Condenser and Circulating Water System
-
Upload
khairun-nisa -
Category
Documents
-
view
579 -
download
26
Transcript of Condenser and Circulating Water System
Condenser and Cooling Water
System
By Aklilu Tesfamichael (Dr.)
Condenser
What is the purpose of condenser in a
power plant?
1. To reduce the turbine exhaust
pressure so that
The turbine specific output (thermal
efficiency of the plant) increases.
(for p=1 atm (1 bar) Tsat=100 oC and
P=0.074 bar (Tsat=40 oC) this can
reject heat to 30 oC cooling water.
Reduce the steam flow rate for a
given plant power output
2. To recover high quality feedwater in the form of condensate
and reuse it without any further treatment. Hence, only
makeup water that is required to top up the water lost in the
cycle needs treatment
Types of condensers
They are two types 1. Direct contact: where the condensate and the cooling water
directly mix and come out as a single stream
Fig: Schematic diagram of a direct contact condenser and its T-s diagram
2. Surface condensers
They are shell and tube heat exchangers.
Cooling water and condensate are separated by a solid surface. Heat
transfer is through the walls of the tubes into the cooling water.
For cleaning purpose cooling water flows inside the tubes and the steam
condenses outside the tubes.
Fig: schematic of one and two-pass surface condensers
Condensing process and design
consideration
• Steam contacts the cold surface
• The average heat transfer coefficient as given by Nusselt
4123
41
41
41
725.0
,/1
,/1
of
fgff
av
fgav
wsatav
av
dN
ghkh
hh
tth
tubeshorizontalofnumberNNh
The inside heat transfer coefficient on the water side may be obtained as
4.08.0PrRe023.0 ddNu
,,, incwecwcwp
scw
ttc
hmm
Energy balance between the steam and the cooling water gives:
The rise in cooling water temperature is limited to about 8-10 oC.
For every kg of steam condensate, 75 to 100 kg of water is required.
Hence, to meet the water demand the plant is located where water is available
in plenty.
lmooincwoutcwcwpcwoutsins tAUTTcmhh ,,,,,smQ
e
i
eilm
t
t
ttt
ln
Ct
CtC
o
e
o
in
o
3
1711
rangedRecommende
Condensing process and design
consideration (contd.)
Cooling Water Outlet Temperature
Calculation The surface area needed by the condenser is obtained by:
2.5m/s)(1.8waterofvelocityV
waterofdensityρwhere
4
:is tubestheinrateflowwater The
.condenser)passsinglea(fortubeoneoflengthl
andtubes,ofnumbernwhere
2Vdnm
l dnTU
hmA
ic
o
lmo
so
Air removalWhat will happen if air enters to the condenser?
Affects the condenser performance badly because
1. It reduces the heat transfer considerably as air has low
thermal conductivity
2. It reduces the condenser vacuum pressure and increase the
turbine exhaust pressure thus reducing the turbine output.
Source of air leakages
Turbine gland, large diameter flanges such as the steam inlet or
turbine exhaust, open valves or steam chest on the ejectors.
tempmeasured shellat pressure saturated theis p;ppp
pressure saturated steam
pressureair pressure totalmeasured Shell
pressure. partial of law sDalton'by
estimated becan shell the theinto dinfiltrate pressureair The
satsatairmsh,
Fig: Turbine shaft gland
Air removal (contd.)
watercooling of rise re temperatuMaximum
watercooling of rise re temperatuActual efficiencyCondenser
pressure steamexhaust at pressure saturation - pressure Barometric
inlet condenser steamby produced Vacuumefficiency Vacuum
shell.condenser thefrom removedly continuous be tohasair This
equation. above thefrom estimated becan leakageair of rate theHence,
kJ/kgK 0.287air ofconstant gas sticcharacteriR
steamexhaust of volumespecfic where
273)(tRmmp
pressure, lowsuch at gas idealan as behavesair Assuming
a
2
msh,aa2sair
Condenser performance
Cooling water
Circulating water system supplies cooling water to the turbine condenser thus it act as a medium through which heat is rejected from the steam cycle to the environment.
Cooling water can flow through the condenser in two ways
(a) One through system
(b) Closed loop system
Once through system
Used when there is alarge source of waterlike river, lake or oceanare available.
Fig: schematic of once-through circulating water system
Closed loop water circulating system
• More universal to avoid thermal pollution of river or oceans plus huge water is not every where available
• But this system needs cooling tower
Condenser
Fig: schematic of wet cooling tower operating in closed system
Cooling Towers
Cool the warm water discharged from the condenser by atmospheric air and feed it back to the condenser.
According to the main mode of heat transfer there are two types: wet (evaporative) cooling tower and dry (sensible) cooling tower.
Wet cooling towerAir entering the tower is unsaturated when it comes in contact with the water
spray, the water continues to evaporate till the air becomes saturated.
The minimum temperature to which water can be cooled is the adiabatic
saturation or wet bulb temperature of the ambient air.
Evaporation
Causing cooling
According to the draft type the wet cooling
tower is further classified as
1. Mechanical draught
a. Induced draught
b. forced draught
2. Natural draught
Fig: Natural draught cooling tower
Design parameters of cooling towers
A cooling tower is specified by
a. Approach
b. Range
c. Cooling efficiency
a. Approach (A): the difference between the exit cooling water
temperature and the wet bulb temperature of the ambient air
(minimum achievable), or
b. The cooling range or simply range(R) is defined as the
difference in temperature of the incoming warm water (tc1) and
the exiting cooled water (tc2), or
c. The cooling efficiency is defined as the ratio of the actual
cooling water to the maximum cooling possible, or
CCttA oo
wbc 8to6;2
C10 toC6; oo
21 cc ttR
wbc
cccooling
tt
tt
1
21
possiblecoolingmaximum
coolingactual
Dry cooling towers
Advantages of dry cooling towers:
1) There is no thermal pollution and loss of water due to evaporation.
2) Power plant can be located closer to the load centre (does not large supply of cooling water)
Disadvantages:
1) they are not as effective as evaporative cooling. As their performance is dependent on the atmospheric conditions and
so turbine exhaust temperatures are much higher resulting in a substantial loss of turbine efficiency ,
most critical in warm climates.
2) Due to low heat transfer coefficient , dry cooling towers require enormous volumes of air, large surface areas and are
less effective at high natural air temperatures.
Wet Cooling Tower Analysis
• Ambient air is used to cool the warm water exiting the
condenser. Properties associated with air-water vapor mixture
• Atmospheric air (dry air plus water vapor) pressure is given by
• Relative humidity
aw ppp
s
w
p
p
etemperaturairtheatpressuresaturation
airinvaporwatertheofpressurepartialRH )(
ps
pw
td.p.
td.b.
Dew point temperature (tdw) is the
temperature at which water vapor starts to
condense when cooled at constant pressure
Dry bulb (tdb) is the temperature recorded by a
thermometer with a dry bulb.
Wet bulb (twb) is the temperature recorded by
a thermometer when the bulb is enveloped by
a cotton wick saturated with water
Wet Cooling Tower Analysis(contd.)
• Humidity Ratio (w)
• If dry and water vapor act as ideal gases
• Degree of saturation is the ratio of the actual specific humidity
to the saturated specific humidity, both at the same
temperature T,
]/[ airdrykgvaporkgm
m
m
m
airdryofMass
airtheinvaporwaterofMass
a
w
a
w
w
w
pp
p622.0
w
s
s
w
s pp
pp
p
p
Wet Cooling Tower Analysis(contd.)• If is the make-up water supplied to replenish the
evaporative loss, then
• Energy balance,
airdrykgvaporkghumidityspecfic
airdryofrateflowmassmwhere
mm
a
amw
/,
;
12
44223311 cwcwawmwcwcwa hmhmhmhmhm
waacwcwcw hmhhmhhm 121243
m wm
wa
cwpw
acwcw hmhh
mc
mttRRange 121243)(
13)( wbcw ttAApproach
Fig: temperature relationship in counter flow cooling tower
Example 1
A surface condenser receives 250 ton/h of steam at 40oC with
12% moisture. The cooling water enters at 32oC and leaves at
38oC. The pressure inside the condenser is found to be 0.078 bar.
The velocity of circulating water is 1.8 m/s. The condenser tubes
are of 25.4 mm OD and 1.25 mm thickness. Taking the overall
heat transfer coefficient as 2600 W/m2K, determine (a) the rate of
flow of cooling water, b) the rate of air leakage into the condenser
shell, c) the length of tubes, and d) the number of tubes.
Example 2
The following readings were taken during a test on surface
condenser:
Mean condenser temperature = 35oC, Hot well temperature=
30oC, condenser vacuum=69 cmHg, Barometric reading 76
cmHg. Condensate collected 16 kg/min. Cooling water enters at
20oC and leaves at 32.5oC, flow rate being 37,500 kg/h. Calculate
(a) mass of air present per cubic meter of condenser, b) quality of
steam at condenser inlet, c) vacuum efficiency, and d) condenser
efficiency.
Example 3
Water at 30 oC flows into a cooling tower at the rate of 1.15 kg/kg
air. Moist air enters the tower at 8 m3/s volumetric flowrate, 20 oC dbt and a relative humidity of 60%. It leaves at 28oC dbt and
90% relative humidity. Makeup water is supplied at 20oC.
Determine (a) evaluate the mass flow rate of the dry air, b) the
temperature of water leaving the tower, c) the make up water,
and d) the approach and range of the cooling tower. Assume the
atmospheric pressure is 1 atm.
Example 4
Water exiting the condenser of a power plant at 45 C enters a cooling tower
with a mass flow rate of 15000 kg/s. A stream of cooled water is returned to
the condenser from the cooling tower with the same flow rate. Make-up water
is added in a separate stream at 20 C. Atmospheric air enters the cooling tower
at 30 C with a wet bulb temperature of 20 C. The volumetric flow rate of
moist air into the cooling tower is 8000 m3/s. Moist air exits the tower at 40 C
and 90% relative humidity. Assume an atmospheric pressure of 101.3 kPa.
Determine:
a) the mass flow rate of dry air,
b) the mass flow rate of make-up water, and
c) the temperature of the cooled liquid water exiting the cooling tower.