Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ......

16
FEEDER CONTROL METERING PROTECTION RELAY Comprehensive Feeder Protection FCOMP

Transcript of Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ......

Page 1: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

FEEDER CONTROL METERING PROTECTION RELAY

Comprehensive Feeder Protection

FCOMP

Page 2: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

The combines the ruggedness of conventional feeder

protection and the versatility of advanced feeder protection

features, annunciations and metering in MV and LV switchgear

assemblies into one single, simple-to-configure, communicating

module with a large color display.

It is scalable, modular and of the right size to cater to your varied

feeder protection requirements.

To make it suitable for the often dusty and corrosive environs of

substations (as in process industries and petrochemical

complexes), the FCOMP has a conformal coating on its

hardware.

User-friendly options and features

Universal auxiliary power supply of 80-264 VAC /

110-250 VDC oOperating temperature range of -20 C to 85 C

Current-based metering and protection with optional

scalability for voltage-based metering and protection built

into a single unit

Reduced and simplified wiring(especially in auto bus transfer

schemes) and reduced dependence on auxiliary components

in different schematics through varied DI/DO combinations

Facilitation of reconfiguration of auto bus transfer conditions

/interlocks, configuration of load shedding and load-sharing,

reverse interlocking, conditions for tripping and closing of the

circuit breaker, annunciation and status exchange.

Six configurable pushbuttons for control and

12 configurable LEDs for indication

FCOMP

o

ABOUT FCOMP

Advanced substation communication protocol

options, viz.:

Modbus RTU , Profibus, IEC 60870-103

Modbus TCP/IP, IEC 61850

Scaled up substation communication network

architectures with redundancy for IED communications

through dual Rj45 and FO(SC/ST) ports for ethernet

communication and dual RS485 ports for serial

communication

Easy connection with a computer through the default

USB 2.0 port

Easy relay configuration through the indigenous interface TMsoftware, COMPfigurator , which is provided with

configuration settings, communication settings,

protection settings, gate logic, latches, timers, event

recording and disturbance recording. It allows for online

and offline creation of settings files for uploading and

downloading to the relay.

4 setting groups, multiple stages in each

protection settings and user selectable option on

protection source between Fundamental Metering and

RMS metering.

Larsen & Toubro (L&T) is a technology-driven company that infuses engineering with imagination. The Electrical & Automation Group of L&T offers a wide range of advanced solutions through its state-of-the-art products backed by world-class in-house capabilities in technology development customer support.

For complete feeder protection of air, vacuum or gas-insulated circuit breaker operated feeders in medium and low voltage switchgear assemblies, L&T offers a comprehensive Feeder Control Metering

Protection Relay – the FCOMP.

Page 3: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design
Page 4: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

PROTECTION FUNCTIONS

+Note: Optional*Basic voltage based protections are enabled upon selection of the FCOMP with voltage card.

**Advanced voltage base protections are enabled when options are so chosen at the time of ordering.

PROTECTION FUNCTION

Instantaneous Phase OverCurrentInstantaneous Neutral /Ground OCNegative-Sequence Instantaneous OCTimed Phase Over CurrentTimed Neutral / Ground OCNegative-Sequence Timed OCThermal Overload

Under Current

Restricted Earth Fault

+Sensitive Ground Fault

Auto Reclosure & Lockout

Breaker Failure

Trip Circuit SupervisionPhase Sequence MonitoringVoltage *

Positive Sequence voltage *

Negative Sequence Overvoltage *Frequency *

Frequency Gradient *

Power *

Power Factor *

Voltage Restraint for Phase Timed OC *VT Fuse Failure *Synchro Check **

Directional Phase and Neutral/Ground OC **

Directional Phase and Neutral / Ground Timed OC **

ANSI CODE

50P

50N, 50G

50Q

51P51N, 51G51Q49

37P

64

50SG, 51SG

79, 86

50BF

74TC4727P, 27X 59P, 59X. 59N47 O+, 47 U+

47 O-

81U, 81O

81R

32, 32R

55

51V

6025

67P, 67N,67G - IOC

67P,67N,67G - TOC

VARIABLE

Pick Up

Time Delay

Pick Up Accuracy

Time AccuracyPick UpTime DelayPick UpK FactorTMSPick UpTime DelayPick UpTime DelayPick UpTime DelayMax no. of shotsDead TimeModePh current supervisionAlarm DelayThree pole initiate-Time DelayPick UpTime DelayPick UpTime DelayPick UpTime DelayPick UpTime DelayPick UpTime DelayDirectionPick UpTime DelayCharacteristic Angle

DirectionPick UpTime DelayCharacteristic Angle

Pick Up 1A CT Pick Up 5A CT Pick UpTime DelayFunction

-Voltage differenceAngle differenceFrequency difference

RANGE

0.10 – 20.00 In

0 – 600 Sec

+ 2% of setting

+ 30ms 0.10 – 3.20 InIEC, IEEE Curves0.1 to 4.0 In0.1 – 460 – 30000 Sec0.10 – 3.20 In0 – 600 Sec0.02 – 1 In0 – 1 Sec

0.01 – 100 Sec1 - 40.00 – 100 Sec3 pole, 1 Pole

On, Off-0 – 100 Sec0.02 - 1.2 Vn0 – 600 Sec0.02 - 1.2 Vn0 – 600 Sec0.02 - 1.2 Vn0 – 600 Sec20-70 Hz0 - 100 Sec0.01 - 20 Hz/Sec0 – 100 Sec

0.10 – 20.00 In0 – 600 Sec

0.10 – 3.20 In0 – 600 Sec

0.2 – 1300 VAR, KW 1 – 6500 VAR, KW0.05 – 0.991 – 240 SecOn, Off

-0 – 50 V0 - 600 - 2 Hz

0.0025 – 1.6 A

0.01 - 20.00 In10 - 1000 Sec

Forward, Reverse

-180 - +180 Deg (for 67P)-90 - +90 Deg (for 67N/67G)Forward, Reverse

-180 - +180 Deg (for 67P)-90 - +90 Deg (for 67N/67G)

Page 5: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

ADVANCED FEATURES

Blocked Over CurrentSelective Over CurrentCold Load Pick Up

nd2 harmonic BlockingCT SupervisionZone Selective Interlock

Breaker Arcing CurrentBreaker Re-StrikeBreaker Contact Wear MonitoringAuto recloserLoad Shedding & RestorationTrip / Close Logic

COMMUNICATION OPTIONS

ProtocolsModbus RTUModbus TCPIPIEC 61850IEC 60870-103Profibus

MediaSerialEthernet on copperEthernet on Fiber

PortsRS 232 -USB (Front)RS 485 (CPU Card)Dual RJ 45 (CPU Card)Single FO (CPU Card)Dual RS 485 (Communication Card)*Dual RJ 45 (Communication Card)*Dual FO SC / ST (Communication Card)*

*Optional

*Optional

BUS

FEEDR

LINE

BREAKER

3

3

1

1

1*

1

27P* 59P* 59G* 59Q* 81O* 81U*

67IP* 67TP* 32* 32R* 60* 55* 81R* 51V*

50P 50G 50Q 51P 51G 51Q 37P 49

64

50SG* 51SG*

50N 51N 67IN* 67IG* 67TN* 67TG*

25

27S*

59S*

PROTECTION BLOCK

Page 6: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

METERING & MONITORING

REF CTIn (Nominal current) 1ARated Range : 0.02–1.2 AContinuous Rating : 1 A1 Second Thermal : 2 ARated Frequency : 50/60 ± 5 Hz

In (Nominal current)5ARated Range : 0.1 – 6 AContinuous Rating : 5 A1 Second Thermal : 10 ARated Frequency : 50/60 ±5 Hz

SEF CT

Rated Range : 2.5mA – 1.6 AContinuous Rating : 1 A1 Second Thermal : 10 ARated Frequency : 50/60 ±5 Hz

Phase and Neutral CT (R,Y,B,N)In (Nominal current)1ARated Range : 0.02–20.00 AContinuous Rating : 4 A1 Second Thermal : 100 ARated Frequency : 50/60 ± 5 Hz

In (Nominal current)5ARated Range : 0.10–100 AContinuous Rating : 20 A1 Second Thermal : 500 ARated Frequency : 50/60 ±5 Hz

Current

METERING SPECIFICATIONS

Measurement Range : 0 to 20 InAccuracy of reading : ± 0.25%REF Current : ±1 %Ig using CBCT : 1%Instantaneous demand current : Yes Max/Min demand current : YesAvg of all 3 phase RMS currents : Yes

Voltage Rated Operating voltage : 100–250 Vac Rated Continuous Voltage : 300 Vac10 Second Thermal : 600 VacRated Frequency : 50/60 ±5 Hz

Type of measurementPhase to phase –RMS, Max and Average Phase to N - RMS, Max and Average

Measurement Range : 0.1 – 2 VnAccuracy : 0.5% of reading from

0.1 Vn to1.5 Vn Max/Min voltage : YesAvg of all 3-phase RMS voltages : Yes

Phase wise & total Active, Re-active & Apparent Power / Energy Accuracy : 1%

Power / Energy

P.F. Phase wise & total Range : -1 to +1Resolution : 0.01Accuracy : ± 2% of Reading

Harmonics Harmonics measurement up to: 25th component Current & Voltage HarmonicsTHD measurement

Frequency Range : 40 to 70 Hz Accuracy : ± 0.01Hz

Temp Measurement Range : 0° to +250°C RTD protection (Optional PTC available)

Sequence Voltage and Current (Positive, Negative and Zero Sequence Components) - Accuracy : 1%

MONITORING SPECIFICATIONS

Oscillography Oscillographic Sampling Rate - 64 samples per cycleMaximum records: 64 (User-configurable data)AC input channels Protection element stateDigital input and output state Pre Trigger & Post Trigger Duration programmable : 64 Samples x 16 Cycles x 6 Channels x 2 Byte

Event Record 1024-Event history

Hour Meter Records operating hours of the equipment in operationRecords number of hours since last auxiliary power off

This Document and Design are the property of and must not be copied or lent without their permission in writing.Larsen & Toubro Limited

No. of CTs: 5 (R,Y,B,REF,N/SEF)

Page 7: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

Communication card

IO card – Slot 1

IO card – Slot 2

IO card – Slot 3

Voltage + Sync Voltage Card

CT card: 3Ph + 1 REF + 1 Neu / SEF

Serial port – Modbus RTU

Dual Ethernet port – Modbus TCPIP(Fiber or Copper)

Dual Ethernet port – IEC 61850(Fiber or Copper)

Dual Serial port – Modbus RTU / Profibus / IEC 60870 - 103

Universal power supply(80-264 VAC / 110-250 VDC)

Processor card2DI + 2 DO (Heavy duty)

Basi

c U

nit

Opt

iona

l Car

dsBa

sic

Uni

tCONFIGURATION

IO OPTIONS

Input voltage option in DI:

24 VDC110 VAC/VDC or 230 VAC/VDC (Software Selectable)

Output contact rating of DO:

Form A Contact Rating: 8A at 250VAC and 5A at 30VDC, 0.2A at 100VDC Maximum operating rating (AC): 2000VA

Form C Contact Rating:

8A at 250VAC and 5A at 30VDC, 0.3A at 300VDC Maximum operating rating (AC): 2000VA

Input Option in AI:

(+) 10 V or (+) 20mA input2-wire PT100 input, 0-250°C

Digital Input Output Card variants:

7 Digital input + 2 Digital output (Form C)4 Digital input + 2 Digital output (Form C) + 3 Digital output (Form A)9 Digital input6 Digital input + 2 Digital output (Form C) + 1 Digital Output (Form A)6 Digital output (FormC) + 1 Digital output (Form A)

Analog Input Output Card variants:

3 Analog input + 2 Analog output + 5 DI (230/110 V AC/DC)5 Channel RTD + 5 DI (230/110 V AC/DC) 10 Channel RTD

Page 8: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

INTERFACE SOFTWARE

TMThe COMPfigurator is a specialized software designed to interface with the FCOMP.FCOMP parameters can be configured, metered, monitored

TMthrough the COMPfigurator .

The FCOMP settings file can be generated by the TMCOMPfigurator by either of these methods:

Online mode (FCOMP-powered on and connected with TMthe COMPfigurator )

Offline mode (FCOMP disconnected). The settings file is generated with FCOMP disconnected and downloaded later onto it.

The settings file comprises the following configurations which can be modified as per user requirement:

General settings (CT ratio, PT ratio, sync input, DIO, AIO, phase rotation, nominal freq, etc.)Protection settings (All current and voltage-based protections)Pushbuttons LEDsDigital output, analog outputEvent recordPre- and post-fault settings of disturbance recordSingle line diagram

TMThe COMPfigurator can also be used for real time / online metering of:

Analog Data: Current, Voltage, Frequency, Power, Power factor Digital Data: Digital input status, digital output status, electrical fault status

TMThe COMPfigurator can also be used to monitor and record parameters like event history, sequence of events (1024), disturbance record (64 samples / cycle x 6 channels) and hour meter.

TMThe COMPfigurator has an option to save the setpoint files file and event records, as required, with password protection.

This Document and Design are the property of Larsen & Toubro Limited and must not be copied or lent without their permission in writing.

Page 9: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

TMCOMPlogic

TM TMThe COMPlogic is part of the COMPfigurator software.It is used to programme the FCOMP to tailor the control and operation of the circuit breaker.

The COMPlogic includes:Arithmetic operation (+, -, >, <, =)Logic Gate (AND, OR, NOT)Timer (Pick up, Drop out) Latch512 lines for control equations

Note: For details of sample control equations to implement schematics, refer to the FCOMP operation manual.

Page 10: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

USER INTERFACE

Rear Panel

Dual port

Modbus RTURS- 485

Speed: 300-38400 bps

DCSHMISCADAPC Interface

IEC 6185010 / 100 MbpsCopper / FibreSeparate IP Address

Modbus RTURS- 485Speed: 300-38400 bps

Modbus TCP/IP10 / 100 MbpsCopper / FiberSame IP Address

Front Panel

Modbus RTUSpeed: 300-38400 bps

USB port

PC Interface

This Document and Design are the property of and must not be copied or lent without their permission in writing.Larsen & Toubro Limited

Page 11: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

DIMENSIONAL DETAILS

COMPLIANCE

Tests

Enclosure Protection : IEC 60529:2001IP65 enclosed in panelIP20 for terminals

Vibration : IEC 60068-2-6:1995IEC 60255-21-1:1988, Class 1IEC 60255-21-3:1993, Class 2

Shock : IEC 60255-21-2:1988, Class 1Cold : IEC 60068-2-1:1990Damp Heat : IEC 60068-2-78:2001Steady StateTemperature Cyclic : IEC 60068-2-30:1980Test (with Humidity)

Dielectric Strength and Impulse Test

Dielectric (HIPOT) : IEC 60255-5:2000IEEE C37.90-1989

Impulse : IEC 60255-5:2000

RFI and Interference Test

ESD Immunity : IEC 61000-4-2:2001Radiated RF Immunity : IEC 61000-4-3:2002EFT Immunity : IEC 61000-4-4:2001Surge Immunity : IEC 61000-4-5:2001Surge Withstand : IEC 60255-22-1:1988Capability ImmunityConducted RF Immunity : IEC 61000-4-6:2003Magnetic Field Immunity : IEC 61000-4-8:2001Conducted Emissions : EN 55011:1998, CISPR 22Radiated Emissions : EN 55011:1998, CISPR 22

DoorCutout

160mm

285mm

252mm

143mm

130mm

256mm268mm

Page 12: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

TYPICAL WIRING DIAGRAM

This Document and Design are the property of and must not be copied or lent without their permission in writing.Larsen & Toubro Limited

USB

R

Y

B

BUS

LINE

R

Y

B

A03

A02

A01

P/+N/-G

Z01

Z02

Z03

Z04

Z05

Z06

Z09

Z10

Z07

Z08

FRONT PORT

R

Y

B

SEF /

REF

N

PC INTERFACE

VT CONNECTION

SYN

CHRO

NIS

M C

HECK

CT CONNECTION

STABILISING RESISTOR

CBCT

SEF CONNECTION

METROSIL

REF CONNECTION

AUXILIARY SUPPLY

FEEDER CONTROL METERINGPROTECTION

Y01

Y02

Y03

Y04

Y05

R Y B N Vs Ns

Y06

CLASS PX CT

1 2 3 4 5

+TX -TX

+RX -RX

SHLD

PORT

A

B1

PORT B2MODBUS

RTUMODBUSTCP/IP

1 2 3 4 5

+TX -TX

+RX -RX

SHLD

PORT C1

1 2 3 4 5

+TX -TX

+RX -RX

SHLD

PORT C3

A B

MODBUSRTU PO

RT C2 MODBUSRTU

IEC 61850

01

02

03

04

05

06

09

10

11

12

13

14

15

16

17

18

19

20

07

08

DI2

DI3

DI4

DI5

DI6

DI7

DI1

DI8

DI9

FUSE

CIRCUIT BREAKER

B01

B02

B03

B04

B05

B06

B07

B08

DI2

DI1

DO2

DO1

01

02

03

04

05

06

09

10

11

12

13

14

15

16

17

18

19

20

07

08

DO6

DO7

DO1

DO2

DO3

DO4

DO5

01

02

03

04

05

06

09

10

11

12

13

14

15

16

17

18

19

20

07

08

DI2

DI3

DI4

DI5

DI6

DO1

DO3

DI1

DO2

FCOMP

Page 13: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

To Modbus RTU master device To Modbus RTU master device

STP cable

STP cable

IED 1 IED 2 IED n

COMMUNICATION ARCHITECTURE

MODBUS RTU – DUAL DAISY-CHAIN REDUNDANT COMMUNICATION CONNECTION

IEC61850 – STAR REDUNDANT COMMUNICATION CONNECTION

DUAL DAISY CHAIN

PROFIBUS – DAISY-CHAIN COMMUNICATION CONNECTION

To Profibus master Primary device on serial or FO link

To Profibus master Secondary device on serial or FO linkRedundancyModule

Profibus cable

Terminating resistor

IED 1 IED 2 IED n

To Modbus RTU master device

STP cable

IED 1 IED 2 IED n

MODBUS RTU – DAISY-CHAIN REDUNDANT COMMUNICATION CONNECTION

DAISY CHAIN

To Modbus TCP/IP master device To Modbus TCP/IP master device

IED 1 IED 2 IED n

ETHERNET SWITCH CAT 5e cable

MODBUS TCP/IP – DAISY-CHAIN COMMUNICATION CONNECTION

To IEC 61850 master device To IEC 61850 master device

ETHERNET SWITCH 1ETHERNET SWITCH 1

SMFO cable SMFO cable

IED 1 IED 2 IED n

Page 14: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

COMPLETE SUBSTATION INTEGRATION

L&T DC Redundant Pair

IEC61850 NetworkModbus TCP/IP Network

Modbus RTU to TCP Converter

MCOMP on Modbus TCP/IP

FCOMP on IEC61850 MCOMP on Modbus RTU

GPS Server for Time Synchronization

ES-2 ES-3

OWS EWS RDBS Viewer

Modbus TCP/IP Network

Alarm Printer

Laser Printer

L&T Gateway Redundant Pair

Substation HMI

IPCS LAN

MCR LAN

IPCS

MCR

LV / MV SWGR

ES-1

SUBSTATION HMI

Page 15: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

ORDER CODE

FCOMP PART NOPSU VT CT

FCOMP A BXXX X XXX 1XX X 2XX X 3XX X XX C1 FCOMPABXXXXXXX1XXX2XXX3XXXXXC1

Auxiliary Input A 85 - 265 VAC @ 50 / 60 Hz, 110 - 250 VDC

Rs485 for Modbus RTU communication interface (Basic Included)

ETH

2 Digital input (230/110 VAC / VDC) 2 Digital output (Basic Included)

FSC

No Modbus TCP/IP

FST Fiber Optic communication interface; Single port with ST connector (Modbus TCP/IP)

X

M

No Card

P

Rs485 for Modbus communication interface, 300-38400 bps Rs485 for Profibus communication interfaceNo cardEthernet communication interface; Dual RJ-45 port

XX

Fiber Optic communication interface; Dual port with SC connector

D1

Fiber Optic communication interface; Dual port with ST connector

D2

No Card

1

24 VAC / VDC Voltage input

2

230/110 VAC / VDC Voltage input

3

7 Digital input + 2 Digital output (Form C)

4

4 Digital input + 2 Digital output (Form C) + 3 Digital output (Form A)

5

9 Digital input

A1

6 Digital input + 2 Digital output (Form C) + 1 Digital Output (Form A)

1

6 Digital output (Form C) + 1 Digital output (Form A)

R1

Analog Input Output Card

1

3 Analog input + 2 Analog output + 5 DI (230/110 V AC/DC)

2

RTD Input Card

XX

5 Channel RTD (2 wire PT100 i/p, 0 - 250 deg C) + 5 DI (230/110 V AC/DC)

V1

10 Channel RTD (2 wire PT100 i/p, 0 - 250 deg C)

C1

3 Phase Voltage input with Vsync option; 10‐132 V AC

C2

3 Phase Voltage input with Vsync option; 90‐300 V AC

C3

5 AC Current input, 1 Amp phase (R,Y,B) and 1 Amp neutral (N) + REF

C4

5 AC Current input, 5 Amp phase (R,Y,B) and 5 Amp neutral (N) + REF

FCOMP PART NO SELECTION OPTIONS

Basic Processor

Card

Communication

Card (Optional)

COMM

IO Slot (Optional)

IO3

Voltage Input

(Optional)

CT Input

IO1 IO2CPU

XXX

ETH

FSC

FST

XXX

X

V2

No Card

5 AC Current input, 1 Amp phase (R,Y,B), 1 Amp CBCT + REF

5 AC Current input, 5 Amp phase (R,Y,B), 5 Amp CBCT + REF

Page 16: Comprehensive Feeder Protection - Larsen & · PDF filecircuit breaker, annunciation and ... For complete feeder protection of ... with password protection. This Document and Design

The information contained herein is correct at the time of publication. This information may be subject to change without notice.

Larsen & Toubro Limited, Electrical Systems & EquipmentGate No. 7, North Wing, Level 1, Saki-Vihar Road, Powai, Mumbai - 400 072, INDIATel: +91 22 6705 4115 / 2857 Fax: +91 22 6705 1024 Email: [email protected]

Registered Office: L&T House, N. M. MargBallard EstateMumbai 400 001, INDIA

FCA

18.0

5.13

/PRD

Sales Offices - India Sales Offices - International

Chennai

TC-1 Building, II Floor Mount-Poonamallee Road Manapakkam Chennai 600 089 Tel: +91-44-2270 6801Fax: +91-44-2270 6930Email:

HyderabadPost Bag12,Vasantha Chambers2 floor, 5-10-73, Fateh Maidan RoadHyderabad 500 004Tel: +91-40-6672 0210Fax: +91-40-2324 2356Email: [email protected]

KolkataPost Bag 6193-B, Shakespeare SaraniKolkata 700 071Tel: +91-33-4400 2550/2558Fax: +91-33-22827587/1025Email: [email protected]

MumbaiGate no. 7, North Wing, Level 2Saki-Vihar Road, PowaiMumbai 400 072Tel: +91-22-6705 3083Fax: +91-22-6705 1556Email: [email protected]

New DelhiPost Bag 622332, Shivaji MargNew Delhi 110 015Tel: +91-11-4141 9620/9942Fax: +91-11-4141 9625Email: [email protected]

VadodaraRadhadaya Complex, J.P. RoadVadodara 390 015Tel: +91-265-66136 37/38Fax: +91-265-2336184Email: [email protected]

L&T Construction Campus

[email protected]

IndiaGate No.7, Saki-Vihar RoadNorth Wing, Level 1Mumbai 400 072Tel: +91-22-6705 2813Fax: +91-22-6705 1024Email: [email protected]

Saudi ArabiaL&T Electricals Saudi Arabia Company Limited - L. L. CMH-4, Plot: 17+192nd Industrial Area, DammamKingdom of Saudi ArabiaTel: +966-3-8127708Fax: +966-3-8127780Email: [email protected]

UAE2202, 22nd floorGreen Emirates Tower - AElectra Street, P.O. Box 30803Abu Dhabi, UAETel: +971-2-676 5988Fax: +971-2-676 6399Email: [email protected]

OmanP.O. Box 598, Ruwi, Postal Code-112Sultanate of OmanTel: +968 98034317Mob: +968 98034317Email: [email protected]

MalaysiaTAMCO SWITCHGEAR (MALAYSIA) SDN BHDSub Lot 24, Lot 16505, Jalan Keluli 1PO Box 2100, Bukit Raja Industrial Area Section 740802 ShahAlam, Selangor, MalaysiaTel: +603 3361 8200Fax: +603 3341 6200Email: [email protected]

AustraliaTAMCO Electrical Industries Australia Pty Ltd31 Kitchen Road, Dandenong 3175Melbourne, Victoria, AustraliaTel:+613 9706 7288Fax:+613 9706 9112Email: [email protected]

IndonesiaPT. TAMCO IndonesiaF-36, Jalan Jababeka Raya Jababeka Industrial EstateCikarang Utara, Bekasi,17530, IndonesiaTel: +62 21 893 5070 Fax: +62 21 893 5071 Email: [email protected]

Kenya1A, 3rd FloorWestlands Business Park04, Chiromo LaneWestlands, P.O. Box no. 13903 - 00800Nairobi, KenyaTel: +254-770-412 008Email: [email protected]

Qatar2 & 3rd Floor, Building No. 209Zone 42, Street 230Najma Intersection, Opp: Doha Cinema, aC-Ring Road, P.O. Box No - 24399Doha, QatarTel: +974-44-239 000Fax: +974-44-551 286Email: [email protected]