Compact Cabinet Coolers - globalmetech.com · Air conditioners and other below ambient type coolers...
Transcript of Compact Cabinet Coolers - globalmetech.com · Air conditioners and other below ambient type coolers...
Compact CabinetCoolers
C a t a l o g
Com
pact Cabinet C
oolersNOREN ProductsInc.2
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
Table of ContentsClick on the link to view the content
IntroductionFeaturesDetermine Heat LoadExample ApplicationsDrop-In ModelsFlush Mount ModelsCC200CC250FCC400F & 600FCC500, 800, 1400 & 2000CC900F, 1300F & 2500FAir-to-Water UnitsCC2060CC3060CC3260CC6360Explosion Proof ModelsCC850-XP & CC1250-XPCC4000CC450RSizing Sheet
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 3
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
INTRODUCTION
Noren Products Inc. produces a broad range of heat transfer devices incorporating heatpipes. Several of the company's products are widely recognized by their brand names.They include Compact Cabinet Coolers, Thermal Pins, and Megaflats.The first Noren Heat Pipes were manufactured over 30 years ago. During this time, NorenProducts has successfully solved thermal management problems in the military, machinetool, instrument, robotics, food and power industries, to name a few. The heat pipe is thebasic rapid heat transfer device in all of Noren's cooling products.
What is a real Heat Pipe?
A heat pipe consists of a sealed aluminum or copper container whose inner surfaces have acapillary wicking material. Inside the container is a liquid (usually alcohol) under its ownpressure, that enters the pores of the capillary material, wetting all internal surfaces.Applying heat at any point along the surface of the heat pipe causes the liquid at that pointto boil and enter a vapor state. When that happens, the gas picks up the latent heat ofvaporization. The gas, which then has a higher pressure, moves inside the sealed containerto a colder location where it condenses. Thus, the gas gives up the latent heat ofvaporization and moves heat from the input to the output end of the heat pipe. This processtakes place at great speed reaching over 500 MPH.
One thousand times more conductive than copper of the same weight, heat pipes conductlarge volumes of thermal energy away from the heat source. The heat pipe design is sosimple and efficient that its cooling is advantageous for maintenance retrofit as well as theOEM production application.
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.4
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
The Reliable, Cost Effective Alternative To Cool Sealed Enclosures
Modern day electronics continue to be placed in denser packaging and smaller enclosures.Consequently, electronics are being designed to handle higher temperatures. For example,many industrial logic controllers in today’s market have thermal ratings of at least 140° F.
Moisture and airborne dust, oil, dirt, and other contaminants can damage sensitive electronicequipment. Sealed enclosures protect the electronics but can lead to overheating, whichcauses reliability problems and unnecessary downtime.
The Compact Cabinet Cooler is an air-to-air heat exchanger that solves these problems bycooling and recirculating the clean air inside the cabinet. At the same time, it maintains theenclosure’s protective seal against contaminants.
Air conditioners and other below ambient type coolers are not necessary for most enclosurecooling applications. Compact Cabinet Coolers, built around the heat pipe principle, allow theuse of slightly above-ambient cooling. Cabinet Coolers provide enough cooling even whensummertime temperatures reach 120° F.
GREATER COOLING POWER FOR SEALED ELECTRONIC ENCLOSURES
The Cabinet cooler customer receives many benefits over standard A/C; i.e., smaller size andweight, one-tenth the power draw, longer life and the fact that no condensation is created insidethe cabinet. Also, one hour installation, wiring into the control circuit and easy maintenanceallow the customer to walk away from the Cabinet Cooler after it is installed - worry free. Justchange fans every four or five years.
The Cabinet Cooler’s closed loop design cools and recirculates clean air while isolating sensi-tive components from the hostile environment. Kept in inventory at the manufacturer, standardCabinet Coolers are designed for NEMA 12 type applications.
NEMA 4 and NEMA 4X models are available for operation outdoors or in corrosive environ-ments, when weather protection or external protective coatings are required. Ask our applica-tions engineers for these special protections.
Back toTOC
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 5
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
Benefits
• Minimizes down time• Cost savings• Easy to design into existing applications• Easy to retrofit• Worry free operation
Features
• Cools electronics down to slightly above outside ambient air temperature.• Maintains NEMA 12 seal. With added protection, units may be made splash proof (P unit).• Air is circulated inside cabinet to keep hot spots from forming.• Maintenance free cooling. Fans need changing only once in every four years.• Flange and neoprene gasket keep contaminants out.• Easy to install on top, door, sides, or back of cabinet. One person can cut a hole in the cabinet and bolt unit on in less than one hour.• Compact and lightweight. One person can easily carry two units under his arm.• Low power draw. 32 watts per fan results in low operating costs. No new electrical line required.• Causes no condensation like air conditioners.• Corrosion resistant. Anodized aluminum housing (standard). Additional salt water and chemical protection available (please inquire).• Allowable ambient temperature. -40°F to 160°F.• Explosion proof model available.• Oil cooling models available.• 115v 50/60 Hz or 220v 50/60 Hz fans. DC fans also available.
Noren Cabinet Coolers as compared toAir Conditioners are:
• 1/6 the SIZE• 1/7 the WEIGHT• 1/10 the ENERGYand
• 1/5 the COST• FREON FREEand work 13X longer
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.6
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
I. Determine Heat Load
� Existing Cabinets
To find heat load in the cabinet, first determine temperature rise inside the enclosure aboveoutside ambient. Then calculate cabinet surface area available for cooling.
� Measurement and Calculation
1. Seal cabinet.2. Measure T1 inside cabinet air temperature in °F. Measure T2 outside ambient airtemperature approximately 6" from cabinet.3. Calculate surface of cabinet available for free air convection, any surface 3" away from wall.Express surface area in ft2.4. Using (2) and (3) above, heat load in metal cabinet will be:
9 x AREA x (T1 - T2)P (watts)= 36
(Use 2.2 instead of 9 for plastic cabinets.)
� NewCabinets
Several methods are available to the engineer to estimate waste heat load in a newly developedcabinet. Some of the important methods are:
A. Component efficiency.
B. Incoming vs, outgoing power from a bread board unit.
C. Temperature rise and volume of air passing over equipment.
D. Manufacturer’s rating.
E. Simple test of each component.
F. Test in foam or wooden box.
For Computer aided applications assistance, call 650-322-9500 or fax, and we will help you sizeyour enclosure for cooling within two minutes over the phone.
Back toTOC
7
Know:
P = heat load (watts) from Step IA = surface area of cabinet (ft2)
∆T = allowable rise in temperature above ambient after Cabinet Cooler is installed (°F)
C = Cabinet cooler rating (found in table)
For metal cabinet: C=
Then look in table to find the Cabinet Cooler with at least that capacity (C).
For heat loads requiring more than one Cabinet Cooler to attain desired ∆T, add another
II. Select Correct Model Cabinet Cooler for Individual Applications
36P∆T
- 9A
36P∆T
- 9AC + C =
* Ratings are net values notincluding heat loss through cabinetwalls.
Compact Cabinet Cooler* Rating Table
Watts/20°C∆T(36°F∆T) Installed Unit C CC200 330 CC500 700 CC800 1100 CC1200 1500 CC1400 1500 CC2000 2200 CC250F 322 CC400F 408 CC600F 988 CC900F 1320 CC1300F 1500 CC2500F 2080
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.8
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
• How does the Compact Cabinet Cooler work?
The Compact Cabinet Cooler continuously removes heat from the enclosure’s interior in order to coolsensitive electronic components without exposing them to harsh environments. Referring to theillustration above, the interior fan draws air, which has been heated by the electronics, over the inside halfof the Compact Cabinet Cooler core. The heat pipe core absorbs the heat and transfers it to the outsidefins.
The heat it is removed by the cooler ambient air circulated by the exterior fan. The inside fan blows thecooled air toward the electronic components to cool them. This kind of system is known as an air-to-airheat exchanger.
The heat pipe core of the Compact Cabinet Cooler transfers heat very efficiently. As the core absorbsheat inside the enclosure, the working fluid inside the heat pipes vaporizes and travels to the cooler endof the core, where it gives up its latent heat of vaporization. The exterior fan draws ambient air over thecore and blows the heat away.
The now-cooled fluid condenses and flows back to the hotter end. Notice that the two air streams arekept completely separate. You cool electronic components effectively while protecting them fromenvironmental contamination.
• Example Applications
In example A, we want to cool a NEMA 12, 72" X 36" X 24" uninsulated, floor mounted, sheet metalenclosure. We measured inside cabinet temperature and found it to be 126°F. Outside the cabinet was90°F. Then, from Step 4 on page 3, we calculated heat load (P) to be 600 watts. In this application,allowable temperature rise above ambient (∆T’) is 20°F. Using C=36P/∆T’-9A, we find C=486 watts. Weselect a Cabinet Cooler from the table with a rating of at least 486 watts. Therefore, we choosethe CC500, because it is closest in performance above 486 watts.
In example B, with the same enclosure, if we decrease the allowable rise in temperature to only 10°F,then using C=36P/∆T’-9A again, the Cabinet Cooler rating must exceed 1566 watts. The CC2500F willmeet the requirement.
Choose the first Cabinet Cooler with the rating exceeding that of your heat load. Both standard Drop-inand Flush Mount models are available to accommodate individual enclosure dimensions.Noren’s computer aided application engineers can size your cabinet for cooling in minutes. Providedimensions of the enclosure, inside temperature and outside ambient temperatures (or waste heat load inwatts) for an on-the-spot quotation. Phone 650-322-9500 for information.
• SIMPLE• SMALL• POWERFUL• LONG LIFE
Back toTOC
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 9
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
Compact Drop-In Models
Features
Most compact but powerful cooling
1100 - 7500 BTU’s/hr
Energy Efficient. Light Weight.
Fans of 100 - 215 CFM each.
Extends 5 ¾” - 15” respectively into cabinet.
Maintenance Free - Just change fansevery four years.
Quiet - Low dBA
Thin Flush Mount Models
Features
Thin Flush Models
1100 - 3300 BTU´s/hr
Energy Efficient. Light Weight
Fans of 100 - 215 CFM each.
Mounts outside, flush to enclosure
Maintenance Free - Just change fansevery four years.
Quiet - Low dBA
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.10
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
High Power Flush Mount Models
Features
Most poweful Flush Models.
4500 - 7100 BTU´s/hr.
Energy Efficient. Light Weight.
Mounts outside, flush to enclosure.
Maintenace free - just change fans every four years.
Quiet - Low dBA.
Back toTOC
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 11
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
Air-to-Water Compact Cabinet Coolers
Below Ambient Cooling System
Features of Noren Water Units
Cools below ambient
3,351, 8,557,9,300 and 21,800 BTU’s/hr respectively
Maintenance free
No filters to clog. No external fans.
Energy efficient - 13, 35 and 100 Watts respectively.
Mounts on the outside, flush mount
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.12
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
CC200
Filters for the dirtiest environments
F20-A F20-P FH-20Washables Disposable Filter Housing
Specifications
Noise LeveldB(A) @ 3 ft.
*230 VAC and 12,24 and 48 VDC Fans also available.
Model EfficiencyWatts/°C
BTU/Hr@20°C∆T
Voltage*
Hz*
Amps No. of Fans& Size
16.5CC200 1100 115 50/60 2 (4”)0.4 50/53
Back toTOC
0 100 200 300 400 500 600
Total Heat Dissipated (Watts)
Insi
de
Tem
per
atu
re R
ise
Ab
ove
Am
bie
nt
(T
)
54°F
45°F
36°F
27°F
18°F
9°F
0°F
30°C
25°C
20°C
15°C
10°C
5°C
0°C
CC200 Insta
lled
Cab
inet
Onl
y
13Dimensions
Back toTOC
14
CC500, 800, 1400 & 2000
*230 VAC and 12,24 and 48 VDC Fans also available.
Specifications
Model EfficiencyWatts/°C
BTU/Hr@20°C∆T
Voltage*
Hz*
Amps No. of Fansand Size
Noise LeveldB(A) @ 3 ft.
35.2CC500 2400 115 50/60 2 (6”)0.6 52/56
55.2CC800 3800 115 50/60 2 (6”)0.6 52/5675.0CC1200 5100 115 50/60 2 (6”)0.6 52/5675.0CC1400 5100 115 50/60 3 (6”)0.9 58/62110.4CC2000 7500 115 50/60 4 (6”)1.2 58/62
Filters for the dirtiest environments
F80-AF80-A
F80-PF80-P
FH-80FH-80
F120-AF200-A
F120-PF200-P
FH-120FH-200
F200-A F200-P FH-200
Washable Disposable Filter Housing
Back toTOC
0 1000 2000 3000
Total Heat Dissipated (Watts)
Insi
de
Tem
per
atu
re R
ise
Ab
ove
Am
bie
nt
(T
)
54°F
45°F
36°F
27°F
18°F
9°F
0°F
30°C
25°C
20°C
15°C
10°C
5°C
0°CC
abin
et O
nly
CC
500
Inst
alle
d
CC
800
Inst
alle
d
CC1200
or 1
400
Insta
lled
CC2000 Insta
lled
15
Dimensions in inchesModel A BCC500 7 1/2 7 1/2CC800 7 1/2 7 1/2CC1200 11 11CC1400 15 7 1/2CC2000 15 15
DimensionsBack to
TOC
Com
pact Cabinet C
oolersNOREN ProductsInc.16
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
0 100 200 300 400 500 600
Total Heat Dissipated (Watts)
Insi
de
Tem
per
atu
re R
ise
Ab
ove
Am
bie
nt
(
T)
54°F
45°F
36°F
27°F
18°F
9°F
0°F
30°C
25°C
20°C
15°C
10°C
5°C
0°C
*230 VAC and 12,24 and 48 VDC Fans also available.
Specifications
Model EffiencyWatts/°C
BTU/Hr@20°C∆T
Voltage*
Hz*
Amps No. of Fans& Size
NoisedB(A) @ 3 ft.
16.1CC250F 1100 115 50/60 2 (4”)0.4 50/53
CC250F
Filters for dirtiest environments
F25-A F25-P N/AWashable Disposable Filter Housings
Cab
inet
Onl
y
CC250F Insta
lled
Back toTOC
17Back to
TOCDimensiones
Com
pact Cabinet C
oolersNOREN ProductsInc.18
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
0 500 1000 1500
Total Heat Dissipated (Watts)
Insi
de
Tem
per
atu
re R
ise
Ab
ove
Am
bie
nt
(T
)
54°F
45°F
36°F
27°F
18°F
9°F
0°F
30°C
25°C
20°C
15°C
10°C
5°C
0°C
CC400F and CC600F
Cab
inet
Onl
yC
C40
0F In
stal
led
CC600F Insta
lled
Filters for the dirtiest environmentsWashables Disposables Filter Housing
F40-AF60-A
F40-PF60-P
FH-40FH-60
ModelCC400FCC600F
Especificaciones
Model EfficiencyWatts/°C
BTU/Hr@20°C∆T
Voltage*
Hz*
Amps No. of Fans& Size
Noise LeveldB(A) @ 3 ft.
20.4CC400F 1400 115 50/60 2 (4”)0.4 50/5349.2CC600F 3300 115 50/60 2 (6”)0.6 52/56
*230 VAC and 12,24 and 48 VDC Fans also available.
Back toTOC
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 19
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
CC400F Dimensions
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.20
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
CC600F Dimensions
Back toTOC
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 21
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
0 1000 2000 3000
Total Heat Dissipated (Watts)
Insi
de
Tem
per
atu
re R
ise
Ab
ove
Am
bie
nt
(T
)
54°F
45°F
36°F
27°F
18°F
9°F
0°F
30°C
25°C
20°C
15°C
10°C
5°C
0°C
*230 VAC and 12,24 and 48 VDC Fans also available.
Specifications
Model EfficiencyWatts/°C
BTU/Hr@20°C∆T
Voltage*
Hz*
Amps No. of Fans& Size
Noise LeveldB(A) @ 3 ft.
66CC900F 4500 115 50/60 2 (6”)0.6 52/56
75CC1300F 5100 115 50/60 2 (6”)0.6 52/56104CC2500F 7500 115 50/60 4 (6”)1.2 58/62
Filters for the dirtiest environmentsWashables Disposables Filter Housing
F90-AF130-AF250-A
F90-PF130-PF250-P
FH-250FH-250FH-250
ModelCC900FCC1300FCC2500F
Cab
inet
Onl
y
CC900F
Inst
alle
d
CC1300
F Insta
lled
CC2500F Insta
lled
CC900F, 1300F & 2500F
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.22
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
CC900F Dimensions
Back toTOC
23CC1300F and CC2500FDimensions
Dimensions (in inches)
2229
1114.5
ModelCC1300FCC2500F
1926
811.5
1013.5
A B C D E
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.24
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
Below Ambient Coolers
Features of Noren Water Units
• Cools below ambient• 3,351, 8,557, 9,300 and 21800 BTU’s respectively• Maintenance free• No filters to clog• No external fans• Energy efficient - 13, 35 and 100 Watts respectively• Mounts on outside, flush mount enclosure
Requirements
One gallon per minute of circulating water isrequired, from virtually any source. If you havean already low pressure supply, we can help youwork out a simple way to give our cooler the oneGPM it requires without reducing the flow ofother applications.
Condensation
Unlike A/C solutions that create condensation,our water units do not use any refrigerants.Because our units use water, the condensationconcerns are greatly reduced and oftencompletely eliminated.
Safety Factor
Noren air-to-water units are safe. We also manufacture DRY Water solutions. Askour applications engineer for more information.
Back toTOC
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 25
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
0 1000 2000 3000
Total Heat Dissipated (Watts)
Insi
de
Tem
per
atu
re R
ise
Ab
ove
Am
ibie
nt
(T
)108°F
90°F
72°F
54°F
36°F
18°F
0°F
60°C
50°C
40°C
30°C
20°C
10°C
0°C
Cab
inet
Onl
yCC20
60 In
stal
led
Typical performance with 1 GPM of cooling water at20°C and ambient air at 40°C when mounted to anuninsulated 72"X36"X24" cabinet.
*230 VAC and 12,24 and 48 VDC Fans also available.
Specifications
Model EfficiencyWatts/°C
BTU/Hr@40°C∆T
Voltage*
Hz*
Amps No. of Fans& Size
Noise LeveldB(A) @ 3 ft.
24.5CC2060 3,351 115 50/60 1 (4”)0.2 Less than 50
Air-to-Water UnitModel CC2060
Back toTOC
26
CC2060Dimensions
Back toTOC
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 27
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
CC2060 Dimensions
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.28
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
0 1000 2000 3000 4000 5000 6000
Total Heat Dissipated (Watts)
Insi
de
Tem
per
atu
re R
ise
Ab
ove
Am
ibie
nt
(T
)
108°F
90°F
72°F
54°F
36°F
18°F
0°F
60°C
50°C
40°C
30°C
20°C
10°C
0°C
Typical performance with 1 GPM of cooling water at20°C and ambient air at 40°C when mounted to anuninsulated 72"X36"X24" cabinet.
*230 VAC and 12,24 and 48 VDC Fans also available.
Especificaciones
Model EfficiencyWatts/°C
BTU/Hr@40°C∆T
Voltage*
Hz*
Amps No. of Fans& Size
Noise LeveldB(A) @ 3 ft.
68.8CC3060 9,300 115 50/60 1 (6”)0.3 Less than 50
Air-to-Water UnitModel Cc3060
Cab
inet
Onl
y
CC3060
Insta
lled
Back toTOC
29CC3060 Dimensions
Back toTOC
7 x 7.75
Com
pact Cabinet C
oolersNOREN ProductsInc.30
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
0 1000 2000 3000
Total Heat Dissipated (Watts)
Insi
de
Tem
per
atu
re R
ise
Ab
ove
Am
ibie
nt
(T
)
108°F
90°F
72°F
54°F
36°F
18°F
0°F
60°C
50°C
40°C
30°C
20°C
10°C
0°C
*230 VAC and 12,24 and 48 VDC Fans also available.
Specifications
Model EfficiencyWatts/°C
BTU/Hr@40°C∆T
Voltage*
Hz*
Amps No. of Fans& Size
Noise LeveldB(A) @ 3 ft.
62.7CC3260 8,557 115 50/60 1 (6”)0.3 Less than 50
Air-to-Water UnitModel CC3260
Typical performance with 1 GPM of cooling water at20°C and ambient air at 40°C when mounted to anuninsulated 72"X36"X24" cabinet.
CC3260 InstalledCab
inet
Onl
y
Back toTOC
31CC3260 Dimensions Back to
TOC
32CC3260 DimensionsBack to
TOC
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 33
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
0 3000 6000 9000
Total Heat Dissipated (Watts)
Insi
de
Tem
per
atu
re R
ise
Ab
ove
Am
ibie
nt
(T
)
108°F
90°F
72°F
54°F
36°F
18°F
0°F
60°C
50°C
40°C
30°C
20°C
10°C
0°C
Air-to-Water UnitModel CC6360
*230 VAC and 12,24 and 48 VDC Fans also available.
Specifications
Model EfficiencyWatts/°C
BTU/Hr@40°C∆T
Voltage*
Hz*
Amps No. of Fans& Size
Noise LeveldB(A) @ 3 ft.
159.7CC6360 21,800 115 50/60 3 (6”)0.9 Less than 50
Cab
inet
Onl
y
CC6360 Insta
lled
Typical performance with 1 GPM of cooling water at20°C and ambient air at 40°C when mounted to anuninsulated 72"X36"X24" cabinet.
Back toTOC
34 CC6360 Dimensions
Back toTOC
35CC6360 Dimensions Back to
TOC
Hazardous Location Applications
Compact Cabinet Coolers™ for a wide variety of Hazardous Locations.
Typical applications
Class I
● Petroleum refineries● Petrochemical companies● Dry cleaning plants● Applications near paint or plastic
spraying● Aircraft hangers, fuel servicing● Utility gas plants
Class II
● Grain elevators, flour, feedmills
● Magnesium, aluminumpowderprocessing
● Chemical, metallurgicalprocesses
● Manufacturing of plastics,medicines, fireworks
● Starch or candymanufacturing
● Coal or carbon handlingprocessing operations
New XP FANS
New XP fans now available for Class 1, Div 2 Group A,B,C and D are available for sale as astand alone product or with the following heat exchangers in purged or non-purgedapplications:
Purged and non-purged applications:
AIR-to-AIRCC500P, CC800P, CC1200P, CC1400P, CC2000P, CC600FP, CC900FP, CC1300FP,CC2500FP CC4000FP See Use Table Safety: Important Notice
AIR-to-WATERCC3060P, CC3260P CC6360P See Use Table Safety: Important Notice
Purged applications only use:
AIR-to-WATER CC2060P See Use Table Safety: Important Notice
AIR-to-AIR CC851-XP, CC1251-XP See Use Table Safety: Important Notice
Cabinet Cooler Use in Hazardous Locations
DIVISION 1
(Hazard is normally present)
DIVISION 2
(Hazard is not normally present)
PurgeType →
X purge Y purge Z purge None (no purge)
CabinetCooler Type * →
XP A/W XP
+
IHL
A/W
+
IHL
XP
A/W
HL
XP
+
IHL
A/W
+
IHL
HL2
CLASS 1
GROUP A:Acetylene
No 2060P3060P3260P6360P
No 3060P-IHL,
3260P-IHL,
6360P-IHL
No 2060P3060P3260P6360P
CC500,800,
1200,1400,
& 2000P-HL.
CC600F,900F,
1300F,2500F,
&4000FP-
HL
No 3060P-IHL,
3260P-IHL,
6360P-IHL
CC500,800,
1200,1400,
& 2000P-HL2.
CC600F,900F,
1300F,2500F,
& 4000FP-HL2
GROUP B:Hydrogen,ManufacturedGas, etc.
No** 2060P3060P3260P6360P
No** 3060P-IHL,
3260P-IHL,
6360P-IHL
No** 2060P3060P3260P6360P
CC500,800,
1200,1400,
& 2000P-HL.
CC600F,900F,
1300F,2500F,
&4000FP-
HL
No** 3060P-IHL,
3260P-IHL,
6360P-IHL
CC500,800,
1200,1400,
& 2000P-HL2.
CC600F,900F,
1300F,2500F,
& 4000FP-HL2
GROUP C:Diethyl ether,ethylene,cyclopropane,etc.
851XP
1251XP
2060P3060P3260P6360P
851XP-IHL
1251XP-IHL
3060P-IHL,
3260P-IHL,
6360P-IHL
851XP
1251XP
2060P3060P3260P6360P
CC500,800,
1200,1400,
& 2000P-HL.
CC600F,900F,
1300F,2500F,
&4000FP-
HL
851XP-IHL
1251XP-IHL
3060P-IHL,
3260P-IHL,
6360P-IHL
CC500,800,
1200,1400,
& 2000P-HL2.
CC600F,900F,
1300F,2500F,
& 4000FP-HL2
GROUP D:Gasoline,hexane,butane,naphtha,propane,toluene,isoprene,alcohol,acetone,lacquersolvent,natural gas,etc.
851XP
1251XP
2060P3060P3260P6360P
851XP-IHL
1251XP-IHL
3060P-IHL,
3260P-IHL,
6360P-IHL
851XP
1251XP
2060P3060P3260P6360P
CC500,800,
1200,1400,
& 2000P-HL.
CC600F,900F,
1300F,2500F,
&4000FP-
HL
851XP-IHL
1251XP-IHL
3060P-IHL,
3260P-IHL,
6360P-IHL
CC500,800,
1200,1400,
& 2000P-HL2.
CC600F,900F,
1300F,2500F,
& 4000FP-HL2
CLASS 2
GROUP E:Flammablemetalpowders, etc.
(S)
851XP
1251XP
2060P3060P3260P6360P
No No (S)
851XP
1251XP
2060P3060P3260P6360P
No No No No
GROUP F:
Carbon black,coal dust,coke dust, etc.
851XP
1251XP
2060P3060P3260P6360P
No No 851XP
1251XP
2060P3060P3260P6360P
No No No No
GROUP G:
Flour, starch,grain dust,etc.
851XP
1251XP
2060P3060P3260P6360P
No No 851XP
1251XP
2060P3060P3260P6360P
No No No No
NOTES:
All Cabinet Cooler models for Hazardous Location duty are pressure tested (P suffix) toassure a liquid tight and airtight seal.
Type X purging changes the interior hazard class of the enclosure from Div. 1 to non-hazardous.
Type Y purging changes the interior hazard class of the enclosure from Div. 1 to Div. 2.
Type Z purging changes the interior hazard class of the enclosure from Div. 2 to non-hazardous.
*Cabinet Cooler Types:
XP: Air to Air Unit with external Explosion Proof blower (internal fan is standard duty).Models: CC851XP, CC1251XP. Voltage: 115 or 230 VAC.
A/W: Air to Water unit with no external electrical or moving parts (internal fan is standardduty). Models: CC2060P, CC3060P, CC3260P, CC6360P. Voltage: 115 or 230 VAC, 12, 24,or 48 VDC.
IHL: Air to Water or XP Unit with Internal Hazardous Location fan(s): Air to Water models:CC3060P-IHL, CC3260P-IHL, and CC6360P-IHL. XP models include CC851XP-IHL,CC1251XP-IHL. Voltage: 115 VAC.
HL: Air to Air Unit with external Hazardous Location Fan(s). Models: CC500P-HL, CC800P-HL, CC1200P-HL, CC1400P-HL, CC2000P-HL, CC600FP-HL, CC900FP-HL, CC1300FP-HL, CC2500FP-HL, CC4000FP-HL. Voltage: 115 VAC.
HL2: Air to Air Unit with external and internal Hazardous Location Fan(s). Models:CC500P-HL2, CC800P-HL2, CC1200P-HL2, CC1400P-HL2, CC2000P-HL2, CC600FP-HL2, CC900FP-HL2, CC1300FP-HL2, CC2500FP-HL2, CC4000FP-HL2. Voltage: 115 VAC.
No = Not usable
** = Explosion Proof Blowers for this environment may be available in the future.
(S) = Special order
---------------------------------------------------------------------------------------------------------
SAFETY: IMPORTANT NOTICE
USING NOREN “XP”, “HL”, “HL2”, “-IHL”, AND “AIR TO WATER” CABINETCOOLERSTM IN HAZARDOUS LOCATIONS
1. Only use HL2 Cabinet CoolersTM without purged / pressurized systems if an internalDiv 2 hazard condition is allowable. All fans are rated for Division 2 use.
2. Only use “Air to Water type IHL” Cabinet CoolersTM without purged / pressurizedsystems if an internal Div 2 hazard condition is allowable. The Internal Hazardous Locationfan(s) are rated for Division 2 use.
3. Always use standard Noren “HL” Cabinet CoolersTM in conjunction with type Z purged/ pressurized systems. The internal fan is not rated for hazardous use.
4. Noren “XP type IHL” and “Air to Water type IHL” Cabinet CoolersTM have InternalHazardous Location fans rated for Division 2 use. This may permit the use of a Type Ypurging system in Division 1 Locations if an internal Division 2 hazard condition isallowable.
5. Always use standard Noren “XP” or standard “Air to Water” Cabinet CoolerTM inconjunction with type X or type Z purged / pressurized systems.
6. Never use standard Noren “XP”, “HL”, or “Air to Water” Cabinet CoolerTM with type Ypurged / pressurized systems. The internal fan is not rated for Div 2 use.
7. Only use Noren “XP” or “HL” Cabinet CoolersTM in locations for which the external XP(eXplosion Proof) or HL (Hazardous Location) motor is designed.
8. Read the hazard classification on nameplate of the motor(s) you receive to assure theyare appropriate for your application.
9. Noren “Air to Water” Cabinet CoolerTM can be used in some hazardous locations whereNoren XP or HL units cannot. Depending on which internal fan is used and your purgingsystem, this may include Class 1, Div 1, Groups A & B (acetylene, hydrogen, manufactured
gas). “Air to Water” Cabinet CoolesTM have no external electrical or moving parts.
10. Noren Cabinet CoolersTM will not maintain the explosion proof integrity of NEMA 7type enclosures.
11. It is the customer’s responsibility to know what protection their purged / pressurized
system provides. Install the Noren Cabinet CoolerTM correctly and safely in accordance withthe National Electrical Code (N.E.C.)
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 37
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
Models CC851XP and CC1251-XPExplosion Proof Units
Especificaciones
Model
CC850-XPCC1250-XP
EfficiencyWatts/°C
BTU/Hr@20°C∆T
Voltage*
Hz*
Amps Weight Dimensions extendinginto cabinet
60 3700 115 50/60 50 lbs.5 7 1/2
80 5000 115 50/60 51 lbs.5 11
0 500 1000 1500 2000 2500 3000
Total Heat Dissipated (Watts)
Insi
de
Tem
per
atu
re R
ise
Ab
ove
Am
bie
nt
(T
)
54°F
45°F
36°F
27°F
18°F
9°F
0°F
30°C
25°C
20°C
15°C
10°C
5°C
0°CCC85
1
-XP
Inst
alle
d
Cab
inet
Onl
y
CC125
1
-XP In
stalle
d
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.38
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
CC850 and CC1250-XP Dimensions
Back toTOC
39
CC851 and CC1251-XP Dimensions
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.40
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
������ �����
�������
���� �� �� ������������� ����������������� ��� ��� �������������� ������ � � ������!
������
���"��#
������#
���$��#�
�����#�
�����#
$��#
���%�&'�!�(��#����%)��*���+�, ���+������-�� ��
)
$�$#���%
.����%
�)���%%"�
%����.%����%
%�
�.���%
�
����%��.
����
New ModelsNoren’s Largest Standard Compact Cabinet Cooler
Customer demand drives the Noren engineering to develop the CC4000. Still a compact model,it removes twice the heat as the CC2500F. Larger model are in development.
������������
����/0��� � ��1+2��3
���456+2)%7 ∆5
�����8�
9*�
����
��:!�;�9 <=
��>�?� �;��7@�A6�
�� �3
:))).++ )!))% )))B�� $�� )#�)$ #!� @C#A� %#��$ !,��.
� ��,�� �>������:+&8�.���.%B%����+�8)�%
stnemnorivnetseitridehtrofsretliF
ledoM elbahsaW elbasopsiD gnisuoHretliF
F0004CC redrOlaicepS
Back toTOC
Com
pact
Cab
inet
Coo
lers
NOREN ProductsInc. 41
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
#!"$�
�"�
�!))/��!
�!�
%��/ � ���
.!.$�
�!$)&��
%!))/ �!
%!���&��.!��
%%!%$
%)!�%
D��� ��6��
%!�%
)
)!$)) "!#��)!��
E���� E����
+���� �
+���� �
/��� ������
"��%A)!%�@�(.�/��� ���*���
������
Remote Surface Mount
This special model was developed for a customer that is not able to mount a cabinetcooler on the enclosure. Especially thin cabinets or small cabinets are perfectcandidates for the CC450R.
������������
����/0��� � ��1+2��3
���456+2)%7 ∆5
�����8�
9*�
����
��:!�;�9 <=
��>�?� �;��7@�A6�
�� �3
E)$.++ )!)% )).� $�� )#�)$ .! @C#A� �$�)$ !,�$�
� ��,�� �>������:+&8�.���.%B%����+�8)�%
stnemnorivnetseitridehtrofsretliF
ledoM elbahsaW elbasopsiD gnisuoHretliF
R054CC 54F A54F P54F
Back toTOC
Com
pact Cabinet C
oolersNOREN ProductsInc.42
Noren Products, Inc.1010 O'Brien Drive, Menlo Park, CA 94025
(650)322-9500 Fax: (650)324-1348http://www.norenproducts.com
CALL, FAX OR EMAIL US TO COOL YOURSEALED ELECTRONIC ENCLOSURES
THESE ARE SOME OF THE AVAILABLE FEATURES:
- NEMA 4, NEMA 4X, NEMA 12 - Stainless Steel- Explosion Proof - Interior Mount- UL Recognized units are Available in Nema 12
!!!OBTAIN A FAST COOLING SOLUTION FOR YOUR CABINET!!!WE MANUFACTURE SPECIAL UNITS TO SOLVE CUSTOM APPLICATIONS
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Call, Email or send us a fax. We will help you size your enclosure for cooling within two minutesover the phone.
DATE: _______________________NAME: _____________________________________________COMPANY: _______________________________________________________________ADDRESS: ______________________________________________________________CITY: ________________________________ STATE: _________________________ZIP CODE _______________PHONE NUMBER: ____________________________________FAX NUMBER ___________________________________________EMAIL ADDRESS_________________________________________
SIZE OF CABINET:
HEIGHT: _______ WIDTH __________ LENGTH __________
*INTERIOR TEMPERATURE INTERIOR OF CABINET ____ ° F
HEAT LOAD ________BTU/HR.
*AMBIENT TEMPERATURE OUTSIDE OF CABINET ____° F
OR _________ WATTS(*) Taken simultaneously
For Air-to-Water Applications: Water Temperature _________°F
Email us at: [email protected]
Back toTOC