we conducted for you on Monday, May 6, 2019 at:

5410 Kendra Ct SELacey, Washington 98513

Our report is designed to be clear, easy to understand, and helpful. Please take the time to review it carefully. If there is anything you would like us to explain, or if there is other information you would like, please feel free to call us. We would be happy to answer any questions you may have.

Throughout the report, you'll find special symbols at the front of certain comments. Below are the symbols and their meanings:

= Issue that should be addressed over the course of repairs/maintenance, but not time sensitive.

= Upgrade recommended, but not required

= Dangerous or potentially dangerous or hazardous situation that should be corrected as soon as possible.

= Item not operating at the time of the inspection, or unable to be inspected for another reason.

= Item that warrants continued monitoring or further evaluation by a licensed professional. Though issues may not necessarily exist at present or are not readily visible, ongoing monitoring or evaluation are recommended.

We thank you for the opportunity to be of service to you.

Sincerely,

Inspector, Isaac McPheeStrong Foundations Home Inspection

Page 10: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 10 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Page 11: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Table of Contents

Executive Summary.......................................................................................................................................2

Introduction..................................................................................................................................................12

Introductory Notes.......................................................................................................................................12

Exterior/Site/Ground....................................................................................................................................14

Roofing........................................................................................................................................................22

Garage.........................................................................................................................................................26

Kitchen.........................................................................................................................................................29

Bathroom.....................................................................................................................................................34

Laundry Area...............................................................................................................................................43

Bedroom......................................................................................................................................................45

Additional Rooms........................................................................................................................................55

Interior.........................................................................................................................................................58

Attic..............................................................................................................................................................60

Crawl Space................................................................................................................................................62

Plumbing......................................................................................................................................................65

Water Heater...............................................................................................................................................69

Heat.............................................................................................................................................................72

Electrical System.........................................................................................................................................77

Insulation/Energy.........................................................................................................................................81

Locations of Emergency Controls................................................................................................................82

Environmental Concerns.............................................................................................................................84

Conclusion...................................................................................................................................................84

Addenda......................................................................................................................................................86

Page 12: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 12 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Introduction

We have inspected the major structural components and mechanical systems for signs of significant non- performance, excessive or unusual wear and general state of repair. The following report is an overview of the conditions observed.

In the report, there may be specific references to areas and items that were inaccessible. We can make no representations regarding conditions that may be present but were concealed or inaccessible for review. With access and an opportunity for inspection, reportable conditions may be discovered. Inspection of the inaccessible areas will be performed upon arrangement and at additional cost after access is provided.

We do not review plans, permits, recall lists, and/or government or local municipality documents. Information regarding recalled appliances, fixtures and any other items in this property can be found on the Consumer Product Safety website. These items may be present but are not reviewed.

Our recommendations are not intended as criticisms of the building, but as professional opinions regarding conditions present. As a courtesy, the inspector may list items that they feel have priority in the Executive Summary portion of the report. Although the items listed in this section may be of higher priority in the opinion of the inspector, it is ultimately the client's responsibility to review the entire report. If the client has questions regarding any of the items listed, please contact the inspector for further consultation.

Lower priority conditions contained in the body of the report that are neglected may become higher priority conditions. Do not equate low cost with low priority. Cost should not be the primary motivation for performing repairs. All repair and upgrade recommendations are important and need attention.

This report is a "snapshot" of the property on the date of the inspection. The structure and all related components will continue to deteriorate/wear out with time and may not be in the same condition at the close of escrow.

Anywhere in the report that the inspector recommends further review, it is strongly recommended that this be done PRIOR TO THE CLOSE OF ESCROW. This report is not intended for use by anyone other than the client named herein. No other persons should rely upon the information in this report. Client agrees to indemnify, defend and hold inspector harmless from any third party claims arising out of client's unauthorized distribution of the inspection report.

By accepting this inspection report, you acknowledge that you have reviewed and are in agreement with all of the terms contained in the standard contract provided by the inspector who prepared this report.

Introductory Notes

ORIENTATIONFor purposes of identification and reporting, the front of this building faces south.

For purposes of identification and reporting, the front of the building is the side containing the primary access.

NOTESThe house was estimated to be approximately 23+ years old.

Page 13: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 13 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

The weather was sunny at the time of our inspection.

Over the course of this inspection the temperature was estimated to be between 50 and 60 degrees.

We make no representations as to the extent or presence of code violations, nor do we warrant the legal use of this building. This information would have to be obtained from the local building and/or zoning department.

A driveway and/or street is shared with other properties. To determine if maintenance-sharing or liability agreements are in effect regarding the driveway or street, consult the owner of the subject property, neighboring owners or public records.

There may be information pertinent to this property which is a matter of public record. A search of public records is not within the scope of this inspection. We recommend the client or their representative review all appropriate public records.

Review of the detached structure(s) is not a part of this inspection and report. With access and an opportunity for inspection, reportable conditions may be discovered.

The scope of this inspection is limited to reasonably accessible areas. We make no attempt to move furnishings, stored personal property, and/or vegetation. Although no problems are anticipated, removal of these items may reveal reportable items.

Your inspector may choose to include photos in your inspection report. There are times when only a picture can fully explain the condition or if the client is unable to attend the inspection. Photo inclusion is at the discretion of the inspector and in no way is meant to emphasize or highlight the only conditions that were seen. We always recommend full review of the entire inspection report.

The home was occupied at the time of the inspection, with personal possessions in every room of the home. The presence of personal possessions limited the inspection. Access was denied to a number of wall and floor surfaces, electrical outlets, heat registers, and other items. We recommend a full walkthrough of the home after all items have been removed in order to provide a more thorough evaluation.

Page 14: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 14 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Exterior/Site/Ground

BASIC INFORMATIONGeneral lot topography: Flat lotDriveway: Concrete on grade

Patio: Concrete

Primary exterior wall covering: Composite hardboard and T1-11 plywood siding

Primary exterior window material: Vinyl/plastic or vinyl clad

FOUNDATIONThe foundation and other visible elements of the support structure have performed well and are in good condition for the age of the structure.

Page 15: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 15 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

EXTERIOR PLUMBINGThe plumbing on the exterior of the building and in the yard appears to be properly installed and in serviceable condition, with exceptions noted below. We make no attempt to locate and test every hose bib. Testing of irrigation systems is beyond the scope of our inspection.

One or more of the hose bib handles is damaged/missing. We recommend replacement for full usage of this feature.

The front hose bib appears to have been repaired in an unusual way, and may be prone to leaking. Recommend properly repairing or replacing the hose bib.

OUTDOOR RECEPTACLESGFCI protection was working properly at exterior outlets where tested.

The GFCI protection for the exterior receptacles is provided by a GFCI receptacle located in the garage. We advise testing on a monthly basis.

Page 16: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 16 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

A receptacle cover plate at the front of the home is damaged. We recommend it be replaced during the course of normal maintenance.

OUTDOOR LIGHTSA representative number of exterior light fixtures were tested and found to be in working order.

PLYWOOD SIDING

The plywood siding shows routine wear and some minor damage (primarily along lower edges) but is generally in serviceable condition. We recommend minor maintenance, including painting and caulking, to ensure maximum service life.

Page 17: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 17 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

HARDBOARD SIDING

The siding (skin) on portions of this home is a hardboard/composite style system. Louisiana-Pacific, Weyerhaeuser, Masonite, Georgia-Pacific, and several others have a long history of problems. In this case, the siding on the home appears to be generally in functional condition, though with some indications of splitting or swelling that indicate maintenance may be necessary, as well as some surface damage, primarily along lower edges.

Even in areas where deterioration may not be present, ensure that the siding is properly painted and caulked, with specific focus on the bottom edges, which are prone to swelling.

The expected deterioration due to product defects may be reduced and even arrested by extensive preparation (wire brushing the leading edges), caulking, proper priming (elastomeric primers) and painting (mildew treatment added). Have the siding evaluated by a licensed painting contractor familiar with composite siding issues for a full cost estimate.

The limits of a physical/visual home inspection may necessitate the removal of a localized section of siding in order to determine if, or the extent of any moisture intrusion that may have occurred. The conditions reported are the result of a careful visual inspection. There is a possibility that other damage or conditions conducive to damage may be present that are not readily identifiable at visual means at the time of inspection. The home inspection report is not a warranty or guarantee that all damage or conducive conditions associated with the composition siding have been identified.

Page 18: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 18 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

DOORSThe exterior doors appear to be properly installed and in serviceable condition.

GRADINGThe grading of the lot appears to properly and adequately drain excess surface water and roof runoff away from the structure.

DRAINAGEThere is no drainage system for this property. The grading and soil conditions appear to be such that excessive surface water, subsurface moisture, and/or runoff has not been a problem. Consult owner/expert.

Page 19: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 19 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

DOWNSPOUTS

Runoff water from the roof discharges next to the house in one or more locations. We recommend the downspouts be routed sufficiently away from the structure to prevent puddling, pooling, and saturation of the soil around the building.

PUBLIC WORKSThe owner may have rights and responsibilities concerning the public improvements associated with this property. We suggest inquiries of the local public works department, particularly regarding liabilities for future maintenance costs.

The public sidewalks appear to be properly installed and are in serviceable condition.

Page 20: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 20 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

DRIVEWAY

The minor cracks in the driveway are of a cosmetic nature. However, they do indicate movement in the soil and, over time, may develop into an aesthetic issue and/or a safety concern because of tripping hazards.

PATIO SURFACEThe patio appears to be installed in a workmanlike manner and is in good condition.

FENCINGThe fences appear to be properly installed and in serviceable condition.

It should be stated that wood fences do have a finite service life. Maintaining the bases of the fence posts free and clear of rotting leaves, and an occasional treatment with a wood preservative will be most effective in prolonging service life.

GATES

The gate at the front of the home is difficult to operate. We recommend repair or maintenance.

Page 21: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 21 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

VEGETATION

Some trees or shrubs were near or in contact with the home's siding. This can lead to moisture or pest damage. Recommend ensuring all trees and shrubs are trimmed away from the side of the home, at least 6 inches, in order to preserve the siding materials.

TRIMThe exterior trim appears to be properly installed and is in good condition.

FASCIAThe fascia appears to be properly installed and in good condition.

EAVES/SOFFITSThe eaves and overhangs appear to be properly installed and in good condition.

PAINT/STAIN

Caulking was needed at several locations at the exterior. Recommend caulking as needed as part of regular maintenance.

Page 22: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 22 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

MISCELLANEOUSThere is a satellite dish on the property. The operation of the dish was not tested and is beyond the scope of this inspection.

GENERAL COMMENTThe exterior features of the building generally appear to be properly installed and in serviceable condition. Exceptions are discussed above and elsewhere in this report. Regular maintenance will prolong the service life of the 'weather shell'.

As preventive maintenance, caulking and sealing the gaps in the exterior of the building around the doors, windows, plumbing and electrical entry points will help prevent heat loss, cold air infiltration and moisture entry.

If caulking is needed for maintenance of any flashing or exterior trim, we suggest a high quality urethane sealant such as 'Sikaflex'. Latex, butyl, oil based, silicone or 'architectural grade' sealants should be avoided.

Roofing

A roof system consists of the surface materials, connections, penetrations and drainage (gutters and downspouts). We visually review these components for damage and deterioration and do not perform any destructive testing. If we find conditions suggesting damage, improper application, or limited remaining service life, these will be noted. We may also offer opinions concerning repair and replacement. Opinions stated herein concerning the roof are based on a limited visual inspection. These do not constitute a warranty that the roof is, or will remain, free of leaks.

Page 23: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 23 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Composition Shingle

BASIC INFORMATIONLocation: Covers whole building

Roof slope: MediumLayers: Single layerAge: Approximately 23+ years oldConnections and penetrations: Sealed with metal flashingRoof drainage system: Gutters and downspouts

INSPECTION METHODOur inspection of this roof was conducted from the roof surface. The inspector walked upon the surface and visually examined the accessible roofing components.

SURFACE

Some moss was observed growing on the roof surface. Moss tends to retain moisture and can damage the roof over a long period of time. Cleaning and treating the roof regularly will minimize damage to the sheathing. Moss treatments are most effective when performed during the wetter, growing seasons, such as spring and fall.

Page 24: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 24 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

The roof is older and we observed evidence of cracked and/or deteriorated shingles on the ridge and throughout the field. In general, the roof appears to be nearing the end of its expected service life, and, though presently watertight, we advise budgeting for eventual roof replacement. Until roof is replaced, continue to monitor the roof surface for signs of unusual wear or tear that would indicate repairs are needed.

Page 25: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 25 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

PLUMBING VENTS

The neoprene "boot" flashings around one or more plumbing vents are showing signs of warping or cracking. This can lead to moisture entry into the attic. Recommend replacing all damaged plumbing boots.

APPLIANCE VENTSThe appliance vents appear to be properly installed and in serviceable condition.

Page 26: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 26 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

GUTTERSRoof runoff water is channeled to the downspouts by a metal gutter system attached to the fascia boards or to the ends of the rafters along the edge of the roof.

The gutters are in serviceable condition, but should be checked for debris and cleaned on a regular basis to prolong their useful life.

GENERAL COMMENTThis roof is near the end of its expected service life. Although it is presently watertight, the need for replacement should be expected within the next few years.

For further evaluation of the conditions of the roof we recommend you consult a licensed roofing contractor.

Garage

Garages and/or vehicle storage areas are visually inspected for general state of repair. Due to the presence of the storage and personal property, our review of these areas is limited.

FRAMINGThe wall framing is not visible. The area around the garage door opening is generally the most vulnerable to movement but no adverse conditions were noted. The construction appears to be original and no action is indicated.

RECEPTACLESGFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

Page 27: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 27 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Several of the receptacles are missing cover plates. We recommend they be replaced to reduce the risk of electrical shorts and hazardous shocks.

GARAGE DOOR OPENERThe garage door opener(s) operated properly to raise and lower the doors, including the auto-reverse mechanisms, which stopped and reversed the direction of the doors when they struck objects in their path.

FLOORThe floor is a concrete slab.

Page 28: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 28 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

There is cracking in the floor slab but there is no vertical displacement of any portion of the slab. No action is indicated.

GARAGE DOORSThe garage door is a single roll up design.

Operation of the door(s) is controlled by a motorized mechanism, more commonly referred to as an automatic opener.

The garage door was operated and appears to be properly installed and in generally serviceable condition.

Gaps in the weatherstripping at the base of the garage door were observed, which can allow pest entry into the garage. Recommend upgrading this seal.

FIRE SEPARATIONThe wall between the garage and the living space is of fire resistive construction as required by today's building standards.

Page 29: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 29 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

GENERAL COMMENTThis area is in need of repair as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Kitchen

The kitchen is visually inspected for proper function of components, active leakage, excessive or unusual wear, and general state of repair. We inspect built-in appliances to the extent possible using normal operating controls. Freestanding stoves are operated, but refrigerators, small appliances, portable dishwashers, and microwave ovens are not tested.

BASIC INFORMATIONEnergy: Electric appliances onlyVentilation: Exhaust ducted to the exteriorRefrigerators, wine coolers, and other cooling appliances are beyond the scope of this inspection

Page 30: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 30 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

DRAIN TRAPSThe drain trap and associated piping are PVC plastic.

AIR GAPThe dishwasher drain is equipped with an air-gap fitting (the cylinder protruding above the sink). This assures separation of the supply water from the waste water.

SINKThe sink is metal.

The sink appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

Page 31: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 31 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

RECEPTACLESThe receptacles appear to be properly installed and were operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

LIGHTSThe overhead lights were tested and were operating properly at the time of the inspection.

One of the stove-top lights beneath the microwave was not working at the time of the inspection. It is likely that the bulb is burned out. Replace the bulb and retest.

FLOORThe wood or laminate/vinyl flooring is in serviceable condition. Kitchen floors receive the most concentrated wear of any area in the house, especially at the sink and stove. We recommend these areas be coated every two to three years as preventive maintenance.

Page 32: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 32 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

CABINETS

One cabinet door is damaged/disconnected. We recommend it be repaired or replaced.

COUNTERTOPSThe countertop is a plastic laminate.

The countertop shows typical wear and tear, normal for this heavily used component. We considered the flaws cosmetic in nature with no action indicated.

Page 33: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 33 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

VENTILATIONKitchen ventilation is provided by a range hood over the burners, venting to the exterior. The fan appears to be properly installed and in serviceable condition.

STOVEThe stove was turned on with the normal operating controls and found to be in satisfactory working condition.

OVENThe oven was turned on with the normal operating controls and found to be in satisfactory working condition.

DISPOSALThe disposal was turned on with normal user controls and observed to be in satisfactory working condition.

DISHWASHERThe dishwasher responded to normal user controls and was found in good condition.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Page 34: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 34 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Bathroom

Bathrooms are visually inspected for proper function of components, active leakage, excessive or unusual wear and general state of repair. Fixtures are tested using normal operating features and controls. Due to finished surfaces such as drywall/plaster, tile, and flooring, much of the bathroom is considered inaccessible. We do not test or confirm proper application of secondary equipment including but not limited to steam units, spa tubs, heated towel bars, etc.

Main Floor Master Bathroom

BASIC INFORMATIONToilet: Ceramic unit with a porcelain finish

Wash basin: Ceramic unit with a porcelain finish

Page 35: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 35 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Bathtub: Molded fiberglass

Shower walls: Molded fiberglass

DRAIN TRAPThe drain trap(s) and associated piping are PVC plastic.

The flexible rubber or plastic fitting used in the drain trap is nonconforming. The system is functional, though flexible piping can be prone to clogging and can trap bacteria and other harmful substances. However, modification would be considered optional.

Page 36: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 36 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

TOILETThe toilet was flushed and appeared to be functioning properly.

WATER BASINThe wash basin appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

BATHTUB

The bathtub is worn and the surface is chipped, suggesting its useful life is limited.

SHOWER

The showerhead fitting leaks and is in need of tightening.

RECEPTACLESThe receptacle appears to be properly installed and was operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

LIGHTSThe overhead lights were tested and found to be operational at the time of the inspection.

Page 37: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 37 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

SHOWER WALLSThe shower walls appear to be properly installed and generally in serviceable condition, with exceptions noted below.

There was a gap behind the tub spout at the wall that could allow moisture entry. Recommend caulking this gap to prevent damage.

BATHROOM FLOORThe finish floor in this bathroom is wood or laminate/vinyl.

Page 38: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 38 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Caulking at the base of the tub or shower is in marginal condition. It is important to maintain the caulking around bathtubs and showers, especially at the intersection between the tub or shower and the floor. Failure to maintain this seal will often result in damage to flooring materials, subflooring and framing.

We suggest the use of a quality sealant such as 'GE Sanitary Silicone' or 'Dow Corning 786' for bathroom caulking. Latex and 'latex with silicone' sealants are inferior materials and their use in bathrooms is strongly discouraged.

COUNTERTOPSThe countertop is granite or other hard-surface material, such as quartz.

The joint between the countertop and the backsplash is open and subject to moisture damage from water penetration. We recommend this joint be caulked and maintained to prevent water entry and subsequent damage.

Page 39: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 39 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

VENTILATIONVentilation in this bathroom is provided by a ceiling fan. This fan was operated and was found to be working satisfactorily.

GENERAL COMMENTThis area is in need of repair as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Page 40: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 40 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Main Floor Hallway Bathroom

BASIC INFORMATIONToilet: Ceramic unit with a porcelain finish

Wash basin: Ceramic unit with a porcelain finish

Bathtub: Molded fiberglass

Page 41: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 41 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Shower walls: Molded fiberglass

DRAIN TRAPThe drain trap(s) and associated piping are PVC plastic.

The flexible rubber or plastic fitting used in the drain trap is nonconforming. The system is functional, though flexible piping can be prone to clogging and can trap bacteria and other harmful substances. However, modification would be considered optional.

TOILETThe toilet was flushed and appeared to be functioning properly.

WATER BASINThe wash basin appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

There is no overflow drain. Without an overflow drain, wash basin overflow is possible. The wash basin should never be filled while unattended.

BATHTUBThe bathtub appears to be properly installed and in serviceable condition.

SHOWERThe shower was operated for the inspection and appeared to be in serviceable condition.

Page 42: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 42 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

RECEPTACLESThe receptacle appears to be properly installed and was operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

LIGHTSThe overhead lights were tested and found to be operational at the time of the inspection.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

SHOWER WALLSThe shower walls appear to be properly installed and in serviceable condition.

BATHROOM FLOORThe finish floor in this bathroom is wood or laminate/vinyl.

COUNTERTOPSThe countertop shows typical wear and tear, normal for this heavily used component. We considered the flaws cosmetic in nature with no action indicated.

VENTILATIONVentilation in this bathroom is provided by a ceiling fan. This fan was operated and was found to be working satisfactorily.

Page 43: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 43 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

The bathroom exhaust fan is visibly dirty. This can impede airflow and cause damage to the fan motor. Recommend cleaning fan.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Laundry Area

Laundry areas and/or laundry rooms are visually inspected for general state of repair. Due to their hidden nature, we do not review appliances, connections, hookups, or venting.

RECEPTACLESThe receptacle appears to be properly installed and was operational.

Page 44: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 44 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

VENTILATION

The bathroom exhaust fan is visibly dirty. This can impede airflow and cause damage to the fan motor. Recommend cleaning fan.

DRYER VENTThe dryer vent appears properly installed and in serviceable condition.

Page 45: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 45 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

WASHER/DRYERThe hookups for the washer and dryer are properly installed and in serviceable condition. The appliances themselves were not tested.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Bedroom

Main Floor Master Bedroom

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

Page 46: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 46 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

SWITCHES

There are switches for which no purpose was immediately obvious. We recommend inquiries of the owner to determine what is controlled by these switches.

LIGHTS / FANThe overhead lights and/or ceiling fan were tested and appeared operational at the time of the inspection.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

Page 47: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 47 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

FLOORThe wood or laminate/vinyl flooring appears properly installed and in good condition.

DOORS

The closet door rubs on the frame. We recommend it be planed or sanded for smoother operation.

The exterior door has a poor fit and is difficult to operate. We recommend the door be planed or sanded for smoother operation. After adjustment, all six sides must be sealed to prevent moisture intrusion and additional distortion.

Page 48: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 48 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

SMOKE DETECTORThe smoke detector in this area appeared to be properly located and installed.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Main Floor Northeast Bedroom

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

Page 49: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 49 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

LIGHTS / FANThe overhead lights and/or ceiling fan were tested and appeared operational at the time of the inspection.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

FLOORThe wood or laminate/vinyl flooring appears properly installed and in good condition.

Page 50: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 50 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

CLOSET DOORS

No closet door is installed in this area. We recommend a closet door be installed as an upgrade.

SMOKE DETECTORThe smoke detector in this area appeared to be properly located and installed.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Page 51: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 51 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Main Floor North Middle Bedroom

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

LIGHTS / FANThe overhead lights and/or ceiling fan were tested and appeared operational at the time of the inspection.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

FLOORThe wood or laminate/vinyl flooring appears properly installed and in good condition.

Page 52: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 52 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

CLOSET DOORS

No closet door is installed in this area. We recommend a closet door be installed as an upgrade.

WINDOWS

There is condensation between the panes of glass of one double pane window. This indicates a failed seal. We recommend the lens assembly be replaced, which is the only method for correcting this deficiency.

SMOKE DETECTOR

There is no smoke detector in this area, as required. We recommend one be installed.

Page 53: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 53 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

GENERAL COMMENTThis area is in need of repair as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Main Floor Northwest Bedroom

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

LIGHTS / FANThe overhead lights and/or ceiling fan were tested and appeared operational at the time of the inspection.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

Page 54: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 54 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

FLOORThe wood or laminate/vinyl flooring appears properly installed and in good condition.

SMOKE DETECTORThe smoke detector in this area appeared to be properly located and installed.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection.

Page 55: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 55 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Additional Rooms

Main Floor Living Room Additional Rooms

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

SWITCHES

There are switches for which no purpose was immediately obvious. We recommend inquiries of the owner to determine what is controlled by these switches.

LIGHTSThere is no ceiling fixture in portions of this room. Building practices require the ability to turn on a light from a switch in every room. In this case, one of the receptacles is connected to the switch, allowing control of a cord connected lamp.

HEAT OUTLETThe heating outlet is blocked, preventing the flow of conditioned air into this area. We recommend the outlet be cleared of all debris.

Page 56: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 56 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

FLOORThe wood or laminate flooring appeared properly installed and in good condition at the time of the inspection.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Page 57: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 57 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Main Floor Family Room Additional Rooms

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

LIGHTSThe light fixtures in this room were tested and appeared operational at the time of the inspection.

HEAT OUTLETThe heating outlet(s) is/are in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

FLOORThe wood or laminate flooring appeared properly installed and in good condition at the time of the inspection.

Page 58: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 58 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Interior

Our review of the interior includes inspection of walls, ceilings, floors, doors, windows, steps, stairways, balconies and railings. These features are visually examined for proper function, excessive wear and general state of repair. Some of these components may not be visible/accessible because of furnishings and/or storage. In such cases these items are not inspected.

BASIC INFORMATIONNumber of bedrooms: FourNumber of bathrooms: TwoWindow material: VinylWindow type: Horizontal sliding windowsWindow glazing: Double panePrimary finished ceiling material: DrywallFinished floor material: Wood or laminate/vinylPrimary finished wall material: Drywall

Page 59: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 59 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

WALLS & CEILINGSThe interior wall and ceiling blemishes are cosmetic and can be repaired in the course of routine maintenance.

FLOORS: OVERALLThe floors have a good appearance and are in serviceable condition.

DOORS: OVERALLThe interior doors appear to be properly installed and in good condition, with exceptions noted below.

WINDOWS: OVERALLWe operate a representative sample of the windows, but do not necessarily open, close, and latch every window. Our inspection standards require testing a minimum of one window in every room.

The windows tested appear to be properly installed and generally in serviceable condition, with exceptions noted below or elsewhere in this report.

DETECTORS: OVERALLThe smoke detectors were inspected for location only. For future reference, testing with only the built-in test button verifies proper battery and horn function, but does not test the smoke sensor. We advise testing with real or simulated smoke.

Several smoke or carbon monoxide detectors have been removed or have missing batteries. We recommend ensuring smoke/CO detectors are installed and operable throughout the home per modern building safety standards.

HEAT SOURCEWe observed a permanent heat source in each room throughout the building.

GENERAL COMMENTThe interior surfaces, hardware, fixtures, doors and windows appear to be properly installed and generally in serviceable condition, with exceptions noted above.

There is wear and tear that is typical of the age of the home. We make no attempt to list all cosmetic flaws and suggest that most of these deficiencies will be addressed by normal maintenance and upgrading.

Page 60: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 60 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Attic

The attic contains the roof framing and serves as a raceway for components of the mechanical systems. There are often heating ducts, electrical wiring and appliance vents in the attic. We visually examine the attic components for proper function, excessive or unusual wear, general state of repair, leakage, venting and misguided improvements. Where walking in an unfinished attic can result in damage to the ceiling, inspection is from the access opening only.

ACCESS/ENTRYAttic access hatches are located in the laundry room and the garage.

Because of the vaulted, or 'cathedral', ceiling design in portions of the building, these areas did not include an accessible attic space. The roof structure and related building components in these areas could not be inspected.

SHEATHINGThe roof sheathing is the material directly supporting the roof covering.

The roof sheathing is 'OSB' - Oriented Strand Board, nailed solidly across the rafters.

ROOF TRUSSESRoof trusses support the roof sheathing and roof covering, transferring loads to the bearing walls. The bottom of a truss supports the finished ceiling. Trusses are usually engineered components assembled in a factory and delivered to the site.

Page 61: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 61 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

The trusses are generally in good condition, where seen, and have performed adequately since their installation.

VENT LINES

Minor moisture entry was observed around one or more plumbing vents due to deteriorated flashings (see "Roof" section for more information). This condition should be resolved by replacing the plumbing flashing as needed.

Page 62: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 62 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

VENTILATIONOur feeling regarding attic ventilation is that 'you can never have too much'. Attic ventilation can be provided by eave, gable, and ridge vents as well as by automatic and wind driven fans. We encourage use of any or all of the above.

There is evidence of improper or incomplete ventilation in portions of the attic. The lack of adequate ventilation, when combined with cold weather and high indoor relative humidity, causes water vapor produced inside the house to rise into the attic, causing condensation on the cold surfaces.

Staining/discoloration was observed on the attic sheathing in numerous locations. This is an indication of excess moisture and can be caused by many conditions such as current or prior leaks, condensation/humidity from lack of adequate ventilation, poorly sealed penetrations from the building envelope, such as attic hatches, light fixtures, fan units terminating into the attic, prior or current excessive moss, etc. Proper removal/remediation of the stained materials is recommended. The actual presence of mold can only be determined by proper testing, which is not part of this inspection.

Crawl Space

The crawl space is where most of the building's structural elements and portions of its mechanical systems are located. These include foundation, structural framing, electrical, plumbing and heating. Each accessible and visible component and system is examined for proper function, excessive or unusual wear and general state of repair. It is not unusual to find occasional moisture and dampness in crawl spaces. Significant and/or frequent water accumulation can adversely affect the building foundation and support system and would indicate the need for further evaluation by a specialist. Although observed in the crawl space, some items will be reported under the individual systems to which they belong.

BASIC INFORMATIONFoundation type: Raised perimeter with isolated piers

Page 63: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 63 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Foundation material: Poured concrete

Mudsill: Inaccessible, unknown if bolted, nailed or strappedWall system: Wood stud wallsFloor system: Wood joists support by beams

ACCESSThe crawl space is accessible through an interior closet.

FOUNDATION

Hairline and/or small cracks, within normal tolerances, are visible. This type of cracking is often a result of shrinkage of materials and/or minor settlement and usually does not affect the strength of the foundation. No action is indicated.

MUDSILLThe mudsill is the first wood member of the framing, resting directly on the foundation. The accessible sections of mudsill are in good condition.

FLOOR JOISTSIn the areas where the floor framing is visible, all components appear to be properly installed and in good condition.

Page 64: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 64 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

POSTSThe floor system is supported by wooden posts set over concrete pier blocks.

The support posts have performed adequately over time and would be expected to continue to do so.

ANCHOR BOLTSAnchor bolts are fasteners that connect the wood framing to the foundation. They limit the framing's ability to move independently on the foundation in the event of seismic activity.

Because of the design and/or configuration of the structure, we cannot verify the presence or condition of anchor bolts. Because of the age of the structure, we assume that proper bolting was installed, as per standards in effect at the time.

MOISTUREThe soil was dry at the time of our inspection, and there were no adverse conditions or damage observed related to excessive moisture.

Page 65: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 65 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

VAPORT BARRIER

The vapor barrier in the crawlspace is properly installed, but is torn in several areas, and dirty, with construction debris, rodent droppings, and other detritus. We recommend removing the existing vapor barrier and replacing with new black 6mm plastic to ensure a clean environment.

VENTILATION

One or more of the crawl space vent screens is torn; additionally, a very large gap was observed around the drain piping as it exits the crawlspace. We recommend any damaged screens be repaired or replaced and gaps be properly filled to prevent access by rodents or other pests.

PEST CONTROL

Rodents, and possibly larger animals, have been active in the crawlspace. We recommend the crawlspace be cleaned by a qualified specialist, and that any gaps to the exterior be sealed and that bait or traps be set and monitored. The advice and services of a licensed exterminator would be recommended if problems persist.

GENERAL COMMENTAll of the structural elements appear to be performing as would be expected for a dwelling of this age and type. However, we direct your attention to items noted above in need of repair or upgrading.

Plumbing

A plumbing system consists of the domestic water supply lines, drain, waste and vent lines and gas lines.

Page 66: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 66 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Inspection of the plumbing system is limited to visible faucets, fixtures, valves, drains, traps, exposed pipes and fittings. These items are examined for proper function, excessive or unusual wear, leakage, and general state of repair. The hidden nature of piping prevents inspection of every pipe and joint. A sewer lateral test, necessary to determine the condition of the underground sewer lines, is beyond the scope of this inspection If desired, a qualified individual could be retained for such a test. Our review of the plumbing system does not include landscape watering, fire suppression systems, private water supply/waste disposal systems, or recalled plumbing supplies. Review of these systems requires a qualified and licensed specialist.

BASIC INFORMATIONDomestic water source: Public supply

Main water line: Copper where seen

Supply piping: Copper where seenWaste disposal: Municipal

Page 67: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 67 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Waste piping: Plastic where seen

Water pressure: Mid-range of normal water pressure

WATER SHUTOFF LOCATIONThe domestic water supply main shut-off valve is located below the master bathroom sink.

WATER SHUTOFF COMMENTSThe main shut-off valve was located but testing the operation of this valve is not within the scope of our inspection. Operation of the valve from time to time will keep it functional and maximize its useful life.

INTERIOR SUPPLYThe exposed and accessible supply piping generally appears to be properly installed and in good condition.

WATER PRESSUREThe system water pressure, as measured at the exterior hose bibs, is within the range of normal.

DRAIN LINESThe visible drain piping appears to be properly installed and in serviceable condition.

Page 68: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 68 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

SEWER CLEANOUTThe sewer cleanout is located in the crawl space.

VENT LINESThe vent piping for the waste system appears to be properly installed and in good condition.

GAS PIPINGThe gas piping appears to be properly installed and in serviceable condition. We detected no evidence of leakage at any of the exposed gas piping. Pressure testing may reveal leaks, but this procedure is beyond the scope of our inspection.

GAS METER LOCATIONThe gas meter is outside on the left side of the building. The main gas supply shutoff valve is located on the riser pipe between the ground and the meter. This valve should be turned 90 degrees (either way) in order to shut off the gas.

GENERAL COMMENTThe plumbing system appears to be in good condition.

A representative number of fixtures were operated and we observed reasonable flow when other fixtures were operated simultaneously.

A representative number of drains were tested and each emptied in a reasonable amount of time and did not overflow when other fixtures were drained simultaneously.

Page 69: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 69 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

The supply piping is copper where seen. Copper is generally considered a very desirable type of piping and is expected to last the lifetime of the building.

Water Heater

Our review of water heaters includes the tank, water and gas connections, electrical connections, venting and safety valves. These items are examined for proper function, excessive or unusual wear, leakage and general state of repair. We do not fully review tankless/on-demand systems and suggest you consult a specialist. The hidden nature of piping and venting prevents inspection of every pipe, joint, vent and connection.

BASIC INFORMATIONLocation: In the garage

Energy source: Natural gasCapacity: 38 gallonsAge: Estimated to be 12+ years oldUnit type: Free standing tankWater heater temperature settings should be maintained in the mid-range to avoid injury from scaldingInsulation: Yes, installed behind outer jacket

T/P RELEASE VALVEThe water heater is equipped with a temperature and pressure relief valve. This device is an important safety device and should not be altered or tampered with. We observed no adverse conditions.

Page 70: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 70 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

EXPANSION TANKThe water heater is equipped with an expansion tank that appears properly installed and in serviceable condition. However, review of this equipment is beyond the scope of this inspection.

GAS SUPPLYThe gas piping for the appliance includes a local 90 degree shut-off valve for use in an emergency or in case of repair. The valve was not tested at the time of inspection, but is of a type usually found to be serviceable.

The gas connector is an approved flexible type in good condition.

Page 71: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 71 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

VENTINGThe water heater vent is properly installed and appears in serviceable condition.

COMBUSTION AIRCombustion air provides the oxygen for fuel burning appliances. Adequate ventilation around all fuel burning appliances is vital for their safe operation. The air can come from inside or outside, providing industry standards are met.

The combustion air supply is adequate.

BURNERS

The burner flame is yellow tipped, suggesting too little primary air, clogged burner ports, misaligned burner orifices, and/or a clogged draft hood. We recommend that the unit be serviced, cleaned and tuned.

WATER CONNECTORSThe cold water inlet and hot water outlet connections appear properly installed and in serviceable condition.

SEISMIC RESTRAINTThe water heater tank has been secured. This feature will help prevent water heater movement and possible gas leakage, limit damage and provide a source of usable domestic water in the event of a major earthquake.

Page 72: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 72 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

ELEVATION/LOCATIONThe water heater has been elevated above the garage floor in accordance with present standards. This is a beneficial configuration which helps prevent the ignition of fumes from spilled flammable liquids.

INSULATIONThere is no insulation blanket installed. Newer water heaters have built-in insulation to meet rigorous conservation standards. Installation of a blanket can be done but offers very little improvement on the existing efficiency of the unit.

GENERAL COMMENT

This water heater is near the end of its expected service life. Although operating, the need for replacement should be expected within the next few years.

Heat

A heating system consists of the heating equipment, operating and safety controls, venting and the means of distribution. These items are visually examined for proper function, excessive or unusual wear and general state of repair. This is a non-evasive, basic function review only. We do not dismantle, uncover or calculate efficiency of any system. Regular servicing and inspection of heating systems is encouraged.

Page 73: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 73 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Forced Hot Air

BASIC INFORMATIONFurnace location: Garage

Energy source: Natural gasFurnace btu input rating: 60,000 btu'sAge: 23+ years oldManufacturer: American Standard

SYSTEM NOTESForced air furnaces operate by heating a stream of air moved by a blower through a system of ducts. Important elements of the system include the heat exchanger, exhaust venting, blower, controls, ducting, and combustion air supply.

GAS SUPPLYThe gas piping includes a 90 degree shutoff valve for emergency use. The valve was not tested at the time of inspection. This age and style of valve is normally found to be operable by hand and generally trouble free.

The gas connector is an approved flexible type in good condition.

Page 74: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 74 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

BURNERSThe burners were inspected and found to be clean and in good working order.

HEAT EXCHANGER

There was limited access for visual inspection of the heat exchanger. Though the furnace was operating, based on the age of the unit, it is very important that the heat exchanger be more fully evaluated by a licensed HVAC technician. Even if no adverse conditions are noted, it is important that proper carbon monoxide detectors be installed in order to ensure notification if any damage occurs to the heat exchanger.

IGNITION SYSTEMThe heating unit is equipped with an electronic ignition system, which is an energy saving feature that allows operation without the need for a continuously burning pilot light.

AIR FILTERSThe air filter for the heating unit is a conventional, disposable filter.

There is no air filter at the heating unit itself. Instead, for ease of access, the filter is located just behind the return air grill in the living room.

Page 75: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 75 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

The filter has accumulated debris which decreases its effectiveness and blocks air flow. This can dramatically decrease the efficiency of the heating system. We recommend the filter be removed, cleaned and replaced if necessary.

CLEARANCEThere is adequate clearance to combustible materials in the area around the heating unit as long as the space is not used for storage. We encourage good housekeeping practices in this area.

VENTThe heating system vent is properly installed and appears in serviceable condition where seen.

COMBUSTION AIRCombustion air provides the oxygen for fuel burning appliances. Adequate ventilation around all fuel burning appliances is vital for their safe operation. The air can come from inside or outside, providing industry standards are met.

There is adequate combustion air for this heating unit.

DUCTSThe ducts appear to be properly installed and are in serviceable condition.

Page 76: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 76 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

THERMOSTATThe thermostat appears to be properly installed and the unit responded to the basic controls. This is a programmable device with many options for setback settings, timed events, etc. No attempt was made to test all functions of the thermostat.

HVAC WIRINGAll accessible wiring appears in good condition.

HVAC DISCONNECT

There is no local disconnect in view of the equipment. We recommend that one be installed as required by present standards.

GENERAL COMMENT

The heating system responded to normal operating controls. Components appear to be properly installed and serviceable. This is an older system showing normal wear and tear, but we noted no conditions considered to be out of the ordinary. It is important to continue to monitor the furnace regularly as the unit ages, along with budgeting for eventual replacement.

Page 77: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 77 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

The heating system presently installed appears to be adequate for the size of this building.

Our inspection of the heating system is non-invasive and is limited to visible components and their basic function. A full evaluation requires extensive testing and is beyond the scope of our inspection.

The last service date of the gas forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if last service date was more than one year ago, recommend that a qualified HVAC technician inspect, clean, and service the system, and make repairs if necessary. For safety reasons, and because the system is fueled by gas, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC technician when it is serviced.

Electrical System

An electrical system consists of the service, distribution, wiring and convenience outlets (switches, lights, and receptacles). Our examination of the electrical system includes the exposed and accessible conductors, branch circuitry, panels, overcurrent protection devices, and a random sampling of convenience outlets. We look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature of the electrical wiring prevents inspection of every length of wire.

BASIC INFORMATIONService entry into building: Underground service lateralVoltage supplied by utility: 120/240 voltsCapacity (available amperage): 200 amperes

Page 78: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 78 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

System grounding source: Driven copper rod

Branch circuit protection: Circuit breakersWiring material: Copper and aluminum wiring where seenWiring method: Non-metallic sheathed cable or 'romex'

ELECTRIC METERThe electric meter is outside on the left side of the building.

MAIN SERVICEThe main electrical service panel is in the garage.

Page 79: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 79 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

MAIN DISCONNECTThe main disconnect is incorporated into the electrical service panel.

MAIN DISCONNECTThe ampacity of the main disconnect is 200 amps.

CB MAIN PANELThe main service panel is in good condition with circuitry installed and fused correctly.

The circuits in the panel are labeled. We did not verify the accuracy of the labeling, but it appears to be typical. When the opportunity arises, we suggest checking the labeling by actually operating the breakers.

Page 80: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 80 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

SERVICE CAPACITYThe service entrance conductors are the wires between the utilities service drop and the main service disconnect or main service panel.

The service entrance conductors appear to be #4/0 Aluminum providing an ampacity of 200.

Our statement regarding service capacity is based upon the labeled rating of the main electrical service disconnect.

The service capacity is normal for a house this size and age, and appears adequate for the present demand and minor additional loads.

SERVICE GROUNDINGThe system and equipment grounding appears to be correct.

BRANCH CIRCUITRYThe accessible branch circuitry was examined and appeared properly installed and in serviceable condition.

CONDUCTOR MATERIALThe wiring in the 120 volt circuits is copper. One or more of the 240 volt circuits are aluminum.

RECEPTACLES: OVERALLFor reference, as receptacles are discussed in this report, present standards for typical room plugs require grounded, 3 prong receptacles within six feet of any point on all walls. Upgrading is required in older buildings only during remodeling.

Based upon our inspection of a representative number, the receptacles were found to be properly installed for the time of construction, in serviceable condition, and operating properly.

SWITCHES: OVERALL

We tested a representative number of switches and found several to be without an obvious function. This is not necessarily a deficiency, but we suggest consultation with the owner as to their purpose.

LIGHTS: OVERALLThe light fixtures in this building are generally in serviceable condition.

GFI PROTECTIONGFCI (ground fault circuit interrupter) protection is a modern safety feature designed to prevent shock hazards. GFCI breakers and receptacles function to de-energize a circuit or a portion of a circuit when a hazardous condition exists.

GFCI protection is inexpensive and can provide a substantial increased margin of safety.

GFCI protection is installed for all of the receptacles where this type of protection is presently required. We recommend testing these devices on a monthly basis.

GENERAL COMMENTThe electrical system is generally in good condition, with only a few instances of needed repair or correction observed. See notes above for specific comments.

Page 81: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 81 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Insulation/Energy

Insulation, weatherstripping, dampers, double-glazed glass and set-back thermostats are features that help reduce heat loss and/or gain and increase system and appliance efficiency. Our visual inspection includes review to determine if these features are present in representative locations and we may offer suggestions for upgrading. Our review of insulation is based upon uniformly insulated or are insulated to current standards. It is our opinion that all homes could benefit from energy conservation upgrades, and we suggest that you consult professionals.

ATTIC INSULATIONThe attic has blown-in fiberglass insulation.

The level of insulation would appear to provide an R-30+ insulating value. This provides very good resistance to heat transfer by present standards.

WALL INSULATIONWe were unable to access the wall cavities and/or determine the presence or condition of insulation.

FLOOR INSULATION

There are numerous fiberglass batts that have fallen out of place or been damaged by rodent activity. We recommend this material be secured back in place and any damaged material be replaced.

GENERAL COMMENTThis structure appears to be partially insulated and energy efficient. Upgrading can further reduce heat loss, cold air infiltration and increase overall energy efficiency.

Page 82: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 82 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Locations of Emergency Controls

In an emergency, you may need to know where to shut off the gas, the water and/or the electrical system. We have listed below these controls and their location for your convenience. We urge that you familiarize yourself with their location and operation.

WATER SHUTOFF LOCATIONPLUMBINGThe domestic water supply main shut-off valve is located below the master bathroom sink.

SEWER CLEANOUTPLUMBINGThe sewer cleanout is located in the crawl space.

Page 83: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 83 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

GAS METER LOCATIONPLUMBINGThe gas meter is outside on the left side of the building. The main gas supply shutoff valve is located on the riser pipe between the ground and the meter. This valve should be turned 90 degrees (either way) in order to shut off the gas.

ELECTRIC METERELECTRICAL SYSTEMThe electric meter is outside on the left side of the building.

Page 84: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 84 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

MAIN SERVICEELECTRICAL SYSTEMThe main electrical service panel is in the garage.

MAIN DISCONNECTELECTRICAL SYSTEMThe main disconnect is incorporated into the electrical service panel.

Environmental Concerns

Environmental issues include but are not limited to radon, fungi/mold, asbestos, lead paint, lead contamination, toxic waste, formaldehyde, electromagnetic radiation, buried fuel oil tanks, ground water contamination and soil contamination. We are not trained or licensed to recognize or discuss any of these materials. We may make reference to one of more of these materials in this report when we recognize one of the common forms of these substances. If further study or analysis seems prudent, the advice and services of the appropriate specialists are advised.

Conclusion

COMMENTSThis structure appears to be of standard quality, in need of miscellaneous repair and upgrading. There is also maintenance in need of attention. Examples of these conditions have been described in this report.

Page 85: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

Page 85 of 106Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-05004

Most of the items that are in need of immediate attention and/or possible major cost items that would require repair in the near future are listed in the report summary. Please be sure to refer to this document for further useful information.

Page 86: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations to survey the readily accessible, easily visible material components, systems and equipment of the building. The inspection is designed to identify material physical deficiencies in the building’s components, systems and equipment, as they exist at the time of the inspection. The work product resulting from completing an inspection in accordance with this contract is an inspection report. The inspection report incorporates the information obtained during the inspection. The inspection report is for the sole use and benefit of the Client. Client agrees to read the entire inspection report when it is received and shall promptly call the Inspector with any questions or concerns Client may have regarding the inspection report or the inspection. The inspection report shall be considered the final and exclusive findings of the Inspector regarding the inspection of the building. Client shall not rely on any oral statement made by the Inspector prior to issuance of the inspection report. 2. Components and systems operated during the inspection will be identified in the inspection report. The identified components and systems shall be operated with normal user controls and as conditions permit. If a component or system is operated, it may be conducted without the aid of special protective clothing, exploratory probing, removing materials, testing, measuring, preparing, calculations or using special equipment, including meters or devices of any kind. Testing, measuring, or preparing calculations for any system or component to determine adequacy, capacity, or compliance with any standard is outside the scope of this contract. 3. The term “poor” or “major concern” in regard to a component mean the presence of conspicuous patent defects or material deferred maintenance of the building’s material systems, components, or building equipment as observed during the inspection. This definition specifically excludes deficiencies that may be remedied with routine maintenance, miscellaneous minor repairs, and normal operating maintenance, and excludes conditions that generally do not present material physical deficiencies of the building. 4. Inspector is an expert generalist and not acting as an expert in any SPECIFIC craft or

Page 87: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

trade. The inspector may make recommendations for further evaluation by an individual(s) who is an expert or specialist IN ONE OR MORE SPECIFIC BUILDING COMPONENTS OR SYSTEMS. 5. The inspection is not technically exhaustive. The cost obtaining information or the time required to conduct a technically exhaustive inspection and prepare the inspection report could outweigh the usefulness of the information and could be detrimental to the orderly and timely completion of Client’s transaction. 6. No inspection can wholly eliminate the uncertainty regarding the presence of physical deficiencies and the performance of the building’s systems. Preparation of an inspection report in accordance with this contract is intended to reduce, but not eliminate, the uncertainty regarding the potential for component or system failure and to reduce the potential that such component or system may not be initially observed. Client recognizes the inherent subjective nature of the inspector’s opinions as to issues such as workmanship, quality of original installation, and estimating the remaining useful life of any given component or system. The inspector’s opinions generally are formed without detailed knowledge from those specifically familiar with the component or system’s performance. 7. The inspection report will contain a representative indication of the property condition at the time of the inspection and is dependent on the information available to the inspector at that time. 8. It is the Client’s duty and obligation to exercise reasonable care to protect himself or herself regarding the condition of the building, including those facts that are known to or within the diligent attention and observation of the Client. SCOPE AND LIMITATIONS OF THIS INSPECTION This inspection is limited to a visual observation of the exposed and readily accessible areas of the home. The concealed and inaccessible areas are not included. The following locations are considered inaccessible due to limited height and excluded from this inspection unless otherwise stated:

• Crawl space areas less than 18 inches in height

• Attic spaces less than 5 feet in height

• Spaces under outdoor decks less than 5 feet high Observation includes operation of the systems or components by means of the normal user controls. Dismantling of equipment, and destructive testing is not included. Some specific items are also excluded, and these are listed in the following section. If you feel there is a need for evaluation of any of these items, then you will need to arrange for specific inspections.

Page 88: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

Items not Included 1. Recreational, leisure, playground or decorative equipment or appliances including but not limited to pools, hot tubs, saunas, steam baths, landscape lighting, fountains, shrubs, trees, and tennis courts; 2. Cosmetic conditions (wallpapering, painting, carpeting, scratches, scrapes, dents, cracks, stains, soiled or faded surfaces on the structure or equipment, soiled, faded, torn, or dirty floor, wall or window coverings etc.); 3. Noise pollution or air quality in the area; 4. Earthquake hazard, liquefaction, flood plain, soil, slide potential or any other geological conditions or evaluations; 5. Engineering level evaluations on any topic; 6. Existence or non-existence of solder or lead in water pipes, asbestos, hazardous waste, radon, urea formaldehyde urethane, lead paint or any other environmental, flammable or toxic contaminants or the existence of water or airborne diseases or illnesses and all other similar or potentially harmful substances (although the inspector may note the possible existence of asbestos in ceiling texture and furnace duct tape); 7. Zoning or municipal code (e.g. building, fire, housing (existing buildings), mechanical, electrical, plumbing, etc. code) restrictions or other legal requirements of any kind; 8. Any repairs which relate to some standard of interior decorating; 9. Cracked heat exchangers or similar devices in furnaces; 10. Any evaluation which requires the calculation of the capacity of any system or item that is expected to be part of the inspection. Examples include but are not limited to the calculation of appropriate wattage or wiring of kitchen appliances, appropriate sizing of flues or chimneys, appropriate ventilation to combustion-based items (e.g. furnaces, water heaters, fireplaces etc.), appropriate sizing, spacing and spanning of joists, beams, columns, girders, trusses, rafters, studs etc., appropriate sizing of plumbing and fuel lines, etc.; 11. Washers and dryers; 12. Circuit breaker operation; 13. Specialty evaluations such as private sewage, wells, solar heating systems, alarms, intercom systems, central vacuum systems, wood and coal stoves, pre-fab and zero clearance fireplaces, space heaters, sprinkler systems, gas logs, gas lights, elevators and common areas unless these have been specifically added to the inspection description above but only to the degree that the inspector is capable of evaluating these items;

Page 89: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

14. Items that are not visible and exposed including but not limited to concealed wiring, plumbing, water leaks, under bathtubs and shower stalls due to faulty pans or otherwise, vent lines, duct work, exterior foundation walls (below grade or covered by shrubs or wall/paneling, stored goods etc.) and footings, underground utilities, and systems and chimney flues; 15. Evaluations involving destructive testing; 16. Evaluation which requires moving personal goods, debris, furniture, equipment, floor covering, insulation or like materials; 17. Design problems and adequacy or operational capacity, quality or suitability; 18. Fireplace drafting; 19. To prevent damages to units, air conditioning when outside temperature below 60 degrees F or if the unit has not been warmed up or on for at least 24 hours prior to inspection; 20. Any evaluation which would involve scraping paint or other wall coverings; 21. Heating system accessories (e.g. humidifiers, electronic air cleaners etc.); 22. Legal description of property such as boundaries, egress/ingress, etc.; 23. Quality of materials; 24. Conformance with plan specifications or manufacturers specifications; 25. Flood conditions or plains; 26. Any other characteristics or items which are generally not included in a building inspection report on a regular basis. Services for inspecting or evaluating the excluded items listed above may be available from the Inspector for an additional fee or from specialists qualified to inspect or evaluate a particular category or item. Disclaimer In some cases we may recommend your consulting a specialist such as a structural engineer or licensed electrician. Hiring a specialist can be a prudent means of providing some protection of your financial investment in this property. WE DO NOT MAKE ANY TYPE OF WARRANTY OR GUARANTEE AS TO THE CONDITION OF THE PROPERTY. SOME THINGS MAY REMAIN HIDDEN OR

Page 90: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

BECOME DEFECTIVE AFTER THE INSPECTION. IT IS NOT POSSIBLE TO DETECT EVERY DEFECT WITHIN A BUILDING DURING THE COURSE OF A GENERAL INSPECTION. THIS REPORT SHOULD BE USED IN CONJUNCTION WITH, AND NOT A REPLACEMENT FOR , A PRE-CLOSING WALK-THROUGH BY THE CLIENT. THIS INSPECTION IS NOT AN INSURANCE POLICY AGAINST HIDDEN DEFECTS, OR CONDITIONS THAT ARE NOT VISIBLE AND READILY APPARENT AT THE TIME OF INSPECTION. THE COST OF THIS INSPECTION DOES NOT ENTITLE YOU TO ANY TYPE OF PROTECTION FROM HIDDEN FLAWS AND DEFECTS. THIS INSPECTION DOES NOT TRANSFER YOUR ULTIMATE RESPONSIBILITY TO ALL POINT HOME INSPECTIONS. ENVIRONMENTAL CONCERNS: Client acknowledges that what is being contracted for is a building inspection and not an environmental evaluation and the inspection is not intended to detect, identify or disclose any health or environmental concerns regarding this building or property, including, but not limited to, the presence of asbestos, radon, lead, urea formaldehyde, fungi, mold, mildew, PCB’s or other toxic materials or substances in the water, air, soil or building materials. CONFIDENTIAL REPORT: The inspection report to be prepared for the Client is solely and exclusively for the Client’s own information and may not be relied upon by any other person. Client agrees to maintain the confidentiality of the inspection report and agrees not to disclose any part of it to any other person. Client my distribute copies of the inspection report to other persons directly involved in this transaction, but the Client and Inspector do not in any way intend to benefit said other persons directly or indirectly through this Contract, the inspection or the inspection report. CLIENT AGREES TO INDEMNIFY, DEFEND AND HOLD THE INSPECTOR HARMLESS FROM ANY THRID PARTY CLAIMS ARISING OUT OF THE CLIENT’S UNAUTHORIZED DISTRIBUTION OF THE INSPECTION REPORT. LIQUIDATED DAMAGES: IT IS UNDERSTOOD AND AGREES BY AND BETWEEN THE PARTIES HERETO THAT THE INSPECTOR/INSPECTION COMPANY IS NOT AN INSURER, THAT THE PAYMENT FOR THE SUBJECT INSPECTION IS BASED SOLELY ON THE VALUE OF THE SERVICES PROVIDED BY THE INSPECTOR/INSPECTION COMPANY IN THE PREFORMANCE OF THE INSPECTION AND PRODUCTION OF THE INSPECTION REPORT AS DESCRIBED HEREIN, THATIT IS IMPRACTICABLE AND EXTREMELY DIFFICULT TO FIX THE ACTUAL DAMAGES, OF ANY, WHICH MAY RESULT FROM A FAILURE TO PERFORM SUCH SERVICES, AND IN CASE OF FAILURE TO PERFORM SUCH SERVICES AND A RESULTING LOSS, THE CLIENT’S DAMAGES HEREIN SHALL BE LIQUIDATER AND FIXED IN AN AMOUNT EQUAL TO THE INSPECTION FEE PAID MULTIPLIED BY ONE HUNDRED TWENT-FIVE PERCENT (125%) AS

Page 91: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

LIQUIDATED DAMAGES AND NOT AS A PENALTY, AND THIS REMEDY SHALL BE EXCLUSIVE. GENERAL PROVISIONS: A. This inspection contract, the inspection, and the inspection report do not constitute a warranty, guarantee, or insurance policy of any kind whatsoever. B. No legal action or proceeding of any kind, including in tort or contract can be commenced against Inspector/Inspection Company, or its officers, agents or employees more than one year after the date of the subject inspection. Time is expressly of the essence herein. THIS TIME PERIOD IS SHORTER THAN OTHERWISE PROVIDED BY LAW. C. In the event the Client discovers a material physical deficiency in a component, system or equipment of the building that was not identified and reported by the Inspector, Client shall so notify the Inspector in writing and allow Inspector and/or Inspector’s designated representative to re-inspect and document the condition(s) of the material physical deficiency prior to making any repair, alteration, or replacement to said physical deficiency. D. Should any provision of this contract be held by a court of competent jurisdiction to be either invalid or unenforceable, the remaining provisions of this contract shall remain in full force and effect, unimpaired by the court’s holding. E. This contract shall be binding upon and inure to the benefit of only the undersigned parties and their heirs, successors and assigns. F. This contract constitutes the entire integrated agreement between the parties hereto pertaining to the subject matter hereof, and may be modified only by a written agreement signed by all of the parties hereto. No oral agreements, understanding, or representations shall change, modify, or amend any part of this contract. G. Each party signing this contract warrants and represents that he/she has the full capacity and authority to execute this contract on behalf of the named party whether it is a corporation, partnership, or other entity. If this contract is executed on behalf of the Client by a third party, the person executing this contract expressly represents to the Inspector that he/she has the full and complete authority to execute this contract on the Client’s behalf and to fully and completely bind the Client to all of the terms, conditions, limitations, exceptions and exclusions of this contract. This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited. FOLLOW-UP INSPECTION POLICY Generally we discourage follow-up inspections for these reasons

Page 92: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

1. Quality of repairs

If repairs are made to a property based on the results of an inspection, the work should be performed by qualified contractors, not the seller. By qualified, we mean licensed, bonded, state-certified where applicable and with a reasonable amount of experience. Contractors providing repairs should provide legible documentation in the form of work orders and/or receipts. If repairs are made in this way, then there's generally no need for a follow-up inspection. Additionally, it may be better to negotiate a lower price on your home and have repairs made by contractors you choose rather than the seller making repairs as cheaply as possible. ________________________________________ As a part of our service, we sometimes provide approximate, cost of repair estimates for particular items. These estimates should be considered as background information only. It is beyond the scope of this inspection and report to supply you with accurate repair costs. Such estimates should be supplied by contractors who specialize in this type of work. Our estimates should be used only as guidelines. If you intend to negotiate the price of this property based on defects found during this inspection, we strongly suggest you obtain one or more written bids from a licensed contractor(s). It is a conflict of interest for Strong Foundations Home Inspection to recommend any specific contractor.

Page 93: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

Life Expectancy Charts for Homes PLEASE NOTE: These life expectancies have been determined through research and testing based on regular recommended maintenance and conditions of normal wear and tear, and not extreme weather or other conditions, neglect, over-use or abuse. Therefore, they should be used as guidelines only, and not relied upon as guarantees or warranties.

Surface preparation and paint quality are the most important determinants of a paint's life expectancy. Ultraviolet (UV) rays via sunshine can shorten life expectancy. Additionally, conditions of high humidity indoors or outdoors can affect the lifespan of these components, which is why they should be inspected and maintained seasonally.

ADHESIVES, CAULK &

PAINTS

YEARS

Caulking (interior & exterior) 5 to 10

Construction Glue 20+

Paint (exterior) 7 to 10

Paint (interior) 10 to 15

Roofing Adhesives/Cements 15+

Sealants 8

Stains 3 to 8

Appliance life expectancy depends to a great extent on the use it receives. Furthermore, consumers often replace appliances long before they become worn out due to changes in styling, technology and consumer preferences.

APPLIANCES YEARS

Air Conditioner (window) 5 to 7

Compactor (trash) 6

Dehumidifier 8

Dishwasher 9

Disposal (food waste) 12

Dryer Vent (plastic) 5

Dryer Vent (steel) 20

Dryer (clothes) 13

Exhaust Fans 10

Freezer 10 to 20

Gas Oven 10 to 18

Hand Dryer 10 to 12

Humidifier (portable) 8

Microwave Oven 9

Range/Oven Hood 14

Electric Range 13 to 15

Gas Range 15 to 17

Refrigerator 9 to 13

Page 94: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

Swamp Cooler 5 to 15

Washing Machine 5 to 15

Whole-House Vacuum System 20

Modern kitchens today are larger and more elaborate. Together with the family room, they now form the “great room.”

CABINETRY & STORAGE YEARS

Bathroom Cabinets 50+

Closet Shelves 100+

Entertainment Center/Home Office 10

Garage/Laundry Cabinets 70+

Kitchen Cabinets 50

Medicine Cabinet 25+

Modular (stock manufacturing-type) 50

Walls and ceilings last the full lifespan of the home.

CEILINGS & WALLS YEARS

Acoustical Tile Ceiling 40+ (older than 25 years may

contain asbestos)

Ceramic Tile 70+

Concrete 75+

Gypsum 75

Wood Paneling 20 to 50

Suspended Ceiling 25+

Natural stone countertops, which are less expensive than they were just a few years ago, are becoming more popular, and one can expect them to last a lifetime. Cultured marble countertops have a shorter life expectancy, however.

COUNTERTOPS YEARS

Concrete 50

Cultured Marble 20

Natural Stone 100+

Laminate 20 to 30

Resin 10+

Tile 100+

Wood 100+

Page 95: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

Decks are exposed to a wide range of conditions in different climates, from wind and hail in some areas, to relatively consistent, dry weather in others. See FASTENERS & STEEL section for fasteners.

DECKS YEARS

Deck Planks 15

Composite 8 to 25

Structural Wood 10 to 30

Exterior fiberglass, steel and wood doors will last as long as the house, while vinyl and screen doors have a shorter life expectancy. The gaskets/weatherstripping of exterior doors may have to be replaced every 5 to 8 years.

DOORS YEARS

Closet (interior) 100+

Fiberglass (exterior) 100+

Fire-Rated Steel (exterior) 100+

French (interior) 30 to 50

Screen (exterior) 30

Sliding Glass/Patio (exterior) 20 (for roller wheel/track

repair/replacement)

Vinyl (exterior) 20

Wood (exterior) 100+

Wood (hollow-core interior) 20 to 30

Wood (solid-core interior) 30 to 100+

Copper-plated wiring, copper-clad aluminum, and bare copper wiring are expected to last a lifetime, whereas electrical accessories and lighting controls, such as dimmer switches, may need to be replaced after 10 years. GFCIs could last 30 years, but much less if tripped regularly. Remember that faulty, damaged or overloaded electrical circuits or equipment are the leading cause of house fires, so they should be inspected regularly and repaired or updated as needed.

ELECTRICAL YEARS

Accessories 10+

Arc-Fault Circuit Interrupters

(AFCIs)

30

Bare Copper 100+

Bulbs (compact fluorescent) 8,000 to 10,000+ hours

Bulbs (halogen) 4,000 to 8,000+ hours

Bulbs (incandescent) 1,000 to 2,000+ hours

Bulbs (LED) 30,000 to 50,000+ hours

Copper-Clad Aluminum 100+

Copper-Plated 100+

Page 96: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

Fixtures 40

Ground-Fault Circuit Interrupters

(GFCIs)

up to 30

Lighting Controls 30+

Residential Propane Backup

Generators

12

Service Panel 60

Solar Panels 20 to 30

Solar System Batteries 3 to 12

Wind Turbine Generators 20

Floor and roof trusses and laminated strand lumber are durable household components, and engineered trim may last 30 years.

ENGINEERED LUMBER YEARS

Engineered Joists 80+

Laminated Strand Lumber 100+

Laminated Veneer Lumber 80+

Trusses 100+

Fastener manufacturers do not give lifespans for their products because they vary too much based on where the fasteners are installed in a home, the materials in which they're installed, and the local climate and environment. However, inspectors can use the guidelines below to make educated judgments about the materials they inspect.

FASTENERS, CONNECTORS &

STEEL

YEARS

Adjustable Steel Columns 50+

Fasteners (bright) 25 to 60

Fasteners (copper) 65 to 80+

Fasteners (galvanized) 10+

Fasteners (electro-galvanized) 15 to 45

Fasteners (hot-dipped galvanized) 35 to 60

Fasteners (stainless) 65 to 100+

Steel Beams 200+

Steel Columns 100+

Steel Plates 100+

Flooring life is dependent on maintenance and the amount of foot traffic the floor endures.

FLOORING YEARS

All Wood Floors 100+

Bamboo 100+

Brick Pavers 100+

Page 97: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

Carpet 8 to 10

Concrete 50+

Engineered Wood 50+

Exotic Wood 100+

Granite 100+

Laminate 15 to 25

Linoleum 25

Marble 100+

Other Domestic Wood 100+

Slate 100

Terrazzo 75+

Tile 75 to 100

Vinyl 25

Concrete and poured-block footings and foundations will last a lifetime, assuming they were properly built. Waterproofing with bituminous coating lasts 10 years, but if it cracks, it is immediately damaged.

FOUNDATIONS YEARS

Baseboard Waterproofing System 50

Bituminous-Coating Waterproofing 10

Concrete Block 100+

Insulated Concrete Forms (ICFs) 100

Permanent Wood Foundation (PWF;

treated)

75

Post and Pier 20 to 65

Post and Tensioned Slab on Grade 100+

Poured-Concrete Footings and

Foundation

100+

Slab on Grade (concrete) 100

Wood Foundation 5 to 40

Framing and structural systems have extended longevities; poured-concrete systems, timber frame houses and structural insulated panels will all last a lifetime.

FRAMING YEARS

Log 80 to 200

Poured-Concrete Systems 100+

Steel 100+

Structural Insulated Panels (SIPs) 100+

Timber Frame 100+

The quality and frequency of use will affect the longevity of garage doors and openers.

Page 98: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

GARAGES YEARS

Garage Doors 20 to 25

Garage Door Openers 10 to 15

Home technology systems have diverse life expectancies and may have to be upgraded due to evolution in technology.

HOME TECHNOLOGY YEARS

Built-In Audio 20

Carbon Monoxide Detectors* 5

Doorbells 45

Home Automation System 5 to 50

Intercoms 20

Security System 5 to 20

Smoke/Heat Detectors* less than 10

Wireless Home Networks 5+

* Batteries should be changed at least annually. Thermostats may last 35 years but they are usually replaced before they fail due to technological improvements.

HVAC YEARS

Air Conditioner (central) 7 to 15

Air Exchanger 15

Attic Fan 15 to 25

Boiler 40

Burner 10+

Ceiling Fan 5 to 10

Chimney Cap (concrete)

100+

Chimney Cap (metal) 10 to 20

Chimney Cap (mortar) 15

Chimney Flue Tile 40 to 120

Condenser 8 to 20

Dampers 20+

Dehumidifier 8

Diffusers, Grilles and Registers 25

Ducting 60 to 100

Electric Radiant Heater 40

Evaporative Cooler 15 to 25

Furnace 15 to 25

Gas Fireplace 15 to 25

Heat Exchanger 10 to 15

Page 99: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

Heat Pump 10 to 15

Heat-Recovery Ventilator 20

Hot-Water and Steam-Radiant

Boiler

40

Humidifier 12

Induction and Fan-Coil Units 10 to 15

Thermostats 35

Ventilator 7

As long as they are not punctured, cut or burned and are kept dry and away from UV rays, cellulose, fiberglass and foam insulation materials will last a lifetime. This is true regardless of whether they were installed as loose-fill, housewrap or batts/rolls.

INSULATION & INFILTRATION

BARRIERS

YEARS

Batts/Rolls 100+

Black Paper (felt paper) 15 to 30

Cellulose 100+

Fiberglass 100+

Foamboard 100+

Housewrap 80+

Liquid-Applied Membrane 50

Loose-Fill 100+

Rockwool 100+

Wrap Tape 80+

Masonry is one of the most enduring household components. Fireplaces, chimneys and brick veneers can last the lifetime of the home.

MASONRY & CONCRETE YEARS

Brick 100+

Insulated Concrete Forms (hybrid

block)

100+

Concrete Masonry Units (CMUs) 100+

Man-Made Stone 25

Masonry Sealant 2 to 20

Stone 100+

Stucco/EIFS 50+

Veneer 100+

Custom millwork and stair parts will last a lifetime and are typically only upgraded for aesthetic reasons.

Page 100: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

MOLDING, MILLWORK &

TRIM

YEARS

Attic Stairs (pull-down) 50

Custom Millwork 100+

Pre-Built Stairs 100+

Stair Parts 100+

Stairs 100+

The lifetime of any wood product depends heavily on moisture intrusion.

PANELS YEARS

Flooring Underlayment 25

Hardboard 40

Particleboard 60

Plywood 100

Softwood 30

Oriented Strand Board (OSB) 60

Wall Panels 100+

The quality of plumbing fixtures varies dramatically. The mineral content of water can shorten the life expectancy of water heaters and clog showerheads. Also, some finishes may require special maintenance with approved cleaning agents per the manufacturers in order to last their expected service lives.

PLUMBING, FIXTURES &

FAUCETS

YEARS

ABS and PVC Waste Pipe 50 to 80

Accessible/ADA Handles 100+

Acrylic Kitchen Sink 50

Cast-Iron Bathtub 100

Cast-Iron Waste Pipe (above

ground)

60

Cast-Iron Waste Pipe (below

ground)

50 to 60

Concrete Waste Pipe 100+

Copper Water Lines 70

Enameled Steel Kitchen Sink 5 to 10+

Faucets and Spray Hose 15 to 20

Fiberglass Bathtub and Shower 20

Gas Lines (black steel) 75

Gas Lines (flex) 30

Hose Bibs 20 to 30

Instant (on-demand) Water Heater 10

PEX 40

Page 101: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

Plastic Water Lines 75

Saunas/Steam Room 15 to 20

Sewer Grinder Pump 10

Shower Enclosure/Module 50

Shower Doors 20

Showerheads 100+ (if not clogged by

mineral/other deposits)

Soapstone Kitchen Sink 100+

Sump Pump 7

Toilet Tank Components 5

Toilets, Bidets and Urinals 100+

Vent Fan (ceiling) 5 to 10

Vessel Sink (stone, glass, porcelain,

copper)

5 to 20+

Water Heater (conventional) 6 to 12

Water Line (copper) 50

Water Line (plastic) 50

Water Softener 20

Well Pump 15

Whirlpool Tub 20 to 50

Radon systems have but one moving part: the radon fan.

RADON SYSTEMS YEARS

Air Exchanger 15

Barometric Backdraft

Damper/Fresh-Air Intake

20

Caulking 5 to 10

Labeling 25

Manometer 15

Piping 50+

Radon Fan 5 to 8

The life of a roof depends on local weather conditions, building and design, material quality, and adequate maintenance. Hot climates drastically reduce asphalt shingle life. Roofs in areas that experience severe weather, such as hail, tornadoes and/or hurricanes, may also experience a shorter-than-normal lifespan overall or may incur isolated damage that requires repair in order to ensure the service life of the surrounding roofing materials.

ROOFING YEARS

Aluminum Coating 3 to 7

Asphalt (architectural) 30

Asphalt Shingles (3-tab) 20

BUR (built-up roofing) 30

Page 102: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

Clay/Concrete 100+

Coal and Tar 30

Copper 70+

EPDM (ethylene propylene diene

monomer) Rubber

15 to 25

Fiber Cement 25

Green (vegetation-covered) 5 to 40

Metal 40 to 80

Modified Bitumen 20

Simulated Slate 10 to 35

Slate 60 to 150

TPO 7 to 20

Wood 25

Outside siding materials typically last a lifetime. Some exterior components may require protection through appropriate paints or sealants, as well as regular maintenance. Also, while well-maintained and undamaged flashing can last a long time, it is their connections that tend to fail, so seasonal inspection and maintenance are strongly recommended.

SIDINGS, FLASHING &

ACCESSORIES

YEARS

Aluminum Gutters, Downspouts,

Soffit and Fascia

20 to 40+

Aluminum Siding 25 to 40+

Asbestos Shingle 100

Brick 100+

Cementitious 100+

Copper Downspouts 100

Copper Gutters 50+

Engineered Wood 100+

Fiber Cement 100+

Galvanized Steel

Gutters/Downspouts

20

Manufactured Stone 100+

Stone 100+

Stucco/EIFS 50+

Trim 25

Vinyl Gutters and Downspouts 25+

Vinyl Siding 60

Wood/Exterior Shutters 20

Site and landscaping elements have life expectancies that vary dramatically.

SITE & LANDSCAPING YEARS

Page 103: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

American Red Clay 100+

Asphalt Driveway 15 to 20

Brick and Concrete Patio 15 to 25

Clay Paving 100+

Concrete Walks 40 to 50

Controllers 15

Gravel Walks 4 to 6

Mulch 1 to 2

Polyvinyl Fencing 100+

Sprinkler Heads 10 to 14

Underground PVC Piping 60+

Valves 20

Wood Chips 1 to 5

Wood Fencing 20

Swimming pools are composed of many systems and components, all with varying life expectancies.

SWIMMING POOLS YEARS

Concrete Shell 25+

Cover 7

Diving Board 10

Filter and Pump 10

Interior Finish 10 to 35

Pool Water Heater 8

Vinyl Liner 10

Waterline Tile 15+

Aluminum windows are expected to last between 15 and 20 years, while wooden windows should last nearly 30 years.

WINDOWS YEARS

Aluminum/Aluminum-Clad 15 to 20

Double-Pane 8 to 20

Skylights 10 to 20

Vinyl/Fiberglass Windows 20 to 40

Window Glazing 10+

Wood 30+

Note: Life expectancy varies with usage, weather, installation, maintenance and quality of materials. This list should be used only as a general guideline and not as a guarantee or warranty regarding the performance or life expectancy of any appliance, product, system or component.

Evaluations are made as to the present age, and remaining economic life of an item, i.e.

Page 104: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

water heaters, roofs, plumbing, furnaces, etc. These evaluations are based on visual observation, industry averages and prior experience. THEY ARE NOT OFFERED AS A WARRANTY OR CERTIFICATION OF REMAINING LIFE.

Page 105: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

HOME MAINTENANCE CHECK LIST: Monthly: 1. Clean any removable dishwasher filters. 2. Purge food disposal by filling the kitchen sink with clean water, then turn on the device until the water drains through. 3. Wash refrigerator/freezer interior walls and door gaskets with a solution of one quart of warm water to two tablespoons of baking soda and wipe dry. 4. Vacuum and clean “return” air ducts/grills. 5. Inspect lighting fixtures and replace any burned-out bulbs. 6. Clean clothes dryer lint trap and/or duct for better energy efficiency and to decrease the risk of fire. Quarterly: 1. Inspect and service doors by cleaning and lubricating latches, hinges or replacing weather-stripping as might be required. 2. Inspect and repair, if necessary, exterior caulking and finish around windows, doors, and siding. 3. Replace/clean, at least quarterly, furnace, heating and cooling system filters. 4. Re-tighten knobs and pulls on cabinets. Clean and lubricate drawer tracks and guides. Semi-annually: 1. Inspect and test smoke and carbon monoxide alarms. Replace backup batteries as might be required. 2. Test (GFCI) ground fault circuit interrupters and (AFCI) arc fault breakers. 3. Inspect and maintain/clean gutters and downspouts. Runoff water must be directed away from the home. 4. Inspect attics and substructure areas for rodent droppings or other signs of pests or leaks/standing water, etc. 5. Prior to the beginning of the rainy season, test sump pumps for adequacy and function. 6. Look for moisture or decay, outside and inside the house, where flat surface decks and landing attach to the house. This is especially important if the landings do not have proper flashings. 7. Clean range hood fan grills and housings. 8. Use a vacuum cleaner to remove dust on coils behind the refrigerator/freezer. Annually: 1. Licensed contractor to inspect and service heating and air-conditioning systems. 2. Professional contractor to inspect and service wood burning appliances and chimneys. 3. Seal any foundation cracks. 4. Inspect, clean and lubricate garage vehicle door tracks and test auto-reverse functions. 5. Clean and lubricate sliding glass door and window tracks. 6. Inspect exterior paint for cracking and wear. Repaint, caulk and seal as needed.

Page 106: Confidential Inspection Report · 2019-05-06 · ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations inspection

©2019 Strong Foundations Home Inspection

7. Reseal, as required, wood decks and landings. 8. Inspect, for water damage, pests or rot, any substructure and attic areas. 9. Inspect roof flashings, chimney caps, shingles. 10. Inspect outside electrical service lines for damage, exposed wires or proximity to tree limbs. 11. Inspect all supply hoses at sinks, toilets and washing machines. 12. Clean and repair caulking or grout in bathrooms or kitchens. 13. Clean bathroom exhaust fan blades and grills. 14. Inspect all electric coeds and replace as needed. 15. Change water filters and have fresh water systems professionally services. Tips for keeping drains clear: 1. Pour a pot of hot water down the drain once a week to help clear away fat or grease that may have built-up in the drain line or the P-trap. 2. If a drain is clogged, try pouring 1/2 cup of white vinegar down the drain. Cover the drain and let the mixture sit for a few minutes. Then pour a pot of hot water down the drain. General Safety tips: Ensure that you know where the following items are located: 1. Emergency contact telephone numbers. 2. Fire extinguishers and water hose pipes. 3. Heating gas/fuel main shut off valve. 4. Main electrical disconnect circuit breaker (breaker box/service panel). 5. Main drain line clean-out. 6. Main water shut-off valve. 7. All window and door exits.