Compact performance - Festo · 2020. 5. 16. · CP connection Plug or socket on the CP modules...

122
Electronics manual CPV valve terminal with direct connection Type CPV..−GE−DN2−8 Field bus protocol: − DeviceNet Manual 526 017 en 0503a [693835] Compact performance

Transcript of Compact performance - Festo · 2020. 5. 16. · CP connection Plug or socket on the CP modules...

  • Electronics manual

    CPV valve terminal

    with

    direct connection

    Type

    CPV..−GE−DN2−8

    Field bus protocol:

    − DeviceNet

    Manual

    526 017

    en 0503a

    [693835]

    Compact performance

  • Contents and general instructions

    I

    Authors U. Reimann, J. Müller. . . . . . . . . . . . . . . . . . . . . . . .

    Editors H.�J. Drung, M. Holder. . . . . . . . . . . . . . . . . . . . . . . .

    Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Translation transline Deutschland. . . . . . . . . . . . . . . . . . . . .

    Layout . . . . . . . . . . . . . . . . . Festo SE & Co. KG, Dept. KG−GD

    Type setting KI−DT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Edition en 0503a. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Title MANUAL−EN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Designation P.BE−CP−DN2−EN. . . . . . . . . . . . . . . . . . . . . . . . .

    Order no. 526 017. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    E�(Festo SE�&�Co. KG, D�73726 Esslingen, Federal Republic of Germany, 2001)

    Internet: �http://www.festo.come−mail: � [email protected]

    The copying, distribution and utilization of this document as well as the communication of its contents to others without expressed authorization is prohibited. Offenders will be held liable for the payment of damages. All rights are reserved, in particular the right to carry out patent, utility model or orna� mental design registration.

    Festo P.BE−CP−DN2−EN en 0503a

  • Contents and general instructions

    II Festo P.BE−CP−DN2−EN en 0503a

  • Contents and general instructions

    IIIFesto P.BE−CP−DN2−EN en 0503a

    Contents

    Designated use VII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Target group� VIII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Service VIII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Notes on the use of this manual VIII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Important user instructions IX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1. Installation 1−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.1 General instructions on installation 1−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2 Setting the CPV Direct 1−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.1 Fitting and removing the switch module 1−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.2 Setting the DIL switches 1−7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3 Connecting to the field bus 1−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.1 Field bus cable 1−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.2 Field bus baud rate and field bus length 1−15. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.3 Connection instructions for DeviceNet 1−16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.4 Micro style connection (2�x�M12) 1−18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.5 Open style connection (screw terminals, IP20) 1−19. . . . . . . . . . . . . . . . . . . . . . .

    1.3.6 Connection example 1−20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.7 Futher connection possibility on the field bus with the Sub−D plug 1−21. . . . . . .

    1.4 Bus termination with terminating resistors 1−24. . . . . . . . . . . . . . . . . . . . . . . . . .

    1.5 Power supply 1−25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.5.1 Cable for power supply 1−25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.5.2 Selecting the power unit� 1−27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.5.3 Connecting the power supply 1−29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.6 Extending the CPV Direct 1−34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • Contents and general instructions

    IV Festo P.BE−CP−DN2−EN en 0503a

    2. Commissioning 2−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1 Preparing the CP valve terminal for commissioning 2−3. . . . . . . . . . . . . . . . . . . .

    2.1.1 Switching on the operating voltage 2−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1.2 Address assignment of the CPV valve terminal 2−4. . . . . . . . . . . . . . . . . . . . . . .

    2.2 Commissioning on the DeviceNet 2−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1 General information 2−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.2 Configuring DeviceNet slave features (EDS) 2−7. . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.3 Valid instructions for parametrizing on the DeviceNet 2−9. . . . . . . . . . . . . . . . . .

    2.2.4 Instructions on parametrizing with RSNetWorx for DeviceNet 2−11. . . . . . . . . . .

    2.2.5 Device−specific parametrizing 2−17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.6 Explicit Message 2−25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3. Diagnosis 3−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1 Diagnosis by means of LEDs 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1.1 Normal operating status 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1.2 Error displays of the LEDs PS and MNS 3−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1.3 LEDs for status display of the valve solenoid coils 3−7. . . . . . . . . . . . . . . . . . . . .

    3.2 Error search when bus is started 3−8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3 Reaction to faults in the control system 3−9. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4 Diagnosis on the DeviceNet 3−10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4.1 Diagnosis via the Software Configurator 3−10. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4.2 Diagnosis via user program 3−13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.5 Short circuit/overload 3−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.5.1 Output module 3−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.5.2 Sensor supply at an input module 3−15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A. Technical data and accessories A−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A.1 Technical specifications A−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A.2 Accessories A−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A.3 Compatibility of the CPV..−GE−DN2−8 to earlier products A−9. . . . . . . . . . . . . . . .

    A.3.1 Adapting the power supply A−9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    A.3.2 Adapting the network configuration A−10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • Contents and general instructions

    VFesto P.BE−CP−DN2−EN en 0503a

    B. DeviceNet objects B−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.1 DeviceNet objects B−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.1.1 DeviceNet object model B−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.1.2 Summary B−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.1.3 Discrete Input Object: Class code 8d B−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.1.4 Discrete Output Object: Class code 9d B−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.1.5 Assembly Object: Class code 4d B−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.1.6 Festo Output Word Object: Class code 100d B−9. . . . . . . . . . . . . . . . . . . . . . . . .

    B.1.7 Festo Input Word Object: Class code 100d B−9. . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.1.8 Festo Diagnostic Object: Class code 102d B−10. . . . . . . . . . . . . . . . . . . . . . . . . . .

    B.1.9 Structure of the diagnostic byte B−12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    C. Index C−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • Contents and general instructions

    VI Festo P.BE−CP−DN2−EN en 0503a

  • Contents and general instructions

    VIIFesto P.BE−CP−DN2−EN en 0503a

    Designated use

    The CPV valve terminal with field bus direct connection (CPV

    direct) described in this documentation is designed exclus�

    ively for use as a slave on the DeviceNet field bus.

    The valve terminal may only be used as follows:

    � in accordance with designated use

    � in its original state

    � without any modifications by the user

    � in faultless technical condition.

    � The maximum values specified for pressures, tempera�

    tures, electrical data, torques etc. must be observed.

    Please comply with national and local safety laws and regula�

    tions.

    If you wish to implement an emergency stop function, please

    observe the measures listed in chapter 1.5.3.

    Warning

    If the CP valve terminal is used as an explosion−proof oper�

    ating medium, do not disconnect the electrical connections

    under tension. Plugs or adapters of the electric connec�

    tions must comply at least with protection class IP64.

  • Contents and general instructions

    VIII Festo P.BE−CP−DN2−EN en 0503a

    Target group�

    This manual is intended exclusively for technicians trained in

    control and automation technology, who have experience in

    installing, commissioning, programming and diagnosing

    slaves on the DeviceNet.

    Service

    Please consult your local Festo service centre if you have any

    technical problems.

    Notes on the use of this manual

    Please note

    This manual contains the functionality of software version

    V3.01.

    This manual contains specific information on installing, com�

    missioning, programming and diagnosing CPV valve terminals

    with direct connection for the DeviceNet.

    This CPV valve terminal has been certified by the ODVA:

    Information on pneumatics can be found in the �Pneumatics

    manual, P.BE−CPV−...".

  • Contents and general instructions

    IXFesto P.BE−CP−DN2−EN en 0503a

    Important user instructions

    Danger categories

    This manual contains instructions on the possible dangers

    which may occur if the product is not used correctly. These

    instructions are marked (Warning, Caution, etc.), printed on a

    shaded background and marked additionally with a picto�

    gram. A distinction is made between the following danger

    warnings:

    Warning

    This means that failure to observe this instruction may

    result in serious personal injury or damage to property.

    Caution

    This means that failure to observe this instruction may

    result in personal injury or damage to property.

    Please note

    This means that failure to observe this instruction may

    result in damage to property.

    The following pictogram marks passages in the text which

    describe activities with electrostatically sensitive compo�

    nents.

    Electrostatically sensitive components may be damaged if

    they are not handled correctly.

  • Contents and general instructions

    X Festo P.BE−CP−DN2−EN en 0503a

    Marking special information

    The following pictograms mark passages in the text contain�

    ing special information.

    Pictograms

    Information:

    Recommendations, tips and references to other sources of

    information.

    Accessories:

    Information on necessary or sensible accessories for the

    Festo product.

    Environment:

    Information on environment−friendly use of Festo products.

    Text markings

    S The bullet indicates activities which may be carried out inany order.

    1. Figures denote activities which must be carried out in the

    numerical order specified.

    � Hyphens indicate general activities.

  • Contents and general instructions

    XIFesto P.BE−CP−DN2−EN en 0503a

    The following product−specific terms and abbreviations are

    used in this manual:

    Term/abbreviation Meaning

    CP Compact performance

    CP cable Special cable for coupling the various CP modules

    CP connection Plug or socket on the CP modules which enables the modules to be

    connected with the CP cable

    CP modules Common term for various modules which can be incorporated in a

    CP system

    CP system Complete system consisting of CPV Direct and CP modules

    CPV Direct CPV valve terminal with field bus direct connection

    I Digital input

    ID Identifier

    I/O modules Common term for the CP modules which provide digital inputs and

    outputs (CP input modules and CP output modules)

    I/Os Digital inputs and outputs

    O Digital output

    OB Output byte

    PLC/IPC Programmable logic controller/industrial PC

    Short circuit/overload Short circuit/overload

  • Contents and general instructions

    XII Festo P.BE−CP−DN2−EN en 0503a

  • Installation

    1−1Festo P.BE−CP−DN2−EN en 0503a

    Chapter 1

  • 1. Installation

    1−2 Festo P.BE−CP−DN2−EN en 0503a

    Contents

    1. Installation 1−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.1 General instructions on installation 1−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2 Setting the CPV Direct 1−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.1 Fitting and removing the switch module 1−5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.2 Setting the DIL switches 1−7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3 Connecting to the field bus 1−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.1 Field bus cable 1−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.2 Field bus baud rate and field bus length 1−15. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.3 Connection instructions for DeviceNet 1−16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.4 Micro style connection (2�x�M12) 1−18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.5 Open style connection (screw terminals, IP20) 1−19. . . . . . . . . . . . . . . . . . . . . . .

    1.3.6 Connection example 1−20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.3.7 Futher connection possibility on the field bus with the Sub−D plug 1−21. . . . . . .

    1.4 Bus termination with terminating resistors 1−24. . . . . . . . . . . . . . . . . . . . . . . . . .

    1.5 Power supply 1−25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.5.1 Cable for power supply 1−25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.5.2 Selecting the power unit� 1−27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.5.3 Connecting the power supply 1−29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.6 Extending the CPV Direct 1−34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 1. Installation

    1−3Festo P.BE−CP−DN2−EN en 0503a

    1.1 General instructions on installation

    Warning

    Before carrying out installation and maintenance work,

    switch off the following:

    � the compressed air supply

    � the operating voltage for the internal logics

    � the load voltage for the valves.

    You can thereby avoid:

    � uncontrolled movements of loose tubing

    � unexpected movements of the connected actuators

    � non−defined switching states of the electronic

    components.

    Caution

    The CPV valve terminal with field bus direct connection

    (CPV Direct) contains electrostatically sensitive compo�

    nents.

    � Do not therefore touch any contacts.

    � Observe the regulations for handling electrostatically

    sensitive components.

    You will then prevent the electronics from being damaged.

  • 1. Installation

    1−4 Festo P.BE−CP−DN2−EN en 0503a

    Electrical connecting and display elements

    The following connecting and display elements can be found

    on the CPV valve terminal with field bus direct connection

    (CPV Direct):

    1

    2

    3

    4

    5

    6

    1 Exchangeable field bus connection:� Micro style connection (2�x�M12)

    � Open style connection (terminal

    strip)

    � 9−pin Sub−D plug

    2 Switch module (can be removed)

    3 Connection for power supply (4−pinM12 plug, operating voltage for

    electronics, load voltage for CP valves)

    4 LEDs:− Power status (�PS", green/red)

    − Module/network status (�MNS",

    green/red)

    5 CP extension connection

    6 Switching status displays of the CPvalve coils (yellow LEDs)

    Fig.�1/1: Connecting and display elements of the CPV Direct

  • 1. Installation

    1−5Festo P.BE−CP−DN2−EN en 0503a

    1.2 Setting the CPV Direct

    1.2.1 Fitting and removing the switch module

    Caution

    The switch module contains electrostatically sensitive

    components.

    � Do not therefore touch any contacts.

    � Observe the regulations for handling electrostatically

    sensitive components.

    The switch module must be removed before the CPV Direct

    can be set.

    Fig.�1/2: Fitting/removing the switch module

  • 1. Installation

    1−6 Festo P.BE−CP−DN2−EN en 0503a

    Removing

    1. Switch off the operating voltage.

    2. Unscrew the two fastening screws of the switch module.

    3. Lift up and remove the switch module.

    Fitting

    1. Place the switch module carefully in the recess.

    2. Tighten the two fastening screws alternately.

    Please note

    � Do not tilt the switch module when fitting it. The fitting

    position is clearly marked by a groove in the housing.

    � Make sure that the seal is seated correctly.

  • 1. Installation

    1−7Festo P.BE−CP−DN2−EN en 0503a

    1.2.2 Setting the DIL switches

    When the switch module has been removed, you will see two

    DIL switches (Fig.�1/3).

    You can set the following parameters with the DIL switches:

    � the baud rate

    � the extension to the CP system

    � the station number on the DeviceNet.

    Proceed as follows:

    1. Switch off the operating voltage.

    2. Remove the switch module (chapter 1.2.1).

    3. Set the baud rate (8−position DIL switch, elements 7...8).

    4. Set the extension to the CP system (4−position DIL switch,

    elements 3...4).

    5. Assign an unused station number to the CPV Direct.

    Set the desired station number (8−position DIL switch,

    elements 1...6)

    6. Fit the switch module (chapter 1.2.1).

  • 1. Installation

    1−8 Festo P.BE−CP−DN2−EN en 0503a

    1

    2

    3

    4

    4−position DIL switch:

    1 Reserved (softwareversion V3.01)

    2 Setting the extensionto the CP system

    8−position DIL switch:

    3 Setting the station number

    4 Setting the baud rate

    Fig.�1/3: DIL switch in the switch module (further informa�

    tion on 1�...�4 see following pages)

    Setting: Software version 1

    Software version V3.01 Setting of the DIL switches

    The DIL switches must be set

    to OFF.

    Fig.�1/4: Reserved setting on the 4−position DIL switch

  • 1. Installation

    1−9Festo P.BE−CP−DN2−EN en 0503a

    Setting the extension to the CP system 2

    Further CP modules can be connected to the CPV Direct. You

    can set the extension to the CP system with switch elements 3

    and 4 of the 4−position DIL switch as shown in the diagram

    below.

    Extension to the CP system Number of inputs/outputs Setting of the

    DIL switches

    CPV Direct

    without extension

    16 O

    CPV Direct

    with extension with:

    � CP input module

    16 O

    +

    16 I

    CPV Direct

    with extension with:

    � a CP valve terminal

    or

    � a CP output module

    16 O

    +

    16 O

    CPV Direct

    with extension with:

    � a CP valve terminal/CP output module

    and

    � a CP input module

    16 O

    +

    16 O

    +

    16 I

    Fig.�1/5: Setting the extension of the CP system with the 4−position DIL switch

    Please note

    Depending on the extension set, the CP system occupies

    a different number of inputs and outputs or station

    numbers. Further information can be found in chapter 1.6.

  • 1. Installation

    1−10 Festo P.BE−CP−DN2−EN en 0503a

    Setting the station number 3

    You can set the field bus station number (binary coded) with

    the 8−position DIL switch.

    Please note

    Station numbers may only be assigned once per field bus

    line.

    The following station numbers are permitted:

    Protocol Address

    identification

    Permitted station

    numbers

    DeviceNet Station number 0; ...; 63

    1 Setting the station number

    (8−position

    DIL switch,

    elements 1...6)

    1

    Fig.�1/6: Setting the station number (8−position DIL switch)

    Set station number: 05 Set station number: 38

    20 + 22 =

    1 + 4 =

    5

    21 + 22 + 25 =

    2 + 4 + 32 =

    38

    Fig.�1/7: Examples of set station numbers

  • 1. Installation

    1−11Festo P.BE−CP−DN2−EN en 0503a

    Recommendation:

    Assign the station numbers in ascending order. Assign the

    station addresses to suit the machine structure of your sys�

    tem.

    The following pages contain a summary of the settings for the

    station numbers.

    Setting the baud rate 4�

    Set the baud rate as follows:

    125 kBaud 250 kBaud 500 kBaud

    Fig.�1/8: Setting the baud rate with switch elements 7 and 8 of the 8−position DIL switch

  • 1. Installation

    1−12 Festo P.BE−CP−DN2−EN en 0503a

    Sta�

    tion

    no.

    1 2 3 4 5 6 7 8 Sta�

    tion

    no.

    1 2 3 4 5 6 7 8

    0OFF OFF OFF OFF OFF OFF

    16OFF OFF OFF OFF

    ON

    OFF

    1 ON

    OFF OFF OFF OFF OFF

    17 ON

    OFF OFF OFF

    ON

    OFF

    2OFF

    ON

    OFF OFF OFF OFF

    18OFF

    ON

    OFF OFF

    ON

    OFF

    3 ON ON

    OFF OFF OFF OFF

    19 ON ON

    OFF OFF

    ON

    OFF

    4OFF OFF

    ON

    OFF OFF OFF

    20OFF OFF

    ON

    OFF

    ON

    OFF

    5 ON

    OFF

    ON

    OFF OFF OFF

    21 ON

    OFF

    ON

    OFF

    ON

    OFF

    6OFF

    ON ON

    OFF OFF OFF

    22OFF

    ON ON

    OFF

    ON

    OFF

    7 ON ON ON

    OFF OFF OFF

    23 ON ON ON

    OFF

    ON

    OFF

    8OFF OFF OFF

    ON

    OFF OFF

    24OFF OFF OFF

    ON ON

    OFF

    9 ON

    OFF OFF

    ON

    OFF OFF

    25 ON

    OFF OFF

    ON ON

    OFF

    10OFF

    ON

    OFF

    ON

    OFF OFF

    26OFF

    ON

    OFF

    ON ON

    OFF

    11 ON ON

    OFF

    ON

    OFF OFF

    27 ON ON

    OFF

    ON ON

    OFF

    12OFF OFF

    ON ON

    OFF OFF

    28OFF OFF

    ON ON ON

    OFF

    13 ON

    OFF

    ON ON

    OFF OFF

    29 ON

    OFF

    ON ON ON

    OFF

    14OFF

    ON ON ON

    OFF OFF

    30OFF

    ON ON ON ON

    OFF

    15 ON ON ON ON

    OFF OFF

    31 ON ON ON ON ON

    OFF

    Fig.�1/9: Setting station numbers 0...31: Position of the DIL switch elements�

  • 1. Installation

    1−13Festo P.BE−CP−DN2−EN en 0503a

    Sta�

    tion

    no.

    1 2 3 4 5 6 7 8 Sta�

    tion

    no.

    1 2 3 4 5 6 7 8

    32OFF OFF OFF OFF OFF

    ON 48OFF OFF OFF OFF

    ON ON

    33 ON

    OFF OFF OFF OFF

    ON 49 ON

    OFF OFF OFF

    ON ON

    34OFF

    ON

    OFF OFF OFF

    ON 50OFF

    ON

    OFF OFF

    ON ON

    35 ON ON

    OFF OFF OFF

    ON 51 ON ON

    OFF OFF

    ON ON

    36OFF OFF

    ON

    OFF OFF

    ON 52OFF OFF

    ON

    OFF

    ON ON

    37 ON

    OFF

    ON

    OFF OFF

    ON 53 ON

    OFF

    ON

    OFF

    ON ON

    38OFF

    ON ON

    OFF OFF

    ON 54OFF

    ON ON

    OFF

    ON ON

    39 ON ON ON

    OFF OFF

    ON 55 ON ON ON

    OFF

    ON ON

    40OFF OFF OFF

    ON

    OFF

    ON 56OFF OFF OFF

    ON ON ON

    41 ON

    OFF OFF

    ON

    OFF

    ON 57 ON

    OFF OFF

    ON ON ON

    42OFF

    ON

    OFF

    ON

    OFF

    ON 58OFF

    ON

    OFF

    ON ON ON

    43 ON ON

    OFF

    ON

    OFF

    ON 59 ON ON

    OFF

    ON ON ON

    44OFF OFF

    ON ON

    OFF

    ON 60OFF OFF

    ON ON ON ON

    45 ON

    OFF

    ON ON

    OFF

    ON 61 ON

    OFF

    ON ON ON ON

    46OFF

    ON ON ON

    OFF

    ON 62OFF

    ON ON ON ON ON

    47 ON ON ON ON

    OFF

    ON 63 ON ON ON ON ON ON

    Fig.�1/10: Setting station numbers 32...63: Position of the DIL switch elements

  • 1. Installation

    1−14 Festo P.BE−CP−DN2−EN en 0503a

    1.3 Connecting to the field bus

    1.3.1 Field bus cable

    Please note

    With incorrect installation and high baud rates, data trans�

    mission errors may occur as a result of signal reflexions

    and attenuations.

    Causes of the transmission errors may be:

    � missing or incorrect terminating resistor

    � incorrect screening connection

    � branch lines too long

    � transmission over long distances

    � unsuitable cables.

    Observe the cable specifications. Refer to the manual for

    your controller for information on the cable type.

    Use a twisted, screened 5−wire cable for the field bus. The

    bus interface is supplied with power via the field bus cable.

    Alternatively, you can use the bus cables of other manufac�

    turers (see also Appendix A, Accessories).

    Please note

    If the valve terminal is fitted onto the moving part of a ma�

    chine, the field bus cable on the moving part must be pro�

    vided with strain relief. Please observe the relevant regula�

    tions in IEC/DIN EN 60204−1.

  • 1. Installation

    1−15Festo P.BE−CP−DN2−EN en 0503a

    1.3.2 Field bus baud rate and field bus length

    The maximum permitted field bus length depends on the

    baud rate used. Fig.�1/11 shows the guideline values.

    Detailed information can be found in the manuals for your

    control system or scanner.

    The maximum permitted length of the branch line depends on

    the total length of the branch lines and the baud rate.

    Please note

    S Refer to the manuals for your control system or bus in�terface for information on the T−adapter and the maxi�

    mum branch line length which is permitted for your con�

    troller.

    S When ascertaining the maximum permitted length of thefield bus cable, take into account also the sum of the

    branch line lengths.

    Baud rate Maximum main

    b l th

    Branch line length

    bus lengthmaximum cumulative

    125 kBaud 500 m

    6 m

    156 m

    250 kBaud 250 m

    6 m

    78 m

    500 kBaud 100 m 39 m

    Fig.�1/11: Maximum field bus length and branch line length

    as a factor of the baud rate (as per ODVA specifica�

    tion V�2.0)

    Information on setting the baud rate can be found in chapter

    1.2.2.

  • 1. Installation

    1−16 Festo P.BE−CP−DN2−EN en 0503a

    1.3.3 Connection instructions for DeviceNet

    Bus supply

    Avoid long distances between the bus interfaces/logic supply

    and the CPV Direct.

    Caution

    S Make sure the polarity is correct when you connect thefield bus interface and the power supply for the bus

    interface/internal�logics.

    S Connect the screening/shield.

    Please note

    Bus slaves of different manufacturers show different toler�

    ances in respect of interface power supply. Take this into

    consideration when planning the bus length and placing

    the power unit.

    The following tolerance of the bus interface supply applies to

    the CPV Direct (pin 2 with the micro style connection or pin�5

    with the open style connection):

    Vmax = 30.0 V

    Vmin = 11.0 V

    Recommendation:

    Place the power unit in or near the centre of the bus.

  • 1. Installation

    1−17Festo P.BE−CP−DN2−EN en 0503a

    Connection diagram for DeviceNet

    Please note

    Always check the pin assignment of your scanner with the

    relevant documentation.

    Connect the field bus cable of your control system to the field

    bus interface of the CPV Direct as follows. The following table

    shows the correlation between the core colour, signal and pin

    assignment of the various connecting possibilities.

    Signal−related

    core colour *)

    Designation Micro style

    connection

    Open style

    connection

    Sub−D plug

    red

    white

    blank

    blue

    black

    24 V DC bus

    CAN_H

    Screening/shield

    CAN_L

    0 V bus

    Pin 2

    Pin 4

    Pin 1

    Pin 5

    Pin 3

    Pin 5

    Pin 4

    Pin 3

    Pin 2

    Pin 1

    Pin 9

    Pin 7

    Pin 5

    Pin 2

    Pin 3

    *)Typical for

    DeviceNet cables Bus connnection

    variants: 1 2 3 4 5

    51

    96

    Fig.�1/12: Connection diagram for DeviceNet

  • 1. Installation

    1−18 Festo P.BE−CP−DN2−EN en 0503a

    1.3.4 Micro style connection (2�x�M12)

    Order this connection from Festo (type: FBA−2−M12−5pol).

    Connection to the bus is made with a 5−pin M12 plug with

    PG9 screw connector. Use the second connection for the con�

    tinuation of the field bus.

    Please note

    Use blanking plugs to seal unused connections. You will

    then comply with protection class IP65.

    Micro style connection Pin no.

    1. Screening/shield

    2. 24 V DC bus (max. 4�A)

    3. 0 V bus

    4. CAN_H

    5. CAN_L

    Blanking plug for

    unused connection

    Bus in

    Bus out

    Fig.�1/13: Pin assignment of the field bus interface (micro

    style connection, M12, 5−pin)

    With the M12 connections you can implement a T−tap (see

    Fig.�1/15). Bus in and Bus out are connected together in the

    micro style connection.

  • 1. Installation

    1−19Festo P.BE−CP−DN2−EN en 0503a

    1.3.5 Open style connection (screw terminals, IP20)

    Order this connection from Festo (type: FBA−1−SL−5pol)

    together with the terminal strip type FBSD−KL−2x5pol.

    Connection to the bus is made with a 2x5−pin terminal strip.

    Use the second row of connections for the continuation of the

    field bus.

    The maximum current at the terminals is 4 A. Use cables with

    a minimum cross−sectional area of 0.34 mm2.

    Open style connection Pin no.

    1 2 3 4 5

    1. 0 V bus

    2. CAN_L

    3. Screening/shield

    4. CAN_H

    5. 24 V DC bus (max. 4 A)

    2x5−pin terminal strip

    Fig.�1/14: Pin assignment of the field bus interface (open

    style connection, 5−pin)

    If you connect the field bus via the terminal strip type

    FBSD−KL−2x5pol from Festo, you can implement a T−tap

    function (double row of screw terminals).

  • 1. Installation

    1−20 Festo P.BE−CP−DN2−EN en 0503a

    1.3.6 Connection example

    1 2 3 4 5

    2

    3

    1

    4 5 6

    1 Micro style connection with T−tap function (if the micro style connection

    is removed completely with the plugs).

    2 T−adapter

    3 Branch line

    4 Field bus

    5 Power supply

    6 Screening/shield

    Fig.�1/15: Structure of the bus interface and connection example

  • 1. Installation

    1−21Festo P.BE−CP−DN2−EN en 0503a

    1.3.7 Futher connection possibility on the field bus with the Sub−D plug

    After removing the micro style or open style connection, you

    will find a 9−pin Sub−D plug on the upper side of the CPV

    Direct.

    This connection serves as a further connection to the field

    bus (supply and continuation). Connect the CPV Direct with

    the Sub−D socket from Festo type FBS−SUB−9−BU−2x4pol.

    Please note

    Please note that only the Festo socket conforms with

    protection class IP65.

    Before connecting the Sub−D sockets of other manufac�

    turers:

    S replace the two flat screws by bolts (part no.�340960).

    Pin DeviceNet Designation Festo Sub−D socket

    (IP65)

    1

    2

    3

    4

    5

    6

    7

    8

    9

    n.c.

    CAN_L

    0 V bus

    n.c.

    BUS screening

    GND optional

    CAN_H

    n.c.

    24 V bus

    not connected

    CAN Low

    Power supply to bus interface

    not connected

    Capacitive connection to housing

    CAN High

    not connected

    Power supply to bus interface

    A/L

    GND

    Cable clip

    B/H

    V+

    (View towards connection on the CPV Direct)

    51

    96

    Fig.�1/16: Pin assignment of the field bus interface (Sub−D plug)

  • 1. Installation

    1−22 Festo P.BE−CP−DN2−EN en 0503a

    Please note

    The screening connection at pin 5 of the Sub−D plug is ca�

    pacitively connected to the housing within the CPV valve

    terminal. This is to prevent equalizing currents flowing

    through the screening of the field bus cable (Fig.�1/17).

    1 Capacitive connection

    2 Housing

    51

    96

    1

    2

    Fig.�1/17: Screening connection within the CPV valve terminal

    Festo Sub−D socket

    Fig.�1/18 shows the pin assignment in the Festo Sub−D socket

    type FBS−SUB−9−BU−2x4pol.

    Screening connection A floating screening connection is provided with the Festo

    Sub−D socket:

    S Fasten the screening/shield for the field bus cable underthe cable clip of the Festo Sub−D socket (Fig.�1/18).

  • 1. Installation

    1−23Festo P.BE−CP−DN2−EN en 0503a

    1 Screening connection,

    cable clip

    2 Only connectedcapacitively

    3 CPV Direct(smaller than

    actual size)

    4 Pin assignment in the socket

    1

    2

    3

    4

    XX

    24�V�bus

    CAN_L

    0�V�bus

    CAN_H

    Fig.�1/18: Festo Sub−D plug, pin assignment and screening/shield connection (see also

    Fig.�1/16)

    Please note

    The cable clip in the Festo Sub−D plug is connected inter�

    nally only capacitively with the metallic housing of the

    Sub−D socket. This is to prevent equalizing currents flow�

    ing through the screening of the field bus cable (Fig.�1/18).

    With this plug, contact with the screening cable is made via

    the cable clip. This connects the incoming and outgoing cable

    screening. With a 5−core cable, you can therefore cut off the

    screening cores.

  • 1. Installation

    1−24 Festo P.BE−CP−DN2−EN en 0503a

    1.4 Bus termination with terminating resistors

    Please note

    Use a bus termination at both ends of the bus segment.

    This also applies when the module or the interface is at the

    beginning of a bus cable.

    If the CPV valve terminal is at the end of the field bus system,

    a bus termination will be required.

    If you are using T−adapters, we recommend that you install

    the terminating resistor at the unused output of the

    T−adapter.

    Recommendation:

    Fit a resistor (120�Ω, 0.25 W) for the bus termination betweenthe connections for CAN_L and CAN_H. Fig.�1/19 shows this

    as an example with the open style connection.

    1 Resistor for bustermination

    (120 Ω, 0.25 W)

    1

    1 2 3 4 5

    Fig.�1/19: Bus termination with resistor on the open style connection

  • 1. Installation

    1−25Festo P.BE−CP−DN2−EN en 0503a

    1.5 Power supply

    1.5.1 Cable for power supply

    S Use a power supply cable with sufficient cross−sectionalarea.

    S Avoid long distances between the power unit and the CPVvalve terminal. Long cables reduce the voltage supplied

    by the power unit.

    S If necessary, ascertain the suitable cross−sectional areaand the maximum permitted cable length.

    The connection for the power supply is in the form of a plug.

    The pin assignment of the plug can be found on the following

    pages.

    For connecting the power supply, use plugs from the Festo

    range which correspond to the outer diameter of the cable

    used (see Appendix A.2).

  • 1. Installation

    1−26 Festo P.BE−CP−DN2−EN en 0503a

    1 Cables

    2 Strain relief

    3 Housing

    4 Connecting part

    12

    3

    4

    Fig.�1/20: Individual parts of plug and cable exit

    Preparing When you have selected suitable cables connect them as

    follows (Fig.�1/20):

    1. In order to open the plug loosen the centre knurled nut.

    2. Open the strain relief on the rear part of the housing.

    Then pass the cable through.

    3. Remove 5 mm of insulation from the end of the cable and

    fit end sleeves on the strands.

    4. Connect the ends of the conductor.

    5. Replace the connecting part back onto the housing of the

    plug. Pull the cable back so that there are no loops inside

    the housing.

    6. Tighten the strain relief.

  • 1. Installation

    1−27Festo P.BE−CP−DN2−EN en 0503a

    1.5.2 Selecting the power unit�

    Warning

    S Use only PELV circuits as per IEC/DIN EN 60204−1 (Pro�tective Extra−Low Voltage, PELV) for the electrical supply.

    Consider also the general requirements for PELV circuits

    in accordance with IEC/DIN EN 60204−1.

    S Use power supplies which guarantee reliable electricalisolation of the operating voltage as per IEC/DIN EN

    60204−1.

    By the use of PELV circuits, protection against electric shock

    (protection against direct and indirect contact) is guaranteed

    in accordance with IEC/EN 60204−1 (Electrical equipment for

    machines, General requirements).

    The current consumption of a CP system depends on the

    number of CP modules valve coils.

    Recommendation:

    S Used closed−loop power units.

    S When selecting the power units, check that they havesufficient output. If required, ascertain here the total cur�

    rent consumption according to the following table.

  • 1. Installation

    1−28 Festo P.BE−CP−DN2−EN en 0503a

    Total current consumption� The table below shows how to calculate the total current con�

    sumption for a CP system. The values specified have been

    rounded up.

    Current consumption of CP electronics

    (pin 1)

    Sums

    CPV Direct max. 100 mA

    CPV valve terminal max. 40 mA

    CPA valve terminal 20 mA

    A CP input module max. 40 mA

    Sensors see manufacturer’s

    specifications

    CP output module max. 40 mA

    Carry forward =_______mA

    Current consumption of valves (pin 2)

    Current consumption

    of all simultaneously

    energized valve

    coils 1)

    __x_____mA =_______mA

    1) Current consumption depends on valve type (see Technical

    specifications for the valves).

  • 1. Installation

    1−29Festo P.BE−CP−DN2−EN en 0503a

    1.5.3 Connecting the power supply

    Warning

    If the valve terminal is supplied with load voltage via an

    output of a �safety I/O module", switch−on test pulses of

    the �safety I/O module" can cause unexpected reactions

    of the valve terminal.

    S Make sure that these switch−on test pulses are reliablysuppressed or switched off.

    Use only a 4−pin M12 socket for the power supply and con�

    nect this only to the connection for the power supply (see

    Fig.�1/1).

    The current consumption depends on the type of valve ter�

    minal. Please refer to the �Pneumatics manual, P.BE−CPV−.."

    and the previous chapter for the values.

    When connecting the 24 V load voltage (pin�2), observe the

    following:

    S Observe the tolerance (20.4 V DC ... 26.4 V). Check the 24 V load voltage of the valves while your system is oper�

    ating.

    Caution

    Protect the load voltage of the CPV valve coils externally

    with a fuse max. 2 A.

    In this way you can avoid functional damage to the CPV

    Direct in the event of a short circuit.

  • 1. Installation

    1−30 Festo P.BE−CP−DN2−EN en 0503a

    Please note

    Check within the framework of your EMERGENCY STOP

    circuit, to ascertain the measures necessary for putting

    your machine/system into a safe state in the event of an

    EMERGENCY�STOP.

    � Switch off the load voltage of the valves and output

    modules in the secondary circuit of the power unit.

    � Switch off the compressed air supply to the valve

    terminal.

    Due to energy being stored in the input circuit of valve

    terminals, there may be a delay when the load voltage is

    switched off before the valves are switched off.

    Take this into consideration as follows:

    � Register the fact that the load voltage is switched off

    by means of an input signal in the controller.

    � Block the control signal of the valves by locking the

    output signal with the input signal �load voltage".

  • 1. Installation

    1−31Festo P.BE−CP−DN2−EN en 0503a

    Pin assignment of the power supply connection for

    the CPV valve terminal

    1

    1 Pin assignment1: 24 V DC operating voltage for electronics (and

    inputs; in the case of connected modules on the

    extension connection)

    2: 24 V DC load voltage for valves

    3: 0 V

    4: Earth/ground�connection

    Fig.�1/21: Pin assignment of power supply connection

  • 1. Installation

    1−32 Festo P.BE−CP−DN2−EN en 0503a

    Potential equalization

    The CPV valve terminal has two earthing connections for

    potential equalization:

    � on the power supply connection

    � on the end plate.

    Please note

    S Always connect the earth potential to pin 4 of the powersupply connection.

    S Connect the earth connection of the left−hand end platewith low impedance (short cable with large cross−sec�

    tional area) to the earth potential.

    S With low−impedance connections you can ensure thatthe housing of the valve terminal and the earth connec�

    tion at pin 4 have the same potential and that there are

    no equalizing currents.

    In this way, you will avoid interference caused by electro�

    magnetic�influences.

  • 1. Installation

    1−33Festo P.BE−CP−DN2−EN en 0503a

    3 1 2 4PS

    MNS

    1

    43

    24 V

    0 V

    2 3 5

    2 A

    2 A

    1 Connection for the power supply to the CPV Direct

    2 PE

    3 Potential equalization

    4 Load voltage can be switched off separately and external fuses

    5 The earth connection at pin 4 is designed for 3 A

    Fig.�1/22: Example of connection of PELV power unit and

    potential equalization

  • 1. Installation

    1−34 Festo P.BE−CP−DN2−EN en 0503a

    1.6 Extending the CPV Direct

    You can connect further modules of the CP system to the CPV

    Direct via the CP extension connection.

    PS

    MNS

    1

    1 CP extension connection

    Fig.�1/23: CP extension connection

    Please note

    Set the exact extension of your CP system on the 4−posi�

    tion DIL switch on the switch module.

    Modules which you connect to the CP extension connec�

    tion will be recognized only if the DIL switch is set cor�

    rectly.

    Information on setting the DIL switches can be found in

    chapter 1.2.2.

  • 1. Installation

    1−35Festo P.BE−CP−DN2−EN en 0503a

    You can connect the following CP modules to the CP exten�

    sion connection:

    � CP input module with 16 inputs, either with 8 x M12 plug

    (sockets assigned twice), 16 x M8 plug (sockets assigned

    once) or terminals (IP20).

    � CP input module (IP20) with 16 inputs.

    � CP output module with 8 outputs each with 0.5 A. The

    power for the module is also supplied via the CP exten�

    sion connection. The load voltage must be supplied

    separately via an M18 plug.

    � CPV valve terminals of widths 10, 14 and 18 mm. These

    are available with 4, 6 or 8 CP valve plates.

    � CPV valve terminals of widths 10 and 14 mm.

    These are available for field bus connections with max. 8

    double−solenoid or 16 single−solenoid valve plates.

    Please note

    The CPV Direct can be extended by maximum:

    � one CP input module

    � one CP valve terminal or one CP output module.

  • 1. Installation

    1−36 Festo P.BE−CP−DN2−EN en 0503a

    Caution

    The maximum cable length between the CPV Direct and the

    last CP module must not exceed 10 m.

    The CP connecting cables must have special electrical

    characteristics. Always use, therefore, Festo CP connecting

    cables.

    You can obtain ready−to−use CP connecting cables from Festo.

    These are available in various lengths and types. You will find

    a summary in Appendix A.

    Seal unused CP connections of your CP system with the rel�

    evant seal provided. You will then comply with protection

    class IP65.

    The following diagram shows possible extensions:

  • 1. Installation

    1−37Festo P.BE−CP−DN2−EN en 0503a

    Extension to the CP system Position of the switch elements in

    4 iti DIL it hCPV Direct Output

    module or CP

    valve terminal

    Input� module4−position DIL switch

    1BUS POWER

    1

    320

    14

    58

    912

    23

    671

    011

    1415

    POW

    ERD

    IAG

    INP

    UT

    P

    POWER

    12

    BUS

    POWER

    4

    1

    2

    POWER

    POWER 5

    1

    4 32 2

    01

    45

    89

    122

    36

    710

    1114

    15 13PO

    WER

    DIA

    G

    INP

    UT

    P

    BUS

    POWER

    1

    3

    522

    01

    45

    89

    122

    36

    710

    1114

    15PO

    WER

    DIA

    G

    INP

    UT

    P

    POWER

    POWER

    Total cable length of the CP system: maximum 10 m

    1 CPV Direct

    2 CP connecting cable 0.5�m, 2�m, 5�m, 8�m

    3 CP input module 16 inputs (8�x�M12, 16�x�M8 plug)

    4 CP output module 8 outputs (8�x�M12 plug)

    5 CPV or CPA valve terminal

    Fig.�1/24: Extension possibilities for the CPV Direct

  • 1. Installation

    1−38 Festo P.BE−CP−DN2−EN en 0503a

  • Commissioning

    2−1Festo P.BE−CP−DN2−EN en 0503a

    Chapter 2

  • 2. Commissioning

    2−2 Festo P.BE−CP−DN2−EN en 0503a

    Contents

    2. Commissioning 2−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1 Preparing the CP valve terminal for commissioning 2−3. . . . . . . . . . . . . . . . . . . .

    2.1.1 Switching on the operating voltage 2−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.1.2 Address assignment of the CPV valve terminal 2−4. . . . . . . . . . . . . . . . . . . . . . .

    2.2 Commissioning on the DeviceNet 2−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1 General information 2−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.2 Configuring DeviceNet slave features (EDS) 2−7. . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.3 Valid instructions for parametrizing on the DeviceNet 2−9. . . . . . . . . . . . . . . . . .

    2.2.4 Instructions on parametrizing with RSNetWorx for DeviceNet 2−11. . . . . . . . . . .

    2.2.5 Device−specific parametrizing 2−17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.6 Explicit Message 2−25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 2. Commissioning

    2−3Festo P.BE−CP−DN2−EN en 0503a

    2.1 Preparing the CP valve terminal for commissioning

    2.1.1 Switching on the operating voltage

    Please note

    Please observe also the switching−on instructions in the

    manual for your PLC controller.

    S Before switching on, make sure that the specifications onthe field bus configuration are complete and correct.

    Please observe the following points when switching on the

    power supply:

    Common supply If there is a common supply for the control system and for all

    the field bus slaves, the power should be switched on via a

    central power unit or central switch.

    Separate supply If there is a separate supply for the control system and for the

    field bus slaves, the power should be switched on in the fol�

    lowing sequence:

    1. the power supply for all the field bus slaves

    2. the power supply for the controller.

  • 2. Commissioning

    2−4 Festo P.BE−CP−DN2−EN en 0503a

    2.1.2 Address assignment of the CPV valve terminal

    The CPV valve terminal with field bus direct connection al�

    ways occupies 16 output addresses, irrespective of the

    number of valve solenoid coils fitted on it. This enables the

    CPV valve terminal to be extended at a later stage without the

    need to shift the addresses.

    The following diagram shows the addressing sequence of the

    individual CPV valve plates.

    0−1

    2−3

    4−5 8−9

    10−11

    12−13

    6−7 14−15

    Fig.�2/1: Addressing sequence of a CPV valve terminal. The

    figures also indicate the numbers of the outputs.

    � A valve location on the CPV valve terminal always oc�

    cupies 2 addresses, even if it is fitted with a blanking

    plate or pressure−separator plate. If a valve location is

    fitted with a double−solenoid valve, the following assign�

    ment applies:

    � pilot solenoid 14 occupies the lower−value address;

    � pilot solenoid 12 occupies the higher−value address.

    With single−solenoid valves the higher−value address

    remains unused.

  • 2. Commissioning

    2−5Festo P.BE−CP−DN2−EN en 0503a

    � Addresses are assigned from left to right on the CPV valve

    terminal and from the front to the rear on the individual

    valve locations.

    PS

    MNS

    Byte 0 Byte 1

    Bit�0

    Bit�1

    Bit�3

    Bit�2

    Bit�5

    Bit�4

    Bit�6

    Bit�7

    Bit�1

    Bit�0

    Bit�3

    Bit�2

    Bit�5

    Bit�4

    Bit�7

    Bit�6

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15Numbers

    of the outputs

    Fig.�2/2: Address assignment of the CPV valve terminal

    (outputs) with examples for byte 0 and byte 1

  • 2. Commissioning

    2−6 Festo P.BE−CP−DN2−EN en 0503a

    2.2 Commissioning on the DeviceNet

    Please note

    � The Festo valve terminal type CPV...−GE−DN2−8 can be

    used on all DeviceNet masters.

    � This chapter describes configuration and commissioning

    using as an example the controllers from Allen−Bradley.

    2.2.1 General information

    Please note the following special features when using the CPV

    valve terminal on the DeviceNet:

    � The I/O addresses of all recognized DeviceNet slaves can

    be freely assigned as M−file addresses or as discrete I/Os

    in the Scanlist.

    � The addresses of network slaves are normally assigned in

    ascending order.

    � The input and output addresses can be assigned indepen�

    dently of each other.

    Please note

    Order the I/O addresses of the network slaves so that

    there is sufficient reserve for later extensions.

    The following sections contain generally valid instructions for

    configuring a valve terminal on the DeviceNet.

    Detailed information can be found in the documentation or in

    the help for the configuration program you are using.

  • 2. Commissioning

    2−7Festo P.BE−CP−DN2−EN en 0503a

    2.2.2 Configuring DeviceNet slave features (EDS)

    When you commission a new DeviceNet slave the first time,

    you must inform your configuration program of certain fea�

    tures of the slave. The features of the various slaves are

    usually administered by the configuration program in a list or

    library e.�g. �EDS library" (EDS for electronic data sheets).

    The following possibilities are available for extending an

    �EDS library":

    � Installing an EDS−file

    � Entering the slave features by hand.

    Installing an EDS−file

    Internet Current EDS−files and icons can be found under the following

    address in Internet:

    � www.festo.com: Go to the Business Area �Pneumatics"

    and then to �Download Area".

    For the CPV Direct you will require the following files:

    File type File name

    EDS−file DN2DICP.EDS

    ICO file (Icon) DN2DICP.ICO

    BMP file (Bitmap) DN2DICP.BMP

    EDS file The EDS file contains all the necessary features of valve ter�

    minal type CPV...GE−DN2−8. You can install this file with the

    aid of your configuration program.

    ICO/BMP file Depending on the configuration program used, you can as�

    sign the bitmap file or icon file to the valve terminal. The valve

    terminal will then be represented accordingly in the configur�

    ation program.

  • 2. Commissioning

    2−8 Festo P.BE−CP−DN2−EN en 0503a

    Instructions on installing an EDS file and an ICO or BMP file

    can be found in the manual or in the help for your configur�

    ation program.

    Entering the slave features by hand

    When an EDS file is installed, the following information about

    the DeviceNet slave is added to the EDS library. This informa�

    tion can also be entered manually.

    Information Manual

    Vendor name Festo Corporation

    Device type 27D 1BH

    Product code 8942D 22EEH

    Major revision / minor revision 3.01

    Input size / output size Depending on the string assign�

    ment set in the switch module

    (see Fig.�2/3).

    Product name CPV−DN2−8

    Catalogue number 525630

    When the EDS library has been extended, the valve terminal

    is entered in the slave list as a possible DeviceNet slave. It

    can now be added to a network.

  • 2. Commissioning

    2−9Festo P.BE−CP−DN2−EN en 0503a

    2.2.3 Valid instructions for parametrizing on the DeviceNet

    When the slave features have been configured (e.g. by instal�

    ling the EDS file), the following steps are required for parame�

    trizing, depending on the configuration program.

    1. Insert the slave in the project/network (online or offline).

    If the slave is inserted e.g. offline, it will be selected from

    the slave list and added to the network.

    2. Assign a slave to a scanner. A network can contain several

    scanners. The slave must be assigned to a scanner.

    3. Determine the I/O parameters of the slave. The following

    specifications are required here:

    S The number of I/O bytes to be transmitted. For theCPV Direct, the number depends on the connected

    extensions (see chapter 1.6):

    − 2 input bytes occupied

    − 2 or 4 output bytes occupied.

    The table in Fig.�2/3 shows the assignment.

    S Specification of communication type. The followingapplies for the CPV Direct:

    − �Polled Communication"

    or

    − �Change of State / Cyclic".

    In addition to these communication connnections a

    �Strobed I/O" connection must be used in each case

    for the diagnosis.

  • 2. Commissioning

    2−10 Festo P.BE−CP−DN2−EN en 0503a

    Please note

    The following applies to an SLC 500 with an Allen−Bradley

    scanner type 1747−SDN:

    � �Change of State / Cyclic" can be used in combination

    with the diagnosis via Strobed I/O only as from software

    version V4.015 of the scanner.

    � �Polled I/O" with �Strobed I/O" is also supported by

    earlier versions.

    S Assign the I/O addresses of the slave to the PLC operands.

    S Assign 1 diagnostic byte to the PLC operands.

    4. Load the configuration into the scanner.

    Extension to the CP system Number of

    inputs/

    outputs

    Number of

    I/O bytes

    CPV Direct without extension 16 O 2 O−bytes

    CPV Direct extended with:

    � a CP input module

    16 I, 16 O 2 I−bytes

    2 O−bytes

    CPV Direct extended with:

    � a CP valve terminal

    or

    � CP output module

    32 O 4 O−bytes

    CPV Direct extended with:

    � a CP valve terminal/CP output

    module

    and

    � a CP input module

    16 I, 32 O 2 I−bytes

    4 O−bytes

    Fig.�2/3: Number of occupied I/O bytes depending on the

    extension to the CPV Direct.

  • 2. Commissioning

    2−11Festo P.BE−CP−DN2−EN en 0503a

    2.2.4 Instructions on parametrizing with RSNetWorx for DeviceNet

    This section gives instructions on parametrizing with

    RSNetWorx for DeviceNet version 3.00.00 from Rockwell.

    Please note

    All the steps explained refer as an axample to the Allen−

    Bradley scanner 1747−SDN. They also apply to other

    masters.

    Inserting the slave into the project/network

    RSNetWorx for DeviceNet contains an EDS assistant which

    will support you in installing the EDS file. After installing the

    EDS−file, you will find the CPV Direct in the list �Hardware".

    By pulling the cursor across, you can insert slaves in the net�

    work on the right−hand side.

  • 2. Commissioning

    2−12 Festo P.BE−CP−DN2−EN en 0503a

    1

    1 CPV Direct type CPV..−GE−DN2−8 in the list �Hardware"

    Fig.�2/4: Hardware list and network in RSNetWorx for DeviceNet

  • 2. Commissioning

    2−13Festo P.BE−CP−DN2−EN en 0503a

    Assigning a slave to a scanner

    1. Double−click on the desired scanner in the network.

    A mask will open.

    2. Select the register �Scanlist" and assign the existing

    slaves to the scanner:

    1

    1 Button for assigning the slave

    Fig.�2/5: Register �Scanlist" (example)

  • 2. Commissioning

    2−14 Festo P.BE−CP−DN2−EN en 0503a

    Parametrizing slaves

    1. Double−click on one of the slaves in the �Scanlist"

    (Fig.�2/5). A mask will open.

    2. Determine the I/O parameters of the slave. Confirm with

    OK.

    Fig.�2/6: Mask for determining the I/O parameters of the

    slave

    In this configuration example a CPV Direct with maximum

    extension is parametrized:

    � Communication type: �Polled" or �Strobed" (1 input byte

    for diagnostic information).

    � 2 input bytes for a CP input module in the extension.

    � 4 output bytes for the CPV Direct and an output module

    in the extension.

    Observe the summary in Fig.�2/3.

  • 2. Commissioning

    2−15Festo P.BE−CP−DN2−EN en 0503a

    Assigning the I/O addresses of the slave

    With the registers �Output" and �Input" you can assign the

    I/O addresses of the node to the PLC operands.

    Fig.�2/7: Address assignment of the input of the 1−byte

    diagnostic information (�Strobed")

    The CPV Direct appears in the input data with two separate

    communication connections:

    � A �Strobed" connection for transmitting the diagnostic

    information.

    � A �Polled" or �Change of State" connection for transmit�

    ting the physical input data.

  • 2. Commissioning

    2−16 Festo P.BE−CP−DN2−EN en 0503a

    The physical output data are transmitted through the com�

    munication connection �Polled" or �Change of State". In this

    example �Polled":

    Fig.�2/8: Address assignment of the output (example)

    Loading the configuration into the scanner

    To conclude, load the configuration into the scanner. Further

    information on this can be found in the documentation for

    your scanner.

  • 2. Commissioning

    2−17Festo P.BE−CP−DN2−EN en 0503a

    2.2.5 Device−specific parametrizing

    The CPV Direct supports various device parameters by means

    of which you can set the reaction of the valve control and

    some status messages. The parameters are set by means of

    the �Device Parameter" in the network configurator.

    The table in Fig.�2/9 shows how you can address the valve

    coils.

    The program−controlled access by the PLC is made with the

    �Explicit Message" programming. The addresses of the Devi�

    ceNet Object Model necessary for this can be found in Appen�

    dix B.

    Reaction of the outputs in the Fault mode

    If communication via the DeviceNet is interrupted, the bus

    slaves assume the Fault mode. The reasons for this can be:

    � Physical interruption in the network

    � Interference by data telegrams.

    In the Fault mode, the outputs for the valve control and the

    outputs of the output module can assume one of the follow�

    ing states:

    � Reset the output

    � Set the output

    � Freeze the current status of the output.

    You can determine the status to be assumed for each output

    separately. The standard setting is �Reset the output".

  • 2. Commissioning

    2−18 Festo P.BE−CP−DN2−EN en 0503a

    The valves of the CPV Direct basic unit and the outputs of the

    modules in the extension are set with separate parameters:

    Parameter �Fault Action, main unit"

    With this 16−bit parameter you can determine whether each

    output is to freeze the current status or assume a certain

    output status (0/1) in Fault mode.

    Parameter

    value

    Meaning

    0 The output is set to a certain output status (0 or 1).

    The output status is defined with the parameter

    �Fault Value, main unit".

    1 The status of the output is frozen.

    Parameter �Fault Value, main unit"

    With this parameter you can determine the output status

    (0 or 1) which each output is to assume in Fault mode.

    Parameter

    value

    Meaning

    0 The output is reset

    1 The output is set

    The set parameter value is only taken into consideration if the

    appropriate output is set to 0 in the parameter Fault Action.

  • 2. Commissioning

    2−19Festo P.BE−CP−DN2−EN en 0503a

    Parameter �Fault Action, extension unit"

    The same function as above with �main unit", but for the out�

    put module in the extension.

    Parameter �Fault Value, extension unit"

    The same function as above with �main unit", but for the out�

    put module in the extension.

    Reaction of the outputs in the Idle mode

    The Idle mode is assumed by the slave after request by the

    master or scanner. The following applies in this status:

    � Inputs are transmitted

    � Outputs of the slaves are no longer updated.

    In the Idle mode, the outputs for the valve control and the

    outputs of the output module can assume one of the follow�

    ing states:

    � Reset the output

    � Set the output

    � Freeze the current status of the output.

    You can determine the status to be assumed for each output

    separately. The standard setting is �Reset the output".

    The valves of the CPV Direct basic unit and the outputs of the

    modules in the extension are set with separate parameters:

    Parameter �Idle Action, main unit"

    With this 16−bit parameter you can determine whether each

    output is to freeze the current status or assume a certain

    output status (0/1) in Idle mode.

  • 2. Commissioning

    2−20 Festo P.BE−CP−DN2−EN en 0503a

    Parameter

    value

    Meaning

    0 The output is set to a certain output status (0 or 1).

    The output status is defined with the parameter

    �Idle Value, main unit".

    1 The status of the output is frozen.

    Parameter �Idle Value, main unit"

    With this parameter you can determine the output value (0 or

    1) which each output is to assume in Idle mode.

    Parameter

    value

    Meaning

    0 The output is reset

    1 The output is set

    The set parameter value is only taken into consideration if the

    appropriate output is set to 0 in the parameter Fault Action.

    Parameter �Idle Action, extension unit"

    The same function as above with �main unit", but for the out�

    put module in the extension.

    Parameter �Idle Value, extension unit"

    The same function as above with �main unit", but for the out�

    put module in the extension.

  • 2. Commissioning

    2−21Festo P.BE−CP−DN2−EN en 0503a

    The following table shows the bit with which you can address

    the valve coils for the parametrizing.

    Bit Assigned valve Parameter value *)

    0 1. Valve/coil 14 0/1

    1 1. Valve/coil 12 0/1

    2 2. Valve/coil 14 0/1

    3 2. Valve/coil 12 0/1

    4 3. Valve/coil 14 0/1

    5 3. Valve/coil 12 0/1

    6 4. Valve/coil 14 0/1

    7 4. Valve/coil 12 0/1

    8 5. Valve/coil 14 0/1

    9 5. Valve/coil 12 0/1

    10 6. Valve/coil 14 0/1

    11 6. Valve/coil 12 0/1

    12 7. Valve/coil 14 0/1

    13 7. Valve/coil 12 0/1

    14 8. Valve/coil 14 0/1

    15 8. Valve/coil 12 0/1

    *) Explanation see text

    Fig.�2/9: Assignment of the parameter bit values to the valve

    coils of the CPV Direct

  • 2. Commissioning

    2−22 Festo P.BE−CP−DN2−EN en 0503a

    Parameter example �Idle action, main unit"

    Fig.�2/10: Example for parametrizing with RSNetWorx

  • 2. Commissioning

    2−23Festo P.BE−CP−DN2−EN en 0503a

    Condition Counter for the valve function

    The Condition Counter serves for the preventative mainten�

    ance of wearing parts, necessary adjustments depending on

    movement, etc.

    There is a counter for each valve coil. The values are provided

    in 32−bit format. You can compare the actual value automati�

    cally with a specified nominal value.

    The following table shows the elements of the 16 Condition

    Counters:

    Name Format

    �Condition Counter Value" *) unsigned double integer

    �Condition Counter Preselect" *) unsigned double integer

    �Reset Condition Counter Value" unsigned short integer

    �Condition Counter compare" unsigned short integer

    *) Saved remanently in the CPV Direct

    You can set or read out these parameters via the device para�

    meters of your network configuration software.

    Reset Cond. Counter ValueBit

    U32

    Condition Counter

    U32

    (Coil)Cond. Counter compare

    Cond. Counter Value

    Cond. Counter Preselect

    Fig.�2/11: Functioning method of the Condition Counter

    The switching cycle counters count automatically the number

    of valve actuations. With the parameter �Reset Condition

    Counter Value", you can reset the counter value (�Condition

    Counter Value") at any time. The reset parameter works

  • 2. Commissioning

    2−24 Festo P.BE−CP−DN2−EN en 0503a

    positively edge−orientated, only the change from �0" to the

    value �1" leads to the resetting of the �Condition Counter

    Value".

    With the parameter �Condition Counter Preselect", you can

    define a limit value for each counter. If this value is exceeded,

    the parameter �Condition Counter compare" will be set. In

    addition to the individual counter compare Status, all 16 com�

    parison results are represented together in the parameter

    �Counter preselect compare 1..16".

    With the value �0" in the �Condition Counter Preselect" the

    compare function is made inactive (standard setting).

    Example

    Fig.�2/12: Example for parametrizing the Condition Counter

    with RSNetWorx

  • 2. Commissioning

    2−25Festo P.BE−CP−DN2−EN en 0503a

    2.2.6 Explicit Message

    The parameters listed in chapter 2.2.5 can also be read and

    written by the PLC. In order to do this use communication via

    �Explicit Message". Refere to the manual for your control

    system for information on how to program this data transfer.

    In order to address the CPV Direct you will require the follow�

    ing object descriptions:

    Object

    class

    Instance Attribute Object name Type

    8d 1...16 3d Discrete Input Object Boolean

    9d 1...16 3d Discrete Output Object Boolean

    4d 15, 35, 37 − Assembly Object Output UINT

    100d 1, 2 1...5 Festo Output Word Object UINT

    101d 1 1 Festo Input Word Object UINT

    102d 1...33 1...6 Festo Diagnostic Object (various)

    Detailed object descriptions can be found in Appendix B.

  • 2. Commissioning

    2−26 Festo P.BE−CP−DN2−EN en 0503a

  • Diagnosis

    3−1Festo P.BE−CP−DN2−EN en 0503a

    Chapter 3

  • 3. Diagnosis

    3−2 Festo P.BE−CP−DN2−EN en 0503a

    Contents

    3. Diagnosis 3−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1 Diagnosis by means of LEDs 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1.1 Normal operating status 3−3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1.2 Error displays of the LEDs PS and MNS 3−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1.3 LEDs for status display of the valve solenoid coils 3−7. . . . . . . . . . . . . . . . . . . . .

    3.2 Error search when bus is started 3−8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3 Reaction to faults in the control system 3−9. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4 Diagnosis on the DeviceNet 3−10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4.1 Diagnosis via the Software Configurator 3−10. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4.2 Diagnosis via user program 3−13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.5 Short circuit/overload 3−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.5.1 Output module 3−14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.5.2 Sensor supply at an input module 3−15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 3. Diagnosis

    3−3Festo P.BE−CP−DN2−EN en 0503a

    3.1 Diagnosis by means of LEDs

    The LEDs on the cover indicate the operating status of the

    CPV valve terminal.

    1 Green−red LED:Power status (PS)

    2 Green−red LED:Module/network

    status (MNS)

    3 Yellow LED rowfor pilot sole�

    noids (�12")

    4 Yellow LED rowfor pilot sole�

    noids (�14")

    PS

    MNS

    1

    2

    3 4

    Fig.�3/1: LEDs of the CPV Direct

    3.1.1 Normal operating status

    In the normal operating status both the LEDs light up green.

    ( � lights up; flashes; out)

    LED Sequence Colour Operating status Error treatment

    PSON

    OFF

    green

    lights up

    CP system OK None

    MNSON

    OFF

    green

    lights up

    The CPV Direct is assigned

    to a master.

    None

  • 3. Diagnosis

    3−4 Festo P.BE−CP−DN2−EN en 0503a

    3.1.2 Error displays of the LEDs PS and MNS

    Error diagnosis with the LED PS

    The PS LED (Power status) indicates an internal error of the

    CP system.

    LED Sequence Colour Operating status Error treatment

    PSON

    OFF

    off Operating voltage for

    electronics not applied

    S Check the operating voltage (pin 1)

    PSON

    OFF

    flashes

    green

    � Load voltage for CP

    valves < 20.4 V (Vval) or

  • 3. Diagnosis

    3−5Festo P.BE−CP−DN2−EN en 0503a

    LED Error treatmentOperating statusColourSequence

    PSON

    OFF

    red

    lights up

    � CP string interruption

    � One of the modules in

    the extension cannot be

    addressed

    � Short circuit/overload at

    CP output module

    � Short circuit/overload at

    CP input module

    � Failure in sensor power

    supply at CP input

    module

    � Failure in sensor power

    supply with CP−E16−M8−Z

    � The set station number

    is not permitted

    � Non−permitted module

    type

    S Check cables/plug connectors

    S Check cables/plug connectors

    S Eliminate short circuit/overload

    S Eliminate short circuit/overload

    S Check power supply

    S Check power supply

    S Correct station number

    S Check the extension to theCP system

    PS � red−green

    flashes

    � Switch module is

    missing

    � Switch module is

    defective

    S Install switch module

    S Replace switch module

  • 3. Diagnosis

    3−6 Festo P.BE−CP−DN2−EN en 0503a

    Error diagnosis with the LED MNS

    LED Sequence Colour Operating status Error treatment

    MNSON

    OFF

    off � Operating voltage for

    electronics not applied

    � Dup_MAC_ID test *) is

    not yet concluded

    S Check the operating voltage (pin 1)

    S Wait for test to finish. If the LED remains off:

    S Station number may be assigned twice. If necess�

    ary, correct station number

    MNSON

    OFF

    flashes

    green

    � The CPV Direct is not

    assigned to a master

    � Dup_MAC_ID test is

    concluded, but CPV

    Direct has no connection

    to the field bus

    S Check the configuration

    S The master is possibly notin the RUN mode: Check

    the master status

    MNSON

    OFF

    flashes red � Connection time−out

    or

    � Fault in master

    S Clarify reason for time outand eliminate

    S Check the master status

    MNS

    ON

    OFF

    red

    lights up

    � Communication fault

    � Hardware fault cannot

    be rectified

    S Check the baud rate set�ting and the connection to

    the network

    S Replace CPV Direct, Servicing required

    MNS red−green

    flashes

    � Specific communication

    fault

    S Check the field busS Check the master status

    *) Test algorhythm makes sure that no station numbers are assigned twice on the network. The test

    is usually carried out automatically when connection is made to the network.

  • 3. Diagnosis

    3−7Festo P.BE−CP−DN2−EN en 0503a

    3.1.3 LEDs for status display of the valve solenoid coils

    There is a yellow LED for every valve solenoid coil (see

    Fig.�3/1). The LED indicates the switching status of the valve

    solenoid coil.

    Please note

    The LEDs show the signal states only when there are valve

    coils at the relevant valve locations. For this purpose the

    load voltage must lie within the permitted tolerance.

    LED Colour Valve solenoid coil Meaning

    off � Basic position

    � Switch position

    No signal (logic �0")

    Signal present (logic �1") but:

    � load voltage of the valves lies below

    the permitted tolerance range

    (�

  • 3. Diagnosis

    3−8 Festo P.BE−CP−DN2−EN en 0503a

    3.2 Error search when bus is started

    A deviation in the actual extension of your CPV Direct from

    the extension set in the switch module can lead to problems

    when the system is started. Please refer in this case to

    chapter 1.6. The following table shows the reaction:

    Extending the CPV Direct (examples) Deviation Behaviour

    >

    BUS

    POWER

    BUS

    POWER

    Extension

    greater than

    position of DIL

    switch

    � System starts.

    � LED PS lights up green.

    A redundant non−configured

    module will be ignored.

    <

    BUS

    POWER

    BUS

    POWER

    Extension

    smaller than

    position of DIL

    switch. Module

    is missing.

    � System starts.

    � LED PS lights up red.

    If the missing module is added

    later, it will be recognized auto�

    matically.

    Fig.�3/3: Behaviour if the system extension differs from the setting of the DIL switch

  • 3. Diagnosis

    3−9Festo P.BE−CP−DN2−EN en 0503a

    3.3 Reaction to faults in the control system

    The reaction of the outputs to control faults or communica�

    tion faults can be set with the parameters:

    � �Fault Value" and �Fault Action"

    � �Idle Value" and �Idle Action".

    The standard setting is �Reset the output".

    Further information on parametrizing can be found in chapter

    2.2.5.

    Please note

    If the outputs are reset in the event of a PLC stop, field bus

    interruption or field bus fault, please observe the follow�

    ing:

    � Single−solenoid valves move to the basic position.

    � Double−solenoid valves remain in the current position.

    � Mid−position valves move to the mid−position (depend�

    ing on valve type: pressurized, exhausted or blocked).

  • 3. Diagnosis

    3−10 Festo P.BE−CP−DN2−EN en 0503a

    3.4 Diagnosis on the DeviceNet

    The following bus diagnoses are available:

    � Diagnosis via the DeviceNet Scanner.

    � Diagnosis via the Software Configurator (e.g. RSNetWorx,

    see chapter 3.4.1).

    � Diagnosis via the user program (see chapter 3.4.2).

    3.4.1 Diagnosis via the Software Configurator

    1. Make sure that the node is online on the DeviceNet.

    2. Double−click the icon of the valve terminal in the Software

    Configurator (e.g. RSNetWorx).

    3. Click the rider �Device Parameters".

    4. Double−click the parameter line �Status word".

    Detailed information will be shown (see Fig.�3/4).

    Further information can be found in Fig.�3/5.

  • 3. Diagnosis

    3−11Festo P.BE−CP−DN2−EN en 0503a

    Fig.�3/4: Display of detailed information on diagnosis

    (explanations see text)

  • 3. Diagnosis

    3−12 Festo P.BE−CP−DN2−EN en 0503a

    The following table shows the composition of the diagnostic

    information.

    Bit Diagnosis valid for Comment in

    EDS file

    Explanation

    0 � CP valve terminal

    in the extension

    Valve/output

    module missing

    CP connection interrupted at

    output module

    1 � Input module

    in the extension

    Input module

    missing

    CP connection interrupted at input

    module

    2 � Output module

    in the extension

    Electric overload

    at output

    Short circuit/overload at output

    module (see chapter 3.5.1)

    3 � Output module

    in the extension

    No supply at

    output

    Voff Load voltage failure at output

    module

    4 � Input module

    in the extension

    No or overloaded

    sensor supply

    Vsen Operating voltage failure at

    input module or sensors, short cir�

    cuit/overload of sensor supply

    (see chapter 3.5.2)

    5 � CP valve terminal

    in the extension

    Below 20.4 V at

    valve extension

    Vtol Load voltage of valve coils

    < 20.4 V

    6 � CPV Direct basic unit Condition Counter

    reached counter

    preselect

    Condition monitoring: At least one

    valve counter has exceeded the

    limit

    7 � CPV Direct basic unit Below 20.4 V at

    valve main block

    VLoad Power supply of the CPV

    Direct < 20.4 V

    Fig.�3/5: Table with explanation of the diagnostic information

    Additional information can be found in Appendix B.1.9.

  • 3. Diagnosis

    3−13Festo P.BE−CP−DN2−EN en 0503a

    3.4.2 Diagnosis via user program

    If the separate communication connection �Strobed I/O" is

    configured for the CP system (see Fig.�2/7), the diagnostic

    information from the above table (Fig.�3/5) is then available

    for the user program. The data from the �Strobed I/O" con�

    nection can be placed in the input file or in the M1 file of the

    controller.

  • 3. Diagnosis

    3−14 Festo P.BE−CP−DN2−EN en 0503a

    3.5 Short circuit/overload

    Detailed information on input and output modules can be

    found in the manual �CP modules electronics".

    3.5.1 Output module

    In the event of a short circuit or overload:

    � all the digital outputs of an output module will be

    switched off,

    � the green LED �Diag" on the output module will flash

    quickly,

    � bit 2 (short circuit/overload) in the Device Status byte will

    be set to logic �1".

    Please note

    The outputs cannot be used again until the short circuit or

    overload has been eliminated and the error deleted.

    Deleting the error

    You can delete the error by resetting all eight outputs. You

    can select one of the following possibilities:

    Possibilities Explanation

    S Set all the outputs of the output module tological �0" (RESET)

    or

    � Manually or automatically in the program

    or

    S briefly interrupt the CP connection at the CPoutput module

    or

    � Outputs on the output module will be reset

    automatically

    or

    S briefly interrupt the operating voltage for theCP system

    � All outputs of the CP system will be reset auto�

    matically

  • 3. Diagnosis

    3−15Festo P.BE−CP−DN2−EN en 0503a

    The outputs can then be used again. If the short circuit/over�

    load still exists, the outputs will be switched off again.

    3.5.2 Sensor supply at an input module

    If there is a short circuit, overload or voltage fault in the sen�

    sor supply:

    � the sensor supply for all inputs of the module will be

    switched off,

    � the green LED �Diag" on the input module will flash

    quickly,

    � error bit Vsen (bit 4 in the Device Status byte) will be set to

    logic �1".

    Please note

    The outputs cannot be used again until the short circuit or

    overload has been eliminated and theerror deleted.

    Deleting the error/short circuit/overload

    You can delete the error in one of the following ways:

    S Briefly interrupt the CP connection at the CP input module

    or

    S briefly interrupt the operating voltage of the CP system onthe CPV Direct.

    The inputs can then be scanned again. If the short circuit/

    overload still exists, the error will be shown again.

    Module CP−E16−M8−Z:

    The short circuit/overload will be reset automatically and the

    voltage will be switched on again.

  • 3. Diagnosis

    3−16 Festo P.BE−CP−DN2−EN en 0503a

  • Technical data and accessories

    A−1Festo P.BE−CP−DN2−EN en 0503a

    Appendix A

  • A. Technical data and accessories

    A−2 Festo P.BE−CP−DN2−EN en 0503a

    Contents

    A. Technical data and accessories A−1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .