Comparison of Governor Deadband Settings Feb 2010
-
Upload
abinash-mishra -
Category
Documents
-
view
219 -
download
2
Transcript of Comparison of Governor Deadband Settings Feb 2010
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 1/11
A 0.01666 Hz Deadband with a Straight LineProportional 5% Droop Curve Compared to a 0.036
Hz Deadband with a “Step” Straight LineProportional 5% Droop Curve from the Deadband
Comparison of Governor Deadband
& Droop Settings of a Single 600 MW
Unit
Sydney Niemeyer, NRG
February 9, 2010
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 2/11
2
Governor Settings Prior to November 2008
● 2008 Had Ten Months of Operation with no
Governor setting changes. ERCOT Operating Guides called for a maximum
+/-0.036 Hz deadband on Governors.
5% Droop Setting with no clarification as to
implementation. With or without a step function atthe deadband.
To meet the 5% droop performance, Governorswere encouraged to “step” into the 5% droop curve
at the deadband.
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 3/11
3
Governor Settings After November 3, 2008
● Deadbands were decreased to +/-0.0166 Hz (1 rpm
on a 3600 rpm turbine).● The Droop curve implemented was a straight line
proportional curve from the deadband eliminatingany “step” function.
● Initially only 4 Unit’s Governors were changed.
Total Capacity of 2486 MW or approximately 82.8MW/0.1 Hz of Primary Frequency Response.
● The coordinated Boiler Control Systemimplemented the same Droop curve and deadbandas the turbine Governor.
● Additional Units changed their Governor settingsthroughout 2009 and 2010, mostly after July 2009.
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 4/11
4
Status as of February 1, 2010
● Units with Governors presently set with an
intentional deadband less than or equal to +/-0.01666 Hz and droop curve with no stepfunction.
11,607 MW Total Capacity Identified by PDCWGmembers.
• 1690 MW Lignite
• 4139 MW Coal
• 3620 MW Combustion Turbine Combined Cycle
• 1519 MW Combustion Turbine Simple Cycle
• 399 MW Steam Turbine – natural gas fired
• 240 MW Hydro
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 5/11
5
2008 Jan thru Oct
0
20000
40000
60000
80000
100000
120000
140000
160000
5 9 . 9
5 9 . 9 1
5 9 . 9 2
5 9 . 9 3
5 9 . 9 4
5 9 . 9 5
5 9 . 9 6
5 9 . 9 7
5 9 . 9 8
5 9 . 9 9 6 0
6 0 . 0 1
6 0 . 0 2
6 0 . 0 3
6 0 . 0 4
6 0 . 0 5
6 0 . 0 6
6 0 . 0 7
6 0 . 0 8
6 0 . 0 9
6 0 . 1
M W
2008 MW Response of 0.036 db 2008 MW Response of 0.0166 db
591324.0
782765.9 MW Res onse of 0.0166 db
MW Response of 0.036 db
32.38% Increase in MW
movement with
lower deadband.
MW-Minute Primary Frequency Response of a 600 MW Unit To
All Frequency Deviations During The First 10 Months of 2008
M i n u t e
This compares the difference a single 600MW unit would have experienced as a result
of Primary Frequency Response if on-linethe first 10 months of 2008 and had marginto move.
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 6/11
6
2008 Jan thru Dec
0
20000
40000
60000
80000
100000
120000
140000
160000
5 9 . 9
5 9 . 9 1
5 9 . 9 2
5 9 . 9 3
5 9 . 9 4
5 9 . 9 5
5 9 . 9 6
5 9 . 9 7
5 9 . 9 8
5 9 . 9 9 6 0
6 0 . 0 1
6 0 . 0 2
6 0 . 0 3
6 0 . 0 4
6 0 . 0 5
6 0 . 0 6
6 0 . 0 7
6 0 . 0 8
6 0 . 0 9
6 0 . 1
M W
2008 MW Response of 0.036 db 2008 MW Response of 0.0166 db
662574.0
893164.2 MW Res onse of 0.0166 db
MW Response of 0.036 db
34.80% Increase in MW
movement with
lower deadband.
MW-Minute Primary Frequency Response of a 600 MW Unit To
All Frequency Deviations in 2008
M i n
u t e
This compares the difference a single 600MW unit would have experienced as a result
of Primary Frequency Response if on-line allof 2008 and had margin to move.
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 7/117
2009 Jan thru Dec
0
20000
40000
60000
80000
100000
120000
140000
5 9 . 9
5 9 . 9 1
5 9 . 9 2
5 9 . 9 3
5 9 . 9 4
5 9 . 9 5
5 9 . 9 6
5 9 . 9 7
5 9 . 9 8
5 9 . 9 9 6 0
6 0 . 0 1
6 0 . 0 2
6 0 . 0 3
6 0 . 0 4
6 0 . 0 5
6 0 . 0 6
6 0 . 0 7
6 0 . 0 8
6 0 . 0 9
6 0 . 1
M W
2009 MW Response of 0.036 db 2009 MW Response of 0.0166 db
446244.0
692039.8 MW Res onse of 0.0166 db
MW Response of 0.036 db
55.08% Increase in MWmovement withlower deadband.
However, the 692039.8 MW Response of
the 0.0166 db unit is only 29465.8 MWmore than the 2008 MW Response of the0.036 db unit (662574.0 MW). A 4.45%increase with the benefit of the improvedfrequency profile.
The MW responseof the 0.036 db
unit decreased216330.0 MW in2009 from 2008.This is a 32.645%decrease inmovement.
MW-Minute Primary Frequency Response of a 600 MW Unit To All
Frequency Deviations in 2009
M i n u t e
The MW response
of the 0.0166 dbunit decreased201124.4 MW in2009 from 2008.This is a 22.518%decrease in
movement.
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 8/118
ERCOT Frequency Profile Comparison
0
5000
10000
15000
20000
25000
30000
35000
40000
45000
5 9 . 9
5 9 . 9 1
5 9 . 9 2
5 9 . 9 3
5 9 . 9 4
5 9 . 9 5
5 9 . 9 6
5 9 . 9 7
5 9 . 9 8
5 9 . 9 9 6 0
6 0 . 0 1
6 0 . 0 2
6 0 . 0 3
6 0 . 0 4
6 0 . 0 5
6 0 . 0 6
6 0 . 0 7
6 0 . 0 8
6 0 . 0 9
6 0 . 1
O
n e M i n u t e O c c u r a n c e s
2009 2008
525,600 One Minute Periods per Year 2009 FrequencyProfile more “Normal”
than 2008. Note: 2008had two months ofoperation at the lowergovernor deadbandsettings (Nov & Dec).
ERCOT Frequency Profile 2008 and 2009
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 9/119
ERCOT Frequency Profile Comparison
0
500
1000
1500
2000
2500
3000
3500
4000
4500
5 9 . 9
5 9 . 9 1
5 9 . 9 2
5 9 . 9 3
5 9 . 9 4
5 9 . 9 5
5 9 . 9 6
5 9 . 9 7
5 9 . 9 8
5 9 . 9 9 6 0
6 0 . 0 1
6 0 . 0 2
6 0 . 0 3
6 0 . 0 4
6 0 . 0 5
6 0 . 0 6
6 0 . 0 7
6 0 . 0 8
6 0 . 0 9
6 0 . 1
O n e M i n u t e O c c u r a
n c e s
December 2009 January 2010 November 2009
December 2009 and January 2010 improved over typical (November 2009) performance.Several additional units changed their deadbands in
December 2009 and January 2010.
ERCOT Frequency Profile Had Additional Improvement in December
2009 and January 2010
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 10/11
10
MW-Minute Primary Frequency Response of a 600 MW
Unit To All Frequency Deviations During January 2010
January 2010 Primary Frequency Response
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
5 9 . 9
5 9 . 9 1
5 9 . 9 2
5 9 . 9 3
5 9 . 9 4
5 9 . 9 5
5 9 . 9 6
5 9 . 9 7
5 9 . 9 8
5 9 . 9 9 6 0
6 0 . 0 1
6 0 . 0 2
6 0 . 0 3
6 0 . 0 4
6 0 . 0 5
6 0 . 0 6
6 0 . 0 7
6 0 . 0 8
6 0 . 0 9
6 0 . 1
M W M
i n u t e s
MW Response of 0.036 db MW Response of 0.0166 db
53656.4
37384.0
MW Response of 0.0166 db
MW Response of 0.036 db
As the frequency profile continues to improve, the lower
deadband unit provides 43.538% more MW movement
than the larger deadband unit, but overall MW movement is
less as the frequency deviations decrease in magnitude.
8/3/2019 Comparison of Governor Deadband Settings Feb 2010
http://slidepdf.com/reader/full/comparison-of-governor-deadband-settings-feb-2010 11/11
11
Conclusions
● Clearly the MW-Minute Movement of a Unit with a
lower deadband setting is more than that of alarger deadband.
● The MW-Minute movement of the lower deadbandhas a gradual injection of Primary FrequencyResponse compared to the “step” implementation
of the larger deadband. Better Unit stability
Better Frequency stability
● As more Units implement the lower deadband andnon-”step” droop curve, the frequency profile
improves and the total MW-Minute movement ofthe grid decreases.