COMPARISON OF AIRCONDITIONING SYSTEM
-
8/17/2019 Comparison of Air Conditioning System (1)
2/26
Air ConditioningSystem
Chilled Water Direct Expansion
Water-CooledChiller
Air-CooledChiller
Water-CooledPackaged
Air-CooledPackaged
-
8/17/2019 Comparison of Air Conditioning System (1)
3/26
When selecting a cooling system, the firststep is to analyze commercial aspects andapplications of the systems to the job site.
There are a few criteria to considered whenselecting a cooling systemcapital costOperating cost
User’s ability to operateService and maintenance
-
8/17/2019 Comparison of Air Conditioning System (1)
4/26
1) CAPITAL COST
-
8/17/2019 Comparison of Air Conditioning System (1)
5/26
1) CAPITAL COST
WCChiller
ACChiller
WCPackaged
ACPackaged
System Price/ RT
RM 7000 TORM 8000
RM 5000TO RM 6000
RM 3500 TORM 4000
RM 3000 TORM 3500
i) Centralized chilled water system capital cost is higher compareto packaged system. However, capital cost is not the only criteriato justify which system to use. Other criteria should also take intoconsideration before any system is selected.
RT = Refrigerant Tonnage
-
8/17/2019 Comparison of Air Conditioning System (1)
6/26
4) OPERATION COST
-
8/17/2019 Comparison of Air Conditioning System (1)
7/26
4) OPERATION COST
WCChiller
ACChiller
WCPackaged
ACPackaged
Overall Efficiencykw/tr 0.9
i) Centralized chilled water system has a better overall efficiencydue to precise control of chillers, pump and valves operations inaccordance to the varying load. The capacity regulation of chilledwater system is stepless (continuous). Optimization of chiller plantefficiency can be done with chilled water system. Variable flow
systems and inverter driven chiller provide better energy efficiencyand optimization to the chiller plant operation.ii) Packaged system has poor overall efficiency due to poor controlof capacity as the compressor can not load/unload precisely andcontinuously. Compressor can only on/off, control of capacity arebased on steps.
1.5 1.1 1.1
-
8/17/2019 Comparison of Air Conditioning System (1)
8/26
4) OPERATION COST
The Air Conditioning and Refrigerant Institute (ARI) has establisheda system in ARI standard 550/590 – 2003 for measuring the totalchiller performance over full and part load conditions. It defines asintegrated part load value (IPLV) as an excellent method ofcomparing equipment on an equal basis.
IPLV =0.01
A+
0.42
B
0.45
C
0.12
D+ +
1
A = kw/tr at 100% loadB = kw/tr at 75% load
C = kw/tr at 50% loadD = kw/tr at 25% load
-
8/17/2019 Comparison of Air Conditioning System (1)
9/26
-
8/17/2019 Comparison of Air Conditioning System (1)
10/26
2) ADVANTAGES /DISADVANTAGES
-
8/17/2019 Comparison of Air Conditioning System (1)
11/26
2) ADVANTAGES / DISADVANTAGES
WCChiller
ACChiller
WCPackaged
ACPackaged
1) DiversityFactor
Yes(0.8-0.9)
Yes(0.8-0.9) No No
i) Diversity factor can be applied to centralized chilled watersystem. This is because the chilled water plant can be sized for theinstanteous cooling load. Since, all loads do not peak at the sametime, centralized chilled water system is 10% to 20% smaller thanthe total of the individual units at its peak.
ii) Diversity factor cannot be applied to packaged unit due to thefact that each unit serves individual rooms. As a result, there is aredundancy in capacity as units are selected based individual peakloads.
-
8/17/2019 Comparison of Air Conditioning System (1)
12/26
2) ADVANTAGES / DISADVANTAGES
WCChiller
ACChiller
WCPackaged
ACPackaged
2) CapacityControl
Good Good
i) Centralized chilled water system has better capacity control andexcellent part load performance value (IPLV) as the compressor isable to load and unload according to the building load. Hence amore precise control on the temperature and relative humidity (RH)
of the room.ii) Packaged system has poor capacity control as the compressor isable to cut in/out. As a result, load fluctuation and inconsistency incapacity control makes it difficult to achieve continuous comfortlevel and precise temperature and humidity control.
Poor Poor
-
8/17/2019 Comparison of Air Conditioning System (1)
13/26
2) ADVANTAGES / DISADVANTAGES
WCChiller
ACChiller
WCPackaged
ACPackaged
Standby Yes Yes
i) Centralized chilled water system has standby chiller that will runin case of chiller failure. Using multiple compressors will alsofurther increase the standby (or redundancy) of the system.Multiple compressor chiller can be used to provide standby withpartial load in case space for chiller system not sufficient to fit instandby chiller.ii) Each package system has poor standby. In case of compressorfailure, the package system still can operate at part load. Nostandby package system is installed. But to overall building,because it consists of many package system, if one packagesystem fails, the other package system still operates normally and
not affected.
No No
-
8/17/2019 Comparison of Air Conditioning System (1)
14/26
2) ADVANTAGES / DISADVANTAGES
WCChiller
ACChiller
WCPackaged
ACPackaged
4) Life Span(Years)
15-20
i) Centralized chilled water system using screw compressor isdesigned for rugged and reliable operation with few moving parts,low speed operation and high quality bearing. Life span of screwcompressor is up to 20 years.
ii) Packaged system using scroll compressor is not as rugged andreliable as screw compressor. The life span is shorter due tofrequent start / stop of the compressor. Generally, scrollcompressors are expected to last 8 to 10 years only.
15-20 8-10 8-10
-
8/17/2019 Comparison of Air Conditioning System (1)
15/26
2) ADVANTAGES / DISADVANTAGES
WC Chiller
5) SpaceRequirement
i) WC Chiller & Pumps - Plant Roomii) Cooling Tower - Roof topiii) Make Up Water Tank - Roof top
iv) AHU – AHU Room
AC Chiller
5) SpaceRequirement
i) AC Chiller & Pumps – Roof topii) AHU – AHU Room
AHU – Air Handling Unit
-
8/17/2019 Comparison of Air Conditioning System (1)
16/26
2) ADVANTAGES / DISADVANTAGES
WC Packaged
5) SpaceRequirement
i) WC Packaged - AHU Roomii) Cooling Tower & Pumps- Roof topiii) Make Up Water Tank - Roof top
AC Packaged
5) SpaceRequirement
i) Outdoor Unit - Roof top / Building Wallii) Indoor Unit - AHU Room
AHU – Air Handling Unit
-
8/17/2019 Comparison of Air Conditioning System (1)
17/26
2) ADVANTAGES / DISADVANTAGES
WCChiller
ACChiller
WCPackaged
ACPackaged
6) DistanceLimitation
No No
i) Centralized chilled water system has no distance limitation.Chilled water and condenser water pumps are able to circulatechilled water and condenser water over a long distance.
ii) WC Packaged also has no distance limitation. The condenserwater pumps are able to circulate the condenser water over a longdistance.
No Yes
iii) AC Packaged has distance limitation. The distance betweenindoor and outdoor unit is limited by the length of refrigerant piping.To properly allocating the outdoor unit can be troublesome.
-
8/17/2019 Comparison of Air Conditioning System (1)
18/26
2) ADVANTAGES / DISADVANTAGES
WCChiller
ACChiller
WCPackaged
ACPackaged
7) PotentialHealth Hazard(Legionnaire disease)
Yes No
i) WC Chiller and WC Packaged can has potential health hazardas cooling tower are open to contamination. Warm water is apotential breeding ground for bacteria and microorganismsespecially legionnaires' disease.
Yes No
ii) AC Chiller and AC Packaged does not use cooling tower. Hencethere are no potential health hazard on legionnaires' disease.
-
8/17/2019 Comparison of Air Conditioning System (1)
19/26
2) ADVANTAGES / DISADVANTAGES
WCChiller
ACChiller
WCPackaged
ACPackaged
7) PotentialHealth Hazard(Refrigerant Leakage)
No No
i) Centralized chilled water system are does not have any potentialrefrigerant exposure to the occupants. Refrigerant is confinedwithin chillers only. Leaking in water piping can be easily detected.
Yes Yes
ii) Packaged system has potential refrigerant exposure to occupants.Refrigerant leakage is difficult to detect.
-
8/17/2019 Comparison of Air Conditioning System (1)
20/26
2) ADVANTAGES / DISADVANTAGES
WCChiller
ACChiller
WCPackaged
ACPackaged
8) Noise levelTreatment
Good
i) Centralized chilled water system noise level can be properlytreated within the chiller plant room.
ii) WC Packaged noise level is difficult to be treated as thecompressor is inside the indoor unit. To properly treated the noise
level can be costly.iii) AC Packaged noise level is also difficult to be treated as thecompressor is inside the outdoor unit. Since the outdoor unit isnormally scattered around the building to properly treated the noiselevel is very costly.
Good Poor Poor
-
8/17/2019 Comparison of Air Conditioning System (1)
21/26
3) MAINTENANCE
-
8/17/2019 Comparison of Air Conditioning System (1)
22/26
-
8/17/2019 Comparison of Air Conditioning System (1)
23/26
WCChiller
ACChiller
WCPackaged
ACPackaged
2) ChemicalTreatment Yes No Yes No
1) CondenserTube Cleaning Yes No Yes No
3) MAINTENANCE
i) WC Chiller and WC Packaged requires additional condensertube cleaning and chemical treatment which can add on
maintenance cost.
-
8/17/2019 Comparison of Air Conditioning System (1)
24/26
Lower Entering AIR and WATER Temperatures
1) AIR COOLED CHILLER Chiller
kW/ton
CHWP
kW/ton
CT
kW/ton
CWP
kW/ton
Total
kW/ton
950F @ 100% FL 1.10 0.12 0 0 1.160
850F @ 75% FL 0.90 0.12 0 0 1.020
750F @ 50% FL 0.82 0.12 0 0 0.940
750F @ 25% FL 0.82 0.12 0 0 0.940
Integrated System kW per ton 0.974
2) WATER COOLED CHILLER ChillerkW/ton
CHWPkW/ton
CTkW/ton
CWPkW/ton
TotalkW/ton
870F @ 100% FL 0.62 0.12 0.05 0.08 0.870
83.5 0F @ 75% FL 0.71 0.12 0.05 0.08 0.960
800F @ 50% FL 0.85 0.12 0.05 0.08 1.100
800F @ 25% FL 1.25 0.12 0.05 0.08 1.500
Integrated System kW per ton 0.811
-
8/17/2019 Comparison of Air Conditioning System (1)
25/26
Lower Entering AIR and WATER Temperatures
1) AIR COOLED PACKAGED AC Packaged
kW/ton
CHWP
kW/ton
CT
kW/ton
CWP
kW/ton
Total
kW/ton
950F @ 100% FL 1.210 0 0 0 1.210
850F @ 75% FL 1.330 0 0 0 1.330
750F @ 50% FL 1.250 0 0 0 1.250
750F @ 25% FL 1.310 0 0 0 1.310
Integrated System kW per ton 1.289
2) WATER COOLED PACKAGED WC PackagedkW/ton
CHWPkW/ton
CTkW/ton
CWPkW/ton
TotalkW/ton
870F @ 100% FL 0.780 0 0.05 0.08 0.910
83.5 0F @ 75% FL 0.960 0 0.05 0.08 1.090
800F @ 50% FL 0.980 0 0.05 0.08 1.110
800F @ 25% FL 1.250 0 0.05 0.08 1.380
Integrated System kW per ton 1.125
-