COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg...

37
COMMITTEES ON NFPA BUILDING CODE Technical Committee on Structures, Construction and Materials NFPA 5000 and NFPA 703 ROC Meeting Agenda Tuesday, October 5, 2010 Hotel Monteleone New Orleans, LA 1. Call to Order. The BLD-SCM meeting will be called to order by Chair, Peter J. Willse at 8:00 a.m. on Tuesday, October 5, 2010, at the Hotel Monteleone, New Orleans, LA. 2. Introduction of Attendees. A current committee roster is attached. (Page 2) 3. Approval of Minutes. Approve the NFPA 5000 and NFPA 703 September 22, 2009 Meeting Minutes. (Page 4) 4. TC Meeting Presentation (Page 7) 5. NFPA 5000 Public Comment Preparation (ROC). Review of NFPA 5000 Public Comments. (Page 13) 6. NFPA 703 Public Comment Preparation (ROC). Review of NFPA 703 Public Comments. (Page 36) 7. New Business. Fire Protection Research Foundation project ideas 8. Date and Location of Next Meeting. 9. Adjournment. Attachments BLD-SCM ROC AGENDA Page 1 of 37

Transcript of COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg...

Page 1: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

COMMITTEES ON NFPA BUILDING CODE Technical Committee on Structures, Construction and Materials

NFPA 5000 and NFPA 703 ROC Meeting Agenda Tuesday, October 5, 2010

Hotel Monteleone

New Orleans, LA

1. Call to Order.

The BLD-SCM meeting will be called to order by Chair, Peter J. Willse at 8:00

a.m. on Tuesday, October 5, 2010, at the Hotel Monteleone, New Orleans, LA.

2. Introduction of Attendees.

A current committee roster is attached. (Page 2)

3. Approval of Minutes.

Approve the NFPA 5000 and NFPA 703 September 22, 2009 Meeting Minutes.

(Page 4)

4. TC Meeting Presentation (Page 7)

5. NFPA 5000 Public Comment Preparation (ROC).

Review of NFPA 5000 Public Comments. (Page 13)

6. NFPA 703 Public Comment Preparation (ROC).

Review of NFPA 703 Public Comments. (Page 36)

7. New Business. Fire Protection Research Foundation project ideas

8. Date and Location of Next Meeting.

9. Adjournment. Attachments

BLD-SCM ROC AGENDA Page 1 of 37

Page 2: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Address List No PhoneStructures, Construction, and Materials BLD-SCM

Building Code

Tracy L. Golinveaux9/2/2010

BLD-SCM

Peter J. Willse

ChairXL Global Asset Protection Services100 Constitution Plaza, 12th FloorHartford, CT 06103

I 3/21/2006BLD-SCM

Jesse J. Beitel

PrincipalHughes Associates, Inc.3610 Commerce Drive, Suite 817Baltimore, MD 21227-1652

SE 3/21/2006

BLD-SCM

David S. Collins

PrincipalThe Preview Group, Inc.632 Race StreetCincinnati, OH 45202American Institute of Architects

SE 3/21/2006BLD-SCM

Ralph Dorio

PrincipalInsurance Services Office, Inc.545 Washington BoulevardJersey City, NJ 07310-1686

I 3/21/2006

BLD-SCM

Jeffrey Feid

PrincipalState Farm Insurance CompanyOne State Farm Plaza D-1Bloomington, IL 61710-0001

I 3/21/2006BLD-SCM

Michael A. Gardner

PrincipalGypsum Association6525 Belcrest Road, Suite 480Hyattsville, MD 20782

M 3/21/2006

BLD-SCM

Mark S. Graham

PrincipalNational Roofing Contractors Association10255 West Higgins Road, Suite 600Rosemont, IL 60018-5607

IM 10/4/2007BLD-SCM

J. C. Harrington

PrincipalFM Global1151 Boston Providence TurnpikePO Box 9102Norwood, MA 02062-9102Alternate: Richard J. Davis

I 3/21/2006

BLD-SCM

Alfred J. Hogan

Principal3391 Lakeview Drive, SEWinter Haven, FL 33884-3172New England Association of Fire Marshals

E 7/26/2007BLD-SCM

Joseph T. Holland

PrincipalHoover Treated Wood Products1225 North Halifax AvenueDaytona Beach, FL 32118Alternate: David G. Bueche

M 3/21/2006

BLD-SCM

Bonnie E. Manley

PrincipalAmerican Iron and Steel Institute41 Tucker RoadNorfolk, MA 02056Alternate: Farid Alfawakhiri

M 3/21/2006BLD-SCM

Joseph J. Messersmith, Jr.

Principal11479 Primose LaneRockville, VA 23146Portland Cement AssociationAlternate: Stephen V. Skalko

M 3/21/2006

BLD-SCM

Eugene M. Novak, Jr.

PrincipalCommonwealth of MassachusettsDepartment of Public Safety19 Partridge RoadFramingham, MA 01701-4242

E 3/21/2006BLD-SCM

Dennis L. Pitts

PrincipalAmerican Forest & Paper AssociationAmerican Wood Council1721 West Plano Parkway, #224Plano, TX 75075American Forest & Paper Association

M 3/21/2006

1BLD-SCM ROC AGENDA Page 2 of 37

Page 3: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Address List No PhoneStructures, Construction, and Materials BLD-SCM

Building Code

Tracy L. Golinveaux9/2/2010

BLD-SCM

James A. Rossberg

PrincipalAmerican Society of Civil EngineersStructural Engineering Institute1801 Alexander Bell DriveReston, VA 20191

SE 3/15/2007BLD-SCM

Joseph H. Versteeg

PrincipalVersteeg Associates86 University DriveTorrington, CT 06790International Fire Marshals Association

E 3/21/2006

BLD-SCM

John Younghusband

PrincipalAon/Schirmer Engineering Corporation21221 South Western Ave., Suite 100Torrance, CA 90501Alternate: Moriel E. Kaplan

I 10/27/2009BLD-SCM

Farid Alfawakhiri

AlternateAmerican Iron and Steel Institute594 Windham LaneNaperville, IL 60563Principal: Bonnie E. Manley

M 7/23/2008

BLD-SCM

David G. Bueche

AlternateHoover Treated Wood Products13768 West Asbury CircleLakewood, CO 80228Principal: Joseph T. Holland

M 7/28/2006BLD-SCM

Richard J. Davis

AlternateFM Global1151 Boston-Providence TurnpikePO Box 9102Norwood, MA 02062-9102Principal: J. C. Harrington

I 3/21/2006

BLD-SCM

Moriel E. Kaplan

AlternateAon/Schirmer Engineering Corporation6305 Ivy Lane, Suite 220Greenbelt, MD 20770Principal: John Younghusband

I 10/27/2009BLD-SCM

Stephen V. Skalko

AlternatePortland Cement Association128 Summerfield DriveMacon, GA 31210Portland Cement AssociationPrincipal: Joseph J. Messersmith, Jr.

M 3/21/2006

BLD-SCM

Tracy L. Golinveaux

Staff LiaisonNational Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

01/04/2010

2BLD-SCM ROC AGENDA Page 3 of 37

Page 4: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

NFPA 703 and NFPA 5000 ROP Meeting Minutes of the Technical Committee on Structures, Construction and

Materials September 22, 2009

Embassy Suites Hotel Cleveland, OH

Item 1, Call to Order. The meeting of the NFPA 703 and NFPA 5000 Technical Committee on Structures, Construction and Materials was called to order by the Chair, Pete Willse at 8:00 a.m. on Tuesday, September 22, 2009 at the Embassy Suites Hotel, Cleveland - Downtown, Ohio.

Item 2, Introduction of Attendees. The Chair opened the meeting with welcoming remarks, and self-introductions of meeting attendees and guests were conducted. The following Principal, Voting Alternate and Alternate Members were present:

NAME

COMPANY

Pete Willse, Chair XL Global Asset Protection Services Jesse Beitel, Principal Hughes Associates, Inc.

Dave Collins, Principal The Preview Group, Inc./Representing American Institute of Architects

Ralph Dorio, Principal Insurance Services Office, Inc. Jeffrey Feid, Principal State Farm Insurance Company

J.C. Harrington, Principal FM Global Joseph Holland, Principal Hoover Treated Wood Products Joseph Versteeg, Principal International Fire Marshals Association

Dennis Pitts, Voting Alternate American Forest & Paper Association David Bueche, Alternate to J. Holland Hoover Treated Wood Products

BLD-SCM ROC AGENDA Page 4 of 37

Page 5: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

NFPA Technical Committee on Structures, Construction and Materials ROP Meeting September 22, 2009 Page 2

2

The following Technical Committee Principal Members were absent (with no alternate present):

NAME COMPANY Michael Gardner, Principal Gypsum Association

Mark Graham, Principal National Roofing Contractors Association Alfred Hogan, Principal New England Association of Fire Marshals

Bonnie Manley, Principal American Iron and Steel Institute Jim Messersmith, Principal Portland Cement Association

Gene Novak, Principal Commonwealth of Massachusetts James Rossberg, Principal American Society of Civil Engineers

The following Guests were in attendance:

NAME COMPANY Jonathan Humble AISI

Thomas Sputo Steel Deck Institute Robert Wessel Gypsum Association

The following NFPA staff was in attendance:

Allan Fraser Robert Solomon

Item 3, Approval of Minutes. The minutes of the NFPA 703 and NFPA 5000 October 1, 2007 ROC Meeting Minutes were approved as submitted. Item 4, NFPA 5000 Public Proposal Preparation. The committee reviewed and acted on 43 public proposals. 6 committee proposals were developed.

BLD-SCM ROC AGENDA Page 5 of 37

Page 6: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

NFPA Technical Committee on Structures, Construction and Materials ROP Meeting September 22, 2009 Page 3

3

Item 5, NFPA 703 Public Proposal Preparation. The committee reviewed and acted on 13 public proposals (no committee proposals were developed). Item 6, New Business. There was no new business discussed. Item 7, Date and Location of Next Meeting. The ROC meeting will be held Tuesday, October 5, 2010 in New Orleans, LA. Item 8, Adjournment.

The Chair, Pete Willse, adjourned the meeting at 3:00 p.m. AF/DM

BLD-SCM ROC AGENDA Page 6 of 37

Page 7: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Page 1

BLD/SAF CommitteesReport on Comments (ROC) Meetings

NFPA 101 and NFPA 5000 ROC Meetings

1

Meetings

October 2010

Monteleone Hotel

New Orleans, LA

BLD/SAF CommitteesReport on Comments (ROC) Meetings

NFPA is concerned with your Safety

If the fire alarm sounds, we will evacuate

2

,

Exiting…exits are ……..

BLD/SAF CommitteesReport on Comments (ROC) Meetings

OverviewGeneral Procedures for Meeting

Timeline for Processing the Code

3

Committee Actions

Committee Statements

Balloting

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Participation in NFPA Committee Meetings is generally limited to Committee Members and NFPA Staff

4

Participation by guests is usually granted by the Chair

The Chair may limit the time of any presentation (member or guest)

BLD/SAF CommitteesReport on Comments (ROC) Meetings

All guests are requested to sign-in and identify their affiliation

Members please verify/update your contact

5

Members, please verify/update your contact information on pages attached to sign-in

Use of tape recorders or other means of reproducing verbatim transcriptions of the meeting are prohibited

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Formal voting Secured by post-meeting letter ballot (2/3

majority agreement)

V ti d i ti i i l

6

Voting during meeting requires simple majority vote and is used to establish a sense of agreement that can be letter balloted

Only the results of the letter ballot determine the official position of the Committee on any Comment

BLD-SCM ROC AGENDA Page 7 of 37

Page 8: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Page 2

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Reminder to Members in Special Expert (SE) Category: If representing a non-SE interest (such as a consultant representing a manufacturer or an association of

7

a manufacturer or an association of users), this must be declared. The member should refrain from voting on the issue.

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Remaining timeline for processing the 2012 edition of NFPA 101 and NFPA 5000

Comment Closing Date: September 3, 2010 TC ROC meetings:

8

g Core Chapters October 4-8; balloting follows Occupancy Chapters October 18-22; balloting follows

TCCs meet: January 5-6, 2011 NITMAM Closing Date: April 8, 2011 NFPA Annual Meeting: June 12-15, 2011 Amendment ballots: mid to late June (TCC – July) Standards Council Issuance: August 11, 2011

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Report on Comments (ROC) preparation - today

9

BLD/SAF CommitteesReport on Comments (ROC) Meetings

General Procedures Follow Robert’s Rules of Order

Prior to discussion, a motion is

10

o to d scuss o , a ot o srequired

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Committee Member participation:

Member addresses the Chair

Member receives recognition from the

11

e be ece es ecog t o o t eChair

Member speaks to the Chair

Member poses questions to others through the Chair

Member answers questions through the Chair

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Committee Chair Actions:

States the Motion

Calls for discussion

12

Ca s o d scuss o

Ensures all issues have been heard

Takes the Vote

Announces the result of the Vote

BLD-SCM ROC AGENDA Page 8 of 37

Page 9: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Page 3

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Committee Actions on Comments:

Accept

Accept In Principle

13

Accept In Principle

Accept In Part

Accept In Principle In Part

Reject

Hold

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Accept: The Comment is accepted by the Committee

without change

No Committee Statement is required for an

14

No Committee Statement is required for an Accept, but one is permitted to be provided for clarification

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Accept in Principle: The Committee agrees with the change in

principle, and accepts the Comment but with change in wording

15

change in wording

Committee must indicate change in Committee Action and rationale in Committee Statement

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Accept in Part: Only part of the Comment is accepted

Committee must indicate accepted part in Committee Action and address rejected part and

16

Committee Action and address rejected part and rationale for rejection in Committee Statement

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Accept in Principle in Part: A combination of Accept in Principle and Accept

in Part

Committee must indicate accepted and changed

17

Committee must indicate accepted and changed parts in Committee Action

Committee must indicate rejected parts and rationale for changed/rejected parts in Committee Statement

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Reject: The Committee rejects the Comment in entirety

Committee must indicate reasons for rejection in Committee Statement

18

Committee Statement

BLD-SCM ROC AGENDA Page 9 of 37

Page 10: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Page 4

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Hold:The Committee holds for processing as a proposal for next cycle, a Comment that:

19

introduces concept that has not had public review

changes text to point TC would have to restudy ROP or other affected parts of document

proposes something that can’t be handled within time frame for processing the ROC

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Committee Statements (Explaining the Committee Action): Action of “Accept” requires no

20

Committee Statement

All other actions require a Committee Statement to explain the action of the Committee

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Committee Statement must include a valid reason for the action

The reason should be technical where li bl

21

applicable

Must explain why the Comment was not accepted

Acceptance of another Comment is not an adequate reason to reject a Comment

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Committee Statements (continued)

Should not reference a Comment with opposing action unless the referenced C t ti f t il l i th

22

Comment satisfactorily explains the rejection

Should not make a vague reference to intent

Should explain how submitter’s substantiation is inadequate

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Letter ballots are on the Committee Action

The Ballot form allows you to vote

Affirmative on all actions

23

Affirmative on all actions except those specifically noted

The Ballot form provides a column for affirmative with comment

Note: This box only needs to be checked if there is an accompanying comment

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Your ballot form is electronically submit-ableYou can save a copy f lf

24

for yourself

You can also print and fax/mail it to NFPA

All you need is (free) Adobe Reader

BLD-SCM ROC AGENDA Page 10 of 37

Page 11: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Page 5

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Alternates are encouraged to return ballots (insurance if Principal’s ballot not received)

B ll ti P

25

Balloting Process: Initial letter ballot

Circulation of Negatives, if any received

Circulation serves as second ballot to allow change of vote

Final vote reported

BLD/SAF CommitteesReport on Comments (ROC) Meetings

Questions?

26

Questions?

BLD-SCM ROC AGENDA Page 11 of 37

Page 12: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

ANNUAL 2011 REVISION CYCLE

NFPA 101 AND NFPA 5000

PROCESS STAGE PROCESS STEP

DATES FOR TC

DATES FOR TCC

1 PRELIMINARY 1.0 Notification of intent to enter cycle

2 REPORT ON PROPOSALS

(ROP)

2.1 Proposal closing date 7/31/09 7/31/09 2.2 Final date for ROP meeting 12/11/09 2.3 Final date for mailing TC ballots 12/18/09 2.4 Receipt of (TC) ballots by staff liaison 1/8/10 2.5 Receipt of TC recirculation ballots 1/22/10 2.6 Final date for TCC meeting 3/31/10 2.7 Final date for mailing TCC ballots 4/6/10 2.8 Receipt of TCC ballots 4/27/10 2.9 Receipt of TCC recirculation ballots 5/14/10 2.10 Final copy (w/ ballot statements) to Secretary, Standards Council 5/18/10 2.11 Completion of Reports 6/4/10 2.12 ROP Published and Posted 6/25/10

3 REPORT ON COMMENTS

(ROC)

3.1 Comment closing date 9/3/10 9/3/10 3.2 Final date for ROC meeting 10/22/10 3.3 Final date for mailing TC ballots 10/29/10 3.4 Receipt of (TC) ballots by staff liaison 11/12/10 3.5 Receipt of TC recirculation ballots 11/26/10 3.6 Final date for TCC meeting 1/6/11 3.7 Final date for mailing TCC ballots 1/11/11 3.8 Receipt of TCC ballots 1/21/11 3.9 Receipt of TCC recirculation ballots 2/1/11 3.10 Final copy (w/ ballot statements) to Secretary, Standards Council 2/10/11 3.11 Completion of Reports 2/17/11 3.12 ROC Published and Posted 2/25/11

4

TECH SESSION PREPARATION

ON & ISSUANCE OF

CONSENT DOCUMENTS

4.1 Notice of Intent to Make a Motion (NITMAM) Closing Date 4/8/11 4/8/11 4.2 Posting of Filed NITMAM 5/6/11 5/6/11 4.3 Council Issuance Date for Consent Documents 5/31/11 5/31/11

4.4 Appeal Closing Date for Consent Documents 6/15/11 6/15/11

5 TECHNICAL SESSION

5.0 Association Meeting for Documents with Certified Amending Motions 6/12-16/11 6/12-16/11

6

APPEALS & ISSUANCE OF DOCUMENTS

W/CAMS

6.1 Appeal closing date for Documents with Certified Amending Motions 7/6/11 7/6/11

6.2 Council issuance for Documents with Certified Amending Motions 8/11/11 8/11/11

Schedules for Revision Cycles may change. Please check the NFPA website (www.nfpa.org) for the most up-to-date information on schedules. March 2009 REVISED: September, 2010

BLD-SCM ROC AGENDA Page 12 of 37

Page 13: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-3 Log #107 BLD-SCM

_______________________________________________________________________________________________Bonnie E. Manley, American Iron and Steel Institute / Rep. American Institute of Steel Construction

5000-9Revise Section 2.3.4 as follows:

American Institute of Steel Construction, One East Wacker Drive, Suite 3100, Chicago, IL60601-2001.ANSI/AISC 341, Seismic Provisions for Structural Steel Buildings, 20052010.ANSI/AISC 360, Specification for Structural Steel Buildings, 20052010.

This comment updates the references to AISC 341 and AISC 360. Both editions are complete and willbe published by the end of the year. Summaries of the major changes follow.Note: Supporting material is available for review at NFPA Headquarters.

1Printed on 9/16/2010BLD-SCM ROC AGENDA Page 13 of 37

Page 14: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-4 Log #109 BLD-SCM

_______________________________________________________________________________________________Bonnie E. Manley, American Iron and Steel Institute

5000-10Revise Section 2.3.5 as follows:

American Iron and Steel Institute, 1401 Connecticut Avenue, Suite 705, Washington, DC20036.AISI-S100, , 2007, including

Supplement 2 (2010).AISI-S200, , 2007.AISI-S210, , 2007.AISI-S211, , 2007.AISI-S212, , 2007.AISI-S213, , 2007, including Supplement 1

(2009).AISI-S214, , including Supplement 2 (June

2008).AISI-S230, ,

including Supplement 2 (June 2008).AISI S 214 and S230 references have been updated by a tentative interim amendment (TIA). See page 1.

This comment updates the references to the AISI documents. All supplements are complete andavailable to the public.Supplement No. 2 to the , 2007

edition, includes the following updates and improvements: Included all the changes and updates provided in Supplement No. 1 to the

, 2007 Edition. Supplement 1 to AISI S100,, 2007 Edition, modifies Section F1.1, Load and

Resistance Factor Design and Limit States Design, to recognize that the behavior and probability of failure for acomposite interior partition wall stud differs from the direct load bearing system. Additionally, a reference to SupplementNo. 1 of AISI S213, , is included. TheSupplement also has included errata to the North American Specification. Added new Section B2.5, Uniformly Compressed Elements Restrained by Intermittent Connections. Unified country specific provisions, C2, Tension Members, and the section has moved from Appendices A and B to

the main body of the . Moved the simplified provisions for determine distortional buckling strength of C- or Zsection beams and columns to

the . Revised Sections D1.1, D1.2, D3 and D3.2 to clarify certain terminologies. Consolidated whole Chapter E, Connections and Joints. Additionally, flare groove weld provisions were revised; and

the interaction check of combined shear and tension of arc spot weld was added. Expanded the geometric and material limitations of pre-qualified columns and beams for using the safety and

resistance factors defined in Sections 1.2.1 and 1.2.2, respectivelyChanges made in Supplement 1 to AISI S213,

, 2007 Edition include the following: Rd values in Table A4-1 for diagonal strap braced (concentric) walls were adjusted to match the values approved by

the Canadian National Committee on Earthquake Engineering (CANCEE) for inclusion in the National Building Code ofCanada (NBCC) seismic provisions. Language in C1.1 was modified to clarify when design must comply with the special seismic requirements. The existing provisions on setbacks in Section C2, which the Committee felt should be limited to prescriptive

methods with defined limits of applicability, were replaced with a requirement deemed to be more appropriate for adesign standard. Adjustments were made to Table C2.1-3 for 0.027” steel sheet, one side, based on testing at the University of North

Texas (Yu, 2007). Designation thickness for stud, track and blocking associated with the existing tabulated values wasincreased from 33 mils (min.) to 43 mils (min.). New values were added for designation thickness for stud, track andblocking equal to 33 mils (min.).

2Printed on 9/16/2010BLD-SCM ROC AGENDA Page 14 of 37

Page 15: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000 Equation C2.1-1 for determining the design deflection of a blocked wood structural panel or sheet steel shear wall

was consolidated for SI and Metric units. The word “countersunk” was deleted and commentary added to clarify provisions for tapping screws to attach wood

structural panel sheathing in Section C2.2.2. Language in C3.3.2 was modified to clarify when the uplift anchorage and boundary chords must comply with the

special seismic requirements. Equation D2.1-1 for determining the design deflection of a blocked wood structural panel diaphragm was

consolidated for SI and Metric units.Note: Supporting material is available for review at NFPA Headquarters.

_______________________________________________________________________________________________5000-5 Log #111 BLD-SCM

_______________________________________________________________________________________________Bonnie E. Manley, American Iron and Steel Institute

5000-75aConfirm and update all references to ASCE 7-10.

The 2010 edition of ASCE 7 has undergone a major update from the 2005 edition. Not only has thewind load chapter (Chapter 6) been expanded to cover Chapters 26 through 31, but the seismic maps have beenupdated and the associated terminology has been changed. Each reference to ASCE 7 in NFPA 5000 needs to beevaluated for accuracy and updated, if necessary.Note: Supporting material is available for review at NFPA Headquarters.

3Printed on 9/16/2010BLD-SCM ROC AGENDA Page 15 of 37

Page 16: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-13 Log #131 BLD-SCM

_______________________________________________________________________________________________Bonnie E. Manley, American Iron and Steel Institute / Rep. Steel Joist Institute

5000-21Revise 2.3.32 as follows:

Steel Joist Institute, 1173B London Links Drive, Forest, VA 245513127 Mr. Joe WhiteAvenue, Myrtle Beach, SC 29577 6760.SJI CJ, 20062010.SJI JG, 20052010

2005.SJI K, 2010.SJI LH/DLH.

20052010.2005.

This comment editorially corrects the SJI references to reflect the actual document titles and updatesthe document editions to 2010. Major changes to the new editions of the SJI standard specifications include thefollowing:· Most significant is the extension of the DLH joist range from maximums of 72” deep

and 144 feet long to maximums of 120” deep and 240 feet long. In conjunction with the increased range, the standardcamber for spans over 100 feet has been reduced and the LH/DLH Load Tables have been converted from a Clearspanto Span basis. An alternate “load/load” method of specifying longspan joists has been introduced. Changes were alsomade with regard to Joist Substitutes and Top Chord Extensions.· Substantial changes were made to the criteria for the spacing of bridging rows and the design of bridging.

The changes make the criteria more cohesive between K-Series and LH-Series joists.· A number of changes were made relative to bearing seat and end anchorage conditions —

primarily incremental criteria rather than one standard for all LH/DLH joists due to the broad range. In addition, designresponsibilities are better defined and additional options for masonry bearing conditions are permitted.· Several design criteria or checks that were already being done but had not been shown in the SPEC

are now included, such as node shear, girder top chord transverse bending, and weld design criteria. Based on SJIresearch, new criteria for crimped end angle webs have been applied.· The Code of Standard Practice is updated with more discussion of the options available

when specifying joists for non-uniform loads.Several other minor changes and editorial/clarification changes are being finalized. Specifically, SJI is in the process of

receiving Public Review and Canvass Committee reviews and ballots for their standards. They anticipate having asecond public review later this fall and plan on completing the standards in the 4th Quarter of 2010.

Note: Supporting material is available for review at NFPA Headquarters.

4Printed on 9/16/2010BLD-SCM ROC AGENDA Page 16 of 37

Page 17: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-21 Log #8 BLD-SCM

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

5000-37Revise definition to read as follows:

3.3.46.3* Thermal Barrier. A material that limits the average temperature rise of an unexposed surface to not morethan 250°F (139°C) for a specified fire exposure complying with the standard time–temperature curve of NFPA 251,Standard Methods of Tests of Fire Resistance of Building Construction and Materials. A material, product, or assemblythat prevents or delays ignition of an unexposed surface by limiting the temperature rise and by acting as a flameexposure barrier for a 15-minute time period.A.3.3.46.3 Thermal Barrier. Finish ratings, as published in the UL Fire Resistance Directory, are one way of determiningthermal barrier. A test method developed in order to assess whether a material, product, or assembly constitutes athermal barrier (NFPA 275) requires thermal barriers to meet both a test for fire resistance (which limits temperature riseon the unexposed side) and for reaction-to-fire (intended to prevent or delay ignition of the material on the unexposedside). The reaction to fire test can be NFPA 286, FM 4880, UL 1040 or UL 1715.

With the development of NFPA 275 the existing definition of thermal barrier is no longer correctbecause thermal barriers both limit the temperature rise and act as a flame exposure barrier, to delay or prevent ignition.The definition and the proposed annex note have been amended to clarify this. This makes the definition more generic.For information: thermal barrier is referred to in NFPA 5000 in the following locations: 26.2.3.6.1 (where it applies more

generically than to foam plastic), 37.4.4 (where it applies to MCMs; NFPA 275 applies also to MCMs), 48.3.3 (where itapplies to foam plastics), 48.4.1.3 (where it applies to foam plastics), 48.4.1.8.3 (which refers back to 48.3.3) and 48.4.3(where it applies to foam plastics).The technical committee should consider whether the revised definition of thermal barrier applies to section 26.2.3.6.1.

The commenter believes it does.In view of the TCC comment and the fact that the committee on Fire Protection Features did not see the action of thecommittee on Structures, Construction, and Materials, this comment is directed at both committees; they acted onproposals 5000-36 and 5000-37 respectively.

_______________________________________________________________________________________________5000-31 Log #9 BLD-SCM

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

5000-68bReject proposal 5000-68b.

This proposal introduces a proprietary concept that is not appropriate for a code or standard because itis not related to the performance of the material. Different methods exist or could be developed to manufacturefire-retardant-treated wood (FRTW) and they may or may not involve the pressure process. The issue is whether FRTWdoes or does not perform as required: flame spread index no larger than 25, no significant progressive combustion andno flame spread beyond 12.5 ft.This proposal also introduces a requirement (that the material must be listed and labeled) which should not be in adefinition but should be in the body of the document. The NFPA Manual of Style does not allow requirements indefinitions. I agree that FRTW should be listed and labeled but the definition should not state this requirement; therequirement should be in a section in the body of NFPA 5000.

5Printed on 9/16/2010BLD-SCM ROC AGENDA Page 17 of 37

Page 18: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-53 Log #17b BLD-SCM

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

5000-76Revise text to read as follows:

7.2.3.2.14 Ceiling and Raised Floor Plenums. The space between the top of the finished ceiling and the underside ofthe floor or roof above and the space between the top of the finished floor and the underside of a raised floor Plenums*shall be permitted to be used to supply air to the occupied area or return and exhaust air from the occupied area,provided that the requirements of 7.2.3.2.15 through 7.2.3.2.21 7.2.3.2.20 are met.A.7.2.3.2.14 NFPA 90A recognizes the following types of plenums: ceiling cavity plenum, apparatus casing plenum,

air-handling room plenum and raised floor plenum. The requirements in NFPA 90A are different for each type of plenumand Chapter 3 of this code shows definitions for each type of plenum.7.2.3.2.15 Plenum Materials Combustibility. Materials within a ceiling cavity plenum exposed to the airflow shall comply

with the requirements of section 4.3.11 of NFPA 90A be noncombustible or comply with one of the following.[90A:4.3.11.2.6]7.2.3.2.15.1 Electrical wires and cables and optical fiber cables shall be listed as having a maximum peak opticaldensity of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500mm) or less when tested in accordance with NFPA 262, Standard Method of Test for Flame Travel and Smoke of Wiresand Cables for Use in Air-Handling Spaces or shall be installed in metal raceways, metal sheathed cable, or totallyenclosed non-ventilated busway. [90A:4.3.11.2.6.1]7.2.3.2.15.2 Pneumatic tubing for control systems shall be listed as having a maximum peak optical density of 0.5 orless, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or less whentested in accordance with ANSI/UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and SmokeCharacteristics. [90A:4.3.11.2.6.2]7.2.3.2.15.3 Nonmetallic fire sprinkler piping shall be listed as having a maximum peak optical density of 0.5 or less, anaverage optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or less when testedin accordance with ANSI/UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and SmokeCharacteristics. [90A:4.3.11.2.6.3]7.2.3.2.15.4 Optical-fiber and communication raceways shall be listed as having a maximum peak optical density of 0.5or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or lesswhen tested in accordance with ANSI/UL 2024, Standard for Optical-Fiber and Communications Cable Raceway.[90A:4.3.11.2.6.4]7.2.3.2.15.5 Loudspeaker recessed lighting fixture and other electrical equipment with combustible enclosures,including their assemblies and accessories, cable ties, and other discrete products shall be permitted in the ceilingcavity plenum where listed as having a maximum peak optical density of 0.5 or less, an average optical density of 0.15or less, and a peak heat release rate of 100 kW or less when tested in accordance with UL 2043, Standard for Fire Testfor Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces.[90A:4.3.11.2.6.5]7.2.3.2.15.6 Supplementary materials for air distribution systems shall be permitted when complying with the provisionsof 4.3.3 of NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. [90A:4.3.11.2.6.6]7.2.3.2.15.7 Smoke detectors shall not be required to meet the provisions of 7.2.3.2.15. [90A:4.3.11.2.6.7]7.2.3.2.15.8 Fire-retardant-treated wood complying with Chapter 45 shall be permitted.7.2.3.2.16 Wall or ceiling finish in plenums shall comply with section 4.3.11.6 of NFPA 90A.7.2.3.2.16 7.2.3.2.17 Plenum Fire Stopping. The integrity of the fire stopping for penetrations shall be maintained.7.2.3.2.17 7.2.3.2.18 Plenum Light Diffusers. Light diffusers, other than those made of metal or glass, used inair-handling light fixtures shall be listed and marked as follows:Fixture Light Diffusers for Air-Handling Fixtures7.2.3.2.18 7.2.3.2.19 Plenum Air Temperature. The temperature of air delivered to plenums shall not exceed 250°F(121°C).7.2.3.2.19 7.2.3.2.20 Plenum Materials Exposure. Materials used in the construction of a plenum shall be suitable forcontinuous exposure to the temperature and humidity conditions of the environmental air in the plenum.7.2.3.2.20 7.2.3.2.21 Ceiling Plenum Tested Assembly. Where the plenum is a part of a floor/ceiling or roof/ceilingassembly that has been tested or investigated and assigned a fire resistance rating of 1 hour or more, and the assemblycontains air ducts and openings for air ducts, all the materials and the construction of the assembly, including the air

6Printed on 9/16/2010BLD-SCM ROC AGENDA Page 18 of 37

Page 19: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000duct materials and the size and protection of the openings, shall conform with the design of the fire resistance–ratedassembly, as tested in accordance with NFPA 251, Standard Methods of Tests of Fire Resistance of BuildingConstruction and Materials; ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials;or UL 263, Standard for Fire Tests of Building Construction and Materials.48.4.3* Plenums. The use of foam plastic insulation as wall or ceiling finish in plenums shall comply with section4.3.11.6 of NFPA 90A. be permitted where the insulation meets one of the following criteria:(1) The foam plastic insulation complies with 48.3.2.1 and is separated from the plenum by a thermal barrier complyingwith 48.3.3.(2) The foam plastic insulation has a flame spread index of 25 or less and a smoke developed index of 50 or less whentested in accordance with ASTM E 84 or UL 723 and meets one of the following criteria:(a) The foam plastic is separated from the plenum by a thermal barrier complying with 48.3.3.(b) The foam plastic is approved based on tests conducted in accordance with 48.4.4.(3) The foam plastic insulation complies with 48.3.2.1 and is covered by corrosion-resistant steel having a base metalthickness of not less than 0.016 in. (0.4 mm) and meets one of the following:(a) The foam plastic is separated from the plenum by a thermal barrier complying with 48.3.3.(b) The foam plastic is approved based on tests conducted in accordance with 48.4.4.A.48.4.3 These requirements are consistent with the requirements in section 7.2.3.2.17 of this code.Also, add the following definitions into chapter 3:Air-Handling Unit Room Plenum. An individual room containing an air-handling unit(s) used to gather air from varioussources and combine the air within the room for returning to the air-handling unit. [90A: 3.3.22.1]Apparatus Casing Plenum. A sheet metal construction attached directly to a fan enclosure, fan coil unit, air-handlingunit, or furnace bonnet for the purpose of connecting distribution ducts. [90A: 3.3.22.2]Ceiling Cavity Plenum. The space between the top of the finished ceiling and the underside of the floor or roof abovewhere used to supply air to the occupied area, or to return or exhaust air from the occupied area. [90A: 3.3.22.3]Raised Floor Plenum. The space between the top of the finished floor and the underside of a raised floor where used tosupply air to the occupied area, or to return or exhaust air from the occupied area. [90A: 3.3.22.4]

NFPA Standards Council specified that NFPA 90A has primary jurisdiction over materials in plenums.The text contained in present sections 7.2.3.2.14 through 7.2.3.2.20 and that contained in present section 48.4.3 ofNFPA 5000 is not consistent with either the 2009 or the upcoming 2012 editions of NFPA 90A. This needs to bechanged. Moreover, the requirements for Wall or Ceiling Finish in Plenums (from 4.3.11.6 of NFPA 90A and itssubsections) are missing in NFPA 5000 or are incorrect in 48.4.3. The permission to use fire retardant treated wood in7.2.3.2.15.8 is not consistent with the requirements in NFPA 90A. Finally, the requirements in NFPA 90A are differentfor each of the four types of plenums recognized by NFPA 90A.This comment deletes all the specific requirements and refers to section 4.3.11 of NFPA 90A. A section on wall or

ceiling finish in plenums is added (simply with reference to section 4.3.11.6 of NFPA 90A) because wall or ceiling finishin plenums is treated as a separate section within NFPA 90A and not within the individual plenum sections. Thissection, which addresses material combustibility, is placed before the other sections already contained in NFPA 5000,which are not associated with material combustibility or with NFPA 90A.This comment is made to proposals 5000-76, 5000-77, 5000-78 and 5000-80a and the legislative text is based on the

existing text in NFPA 5000 rather than on the revisions proposed by the technical committee on building construction, inview of the various TCC notes. If this comment is accepted, the section on plenum materials will be shorter andcompletely consistent with NFPA 90A.

7Printed on 9/16/2010BLD-SCM ROC AGENDA Page 19 of 37

Page 20: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-55 Log #18b BLD-SCM

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

5000-77Revise text to read as follows:

7.2.3.2.14 Ceiling and Raised Floor Plenums. The space between the top of the finished ceiling and the underside ofthe floor or roof above and the space between the top of the finished floor and the underside of a raised floor Plenums*shall be permitted to be used to supply air to the occupied area or return and exhaust air from the occupied area,provided that the requirements of 7.2.3.2.15 through 7.2.3.2.21 7.2.3.2.20 are met.A.7.2.3.2.14 NFPA 90A recognizes the following types of plenums: ceiling cavity plenum, apparatus casing plenum,

air-handling room plenum and raised floor plenum. The requirements in NFPA 90A are different for each type of plenumand Chapter 3 of this code shows definitions for each type of plenum.7.2.3.2.15 Plenum Materials Combustibility. Materials within a ceiling cavity plenum exposed to the airflow shall comply

with the requirements of section 4.3.11 of NFPA 90A be noncombustible or comply with one of the following.[90A:4.3.11.2.6]7.2.3.2.15.1 Electrical wires and cables and optical fiber cables shall be listed as having a maximum peak opticaldensity of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500mm) or less when tested in accordance with NFPA 262, Standard Method of Test for Flame Travel and Smoke of Wiresand Cables for Use in Air-Handling Spaces or shall be installed in metal raceways, metal sheathed cable, or totallyenclosed non-ventilated busway. [90A:4.3.11.2.6.1]7.2.3.2.15.2 Pneumatic tubing for control systems shall be listed as having a maximum peak optical density of 0.5 orless, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or less whentested in accordance with ANSI/UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and SmokeCharacteristics. [90A:4.3.11.2.6.2]7.2.3.2.15.3 Nonmetallic fire sprinkler piping shall be listed as having a maximum peak optical density of 0.5 or less, anaverage optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or less when testedin accordance with ANSI/UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and SmokeCharacteristics. [90A:4.3.11.2.6.3]7.2.3.2.15.4 Optical-fiber and communication raceways shall be listed as having a maximum peak optical density of 0.5or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or lesswhen tested in accordance with ANSI/UL 2024, Standard for Optical-Fiber and Communications Cable Raceway.[90A:4.3.11.2.6.4]7.2.3.2.15.5 Loudspeaker recessed lighting fixture and other electrical equipment with combustible enclosures,including their assemblies and accessories, cable ties, and other discrete products shall be permitted in the ceilingcavity plenum where listed as having a maximum peak optical density of 0.5 or less, an average optical density of 0.15or less, and a peak heat release rate of 100 kW or less when tested in accordance with UL 2043, Standard for Fire Testfor Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces.[90A:4.3.11.2.6.5]7.2.3.2.15.6 Supplementary materials for air distribution systems shall be permitted when complying with the provisionsof 4.3.3 of NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. [90A:4.3.11.2.6.6]7.2.3.2.15.7 Smoke detectors shall not be required to meet the provisions of 7.2.3.2.15. [90A:4.3.11.2.6.7]7.2.3.2.15.8 Fire-retardant-treated wood complying with Chapter 45 shall be permitted.7.2.3.2.16 Wall or ceiling finish in plenums shall comply with section 4.3.11.6 of NFPA 90A.7.2.3.2.16 7.2.3.2.17 Plenum Fire Stopping. The integrity of the fire stopping for penetrations shall be maintained.7.2.3.2.17 7.2.3.2.18 Plenum Light Diffusers. Light diffusers, other than those made of metal or glass, used inair-handling light fixtures shall be listed and marked as follows:Fixture Light Diffusers for Air-Handling Fixtures7.2.3.2.18 7.2.3.2.19 Plenum Air Temperature. The temperature of air delivered to plenums shall not exceed 250°F(121°C).7.2.3.2.19 7.2.3.2.20 Plenum Materials Exposure. Materials used in the construction of a plenum shall be suitable forcontinuous exposure to the temperature and humidity conditions of the environmental air in the plenum.7.2.3.2.20 7.2.3.2.21 Ceiling Plenum Tested Assembly. Where the plenum is a part of a floor/ceiling or roof/ceilingassembly that has been tested or investigated and assigned a fire resistance rating of 1 hour or more, and the assemblycontains air ducts and openings for air ducts, all the materials and the construction of the assembly, including the air

8Printed on 9/16/2010BLD-SCM ROC AGENDA Page 20 of 37

Page 21: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000duct materials and the size and protection of the openings, shall conform with the design of the fire resistance–ratedassembly, as tested in accordance with NFPA 251, Standard Methods of Tests of Fire Resistance of BuildingConstruction and Materials; ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials;or UL 263, Standard for Fire Tests of Building Construction and Materials.48.4.3* Plenums. The use of foam plastic insulation as wall or ceiling finish in plenums shall comply with section4.3.11.6 of NFPA 90A. be permitted where the insulation meets one of the following criteria:(1) The foam plastic insulation complies with 48.3.2.1 and is separated from the plenum by a thermal barrier complyingwith 48.3.3.(2) The foam plastic insulation has a flame spread index of 25 or less and a smoke developed index of 50 or less whentested in accordance with ASTM E 84 or UL 723 and meets one of the following criteria:(a) The foam plastic is separated from the plenum by a thermal barrier complying with 48.3.3.(b) The foam plastic is approved based on tests conducted in accordance with 48.4.4.(3) The foam plastic insulation complies with 48.3.2.1 and is covered by corrosion-resistant steel having a base metalthickness of not less than 0.016 in. (0.4 mm) and meets one of the following:(a) The foam plastic is separated from the plenum by a thermal barrier complying with 48.3.3.(b) The foam plastic is approved based on tests conducted in accordance with 48.4.4.A.48.4.3 These requirements are consistent with the requirements in section 7.2.3.2.17 of this code.Also, add the following definitions into chapter 3:Air-Handling Unit Room Plenum. An individual room containing an air-handling unit(s) used to gather air from varioussources and combine the air within the room for returning to the air-handling unit. [90A: 3.3.22.1]Apparatus Casing Plenum. A sheet metal construction attached directly to a fan enclosure, fan coil unit, air-handlingunit, or furnace bonnet for the purpose of connecting distribution ducts. [90A: 3.3.22.2]Ceiling Cavity Plenum. The space between the top of the finished ceiling and the underside of the floor or roof abovewhere used to supply air to the occupied area, or to return or exhaust air from the occupied area. [90A: 3.3.22.3]Raised Floor Plenum. The space between the top of the finished floor and the underside of a raised floor where used tosupply air to the occupied area, or to return or exhaust air from the occupied area. [90A: 3.3.22.4]

NFPA Standards Council specified that NFPA 90A has primary jurisdiction over materials in plenums.The text contained in present sections 7.2.3.2.14 through 7.2.3.2.20 and that contained in present section 48.4.3 ofNFPA 5000 is not consistent with either the 2009 or the upcoming 2012 editions of NFPA 90A. This needs to bechanged. Moreover, the requirements for Wall or Ceiling Finish in Plenums (from 4.3.11.6 of NFPA 90A and itssubsections) are missing in NFPA 5000 or are incorrect in 48.4.3. The permission to use fire retardant treated wood in7.2.3.2.15.8 is not consistent with the requirements in NFPA 90A. Finally, the requirements in NFPA 90A are differentfor each of the four types of plenums recognized by NFPA 90A.This comment deletes all the specific requirements and refers to section 4.3.11 of NFPA 90A. A section on wall or

ceiling finish in plenums is added (simply with reference to section 4.3.11.6 of NFPA 90A) because wall or ceiling finishin plenums is treated as a separate section within NFPA 90A and not within the individual plenum sections. Thissection, which addresses material combustibility, is placed before the other sections already contained in NFPA 5000,which are not associated with material combustibility or with NFPA 90A.This comment is made to proposals 5000-76, 5000-77, 5000-78 and 5000-80a and the legislative text is based on the

existing text in NFPA 5000 rather than on the revisions proposed by the technical committee on building construction, inview of the various TCC notes. If this comment is accepted, the section on plenum materials will be shorter andcompletely consistent with NFPA 90A.

9Printed on 9/16/2010BLD-SCM ROC AGENDA Page 21 of 37

Page 22: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-57 Log #19b BLD-SCM

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

5000-78Revise text to read as follows:

7.2.3.2.14 Ceiling and Raised Floor Plenums. The space between the top of the finished ceiling and the underside ofthe floor or roof above and the space between the top of the finished floor and the underside of a raised floor Plenums*shall be permitted to be used to supply air to the occupied area or return and exhaust air from the occupied area,provided that the requirements of 7.2.3.2.15 through 7.2.3.2.21 7.2.3.2.20 are met.A.7.2.3.2.14 NFPA 90A recognizes the following types of plenums: ceiling cavity plenum, apparatus casing plenum,air-handling room plenum and raised floor plenum. The requirements in NFPA 90A are different for each type of plenumand Chapter 3 of this code shows definitions for each type of plenum.7.2.3.2.15 Plenum Materials Combustibility. Materials within a ceiling cavity plenum exposed to the airflow shall complywith the requirements of section 4.3.11 of NFPA 90A be noncombustible or comply with one of the following.[90A:4.3.11.2.6]7.2.3.2.15.1 Electrical wires and cables and optical fiber cables shall be listed as having a maximum peak opticaldensity of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500mm) or less when tested in accordance with NFPA 262, Standard Method of Test for Flame Travel and Smoke of Wiresand Cables for Use in Air-Handling Spaces or shall be installed in metal raceways, metal sheathed cable, or totallyenclosed non-ventilated busway. [90A:4.3.11.2.6.1]7.2.3.2.15.2 Pneumatic tubing for control systems shall be listed as having a maximum peak optical density of 0.5 orless, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or less whentested in accordance with ANSI/UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and SmokeCharacteristics. [90A:4.3.11.2.6.2]7.2.3.2.15.3 Nonmetallic fire sprinkler piping shall be listed as having a maximum peak optical density of 0.5 or less, anaverage optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or less when testedin accordance with ANSI/UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and SmokeCharacteristics. [90A:4.3.11.2.6.3]7.2.3.2.15.4 Optical-fiber and communication raceways shall be listed as having a maximum peak optical density of 0.5or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or lesswhen tested in accordance with ANSI/UL 2024, Standard for Optical-Fiber and Communications Cable Raceway.[90A:4.3.11.2.6.4]7.2.3.2.15.5 Loudspeaker recessed lighting fixture and other electrical equipment with combustible enclosures,including their assemblies and accessories, cable ties, and other discrete products shall be permitted in the ceilingcavity plenum where listed as having a maximum peak optical density of 0.5 or less, an average optical density of 0.15or less, and a peak heat release rate of 100 kW or less when tested in accordance with UL 2043, Standard for Fire Testfor Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces.[90A:4.3.11.2.6.5]7.2.3.2.15.6 Supplementary materials for air distribution systems shall be permitted when complying with the provisionsof 4.3.3 of NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. [90A:4.3.11.2.6.6]7.2.3.2.15.7 Smoke detectors shall not be required to meet the provisions of 7.2.3.2.15. [90A:4.3.11.2.6.7]7.2.3.2.15.8 Fire-retardant-treated wood complying with Chapter 45 shall be permitted.7.2.3.2.16 Wall or ceiling finish in plenums shall comply with section 4.3.11.6 of NFPA 90A.7.2.3.2.16 7.2.3.2.17 Plenum Fire Stopping. The integrity of the fire stopping for penetrations shall be maintained.7.2.3.2.17 7.2.3.2.18 Plenum Light Diffusers. Light diffusers, other than those made of metal or glass, used inair-handling light fixtures shall be listed and marked as follows:Fixture Light Diffusers for Air-Handling Fixtures7.2.3.2.18 7.2.3.2.19 Plenum Air Temperature. The temperature of air delivered to plenums shall not exceed 250°F(121°C).7.2.3.2.19 7.2.3.2.20 Plenum Materials Exposure. Materials used in the construction of a plenum shall be suitable forcontinuous exposure to the temperature and humidity conditions of the environmental air in the plenum.7.2.3.2.20 7.2.3.2.21 Ceiling Plenum Tested Assembly. Where the plenum is a part of a floor/ceiling or roof/ceilingassembly that has been tested or investigated and assigned a fire resistance rating of 1 hour or more, and the assemblycontains air ducts and openings for air ducts, all the materials and the construction of the assembly, including the air

10Printed on 9/16/2010BLD-SCM ROC AGENDA Page 22 of 37

Page 23: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000duct materials and the size and protection of the openings, shall conform with the design of the fire resistance–ratedassembly, as tested in accordance with NFPA 251, Standard Methods of Tests of Fire Resistance of BuildingConstruction and Materials; ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials;or UL 263, Standard for Fire Tests of Building Construction and Materials.48.4.3* Plenums. The use of foam plastic insulation as wall or ceiling finish in plenums shall comply with section4.3.11.6 of NFPA 90A. be permitted where the insulation meets one of the following criteria:(1) The foam plastic insulation complies with 48.3.2.1 and is separated from the plenum by a thermal barrier complyingwith 48.3.3.(2) The foam plastic insulation has a flame spread index of 25 or less and a smoke developed index of 50 or less whentested in accordance with ASTM E 84 or UL 723 and meets one of the following criteria:(a) The foam plastic is separated from the plenum by a thermal barrier complying with 48.3.3.(b) The foam plastic is approved based on tests conducted in accordance with 48.4.4.(3) The foam plastic insulation complies with 48.3.2.1 and is covered by corrosion-resistant steel having a base metalthickness of not less than 0.016 in. (0.4 mm) and meets one of the following:(a) The foam plastic is separated from the plenum by a thermal barrier complying with 48.3.3.(b) The foam plastic is approved based on tests conducted in accordance with 48.4.4.A.48.4.3 These requirements are consistent with the requirements in section 7.2.3.2.17 of this code.Also, add the following definitions into chapter 3:Air-Handling Unit Room Plenum. An individual room containing an air-handling unit(s) used to gather air from varioussources and combine the air within the room for returning to the air-handling unit. [90A: 3.3.22.1]Apparatus Casing Plenum. A sheet metal construction attached directly to a fan enclosure, fan coil unit, air-handlingunit, or furnace bonnet for the purpose of connecting distribution ducts. [90A: 3.3.22.2]Ceiling Cavity Plenum. The space between the top of the finished ceiling and the underside of the floor or roof abovewhere used to supply air to the occupied area, or to return or exhaust air from the occupied area. [90A: 3.3.22.3]Raised Floor Plenum. The space between the top of the finished floor and the underside of a raised floor where used tosupply air to the occupied area, or to return or exhaust air from the occupied area. [90A: 3.3.22.4]

NFPA Standards Council specified that NFPA 90A has primary jurisdiction over materials in plenums.The text contained in present sections 7.2.3.2.14 through 7.2.3.2.20 and that contained in present section 48.4.3 ofNFPA 5000 is not consistent with either the 2009 or the upcoming 2012 editions of NFPA 90A. This needs to bechanged. Moreover, the requirements for Wall or Ceiling Finish in Plenums (from 4.3.11.6 of NFPA 90A and itssubsections) are missing in NFPA 5000 or are incorrect in 48.4.3. The permission to use fire retardant treated wood in7.2.3.2.15.8 is not consistent with the requirements in NFPA 90A. Finally, the requirements in NFPA 90A are differentfor each of the four types of plenums recognized by NFPA 90A.This comment deletes all the specific requirements and refers to section 4.3.11 of NFPA 90A. A section on wall orceiling finish in plenums is added (simply with reference to section 4.3.11.6 of NFPA 90A) because wall or ceiling finishin plenums is treated as a separate section within NFPA 90A and not within the individual plenum sections. Thissection, which addresses material combustibility, is placed before the other sections already contained in NFPA 5000,which are not associated with material combustibility or with NFPA 90A.This comment is made to proposals 5000-76, 5000-77, 5000-78 and 5000-80a and the legislative text is based on theexisting text in NFPA 5000 rather than on the revisions proposed by the technical committee on building construction, inview of the various TCC notes. If this comment is accepted, the section on plenum materials will be shorter andcompletely consistent with NFPA 90A.

11Printed on 9/16/2010BLD-SCM ROC AGENDA Page 23 of 37

Page 24: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-59 Log #20b BLD-SCM

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

5000-80aRevise text to read as follows:

7.2.3.2.14 Ceiling and Raised Floor Plenums. The space between the top of the finished ceiling and the underside ofthe floor or roof above and the space between the top of the finished floor and the underside of a raised floor Plenums*shall be permitted to be used to supply air to the occupied area or return and exhaust air from the occupied area,provided that the requirements of 7.2.3.2.15 through 7.2.3.2.21 7.2.3.2.20 are met.A.7.2.3.2.14 NFPA 90A recognizes the following types of plenums: ceiling cavity plenum, apparatus casing plenum,

air-handling room plenum and raised floor plenum. The requirements in NFPA 90A are different for each type of plenumand Chapter 3 of this code shows definitions for each type of plenum.7.2.3.2.15 Plenum Materials Combustibility. Materials within a ceiling cavity plenum exposed to the airflow shall comply

with the requirements of section 4.3.11 of NFPA 90A be noncombustible or comply with one of the following.[90A:4.3.11.2.6]7.2.3.2.15.1 Electrical wires and cables and optical fiber cables shall be listed as having a maximum peak opticaldensity of 0.5 or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500mm) or less when tested in accordance with NFPA 262, Standard Method of Test for Flame Travel and Smoke of Wiresand Cables for Use in Air-Handling Spaces or shall be installed in metal raceways, metal sheathed cable, or totallyenclosed non-ventilated busway. [90A:4.3.11.2.6.1]7.2.3.2.15.2 Pneumatic tubing for control systems shall be listed as having a maximum peak optical density of 0.5 orless, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or less whentested in accordance with ANSI/UL 1820, Standard for Safety Fire Test of Pneumatic Tubing for Flame and SmokeCharacteristics. [90A:4.3.11.2.6.2]7.2.3.2.15.3 Nonmetallic fire sprinkler piping shall be listed as having a maximum peak optical density of 0.5 or less, anaverage optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or less when testedin accordance with ANSI/UL 1887, Standard for Safety Fire Test of Plastic Sprinkler Pipe for Visible Flame and SmokeCharacteristics. [90A:4.3.11.2.6.3]7.2.3.2.15.4 Optical-fiber and communication raceways shall be listed as having a maximum peak optical density of 0.5or less, an average optical density of 0.15 or less, and a maximum flame spread distance of 60 in. (1500 mm) or lesswhen tested in accordance with ANSI/UL 2024, Standard for Optical-Fiber and Communications Cable Raceway.[90A:4.3.11.2.6.4]7.2.3.2.15.5 Loudspeaker recessed lighting fixture and other electrical equipment with combustible enclosures,including their assemblies and accessories, cable ties, and other discrete products shall be permitted in the ceilingcavity plenum where listed as having a maximum peak optical density of 0.5 or less, an average optical density of 0.15or less, and a peak heat release rate of 100 kW or less when tested in accordance with UL 2043, Standard for Fire Testfor Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-Handling Spaces.[90A:4.3.11.2.6.5]7.2.3.2.15.6 Supplementary materials for air distribution systems shall be permitted when complying with the provisionsof 4.3.3 of NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. [90A:4.3.11.2.6.6]7.2.3.2.15.7 Smoke detectors shall not be required to meet the provisions of 7.2.3.2.15. [90A:4.3.11.2.6.7]7.2.3.2.15.8 Fire-retardant-treated wood complying with Chapter 45 shall be permitted.7.2.3.2.16 Wall or ceiling finish in plenums shall comply with section 4.3.11.6 of NFPA 90A.7.2.3.2.16 7.2.3.2.17 Plenum Fire Stopping. The integrity of the fire stopping for penetrations shall be maintained.7.2.3.2.17 7.2.3.2.18 Plenum Light Diffusers. Light diffusers, other than those made of metal or glass, used inair-handling light fixtures shall be listed and marked as follows:Fixture Light Diffusers for Air-Handling Fixtures7.2.3.2.18 7.2.3.2.19 Plenum Air Temperature. The temperature of air delivered to plenums shall not exceed 250°F(121°C).7.2.3.2.19 7.2.3.2.20 Plenum Materials Exposure. Materials used in the construction of a plenum shall be suitable forcontinuous exposure to the temperature and humidity conditions of the environmental air in the plenum.7.2.3.2.20 7.2.3.2.21 Ceiling Plenum Tested Assembly. Where the plenum is a part of a floor/ceiling or roof/ceilingassembly that has been tested or investigated and assigned a fire resistance rating of 1 hour or more, and the assemblycontains air ducts and openings for air ducts, all the materials and the construction of the assembly, including the air

12Printed on 9/16/2010BLD-SCM ROC AGENDA Page 24 of 37

Page 25: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000duct materials and the size and protection of the openings, shall conform with the design of the fire resistance–ratedassembly, as tested in accordance with NFPA 251, Standard Methods of Tests of Fire Resistance of BuildingConstruction and Materials; ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and Materials;or UL 263, Standard for Fire Tests of Building Construction and Materials.48.4.3* Plenums. The use of foam plastic insulation as wall or ceiling finish in plenums shall comply with section4.3.11.6 of NFPA 90A. be permitted where the insulation meets one of the following criteria:(1) The foam plastic insulation complies with 48.3.2.1 and is separated from the plenum by a thermal barrier complyingwith 48.3.3.(2) The foam plastic insulation has a flame spread index of 25 or less and a smoke developed index of 50 or less whentested in accordance with ASTM E 84 or UL 723 and meets one of the following criteria:(a) The foam plastic is separated from the plenum by a thermal barrier complying with 48.3.3.(b) The foam plastic is approved based on tests conducted in accordance with 48.4.4.(3) The foam plastic insulation complies with 48.3.2.1 and is covered by corrosion-resistant steel having a base metalthickness of not less than 0.016 in. (0.4 mm) and meets one of the following:(a) The foam plastic is separated from the plenum by a thermal barrier complying with 48.3.3.(b) The foam plastic is approved based on tests conducted in accordance with 48.4.4.A.48.4.3 These requirements are consistent with the requirements in section 7.2.3.2.17 of this code.Also, add the following definitions into chapter 3:Air-Handling Unit Room Plenum. An individual room containing an air-handling unit(s) used to gather air from varioussources and combine the air within the room for returning to the air-handling unit. [90A: 3.3.22.1]Apparatus Casing Plenum. A sheet metal construction attached directly to a fan enclosure, fan coil unit, air-handlingunit, or furnace bonnet for the purpose of connecting distribution ducts. [90A: 3.3.22.2]Ceiling Cavity Plenum. The space between the top of the finished ceiling and the underside of the floor or roof abovewhere used to supply air to the occupied area, or to return or exhaust air from the occupied area. [90A: 3.3.22.3]Raised Floor Plenum. The space between the top of the finished floor and the underside of a raised floor where used tosupply air to the occupied area, or to return or exhaust air from the occupied area. [90A: 3.3.22.4]

NFPA Standards Council specified that NFPA 90A has primary jurisdiction over materials in plenums.The text contained in present sections 7.2.3.2.14 through 7.2.3.2.20 and that contained in present section 48.4.3 ofNFPA 5000 is not consistent with either the 2009 or the upcoming 2012 editions of NFPA 90A. This needs to bechanged. Moreover, the requirements for Wall or Ceiling Finish in Plenums (from 4.3.11.6 of NFPA 90A and itssubsections) are missing in NFPA 5000 or are incorrect in 48.4.3. The permission to use fire retardant treated wood in7.2.3.2.15.8 is not consistent with the requirements in NFPA 90A. Finally, the requirements in NFPA 90A are differentfor each of the four types of plenums recognized by NFPA 90A.This comment deletes all the specific requirements and refers to section 4.3.11 of NFPA 90A. A section on wall or

ceiling finish in plenums is added (simply with reference to section 4.3.11.6 of NFPA 90A) because wall or ceiling finishin plenums is treated as a separate section within NFPA 90A and not within the individual plenum sections. Thissection, which addresses material combustibility, is placed before the other sections already contained in NFPA 5000,which are not associated with material combustibility or with NFPA 90A.This comment is made to proposals 5000-76, 5000-77, 5000-78 and 5000-80a and the legislative text is based on the

existing text in NFPA 5000 rather than on the revisions proposed by the technical committee on building construction, inview of the various TCC notes. If this comment is accepted, the section on plenum materials will be shorter andcompletely consistent with NFPA 90A.

_______________________________________________________________________________________________5000-156 Log #CC3 BLD-SCM

_______________________________________________________________________________________________Technical Committee on Fundamentals,

5000-1Revise text as follows:

Where roof coverings are required by 38.2.2 to be fire resistance rated as either Class A, Class B, or Class Cfor exterior fire exposure, they shall be tested according to either NFPA 256, or other approved test methods; FM 4470,Approval for Class 1 Roof Covers; UL 790, ; or ASTM E 108,

.NFPA 256 was withdrawn and is no longer published.

13Printed on 9/16/2010BLD-SCM ROC AGENDA Page 25 of 37

Page 26: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-157 Log #108 BLD-SCM

_______________________________________________________________________________________________Bonnie E. Manley, American Iron and Steel Institute / Rep. AISI, AISC

5000-215Revise Section 40.3.10 and Tables 40.3.10(a) and 40.3.10(b) as follows:

Structural tests and inspections for steel materials, fabrication, and erection shall be asrequired by the following:(1) Structural steel construction shall comply with AISC 360 and AISC 341, as applicableTable 40.3.10(a).(2) Cold-formed steel light-frame construction shall comply with Table 40.3.10(a)(b).(3) Other steel construction shall comply with Table 40.3.10(b)

****Insert Table 40.3.10(b) and Table 40.3.10(a) Here****

The recently completed 2010 edition of ANSI/AISC 360,, incorporates a new Chapter N, which addresses comprehensive quality control and quality

assurance requirements for all structural steel construction. These requirements are similar in nature to those that wereincorporated into the 2005 edition of AISC 341, Appendix Q. AISC 360-10, Chapter N provisions provide the foundationfor the quality control and quality assurance requirements for general structural steel construction, with AISC 341-10,Chapter I (previously contained in AISC 341-05, Appendix Q) extending specific requirements to high-seismicapplications.The present Section 40.3.10 addresses all forms of steel construction. The majority of the requirements in Table

40.3.10(a) pertain to structural steel construction. However, there are a few items that are applicable to “steelconstruction other than structural steel”, which are not covered by AISC 360. This comment keeps those particularrequirements while deleting the specific quality assurance requirements for structural steel. For structural steel, a directreference is made in Section 40.3.10 to the more detailed requirements of AISC 360 and AISC 341.Specifically, topics currently in Table 40.3.10(a) that are covered in AISC 360, Chapter N are as follows: Table 40.3.10(a), Fabricator Inspection: AISC 360, Section N (General) Table 40.3.10(a), Materials: AISC 360, Section N5.2 Table 40.3.10(a), Anchor Rods: AISC 360, Section N5.7 Table 40.3.10(a), Bolting: AISC 360, Section N5.6 Table 40.3.10(a), Welding: AISC 360, Section N5.4 Table 40.3.10(a), Shear Connectors: AISC 360, Section N6 Table 40.3.10(a), Structural framing, bracing, details and assemblies: AISC 360, Section N5.7Please note, both AISC 360-10 and AISC 341-10 are complete and summaries of the major changes have been

included with the public comment on Proposal 5000-9.In the 2003 and 2006 editions of NFPA 5000, this table specifically referenced

“light frame cold-formed steel”. However, the charging text in both editions called out “cold-formed steel”. In an attemptto have the text coordinate with the table, “light frame” was deleted from the table in the 2009 edition of NFPA 5000.However, this was not the correct solution; since there are cold-formed steel components addressed in Table 40.3.10(a)– i.e. metal decking. This comment adds “light frame” back into the table and corrects the charging language to reflectthe true scope of the table.

Since the structural steel items have been removed from Table 40.3.10(a), it has beenrecast as applicable to “other steel construction” and moved after the cold-formed steel light-frame construction table.Additionally, the steel joist entry was clarified to apply in field settings only.

14Printed on 9/16/2010BLD-SCM ROC AGENDA Page 26 of 37

Page 27: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

NFPA 5000 Log #108 F2011 ROC 1

Table 40.3.10(b)(a) Other Steel Construction Item Scope (frequency determined by RDP

responsible for design)Steel construction quality control review

Review contractor’s field quality control procedures. Review frequency and scope of field testing and inspections.

Fabricator certification/ quality control procedures

Review each fabricator’s quality control procedures.

Fabricator inspection Inspect in-plant fabrication, or review fabricator’s approved independent inspection agency’s reports.

Materials Review materials certifications for conformance to the specifications.

Anchor rods Review contractor’s as-built survey. Verify that all anchor rods have been properly tightened and have adequate fit-up.

Bolting Test and inspect bolted connections in accordance with specifications. Verify bolt size and grade.

Welding Check welder qualifications. Visually inspect fillet welds and test full-penetration field welds in accordance with specifications.

Shear connectors Inspect for size and placement. Test for proper weld attachment.

Structural framing, bracing, details, and assemblies

Inspect for size, grade of steel, camber, installation, and connection details. Check against approved construction documents and shop drawings.

Open web steel joists Inspect for size, placement, bridging, bearing, and connection to structure. Visually inspect all field welds of a minimum of 5 percent of the joists, randomly selected.

Expansion and adhesive anchors Review installation procedures for both mechanical anchors and adhesive anchors. Verify that materials are suitable for job conditions.

Metal decking Verify gauge width and type. Inspect placement, laps, welds, sidelap attachment, and screws or other mechanical fasteners. Check welder’s qualifications.

Field correction of fabricated items

Review documentation of repair approved by the RDP responsible for design, and verify completion of repairs.

BLD-SCM ROC AGENDA Page 27 of 37

Page 28: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

NFPA 5000 Log #108 F2011 ROC 2

Table 40.3.10(a)(b) Cold-Formed Steel Light-Frame Construction Item Scope (frequency determined by RDP

responsible for design) Cold-formed steel light-frame construction quality control review

Review contractor’s field quality control procedures. Review scope of testing and inspections.

Fabricator’s quality control procedures Review fabricator’s quality control procedures.

Material certification Review for conformance to construction documents.

Fabrication inspection Inspect in-plant fabrication, or review fabricator’s approved independent inspection agency’s reports.

Shear walls, diaphragms, and hold-downs Inspect thickness and grade of wood structural panel, blocking, hold-down anchors, and the edge and field attachment of the structural wood panel to the framing for conformance to the submittals approved by the RDP responsible for design and the construction documents. Review panelized construction for proper wood structural panel overlaps.

Installation Verify that type, size, quantity, location, details, and connections of framing and bracing members conform to submittals approved by the RDP responsible for design and the construction documents.

Welding Check welders’ qualifications. Verify that welding conforms to AWS specifications, submittals approved by the RDP responsible for design, and the construction documents. Visually inspect welds.

Other fasteners Verify fastener type and installation procedures. Verify that fasteners conform to submittals approved by the RDP responsible for design and the construction documents. Verify that fasteners are installed tight.

Field correction of fabricated items Review documentation of repair approved by the RDP responsible for design, and verify completion of repairs.

BLD-SCM ROC AGENDA Page 28 of 37

Page 29: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-158 Log #112 BLD-SCM

_______________________________________________________________________________________________Bonnie E. Manley, American Iron and Steel Institute / Rep. Rack Manufacturers Institute

5000-220Part I: Revise Section 44.5 as follows:

The design, testing, and utilization of industrial steel storage racks, made of cold-formed or hot-rolled steelstructural members, shall be in accordance with ANSI MH16.1,

, the scope of which includes industrial pallet racks, movable shelf racks, and stackerracks.

ANSI MH16.1 shall not apply to other types of racks, such as drive-in and drive-through racks, cantilever racks,portable racks, or rack buildings.

Where required by ASCE 7, the seismic design of storage racks shall also be in accordance with therequirements of Section 15.5.3 of ASCE/SEI 7 except that the mapped acceleration parameters Ss and S1 shall bedetermined in accordance with Section 35.10.3.Part II: Revise Section 2.3.31 as follows:

Rack Manufacturers Institute, 8720 Red Oak Boulevard, Suite 201, Charlotte, NC 28217RMI/ANSI MH16.1, , 20052008.

Part I of this comment editorially tightens up Section 44.5 by deleting the repetition of the scope ofANSI MH16.1. It also adds language which clarifies that racks can be made from either cold-formed steel or hot-rolledsteel. Finally, to coordinate the 2008 edition of the standard with ASCE 7-10, it is necessary to redirect users to the newASCE 7-10 maps, which are referenced in NFPA 5000, Section 35.10.3. Part II of the comment updates the editionyear of RMI’s ANSI/MH 16.1, , from2005 to 2008.Note: Supporting material is available for review at NFPA Headquarters.

15Printed on 9/16/2010BLD-SCM ROC AGENDA Page 29 of 37

Page 30: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-159 Log #110 BLD-SCM

_______________________________________________________________________________________________Bonnie E. Manley, American Iron and Steel Institute

5000-221

The design of cold-formed carbon and low alloy steel structural members shall be in accordance withAISI-S100,

The design of cold-formed stainless steel structural members shall be in accordance with ASCE/SEI 8,

. The design and construction of cold-formed steel decks shall be in accordance with this section.Composite slabs of concrete on steel decks shall be designed and

constructed in accordance with ASCE/SEI 3,

Where a response modification coefficient, R, inaccordance with ASCE 7, Table 12.2-1 is used for the design of cold-formed steel structures, the structures shall bedesigned and detailed in accordance with the requirements of AISI S100, ASCE 8, and, for cold-formed steel specialbolted moment frames, AISI S110.

American Iron and Steel Institute, 1401 Connecticut Avenue, Suite 705, Washington, DC20036.AISI S110, ,

2007, including Supplement 1 (2009).This comment introduces a reference to AISI S110,

which is based upon research conducted by Drs. Uang andSato at UCSD (2007). Specifically, the standard focuses on providing design provisions for a newly defined seismicforce resisting system entitled “Cold-formed Steel – Special Bolted Moment Frame” or CFS-SBMFs. This type of systemis expected to experience substantial inelastic deformation during significant seismic events. It is intended that most ofthe inelastic deformation will take place at the bolted connections, due to slip and bearing. In order to develop thedesignated mechanism, requirements based on the capacity design principles are provided for the design of the beams,columns and associated connections. Additionally, AISI S110 has specific requirements for the application of qualityassurance and quality control procedures.This system has been vetted through the BSSC process and is included in Part I of the 2009 NEHRP Provisions.

Additionally, it has been adopted in the 2010 edition of ASCE 7. ASCE 7-10 has set the Response ModificationCoefficient, R, at 3.5. Cyclic testing has shown that CFS-SBMFs have very large ductility capacity and significanthardening. This justifies the use of a value of 3.5 for the R-factor. The derivation of the deflection amplification factor,Cd, can be found in the AISI S110 Commentary, Section D1.3. Furthermore, a capacity design procedure has beenprovided in Section D1.5 of AISI S110 Commentary so that the designer can explicitly calculate the seismic load effectwith overstrength, Emh,. at the design story drift level. Alternatively, a conservative system overstrength factor, Ωo, is also

provided to be compatible with the conventional approach to compute Emh in ASCE 7. Finally the height limitation of 35feet for all SDCs is based on practical use only and not from any limits on the CFS-SBMF system strength.Modifications to AISI S110 (2007 edition), which were presented in the original proposal in Section 44.6.4, were

developed primarily in the BSSC’s NEHRP process and adopted by ASCE 7 in Chapter 14, which is not adopted inNFPA 5000. However, the modifications to AISI S110-07 no longer need to be adopted in NFPA 5000; last year, theAISI committee responsible for AISI S110 issued a supplement which adopts all of the ASCE 7, Chapter 14modifications.

Note: Supporting material is available for review at NFPA Headquarters.

16Printed on 9/16/2010BLD-SCM ROC AGENDA Page 30 of 37

Page 31: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-160 Log #CC4 BLD-SCM

_______________________________________________________________________________________________Technical Committee on Fundamentals,

5000-1Revise text as follows:

Foam plastic insulation meeting the requirements of 48.3.1 through 48.3.3 shall be approved as part ofa roof-covering assembly where the assembly is tested as an assembly in accordance with NFPA 256 ASTM E 108,

, or ANSI/UL 790,, and has been determined to meet the requirements of Class A, Class B, or Class C.

Unless the skylight meets the Class B burning brand test, as described in NFPA 256 ASTM E 108,, or ANSI/UL 790, ,

skylights shall have the following slopes:(1) Flat or corrugated light-transmitting plastic skylights shall slope at least 4 units vertical in 12 units horizontal (4:12).(2) Dome-shaped skylights shall rise above the mounting flange for a minimum distance equal to 10 percent of themaximum span of the dome, but not less than 3 in. (75 mm).

NFPA 256 was withdrawn and is no longer published. ASTM E 108 and ANSI/UL 790 are the applicabletest standards.

17Printed on 9/16/2010BLD-SCM ROC AGENDA Page 31 of 37

Page 32: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000_______________________________________________________________________________________________5000-162 Log #100b BLD-SCM

_______________________________________________________________________________________________Steve Gutmann, City of Santa Ana Planning and Building Agency / Rep. NFPA Building Code Development

Committee (BCDC)5000-268

Keep the original proposal and add the following section:51.7 Photovoltaic Systems. [1:11.10]51.7.1 New photovoltaic systems installed for all existing buildings shall be in accordance with Section 11.10 and

NFPA 70. [1:11.10.1]51.7.2 Building Mounted Photovoltaic Installations. [1:11.10.2]51.7.2.1* Marking. Photovoltaic systems shall be permanently marked as specified in this section. [1:11.10.2.1]51.7.2.1.1 Main Service Disconnect Marking. A placard shall be permanently affixed to the main service disconnect

panel serving alternating current (AC) and direct current (DC) photovoltaic systems. The placard shall be red with whitecapital letters at least ¾ inch in height and in a non-serif font, to read:“SOLAR DISCONNECT INSIDE PANEL”.The placard shall be constructed of weather resistant, durable plastic with engraved letters, or other approved material.

[1:11.10.2.1.1]51.7.2.1.2 Circuit Disconnecting Means Marking. A permanent label shall be affixed adjacent to the circuit breaker

controlling the inverter or other photovoltaic system electrical controller serving alternating current (AC) and directcurrent (DC) photovoltaic systems.The label shall have contrasting color with capital letters at least 3/8 inch in height and in a non-serif font, to read:“SOLAR DISCONNECT”.The label shall be constructed of durable adhesive material, or other approved material. [1:11.10.2.1.2]51.7.2.1.3* Conduit, Raceway, Enclosure, Cable Assembly, and Junction Box Markings. Marking is required on all

interior and exterior direct current (DC) conduits, raceways, enclosures, cable assemblies, and junction boxes.[1:11.10.2.1.3]51.7.2.1.3.1 Marking Locations. Marking shall be placed on all direct current (DC) conduits, raceways, enclosures, and

cable assemblies every ten feet, at turns, and above and below penetrations. Marking shall be placed on all directcurrent (DC) combiner and junction boxes. [1:11.10.2.1.3.1]51.7.2.1.3.2* Marking Content and Format. Marking for direct current (DC) conduits, raceways, enclosures, cable

assemblies, and junction boxes shall be red with white lettering with minimum 3/8 inch capital letters in a non-serif font,to read:“WARNING: SOLAR CIRCUIT”.Marking shall be reflective, weather resistant, and suitable for the environment. [1:11.10.2.1.3.2]51.7.2.1.4 Secondary Power Source Markings. Where photovoltaic systems are interconnected to battery systems,

generator backup systems, or other secondary power systems, additional signage acceptable to the authority havingjurisdiction shall be required indicating the location of the secondary power source shutoff switch. [1:11.10.2.1.4]51.7.2.1.5 Installer Information. Signage, acceptable to the authority having jurisdiction, shall be installed adjacent to

the main disconnect indicating the name and emergency telephone number of the installing contractor. [1:11.10.2.1.5]51.7.2.1.6* Inverter Marking. Markings are not required for inverters. [1:11.10.2.1.6]51.7.2.2 Access, Pathways, and Smoke Ventilation. [1:11.10.2.2]51.7.2.2.1 General. Access and spacing requirements are required to provide emergency access to the roof, provide

pathways to specific areas of the roof, provide for smoke ventilation opportunity areas, and to provide emergency egressfrom the roof. [1:11.10.2.2.1]51.7.2.2.1.1 Exceptions. The authority having jurisdiction is allowed to grant exceptions where access, pathway or

ventilation requirements are reduced due to any of the following circumstances:1. Proximity and type of adjacent exposures2. Alternative access opportunities, as from adjoining roofs.3. Ground level access to the roof.4. Adequate ventilation opportunities beneath solar module arrays.5. Adequate ventilation opportunities afforded by module set back from other rooftop equipment.6. Automatic ventilation devices.7. New technologies, methods, or other innovations that ensure adequate fire department access, pathways, and

ventilation opportunities. [1:11.10.2.2.1.1]

18Printed on 9/16/2010BLD-SCM ROC AGENDA Page 32 of 37

Page 33: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 500051.7.2.2.1.2 Pitch. Designation of ridge, hip, and valley does not apply to roofs with 2-in-12 or less pitch.

[1:11.10.2.2.1.2]51.7.2.2.1.3 Roof Access Points. Roof access points shall be defined as areas where fire department ladders are not

placed over openings (windows or doors), are located at strong points of building construction, and are in locationswhere they will not conflict with overhead obstructions (tree limbs, wires, or signs). [1:11.10.2.2.1.3]51.7.2.2.2 One- and Two-Family Dwellings and Townhouses. Photovoltaic systems installed in one- and two-family

dwellings and townhouses shall be in accordance with this section. [1:11.10.2.2.2]51.7.2.2.2.1 Access and Pathways. [1:11.10.2.2.2.1]51.7.2.2.2.1.1 Hip Roof Layouts. Photovoltaic modules shall be located in a manner that provides a 3 foot wide clear

access pathway from the eave to the ridge of each roof slope where the photovoltaic modules are located. The accesspathway shall be located at a structurally strong location of the building, such as a bearing wall. [1:11.10.2.2.2.1.1]51.7.2.2.2.1.1.1 Exception. Where adjoining roof planes provide a three-foot (3’) wide clear access pathway.

[1:11.10.2.2.2.1.1.1]51.7.2.2.2.1.2 Single Ridge Layouts. Photovoltaic modules shall be located in a manner that provides two 3 foot wide

access pathways from the eave to the ridge on each roof slope where the modules are located. [1:11.10.2.2.2.1.2]51.7.2.2.2.1.3 Hip and Valley Layouts. Photovoltaic modules shall be located no closer than 1-1/2 feet to a hip or valley

if modules are to be placed on both sides of the hip or valley. Where modules are located on only one side of a hip orvalley of equal length, the photovoltaic modules shall be allowed to be placed directly adjacent to the hip or valley.[1:11.10.2.2.2.1.3]51.7.2.2.2.2 Ridge Setback. Photovoltaic modules shall be located no higher than 1-1/2 feet below the ridge.

[1:11.10.2.2.2.2]51.7.2.2.3 Buildings other than One- and Two-Family Dwellings and Townhouses. Photovoltaic energy systems

installed in any building other than one- and two-family dwellings and townhouses shall be in accordance with thissection. Where the authority having jurisdiction determines that the roof configuration is similar to a one- and two-familydwelling or townhouse, the authority having jurisdiction shall allow the requirements of Section 11.10.2.2.2.[1:11.10.2.2.3]51.7.2.2.3.1 Access. A minimum 4 foot wide clear perimeter shall be provided around the edges of the roof for

buildings with a length or width of 250 feet or less along either axis. A minimum 6 foot wide clear perimeter shall beprovided around the edges of the roof for buildings having length or width greater than 250 feet along either axis.[1:11.10.2.2.3.1]51.7.2.2.3.2 Pathways. Pathways shall be established as follows:1. Pathways shall be over structural members.2. Centerline axis pathways shall be provided in both axes of the roof.3. Centerline axis pathways shall run on structural members or over the next closest structural member nearest to the

center lines of the roof.4. Pathways shall be in a straight line not less than 4 feet clear to skylights, ventilation hatches, and roof standpipes.5. Pathways shall provide not less than 4 feet clear around roof access hatches with at least one not less than 4 feet

clear pathway to the parapet or roof edge. [1:11.10.2.2.3.2]51.7.2.2.3.3 Smoke Ventilation. Ability for fire department smoke ventilation shall be provided in accordance with this

section. [1:11.10.2.2.3.3]51.7.2.2.3.3.1 Maximum array. Arrays of photovoltaic modules shall be no greater than 150 feet by 150 feet in distance

in either axis. [1:11.10.2.2.3.3.1]51.7.2.2.3.3.2 Ventilation options. Ventilation options between array sections shall be either:1. A pathway 8 feet or greater in width;2. A pathway 4 feet or greater in width and bordering on existing roof skylights or ventilation hatches; or3. A pathway 4 feet or greater in width and bordering 4 foot by 8 foot venting cutouts options every 20 feet on

alternating sides of the pathway. [1:11.10.2.2.3.3.2]51.7.2.2.4 Location of Direct Current (DC) Conductors. [1:11.10.2.2.4]51.7.2.2.4.1 Exterior mounted Direct Current conduits, wiring systems and raceways for photovoltaic circuits shall be

located as close as possible to the ridge, hip or valley and from the hip or valley as directly as possible to an outside wallto reduce trip hazards and maximize ventilation opportunities. [1:11.10.2.2.4.1]51.7.2.2.4.2 Conduit runs between sub-arrays and to DC combiner boxes shall be designed to take the shortest path

from the array to the DC combiner box. [1:11.10.2.2.4.2]51.7.2.2.4.2 Direct current (DC) combiner boxes shall be located so that conduit runs are minimized in the pathways

between arrays. [1:11.10.2.2.4.2]51.7.2.2.4.3 Direct current (DC) wiring shall be run in metallic conduit or raceways when located within enclosed

spaces in a building and shall be run as follows:

19Printed on 9/16/2010BLD-SCM ROC AGENDA Page 33 of 37

Page 34: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 50001. When run perpendicular or parallel to load-bearing members, a minimum 10 inch space below roof decking or

sheathing shall be maintained.2. Where flexible metal conduit (FMC) or metal clad cable (MC) containing PV power circuit conductors is installed

across ceilings or floor joists, the raceway or cable shall be protected by guard strips. [1:11.10.2.2.4.3]51.7.3 Ground-Mounted Photovoltaic System Installations. Ground-mounted photovoltaic systems shall be installed in

accordance with this section. [1:11.10.3]51.7.3.1* Clearances. A clear area of ten feet (10’) around ground-mounted photovoltaic installations shall be provided.

[1:11.10.3.1]51.7.3.2* Non-Combustible Base. A gravel base or other non-combustible base acceptable to the authority having

jurisdiction shall be installed and maintained under and around the installation. [1:11.10.3.2]51.7.3.3* Security Barriers. Fencing, skirting or other suitable security barrier shall be installed when required by the

authority having jurisdiction. [1:11.10.3.3]Also, add the following annex information to Annex A to read as follows:A.51.7.2.1 Marking is needed to provide emergency responders with appropriate warning and guidance with respect to

working around and isolating the solar electric system. This can facilitate identifying energized electrical lines thatconnect the solar modules to the inverter, which should not be cut when venting for smoke removal during firefightingoperations. [1:A11.10.2.1]A.51.7.2.1.3 Markings are intended to alert emergency responders to avoid inadvertent cutting through the conduits,

raceways or cable assemblies during firefighting operations. [1:A11.10.2.1.3]A.51.7.2.1.3.2 Materials used for marking should be in compliance with Underwriters Laboratories (UL) Standard 969,

Marking and Labeling System Standard. [1:A11.10.2.1.3.2]A.51.7.2.1.6 Inverters are devices used to convert DC electricity from the solar system to AC electricity for use in the

building’s electrical system or the grid. [1:A11.10.2.1.6]A.51.7.3.1 The zoning regulations of the jurisdiction setback requirements between buildings or property lines, and

accessory structures may apply. [1:A11.10.3.1]A.51.7.3.2 Though dirt with minor growth is not considered noncombustible, the authority having jurisdiction might

approve dirt bases as long as any growth is maintained under and around the installation to reduce the risk of ignitionfrom the electrical system. This could be a serious consideration for large ground mounted photovoltaic systems. Notonly should the base be considered under the systems, but also around the systems to the point that the risk of fire fromgrowth or other ignition sources will be reduced. [1:A11.10.3.2]A.51.7.3.3 Security barriers are intended to protect individuals and animals from contact with energized conductors or

other components. [1:A11.10.3.3]

Note: This comment was developed by the proponent as a member of NFPA’s Building CodeDevelopment Committee (BCDC) with the committee's endorsement.These provisions have been accepted by the NFPA 1 TC as ROP 1-81. We have submitted the text in this comment to

NFPA 5000 because it would be useful to have this information in the building code for new construction. It is intendedthat the provisions be extracted from one document to the other. Proposed section 51.7.2.2.4.3 Item 2 has been shownwith strikeout because the NFPA 1 Technical Committee has deleted it in their committee action. Since the provisionsare related to “green construction”, we believe the Comment is germane to ROP 5000-268.The following is the substantiation from the ROP 1-81:Many buildings are being retrofitted – or built – with photovoltaic (PV) systems. Photovoltaic systems present unique

life & safety hazards to building occupants and firefighters. These electrical systems carry voltages up to 600 v (DC) andcurrents up to 8 amps in residential systems, and there is no way to isolate the power at the modules in the daytimehours. Because of the lifethreatening voltages and current, these systems, not prevalent until recently, pose significantrisks to people on the roofs of these buildings – particularly firefighters, who conduct dangerous ventilation (and other)procedures during fire operations. Photovoltaic system installations should take into consideration the tactics employedby the fire service by providing safe roof access and means for identification of the presence of a PV system. Theseprovisions are intended to address firefighter safety during fire operations.This proposal is modeled after guidelines established by the California State Fire Marshal, entitled Solar Photovoltaic

Installation Guidelines, April 22, 2008, and particularly an ordinance under review by the City of Monterey. TheGuidelines are available on-line at http://www.osfm.fire.ca.gov/pdf/reports/solarphotovoltaicguideline.pdf.The main difference between the guidelines from the California State Fire Marshal and the suggested Monterey

ordinance is that the California guidelines require a three foot setback from the ridge, and a three foot setback from eveto ridge on full hip roof, even when the opposing hip is unobstructed. Whereas, the proposed Monterey ordinancereduces this to 18" (which is supported by many in California) including the requirement for hipped roofs, this reduced

20Printed on 9/16/2010BLD-SCM ROC AGENDA Page 34 of 37

Page 35: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 5000requirement is in practice in San Francisco.The proposal provides three basic safety measures: it establishes markings on photovoltaic system components to

alert responding firefighters to the dangers of the system, it provides access and pathways within solar module arraysfor roof ventilation and other firefighting duties during fire operations, and it provides other safety measures forfirefighters and others.Drawings similar to those at the end of the California State Fire Marshal Guidelines may be useful to readers of these

code provisions as Annex material. Consideration should be give to including them, with the appropriate 18 inchdimensions noted in this proposal (which differ from those 3 foot dimensions in the Guidelines.)

21Printed on 9/16/2010BLD-SCM ROC AGENDA Page 35 of 37

Page 36: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 703_______________________________________________________________________________________________703-1 Log #2 BLD-SCM

_______________________________________________________________________________________________John F. Bender, Underwriters Laboratories Inc.

703-3Revise text to read as follows:

2.3.2 UL Publications.Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, Revised 2010.

Update referenced standards to reflect most recent revisions.

_______________________________________________________________________________________________703-2 Log #5 BLD-SCM

_______________________________________________________________________________________________Joseph T. Holland, Hoover Treated Wood Products

703-5Accept the proposal as written in the Report on Proposals.

The TCC proposal criticizes the action of the committee as limiting the NFPA document to a uniqueprocess and is based on the negative statement to 5000-69. The substantiation statement clearly outlines the reasonfor the proposal. It was thoroughly discussed during the BLD-BLC committee meeting. This is a definition. Therequirement for pressure treatment is consistent with other standards; notably the 2006 and 2009 edition of theInternational Building Code.

The definition from the 2009 is shown below:Fire-retardant-treated wood. Pressure-treated (emphasis added) lumber and plywood that exhibit reduced

surface-burning characteristics and resist propagation of fire.There are no products currently in the marketplace nor are any products anticipated to be in the marketplace that are

produced by "other means during manufacture". That may be where the confusion arises. Until recently the phrase wasopen to interpretation. It has been clarified in Section 2303.2.2 of the 2009 edition of the

2303.2.2 Other means during manufacture. For wood products produced by other means during manufacture, thetreatment shall be an integral part of the manufacturing process of the wood product. The treatment shall providepermanent protection to all surfaces of the wood product.

The negative voter needs to identify what other "manufacturing processes" he has identified. One thought is it may bea coating or paint. NFPA 5000 is clear in Section 10.3.1.3 that for new construction they can not be used to reduceflame spread.

1Printed on 9/16/2010BLD-SCM ROC AGENDA Page 36 of 37

Page 37: COMMITTEES ON NFPA BUILDING CODE Technical Committee on ... · 9/2/2010 BLD-SCM James A. Rossberg Principal American Society of Civil Engineers Structural Engineering Institute 1801

Report on Comments – June 2011 NFPA 703_______________________________________________________________________________________________703-3 Log #1 BLD-SCM

_______________________________________________________________________________________________Marcelo M. Hirschler, GBH International / Rep. American Fire Safety Council

703-5Reject proposal 703-5.

This proposal introduces a proprietary concept that is not appropriate for a code or standard because itis not related to the performance of the material. Different methods exist or could be developed to manufacturefire-retardant-treated wood (FRTW) and they may or may not involve the pressure process. The issue is whether FRTWdoes or does not perform as required: flame spread index no larger than 25, no significant progressive combustion andno flame spread beyond 12.5 ft.

This proposal also introduces a requirement (that the material must be listed and labeled) which should not be in adefinition but should be in the body of the document. The NFPA Manual of Style does not allow requirements indefinitions. I agree that FRTW should be listed and labeled but the definition should not state this requirement; therequirement should be in a section in the body of NFPA 703.

In fact, section 4.5 already includes the requirement that these materials must be listed and labeled.The rejection of proposal 703-5 should not affect the continued acceptance of proposal 703-4, which contains needed

editorial changes.

_______________________________________________________________________________________________703-4 Log #4 BLD-SCM

_______________________________________________________________________________________________Joseph T. Holland, Hoover Treated Wood Products

703-11Add text to read as follows:

A.3.3.2 Wood or wood products with topically applied materials or chemicals are not “fire-retardant treated wood”.Fire-retardant treated wood is required to be “pressure treated”. The treatment becomes an integral part of the wood.Pressure treatment is done in closed vessels under pressures not less than 50 pounds per square inch gauge (psig)(345 kPa). (International Building Code, Section 2303.2.1). Because topically applied material is usually done to onlyone side it is only tested on one side. The treatment for fire-retardant treated wood is required to be symmetrical.Pressure treatment insures that it is.

The proposed revision will further clarify the manufacture and testing differences in the two products.

_______________________________________________________________________________________________703-5 Log #3 BLD-SCM

_______________________________________________________________________________________________Joseph T. Holland, Hoover Treated Wood Products

703-11Add text to read as follows:

A.3.3.2 Wood or wood products with topically applied materials or chemicals are not “fire-retardant treated wood”.Fire-retardant treated wood is required to be “pressure treated” or “other means during manufacture”. In both instancesthe treatment becomes an integral part of the wood. Pressure treatment is done in closed vessels under pressures notless than 50 pounds per square inch gauge (psig) (345 kPa). (International Building Code, Section 2303.2.1). For woodproducts produced by “other means during manufacture”, the treatment is a fundamental part of the manufacturingprocess of the wood product. The treatment must provide permanent protection to all surfaces of the wood product.(International Building Code, Section 2303.2.2.) Because topically applied material is usually done to only one side it isonly tested on one side. The treatment for fire-retardant treated wood is required to be symmetrical. Pressuretreatment insures that it is. For wood products produced by other means during manufacture all sides of the woodproduct shall be tested in accordance with and produce the results required in Section 3.3.2. Only the front and backfaces of wood structural panels need to be tested. (International Building Code, Section 2303.2.3.)

The proposed revision will further clarify the manufacture and testing differences in the two products.

2Printed on 9/16/2010BLD-SCM ROC AGENDA Page 37 of 37