    1/3552 Merlin Gerin

    csource changeover cswitch-disconnectors

    cprotection ofmotor starters

    cprotection of low-voltagedistribution networksv installation in power distributionswitchboardsv installation on symmetrical rails

    Compact: presentation

    an international referenceWith the Compact system, Merlin Gerin

    is today Europes leading manufacturer ofmoulded-case circuit breakers.The Compact range covers all ratings from15 to 1250 A:c Compact NS, from 15 to 630 A;c Compact C, from 800 to 1250 A.

    A number of versions:c 1, 2, 3 or 4 poles;c fixed, plug-in or withdrawable;c a comprehensive range of trip units.Circuit breakers designed for allapplications:c 1000 V AC models;c models for DC systems;c source changeover systems.

    Compact NS circuit breaker

    1 terminals2 cover3 toggle and position indicator4 push-to-trip button

    5 trip unit6 test kit connector

    1

    2

    5

    6

    053100

    3

    4

    N R

    push

    totr ip

    push

    totrip

    pushtotrip

    pushtotrip

    pushtotrip

    pushto

    trip

    pushtotrip

    push

    totrip

    push

    totrip

    applicationsE26988

    E21272

    E32454

    E20999

    pushtotr ip

    E44356

    ccccc protection of incoming devicesof industrial control panel

    push

    totr ip

    MG

    ccccc earth fault protection

    E44357

  • 7/29/2019 Compact 80-1250

    2/355Merlin Gerin 3

    rated current (A)

    ultimate breaking capacity Icu (kA rms)

    at 380/415 V (IEC 947-2)

    ratings and breaking

    capacitiesThe rating plates on the front face of thecircuit breakers indicate the breakingcapacity:N: normal

    H: highL: very high.

    compact

    NS 250 NUi750V Uimp8kVUe(V)

    Icu(kA)

    220/240

    380/415

    440

    500

    525

    660/690

    250

    85

    36

    35

    30

    22

    8

    50

    cat A

    Ics = 100 % Icu

    IEC 947-2UTE VDE BS CEI UNE NEMA

    compact

    NS 250 HUi750V Uimp8kVUe(V)

    Icu(kA)

    220/240

    380/415

    440

    500

    525

    660/690

    250

    100

    70

    65

    50

    35

    10

    85

    cat A

    Ics = 100 % Icu

    IEC 947-2UTE VDE BS CEI UNE NEMA

    compact

    NS 250 LUi750V Uimp8kV

    Ue(V)

    Icu(kA)

    220/240

    380/415

    440

    500

    525

    660/690

    250

    150

    150

    130

    70

    50

    20

    100

    cat A

    Ics = 100 % Icu

    IEC 947-2UTE VDE BS CEI UNE NEMA

    pushtotr ip

    pushtotrip

    pushtotrip

    pushtotrip

    pushtotrip

    pushtotrip

    discrimination Even when equipped with standard tripunits, Compact circuit breakers offer the bestguarantee of electrical power availabilitywhen faults occur. In most cases,discrimination between protective devices

    is ensured for all types of faults (overloads,low and high short-circuit currents).

    E27836

    E27837

    E27838

    E3245

    6

    E22051

  • 7/29/2019 Compact 80-1250

    3/3554 Merlin Gerin

    E2460

    3

    Compact: presentation

    modular system A wider range of add-on modules makes itpossible to adapt the Compact system to amaximum number of configurations.

    Trip units, auxiliaries and installation andconnection accessories are the same for allmodels within each of following ranges:c Compact NS80 and NSA125/160c Compact NS100 to NS250,c Compact NS400 to NS630,

    c Compact C801 to C1251.The common modules for Compact NS100to NS250 circuit breakers and switch-

    disconnectors are shown opposite.The same principle applies to CompactNS400 to NS630 and Compact C801 toC1251 circuit breakers.Fewer catalogue numbers means immediateavailability of parts for all solutions.

    2

    1

    7 8

    12

    15

    16

    14

    10

    11

    2

    3

    6

    4

    9

    13

    5

    System of add-on modules for Compact NS100N/H/L to NS250N/H/L.

    1. Breaking unit.2. Trip unit.3. Vigi earth-fault protection module.

    4. Insulation monitoring module.5. Voltage presence indicator.6. Ammeter.

    7. Voltage releases MN or MX.8. Multifunction auxiliary switch.9. Direct rotary handle.10. Extended rotary handle.11. Motor mechanism.12. Plug-in base.

    13. Connection of plug-in andwithdrawable configuration auxiliary

    circuits.14. Connection accessories.15. Short terminal shields.16. Long terminal shields.

  • 7/29/2019 Compact 80-1250

    4/355Merlin Gerin 5

    simplified installation Compact circuit breakers make it possibleto standardise switchboards, meaning faster

    installation and fewer errors.

    All type L Compact circuit breakers (150 kA)are housed in the same frame as the type Nand type H models with the same ratings.

    Compact circuit breakers can be easilyinstalled side-by-side in a minimum amount

    of space.

    4 sizes from 80 to 1250 A

    100 to 250 A 400 to 630 A 800 to 1250 ACompact

    Connection parts for Compact NS.

    connection Numerous connection possibilities, includingfront and rear connections for bare cables,cable lugs or bars, as well as plug-in orwithdrawable versions, are available using

    a full set of accessories that can be rapidlyadded to the circuit breaker.

    plug-in and withdrawable

    versions

    Withdrawable Compact NS250N on a chassis.

    Plug-in and withdrawable versions for:c fast removal or insertion of the circuitbreaker without exposure to live parts;c standby outgoing circuits ready for wiring

    and circuit breaker installation at a laterdate;c for visible break disconnection.

    prefabricated

    trunking

    Compact NS circuit breakers can be

    installed in junction boxes of theTelemecanique Canalis range ofprefabricated trunking (see correspondingcatalogue).

    80 A

    046751

    045345

    053100

    046893

    041650

    042788

    E32455

  • 7/29/2019 Compact 80-1250

    5/3556 Merlin Gerin

    Compact: presentation

    interchangeable

    trip units

    Each Compact device provides differenttypes of protection depending on theassociated trip unit:

    c standard protection,c protection of networks supplied bygenerators,c protection of long cables,c protection of DC networks,c protection of motor-starters,c service connection circuit breaker (forspecial subscriber contracts).

    Electronic trip unit STR22SE.

    On Compact NS100 to NS250 circuit

    breakers, the thermal-magnetic andelectronic trip units are interchangeable andmay be rapidly fitted to the circuit breakers.

    It is therefore easy to change the protection

    of a given circuit following a modification inan installation.

    On Compact NS400 and NS630 circuitbreakers, the electronic trip units areinterchangeable plug-in modules.Trip unit STR53UE offers a large number ofprotection settings.

    Compact NS100... 630

    Thermal-magnetic trip unit TM.

    Compact NS250H.

    Compact C801... 1251

    Compact C1251H circuit breaker.

    Electronic trip units allow perfect adaptationof the protection to each circuit in the

    electrical distribution network, and, at thesame time, simplify the selection, installationand operation of the devices:c wider range of settings, so that a singletrip unit can provide several types ofprotection,c easier checking during assembly or onsite,c new functions offered by the trip unit, such

    as load monitoring and local indications.

    Electronic trip unit STR35SE.

    041625

    041638

    041641

    046893

    051

    166

  • 7/29/2019 Compact 80-1250

    6/355Merlin Gerin 7

    other functions

    indicationand measurement

    Compact NS250L with ammeter module.

    Four indication and measurement functionsmay be mounted directly on Compact NScircuit breakers:

    c voltage presence indicator for the circuitbreaker terminals, particularly useful onswitchboard incoming units,c display of current readings,c remote transmission of current readings,c earth fault indication for earth fault

    detection on TNS systems or assistance inlocating earth faults on TT systems.

    options for trip unitSTR53UE

    On Compact NS400/630 circuit breakers,trip unit STR53UE offers:c specific indications for different faults(overloads, short-circuits, etc.),... and a number of optional functions:c built-in ammeter;c earth-fault protection;c zone selective interlocking;c transmission of all information concerning

    circuit-breaker operation to a monitoring,control or automated distribution centre, viaDialpact modules (see below).

    Digipact: electrical installation management Compact circuit breakers incorporate or maybe equipped with Digipact communications

    modules. From a remote location (standardpersonal computer PC or programmablelogic controller PLC), the operator can:

    c display the status of circuit breakers;c control the circuit breakers;c access information provided by theelectronic trip units.It is also possible to check the status of theUA150 automatic source-changeover

    controllers.For more information: see Digipact

    catalogue.

    0452

    12

    053102

    Compact NS trip unit STR53UE.

    E37615

    management

    Modbus / JBus DC150 data concentrator

    internal Digipact bus

    PM150power meter

    CLS150indicationand localcontrolmodule

    circuit breaker orother power-circuitactuator

    UA150 automaticsource-changeovercontroller

    Multi 9 controldevice andATB 1Sinterface

  • 7/29/2019 Compact 80-1250

    7/3558 Merlin Gerin

    Compact: presentation

    common accessories

    electrical auxiliaries

    Auxiliary switch and MX release for Compact NS.

    motor mechanism

    Compact NS250N with motor mechanism.

    A motor mechanism can be fitted to the frontface of Compact NS100 to C1251 circuitbreakers. Remote control of the opening,closing and reset functions is then possiblevia 2 or 3 impulse or maintained signals.If necessary, the circuit breakers can still beoperated locally via the controls on the front

    face.The motor mechanism modules for each

    range have a common size.The motor mechanism module forCompact NS is also available incommunicating version (see Digipact

    catalogue).

    Vigi earth-fault protectionmodule

    Vigi modules can be added to Compact NS

    circuit breakers to provide earth-faultprotection. The Vigi modules fit directly onthe circuit breaker terminals.

    The addition of a Vigi module has no effecton the other performance characteristics ofthe circuit breaker.

    Compact NS250H with Vigi earth-fault protection module.

    c auxiliary switches:

    v Compact NS: just one model, the same forall Compact NS80 to NS630 and NSA125/160 circuit breakers, provides four differentfunctions (OF, SD, SDE and SDV)depending on where it is fitted in the circuitbreaker,v Compact C: two models, the same for allCompact C801 to C1251 circuit breakers,provide remote indications of circuit breaker

    status and electrical faults (e.g. 30F + 1SD),c the MN or MX voltage releases arecommon for all models within each of

    following ranges:v NS80 and NSA125/160,v NS100 to NS630,v

    C801 to C1251.c auxiliary switches for Compact NS arealso available in communicating version and

    can be installed in place of the standardswitches (see Digipact catalogue).

    0

    44313

    0

    44314

    047313

    044333

  • 7/29/2019 Compact 80-1250

    8/3559

    LV circuit breakersand switch-disconnectors

    Compact80 to 1250 A

    functions

    and characteristics

    page

    Compact range and its applications 10

    general characteristics 14

    circuit breakers for:

    low-voltage distribution 16circuit breaker C1251N 1000 V 36earth fault protection 38

    motor protection 40industrial control panels 50

    switch-disconnectors 54

    installation 58

    connection 60auxiliaries 64

    accessories 72

    source changeover systems 76

  • 7/29/2019 Compact 80-1250

    9/35510 Merlin Gerin

    circuit breakers for protection of low voltage distribution networks page 16

    Compact: functions and characteristics

    applications

    motor rating 0.37 37 1.1 220 110250 160670

    power (kW)

    Compact NS80 NS100/160/250 NS400/630 C801/C1001/C1251

    breaking N 25/36 50

    capacity (kA rms) H 70 70 70 70

    380/415 V L 150 150

    circuit breakers for motor protection page 40

    rated 12.5 12.5 12.5 60 250 320 400 500

    current (A) 100 160 250 400 630 800 1000 1250

    Compact NS100 NS160 NS250 NS400 NS630 C801 C1001 C1251

    Vigicompact

    breaking N 25 36 36 45 45 50 50 50

    capacity (kA rms) H 70 70 70 70 70 70 70 70

    380/415 V L 150 150 150 150 150 150 150

    0467

    51

    041624

    045198

    051162

    053100

    045345

    046893

    E20999

    E26988

    for AC networks up to 1000 V : page 36

    Compact NS400 N 1000 VCompact C1251N 1000 V

    The interchangeable thermal-magnetic or electronic trip units of the Compact NS are designedto protect the following types of electrical installations:

    c Standard installation (supplied by a transformer);

    c Installations supplied by a generator;

    c DC installations;

    c Long cable lengths for IT and TN;

    c Motors and motor starters.

    protection page 22

    E43842

    E43843

    pushtotrip

    pushtotrip

    pushtotrip

    pushto

    tr ip

    G

    push

    to

    tr ip

    +

    push

    totr ip

  • 7/29/2019 Compact 80-1250

    10/355

    Merlin Gerin 11

    rated 12.5 100 12.5 12.5 ... 12.5 ... 60... 250...current (A) 100 160 250 400 630

    Compact NSC100 NS100 NS160 NS250 NS400 NS630(CEI947-2 / UL508 / CSA22-2)breaking capacity N 18 25 35 35 42 42

    (kA rms) 380/480 V H 65 65 65 65 65rated 15-100 15-250 60-600current (A)

    Compact NSE100 NSF150 NSF250 NSJ400 NSJ600

    (UL 489 / CEI947-2 / CSA22-2)

    breaking capacity N 18 35 35 35 35(kA rms) 480 V H 65 65 65 65

    L 100 100

    circuit breakers for protection of industrial control panels page 50

    E44356

    refe

    rtoded

    icate

    dca

    talog

    054556

    041624

    045198

    054561

    054569

    054580

    rated 100630

    current (A)

    Compact NSC100 N NS100 N/H/L NS400 N/H/L

    Vigicompact NS160 N/H/L NS630 N/H/L

    NS250 N/H/L

    circuit breakers and relays for earth fault protection page 38

    Vigirex earth fault relays separate toroids

    circuit breakers all Compact NS equiped by a voltage release (MN or MX)associated

    refe

    rto

    dedic

    ated

    cata

    log

    E44357

    044333

    044322 0

    51352

    054556

    push

    totrip

    pushtotrip

    MG

  • 7/29/2019 Compact 80-1250

    11/35512Merlin Gerin

    source-changeover page 76

    E3245

    4

    rated 12.5 12.5 12.5 160 250 320 400 500current (A) 100 160 250 400 630 800 1000 1250

    manual source- by toggle

    changeover by rotary handle

    system by keylock

    automatic

    source-

    changeover

    systems

    Compact NS100 to NS250 NS400 to NS630 C801 to C1251

    Al l NS100 to NS250 type Al l NS400 to NS630 type Al l C801 to C1251 type N/H/NI

    N/H/L/NA fi xed or pl ug -i n N/H/L/NA fi xed or pl ug- in and C801 to C1251 type L

    devices. devices. fixed devices.

    Compact: functions and characteristics

    applications(cont.)

    053060

    053042

    053058

    N R

    pushtotr ip

    pushtot r ip

  • 7/29/2019 Compact 80-1250

    12/355Merlin Gerin 13

    E21272

    rated 406380 100125...160 250400...630 1000...1600... 2500current (A)

    Interpact INS40 INS100 IN250 IN1000

    INS63 INS125 IN400 IN1600

    INS80 INS160 IN630 IN2500

    rated 50...63 125...160 250...400 630current (A)

    Fupact UC50 UC125 UD250T UD630T

    switches UD63 UD125 UD400T

    UD160

    switch-disconnectors page 56

    rated 100160250 400630 8001250current (A)

    Compact NSC100NA NS400NA C801NI

    Vigicompact NS100NA NS630NA C1251NI

    NS160NA

    NS250NA

    refer

    toded

    icated

    catal

    og

    refer

    tode

    dicate

    dcat

    alog

    035053

    052168

    052164

    86081

    86083

    86087

    084642

    pushtotrip

    pushtotrip

    pushtotrip

  • 7/29/2019 Compact 80-1250

    13/35514Merlin Gerin

    Compact: functions and characteristics

    general characteristics

    tropicalisationCompact and derived circuit breakers

    comply with NF C 63-100 standard level 2conditions (95% relative humidity at 45C or80% at 55C, hot and humid climateconditions). They also comply with thefollowing standards:c IEC 68-2-30 damp heat;c IEC 68-2-2 dry heat;c IEC 68-2-11 salt spray;c IEC 68-2-1 low temperatures.

    environmental protectionCompact circuit breakers takeinto account current concerns forenvironmental protection. Most componentsare recyclable and parts are marked as

    specified in applicable standards.

    ambient temperaturec Compact circuit breakers can be used attemperatures ranging from -25C to 70C.Above 40C (or 65C for circuit breakersused to protect motor feeders), always take

    into account the derating coefficientsindicated in the documentation;c wherever possible the circuit breakersshould be put into service at their normal

    ambient operating temperature, however thiscan be done at temperatures between -35Cand -25C as long as this condition does notlast for an extended period;c in their original pack, Compact circuitbreakers may be stored at temperaturesranging from -50 to +85C.

    conformity with standards Compact circuit breakers and auxiliariescomply with the following internationalrecommendations:c IEC 947-1: general rules;c IEC 947-2: circuit breakers;c IEC 947-3: switches, disconnectors,switch-disconnectors, etc;c IEC 947-4: contactors and motors startersc IEC 947-5.1 and following - control circuitdevices and switching elements; automaticcontrol components.In that these recommendations are appliedin most countries, Compact circuit breakers

    and auxiliaries comply with European(EN 60947-1 and EN 60947-2) and thecorresponding national standards:c France NF;c Germany VDE;c U.K BS;c Austrialia AS;c Italy CEI.They also comply with the specifications ofthe marine classification companies (Veritas,Lloyds Register of Shipping, Det NorskeVeritas, etc).Compact circuit breakers are also designedfor the protection of machine tools in thatthey comply with French standardNF C 79-130 and with the recommendationsissued by the CNOMO organisation.Concerning the United States UL, CanadianCSA, Mexican NOM and Japanese JISstandards, please consult us.

    pollution degreeCompact circuit breakers are certified foroperation in pollution-degree IIIenvironments as defined by IECstandard 947 (industrial environments).

    Standardised characteristics indicatedon the rating plateUi: rated insulation voltageUimp: rated impulse withstand voltageIcu: ultimate breaking capacity, for variousvalues of the rated operational voltage Ue

    cat: utilisation categoryIcw: short-time withstand currentIcs: service breaking capacityIn: rated current

    : suitable for isolation

    discriminationIn most cases, discrimination is totalbetween two Compact NS circuit breakersequipped with standard trip units(or between Compact NS and Multi 9 circuitbreakers).The table opposite indicates the

    combinations providing total discriminationfor N-type circuit breakers equipped withstandard trip units.

    upstream Compact NS160N NS250N NS400N NS630Nrating (A) 80 100 125 160 200 250 400 630

    downstreamcircuit breaker rating (A)

    multi 9 C60N 1025 c c c c c c c c

    3240 c c c c c c

    63 c c c c c

    Compact NS80H 2.56.3 c c c c c c c c

    12.5 c c c c c c c

    2580 c c c c c

    NS100N 16100 c c c c

    NS160N 125160 c c

    NS250N 200250 c

    ctotal discrimination: only the circuit breaker immediately upstream from a fault trips.

    E18567

    E22037

    MERLIN GERIN

    compact

    NS160 HUi 750V. Uimp 8kV.

    Ue

    (V)

    220/240

    380/415

    440

    500/525

    660/690

    250

    Icu

    (kA)

    100

    70

    65

    50

    10

    85

    cat A

    Ics = 100% Icu

    IEC 947.2UTE VDE BS CEI UNE NEMA

    D2

    D1

  • 7/29/2019 Compact 80-1250

    14/355Merlin Gerin 15

    All Compact circuit breakers aresuitable for isolation as defined in IECstandard 947-2:cthe isolation position corresponds to the O(OFF position);cthe operating handle cannot indicatethe "off" position unless the contacts areeffectively open;cpadlocks may not be installed unless thecontacts are open.Installation of a rotary handle or a motormechanism does not alter the reliabilitythe position indication system.

    The isolation function is certified by testsguaranteeing:cthe mechanical reliability of the positionindication system;cthe absence of leakage currents;covervoltage withstand capacity betweenupstream and downstream connections.

    suitability for isolationpositive contact indication

    degree of protection(as per standards IEC 529)

    installation in class II

    switchboardsAll Compact circuit breakers, even whenfitted with a rotary handle or a motormechanism, may be installed throughthe door of class II switchboards (as per IECstandard 664).

    Installation requires no special operationsbecause the Compact provides class II

    insulation between the front face and allinternal circuits.

    bare circuit breaker with terminal shieldswith toggle IP40

    with direct rotary handle standard / VDE IP40

    circuit breaker installed in switchboardwith toggle IP 40

    with direct rotary handle standard / VDE IP40

    MCC IP43

    CNOMO IP54

    with extended rotary handle IP55

    with motor mechanism IP40

    044

    334

    E18569

    E18570

    E28439

    E21277

    E28440

    E28441

    E28442

    pushtotrip

    2

    I

    pushON

    Opush

    OFF

    1

    manu/aut

    o

    push

    totrip

    pushtotrip

    ONI

    OOFF

    pushtotrip

    ONI

    OOFF

    pushtotr ip

    ONI

    OOFF

    ONI

    OFF

    pushtotr ip

  • 7/29/2019 Compact 80-1250

    15/355Merlin Gerin16

    Compact: functions and characteristics

    protection of low-voltage distribution networks (cont.)

    circuit breakers

    for power distribution

    switchboards

    pushtotrip

    pushtotrip

    pushtotrip

    (*) 2P only for N-types

    (**) for operational voltage up to 500 V

    Compact circuit breakersnumber of poles

    electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40C

    rated insulation voltage (V) Ui

    rated impulse withstand voltage (kV) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    DC

    ultimate breaking capacity Icu AC 50/60 Hz 220/240 V(kA rms) 380/415 V

    440 V

    500 V

    525 V

    660/690 V

    DC 250 V (1 P)500 V (2 P in series)

    service breaking capacity Ics (% Icu)

    utilisation category

    suitability for isolation

    endurance (C-O cycles) mechanical

    electrical 440 V - In/2

    440 V - In

    electrical characteristics as per standard Nema AB1breaking capacity (kA) 240 V

    480 V

    600 V

    protection (see following pages)protection against interchangeable trip unitsovercurrents (A) Ir setting current

    earth fault protection add-on Vigi module

    Vigirex relay

    installation and connectionfixed/front connection

    fixed/rear connection

    plug-in (on base)

    withdrawable (on chassis)

    indication and measurement auxiliariesauxiliary switches

    electronic trip unit related functions

    voltage presence indicator

    current transformer module

    ammeter module

    insulation monitoring module

    control auxiliariesauxiliary releases

    motor mechanism

    rotary handles (direct, extended)

    manual/automatic source changeover systems

    installation and connection accessoriesbare cable connectors

    terminal extensions and spreaders

    terminal shields and phase barriers

    escutcheonsdimensions and weightsdimensions 2/3 poles, fixed, FC

    L x H x D (mm) 4 poles, fixed, FC

    weight (kg) 3 poles, fixed, FC

    4 poles, fixed, FC

    045345

    Compact NS250H

    048286

    Compact NS630L

    E20999

  • 7/29/2019 Compact 80-1250

    16/35517Merlin Gerin

    NS100 NS160 NS250 NS400 NS6302 (*), 3, 4 2 (*), 3, 4 2 (*), 3, 4 3, 4 3, 4

    100 160 250 400 630

    750 750 750 750 750

    8 8 8 8 8

    690 690 690 690 690

    500 500 500 500 500

    N H L N H L N H L N H L N H L85 100 150 85 100 150 85 100 150 85 100 150 85 100 150

    25 70 150 36 70 150 36 70 150 45 70 150 45 70 150

    25 65 130 35 65 130 35 65 130 42 65 130 42 65 130

    18 50 100 30 50 70 30 50 70 30 50 100 30 50 70

    18 35 100 22 35 50 22 35 50 22 35 100 22 35 50

    8 10 75 8 10 20 8 10 20 10 20 75 10 20 35

    50 85 100 50 85 100 50 85 100 85 8550 85 100 50 85 100 50 85 100 85 85

    100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%** 100%** 100%**

    A A A A A A A A A A A A A A A

    c c c c c c c c c c c c c c c

    50000 40000 20000 15000 15000

    50000 40000 20000 12000 8000

    30000 20000 10000 6000 4000

    85 100 200 85 100 200 85 100 200 85 100 200 85 100 200

    25 65 130 35 65 130 35 65 130 42 65 130 42 65 130

    10 35 50 20 35 50 20 35 50 20 35 50 20 35 50

    c c c c c

    12.5...100 12.5...160 12.5...250 160...400 250...630

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    105 x 161 x 86 105 x 161 x 86 105 x 161 x 86 140 x 255 x 110 140 x 255 x 110

    140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 185 x 255 x 110 185 x 255 x 110

    1.6 1.6 1.9 6.0 6.0

    2.1 2.1 2.3 7.8 7.8

  • 7/29/2019 Compact 80-1250

    17/355Merlin Gerin18

    Compact: functions et characteristics

    protection of low-voltage distribution networks (cont.)

    circuit breakers for powerdistribution switchboards,

    single-pole and two-polecircuit breakers

    Compact circuit breakersnumber of poles

    electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40C

    rated insulation voltage (V) Ui

    rated impulse withstand voltage (kV) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    DC

    ultimate breaking capacity Icu AC 50/60 Hz 220 V

    (kA rms) 277 V

    380/415 V

    440 V

    500 V

    525 V660/690 V

    DC 250 V (1 pole)

    500 V (2 poles)

    service breaking capacity Ics (% Icu)

    utilisation category

    suitability for isolation

    endurance (C-O cycles) mechanical

    electrical 440 V (277 V for 1P) - In/2

    440 V (277 V for 1P) - In/2

    electrical characteristics as per Nema AB1breaking capacity (KA) 240 V

    277 V

    480 V600 V

    protection (see next pages)protection against interchangeable trip units

    overcurrents (A) Ir setting current

    earth fault protection add-on Vigi module

    Vigirex relay

    installation and connectionsfixed/front connection

    fixed/rear connection

    plug-in (on base)

    withdrawable (on chassis)

    indication and measurement auxiliariesauxiliary switches

    voltage presence indicator

    voltage transformer module

    ammeter module

    control auxiliariesauxiliary releases

    motor mechanism

    rotary handles (direct, extended)

    manual/automatic source changeover systems

    installation and connection accessoriesbare-cable connectors

    terminal extensions and spreaders

    terminal shields and phase barriers

    front panel escutcheons

    dimensions and weightsdimensions: W x H x D (mm)

    weight (kg)

    86099

    single-pole Compact NS160H

    86101

    two-pole Compact NS100N

    E29210

  • 7/29/2019 Compact 80-1250

    18/35519Merlin Gerin

    NS100 NS160 NS2501 2 1 2 1

    100 100 160 160 250

    750 750 750 750 750

    8 8 8 8 8

    277 690 277 690 277

    250 500 250 500 250

    N H N H N H N H N25 40 85 100 25 40 85 100 25

    25 40 25 40 25

    25 70 36 70

    25 65 35 65

    18 50 30 50

    18 35 22 358 10 8 10

    25 40 50 85 25 40 50 85 25

    50 85 50 85

    100% 100% 100% 100% 100% 100% 100% 100% 100%

    A A A A A A A A A

    c c c c c c c c c

    20000 20000 20000 20000 20000 20000 20000 20000 10000

    20000 20000 20000 20000 20000 20000 20000 20000 10000

    10000 10000 10000 10000 10000 10000 10000 10000 5000

    25 40 85 100 25 40 85 100 25

    25 40 25 40 25

    25 65 25 6510 35 10 35

    16...100 16...100 125...160 125...160 160250

    c c c c c

    c c c c c

    c c

    c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    35 x 161 x 86 70 x 161 x 86 35 x 161 x 86 70 x 161 x 86 35 x 161 x 86

    0.7 1.2 0.7 1.2 0.7

  • 7/29/2019 Compact 80-1250

    19/355Merlin Gerin20

    Compact: functions and characteristics

    protection of low-voltage distribution networks (cont.)

    circuit breakersfor power distribution

    switchboards (cont.)

    (*) rated current In at 40C for plug-in/withdrawable units:- C1001N/H: 1000 A- C1001L: 910 A

    - C1251N/H: 1160 A

    046893

    Compact C1251H

    The Compact range also includes a circuitbreaker for 1000 V AC distribution networks(see page 0023).

    Compact circuit breakersnumber of poles

    electrical characteristics as per CEI 947-2 and EN 60947-2rated current (A) In 40C

    rated insulation voltage (V) Ui

    rated impulse withstand voltage (kV) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    DC

    ultimate breaking capacity Icu AC 50/60 Hz 220/240 V(kA rms) 380/415 V

    440 V

    500 V

    525 V

    660/690 V

    DC 125 V250 V

    500 V

    750 V

    service breaking capacity Ics (% Icu)

    short-time withstand current Icw kA rms

    t (s)

    utilisation category

    suitability for isolation

    endurance (cycles C-O) mechanical

    electrical 440 V - In/2

    440 V - In

    electrical characteristics as per standard Nema AB1breaking capacity (kA) 240 V

    480 V

    600 V

    protection (see following pages)protection against interchangeable trip unitovercurrents (A) Ir setting current

    eart fault protection add-on Vigi module

    Vigirex relay

    installation and connectionfixed/front connection

    fixed/rear connection

    plug-in (on base)

    withdrawable (on chassis)

    indication and measurement auxiliariesauxiliary switches

    electronic trip unit related functions

    voltage presence indicator

    insulation monitoring module

    control auxiliariesauxiliary releases

    motor mechanism

    rotary handles (direct, extended)

    manual/automatic source changeover systems

    installation and connection accessoriesbare cable connectors

    terminal extensions and spreadersterminal shields and phase barriers

    escutcheons

    dimensions and weightsdimensions W x H x D (mm) 3/4 poles, fixed, FC

    weight (kg) 3/4 poles, fixed, FC

  • 7/29/2019 Compact 80-1250

    20/35521Merlin Gerin

    C801 C1001 C12513, 4 3, 4 3, 4

    800 1000 (*) 1250 (*)

    750 750 750

    8 8 8

    690 690 690

    750

    N H L N H L N H85 100 150 85 100 150 85 100

    50 70 150 50 70 150 50 70

    42 65 150 42 65 150 42 65

    40 50 100 40 50 100 40 50

    25 40 60 25 40 60 25 40

    50 (1P)50 (2P)

    50 (3P)

    25 (3P)

    50% 50% 50% 50% 50% 50% 50% 50%

    12 12 6.4 15 15 8 15 15

    1 1 1 1 1 1 1 1

    B B A B B A B B

    c c c

    12000 6400 15000 6400 15000

    3000 3000 3000

    1500 1500 1500

    85 100 150 85 100 150 85 100

    42 65 100 42 65 100 42 65

    30 42 65 30 42 65 30 42

    c c c

    320...800 400...1000 500...1250

    c c c

    c c c

    c c c

    c c (*) c (*)

    c c c

    c c c

    c c c

    c c c

    c c c

    c c c

    c c c

    c c c

    c c c

    c c c

    210 / 280 x 374 x 172 210 / 280 x 374 x 262 210 / 280 x 374 x 172 210 / 280 x 374 x 262 210 / 280 x 374 x 172

    13 / 17 25 / 33 13 / 17 25 / 33 13 / 17

  • 7/29/2019 Compact 80-1250

    21/35530Merlin Gerin

    Compact: functions and characteristics

    protection of low-voltage distribution networkstrip units for Compact C801 to C1251

    320 400 500 630 800 1000 1250

    STR 25 DE

    STR 35 GE

    STR 35 SE

    STR 55 UE

    STR 45 AE

    STR 45 BE

    P21 / P41

    N

    H

    L

    N H

    L

    N

    standard protection,

    protection of networks supplied bygenerators,

    protection with discrimination onshort-circuits,

    protection with total discrimination,

    protection of DC networks.

    Ir I

    5

    I

    t

    0

    1

    5

    Ir Im

    3

    I I

    t

    0

    1

    4

    electronic trip units STR35SE/GE

    15 8

    C 801 NHC 1001 NH

    LL

    12

    C 1251NH

    t

    i

    Ir

    Im

    tm

    I

    120s

    A

    A1,5 Ir

    x In

    5

    STR 35SE

    .63 .8

    .5 1

    xIn

    Io

    60 70 80 90 % Ir105

    test Ir Im

    +

    tm

    .9

    .95

    .8 1.85

    4

    6

    1.5 10xIr

    .3

    0 0

    .1

    .3

    .2

    82

    3

    .2

    .1

    on I2t off

    5

    1

    xIo

    1 38 47

    Legend1 "long time" protection threshold2 "long time" protection time delay3 "short time" protection threshold

    4 "short time" protection time delay5 "instantaneous" protection threshold

    6 option (see page 34)7 overload indication8 test connector

    electronic trip unit STR25DE

    5

    STR 25DE

    .63 .8

    .5 1

    xIn

    Io

    60 70 80 90 % Ir

    t Ir

    I

    i

    105

    test Ir I

    +

    .9

    .95

    .8 1xIo

    .85

    4

    6

    1.5 10xIr

    82

    3

    5

    1 51 7

    E23659

    E24039

    E23820

    E24040

    E23821

  • 7/29/2019 Compact 80-1250

    22/355Merlin Gerin 31

    electronic trip unit STR45AE

    electronic trip unit STR45BE

    electronic trip unit STR55UE

    2

    5

    Ir Im

    3

    I I

    t

    0

    1

    4

    2

    Ir Im

    3

    I

    t

    0

    1

    4

    2

    5

    Ir Im

    3

    I I

    t

    0

    1

    4

    protectionc"long time" protection against overloads;c"short time" protection against short-circuits of low intensity;c"instantaneous" protection against short-circuits of high intensity;cresidual earth fault protection as an option(see page 34).Trip units do not have a predefined rating.The "long time" protection thresholddepends only on the circuit breaker currentrating and on the "long time" protectionsetting (see page 32).

    other functions

    Overload indicationsLoad indication (LED) in front (7) allowing to

    avoid tripping:clit at 90% of Ir setting;cflashing at 105% or more of Ir setting.

    TestTest connector in front (8) to check circuitbreaker operation, using a mini test kit or acalibration test kit (see page 73).

    Indication and measurement options (6)(see page 34).

    5

    STR 55UE

    .63 .8

    .5 1

    xIn

    Io

    60 70 80 90 % Ir

    t Ir

    tr

    Im

    i

    tm

    Ih

    th

    105

    test Ir Im

    S

    T

    +

    +

    tr tm

    .9.95

    .8 1xIo

    .85

    15 48030

    24060

    at 1.5Ir

    4

    6

    1.5 10xIr

    .3

    0 0

    .1

    .3

    .2

    82

    3

    .2

    .1

    Ic1

    .4

    .1

    .3

    on I2t offon I2t off

    TFR

    5

    120

    I5

    8

    2

    3

    4

    6

    .9.95

    .8 1xIr

    .85

    A

    B

    10

    15

    8

    8

    C 801 NHC 1001 NH

    LL

    10

    C 1251NH

    12

    B

    A

    th

    Ih

    .2 .6

    .4

    .5

    .3

    xIn

    Ic1

    I

    fault

    .4

    .3

    .1

    .2.2

    test

    xIn

    3 51 48 21 7 6

    5

    STR 45BE

    .63 .8

    .5 1

    xIn

    Io

    60 70 80 90 % Ir

    t Ir

    tr

    Im

    i

    tm

    Ih

    th

    105

    test Ir Im Ih

    S

    T

    +

    +tr tm th

    .9.95

    .8 1xIo

    .85

    120

    15 48030

    24060

    at 1.5Ir

    4

    6

    1.5 10xIr

    .3

    0 0.1

    .3

    .2

    82

    3

    .2

    .1

    .2 .6xIn

    .4

    .1 .1.2

    .4

    .3

    .4

    .5

    .3

    .3

    .2

    on I2t offon I2t off

    T

    5

    1 1 7 68 2 43

    5

    STR 45AE

    .63 .8

    .5 1

    xIn

    Io

    90 % Ir

    t Ir

    tr

    Im

    i

    tm

    Ih

    th

    105

    test Ir Im

    S

    T

    +

    +

    tr tm

    .9

    .95

    .8 1xIo

    .85

    15 480

    30

    240

    60

    at 1.5Ir

    4

    6

    1.5 10xIr

    .3

    0 0

    .1

    .3

    .2

    82

    3

    .2

    .1

    Ic1

    .4

    .1

    .3

    on I2t offon I2t off

    TFR

    5

    120 .9.95

    .8 1xIr

    .85

    60 70 80

    th

    Ih

    .2 .6

    .4

    .5

    .3

    xIn

    A 20

    C 801NH

    Ic1

    x In 23

    C 1001NH

    18

    C 1251NH

    A

    I

    .2

    .1

    .2

    .3

    .4

    fault

    3 61 48 21 7E

    24037

    E

    23823

    E24036

    E23824

    E24038

    E23822

  • 7/29/2019 Compact 80-1250

    23/35532Merlin Gerin

    Compact: functions and characteristics

    protection of low-voltage distribution networkstrip units for Compact C801 to C1251 (cont.)

    (*) For Compact C801L and C1001L, current settings must not exceed eight times the circuit breaker rating (C801L: 6300 A, C1001L: 8000 A)

    trip units STR25DE STR35SEfor Compact C801...1251N/H c c

    C801...1001L c c

    overload protection (long time)tripping threshold Ir adjustable (4 settings or adjustable (32 settings)

    "fine setting" version: 32 settings)

    0.4...1 x In 0.4...1 x In

    thermal memory

    OFF position

    neutral protection 4P 3d no protection no protection

    4P 4d 1 x Ir 1 x Ir

    4P 3d + Nr 500 A x Ir/In 500 A x Ir/In

    tripping time (s) type fixed fixed

    (min...max) at 1.5 x Ir 96...120 96...120

    at 6 x Ir 6.0...7.5 6.0...7.5

    at 7.2 x Ir 4.2...5.2 4.2...5.2

    short-circuit protection (short time)tripping Im adjustable adjustable

    threshold (A) 1.5...10 x Ir (*) 1.5...10 x Ir (*)

    accuracy 15% 15%

    time delay (ms) max. overcurrent fixed adjustable (4 settings)

    time before tripping 0 0 i 60 i 140 i 230

    total breaking time i 60 i 60 i 140 i 230 i 350

    const I2t positions

    short-circuit protection (instantaneous)tripping I no fixed

    threshold (A) C801N/H 15 x In

    C1001N/H 15 x InC1251N/H 12 x In

    C801L 8 x In

    C1001L 8 x In

    other functionsoverload indications c c

    test connector c c

    earth fault protection option (T)

    fault indications option (F)

    load monitoring option (R)

    communication option (COM)

    zone selective interlocking (Z)

    Constant I2t positionsInverse-time tripping (ST short-timeprotection) to improve discrimination(particularly with downstream fuses).

    Neutral protectionIn the event 4P 4d or 4P 3d + Nr devicesand the corresponding trip units are suppliedseparately, a current sensor must beinstalled on the fourth pole inside the circuitbreaker.

    Tripping thresholds are indicated for 2 or3 poles on load.

    OFF positionLT (long time) protection deactivated formotor-starter protection.

    Thermal memoryConductor cooling time following trippingtaken into account by LT protection.

    Overload indicationLED in front of trip unit:clit at 90% of Ir setting;cflashing at 105 % or more of Ir setting.Option F offers a five threshold indication(60, 70, 80, 90, 105%).

    TestTest connector to check circuit breakeroperation using a mini test kit or a calibrationtest kit (see page 73).

    Indication and measurement options (seepage 34).

  • 7/29/2019 Compact 80-1250

    24/355Merlin Gerin 33

    STR35GE STR45AE STR45BE STR55UEc c c

    c c c

    adjustable (32 settings) adjustable (32 settings) adjustable (32 settings) adjustable (32 settings)

    0.4...1 x In 0.4...1 x In 0.4...1 x In 0.4...1 x In

    c

    c

    no protection no protection no protection no protection

    1 x Ir 1 x Ir 1 x Ir 1 x Ir

    500 A 500 A x Ir/In 500 A x Ir/In 500 A x Ir/In

    fixed adjustable (6 settings)

    12...15 12...15 24...30 48...60 96...120 192...240 384...480

    0.75...0.94 0.75...0.94 1.50...1.88 3.00...3.75 6.0...7.5 12...15 24...30

    0.50...0.65 0.52...0.65 1.04...1.30 2.06...2.60 4.2...5.2 8.3...10.4 17...21

    adjustable adjustable adjustable adjustable

    1.5...10 x Ir (*) 1.5...10 x Ir 1.5...10 x Ir (*) 1.5...10 x Ir (*)

    15% 15% 15% 15%

    adjustable (4 settings)

    0 i 60 i 140 i 230

    i 60 i 140 i 230 i 350

    c

    fixed fixed no adjustable

    15 x In 20 x In 2...15 x In

    15 x In 23 x In 2...15 x In12 x In 18 x In 2...12 x In

    8 x In 2...8 x In

    8 x In 2...8 x In

    c c c c

    c c c c

    c c c

    c c

    c c c

    c c c

    c

  • 7/29/2019 Compact 80-1250

    25/35534Merlin Gerin

    Compact: functions and characteristics

    protection of low-voltage distribution networkstrip units for Compact C801 to C1251 (cont.)

    I

    t

    0

    Ih

    th

    Load monitoring (R)

    tm

    6

    1.5 10xIr

    .3

    0 0

    .1

    .3

    .2

    82

    3

    .2

    .1

    Ic1

    .8

    .5 1

    .7 9

    on I2t off

    8

    1,5

    2

    3

    .9.95

    .8 1xIr

    .85

    Ic2

    B

    A

    xIr

    Two adjustable threshold (only one, Ic1, ifoption R is combined with option T), thatdepends on the LT setting, control the opto-decoupled outputs (transistors) or send asignal via the communication outputs. Thesetwo thresholds (Ic1 and Ic2) are used forapplications such as load shedding andreconnection, interlocking systems andalarms.

    I

    t

    0

    Ic2 Ic1

    Fault indications (F) In addition to indications for standard faults(toggle, SD and SDE auxiliary switches), thisoption differentiates between the threepossible causes of tripping via three LEDs:c overload (LT);c short-circuit (ST + INST);c earth fault.

    A three-LED load monitoring functionindicates 60, 70 and 80% of the LTthresholds in addition to the standard 90 and105% indications. Option F is not available

    on STR45BE trip units. It requires anexternal power supply.

    5

    60 70 80 90 % Ir105

    Ir Im.9

    .95

    .81

    .85

    4

    6

    1.5 10

    82

    3

    5

    fault

    I4

    8

    1,5

    2

    3

    6Ih

    .2.

    .4

    .3

    B

    A

    Communication (COM)The following information is transmitted toDigipact distribution monitoring and controlmodules: all data concerning the currentspassing through the CTs, all trip-unitsettings, including those of options T andR,load-shedding orders, fault indicationsprovided by option F and an alarm indicationwhen the internal temperature is 10C belowthe circuit breaker self-protection threshold.

    Possible combinationsc option Z;c options Z, R and F;c options Z, T, R and F;c options Z, F and COM;c options Z, R, F and COM;c options Z, T, F and COM;c options Z, T, R, F and COM.

    Zone selective interlocking (Z)A number of circuit breakers areinterconnected one after another by a pilot-

    wire. In the event of a short-time or earthfault, the control unit applies the set timedelay only if it receives a signal from adownstream circuit breaker. If not, it trips

    instantaneously (tripping time as 0.1 short-time setting). In this way, the fault is clearedrapidly by the nearest circuit breaker. Thethermal stresses in the installation areminimised while maintaining time

    discrimination throughout the entireinstallation.Opto-electronic outputsThe use of opto-transistors ensures totalisolation between the internal circuits of thecontrol unit and the circuits wired by theuser.

    options for electronic trip units STR45/55

    Earth fault protection (T)

    The earth fault protection is of the residualcurrent type. The circuit breaker trips, afteran adjustable time delay th, at an adjustablethreshold In that depends on the ratedcurrent In.On request, the earth fault protection may beof the "W" type (source ground return) or ofthe neutral protection type.The thermal memory is identical to that ofthe LT protection, with a time constant of20 seconds.

    For distributed neutral systems, option Trequires installation of the 4th polesensor downstream the circuit breaker.

    5Im

    tm

    4

    6

    1.5 10xIr

    .3

    0 0

    .1

    .3

    .2

    82

    3

    .2

    .1

    on I2t off

    5Ih

    th

    .2 .6xIn

    .4

    .1 .1

    .2

    .4

    .3

    .4

    .5

    .3

    .3

    .2

    on I2t off

    I4

    8

    1,5

    2

    3

    6

    B

    A

    E24042

    E23825

    E23826

    E24041

    E24043

  • 7/29/2019 Compact 80-1250

    26/355Merlin Gerin 35

    integrated trip unit for Compact C1251N P21 P41

    tripping threshold Im (A) adjustable

    1600...3200 3200...6400

    accuracy 20% 20%

    (1) For the Ic2 minimum setting, the Ir setting and/or the load must be u 0.5 In:

    load and/or setting Ic2 setting

    0.4 x In 0.81.0 x In

    0.5 x In 0.61.0 x In

    0.6 x In 0.51.0 x In (complete range)

    (2) Minimum operating current 0.22 x In.Ir: tripping threshold of overload protection.

    earth fault protection (T)tripping threshold Ih Ih = 0.20.6 x In

    settings 0.2 - 0.25 - 0.3 - 0.35 - 0.4 - 0.45 - 0.5 - 0.6

    accuracy 15%

    time delay th th = settings 0.1 0.2 0.3 0.4

    max. overcurrent time before tripping 60 140 230 350

    total breaking time 140 230 350 500

    power supply self powered

    load monitoring (R)Ic1 threshold Ic1 = 0.8...1 x Ir

    settings 0.8 - 0.85 - 0.88 - 0.9 - 0.93 - 0.95 - 0.98 - 1.0

    accuracy 8%

    time delay closing tr/2 (tr = LT protection time delay)

    opening 10 s

    Ic2 threshold Ic2 = 0.5...1 x Ir

    settings (1) 0.5 - 0.6 - 0.7 - 0.8 - 0.85 - 0.9 - 0.95 - 1.0

    accuracy 8%

    time delay closing tr/4 (tr = LT protection time delay)

    opening 10 s

    transmission 100 mA opto-decoupled triac outputs, 120 to 240 V, 50/60 Hz or asignal via the communication output when the trip unit isequipped with the COM option.

    power supply self powered (2)

    fault indications (F)3 LEDs on front indicate cause of fault: Ir, Im/I, Ih

    bar graph, 3 LEDs 60, 70, 80% of Ir

    accuracy 6.6%

    reset automatic when circuit breaker is reset

    power supply 24 to 240 V, 50/60 Hz or CCcommunication (COM)

    type of data transmitted I1, I2, I3 Ineutral, Imax, all trip-unit settings, rating plugidentification (UL and JIS versions), load monitoring, faultindications, causes of malfunction, internal temperature.

    power supply self powered (2)

    Magnetic trip units for Compact C1251N,3 poles version, designed particularly for theprotection of DC networks. These tripunits are not interchangeable: the circuitbreaker is supplied fully assembled.All electrical characteristics and circuitbreaker enhancements (auxiliaries andaccessories) are indicated on page 20.

    magnetic trip units P21/P41

    P21 3P

    4800

    6000

    9600

    7800

    t(s)

    I(A)

    E29212

  • 7/29/2019 Compact 80-1250

    27/35536Merlin Gerin

    circuit breaker NS400 1000 V

    Compact circuit breaker NS400 1000 Vnumber of poles 3

    CT (A) (current transformer) 150 250 400

    electrical characteristicsrated operational voltage (V) Ue AC 50/60 Hz 1150 1150 1150

    ultimate breaking capacity (kA rms) Icu AC - 1000 V 10 10 10

    service breaking capacity Ics (% Icu) 100% 100% 100%

    electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40C 150 250 400

    rated insulation voltage (V) Ui 1250 1250 1250

    rated impulse withstand voltage (kV) Uimp 8 8 8

    rated operational voltage (V) Ue AC 50/60 Hz 1000 1000 1000

    ultimate breaking capacity (kA rms) Icu AC - 1000 V 10 10 10service breaking capacity Ics (% Icu) 100% 100% 100%

    suitable for isolation c c c

    utilisation category A A A

    pollution degree III III III

    protectionprotection against overcurrents electronic trip unit

    STR23SP c c c

    instantaneous 9 In 9 In 9 In

    earth fault protection

    installation and connectionsfixed/front connection c c c

    fixed/rear connection consult us

    plug-in (on base) consult uswithdrawable (on chassis) consult us

    indication and measurement auxiliariesauxiliary switches c c c

    voltage presence indicator

    current transformer module

    ammeter module

    insulation monitoring module

    control auxiliariesauxiliary releases c c c

    motor mechanism c c c

    rotary handles (direct extended) c c c

    manual/automatic source changeover systems consult us

    installation and connection accessoriesbare cable connectors consult us

    terminal extensions and spreaders consult us

    terminal shields standard

    escutcheon c c c

    dimensions and weightsdimensions L x H x D (mm) (1) 3 poles, fixed, FC 140 x 480 x 110

    weight (kg) 3 poles, fixed, FC 13

    0531

    82

    NS400 1000 V

    Compact: functions and characteristics

    protection of low-voltage distribution networks1000 V circuit breakers

    (1) with terminal shields.

  • 7/29/2019 Compact 80-1250

    28/355Merlin Gerin 37

    circuit breaker C1251N 1000 V

    (1): For withdrawable version do not use acurrent setting higher than:- 1160 A at 40C,- 1080 A at 50C,- 1000 A at 60C.(2): Defined for a power factor cos = 0.3.

    Compact circuit breaker C1251N 1000 Vnumber of poles 3

    CT (A) (current transformer) 400 800 1250

    electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40C 400 800 1250 (1)

    50C 400 800 1150 (1)

    60C 400 800 1050 (1)

    rated insulation voltage (V) Ui 1000 1000 1000

    rated impulse withstand voltage (kV) Uimp 8 8 8

    rated operational voltage (V) Ue AC 50/60 Hz 1000 1000 1000

    ultimate breaking capacity (kA rms) (2) Icu AC - 1000 V 20 20 20

    service breaking capacity Ics (% Icu) 50% 50% 50%

    short-time withstand current Icw kA rms 15 15 15

    t (s) 1 1 1suitable for isolation c c c

    utilisation category B B B

    pollution degree III III III

    protectionprotection against overcurrents interchangeable

    electronic trip unit c c c

    STR25DE c c c

    STR35GE/SE/ME(3) c c cSTR55UE (3) c c c

    earth fault protection c c c

    installation and connectionsfixed/front connection c c c

    fixed/rear connection c c c

    plug-in (on base)

    withdrawable (on chassis) c c c

    indication and measurement auxiliariesauxiliary switches c c c

    electronic trip unit related functions c c c

    voltage presence indicator

    current transformer module

    ammeter module

    insulation monitoring module

    control auxiliariesauxiliary releases c c c

    motor mechanism c c c

    rotary handles (direct extended) c c c

    manual/automatic source changeover systems c c c

    installation and connection accessoriesbare cable connectors c c c

    terminal extensions and spreaders c c c

    terminal shields and phase barriers c c c

    escutcheon c c c

    dimensions and weightsdimensions L x H x D (mm) 3 poles, fixed, FC 210 x 374 x 172weight (kg) 3 poles, fixed, FC 13

    (3)

    instantaneous CT400/800 CT1250fixed: STR35 15 x In 12 x In

    adjustable: STR552 to: 15 x In 12 x In

    0513

    53

    C1251N 1000 V

  • 7/29/2019 Compact 80-1250

    29/35538Merlin Gerin

    Compact: functions and characteristics

    protection oflow-voltage distribution networksearth fault protection

    Vigi earth fault modules

    Vigicompact NS250N

    Compliance with standardsc IEC 947-2, appendix B;c IEC 255-4 and IEC 801-2 to 5, coveringprotection against nuisance tripping due totransient overvoltages, lightning strikes,switching of devices on the network,electrostatic discharges, radiofrequencyinterference;c IEC 755, class A, immunity to DC

    components up to 6 mA;c VDE 664, operation down to - 25C.

    vigi

    200 / 440 V - 50 / 60 Hz

    2 4 6

    1 3 5

    T

    NS 250

    before dielectric testr e m o v e t h i s c o v e r

    avant test dilectriqueenlever ce couvercle

    N

    310

    150

    60

    0

    0,03 ( t = 0 )

    vigi MH3

    1

    0,3

    t(ms)

    In(A)

    10

    HS

    T R

    1 2 3 4 5 6 7

    Power supplyVigi modules are self-supplied internally bythe network voltage and therefore do notrequire any external source. They continueto function even when supplied by only twophases.

    Remote indicationsVigi modules may be equipped with an SDVauxiliary switch (see page 64) to remotelyindicate tripping due to an earth fault.

    1 sensitivity setting

    2 time-delay setting (for discrimination with earth

    fault protection)

    3 lead seal preventing access to settings

    4 test button for routine tripping checks by

    internally simulating an earth fault

    5 reset button (resetting is required following a trip

    due to an earth fault)

    6 rating plate

    7 slot for SDV auxiliary switch

    Vigicompact circuitbreakers

    Dimensions and weights NS100 - NS160 NS250 NS400 - NS630

    dimensions 3 poles 105 x 236 x 86 135 x 355 x 110L x H x D (mm) 4 poles 140 x 236 x 86 180 x 355 x 110

    weight (kg) 3 poles 2.5 2.8 8.8

    4 poles 3.2 3.4 10.8

    For Compact NS100 to NS630 circuitbreakers, earth fault protection is obtained

    by fitting a "Vigi" earth fault module directlyon the circuit breaker terminals.The addition of the Vigi module does notaffect circuit breaker characteristics (seepages 10 to 13);c conformity with standards;c protection degrees, class II insulation front

    face;

    c suitability for isolation as defined byIEC 947-2;

    celectrical characteristics;c trip unit characteristics;c installation and connection methods;c indication,measurement and controlauxiliaries;c installation and connection accessories.

    earth fault protection modules Vigi ME Vigi MH Vigi MBnumber of poles 3. 4 (*) 3. 4 (*) 3. 4 (*)

    for Compact NS100 N/H/L ccccc ccccc

    NS160 N/H/L ccccc ccccc

    NS250 N/H/L ccccc

    NS400 N/H/L ccccc

    NS630 N/H/L ccccc

    earth fault protection characteristicssensitivity In (A) fixed adjustable adjustable

    0.3 0.03 - 0.3 - 1 - 3 - 10 0.3 - 1 - 3 - 10 - 30

    time delay intentional delay (ms) fixed adjustable adjustable< 40 0 60 (**) 150 (**) 310 (**) 0 60 150 310

    total breaking time (ms) < 40 < 40 < 140 < 300 < 800 < 40 < 140 < 300 < 800

    rated voltage (V) AC 50/60 Hz 200 to 440 200 to 440-440 to 550 200 to 440-440 to 550(*) Vigi 3P modules may also be used on 2P circuit breakers

    (**) If the sensitivity is set to 30 mA, the tripping is not delayed

    044333

    E21007

  • 7/29/2019 Compact 80-1250

    30/355Merlin Gerin 39

    pushtotrip

    MG

    combination of

    Compact circuit breaker

    Vigirex earth faultprotection relay

    This solution can be used with all Compactcircuit breakers.

    For Compact NS100 to NS630, the Vigirexresidual current relays can be used when:c special time delay or tripping thresholdvalues are required;c there are major installation constraints(circuit breaker already installed andconnected, limited space available, etc.).

    Vigirex relay characteristicsResidual current operated relay with

    separated toroid:c sensivity adjustable from 30 mAto 250 A;c eight time-delay settings (0 to 1s);c closed toroids (30 to 300 mm diameter);c split toroids (46 to 110 mm diameter);c options :

    vtrip alarm by a failsafe contact,vpre-alarm contact and indicating light(threshold: 0.5 x In),v400 Hz network, etc.

    Conformity with standardsc IEC 947-2, appendix B;c IEC 255-4 and IEC 801-2 to 5, covering

    protection against nuisance tripping due totransient overvoltages, lightning strikes,switching of devices on the network,electrostatic discharges, radiofrequencyinterference;c IEC 755, class A, immunity to DCcomponents up to 6 mA;c VDE 664, operation down to - 25C.

    For complete information on theVigirex range, consult the correspondingMerlin Gerin documentation.

    residual current measurement toroid

    Vigirex earth fault detection relay

    MN or MX auxiliary release for earth fault tripping.

    E18577

  • 7/29/2019 Compact 80-1250

    31/355Merlin Gerin40

    Compact: functions and characteristics

    motor protection

    push

    to

    tr ip

    The circuit breakers presented here:cccccprovide protection against short-circuits;cccccare suitable for isolation as defined byIEC 947-2 standard.For a complete protection of the motor andits control device, overload protection maybe ensured by either:cccccthe circuit breaker;ccccca separate Telemecanique thermal relay.The control device may be of the direct on-line type (with or without reversing) or of the"star-delta" type.Combinations are governed by IEC 947-4standard.

    protection coordination

    (as defined by IEC 947-4)Whatever the power of the motor, thecoordination between circuit breaker,contactor and relay can be of either type 1 or2 (see the complementary technicalinformation chapter page 195). Selectiondepends on operational requirementsconcerning continuity of service and thetechnical skills of servicing personnel.

    All type 2 Merlin Gerin/Telemecaniquecombinations have been tested under theconditions defined by standards, and theyare certified ASEFA/LOVAG.

    E26988

    Compact circuit breakersnumber of poles

    electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 65C

    rated insulation voltage (V) Ui

    rated impulse withstand voltage (kV) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    ultimate breaking capacity Icu AC 50/60 Hz 220/240 V(kA rms) 380/415 V

    440 V

    500 V

    525 V

    660/690 V

    DC 250 V (1 pole)

    500 V (2 poles)

    service breaking capacity Ics (% Icu)

    utilisation category

    suitability for isolation

    endurance (C-O cycles) mechanical

    electrical 440 V - In/2

    440 V - In

    electrical characteristics as per Nema AB1breaking capacity (kA) 240 V

    480 V

    600 V

    protection

    overload and short-circuit protection rating (A)interchangeable trip units

    short-circuit protection (separate thermal relay) rating (A)

    interchangeable trip units

    earth fault protection add-on Vigi module

    Vigirex relay

    installation and connectionfixed/front connection

    fixed/rear connection

    plug-in (on base)

    withdrawable (on chassis)

    indication and measurement auxiliariesauxiliary switches

    electronic trip unit function

    voltage presence indicator

    current transformer module

    ammeter module

    insulation monitoring module

    control auxiliariesauxiliary releases

    motor mechanism

    rotary handles (direct, extended)

    locking systems

    installation and connection accessoriesbare-cable connectors

    terminal extensions and spreadersterminal shields and phase barriers

    front panel escutcheons

    dimensions and weightsdimensions: L x H x D (mm)

    weight (kg)

  • 7/29/2019 Compact 80-1250

    32/35541Merlin Gerin

    NS80 NS100 NS160 NS2503 3, 4 3, 4 3, 4

    80 100 150 220

    750 750 750 750

    8 8 8 8

    690 690 690 690

    H N H L N H L N H L

    100 85 100 150 85 100 150 85 100 150

    70 25 70 150 36 70 150 36 70 150

    65 25 65 130 35 65 130 35 65 130

    25 18 50 100 30 50 100 30 50 70

    25 18 35 100 22 35 100 22 35 50

    6 8 10 75 8 10 75 8 10 20

    50 85 100 50 85 100 50 85 100

    50 85 100 50 85 100 50 85 100

    100% 100% 100% 100% 100% 100% 100% 100% 100% 100%

    A A A A A A A A A

    c c c c

    20000 50000 40000 20000

    10000 50000 40000 20000

    7000 30000 20000 10000

    100 85 100 200 85 100 200 85 100 200

    65 25 65 130 35 65 130 35 65 130

    10 10 35 50 20 35 50 20 35 50

    24100 24...150 24...220c c c

    1.5...80 2.5...100 2.5...150 2.5...220

    c c c

    c c c

    c c c c

    c c c c

    c c c

    c c c

    c c c

    c c c c

    c c c

    c c c

    c c c

    c c c

    c c c c

    c c c

    c c c c

    c c c c

    built-in c c c

    c c c

    c c c c

    c c c

    90 x 120 x 80 105 x 161 x 86 105 x 161 x 86 105 x 161 x 86

    1.0 1.6 1.6 1.9

  • 7/29/2019 Compact 80-1250

    33/355Merlin Gerin42

    Compact: functions and characteristics

    motor protection(cont.)

    push

    totr ip

    The circuit breakers presented here:cccccprovide protection against short-circuits;cccccare suitable for isolation as defined byIEC 947-2 standard.

    For a complete protection of the motor andits control device, overload protection maybe ensured by either:cccccthe circuit breaker;

    ccccca separate Telemecanique thermal relay.The control device may be of the direct on-line type (with or without reversing) or of the"star-delta" type.Combinations are governed by IEC 947-4standard.

    protection coordination(as defined by IEC 947-4)Whatever the power of the motor, thecoordination between circuit breaker,contactor and relay can be of either type 1 or2 (see the complementary technicalinformation chapter page 195). Selectiondepends on operational requirementsconcerning continuity of service and thetechnical skills of servicing personnel.

    All type 2 Merlin Gerin/Telemecaniquecombinations have been tested under theconditions defined by standards, and theyare certified ASEFA/LOVAG.

    E26988

    Compact circuit breakersnumber of poles

    electrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 65Crated insulation voltage (V) Ui

    rated impulse withstand voltage (kV) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    ultimate breaking capacity Icu AC 50/60 Hz 220/240 V(kA rms) 380/415 V

    440 V

    500 V

    525 V

    660/690 V

    DC 125 V

    250 V500 V

    750 V

    service breaking capacity Ics (% Icu)

    utilisation category

    suitability for isolation

    endurance (C-O cycles) mechanical

    electrical 440 V - In/2

    440 V - In

    electrical characteristics as per Nema AB1breaking capacity (kA) 240 V

    480 V

    600 V

    protectionoverload and short-circuit protection rating (A)

    interchangeable trip units

    short-circuit protection (separate thermal relay) rating (A)

    interchangeable trip units

    earth fault protection add-on Vigi module

    Vigirex relay

    installation and connectionsfixed/front connection

    fixed/rear connection

    plug-in (on base)

    withdrawable (on chassis)

    indication and measurement auxiliariesauxiliary switches

    electronic trip unit related functionvoltage presence indicator

    voltage transformer module

    ammeter module

    insulation monitoring module

    control auxiliariesauxiliary releases

    motor mechanism

    rotary handles (direct, extended)

    locking systems

    installation and connection accessoriesbare-cable connectors

    terminal extensions and spreaders

    terminal shields and phase barriersfront panel escutcheons

    dimensions and weightsdimensions: L x H x D (mm)

    weight (kg)

    (*) Ics = 100% Icu for Ue < 500 V

    (**) Rated current In at 65 C for withdrawable Compact C1251N/H: 960 A

  • 7/29/2019 Compact 80-1250

    34/35543Merlin Gerin

    NS400 NS630 C801 C1001 C12513 3 3 3 3

    320 500 750 875* 1000**750 750 750 750 750

    8 8 8 8 8

    690 690 690 690 690

    N H L N H L N H N H N H

    85 100 150 85 100 150 85 100 85 100 85 100

    45 70 150 45 70 150 50 70 50 70 50 70

    42 65 130 42 65 130 42 65 42 65 42 65

    30 50 100 30 50 70 40 50 40 50 40 50

    22 35 100 22 35 50 40 50 40 50 40 50

    10 20 75 10 20 35 25 40 25 40 25 40

    50 (1P)

    85 85 50 (2P)85 85 50 (3P)

    25 (3P)

    100% 100% 100% 100%* 100%* 100%* 50% 50% 50% 50% 50% 50%

    A A A A A A B B B B B B

    c c c c c

    15000 15000 10000 10000 10000

    12000 8000 3000 3000 3000

    6000 4000 1500 1500 1500

    85 100 200 85 100 200 85 100 85 100 85 100

    42 65 130 42 65 130 42 65 42 65 42 65

    20 35 50 20 35 50 30 42 30 42 30 42

    320 320 320 500 500 500 320...800 400...1000 500...1250c c c c c c c c c

    320 320 500 500 320...800 400...1000 500...1250

    c c c

    c c

    c c c c c

    c c c c c

    c c c c c

    c c

    c c c c c

    c c c c c

    c c c

    c c

    c c

    c c

    c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    c c c c c

    140 x 255 x 110 140 x 255 x 110 210 x 374 x 172 210 x 374 x 172 210 x 374 x 172

    6 6 13 13 25

  • 7/29/2019 Compact 80-1250

    35/355Merlin Gerin44

    E26530

    trip units

    protection

    Compact: functions and characteristics

    motor protectiontrip units selection (cont.)

    For motor protection, Compact circuitbreakers may be fitted with:

    c magnetic trip units, wich provide short-circuit protection;

    c electronic trip units, specifically designedto provide:

    v short-circuit protection,v overload protection,v phase-failure protection.

    overload (long time)tripping Ir adjustable (10 settings) adjustable (40 settings) adjust. (32 settings) adjustable (32 settings)threshold (A) 0.6...1 x In 0.4...0.8 x In 0.4...1 x In 0.4...1 x In

    tripping class 10 10A 10 20 10 10A 10 20 30(IEC 947-4)

    tripping time (s) fixed adjustable fixed adjustable

    (minimaxi) to 1.5 x Ir 120320 144198 270357 433595 96120 4860 96120 192240 384480

    to 6 x Ir 615 5.87.3 10.913.1 17.421.8 67.5 33.7 67.5 1215 2430

    to 7.2 Ir 410 45 7.39.1 1215 4.25.2 2.12.6 4.25.2 8.310.4 1721

    phase-failure (complied with the standard IEC 947-4-1)built into the trip unit c c

    tripping time for phase between 3.5 and 6 s 4 s 10%

    failures (s)

    short-circuit (short time)tripping Im or Isd fixed adjustable (8 settings) adjust. (8 settings) adjustable (8 settings)threshold (A) 13 x Ir 6...13 x Ir 1.5...10 x Ir 1.5...10 x Ir

    accuracy 20% 15% 15% 15%

    max. overcurrent time fixed fixed adjustable adjustable

    before tripping (ms) 10 10 0 60 140 230 0 60 140 230

    total breaking time (ms) 60 60 60 140 230 350 60 140 230 350

    short-circuit (instantaneous)tripping Ii fixed fixed fixed = In x ... adjustable = In x ...

    threshold 15 x In 13 x Ir maxi 15 15 12 2...15 2...15 2...12

    (A) 8(type L) 2...8(type L)

    other functionsSDTAM module c c

    motor overload light c c (standard)

    indications module c (standard) c

    built-in ammeter (I) c

    P (kW) (400 V, 50 Hz)

    Ir (A)

    CompactNS100 NS250

    CompactNS80H-MA

    CompactNS400 NS630

    CompactC801 C1251

    MA

    MA

    STR22ME

    MA

    STR43ME

    STR35ME (LR OFF)

    STR55UE

    0.37

    1.5

    18.5

    40

    3

    6 48

    37

    80 100 160

    110

    205 220

    160

    320

    250

    500 800

    560

    1000

    670

    1250

    1.1

    2.5

    trip units STR22ME STR43ME STR35ME STR55UErating (A) 20 to 70C 10, 12.5, 20, 25, 40, 50, 80,100 150 220 120 200 320 500 800 1000 1250 800 1000 1250

    NS100N/H/L c

    NS160N/H/L c c

    NS250N/H/L c c c

    NS400N/H/L c c c

    NS630N/H/L c

    C801N/H/L c c

    C1001N/H/Lc c

    C1251N/H c c

  • 7/29/2019 Compact 80-1250

    36/35545Merlin Gerin

    rating (A) threshold settings (A)

    10 6 6.3 6.7 7.1 7.5 8 8.5 9 9.5 10

    12.5 7.5 7.9 8.4 8.9 9.4 10 10.6 11.2 11.9 12.5

    20 12 12.6 13.4 14.2 15 16 17 18 19 20

    25 15 15.7 16.7 17.7 18.7 20 21.2 22.5 23.7 25

    40 24 25.5 27 28.5 30 32 34 36 38 40

    50 30 31.5 33.5 35.5 37.5 40 42.5 45 47.5 50

    80 48 51 54 57 60 64 68 72 76 80

    100 60 63 67 71 75 80 85 90 95 100

    150 90 95 101 107 113 120 127 135 142 150

    220 132 140 148 157 166 177 187 198 209 220

    I

    t

    0

    1

    3

    2

    4

    5

    Ir 13Ir

    Ir ImIn=50A

    IEC 947.4 / cl.10

    Ir 13 Ir

    7,2Ir

    7,0s

    Ir

    u1,05 Ir

    testA30 50

    31.5 47.5

    33.5 45

    37.5 40

    35.5 42.5

    STR 22 ME

    1 7 8

    E26985

    E26984

    electronic trip unit STR22ME

    for Compact NS100 to NS250 circuit breakers

    protection c LT (long time) overload protection withadjustable Ir threshold (1), in compliancewith tripping class 10 as defined byIEC 947-4 (2);c single-phasing protection (trips in 3.5 and6 s);c ST (short-time) short-circuit protection:v fixed tripping threshold (13 x Ir) (3),v fixed time delay (4);c INST (instantaneous) short-circuitprotection, with fixed threshold (15 x In) (5).

    other functions IndicationsLoad indication by LED in front (7):c off when: I < 1.05 x Ir;c flashing when: I u 1.05 x Ir.

    TestTest connector in front (8) for connection toa mini test kit or calibration test kit to checkcircuit breaker operation after fitting the tripunit or other accessories.

    Contactor tripping module SDTAM (early

    thermal fault signal, optional):c opens the contactor in the event of anoverload. It is thus possible to differentiatebetween tripping due to overloads and short-

    circuits;

    c may also be used to signal a thermal fault;c must be reset manually (locally orremotely);c compatible with the following controlvoltages:v 24 to 72 V DC and 24 to 48 V AC,v 110 to 240 V AC / DC;c fits in place of the MN or MX auxiliaryvoltage releases.

    c single - phasing protection. The single -phasing complies with the recommendationsof standard IEC 947-4-1. It becomesoperational whenever a phase currentimbalance of 40% or more is present.

    trip unit STR22ME

  • 7/29/2019 Compact 80-1250

    37/355Merlin Gerin46

    I

    t

    0

    1

    3

    2

    4

    5

    Ir Isd Ii

    > Ih

    > Im

    > Ir

    P

    faulttestSTR 43 ME

    Io

    x In

    -test

    +

    31

    .90.93.95

    .98

    1

    .88

    .85

    .8

    9 1011

    12

    13

    8

    7

    6x Io

    Ir Isd

    x Ir

    %Ir >Ir >Isd

    A

    Ir I1 I2 I3IsdIr li

    tr

    tsd

    class

    8 6

    .71 .8.63

    .56

    .5 .8

    20

    10

    10A

    20

    10

    10A

    tr

    2

    IEC 947-4-1

    Compact: functions and characteristics

    motor protection (cont.)

    electronic trip unit STR43ME for Compact NS400to NS630 circuit breakers

    E32566

    E26987

    protection cLT (long time) overload protection,adjustable threshold, based on the actual

    rms current:vadjustable threshold (1)using five Io basesettings (0.5 to 0.8), and fine adjustment Irwith eight settings ranging from 0.8 to 1,v adjustable tripping time (2), in compliancewith tripping classes 10 A, 10 and 20 asdefined by IEC 947-4;c the STR43ME offers two motor coolingtime constants, associated with the motorstarting class:v short cooling time constant (the same as

    the heating time constant), providingmaximum continuity of service andsatisfactory motor protection,v long cooling time constant (four times theheating time constant), providing maximummotor protection,

    c single - phasing protection. The single -phasing complies with the recommendations

    of standard IEC 947-4-1. It becomesoperational whenever a phase currentimbalance of 40% or more is present;c ST (short time) short-circuit protection:v adjustable threshold Isd (3),v fixed time delay (4);c INST (instantaneous) short-circuitprotection, with fixed threshold (5).

    other functions Overload indications (%Ir)LED flashes when the current exceeds the

    long-time threshold Ir.

    Fault indicationsLEDs indicate the type of fault that causedtripping:c overload (LT protection)

    or abnormal component temperature (>Ir);c short-circuit (ST or instantaneousprotection) (>Isd);c single-phasing (LED on the right);c microprocessor malfunction (all three (>Ir),(>Isd) and single-phasing LEDs go on);Battery powered. Spare batteries aresupplied in an adapter box. When a faultoccurs, the LED indicating the type of faultgoes off after about 10 minutes to conservebattery power.The information is howeverstored in memory and the LED can be re-illuminated by pressing the battery/LED testpushbutton (6). The LED automatically goesoff and the memory is cleared when thecircuit breaker is reset.

    Testc test connector in front (8), for connection

    to a mini test kit or calibration test kit (seepage 73) to check circuit breaker operationafter fitting the trip unit or other accessories.c test button (6) for (%Ir), (>Ir), (>Isd) and(single-phasing) LEDs and battery.

    Self-monitoringThe circuit breaker trips for:c microprocessor faults;c abnormal temperatures.

  • 7/29/2019 Compact 80-1250

    38/35547Merlin Gerin

    A

    Ir I1 I2 I3

    options for trip unit STR43ME

    ammeter (I)A digital display continuously indicates the

    current of the phase with the greatest load.By pressing a scroll button, it is alsopossible to display successively thereadings of I1, I2, I3 an the long timethreshold setting Ir.LEDs indicate the phase or setting for whichthe current is displayed.

    Ammeter display limits:c minimum current u 0,2 x In (lower currentsare not displayed) ;c maximum current i 10 x In.

    E33990

    contactor tripping module(SDTAM)

    c opens the contactor in the event of an

    overload. It is thus possible to differentiatebetween tripping due to overloads and short-circuits;c may also be used to signal a thermal fault;c must be reset manually (locally or

    remotely;c compatible with the following controlvoltages:v 24 to 72 V DC and 24 to 48 V AC,v 110 to 240 V AC / DC;

    c fits in place of the MN and MX auxiliary

    voltage releases.

    communication (COM) Transmission of data to Digipact distributionmonitoring and control modules.

    Transmitted data:c settings;c phase currents (rms values);c highest current of the three phases;

    c overload condition alarm;c cause of tripping (overload, short-circuit,

    etc.).

    possible combinations c I;c I + COM;

    c SDTAM;c SDTAM + I;c SDTAM + I + COM.

  • 7/29/2019 Compact 80-1250

    39/355Merlin Gerin48

    electronic trip units for Compact C801...C1251

    electronic trip unit STR35ME

    electronic trip unit STR55UE

    other functions

    (STR35ME and STR55UE)Overload indication

    A LED in front (7) indicates the load level(current flowing through the circuit breakerwith respect to the Ir setting):c lit when load u 90% Ir;c flashing when load > 105% Ir.

    Test

    Test connector in front (8) for connection toa mini test kit or calibration test kit (seepage 73).

    protection (STR55UE)The trip units do not have a specific rating:c LT (long time) overload protection:v adjustable threshold Ir (1),v adjustable time delay (2), in compliancewith tripping classes 5, 10, 20 and 30 asdefined by IEC 947-4-1;c ST (short time) protection against medium-intensity short-circuits:v adjustable threshold Im (3),v adjustable time delay (4);c INST (instantaneous) protection againsthigh-intensity short-circuits, with adjustablethreshold I (5).

    protection (STR35ME)The trip units do not have a specific rating:c LT (long time) overload protection:v adjustable threshold Ir (1), with an OFF

    position to disable the LT protection,v fixed time delay, in compliance withtripping class 10 as defined by IEC 947-4-1;c ST (short time) protection against medium-intensity short-circuits:v adjustable threshold Im (3),v adjustable time delay (4);c INST (instantaneous) protection againsthigh-intensity short-circuits, with fixedthreshold I (5).

    Compact: functions and characteristics

    motor protection (cont.)

    E27366

    E27368

    E24038

    E23822

    5

    STR 55UE

    .63 .8

    .5 1

    xIn

    Io

    60 70 80 90 % Ir

    t Ir

    tr

    Im

    i

    tm

    Ih

    th

    105

    test Ir Im

    S

    T

    +

    +

    tr tm

    .9.95

    .8 1xIo

    .85

    15 48030

    24060

    at 1.5Ir

    46

    1.5 10xIr

    .3

    0 0

    .1

    .3

    .2

    82

    3

    .2

    .1

    Ic1

    .4

    .1

    .3

    on I2t offon I2t off

    TFR

    5

    120

    I5

    8

    2

    3

    46

    .9.95

    .8 1xIr

    .85

    A

    B

    10

    15

    8

    8

    C 801 NHC 1001 NH

    LL

    10

    C 1251NH

    12

    B

    A

    th

    Ih

    .2 .6

    .4

    .5

    .3

    xIn

    Ic1

    I

    fault

    .4

    .3

    .1

    .2.2

    test

    xIn

    3 51 48 21 7 6

    15 8

    C 801 NHC 1001 NH

    LL

    12

    C 1251NH

    t

    i

    Ir

    Im

    tm

    I

    120s

    A

    A1,5 Ir

    x In

    5

    STR 35ME

    .81

    .5xIn

    Io

    60 70 80 90 % Ir105

    test Ir Im

    +

    tm

    .9

    .95

    .8 1.85

    4

    6

    1.5 10xIr

    .3

    0 0

    .1

    .3

    .2

    82

    3

    .2

    .1

    on I2t off

    5

    1 1 38 47

    xIo

    on off

    off

    LR inoprant

    LT inoprativeIr = In

    off

    .63

    5

    Ir Im

    3

    I I

    t

    0

    1

    4

    OFF

    2

    5

    Ir Im

    3

    I I

    t

    0

    1

    4

  • 7/29/2019 Compact 80-1250

    40/35549Merlin Gerin

    Functionsc short-circuit protection using an integratedmagnetic trip unit MA with adjustablesettings;c suitability for isolation.

    ConnectionsFront connection to integrated connectors

    for bare cables with cross-sections from1.5 to 70 mm2.

    characteristics of short-circuit protection deviceswith separate overload protection

    Compact NS100...NS630with trip unit MAFor the protection of motors from 1.1 to250 kW (400 V), Compact NS100 to NS630circuit breakers must be equipped with aspecial trip unit MA with adjustablethresholds.

    This assembly ensures:cshort-circuit protection (magnetic trip unitwith adjustable thresholds);csuitability for isolation.For the Compact NS400 to NS630 circuitbreakers, trip unit MA is not interchangeable.The circuit breaker and trip unit are suppliedalready assembled.

    short-circuit protection (magnetic)rating (A) In (65C) 1.5 2.5 6.3 12.5 25 50 80

    tripping threshold (A) Im adjustable from

    6...14 x In

    Compact C801...C1251For the protection of motors from 160 to670 kW with Compact C801 to C1251 circuit

    breakers, equipped with an STR35ME or anSTR55UE trip unit, it is possible to disablethe LT protection.

    The circuit breakers ensure:c

    short-circuit protection (short time orinstantaneous);csuitability for isolation.

    Electrical characteristicsc Compact NS80/630, see page 40;cCompact C801/1251, see page 42.

    Compact NS80H-MAThis circuit breaker is specially designed forthe protection of motors rated up to 37 kW:cdue to its high current-limiting capacity, iteffectively protects motor starters (type-2coordination as defined by IEC 947-4, withcontactors);csmall size for easy installation in motorcontrol centre (MCC) switchboards.

    046751

    Compact NS80H-MA

    041624

    Compact NS250H

    045198

    Compact NS400H-MA

    trip unit forCompact NS100...NS630rating (A) In (65C) 2.5 6.3 12.5 25 50 100 150 220 320 500

    for Compact N/H/L NS100 c c c c c c

    circuit breaker NS160 c c c c

    NS250 c c c

    H/L NS400 c

    NS630 c

    short-circuit protection (magnetic)tripping Im adjustable from adjustable from

    threshold (A) 6...14 x In 9..14 x In 9..14 x In

  • 7/29/2019 Compact 80-1250

    41/355Merlin Gerin50

    Compact functions and characteristics

    protection of industrial control panels

    (**) for operational voltage up to 500 V

    Compact NS250H

    push

    totrip

    E44356

    Compact NSC100N

    054556

    0416

    25

    Compact circuit breakersnumber of poles

    electrical characteristics as per CEI 947-2 and EN 60 947-2rated current (A) In 40C

    rated insulation voltage (V) Ui

    ratde impulse withstand voltage (kV) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    DC

    ultimate breaking capacity Icu AC 50/60 Hz 220/240 V(kA rms) 380/415 V

    440 V

    500 V

    525 V

    660/690 V

    DC 250 V (1 pole)

    500 V (2 poles in series)

    service breaking capacity Ics (% Icu)

    utilisation category

    suitability for isolation

    endurance (C-O cycles) mechanical

    electrical 440 V - In/2

    440 V - In

    electrical characteritics as per UL 508breaking capacity (kA) 240 V

    480 V

    600 V

    protection (see following pages)protection against interchangeable trip unitsovercurrents (A) Ir setting current

    earth fault protection add-on Vigi module

    Vigirex relay

    installation and connectionfixed / front connection

    adaptator for 60 mm busbars

    indication and measurement auxiliariesauxiliary switches

    early-make or early-break contact

    electronic trip unit related functions

    voltage presence indicator

    current transformer module

    ammeter module

    insulation monitoring module

    control auxiliariesauxiliary releases

    motor mechanism

    rotary handles (direct, extended)

    installation and connection accessoriesbare cable connectors

    terminal extensions and spreaders

    terminal shields and phase barriers

    escutcheons

    DIN rail plate

    dimensions and weightsdimensions 3 poles, fixed, FCW x H x D (mm) 4 poles, fixed, FC

    weights (kg) 3 poles, fixed, FC

    4 poles, fixed, FC

  • 7/29/2019 Compact 80-1250

    42/35551Merlin Gerin

    AVAIL

    ABLE

    IN

    199

    9

    NSC100N NS100 NS160 NS250 NS400 NS6303, 4 3, 4 3, 4 3, 4 3, 4 3, 4

    100 100 150 220 320 500

    750 750 750 750 750 750

    8 8 8 8 8 8

    690 690 690 690 690 690

    250 500 500 500 500 500

    N N H N H N H N H N H42 85 100 85 100 85 100 85 100 85 100

    18 25 70 36 70 36 70 45 70 45 70

    18 25 65 35 65 35 65 42 65 42 65

    10 18 50 30 50 30 50 30 50 30 50

    10 18 35 22 35 22 35 22 35 22 35

    - 8 10 8 10 8 10 10 20 10 20

    5 (125 V) 50 85 50 85 50 85 - 85 - 85

    5 (250 V) 50 85 50 85 50 85 - 85 - 85

    100 100 100 100 100 100 100 100 100 100 100

    A A A A A A A A A A A

    c c c c c c c c c c c

    20000 50000 40000 20000 15000 15000

    10000 50000 40000 20000 12000 8000

    7000 30000 20000 10000 6000 4000

    42 85 85 85 85 85 85 85 85 85 85

    18 25 65 35 65 35 65 42 65 42 65

    10 10 10 10 10 18 18 18 18 30 30

    built-in c c c c c

    16...100 12.5...100 12.5...160 12.5...250 160...400 250...630

    c c c c c c

    c c c c c c

    c c c c c c

    - c c c c c

    c c c c c c

    c c c c c c

    c c c c c

    - c c c c c

    - c c c c c

    - c c c c c

    - c c c c c

    c c c c c c

    - c c c c c

    c c c c c c

    - c c c c c

    - c c c c c

    c c c c c c

    c c c c c c

    c c c c - -

    90 x 120 x 80 105 x 161 x 86 105 x 161 x 86 105 x 161 x 86 140 x 255 x 110 140 x 255 x 110

    120 x 120 x 80 140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 185 x 255 x 110 185 x 255 x 110

    1.0 1.6 1.6 1.9 6.0 6.0

    1.3 2.1 2.1 2.3 7.8 7.8

  • 7/29/2019 Compact 80-1250

    43/355Merlin Gerin52

    installation in an enclosure

    E44458

    200 150

    300

    Marking

    test

    + -IEC 947.4 / cl.10

    A

    Ir

    198209

    148

    157166 177

    187

    140220132

    Ir 13Ir

    7.2 Ir

    7.0 s

    STR 22 MEIn=220A > 1.05 Ir

    Vac115

    230460575

    15

    505050

    40

    75

    200150

    1ph 3phhp

    220A

    100% rated

    Minimum enclosure dimensions for installation

    Height (mm) Depth (mm) Width (mm)

    NSC100N 300 150 200NS100 N/H 457 130 208

    NS160 N/H 457 130 208

    NS250 N/H 457 130 208

    NS400 N/H - - -

    NS630 N/H - - -

    E42651

    LISTED MAN. MOTOR. CTRL.34XL

    NSC100N-NA

    Vac 115 230 460 575

    ratings (A) hp

    1 ph 3 ph 1 ph 3 ph 1 ph 3 ph 1 ph 3 ph

    16

    20

    25

    32

    40

    50

    63

    70

    80

    100

    1

    1.5

    2

    2

    3

    3

    5

    5

    7.5

    10

    2

    3

    5

    5

    7.5

    10

    10

    10

    3

    10

    10

    15

    15

    15

    20

    7.5

    5

    2

    3

    3

    5

    5

    7.5

    10

    10

    15

    20

    25

    30

    30

    5

    7.5

    10

    10

    15

    20

    25

    30

    30

    40

    10

    10

    15

    20

    30

    30

    40

    50

    60

    75

    7.5

    10

    10

    15

    20

    25

    30

    40

    50

    40

    10

    15

    20

    30

    30

    40

    60

    60

    75

    100tripping current 125% 100% rated

    This MMC is suitable for use on a circuit capable of deliveringnot more than the short-circuit current rating of this MMCindicated here below, or the upstream protective deviceinterrupting capability, whichever is less, when protected byany protective device for Group fusing or Group installation.

    SC current rating kA 50/60 HzVac

    240

    480600

    42

    1810

    wire size

    tightening torque

    lb-inch Nm

    14 AWG to 3/0 AWG Cu

    12 AWG to 4/0 AWG Al50 5.5

    temperature rating

    75C

    R

    Trip-unit marking

    device marking (circuit breaker with integreted tripunit)

    E42651

    UL / CSA logo

    cable cross