GE Industrial Solutions Leading the future of electrification
GE Industrial Solutions is leading the future of
electrification with advanced technologies that
distribute, protect and control.
We provide customers, across various industries,
with end-to-end product and service solutions that
ensure the reliability and protection of the electrical
infrastructure; from the power station to the end point
and all the sustainable power technologies in between.
uk.geindustrial.com/markets/marine
The full range in
distribution, protection
and control products
available in EPLAN
GE Industrial Solutions is part of EPLAN data portal. GE has integrated more than 13.000 references in the EPLAN data portal in the field of high voltage switchgear, industrial contactors, starters, low voltage protection devices and enclosures.
Each product reference contains technical data, macro schemes and high quality 2D & 3D images.
This upload allows to work in EPLAN Electric P8, EPLAN Pro Panel
or EPLAN Engineering Center using the complete GE Industrial Solutions product basket.
EPLAN
A classification society is a non-governmental organization that establishes and maintains technical standards for the construction and operation of ships and offshore structures. The society will also validate that construction is according to these standards and carry out regular surveys in service to ensure compliance with the standards.
The International Association of Classification Societies (IACS) is a technically based organization consisting of thirteen marine classification societies headquartered in London.)
RINA (Italy)
Lloyd's Register (UK)
Bureau Veritas (France)
GL Germanischer Lloyd (Germany)
DNV (Norway)
DNV GL Together from 2013
Marine approvals
Components offer
Controls & PEL
Modular
Industrial components
Miniature Circuit Breaker (Mcb’s)
Residual Current Breaker with Overcurrent (1+N RCBO’s)
Residual Current Breaker w. Overcurrent (2P UNIBIS RCBO’s)
Add-On Residual Current Devices
Auxiliaries for modular devices
Compact UNIBIS mcbs (Mcb’s)
Modular CERTIFICATES
BV certification EP60 High (ID 4128) EP100 High (ID 4127) G60S (ID 3094&2793) G100S (ID2888)
DNV certification G60 G60S (ID 4720) G100 G100S (ID 4721)
LR certification EP60 High EP100 High G60S G100S
RINA certification EP60 High (ID 4213&4655) EP100 High (ID 4218&4654) G60 G60S (ID 4212 4211) G100 G100 S(ID 4217&4216)
GL certification G60S High G100S High
MCBs
EP60 EP100 G60-G60S G100-G100S
RINA certification EPC611 EPC62 EPC63 EPC64
Unibis* MCBs EPC60
EPC611
BV DM60/DMA60/ DM100/DMA100
LR
DM60/DMA60 DP60/DPA60 DM100/DMA100 DP100/DP100A
RINA DM60/DMA60/DM100/DMA100 DP60/DPA60/DP100/DP100A)
RCBOs
DM100-DP100
Unibis* 2P RCBOs
DPC Performance Thermal setting In (A) 6-40 Residual current (mA) 30 Tripping characteristics C Rated voltage AC Un (V) 230 Frequency (Hz) 50/60 Minimum operating voltage Ub min. (V) 150 Mechanical / electrical endurance 10000/20000 Tropicalisation acc. to EN/IEC 60068-2 55ºC/95% Terminal capacity flexible / rigid cable (mm²) 25/35 Poles 2 Nuisance tripping resistance (A) 250
Ambient temperature (ºC) Type A: -25 up to 60 Weight / mod. (g) 110
Short-circuit capacity Acc. to EN 61009-1 Residual making and breaking capacity IΔm = 6000A Energy limiting class 3 Short-circuit capacity Icn = 10000A at 230V Acc. to EN 60947-2 Icu= 10kA
RINA
LR
Also available:
Un=120V at 50/60 Hz
DPCA100
RCCBs Add-on devices
BV RCCB ADD-ON DOC_DOCA
LR RCCB ADD-ON DOC RCCB ADD-ON DOC A
RINA RCCB ADD-ON DOC_DOCA
RCCBs Add-on devices
Auxiliary contacts
BV certification Aux. Functions CA/CB (ID 2890)
DNV certification
Aux. Functions CA/CB (ID 4722)
LR certification Aux. Functions CA/CB
RINA certification Aux. Functions CA/CB (ID 4219)
Series CA Series CB
Product Line CERTIFICATES
Moulded case circuit breakers (MCCB)
Air circuit breakers (ACB)
Non-automatic breakers (ACB)
Industrial components
Record Plus
EntelliGuard* G
EntelliGuard* G
Moulded Case Circuit Breakers
Type: FDN FDH
FDL
GL
Series FD160 FD160
Record Plus
Moulded Case Circuit Breakers Record Plus
GL
Series FE160
Type: FEN TM/ETU FEH TM/ETU FEL TM/ETU
Series FE250
Type: FEN TM/ETU FEH TM/ETU FEL TM/ETU
FE160 FE250
*Ith= 80-160A FEN 160 TM, FEH 160 TM, FEL 160 TM
*
*Ith= 25-125A FEN 160 ETU
*Ith= 25-160A FEH 160 ETU, FEL 160 ETU
*
*Ith= 100-2500A FEN 250 TM, FEH 250 TM, FEL 250 TM
*Ith= 125-2500A FEN 250 ETU, FEH 250 ETU, FEL 250 ETU
Moulded Case Circuit Breakers Record Plus Series FG400
Series FG630 Type: FGN FGH
GL
FG400 FG630
FGL
Moulded Case Circuit Breakers Record Plus Series FK800
Series FK1250 Type: FKN G L
FKN800 FKN1250
N N
* *
*Ith= 1000-1250A FKN 1250 *Ith= 630-800A FKN 800
ACB EntelliGuard* G
G L
Frame T GT04-GT16 R/K
Rated current In (40ºC) 400A-1600A
Rated operational voltage Ue 690V
Rated insulation voltage Ui 1000V
Rated impulse withstand voltage Uimp 12kV
Rated frequency 50/60Hz
Utilization category B
Overvoltage Cat./Pollution degree III/3
Rated short-circuit capacity performance at 440V
R K
Icm [kA] 105 105
Icu / Ics [kA] 50/50 65/50
Icw [kA] 42 50
IIT [kA] - 30
Technical performances
NEW Compact
frame
ACB EntelliGuard* G
G L
Frame 1 GG04-GG20 N/H
Rated current In (40ºC) 400A-2000A
Rated operational voltage Ue 690V
Rated insulation voltage Ui 1000V
Rated impulse withstand voltage Uimp 12kV
Rated frequency 50/60Hz
Utilization category B
Overvoltage Cat./Pollution degree III/3
Rated short-circuit capacity performance at 440/690V
N H
Icm [kA] 143 187
Icu = Ics [kA] 65/50* 85/85*
Icw [kA] 65 65*
IIT [kA] 32,5 32,5
Technical performances
*for Frame1 2nd value @ 690V
ACB EntelliGuard* G
G L
GG25-GG40 N/H –/- GG04-GG40 M
Technical performances Frame 2
N H M
Icm [kA] 143 187 200
Icu = Ics [kA] 65/50* 85 100/85*
Icw [kA] 65 65 85
IIT [kA] 32,5 32,5 50
Rated current In (40ºC) 400A-4000A
Rated operational voltage Ue 690V
Rated insulation voltage Ui 1000V
Rated impulse withstand voltage Uimp 12kV
Rated frequency 50/60Hz
Utilization category B
Overvoltage Cat./Pollution degree III/3
Rated short-circuit capacity performance at 440/690V
*for Frame2 2nd value @ 690V
ACB EntelliGuard* G
G L
Frame 3 GG032-GG64 L
Technical performances
Icm [kA] 330
Icu = Ics [kA] 150/100*
Icw [kA] 100
IIT [kA] 65
Rated current In (40ºC) 3200A-6400A
Rated operational voltage Ue 690V
Rated insulation voltage Ui 1000V
Rated impulse withstand voltage Uimp 12kV
Rated frequency 50/60Hz
Utilization category B
Overvoltage Cat./Pollution degree III/3
Rated short-circuit capacity performance at 440/690V
*for Frame3 100kA @ 690V
Non-automatic ACB EntelliGuard* G
G L
Frame T G7 04R – G7 16R
Technical performances
Rated current In (40ºC) 400A-1600A
Rated operational voltage Ue 690V
Rated insulation voltage Ui 1000V
Rated impulse withstand voltage Uimp 12kV
Rated frequency 50/60Hz
Utilization category B
Overvoltage Cat./Pollution degree III/3
Rated short-circuit capacity performance at 500V
Icm [kA] 75
Icw (1sec) [kA] 42
N NEW Compact
frame
Non-automatic ACB EntelliGuard* G
G L
Frame 1 GW04-GW20 N
Technical performances
Rated current In (40ºC) 400A-2000A
Rated operational voltage Ue 690V
Rated insulation voltage Ui 1000V
Rated impulse withstand voltage Uimp 12kV
Rated frequency 50/60Hz
Utilization category B
Overvoltage Cat./Pollution degree III/3
Rated short-circuit capacity performance at 500V
Icm [kA] 143
Icw (1sec) [kA] 65
N
Non-automatic ACB EntelliGuard* G
G L
Frame 2 GJ25-GJ40 N
Technical performances
N
Rated current In (40ºC) 2500A-4000A
Rated operational voltage Ue 690V
Rated insulation voltage Ui 1000V
Rated impulse withstand voltage Uimp 12kV
Rated frequency 50/60Hz
Utilization category B
Overvoltage Cat./Pollution degree III/3
Rated short-circuit capacity performance at 500V
Icm [kA] 143
Icw (1sec) [kA] 65
GW04-GW40 M
Technical performances
Icm [kA] 187
Icw (1sec) [kA] 85
M
Rated current In (40ºC) 400A-4000A
Rated operational voltage Ue 690V
Rated insulation voltage Ui 1000V
Rated impulse withstand voltage Uimp 12kV
Rated frequency 50/60Hz
Utilization category B
Overvoltage Cat./Pollution degree III/3
Rated short-circuit capacity performance at 500V
Non-automatic ACB EntelliGuard* G
G L
GK32-GK40 N
Rated current In (40ºC) 3200A-4000A
Rated operational voltage Ue 690V
Rated insulation voltage Ui 1000V
Rated impulse withstand voltage Uimp 12kV
Rated frequency 50/60Hz
Utilization category B
Overvoltage Cat./Pollution degree III/3
Rated short-circuit capacity performance at 500V
Technical performances
Icm [kA] 143
Icw (1sec) [kA] 65
N
Frame 2 Limited Derating
Thermal Overload Relays
SHIPPING CERTIFICATES Product Line
Contactors
Auxiliary contact blocks
Manual Motor Starters
Auxiliaries of MMS
Control and Signalling
Soft Starters
Controls & PEL
Efficor*
Efficor*
Efficor* Series M
Series M
Series CL
Series CL
Series CL
Series CK
Series CK
Surion
Surion
Contactors Efficor*
BV LR
GL RINA
EC Series
Contactors MC
BV RINA
Series M
Contactors CL
Series CL BV
RINA
Contactors CK07-CK12
Series CK BV GL RINA
Manual Motor Starter Surion
BV LR certification
GL RINA certification
GPS1B GPS1M
Manual Motor Starter Surion
GPS2B GPS2M
BV LR certification
GL RINA certification
Auxiliaries Surion
BV LR certification
GL RINA certification
Control and Signalling Units Series P9
BV
GL RINA
Soft Starters ASTAT
Series ASTAT XB(m)
LR Series ASTAT XL
• Compact design • Built-in bypass • Friendly use • Conformal coated PCBs (3C2) • Din rail mounting up to 30kW, 40HP • Motor protections (XBm series) • Remote operator kit available as option
Features
• From 18 to 1600A, 200 – 690V • Built-in Bypass • Conformal coating as standard • Adaptive Control for user-friendly improved performance • Adjustable busbars from >360A • Fieldbus options plug&play for the complete range • Select and Setup tools for easier configuration and startup
Characteristics
Features
• Compact design • Built-in bypass (up to 1000A) • User friendly programming and
feedback • Conformal coated PCBs (3C2) • Automatically detects in-linear or
inside delta connection • Adjustable for both top and bottom
entry above 360A, 200 to 1100HP • Motor protections • DC injection braking distributed over
the 3 phases
uk.geindustrial.com/markets/marine