Page 1: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

INSTALLATION AND OPERATING INSTRUCTIONS

2545

546

HLK

EN

140

8H

LK V

ersi

on

Resistive Humidifiers

Condair CS 2.0/4.0

Page 2: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

2

Page 3: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

3

Contents

1 Introduction 41.1 To the very beginning 41.2 Notes on the installation and

operating instructions 4

2 For your safety 6

3 Product overview 83.1 Steamhumidifierconstruction 83.2 Function of the display and

operating elements 93.3 Product designation 93.4 Functional description 103.5 Humidificationsystemoverview 113.6 Options 123.7 Accessories 123.8 Standarddelivery 133.9 Storing/Transport/Packaging 13

4 Installation 144.1 Important notes on the installation 144.2 Installationoverview 154.3 Unitfitting 164.3.1 Noteonlocatingandfittingtheunit 164.3.2 Wall mounting 174.3.3 Floormounting 184.3.4 Inspecting the installed unit 194.4 Steam installation 204.4.1 Steam distribution pipe 204.4.1.1 Positioning of the steam distribution pipe 204.4.1.2 Installing the steam distribution pipe 224.4.2 Installation of the steam and

condensate line 234.4.2.1 LayoutwithsteamhoseDS60 234.4.2.2 Layoutwithfixedpiping 254.4.3 Inspecting the steam installation 274.5 Waterinstallation 284.5.1 Overviewwaterinstallation 284.5.2 Noteonwaterinstallation 294.5.3 Inspectingthewaterinstallation 304.6 Electric installation 314.6.1 Wiring diagram 314.6.2 Notes on electric installation 334.6.3 Inspecting the electrical installation 33

5 Operation 345.1 Putting into operation 345.2 Indication of the operating status

on the unit 355.3 Function of the remote indication

relays during operation 365.4 Notes on operation 365.5 Taking out of operation 36

6 Maintenance 376.1 Important notes on maintenance 376.2 Maintenanceintervals/Maintenancelist 386.3 Removing and installing parts for

maintenance 396.4 Notes on cleaning the unit components 466.5 Resetting the maintenance counter

(maintenanceindication) 48

7 Malfunctions 497.1 Fault indication 497.2 Malfunction list 497.3 Notes on fault elimination 527.4 Resetting error indication 52

8 Taking out of service/Disposal 538.1 Takingoutofservice 538.2 Disposal/Recycling 53

9 Productspecifications 549.1 Technical data 549.2 Unit dimensions 55

Page 4: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

4

LimitationThesubjectoftheseinstallationandoperatinginstructionsisthesteamhumidifierCondairCS.Thevariousaccessories(e.g.steamdistributor,filtervalve,etc.)areonlydescribedinsofarasthis is necessary for proper operation of the equipment. Further information on accessories can be obtained in the respective instructions.

These installation and operating instructions are restricted to the installation, commissioning, operation, servicing, and trouble-shootingofthesteamhumidifierCondairCSandismeantforwelltrainedpersonnelbeingsufficientlyqualifiedfortheirrespectivework.

The installation and operating instructions are supplemented by various separate items of documen-tation (spare parts list, manuals for accessories, etc.). Where necessary, appropriate cross-references are made to these publications in the installation and operating instructions.

1 Introduction

We thank you for having purchased the steamhumidifierCondairCS.

ThesteamhumidifierCondairCSincorporatesthelatesttechnicaladvancesandmeetsallrecog-nizedsafetystandards.Nevertheless,improperuseofthesteamhumidifierCondairCSmayresultin danger to the user or third parties and/or impairment of material assets.

Toensureasafe,proper,andeconomicaloperationof thesteamhumidifierCondairCS,pleaseobserveandcomplywithallinformationandsafetyinstructionscontainedinthepresentinstallationand operating instructions.

Ifyouhavequestions,whicharenotorinsufficientlyansweredinthisdocumentation,pleasecontactyourCondairsupplier.Theywillbegladtoassistyou.

1.2 Notes on the installation and operating instructions

1.1 To the very beginning

Page 5: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

5

Symbols used in this manual

CAUTION!Thecatchword“CAUTION”designatesnotesinthisdocumentationthat,ifneglected,maycausedamage and/or malfunction of the unit or other material assets.

WARNING!

Thecatchword“WARNING”usedinconjunctionwiththegeneralcautionsymboldesignatessafetyand danger notes in this documentation that, if neglected, may cause to injury to persons.

DANGER!

Thecatchword“DANGER”usedinconjunctionwiththegeneralcautionsymboldesignatessafetyand danger notes in this documentation that, if neglected, may lead to severe injury or even death of persons.

SafekeepingPleasesafeguardtheseinstallationandoperatinginstructionsinasafeplace,wheretheycanbeimmediately accessed. If the equipment changes hands, the documentation must be passed on to thenewoperator.

Ifthedocumentationgetsmislaid,pleasecontactyourCondairsupplier.

Language versionsThese installation and operating instructions are available in various languages. Please contact your Condairsupplierforinformation.

Copyright protectionThepresentinstallationandoperatinginstructionsisprotectedundertheCopyrightAct.Passing-onandreproductionofthemanual(orpartthereof)aswellasexploitationandcommunicationofthecontentsareprohibitedwithoutwrittenpermissionbythemanufacturer.Violationofcopyrighttermsissubjecttolegalprosecutionandarisesliabilityforindemnification.

Themanufacturerreservestherighttofullyexploitcommercialpatentrights.

Page 6: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

6

2 For your safety

GeneralEverypersonworkingwith theCondairCSmusthave readandunderstood the installationandoperatinginstructionsbeforecarryingoutanywork.Knowingandunderstanding thecontentsof the installationandoperating instructions isabasicrequirement for protecting the personnel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly.

All ideograms, signs and markings applied to the unit must be observed and kept in readable state.

QualificationofpersonnelAllwork(installation,operating,servicing,etc.)describedintheseinstallationandoperatinginstruc-tions mayonlybecarriedoutbyspecialistwhoarewelltrainedandadequatelyqualifiedandare authorized by the customer.Forsafetyandwarrantyreasonsanyactionbeyondthescopeofthismanualmustbecarriedoutonlybyqualifiedpersonnelauthorisedbythemanufacturer.

ItisassumedthatallpersonsworkingwiththeCondairCSarefamiliarandcomplywiththeappro-priateregulationsonworksafetyandthepreventionofaccidents.

Thisunitmaynotbeusedbypersons(includingchildren)withreducedphysical,sensoryormentalabilitiesorpersonswithlackingexperienceand/orknowledge,unlesstheyaresupervisedbyapersonresponsiblefortheirsafetyortheyreceivedinstructionsonhowtooperatetheunit.Childrenmustbesupervisedtomakesurethattheydonotplaywithunit.

Intended useSteamhumidifiersCondairCSareintendedexclusivelyfordirectairhumidificationviaasteamdistributor approved by the manufacturer withinthespecifiedoperatingconditions(seechapter9“Productspecifications”.Anyothertypeofapplication,withoutthewrittenconsentofyourCondairsupplier,isconsideredasnotconformingwiththeintendedpurposeandmayleadtotheCondairCSbecomingdangerous.Operation of the equipment in the intended manner requires that all the information in these ins-tructions are observed (in particular the safety instructions).

Page 7: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

7

Danger that may arise from the unit

DANGER!Danger of electrical shock!

The Condair CS is mains powered. One may get in touch with live parts when the unit is open. Touching live parts may cause severe injury or danger to life.Prevention:BeforecarryingoutanyworksettheCondairCSoutofoperationasdescribedinchapter5.5(switchofftheunit,disconnectitfromthemainsandstopthewatersupply)andsecuretheunitagainstinadvertentpower-up.

WARNING! Hot water vapour - Danger of scalding!

The Condair CS produces hot water vapour. There is danger of scalding when getting in touch with hot water vapour. Prevention:Donotcarryoutanyworkonthesteamsystemduringoperation(steamlines,steamdistributor,etc.).IfthesteamsystemisleakysettheCondairCSimmediatelyoutofoperationasdescribedinchapter5.5.Correctlysealthesteamsystembeforeputtingtheunitintooperationagain.

WARNING! Danger of burning!

During operation the components of the steam system get very hot (up to 100 °C). There is danger of burning when touching the hot components.Prevention: BeforecarryingoutanyworkonthesteamsystemsettheCondairCSoutofoperationasdescribedinchapter5.5,thenwaituntilthecomponentshavecooleddownsufficientlythuspreventing danger of burning.

Behaviour in case of dangerIf it is suspected that safe operation is no longer possible,thentheCondairCSshouldimmediatelybe shut down and secured against accidental power-up according to chapter 5.5. This can be thecaseunderthefollowingcircumstances:

– iftheCondairCSisdamaged– iftheCondairCSisnolongeroperatingcorrectly– if connections and/or piping are not sealed or cables are loose

AllpersonsworkingwiththeCondairCSmustreportanyalterationstotheunitthatmayaffectsafetytotheownerwithoutdelay.

ProhibitedmodificationstotheunitNomodificationsmustbeundertakenontheCondairCSwithouttheexpresswrittenconsentofthe manufacturer.

Forthereplacementofdefectivecomponentsuseexclusivelyoriginal accessories and spare parts availablefromyourCondairsupplier.

Page 8: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

8

3 Product overview

1 Drainkey 2 Unitswitch(On/Off) 3 LEDred“Error” 4 LEDyellow“Warning” 5 LEDgreen“Steamproduction” 6 Excesstemperatureswitchelectronic 7 Controlboard 8 Steamcylinder 9 Cylinderinsert 10 Heating elements 11 Water supply connector R 3/4" 12 Water drain connector ø 40 mm13 Excesstemperatureswitchsteamcylinder 14 Steam outlet connector ø 30 mm

3.1 Steamhumidifierconstruction

15 Steam cylinder support 16 Water cup 17 Water supply hose18 Fillinghose19 Overflow/drainhose20 Couplingsleeve21 Auxiliarydrainhose22 Drainpump23 Floatswitchbasetub 24 Pressure equalizing hose 25 Type plate 26 Inlet valve27 Cableopenings28 Connectionterminalmainssupply

1514

13

12

11

7

10

16

21

27

25

19 2826

19

17

18

24

22

21

20

23

98

6

543

12

Page 9: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

9

3.3 Product designation

Condair AG, CH-8808 Pfäffikon

Made in Switzerland

CS 4.0

Max. Dampf 4kg/hZuleitungsdruck 1...10 bar

AC 230V 50Hz 3.0 kWXXXXXXX 11.06

Type designation Serial number (7-digit) Month/Year

Supply voltage

Maximumsteamcapacity

Admissiblewatersupplypressure

Fieldwithcertificationsymbols

3.2 Function of the display and operating elements

Drain keyFunctions: – Manualflushing(watersupplyopen)ormanual

draining(watersupplyclosed)ofthesteamcyl-inder. By pressing the key the drain pump starts. By pressing the key again the drain pump stops.

– Resetting the maintenance counter/maintenance indication(yellowLED“Warning”flashes8x)

Withtheunitswitchedoff,depressandholdthedrainkeythen,switchontheunit.

Unit switchFunction: Switchingtheunitonandoff

green LED “Steam”Function: flashes1x:unitisreadyforoperation flashes2x:testoflevelunitinprogress lights:unitisproducingsteam

yellow LED “Warning”Function: flashesifamalfunctionispresentbutfurtheropera-

tionisstillpossible(thenumberofflashesindicatesthe type of malfunction, see chapter 7).

red LED “Error”Function: flashesifamalfunctionispresentwhichobstructs

furtheroperationoftheunit(thenumberofflashesindicates the type of malfunction, see chapter 7).

Theproductdesignationisfoundontheratingplate:

Powerconsumption

Page 10: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

10

3.4 Functional description

TheCondairCSsteamhumidifierisanunpressurizedsteamgenerator.Itoperatesontheresistanceheatingprincipleandisdesignedforairhumidificationviaasteamdistributionpipe.

Water supplyThewateristakenviaafiltervalve(accessory“Z261”)tothesteamhumidifier.Itreachesthesteamcylinderviatheinletvalve(levelcontrolled)andtheopenwatercup.

Level regulationThewaterlevelinthesteamcylinderiscontinuouslymonitoredwiththelevelunit.Ifthewaterlevelreachesapresetlevel(owingtotheevaporationprocess)thelevelunitsuppliesasignaltothecon-troller.Thisopenstheinletvalveandthesteamcylinderisfilledup.Whenthepresetoperatinglevelis reached, the level unit supplies another signal to the controller to close the inlet valve.Thepressureequalizingpipebetweenthesteamconnectionandthelevelunitensuresthatthewaterlevels are the same in the steam cylinder and the level unit.

Steam generation regulationThesteamisproducedinthesteamcylinderbytworesistanceheatingelements.Thesteampro-ductioniscontrolledviaanexternalhumidistat(On/Offcontrol)oranexternalcontinuoushumiditycontroller0...10V(continuouscontrol).

FlushingTheevaporationprocessincreasestheconcentrationofmineralsinthewaterofthesteamcylinder.Asuitablevolumeofwatermustbeflushedthroughthesteamcylinderfromtimetotimeandreplacedbyfreshwatertoensurethatthisconcentrationdoesnotexceedaspecificvalueunsuitableforoperation.TheCondairCSsteamhumidifierperformsanauto-adaptiveflushing.Thisconsistsofthefollowingtwoformsofflushing:

– Automaticflushingtakesplaceassoonasthewaterinthesteamcylinderexceedstheupperoperatinglevel(e.g.byfoamingofthewater).

– Flushing dependent on time performstheflushingprocessatpreselected time intervals (inaccordancewiththelocalwaterquality).

Automaticortime-dependentflushingtakesplacedependingonthewaterqualityandtheoperatingdata.Ifthelowestoperatinglevelisreachedduringtheflushingprocess,theinletvalveremainsopenuntilthewaterlevelinthesteamcylinderhasreachedthenormalworkinglevelagain.Ifthelowestoperating level is not reached, the inlet valve is closed.

Page 11: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

11

1 Steamhumidifier 2 Continuoushumiditycontroller0...10V

(room or duct) 3 On/Off humidistat (room or duct) 4 Humiditysensor0-10V

(supplyairlimitation,signalZl) 5 Safety humidistat (room or duct) 6 Voltagesupply 7 Water drain connector

3.5 Humidificationsystemoverview

8 Watersupplyconnector 9 Drainpipe(bycustomer)10 Watersupplyhose(accessory“WIT”)11 Filtervalve(accessory“Z261”) 12 Water drain building side

(funnelwithsiphon)13 Steamhose(accessory“DS60”)14 Condensatehose(accessory“KS10”)15 Steamdistributionpipe(accessory“61-..”)

1 ... 40 °C1 ... 10 bar

min. 1 °Cmax. 40 °C

max. 75 %rFR 3/4"

IP21

80...90 °C

ø40 mm

ø40/32 mm

ø10/8 mm

AC 230V 50Hz9

10

11

12

1

6

78

2

13

15

14

4

5

3

YZ

or or or

or

Page 12: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

12

3.6 Options

Option Designation Description

Pressure compensation kit PCK Kit of hoses for mounting the water cup above the unit cover of the Condair CS to compensate back pressure in the steam hose of up to 2'000 Pa.

3.7 Accessories

Accessories for water installation

Accessory Designation Description

Water supply hose WIT Water connection pipe ø10/8 mm made of plastic with R 3/4" union nut (pressure-proofed and certified for drinking water supply systems). Pipe length 2 m.

Filter valve Z261 Shut-off valve with integrated filter for the installation in the water supply line.

Accessories for steam installation

Accessory Designation Description

Steam hose ø29/38 DS60 Heat-resistant plastic hose specially designed for the steam line. Specify the length in meter when ordering.

Condensate hose KS10 Specify the length in meter when ordering.

Steam distribution pipe 61-.. Type 1) Length (L) 2) steam distribution pipe in mm

Duct width (B)in mm

61-200 200 250...40061-350 350 400...60061-500 500 550...75061-650 650 700...90061-800 800 900...1100

1) material: CrNi steel 2) special length on request

R 1/2"R 1/2"

R 3/4"

Page 13: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

13

3.8 Standard delivery

Thestandarddeliveryincludes:

– SteamhumidifierCondairCScompl.incardboardbox(WxHxD:445mmx440mmx330mm,transportweight:13kg)with:– watersupplyhose– Fixingset– Installation and operating instructions (this document)

– Orderedoptionswithoperatinginstructionsaccordingtochapter3.6,packedseparately.

– Orderedaccessorieswithoperatinginstructionsaccordingtochapter3.7,packedseparately.

3.9 Storing/Transport/Packaging

StoringStoretheunitinaprotectedareameetingthefollowingrequirements:

– roomtemperature:1...40°C– roomhumidity:10...75%rh

TransportForoptimumprotectionalwaystransporttheunitintheoriginalpackaging.

Totransporttheunitwithoutpackagingholdtheunitwithbothhandsonitsbasetub(netweightoftheunit:11.5kg).Alwaysplacetheunitonitsbottomside.

PackagingKeeptheoriginalpackagingoftheCondairCSforlateruse.

Incaseyouwishtodisposeofthepackaging,observethelocalregulationsonwastedisposal.Neverdispose of the packaging to the environment.

Page 14: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

14

4 Installation

QualificationofpersonnelAllmountingandinstallationworkmustbecarriedoutonlybywellqualifiedpersonnelauthorisedby the owner.Itistheowner’sresponsibilitytoverifyproperqualificationofthepersonnel.

General note Strictly observe and comply with all information given in the present installation and operating instructionsregardingthelocationoftheunitandtheinstallationofwater,steamandelectricity.Observe and comply with all local regulationsdealingwithwater,steamandelectricalinstallations.

SafetySomeinstallationworkrequiresremovaloftheunitcover.Pleasenotethefollowing:

DANGER!Danger of electrical shock!

Youmaygetintouchwithlivepartswhentheunitisopen.Thesteamhumidifiermustbeconnected to the mains only after all mounting and installation work has been completed and the cover has been relocated properly.

CAUTION!The electronic componentsinsidethehumidifierarevery sensitive to electrostatic discharge. Whentheunitisopenforinstallationwork,appropriatemeasuresmustbetakentoprotect these components against damage caused by electrostatic discharge (ESD protection).

4.1 Important notes on the installation

Page 15: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

15

4.2 Installation overview

Water installation, see chapter 4.5

Electrical installation, see chapter 4.6

Steamfinstallation, see chapter 4.4

Unitfitting, see chapter 4.3

AC 230V 50Hz

2

4

5

3

YZ

Ømin. 200 mm

min. 1 °Cmax. 40 °C

max. 75 %rh

> 32 mm

Rmin.

300 mm

max.

2 mRmin. 300 mm

IP21

min.

300 m

m

60...70 °C

ø40 mm

ø40/32 mm

ø10/8 mm

Z261

min. 5 %–

min. 5 %–

min. 20 %+

1 ... 40 °C1 ... 10 bar

min. 10 %–

R 3/4"

17 kg

Ømin. 200 mm

max. 2 m

61-..

KS10

KS10

DS60

61-..

or or or

or

Page 16: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

16

min

. 300

mm

min. 250 mm

min. 250 mm

361 mm

min. 600 mm

350

mm

250 mm

4.3 Unitfitting

4.3.1 Noteonlocatingandfittingtheunit

Thefollowingpointsmustbeconsideredandobserved:

– Installthesteamhumidifiersothatthelengthofthesteamhoseiskeptasshortaspossible(max. 2 m) and the requirements regarding the leading of the steam hose can be met (see chapter 4.4).

– ThesteamhumidifiersCondairCSaredesignedforwall-andfloormounting.Makesurethattheconstruction(wall,pillar,floor-mountedconsole,etc.)towhichthehumidifieristobemounted,offersasufficientlyhighload-bearingcapacity(operatingweightofunit:17kg),andissuitablefor the installation.

CAUTION!Donotmountthesteamhumidifierdirectlytotheventilationduct(insufficientstability).

– ThehousingoftheCondairCSisretainingheatduringoperation(max.surfacetemperatureofthemetalhousingapprox.60-70°C).Makesure,therefore,thattheconstruction(wall,pillar,etc.)towhichtheunitistobemounted,doesnotconsistofheat-sensitivematerial.

– Installthesteamhumidifierinsuchamannerthatitisfreely accessiblewithsufficientspaceavailable for maintenance purposes (refer to the illustration above for minimum distances).

– TheCondairCSisprotectedaccordingtoIP21. Make sure the unit is installed in a drip-proof locationandtheadmissibleambientconditionsarecompliedwith.

Operating weight of the unit: 17 kgProtection class of the unit housing: IP21Surface temperature of housing during operation: 60 – 70 °CMax. admissible ambient temperature: 1 – 40 °CMax. admissible ambient humidity: 75 %rh

Page 17: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

17

4.3.2 Wall mounting

Procedure1. Markthethreeattachmentpointsonthewall.

2. Drillholes(diameter:8mm,depth:40mm).

3. Insertthesuppliedplasticplugsintotheholes,andtightenthescrewsuntilthedistancebetweenthewallandthescrewheadis4mm.

4. Unlockthetwoscrewsandremovetheunitcover.

5. Hanguptheunitonthescrews.Usethespiritleveltoadjusttheunithorizontallyandverticallythen,tightenthetopmostscrew.

6. Reattachtheunitcoverandlockitwiththetwoscrews.

– ThesteamhumidifierCondairCSmayonlybeinstalledinroomswithafloordrain.

CAUTION!IfforsomereasontheCondairCSmustbeinstalledinalocationwithoutfloordrain,itismandatorytoprovidealeakagemonitoringdevicetosafelyinterruptthewatersupplyincaseofleakage.

– WhenfixingtheCondairCS,useonlythefixingmaterialssuppliedwiththeunit.Iffixingwiththematerialssuppliedisnotpossibleinyourparticularcase,selectamethodoffixingthatisofsimilarstability.

300 mm

150 mm

15 m

m

100 mm100 mm

235

mm

ø 8

mm

40 mm 4 mm1. 2. 3.

6.

4.

5.

17 kg

Page 18: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

18

4.3.3 Floor mounting

Procedure1. Marktheattachmentpointsonthefloor(twooneachsideoftheunit).

Note:Themountingsurfacemustbeexactlyhorizontal(checkwithspiritlevel).

2. Drillholes(diameter:8mm,depth:40mm).

3. Insert the supplied plastic plugs into the holes.

4. Unlockthetwoscrewsandremovetheunitcover.

5. Fixtheunittothefloorusingthefourscrewssupplied.

6 Reattachtheunitcoverandlockitwiththetwoscrews.

ø 8 mm

40 m

m

2. 3.

6.

4.

5.

322 mm

209

42 mm

6,5 mm

157 mm42 mm

10 mm

8 mm

10 mm

3 mm

1.

17 kg

Page 19: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

19

4.3.4 Inspecting the installed unit

Checkthefollowingpoints:

Is the unit in the correct place (see chapter 4.3.1)?

Istheload-bearingcapacityoftheconstructiontowhichtheunitistobemountedsufficient?

Is the unit correctly aligned vertically and horizontally?

Is the unit properly secured (see chapters 4.3.2 and 4.3.3)?

Istheunitcoverreattachedandsecuredwiththetwoscrews?

Page 20: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

20

4.4 Steam installation

4.4.1 Steam distribution pipe

4.4.1.1 Positioning of the steam distribution pipe

The location for the steam distribution pipe should be determined at the time of dimensioning the airconditioningsystem.Pleasenotethefollowinginstructionstoensureproperhumidificationoftheduct air.

CalculatingthehumidificationdistanceThewater vapour, emitting from the steam distribution pipes, requires a certain distance to beabsorbed by the ambient air so that it is no longer visible as steam. This distance is referred to as humidificationdistance“BN” and serves as a basis for the determination of the minimum distances from the upstream components in the system.

Humidificationdistance BN Expansionandmixingzone

ϕ1:Supplyairhumiditybeforehumidificationϕ2:Supplyairhumidityafterhumidification

Thecalculationof thehumidificationdistance “BN” isdependentonseveral factors.Fora roughestimationofthehumidificationdistance“BN”,thefollowingtableisuseful.Recommendedstandardvalueslistedinthistablearebasedonasupply-airtemperaturerangeof15°Cto30°C.Thevaluesonly apply to steam distribution pipe 61-....

Humidity at inletϕ1 in %rh

LengthofhumidificationdistanceBN in m Humidity at outlet ϕ2 in %rh

40 50 60 70 80 905 0,9 1,1 1,4 1,8 2,3 3,5

10 0,8 1,0 1,3 1,7 2,2 3,420 0,7 0,9 1,2 1,5 2,1 3,230 0,5 0,8 1,0 1,4 1,9 2,940 – 0,5 0,8 1,2 1,7 2,750 – – 0,5 1,0 1,5 2,460 – – – 0,7 1,2 2,170 – – – – 0,8 1,7

ϕ1in%rh: Relativesupplyairhumiditypriortohumidificationatthelowestsupplyairtemperatureϕ2in%rh: Relativesupplyairhumidityafterthesteamdistributionpipeatmaximumcapacity

Examplegiven: ϕ1=30%rh,ϕ2=70%rh

humidificationdistanceBN: 1,4 m

Note:Ifthehumidificationdistancehastobereducedfortechnicalreasons,theamountofsteammustbedividedbetweentwo steam distribution pipes.Ifthisisthecase,contactyourCondairsupplier.

Page 21: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

21

1.5 x BN * BN BN5 cm

Minimum distances to be observedTopreventthewatervapour,thatisemittingfromthesteamdistributionpipe,fromcondensingondownstreamsystemcomponents,aminimumdistancetothesteamdistributionpipemustbeobser-ved(dependsonthehumidificationdistance“BN”).

before/after constriction after expansion before bend

before branch before diffuser before control sensor

before/afterfilter/register before/afterfan,zoneexit

Caution!Thehumidificationdistanceandderivedfromittheminimumdistancebetweenthesteamdistributorandsystemcomponentslocateddownstreamintheductaredeterminedonthebasisoftheexpectedoperatingparameters(e.g.airspeed,supplyairtemperature,etc.)whenplanningthesystem. An alteration of these operating parameters at a later time may induce that the determined humidificationdistance isnotcorrectany longerandsteam iscondensatingduringoperationonsystemcomponentslocateddownstreamintheduct.Thismayleadtodamageofthesystemand/oranexcessivegrowingofgerms.

Installation notes and dimensionsThe steam distribution pipes are designed for either horizontalinstallation(ontheductwall)or,withaccessories, for vertical installation(intheductfloor).Theoutletorificesshouldalwayspointupwardsandatrightanglestotheairflow.

If possible, the steam distribution pipes should be installed on the pressure side of the duct (max. duct pressure 300 Pa). If the steam distribution pipes are installed on the suction side of the duct, the maximum vacuum must not exceed 300 Pa.

Selectalocationfortheinstallation,tailoredtosuityourduct(seethefollowingillustrations)andposition the steam distribution pipes in the duct so that a uniform distribution of steam is achieved.

2,5xBNbeforeaerosolfilter

Page 22: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

22

Inpositioningthesteamdistributionpipes,thefollowingdimensionsshouldbeobserved:

hminhmin

1/2 H1/2

H

1/3

2/3H

H2/72/73/7

1/3 H1/31/3

2/7

2/7

3/7

H

1/21/2

hmin

gmin

g min.= 100 mmhmin.=85mm

H min.= 250 mm H≥400mm H min.= 200 mm

H min.= 400 mm H min.= 350 mm H min.= 300 mm

Guidelines for dimensioning the ventilation ducts– Tofacilitatetheinstallationofthesteamdistributionpipesandforcontrolpurposes,asufficiently

sized control opening should be planned.

– Withintherangeofthehumidificationdistance,theventilationductshouldbewaterproofed.

– Airductspassingthroughcoldroomsshouldbeinsulatedtopreventthehumidifiedairfromcon-densingalongtheductwall.

– Poorairflowconditionswithintheairduct(e.g.causedbyobstacles,tightbends,etc.)canleadtocondensationofthehumidifiedair.

– Steam distribution pipes must not be mounted to round ducts.

IfyouhavequestionsrelatingtothedimensioningofventilationductsincombinationwithsteamhumidifiersCondairCS,contactyourCondairsupplier.

4.4.1.2 Installing the steam distribution pipe

Detailedinformationontheinstallationofsteamdistributionpipe61-...canbefoundintheseparateMounting Instructions for this products.

Page 23: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

23

min.

300 m

m

Ømin. 200 mmKS10

61-....

Rmin.

300 mm

max.

2 mRmin. 300 mm min.

300 m

m

min. 5 %–

min. 5 %–

min. 20 %+

max. 2 m

DS60

1 23

24

5

6

ø29/38 mm

min. 20 %–

min

. 300

mm

Ømin. 200 mmKS10

61-....

4.4.2 Installation of the steam and condensate line

4.4.2.1 Layout with steam hose DS60

Overview

CAUTION!Use original Condair steam hose and condensate hose exclusively. Other types of hoses can cause undesired operational malfunctions.

1 Steam distribution pipe 61-... 2 Hose clamps 3 SteamhoseDS60(ø29/38mm) 4 Steamconnector(ø30/28mm) 5 CondensatehoseKS10 6 Drainfunnelwithsiphon(byclient)

Page 24: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

24

Note on leading the steam hose– Initially, lead the steam hose at least 300 mm perpendicularly upward above the top edge

ofthehumidifier, then lead thehosewithaminimum upslope of 20% and/or a minimum downslope of 5% to the steam distribution pipe.

– The steam hose should be kept as short as possible (max. 2 m)whileobservingtheminimum bend radius of 300 mm.Note:themaximum admissible pressure loss over the entire steam line is 300 Pa.Allowancemust be made for a pressure loss of 10 mm water column (approx. 100 Pa) per meter steam hoseorper90°bow.

Note:Ifyourparticularinstallationexceedsthemaximumsteamhoselengthof2mcontactyourCondairrepresentative.Inanycase,steam hoses longer than 2 m must be insulated in their entire length.

–DANGER!

Reducing the cross section or the complete closure of the steam pipe will cause an ex-cessive increase in pressure in the steam cylinder when the unit is operating and could lead to the risk of scalding accidents. Therefore you must comply with the following instructions:– When installing make sure the steam pipe is open over the entire length and through the

wholecrosssection.Anysealingplugs,adhesivesealingsheetsetc.mustberemovedbeforeconnectingthesteampipeandreductionsincrosssectionbykinking,forexample,mustbeavoided.

– Steam hoses must be prevented from sagging (condensate pockets); if necessary, support steamhosewithpipeclamps,trough,orwallbrackets,orinstallacondensatedrainatlowestpoint in the steam hose.

– It is not permitted to install a stop valve (e.g. a manually controlled stop valve, solenoid valve, etc.) in the steam pipe.

– Important! When deciding on the length and layout of the hose, it should be noted that the steam hosemaybecomesomewhatshorterwithprogressiveageing.

Securing the hoseThesteamhosemustbesecuredtothesteamdistributionpipeandthehumidifiersteamoutletbymeans of hose clamps.

CAUTION!To prevent the steam connector of the unit to be damaged, do not overtighten the hose clamp.

After having secured the steam hose to the steam outlet of the unit reattach the unit cover and lock itwiththetwoscrews.

Note on leading the condensate hoseCondensatehoseisleddownwithaminimum slope of 20 %, in the form of a siphon (min. hose bend diameter Ø200 mm),directlyintoadischargefunnelwithsiphon.

Note:Ifyourunitfeedsanumberofsteamdistributionpipes,theindividualcondensatehosesareto be led into the discharge funnel.

Important! Beforeputtingtheunitintooperation,thesiphonofthecondensatehosemustbefilledwithwater.

Page 25: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

25

4.4.2.2 Layoutwithfixedpiping

Overview

1 Steam distribution pipe 61-... 2 Hose clamps 3 Pieceofsteamhose(DS60) 4 Steamlinemadefromstainlesssteel(min.DIN1.4301) 5 Insulation (mandatory) 6 Steamconnector(ø30/28mm) 7 CondensatehoseKS10 8 Drainfunnelwithsiphon(byclient)

min.

300 m

m

Ømin. 200 mm

KS10

61-....

1

min.

300 m

m

min. 5 %–

min. 20 %+

Rmin.

100 mm

2

23

6

2

3

45

ø 24/28 mm

max. 2 m

7

8

CAUTION!Use original Condair condensate hose exclusively. Other types of condensate hoses can cause undesired operational malfunctions.

Page 26: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

26

NotesonmakingthesteamlinewithfixedpipingForsteamlineswithfixedpiping,thesameinstructionsapplytothelayingandthemaximumlengthofthepiping,asfortheversionwithsteamhoseDS60.Thefollowingadditionalnotesmustbeobserved:

– The minimum internal diameter of 24 mmmustbeappliedoverthewholelengthofthepiping.

– Useexclusivelystainlesssteelpiping(min.DIN1.4301).

– To minimize the condensate formation (=loss), the steam pipes must be insulated over the entire length.

– The minimum bend radius for rigid piping is 100 mm.

– Allowancemustbemadeforapressure loss of 10 mm water column (approx. 100 Pa) per meterlinelengthorper90°angle.

Securing the steam lineThe connection of the steam pipe to the steam distributor and the steam outlet of the steam humi-difieriseffectedbymeansofshortlengthsofsteamhose(use steam hose DS60)securedwithhose clamps.

CAUTION!To prevent the steam connector of the unit to be damaged, do not overtighten the hose clamp.

After having secured the pieces of steam hose to the steam outlet of the unit reattach the unit cover andlockitwiththetwoscrews.

Note on leading the condensate hoseCondensatehoseisleddownwithaminimum slope of 20 %, in the form of a siphon (min. hose bend diameter Ø200 mm),directlyintoadischargefunnelwithsiphon.

Note:Ifyourunitfeedsanumberofsteamdistributionpipes,theindividualcondensatehosesareto be led into the discharge funnel.

Important! Beforeputtingtheunitintooperation,thesiphonofthecondensatehosemustbefilledwithwater.

Page 27: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

27

4.4.3 Inspecting the steam installation

Checkthefollowingpoints:

– Steam distribution pipe

Steam distributors (steam distribution pipe or OptiSorp steam distribution system) correctly positionedandsecured(screwstightened)?

Aretheoutletorificesatrightanglestotheairflowdirection?

– Steam line

Isthemaximumlengthof2mmaintained?

Istheminimumbendradiusof300mm(100mmwithfixedpiping)maintained?

Have the instructions for layoutof thesteam linebeen followed (seechapter4.4.2.1and4.4.2.2)?

Isthesteampipeopenovertheentirelengthandthroughthewholecrosssection?

Steamhose:nosagging(condensatepocket)orisacondensatedrainwithsiphon(hosebendwithmin.diameterof200mm)installedatthelowestpointinthesteamline?

Rigid steam lines: properly insulated?Correct installationmaterial used?Minimal internaldiameter maintained?

Steamhose(orpiecesofsteamhose,respectively)securelyattachedwithclamps?

Heatexpansionduringoperationandshorteningofthehosewithageingtakenintoconside-ration?

Istheunitcoverreattachedandsecuredwiththetwoscrews?

– Condensatehose

Downslopeofatleast20%?

Siphon(min.ø200mm)existingandfilledwithwater?

Condensatehosecorrectlyfixedandnotkinked?

Page 28: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

28

4.5 Water installation

4.5.1 Overview water installation

1 Supply line (min. inner diameter: 8 mm) 2 Manometer (installation recommended, building side) 3 Filter valve (accessory “Z261”, installation mandatory) 4 Water supply hose 90° with union nut R 3/4" (accessory “WIT”) 5 Water supply connector, outside thread R 3/4" 6 Water drain connector, inner diameter 40 mm 7 Drain line (building side, min. inner diameter: 32 mm, min. down-slope 10%) 8 Drain line building side

(funnel with siphon, min. inner diameter: 32 mm)

> 32 mm

R 3/4"

80...90 °C

ø40 mm

ø40/32 mm

ø10/8 mm

ø10/8 mmZ261

1 ... 40 °C1 ... 10 bar

min. 10 %–

min. 10 %–

1

2

3

4

8

7

5

6

Page 29: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

29

4.5.2 Note on water installation

Important: Before connecting the water supply and water drain remove plastic sealing caps from the connectors on the unit.

Water supplyThe water supply is to be carried out according to the figure found in chapter 4.5.1 and the applicable local regulations for water installations. The indicated connection specifications must be observed.

– The installation of the filter valve (accessory Z261, alternatively, a shut-off valve and a water filter may be installed) should be made as close as possible to the steam humidifier

CAUTION!The thread at the humidifier connection is made of plastic. To avoid overtightening, the union nut of the water pipe must be tightened by hand only.

– Notes on water quality:

– For the water supply of the Condair CS, use fully demineralised water.Note: The use of fully demineralised water reduces the time for maintenance and cleaning to a minimum.

– The use of additives such as corrosion inhibitors, disinfectants, etc. is not allowed, since these additives may endanger health and affect proper operation.

– If the Condair CS shall be operated with untreated drinking water, softened or partly softened water, please contact your Condair supplier.

– The connection material must be pressure-proof and certified for use in drinking water supply systems.

When making connections to a fully demineralised water system, use exclusively plastic or stainless steel installation materials (min. DIN 1.4301). Other materials will be attacked by the fully demineralised water.

– Important! Before connecting the water line to the unit, the line must be flushed thoroughly.

Water drainThe water drain is to be carried out according to the figure found in chapter 4.5.1 and the applicable local regulations for water installations. The indicated connection specifications must be observed.

– Make certain that the drain pipe is correctly fixed and easily accessible for inspections and cleaning purposes.

– The drainage temperature is: 80…90 °C. Use only temperature-resistant installation material!

– When operating the Condair CS with fully demineralised water, use exclusively plastic or stain-less steel installation materials (min. DIN 1.4301). Other materials will be attacked by the fully demineralised water.

Page 30: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

30

4.5.3 Inspecting the water installation

Checkthefollowingpoints:

– Water supply

Hasfiltervalveorshut-offvalveandfilter5µmrespectivelybeeninstalledinsupplyline?

Haveadmissiblewaterpressure(1–10bar)andtemperature(1–40°C)beenobserved?

Is the minimum inside diameter of the supply pipe maintained throughout the entire length?

Are all pipes properly secured (threaded connections tightened)?

Is the feed pipe properly sealed?

Doesthewatersupplyinstallationmeettherequirementsofthelocalregulationsforwaterinstallations?

– Water drain

Is the minimum inside diameter of the drain pipe of 40 mm maintained throughout the entire length?

Hasdrainpipebeeninstalledwithadownslopeofatleast10%?

Hastheheatresistanceofthematerialusedbeenverifiedtobeatleast100°C?

Are hoses and lines properly secured (hose clamps and threaded connections tightened)?

Doesthewaterdraininstallationmeettherequirementsofthelocalregulationsforwaterinstallations?

Page 31: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

31

4.6 Electric installation

4.6.1 Wiring diagram

F6 External fuse voltage supply (16 A, slow acting)J1 Short circuited, if no external monitoring devices (e.g. ventilation

interlock “B1”, airflow monitor “B2”, Safety humidistat “B3”) are connected to connection terminal X12

Q External service switch (with minimum contact opening of 3 mm)S1 DIP switch (function see table in the above wiring diagram)X0 Connection terminal voltage supply (see following table)X.. Connection terminal (see following table)

11

1

111

4 3 2 1

OFF

ON

1

1 2

12

31

23

12

31

23

45

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

4 3 2 1

GND

24 VDC/6W

X4

12

3

P

N

PE

X18

X5

X6

X7

X8X9X11 X10X12

X14

X15

X16

X17

F4

Stea

mM

aint

enan

ceEr

ror

On

Ext. Safety chain

B3B2B1J1

X1

12

3

P

N

PE

X2

12

3

P

N

PE

X3

12

3

P

N

PE

F1X0

F5

F2

Mai

ns

L1NPE

L1

N

PE

Q

230

V/1~

/ 50H

z

F6

12

34

56

78

Z-GND

R

R-GND

Z

GND

24 VDC

X13

S1Z

GND

A2

ON-OFF

45

6

Z-GND

R

24 VDC

78

A3

–+φ 56

Z

Z-GND

A1

–+

P / PI

A1 Continuous humidity controller 0...10 V (signal Y)A2 On/Off humidistatA3 Humidity sensor 0...10 V (supply air limitation signal Z)B1 Ventilation interlockB2 Airflow monitorB3 Safety humidistatF1 Fuse control board (3,15 A, slow acting)F2 Fuse Heating High (10 A, slow acting) F4 Fuse Heating Low (10 A, slow acting)F5 Fuse drain pump (500 mA, slow acting)

S1 Function1 OFF: cylinder draining after 15 filling cycles

(factory setting)ON: cylinder draining after 30 filling cycles

2 OFF: standard switching on threshold (factory setting)

ON: increased switching on threshold (de-mand >15%)

3 OFF: maintenance interval 1000 hON: maintenance interval 500 h

(factory setting)Note: a modification of the setting becomes only active after resetting the maintenance counter (see chapter 6.5).

4 OFF: no cylinder draining in standby operati-on (factory setting)

ON: cylinder draining after 24 h without humidity demand

Page 32: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

32

Connection Description Connection-No.

Designation of connection

Cable cross section in mm2

X0 Mains supply AC 230V 50Hz N Neutral 1.5

L1 Phase 1.5

PE Ground 1.5

X12 External safety chainCable bridge “J” installed

1 -- 0.34

2 -- 0.34

X13 External continuous humidity controller 0...10 V, connected to terminals 3 (–) and 4 (+)orExternal On/Off humidistat, connected to terminals 4 and 8––––––––––––––––––––––––––––Supply air limitation signal: humidity sensor 0...10 V, connected to terminals 5 (–) and 6 (+)

1 -- --

2 -- --

3 R-GND 0.34

4 Request 0.34

5 Z-GND 0.34

6 Z 0.34

7 GND 0.34

8 24 VDC 0.34

X14 Relay outlet “On”The relay is activated if the unit is swit-ched on and in stand-by mode (no steam production in progress).

Max. contact loading: 24V/1A (AC/DC)

1 Common 0.34

2 NC 0.34

3 NO 0.34

4 GND 0.34

5 24 VDC 0.34

X15 Relay outlet “Error”The relay is activated if a malfunction is present.

Max. contact loading: 24V/1A (AC/DC)

1 Common 0.34

2 NC 0.34

3 NO 0.34

X16 Relay outlet “Service”The relay is activated as soon as the maintenance counter has expired.

Max. contact loading: 24V/1A (AC/DC)

1 Common 0.34

2 NC 0.34

3 NO 0.34

X17 Relay outlet “Steam”The relay is activated as soon as steam is produced. If the water supply is interrupted the relay is activated and deactivated 3 times for a short time followed by a longer period of inactivity.

Max. contact loading: 24V/1A (AC/DC)

1 Common 0.34

2 NC 0.34

3 NO 0.34

Page 33: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

33

4.6.2 Notes on electric installation

– Theelectricinstallationmustbecarriedoutaccordingtothewiringdiagraminchapter4.6.1andtheapplicablelocalregulations.Allinformationgiveninthewiringdiagramantheconnectiontabletothewiringdiagrammustbefollowedandobserved.

– All cables must be lead into the unit via the cable openings and must be secured to the latches inthehousingwallbymeansofcablestraps(strainrelief).

4.6.3 Inspecting the electrical installation

Checkthefollowingpoints:

Doesthemainsvoltageappliedcorrespondtotherespectivedatastatedonthetypeplate?

Istheserviceswitch“Q”(withaminimumcontactopeningof3mm)installedinthemainssupplyline?

Areallcomponentscorrectlyconnectedinaccordancewiththewiringdiagram(seechapter4.6.1?

Are the minimum cross sections of the cables maintained (see table in chapter 4.6.1)?

Areallcablesleadintotheunitviathecableopeningsandcorrectlysecuredwithcablestrapstothelashesinthehousingwall?

Doestheelectricinstallationmeettheapplicablelocalregulationsforelectricinstallations?

Istheunitcoverreattachedandsecuredwiththetwoscrews?

Page 34: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

34

5 Operation

5.1 Putting into operation

Proceedasfollowswhenputtingtheunitintooperation:

1. Whenputtingthesteamhumidifierintooperationthefirsttimeorwhenputtingthesteamhumidifierintooperationafterworkhasbeencarriedoutonthesteamsystem,thecommissioningpersonnelmustmandatorycheckwhetherthesteampipeisopenovertheentirelength.Todothisproceedasfollows:

• UndothetwoscrewsoftheCondairCSunitcover,thenremovethecover.

• Undothehoseclampofthesteamhose,thenremovesteamhosefromtheconnectorofthesteam cylinder.

• Startuptheventilationsystemandcheckwhetheracleardraughtthatcorrespondsapproxi-mately to the pressure in the ventilation system (positive or negative pressure) can be detected at the open end of the steam hose removed.

DANGER!

A steam pipe that is reduced in cross section or completely closed will cause an exces-sive increase in pressure in the steam cylinder when the unit is operating and could lead to the risk of scalding accidents! Therefore: If no draught or only a slight one can be detected the steam pipe must be checked for blockagesandreductionsincrosssectionbeforecontinuingwithcommissioningandyoumustensurethatthesteampipeisopenacrosstheentirelengthandthroughthewholecrosssection.

2. Examinethesteamhumidifierandinstallationforpossibledamage.

DANGER!

Damageddevicesordeviceswithdamagedinstallationmaypresentdangertohumanlifeorcause severe damage to material assets. Damaged units and/or units with damaged or faulty installation must not be operated.

3. Mountunitcoverandfixitwiththetwoscrews.

4. Open the filtervalve / shut-off valveinthewatersupplyline.5. Switchontheserviceswitchforthemainssupply.

6. Switchonthesteamhumidifiermainswitch.

Theswitchlights.Thesteamhumidifiercarriesoutasystem test.ThethreeLEDslightforapprox.3 seconds.If a fault is detected during the system test, a corresponding fault message is triggered (see chapter 7).

Ifthesystemtestissuccessful,thesteamcylinderfillsupandafloattest is carried out (function checkonthelevelunit).DuringthefloattestthegreenLEDflashes2x.Note: Ifa fault isdetectedduring thefloat test,acorresponding faultmessage is triggered(seechapter 7).

Ifthefloattestissuccessful,theCondairCSwillbeinstand-by mode.ThegreenLEDflashes1x.

Page 35: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

35

TheLEDsontheunitindicatethefollowingoperatingstatus:

Indication on unit Meaning

green LED “Steam”

flashes 1x The unit is switched on ready for operation.

flashes 2x The unit performs a float test.

lights The unit produces steam.

yellow LED “Warning”

flashes with different intervals

A Warning is present (e.g. Maintenance due, yellow LED flashes 8x).---> see chapter 7 “Malfunctions”

red LED “Error”

flashes with different intervals

An Error is present.---> see chapter 7 “Malfunctions”

5.2 Indication of the operating status on the unit

7. The following procedure must be carried out only on the initial commissioning:• Checkforcorrectfunctioningofthemonitoringequipment(externalsafetycircuit).

• Checkthefunctionofthesteamhumidifier:Switchonthehumidificationby raising the set humidity value on the humidity controller/humidistat.Switchoffthehumidificationbyloweringthesethumidityvalueonthehumiditycontroller/humidistat.

• Setthedesiredhumidityvalueonthehumiditycontroller/humidistat.

Assoonas thehumidistator thehumiditycontroller requireshumidity,power isswitchedon forheating.ThegreenLEDlightsupandafterafewminutes(approx.10minutes)steamisproduced.

Page 36: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

36

DuringoperationoftheCondairCSthehumidificationsystemhastobeinspectedweekly.Onthisoccasioncheckthefollowing:

• thewaterandsteaminstallationforanyleakage.

• thesteamhumidifierandtheothersystemcomponentsforcorrectfixingandanydamage.

• theelectricinstallationforanydamage.

If the inspection reveals any irregularities (e.g. leakage, error indication) or any damaged components taketheCondairCSoutofoperationasdescribedinchapter5.5.Then,havethemalfunctionbeeliminatedorthedamagedcomponentbereplacedbyawelltrainedspecialist.

5.4 Notes on operation

5.5 Taking out of operation

Thefollowingprocedureisfollowedwhenitisrequiredtoshutdownthesteamhumidifier:

1. Iftheunithastobeswitchedoffbecauseofamalfunction,pleasenotetheerrorcode(numberofflashesoftheyelloworredLED).

2. Closethefiltervalve/shut-offvalveinthewatersupplyline.

3. Thisstepmustonlybecarriedoutiftheunithasbeopened(e.g.formaintenancework)oriftheunitistakenoutofoperationforanextendedperiodoftime:Pressthedrainkey,waituntilthepump has emptied the steam cylinder then, press the drain key again (drain pump stops).Ifthedrainpumpisdefectiveorifamalfunctionispresent(redLEDflashes)thesteamcylindermust be drained manually via the drain hose. After draining the steam cylinder close drain hose correctly and reattach the hose to the corresponding holder in the unit.

4. Actuatetheunitswitch.

5. Isolatethesteamhumidifierfromthemains:Switchoffserviceswitchinthemainssupplyline. Mark the service switchtopreventitfrombeingswitchedoninaccidentally.

WARNING! Danger of burning!

Ifsteamwasproducedjustbeforetheunitistakenoutofoperation,waitbeforeopeningtheunitandletthesteamcylindercooldowntopreventdangerofburning.

5.3 Function of the remote indication relays during operation

Detailedinformationregardingthefunctionoftheremoteindicationrelaysduringoperationcanbefoundinthetabletothewiringdiagraminchapter4.6.1.

Page 37: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

37

6 Maintenance

6.1 Important notes on maintenance

QualificationofpersonnelAllmaintenanceworkmustbecarriedoutonlybywellqualifiedandtrainedpersonnelauthorisedby the owner.Itistheowner’sresponsibilitytoverifyproperqualificationofthepersonnel.

General note Theinstructionsanddetailsformaintenanceworkmustbefollowedandupheld.

Onlythemaintenanceworkdescribedinthisdocumentationmaybecarriedout.

OnlyuseoriginalCondairsparepartstoreplacefaultyparts.

SafetySomemaintenanceworkrequiresremovaloftheunitcover.Pleasenotethefollowing:

DANGER!Danger of electrical shock!

You may get in touch with live parts when the unit is open. Touching live parts may cause severe injury or even lethal violation.Prevention: BeforecarryingoutanymaintenanceworksettheCondairCSoutofoperationasdescribedinchapter5.5(switchofftheunit,disconnectitfromthemainsandstopthewatersupply)andsecuretheunitagainstinadvertentpower-up.

CAUTION!The electronic componentsinsidethehumidifierarevery sensitive to electrostatic discharge.Prevention: Beforecarryingoutanymaintenanceworktotheelectricalorelectronicequipmentofthehumidifier,appropriatemeasures must be taken to protect the respective components against damage caused by electrostatic discharge (ESD protection).

Page 38: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

38

6.2 Maintenance intervals/Maintenance list

TheCondairCSisequippedwithamaintenancecounterwhichtriggersamaintenanceindicationafteraspecificperiodofoperation.Theintervaltimedependsonthewaterqualityandtheamountofsteamproduced.Exworks,thesetintervaltimeofthemaintenancecounterisbasedonawaterhardnessof11°DH.

As soon as the maintenance indicationappears:yellowLEDflashes8xa complete maintenancemustbecarriedout.Thecompletemaintenanceincludesthefollowingwork:

• Inspectthewaterandsteaminstallationsforcorrectsealinganddamage.

• Inspect the drain line for soiling, clean if necessary.

• Inspect the electrical installation for loose cables and damaged components.

• Inspectthesteam-airhumidifierfordamage.

• Dismantlethesteamcylinderandthecomponentsoftheinternalwatersystemaccordingchap-ter 6.3.

• Checkandcleanthesteamcylinder,thecomponentsoftheinternalwatersystemandtheunitinner chamber according chapter 6.4.

Note:Ifyoudiscoveranexcessivecalcifyingofthecomponentswhenmaintainingtheunitthemain-tenanceintervaltimemustbedecreased.InthatcasepleasecontactyourCondairrepresentative.

Note:The customer is responsible for the regular inspection, cleaning and disinfection of the duct sectioninwhichthesteamdistributorisinstalled.Thismustbeperformedinaccordancewiththehygiene regulations in force for operating air handling units.

Page 39: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

39

6.3 Removing and installing parts for maintenance

2. Undothetwoscrewsoftheunitcover,thenremovetheunitcover.

3. Disconnectthecablesoftheheatingelementsonthecontrolboard(terminalsX3andX4),thencarefully pull the cables through the openings into the cylinder compartment.

1. Set the Condair CS out of operation as described in chapter 5.5, disconnect it from the mains and secure the unit against inadvertent power-up.

32

54

4. Pushtheprotectingsleeveoftheexcesstemperatureswitchupwards,thencarefullydisconnectcables.

5. Release the hose clamp on the steam outlet of the unit, then detach the hose from the steam outlet connection.

X4

X3

Page 40: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

40

6. Undothetwoscrewsofthesteamcylindersupport,thenremovethecylindersupport.

7. Pushthelockofthecontrolboardassemblyupwards,thenslightlyliftthecontrolboardassemblyand turn it to the right until it comes to a stop.

76

98

8. Releasethehoseclampsonthesteamcylinderandonthelevelunitusingscrewdriver, thendetach the pressure compensating hose from the connections.

9. Carefullyliftthesteamcylinderoutofthecouplingsleeve,thenremoveittothefront.

CAUTION!Putsteamcylinderdowncarefullytoavoiddamagetothelowerconnectionpiece!

Page 41: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

41

1110

10. Open and remove the steam cylinder cover clamping ring.

11.Carefullyliftoffthecoverwiththeheatingelements,thenremoveDurosealantfromthecover.

CAUTION!Takecarewiththecoverwhilstitisremoved,soasnot to damage the heating elements.

Ifthecovercannotberemovedduetoheavycalcification(maintenanceperiodexceeded),placethesteamcylinderinabasinofformicacid(8%)untilitcanberemoved(Caution! Therefore observe instructions on the safe use of this cleaning agent).

WARNING!

Formic acid attacks the mucous membranes. Therefore observe instructions on the safe use of this cleaning agent,weargogglesandglovesandworkinawellventilatedroomoroutside.

12. If necessary, loosen the cylinder insert by lightly rotating it in either direction and lift it from the steam cylinder.

12

Page 42: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

42

13

13. If a heating element has to be replaced during servicing, dismantle the corresponding heating elementdownwardsasshownintheillustrationabove.

Assembly and installation of the steam cylinderAssembly of the steam cylinder takes place in reverse sequence of the steps 2 to 13. Please note thefollowinginstructions:

– Installationofanyheatingelementswhichhavebeenremovedshouldfollowtheillustrationinstep13.Theheatingelementsareidenticalandcanbeinterchangedamongeachother.ConnectthecablesoftheheatingelementstoterminalsPandNoftheterminalstripsX3orX4onthecontrolboard.

– BeforeinstallationofthesteamcylindercoverplacetheDurosealantaroundtheedgeofthecover.TheDurosealantmustbecleanandundamaged(replaceifnecessary).

– Before installation of the steam cylinder in the unit check O-rings in the coupling bush for damage and replace if necessary.

– Align steam cylinder in the unit so that the pressure compensation hose can be connected to the respectiveconnectiononthesteamcylinderwithouttension.

– Fastensteamhosewithhoseclamps.Aleakysteamhosecancausedampdamageintheinteriorof the unit.

Page 43: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

43

14.BecauseofthecompactdesignoftheCondairCSwerecommendtoremovethecomponentsoftheinternalwatersystemsasanassemblyanddisassembletheindividualcomponentsafterwards.Proceedasfollows:

a) Undothetwoscrewsatthewatersupplyconnectorandpushtheinletvalveintotheunit.

b) Releasethehoseclampofthewaterdrainhoseinsidetheunit,thenremovethehosefromthe connection.

c) Undothescrew,thenremovetheauxiliarydrainhosefromtheholder.

d) Carefullypullfixingclipofthewatercuptothefront,thenpushwatercupdownandforwardand free it from the holding device.

e) Carefully compress the holding device of the level unit (from outside), then pull the level unit andfreeitfromtheunitwall.

f) Undothetwoscrewsofthedrainpumpsupportontherightsideoftheunit.

g) Undothefourscrewsofthecouplingsleeve.

Nowremovetheelectricalcablesfromtherespectiveconnectionsoftheinletvalve,thelevelunitandthedrainpump.Placethecablesinawaythattheycannotbedamagedwhenthewatersystem assembly is removed.

14

a

bc

e

f

g

d

Page 44: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

44

15

15.Carefullyliftthewatersystemassemblyandremoveittothefront.

Page 45: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

45

16.Disassemblethecomponentsofthewatersystemasshowninthefigureabove.

Assembly and installation of the water systemTheassemblyandtheinstallationofthewatersystemtakesplaceinreversesequenceofthesteps14to16.Observethefollowingnotes:

• Assemblethewatersystemasshownintheillustrationinstep16butdonottightenthehoseclamps yet.

• Afterinstallingandfixingthewatersystemassemblyintheunit(step14)alignallhosesandfixthemwiththehoseclamps.

16

Page 46: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

46

Unit component What to clean and how to clean

Steam cylinder and steam cylinder insert

• Knockoffany limescaleasmuchaspossible. If thepartsareheavilycalcified,placetheminan8%formicacid solution, until the lime scale comes off.

• Finallywashpartsinalukewarmsoapsolutionand rinse wellwithtapwater.

Cover with heating elements • Immersecoverwiththefittedheatingelements(upto2cmbelow the rimof thecover) inacontainerwith8-percentformicacid.Allowtheacidtotakeeffectuntilthe scale coating has dissolved.

Note:Theheatingelementsdonothavetobeentirelyfree from scale.

• Finallyrinsetheheatingelementswellwithtapwater.

CAUTION! Ensure that the electrical connections and the electronic parts remain dry.

CAUTION! On no account remove lime scale from the heatingelementsusingtools(screwdriver,scraper,etc.)or by striking. This could damage the heating elements.

Coupling sleeve

Orificeø6mm

• RemoveO-ringsfromthecouplingsleeve.Useabrushto remove any lime scale from the coupling sleeve (do notuseawirebrush).Checktheorificewithadrillø6mm.

• Finallywashcouplingsleeveinalukewarmsoapsolu-tion andrinsewellwithtapwater.Then,refitO-rings.

Hoses • Removeanylimescalebyslightlyknockingonthetubesusingarubberhammer.Then,rinsethetubeswellwithhottapwater.

6.4 Notes on cleaning the unit components

Page 47: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

47

Unit component What to clean and how to clean

Level unit

Opening ø5 mm

• Flush level unitwith a lukewarmsoap solution, then flushwellwithtapwater.

• Iftheloweropeningisheavilycalcified:Undothethreescrews,thenremovefloat.Useabrushtoremoveanylimescalefromthehousingandthefloat(donotuseawirebrush).Freeupperandloweropeningusingadrillø5mm.Washcomponentswithalukewarmsoapsolu-tion,thenrinsewellwithtapwater.Finallyreassemblethe level unit.

Inlet valve

Strainer insert

• Removestrainerinsertwithpointedpliers.Useabrush(donotuseawirebrush)toremoveanylimescale.

• Washstrainerinsertwithalukewarmsoapsolution, then rinsewellwithtapwater.Remountstrainerinsert.

CAUTION! Ensure that the electrical connections re-main dry.

Drain pump

O-ring

pumpwheel

• Disassemblethedrainpump(bajonetcatchwithlock).

• Useabrushtoremoveanylimescalefromthepumphousingandthepumpwheel(donotuseawirebrush).Wash the pump withalukewarmsoapsolutionandrinsewellwithtapwater.

• Reassemblethedrainpump:moistentheO-ringandthe centering of the housing, then place O-ring on the centeringcollar.Assemblethepumpandlockit(bajonetcatch).

CAUTION! Ensure that the electrical connections re-main dry.

Interior of the unit (water side only) • Wipetheinterioroftheunitwithadampclothwithoutusing any cleaning agent.

CAUTION! Ensure that the electrical connections and electronic components remain dry.

Page 48: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

48

Notes on cleaning agentsOnly use cleaning agents stated in the table above. The use of disinfectants is only permitted if theyleavenotoxicresidues.Thecomponentsmustberinsedthoroughlywithwateraftercleaningin all cases.

WARNING!

Formic acid is indeed harmless to the skin, but it attacks the mucous membranes. Therefore prevent youreyesandrespiratorytractsfromgettingintouchwiththeacidanditsvapours(weargogglesandworkinawellventilatedroomoroutside).

CAUTION!Do not use any solvents, aromatized or halogenized hydrocarbons or other aggressive substances as they may cause damage to the components of the unit.

Itismandatorytoobserveandcomplywiththeinformationandinstructionsregardingcleaningagents.Observeinparticular:allinformationrelatingtotheprotectionofpersonnel,environmentalprotectionand restrictions regarding usage.

6.5 Resetting the maintenance counter (maintenance indication)

Whenmaintenanceworkhasbeencompleted,themaintenance countercanberesetasfollows:1. With the unit switched off,depressandholdthedrainswitch.2. Switchonthesteam-airhumidifierwiththeunitswitch.

3. Releasedrainswitch.

The maintenance counter is reset and the unit ready for operation.

Page 49: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

49

7 Malfunctions

Warning:yellowLEDflashes

Incaseofmalfunctionduringoperation,thehumidifiercontrolcheckswhetherthereisatemporaryproblem(e.g.watersupplyinterruptedforashorttime)orwhetheritcanresolvetheproblembytaking necessary measures. As long as the control tries to resolve the problem the yellow LED “Warning"flashes.Ifthecauseofthemalfunctiondisappearsofitsownaccordorifthecontrolcanrepairthemalfunc-tion,thewarningmessagewillautomaticallyswitchoff.

Error:redLEDflashes

If the control, after several attempts, fails to solve the problem (number of attempts depends on the type of malfunction) or if the problem obstructs further operation, the heating voltage is interrupted and the red LED “Error” blinks.

7.1 Fault indication

7.2 Malfunction list

Most operational malfunctions are not caused by faulty equipment but rather by improper installati-onordisregardingofplanningguidelines.Therefore,acompletefaultdiagnosisalwaysinvolvesathoroughexaminationoftheentiresystem.Often,thesteamhoseconnectionhasnotbeenproperlyexecuted,orthefaultlieswiththehumiditycontrolsystem.Thefollowingtablegivesalistofpossiblemalfunctions,theappropriatewarningorerrormessage,detailsoftheircause,andnotesonhowtodealwitheachproblem.

Malfunction/Indication Cause Remedy

Warningyellow LED

flashes...

Errorred LED

flashes...

1xMin.fillingtime

not reached (Warning only)

––– Water feed to steam cylinder heavilycalcified.Levelinsteamcylinder and level unit do not match.

Carryoutacompletemainte-nance.

Page 50: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

50

Malfunction/Indication Cause Remedy

Warningyellow LED

flashes...

Errorred LED

flashes...

2xExternal

safety chain interrupted

––– One or more monitoring devices (ventilatorinterlock,flowmoni-tor, safety humidistat, etc.) in theexternalsafetychainhavetriggered.

Checkmonitoringdevicesintheexternalsafetychain(ventilatorinterlock,flowmonitor,safetyhu-midistat, etc.) or check ventilation system and control system for malfunctions.

––– 2xInternal

safety chain interrupted

Connectiontoover-temperatureswitchonsteamcylinderbrokenorover-temperatureswitchfaulty.

Checkconnectionsorreplaceover-temperatureswitch.

Ambient temperature sensor defective.

Replace ambient temperature sensor.

Steam cylinder overheating, over-temperatureswitchhasresponded.

Inspect steam cylinder, clean if necessary.Resetexcesstempe-ratureswitchbypressingtheredbutton.

Electronictohot,excesstempe-ratureswitchonthecontrolboardhas triggered.

Switchoffunitandwaitforapprox.30minutes.Then,resetexcesstemperatureswitchbypressing the red button.

3xMax.filling

timeexceeded (Warning only)

––– Waterfeedblocked(mainwatertapclosed,filtervalveclosedorblocked).

Checkwaterfeed(openmainwa-tertap,openorcleanfiltervalve.

Waterpressuretoolow. Raisewaterpressure (range 1 to 10 bar)

Inletvalvedoesnotopen,filtersieve in Inlet valve blocked or inlet valve faulty.

Inspect electrical connections and fuseF2onsupplymodule.CleanfiltersieveorreplaceInletvalve.

Feed hoses inside the steam hu-midifiernotconnectedorkinked.

Inspect hoses inside unit and connect if necessary. Replace faulty hoses.

Level unit not connected. Connectlevelunit.

Float in the level unit sticking or level unit faulty.

Cleanorreplacelevelunit.

4x 4x Individual heating elements faulty. Replace faulty heating elements.

Max.vaporizationtime exceeded

Fuses F2 and/or F4 on the control board faulty.

Replace fuses on control board.

Mainsvoltagetoolow. Checkmainsvoltageandcon-nections

Steam lead too long or not insu-lated.

Maintainmaximumleadlengths(max.2m),Insulatesteamlead.

This error may also occur upon a cold start.

None.

Page 51: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

51

Malfunction/Indication Cause Remedy

Warningyellow LED

flashes...

Errorred LED

flashes...

5x 5x Drainpumpnotconnectedorfaulty.

Connectorreplacedrainpump.

Max.flushingtimeexceeded

Drainhoseinunitkinkedorblocked.

Inspect drain hose in unit, replace if necessary.

Wateroutletblocked(externaldrain pipe or siphon blocked).

Cleanwateroutletleadandsiphon.

Hoses to level unit blocked. Cleanorreplacehoses.

––– 6xInvalid level (Error only)

Level unit faulty. Replace level unit.

Magneticfieldinvicinityoflevelunit.

Eliminatemagneticfield.

––– 7xSteam pressu-re supervision

(Error only)

Steam hose blocked or restricted (watertrap).

Checksteamhose,cleanifnecessary and /or improve steam hose installation.

Back pressure in steam hose too high because of a too long steam hose.

Reduce length of steam hose.

––– 8xSafety level switchinbasetub has trig-

gered

Water accumulation in base tub, safetylevelswitchhastriggered.

Removewaterfrombasetub,thenfindthecauseforthewaterleakage and eliminate leakage.

Safetylevelswitchdefective. Replacesafetylevelswitch.

8xMaintenance

indication

––– Maintenanceintervalexpired. Perform maintenance.

Page 52: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

52

7.3 Notes on fault elimination

DANGER!

Inorder toeliminate faults, thesteamhumidifiermust be switched off and secured against unintentional reconnection as described in chapter 5.5. Take care that the electricity supply to themaincontactorisdisconnected(checkwithvoltagetester).

Onlyallowtrainedandqualifiedpersonneltorepairfaults.Faultsrelatingtoelectricalinstallation(e.g.changeofunitfuse)mustonlybecarriedoutbyauthorizedpersonneloryourCondairrepresentative’sservice technician.

Repair work and replacement of faulty components must only be carried out by your Condairrepresentative’sservicetechnician!

7.4 Resetting error indication

Toresettheerrorindication(redLEDflashes):

Switchoffsteamhumidifierforapprox.5secondsandthenswitchonagain.

Note:Ifthefaulthasnotbeeneliminatedtheerrorindicationappearsagainafterashorttime.

Page 53: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

53

8 Taking out of service/Disposal

8.1 Taking out of service

IftheCondairCSmustbereplacedorifthehumidificationsystemisnotneededanymore,proceedasfollows:

1. Take the unit out of operation as described in chapter 5.5.

2. Havetheunit(andallothersystemcomponents,ifnecessary)unmountedbyaqualifiedservicetechnician.

8.2 Disposal/Recycling

At the end of the service life the unit and its components must be returned to the manufacturer or to a collecting point for disposal or recycling according to the local regulations.

IncaseofdoubtpleasecontactyourlocaladministrationoryourCondairsupplier.

Page 54: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

54

9 Productspecifications

Condair CS 2.0 Condair CS 4.0

Max.Steamcapacity 2 kg/h 4 kg/h

Nominalpowerconsumption 1.5 kW 3.0 kW

Nominal current 6.5 A 13.0 A

Unit voltage AC230V50Hz

Control viaanexternalOn/Offhumidistator anexternalcontinuoushumiditycontroller0...10V

Admissible ambient temperature 1...40°C

Admissible ambient humidity 1...75%rh

Steam connection 30 mm (outside diameter of connector)

Max.backpressureatsteamconnection 300 Pa

Water supply–Connection–Admissiblewaterpressure–Admissiblewatertemperature– Water quality

Outside thread R 3/4"1 ... 10 bar1...40°C

fullydemineralisedwaterwithmax.20µS/cm

Water drain–Connection–Draintemperature

Drainsleevewithinnerdiameter40mmmax.90°C

Weights–Transportweight–Netweight–Operationweight

13 kg11.5 kg17 kg

Dimensions(HxWxD) 350x250x361mm

Conformity CE,VDE,GS

Protection class IP21

9.1 Technical data

Page 55: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

55

9.2 Unit dimensions

ø 30

138

115

361

350

18

250

74

49

18

22 2021

1515

1515

59 303

26

25

157

60

40

R 3/4"

Dimensionsinmm

Page 56: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

Notes

Page 57: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

Notes

Page 58: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

Notes

Page 59: Condair CS 2.0/4 · 3.4 Functional description The Condair CS steam humidifier is an unpressurized steam generator. It operates on the resistance heating principle and is designed

© Condair Ltd., Printed in SwitzerlandTechnical modifications reserved