Commissioning & Maintenance Guide

94
Operation Guide MiCOM P441, P442 & P444 Distance Protection Relays Chapter 3 COMMISSIONING 06/01 OG 1.1671-B

Transcript of Commissioning & Maintenance Guide

Page 1: Commissioning & Maintenance Guide

Operation GuideMiCOM P441, P442 & P444Distance Protection Relays

Chapter 3COMMISSIONING

06/01 OG 1.1671-B

Page 2: Commissioning & Maintenance Guide
Page 3: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 1

SECTION 1 . INTRODUCTION 1

SECTION 2 . SETTING FAMILIARISATION 2

SECTION 3 . EQUIPMENT REQUIRED FOR COMMISSIONING 3

3.1 Minimum Equipment Required 33.2 Optional Equipment 3

SECTION 4 . PRODUCT CHECKS 4

4.1 With the Relay De-energised 44.1.1 Visual Inspection 54.1.2 Current Transformer Shorting Contacts 64.1.3 External Wiring 74.1.4 Insulation 74.1.5 Watchdog Contacts 84.1.6 Auxiliary Supply 84.2 With the Relay Energised 94.2.1 Watchdog Contacts 94.2.2 Date and Time 94.2.3 Light Emitting Diodes (LEDs) 104.2.4 Field Voltage Supply 114.2.5 Input Opto-isolators 114.2.6 Output Relays 124.2.7 Rear Communications Port 154.2.8 Current Inputs 164.2.9 Voltage Inputs 17

SECTION 5 . SETTING CHECKS 18

5.1 Apply Application-Specific Settings 185.2 Check Application-Specific Settings 185.3 Demonstrate Correct Distance function Operation 195.4 Demonstrate Correct Overcurrent Function Operation 205.4.1 Connect the Test Circuit 205.4.2 Perform the Test 205.4.3 Check the Operating Time 215.5 Check Trip and Auto-reclose Cycle 21

SECTION 6 . ON-LOAD CHECKS 22

6.1 Voltage Connections 226.2 Current Connections 23

SECTION 7 . FINAL CHECKS 24

SECTION 8 . MAINTENANCE 25

8.1 Maintenance Period 258.2 Maintenance Checks 258.2.1 Alarms 258.2.2 Opto-isolators 258.2.3 Output Relays 258.2.4 Measurement accuracy 268.3 Method of Repair 268.3.1 Replacing the Complete Relay 268.3.2 Replacing a PCB 278.4 Recalibration 358.5 Changing the battery 358.5.1 Instructions for Replacing The Battery 358.5.2 Post Modification Tests 368.5.3 Battery Disposal 36

Page 4: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 1

SECTION 9 . COMMISSIONING TEST RECORD 37

9.1 Product Checks 379.1.1 With the Relay De-energised 379.1.2 With the Relay Energised 389.2 Setting Checks 43Application-specific function settings applied? Yes/No* 439.2.2 Application-specific function settings verified? Yes/No/na* 439.2.3 Protection Function Timing Tested? Yes/No* 43Trip and Auto-Reclose Cycle Checked Yes/No/na* 439.3 On-load Checks 439.3.1 VT wiring checked? Yes/No/na* 439.3.2 CT wiring checked ? Yes/No/na* 449.4 Final Checks 44

SECTION 10 . SETTING RECORD 45

Page 5: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 1

SECTION 1 . INTRODUCTION

The MiCOM P440 distance protection relays are fully numerical in their design,implementing all protection and non-protection functions in software. The relaysemploy a high degree of self-checking and, in the unlikely event of a failure, willgive an alarm. As a result of this, the commissioning tests do not need to be asextensive as with non-numeric electronic or electro-mechanical relays.

To commission numeric relays, it is only necessary to verify that the hardware isfunctioning correctly and the application-specific software settings have beenapplied to the relay. It is considered unnecessary to test every function of the relayif the settings have been verified by one of the following methods:

• Extracting the settings applied to the relay using appropriate setting software(Preferred method)

• Via the operator interface.

To confirm that the product is operating correctly once the application-specificsettings have been applied, a test should be performed on a single protectionelement.

Unless previously agreed to the contrary, the customer will be responsible fordetermining the application-specific settings to be applied to the relay and fortesting of any scheme logic applied by external wiring and/or configuration of therelays internal programmable scheme logic.

Blank commissioning test and setting records are provided at the end of thischapter for completion as required.

As the relays menu language is user-selectable, it is acceptable for theCommissioning Engineer to change it to allow accurate testing as long as the menuis restored to the customers preferred language on completion.

To simplify the specifying of menu cell locations in these CommissioningInstructions, they will be given in the form [courier reference: COLUMN HEADING,Cell Text]. For example, the cell for selecting the menu language (first cell underthe column heading) is located in the System Data column (column 00) so it wouldbe given as [0001: SYSTEM DATA, Language].

Before carrying out any work on the equipment, the user should be familiar withthe contents of the safety section and chapter 2, installation, of this manual.!

Page 6: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 2

SECTION 2 . SETTING FAMILIARISATION

When commissioning a MiCOM P440 relay for the first time, sufficient time shouldbe allowed to become familiar with the method by which the settings are applied.

Chapter 1 contains a detailed description of the menu structure of the relays.

With the secondary front cover in place all keys except the [Enter] key areaccessible. All menu cells can be read. LEDs and alarms can be reset. However,no protection or configuration settings can be changed, or fault and event recordscleared.

Removing the secondary front cover allows access to all keys so that settings can bechanged, LEDs and alarms reset, and fault and event records cleared. However,menu cells that have access levels higher than the default level will require theappropriate password to be entered before changes can be made.

Alternatively, if a portable PC is available together with suitable setting software(such as MiCOM S1), the menu can be viewed a page at a time to display a fullcolumn of data and text. This PC software also allows settings to be entered moreeasily, saved to a file on disk for future reference or printed to produce a settingrecord. Refer to the PC software user manual for details. If the software is beingused for the first time, allow sufficient time to become familiar with its operation.

Page 7: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 3

SECTION 3 . EQUIPMENT REQUIRED FOR COMMISSIONING

3.1 Minimum Equipment Required

Overcurrent test set with interval timer

110V ac voltage supply (if stage 1 of the overcurrent function is set directional)

Multimeter with suitable ac current range, and ac and dc voltage ranges of 0-440Vand 0-250V respectively

Continuity tester (if not included in multimeter)

Phase angle meter

Phase rotation meter

Note:Modern test equipment may contain many of the above features in one unit.

3.2 Optional Equipment

Multi-finger test plug type MMLB01 (if test block type MMLG installed)

An electronic or brushless insulation tester with a dc output not exceeding 500V(For insulation resistance testing when required).

A portable PC, with appropriate software (This enables the rear communicationsport to be tested if this is to be used and will also save considerable time duringcommissioning).

KITZ K-Bus to RS232 protocol converter (if RS485 K-Bus port is being tested andone is not already installed).

RS485 to RS232 converter (if RS485 Modbus port is being tested).

A printer (for printing a setting record from the portable PC).

Page 8: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 4

SECTION 4 . PRODUCT CHECKS

These product checks cover all aspects of the relay that need to be checked toensure that it has not been physically damaged prior to commissioning, isfunctioning correctly and all input quantity measurements are within the statedtolerances.

If the application-specific settings have been applied to the relay prior tocommissioning, it is advisable to make a copy of the settings so as to allow theirrestoration later. This could be done by:

• Obtaining a setting file on a diskette from the customer (This requires a portablePC with appropriate setting software for transferring the settings from the PC tothe relay)

• Extracting the settings from the relay itself (This again requires a portable PCwith appropriate setting software)

• Manually creating a setting record. This could be done using a copy of thesetting record located at the end of this chapter to record the settings as therelays menu is sequentially stepped through via the front panel user interface.

If password protection is enabled and the customer has changed password 2 thatprevents unauthorised changes to some of the settings, either the revised password2 should be provided, or the customer should restore the original password prior tocommencement of testing.

Note: In the event that the password has been lost, a recovery password can beobtained from ALSTOM by quoting the serial number of the relay. Therecovery password is unique to that relay and will not work on any otherrelay.

4.1 With the Relay De-energised

The following group of tests should be carried out without the auxiliary supplybeing applied to the relay and with the trip circuit isolated.

The current and voltage transformer connections must be isolated from the relayfor these checks. If an MMLG test block is provided, the required isolation caneasily be achieved by inserting test plug type MMLB01 which effectively open-circuits all wiring routed through the test block.

Before inserting the test plug, reference should be made to the scheme (wiring)diagram to ensure that this will not potentially cause damage or a safety hazard.For example, the test block may also be associated with protection currenttransformer circuits. It is essential that the sockets in the test plug which correspondto the current transformer secondary windings are linked before the test plug isinserted into the test block.

DANGER: NEVER OPEN CIRCUIT THE SECONDARY CIRCUIT OF A CURRENTTRANSFORMER SINCE THE HIGH VOLTAGE PRODUCED MAY BE LETHAL ANDCOULD DAMAGE INSULATION.

Page 9: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 5

If a test block is not provided, the voltage transformer supply to the relay should beisolated by means of the panel links or connecting blocks. The line currenttransformers should be short-circuited and disconnected from the relay terminals.Where means of isolating the auxiliary supply and trip circuit (e.g. isolation links,fuses, MCB, etc.) are provided, these should be used. If this is not possible, thewiring to these circuits will have to be disconnected and the exposed ends suitablyterminated to prevent them from being a safety hazard.

4.1.1 Visual Inspection

Carefully examine the relay to see that no physical damage has occurred sinceinstallation.

The rating information given under the top access cover on the front of the relayshould be checked to ensure it is correct for the particular installation.

Ensure that the case earthing connections, bottom left-hand corner at the rear ofthe relay case, are used to connect the relay to a local earth bar using an adequateconductor.

Figure 1a Rear terminal blocks on size 40TE case (P441)

Figure 1b Rear terminal blocks on size 60TE case (P442)

Page 10: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 6

1

2

3

4

5

6

7

8

9

101

1

121

3

141

5

161

7

18

1

2

3

4

5

6

7

8

9

101

1

121

3

141

5

161

7

18

1

2

3

4

5

6

7

8

9

101

1

121

3

141

5

161

7

18

1

2

3

4

5

6

7

8

9

101

1

121

3

141

5

161

7

18

1 2 3 19

7 8 9 21

4 5 6 20

10 11 12 22

13 14 15 23

16 17 18 24

1

2

3

4

5

6

7

8

9

101

1

121

3

141

5

161

7

18

1

2

3

4

5

6

7

8

9

101

1

121

3

141

5

161

7

18

1

2

3

4

5

6

7

8

9

101

1

121

3

141

5

161

7

18

1

2

3

4

5

6

7

8

9

101

1

121

3

141

5

161

7

18

IRIG-B

TXRX

A B C D E F G H J K L M N

Figure 1c Rear terminal blocks on size 80TE case (P444)

4.1.2 Current Transformer Shorting Contacts

If required, the current transformer shorting contacts can be checked to ensure thatthey close when the heavy duty terminal block (block reference C in Figure 1) isdisconnected from the current input PCB.

The heavy duty terminal block is fastened to the rear panel using four crossheadscrews. These are located top and bottom between the first and second, and thirdand fourth, columns of terminals.

Note: The use of a magnetic bladed screwdriver is recommended to minimize therisk of the screws being left in the terminal block or lost.

Pull the terminal block away from the rear of the case and check that all theshorting switches being used are closed with a continuity tester. Table 1 shows theterminals between which shorting contacts are fitted.

Page 11: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 7

Figure 2 Location of Securing Screws for Terminal Blocks

Shorting contact between terminalsCurrent Input

1A CTs 5A CTs

IA C3-C2 C1-C2

IB C6-C5 C4-C5

IC C9-C8 C7-C8

IM C12-C11 C10-C11

Table 1 Current Transformer Shorting Contact Locations

4.1.3 External Wiring

Check that the external wiring is correct to the relevant relay diagram or schemediagram. The relay diagram number appears on the rating label under the topaccess cover on the front of the relay. The corresponding connection diagram willhave been supplied with the ALSTOM order acknowledgement for the relay.

If an MMLG test block is provided, the connections should be checked against thescheme (wiring) diagram. It is recommended that the supply connections are tothe live side of the test block (coloured orange with the odd numbered terminals (1,3, 5, 7 etc.)). The auxiliary supply is normally routed via terminals 13 (supplypositive) and 15 (supply negative), with terminals 14 and 16 connected to therelays positive and negative auxiliary supply terminals respectively. However,check the wiring against the schematic diagram for the installation to ensurecompliance with the customers normal practice.

4.1.4 Insulation

Insulation resistance tests only need to be done during commissioning if it isrequired for them to be done and they havent been performed during installation.

Isolate all wiring from the earth and test the insulation with an electronic orbrushless insulation tester at a dc voltage not exceeding 500V. Terminals of thesame circuits should be temporarily connected together.

The main groups of relay terminals are:

a) Voltage transformer circuits.

b) Current transformer circuits

c) Auxiliary voltage supply.

d) Field voltage output and opto-isolated control inputs.

e) Relay contacts.

f) RS485 communication port.

g) Case earth.

The insulation resistance should be greater than 100MΩ at 500V.

On completion of the insulation resistance tests, ensure all external wiring iscorrectly reconnected to the unit.

Page 12: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 8

4.1.5 Watchdog Contacts

Using a continuity tester, check that the normally closed watchdog contacts are inthe states given in Table 2 for a de-energised relay.

Terminals Contact StateRelay De-energised Relay Energised

F11-F12J11-J12N11-N12

(P441)(P442)(P444)

Closed Open

F13-F14J13-J14N13-N14

(P441)(P442)(P444)

Open Closed

Table 2 Watchdog Contact Status

4.1.6 Auxiliary Supply

The relay can be operated from either a dc only or an ac/dc auxiliary supplydepending on the relays nominal supply rating. The incoming voltage must bewithin the operating range specified in Table 3.

Without energising the relay, measure the auxiliary supply to ensure it is within theoperating range.

Nominal Supply Rating

DC [AC rms]

DC OperatingRange

AC OperatingRange

24/54V [-] 19 - 65V -

48/110V [30/100V] 37 - 150V 24 - 110V

110/250V [100/240V] 87 - 300V 80 - 265V

Table 3 Operational Range of Auxiliary Supply

It should be noted that the relay can withstand an ac ripple of up to 12% of theupper rated voltage on the dc auxiliary supply.

DO NOT ENERGISE THE RELAY USING THE BATTERY CHARGER WITH THEBATTERY DISCONNECTED AS THIS CAN IRREPARABLY DAMAGE THE RELAYSPOWER SUPPLY CIRCUITRY.

Energise the relay if the auxiliary supply is within the operating range. If an MMLGtest block is provided, it may be necessary to link across the front of the test plug toconnect the auxiliary supply to the relay.

!

!

Page 13: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 9

4.2 With the Relay Energised

The following group of tests verify that the relay hardware and software isfunctioning correctly and should be carried out with the auxiliary supply applied tothe relay.

The current and voltage transformer connections must remain isolated from therelay for these checks.

4.2.1 Watchdog Contacts

Using a continuity tester, check the watchdog contacts are in the states given inTable 3 for an energized relay.

4.2.2 Date and Time

The date and time should now be set to the correct values. The method of settingwill depend on whether accuracy is being maintained via the optional Inter-RangeInstrumentation Group standard B (IRIG-B) port on the rear of the relay.

4.2.2.1 With an IRIG-B signal

If a satellite time clock signal conforming to IRIG-B is provided and the relay hasthe optional IRIG-B port fitted, the satellite clock equipment should be energised.

To allow the relays time and date to be maintained from an external IRIG-B sourcecell [0804: DATE and TIME, IRIG-B Sync] must be set to Enabled.

Ensure the relay is receiving the IRIG-B signal by checking that cell [0805: DATEand TIME, IRIG-B Status] reads Active.

Once the IRIG-B signal is active, adjust the time offset of the universal co-ordinatedtime (satellite clock time) on the satellite clock equipment so that local time isdisplayed.

Check the time, date and month are correct in cell [0801: DATE and TIME,Date/Time]. The IRIG-B signal does not contain the current year so it will need tobe set manually in this cell.

In the event of the auxiliary supply failing, with a battery fitted in the compartmentbehind the bottom access cover, the time and date will be maintained. Therefore,when the auxiliary supply is restored, the time and date will be correct and notneed to be set again.

To test this, remove the IRIG-B signal, then remove the auxiliary supply from therelay. Leave the relay de-energized for approximately 30 seconds. On re-energisation, the time in cell [0801: DATE and TIME, Date/Time] should be correct.

Reconnect the IRIG-B signal.

Page 14: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 10

4.2.2.2 Without an IRIG-B signal

If the time and date is not being maintained by an IRIG-B signal, ensure that cell[0804: DATE and TIME, IRIG-B Sync] is set to Disabled.

Set the date and time to the correct local time and date using cell [0801: DATE andTIME, Date/Time].

In the event of the auxiliary supply failing, with a battery fitted in the compartmentbehind the bottom access cover, the time and date will be maintained. Thereforewhen the auxiliary supply is restored the time and date will be correct and not needto be set again.

To test this, remove the auxiliary supply from the relay for approximately 30seconds. On re-energisation, the time in cell [0801: DATE and TIME, Date/Time]should be correct.

4.2.3 Light Emitting Diodes (LEDs)

On power up the green LED should have illuminated and stayed on indicating thatthe relay is healthy. The relay has non-volatile memory which remembers the state(on or off) of the alarm, trip and, if configured to latch, user-programmable LEDindicators when the relay was last energised from an auxiliary supply. Thereforethese indicators may also illuminate when the auxiliary supply is applied.

If any of these LEDs are on then they should be reset before proceeding withfurther testing. If the LEDs successfully reset (the LED goes out), there is no testingrequired for that LED because it is known to be operational.

Testing the alarm and out of service leds

The alarm and out of service LEDs can be tested using the COMMISSIONINGTESTS menu column. Set cell [0F0D: COMMISSIONING TESTS, Test Mode] toEnabled. Check that the alarm and out of service LEDs illuminate.

It is not necessary to return cell [0F0D: COMMISSIONING TESTS, Test Mode] toDisabled at this stage because test mode will be required for later tests.

Testing the trip led

The trip LED can be tested by initiating a manual circuit breaker trip from the relay.However, the trip LED will operate during the setting checks performed later.Therefore no further testing of the trip LED is required at this stage.

Testing the user-programmable leds

To test the user-programmable LEDs set cell [0F10: COMMISSIONING TESTS, TestLEDs] to Apply Test. Check that all 8 LEDs on the right-hand side of the relayilluminate.

Page 15: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 11

4.2.4 Field Voltage Supply

The relay generates a field voltage of nominally 48V that should be used toenergise the opto-isolated inputs.

Measure the field voltage across the terminals given in Table 5. Check that thefield voltage is present at each positive and negative terminal and that the polarityis correct.

Repeat for terminals 8 and 10.

Supply rail Terminals

P441 P442 P444

+ve F7 & F8 J7 & J8 N7 & N8

ve F9 & F10 J9 & J10 N9 & N10

Table 4 Field Voltage Terminals

4.2.5 Input Opto-isolators

This test checks that all the opto-isolated inputs are functioning correctly. The P441relays have 8 opto-isolated inputs while P442 relays have 16 opto-isolated inputsand P444 relays have 24 opto-isolated inputs.

The opto-isolated inputs should be energised one at a time. Ensuring correctpolarity, connect the field supply voltage to the appropriate terminals for the inputbeing tested. The opto-isolated input terminal allocations are given in Table 5.

Note: The opto-isolated inputs may be energised from an external 50V battery insome installations. Check that this is not the case before connecting the fieldvoltage otherwise damage to the relay may result.

The status of each opto-isolated input can be viewed using cell [0020: SYSTEMDATA, Opto I/P Status], a 1 indicating an energised input and a 0 indicating ade-energised input. When each opto-isolated input is energised one of thecharacters on the bottom line of the display will change to the value shown inTable 5 to indicate the new state of the inputs.

Page 16: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 12

Apply field voltage to terminals

P441 P442 P444

-ve +ve -ve +ve -ve +ve

Opto input 1 D1 D2 D1 D2 D1 D2

Opto input 2 D3 D4 D3 D4 D3 D4

Opto input 3 D5 D6 D5 D6 D5 D6

Opto input 4 D7 D8 D7 D8 D7 D8

Opto input 5 D9 D10 D9 D10 D9 D10

Opto input 6 D11 D12 D11 D12 D11 D12

Opto input 7 D13 D14 D13 D14 D13 D14

Opto input 8 D15 D16 D15 D16 D15 D16

Opto input 9 E1 E2 E1 E2

Opto input 10 E3 E4 E3 E4

Opto input 11 E5 E6 E5 E6

Opto input 12 E7 E8 E7 E8

Opto input 13 E9 E10 E9 E10

Opto input 14 E11 E12 E11 E12

Opto input 15 E13 E14 E13 E14

Opto input 16 E15 E16 E15 E16

Opto input 17 F1 F2

Opto input 18 F3 F4

Opto input 19 F5 F6

Opto input 20 F7 F8

Opto input 21 F9 F10

Opto input 22 F11 F12

Opto input 23 F13 F14

Opto input 24 F15 F16

Table 5 Opto-isolated Input Terminals

4.2.6 Output Relays

This test checks that all the output relays are functioning correctly. The P441 relayshave 14 output relays , the P442 relays have 21 output relays and the P444 relayshave 32 output relays.

Ensure that the relay is still in test mode by viewing cell [0F0D: COMMISSIONINGTESTS, Test Mode].

Page 17: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 13

The output relays should be energised one at a time. To select output relay 1 fortesting, set cell [0F0E: COMMISSIONING TESTS, Test Pattern] as shown in Table 6.

Connect an continuity tester across the terminals corresponding to output relay 1given in Table 6.

To operate the output relay set cell [0F0F: COMMISSIONING TESTS, Contact Test]to Apply Test. Operation will be confirmed by the continuity tester operating for anormally open contact and ceasing to operate for a normally closed contact.

Reset the output relay by setting cell [0F0F: COMMISSIONING TESTS, Contact Test]to Remove Test.

Note: It should be ensured that thermal ratings of anything connected to theoutput relays during the contact test procedure is not exceeded by theassociated output relay being operated for too long. It is therefore advisedthat the time between application and removal of contact test is kept to theminimum.

Repeat the test for relays 2 to 14 for P441 relays or relays 2 to 21 for P442 relaysor relays 2 to 32 for P444 relays.

Page 18: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 14

Output Monitor terminalsP441 P442 P444

N/C N/O N/C N/C N/O N/O

Relay 1 - E1-E2 - H1-H2 M1-M2

Relay 2 - E3-E4 - H3-H4 M3-M4

Relay 3 - E5-E6 - H5-H6 M5-M6

Relay 4 E7-E9 E8-E9 H7-H9 H8-H9 M7-M8

Relay 5 E10-E12 E11-E12 H10-H12 H11-H12 M9-M10

Relay 6 E13-E15 E14-E15 H13-H15 H14-H15 M11-M12

Relay 7 E16-E18 E17-E18 H16-H18 H17-H18 M13-M15 M14-M15 Relay 8 - B1-B2 - G1-G2 M16-M18 M17-M18 Relay 9 - B3-B4 - G3-G4 L1-L2

Relay 10 - B5-B6 - G5-G6 L3-L4

Relay 11 B7-B9 B8-B9 G7-G9 G8-G9 L5-L6

Relay 12 B10-B12 B11-B12 G10-G12 G11-G12 L7-L8

Relay 13 B13-B15 B14-B15 G13-G15 G14-G15 L9-L10

Relay 14 B16-B18 B17-B18 G16-G18 G17-G18 L11-L12

Relay 15 - F1-F2 L13-L15 L14-L15

Relay 16 - F3-F4 L16-L18 L17-L18

Relay 17 - F5-F6 K1-K2

Relay 18 F7-F9 F8-F9 K3-K4

Relay 19 F10-F12 F11-F12 K5-K6

Relay 20 F13-F15 F14-F15 K7-K8

Relay 21 F16-F18 F17-F18 K9-K10

Relay 22 K11-K12

Relay 23 K13-K15 K14-K15

Relay 24 K16-K18 K17-K18

Relay 25 J1-J2

Relay 26 J3-J4

Relay 27 J5-J6

Relay 28 J7-J8

Relay 29 J9-J10

Relay 30 J11-J12

Relay 31 J13-J15 J14-J15

Relay 32 J16-J18 J17-J18Table 6 Relay Output Terminals and Test Pattern Settings

Return the relay to service by setting cell [0F0D: COMMISSIONING TESTS, TestMode] to Disabled.

Page 19: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 15

4.2.7 Rear Communications Port

This test should only be performed where the relay is to be accessed from a remotelocation and will vary depending on the communications standard being adopted.

It is not the intention of the test to verify the operation of the complete system fromthe relay to the remote location, just the relays rear communications port and anyprotocol converter necessary.

4.2.7.1 Courier Communications

If a K-Bus to RS232 KITZ protocol converter is installed, connect a portable PCrunning the appropriate software to the incoming (remote from relay) side of theprotocol converter.

If a KITZ protocol converter is not installed, it may not be possible to connect thePC to the type installed. In this case a KITZ protocol converter and portable PCrunning appropriate software should be temporarily connected to the relays K-Busport. The terminal numbers for the relays K-Bus port are given in Table 7.However, as the installed protocol converter is not being used in the test, only thecorrect operation of the relays K-Bus port will be confirmed.

Connection Terminal

K-Bus Modbus orVDEW

P441 P442 P444

Screen Screen F16 J16 N16

1 +ve F17 J17 N17

2 ve F18 J18 N18

Table 7 RS485 Terminals

Ensure that the communications baud rate and parity settings in the applicationsoftware are set the same as those on the protocol converter (usually a KITZ butcould be a SCADA RTU). The relays Courier address in cell [0E02:COMMUNICATIONS, Remote Address] must be set to a value between 0 and 255.

Check that communications can be established with this relay using the portablePC.

4.2.7.2 Modbus Communications

Connect a portable PC running the appropriate Modbus Master Station software tothe relays RS485 port via a RS485 to RS232 interface converter. The terminalnumbers for the relays RS485 port are given in Table 7.

Ensure that the relay address, baud rate and parity settings in the applicationsoftware are set the same as those in cells [0E03: COMMUNICATIONS, RemoteAddress], [0E06: COMMUNICATIONS, Baud Rate] and [0E07:COMMUNICATIONS, Parity] of the relay.

Check that communications with this relay can be established.

4.2.7.3 IEC60870-5-103 (VDEW) Communications

If the relay has the optional fibre optic communications port fitted, the port to beused should be selected by setting cell [0E09: COMMUNICATIONS, Physical Link]to Fibre Optic or RS485.

Page 20: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 16

IEC60870-5-103/VDEW communication systems are designed to have a localMaster Station and this should be used to verify that the relays fibre optic or RS485port, as appropriate, is working.

Ensure that the relay address and baud rate settings in the application software areset the same as those in cells [0E03: COMMUNICATIONS, Remote Address] and[0E06: COMMUNICATIONS, Baud Rate] of the relay.

Check that, using the Master Station, communications with the relay can beestablished.

4.2.8 Current Inputs

This test verifies that the accuracy of current measurement is within the acceptabletolerances.

All relays will leave the factory set for operation at a system frequency of 50Hz. Ifoperation at 60Hz is required then this must be set in cell [0009: SYSTEMDATA, Frequency].

Apply current equal to the line current transformer secondary winding rating to theeach current transformer input of the corresponding rating in turn, checking itsmagnitude using a multimeter. Refer to Table 9 for the corresponding reading inthe relays MEASUREMENTS 1 column and record the value displayed.

Cell in MEASUREMENTS 1 column (02) Apply current to

1A line CT 5A line CT

[0201: IA Magnitude] C3-C2 C1-C2

[0203: IB Magnitude] C6-C5 C4-C5

[0205: IC Magnitude] C9-C8 C7-C8

[0207: IM Magnitude] C12-C11 C10-C11

Table 8 Current Input Terminals

The measured current values on the relay will either be in primary or secondaryAmperes. If cell [0D02: MEASURET SETUP, Local Values] is set to Primary, thevalues displayed on the relay should be equal to the applied current multiplied bythe corresponding current transformer ratio set in the VT and CT RATIOS menucolumn (see Table 8). If cell [0D02: MEASURET SETUP, Local Values] is set toSecondary, the value displayed should be equal to the applied current.

Page 21: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 17

The measurement accuracy of the relay is ±1%. However, an additional allowancemust be made for the accuracy of the test equipment being used.

Cell in MEASUREMENTS 1 column (02) Corresponding CT Ratio(in VT and CT RATIO column (0A) of

menu)

[0201: IA Magnitude][0203: IB Magnitude][0205: IC Magnitude]

[0A07: Phase CT Primary][0A08: Phase CT Sec' y]

[022F: IM Mutual Current Mag]

y]Sec'MComp/CT :[0A0CPrimary]MComp/CT :[0A0B

Table 9 CT Ratio Settings

4.2.9 Voltage Inputs

This test verifies the accuracy of voltage measurement is within the acceptabletolerances.

Apply rated voltage to each voltage transformer input in turn, checking itsmagnitude using a multimeter. Refer to Table 9 for the corresponding reading inthe relays MEASUREMENTS 1 column and record the value displayed.

Cell in MEASUREMENTS 1 column (02) Voltage applied To

[021A: VAN Magnitude] C19-C22

[021C: VBN Magnitude] C20-C22

[021E: VCN Magnitude] C21-C22

[022B: C/S Voltage Mag] C23-C24

Table 10 Voltage Input Terminals

The measured voltage values on the relay will either be in primary or secondaryvolts. If cell [0D02: MEASURET SETUP, Local Values] is set to Primary, the valuesdisplayed on the relay should be equal to the applied voltage multiplied by thecorresponding voltage transformer ratio set in the VT and CT RATIOS menucolumn (see Table 10). If cell [0D02: MEASURET SETUP, Local Values] is set toSecondary, the value displayed should be equal to the applied voltage.

The measurement accuracy of the relay is ±2%. However, an additional allowancemust be made for the accuracy of the test equipment being used.

Cell in MEASUREMENTS 1 column (02) Corresponding VT Ratio(in VT and CT RATIO column (0A) of

menu)

[021A: VAN Magnitude][021C: VBN Magnitude][021E: VCN Magnitude]

[0A01: Main VT Primary][0A02: Main VT Sec' y]

[022B: C/S Voltage Mag] [0A03: C / S VT Primary][0A04: C / S VT Secondary]

Table 11 VT Ratio Settings

Page 22: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 18

SECTION 5 . SETTING CHECKS

The setting checks ensure that all of the application-specific relay settings (i.e. boththe relays function and programmable scheme logic settings) for the particularinstallation have been correctly applied to the relay.

If the application-specific settings are not available, ignore sections 5.1 and 5.2.

5.1 Apply Application-Specific Settings

There are two methods of applying the settings:

• Transferring them from a pre-prepared setting file to the relay using a portablePC running the appropriate software via the relays front RS232 port, locatedunder the bottom access cover, or rear communications port (with a KITZprotocol converter connected). This method is the preferred for transferringfunction settings as it is much faster and there is less margin for error. Ifprogrammable scheme logic other than the default settings with which the relayis supplied are to be used then this is the only way of changing the settings.

If a setting file has been created for the particular application and provided on adiskette, this will further reduce the commissioning time and should always bethe case where programmable scheme logic changes are to be applied to therelay.

• Enter them manually via the relays operator interface. This method is notsuitable for changing the programmable scheme logic.

5.2 Check Application-Specific Settings

The settings applied should be carefully checked against the required application-specific settings to ensure they have been entered correctly. However, this is notconsidered essential if a customer-prepared setting file has been transferred to therelay using a portable PC.

There are two methods of checking the settings:

• Extract the settings from the relay using a portable PC running the appropriatesoftware via the front RS232 port, located under the bottom access cover, orrear communications port (with a KITZ protocol converter connected). Comparethe settings transferred from the relay with the original written application-specific setting record. (For cases where the customer has only provided aprinted copy of the required settings but a portable PC is available).

• Step through the settings using the relays operator interface and compare themwith the original application-specific setting record.

Unless previously agreed to the contrary, the application-specific programmablescheme logic will not be checked as part of the commissioning tests.

Due to the versatility and possible complexity of the programmable scheme logic, itis beyond the scope of these commissioning instructions to detail suitable testprocedures. Therefore, when programmable scheme logic tests must beperformed, written tests which will satisfactorily demonstrate the correct operationof the application-specific scheme logic should be devised by the Engineer whocreated it. These should be provided to the Commissioning Engineer together withthe diskette containing the programmable scheme logic setting file.

Page 23: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 19

5.3 Demonstrate Correct Distance function Operation

This section is not available yet.

Please refer to

publication ME 1.1671

for testing instructions of the

impedance characteristics.

Page 24: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 20

5.4 Demonstrate Correct Overcurrent Function Operation

This test, performed on stage 1 of the overcurrent protection function in settinggroup 1, demonstrates that the relay is operating correctly at the application-specific settings.

It is not considered necessary to check the boundaries of operation where cell[3502: GROUP 1 OVERCURRENT, I>1 Direction] is set to Directional Fwd orDirectional Rev as the test detailed already confirms the correct functionalitybetween current and voltage inputs, processor and outputs and earlier checksconfirmed the measurement accuracy is within the stated tolerance.

5.4.1 Connect the Test Circuit

Determine which output relay has been selected to operate when an I>1 tripoccurs by viewing the relays programmable scheme logic.

The programmable scheme logic can only be changed using the appropriatesoftware. If this software has not been available then the default output relayallocations will still be applicable.

If the trip outputs are phase-segregated (i.e. a different output relay allocated foreach phase), the relay assigned for tripping on A phase faults should be used.

If stage 1 is not mapped directly to an output relay in the programmable schemelogic, output relay 3 should be used for the test as it operates for any trip condition.

The associated terminal numbers can be found either from the external connectiondiagram (Appendix B) or Table 5.

Connect the output relay so that its operation will trip the test set and stop thetimer.

Connect the current output of the test set to the A phase current transformer inputof the relay (terminals C3 and C2 where 1A current transformers are being usedand terminals C1 and C2 for 5A current transformers).

If [3502: GROUP 1 OVERCURRENT, I>1 Direction] is set to Directional Fwd, thecurrent should flow out of terminal C2 but into C2 if set to Directional Rev.

If cell [351D: GROUP 1 OVERCURRENT, VCO Status] is set to Enabled(overcurrent function configured for voltage controlled overcurrent operation) or[3502: GROUP 1 OVERCURRENT, I>1 Direction] has been set to Directional Fwdor Directional Rev then rated voltage should be applied to terminals C19 andC22.

Ensure that the timer will start when the current is applied to the relay.

Note: If the timer does not start when the current is applied and stage 1 has beenset for directional operation, the connections may be incorrect for thedirection of operation set. Try again with the current connections reversed.

5.4.2 Perform the Test

Ensure that the timer is reset.

Apply a current of twice the setting in cell [3503: GROUP 1 OVERCURRENT, I>1Current Set] to the relay and note the time displayed when the timer stops.

Page 25: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 21

5.4.3 Check the Operating Time

Check that the operating time recorded by the timer is within the range shown inTable 12.

Note: Except for the definite time characteristic, the operating times given in Table12 are for a time multiplier or time dial setting of 1. Therefore, to obtainthe operating time at other time multiplier or time dial settings, the timegiven in Table 12 must be multiplied by the setting of cell [3505: GROUP 1OVERCURRENT, I>1 TMS] for IEC and UK characteristics or cell [3506:GROUP 1 OVERCURRENT, Time Dial] for IEEE and US characteristics.

In addition, for definite time and inverse characteristics there is anadditional delay of up to 0.02 second and 0.08 second respectively thatmay need to be added to the relays acceptable range of operating times.

For all characteristics, allowance must be made for the accuracy of the testequipment being used.

Characteristic Operating Time at twice current setting and timemultiplier/time dial setting of 1.0

Nominal(Seconds)

Range(Seconds)

DT [3504: I>1 Time Delay]setting

Setting ±2%

IEC S Inverse 10.03 9.53 - 10.53

IEC V Inverse 13.50 12.83 - 14.18

IEC E Inverse 26.67 24.67 - 28.67

UK LT Inverse 120.00 114.00 - 126.00

IEEE M Inverse 0.64 0.61 - 0.67

IEEE V Inverse 1.42 1.35 - 1.50

IEEE E Inverse 1.46 1.39 - 1.54

US Inverse 0.46 0.44 - 0.49

US ST Inverse 0.26 0.25 - 0.28

Table 12 Characteristic Operating Times for I>1

5.5 Check Trip and Auto-reclose Cycle

If the autoreclose function is being used, the circuit breaker trip and autoreclosecycle can be tested automatically at the application-specific settings.

To test the first autoreclose cycle, set cell [0F11: COMMISSIONING TESTS, TestAutoreclose] to 3 Pole Test. The relay will perform a trip/reclose cycle. Repeatthis operation to test the subsequent autoreclose cycles.

Check all output relays used for circuit breaker tripping and closing, blocking otherdevices, etc. operate at the correct times during the trip/close cycle.

Page 26: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 22

SECTION 6 . ON-LOAD CHECKS

Remove all test leads, temporary shorting leads, etc. and replace any externalwiring that has been removed to allow testing.

If it has been necessary to disconnect any of the external wiring from the relay inorder to perform any of the foregoing tests, it should be ensured that allconnections are replaced in accordance with the relevant external connection orscheme diagram.

The following on-load measuring checks ensure the external wiring to the currentand voltage inputs is correct but can only be carried out if there are no restrictionspreventing the energisation of the plant being protected.

6.1 Voltage Connections

Using a multimeter measure the voltage transformer secondary voltages to ensurethey are correctly rated. Check that the system phase rotation is correct using aphase rotation meter.

Compare the values of the secondary phase voltages with the relays measuredvalues, which can be found in the MEASUREMENTS 1 menu column.

If cell [0D02: MEASURET SETUP, Local Values] is set to Secondary, the valuesdisplayed on the relay should be equal to the applied secondary voltage. The relayvalues should be within 1% of the applied secondary voltages. However, anadditional allowance must be made for the accuracy of the test equipment beingused.

If cell [0D02: MEASURET SETUP, Local Values] is set to Primary, the valuesdisplayed on the relay should be equal to the applied secondary voltage multipliedthe corresponding voltage transformer ratio set in the VT & CT RATIOS menucolumn (see Table 13). Again the relay values should be within 1% of the expectedvalue, plus an additional allowance for the accuracy of the test equipment beingused.

Voltage Cell in MEASUREMENTS 1 column(02)

Corresponding VT Ratio (inVT and CT RATIO column

(0A) of menu)

VAB [0214: VAB Magnitude] [0A01: Main VT Primary][0A02: Main VT Sec' y]

VBC [0216: VBC Magnitude]

VCA [0218: VCA Magnitude]

VAN [021A: VAN Magnitude]

VBN [021C: VBN Magnitude]

VCN [021E: VCN Magnitude]

VCHECKSYNC [022B: C/S Voltage Mag] [0A03: C / S VT Primary][0A04: C / S VT Secondary]

Table 13 Measured Voltages and VT Ratio Settings

Page 27: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 23

6.2 Current Connections

Measure the current transformer secondary values for each using a multimeterconnected in series with corresponding relay current input.

Check that the current transformer polarities are correct by measuring the phaseangle between the current and voltage, either against a phase meter alreadyinstalled on site and known to be correct or by determining the direction of powerflow by contacting the system control centre.

Ensure the current flowing in the neutral circuit of the current transformers isnegligible.

Compare the values of the secondary phase currents and phase angle with therelays measured values, which can be found in the MEASUREMENTS 1 menucolumn.

Note: Under normal load conditions the earth fault function will measure little, ifany, current. It is therefore necessary to simulate a phase to neutral fault.This can be achieved by temporarily disconnecting one or two of the linecurrent transformer connections to the relay and shorting the terminals ofthese current transformer secondary windings.

If cell [0D02: MEASURET SETUP, Local Values] is set to Secondary, the currentsdisplayed on the relay should be equal to the applied secondary current. The relayvalues should be within 1% of the applied secondary currents. However, anadditional allowance must be made for the accuracy of the test equipment beingused.

If cell [0D02: MEASURET SETUP, Local Values] is set to Secondary, the currentsdisplayed on the relay should be equal to the applied secondary current multipliedby the corresponding current transformer ratio set in VT & CT RATIOS menucolumn (see Table 9). Again the relay values should be within 1% of the expectedvalue, plus an additional allowance for the accuracy of the test equipment beingused.

Page 28: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 24

SECTION 7 . FINAL CHECKS

The tests are now complete.

Remove all test or temporary shorting leads, etc. If it has been necessary todisconnect any of the external wiring from the relay in order to perform the wiringverification tests, it should be ensured that all connections are replaced inaccordance with the relevant external connection or scheme diagram.

Ensure that the relay has been restored to service by checking that cell [0F0D:COMMISSIONING TESTS, Test Mode] is set to Disabled.

If the relay is in a new installation or the circuit breaker has just been maintained,the circuit breaker maintenance and current counters should be zero. Thesecounters can be reset using cell [0608: CB CONDITION, Reset All Values]. If therequired access level is not active, the relay will prompt for a password to beentered so that the setting change can be made.

If a MMLG test block is installed, remove the MMLB01 test plug and replace theMMLG cover so that the protection is put into service.

Ensure that all event records, fault records, disturbance records, alarms and LEDshave been reset before leaving the relay.

If applicable, replace the secondary front cover on the relay.

Page 29: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 25

SECTION 8 . MAINTENANCE

8.1 Maintenance Period

It is recommended that products supplied by ALSTOM T&D Protection & Controlreceive regular monitoring after installation. As with all products somedeterioration with time is inevitable. In view of the critical nature of protectiverelays and their infrequent operation, it is desirable to confirm that they areoperating correctly at regular intervals.

ALSTOM protective relays are designed for a life in excess of 20 years.

MiCOM P440 distance relays are self-supervising and so require less maintenancethan earlier designs of relay. Most problems will result in an alarm so thatremedial action can be taken. However, some periodic tests should be done toensure that the relay is functioning correctly and the external wiring is intact.

If a Preventative Maintenance Policy exists within the customers organisation thenthe recommended product checks should be included in the regular program.Maintenance periods will depend on many factors, such as:

• the operating environment

• the accessibility of the site

• the amount of available manpower

• the importance of the installation in the power system

• the consequences of failure

8.2 Maintenance Checks

Although some functionality checks can be performed from a remote location byutilising the communications ability of the relays, these are predominantly restrictedto checking that the relay is measuring the applied currents and voltagesaccurately, and checking the circuit breaker maintenance counters. Therefore it isrecommended that maintenance checks are performed locally (i.e. at thesubstation itself).

BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE USER SHOULDBE FAMILIAR WITH THE SAFETY SECTION AND CHAPTER 2, INSTALLATION,OF THIS MANUAL.

8.2.1 Alarms

The alarm status LED should first be checked to identify if any alarm conditionsexist. If so, press the read key [] repeatedly to step the alarms. Clear the alarmsto extinguish the LED.

8.2.2 Opto-isolators

The opto-isolated inputs can be checked to ensure that the relay responds to theirenergisation by repeating the commissioning test detailed in Section 4.2.5 of thischapter.

8.2.3 Output Relays

The output relays can be checked to ensure that they operate by repeating thecommissioning test detailed in Section 4.2.6 of this chapter.

!

Page 30: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 26

8.2.4 Measurement accuracy

If the power system is energised, the values measured by the relay can becompared with known system values to check that they are in the approximaterange that is expected. If they are then the analogue/digital conversion andcalculations are being performed correctly by the relay. Suitable test methods canbe found in Sections 6.1 and 6.2 of this chapter.

Alternatively, the values measured by the relay can be checked against knownvalues injected into the relay via the test block, if fitted, or injected directly into therelay terminals. Suitable test methods can be found in Sections 4.2.8 and 4.2.9 ofthis chapter. These tests will prove the calibration accuracy is being maintained.

8.3 Method of Repair

If the relay should develop a fault whilst in service, depending on the nature of thefault, the watchdog contacts will change state and an alarm condition will beflagged. Due to the extensive use of surface-mount components faulty PCBsshould be replaced as it is not possible to perform repairs on damaged circuits.Thus either the complete relay or just the faulty PCB, identified by the in-builtdiagnostic software, can be replaced. Advice about identifying the faulty PCB canbe found in Chapter 4, Problem Analysis.

The preferred method is to replace the complete relay as it ensures that the internalcircuitry is protected against electrostatic discharge and physical damage at alltimes and overcomes the possibility of incompatibility between replacement PCBs.However, it may be difficult to remove an installed relay due to limited access in theback of the cubicle and rigidity of the scheme wiring.

Replacing PCBs can reduce transport costs but requires clean, dry conditions on siteand higher skills from the person performing the repair. However, if the repair isnot performed by an approved service centre, the warranty will be invalidated.

BEFORE CARRYING OUT ANY WORK ON THE EQUIPMENT, THE USER SHOULDBE FAMILIAR WITH THE SAFETY SECTION AND CHAPTER 2, INSTALLATION,OF THIS MANUAL. THIS SHOULD ENSURE THAT NO DAMAGE IS CAUSED BYINCORRECT HANDLING OF THE ELECTRONIC COMPONENTS.

8.3.1 Replacing the Complete Relay

The case and rear terminal blocks have been designed to facilitate removal of thecomplete relay should replacement or repair become necessary without having todisconnect the scheme wiring.

Before working at the rear of the relay, isolate all voltage and current supplies tothe relay.

Note: The MiCOM range of relays have integral current transformer shortingswitches which will close when the heavy duty terminal block is removed.

Disconnect the relay earth connection from the rear of the relay.

There are two types of terminal block used on the relay, medium and heavy duty,which are fastened to the rear panel using crosshead screws, as in Figure 2.

Note: The use of a magnetic bladed screwdriver is recommended to minimise therisk of the screws being left in the terminal block or lost.

Without exerting excessive force or damaging the scheme wiring, pull the terminalblocks away from their internal connectors.

!

Page 31: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 27

Remove the screws used to fasten the relay to the panel, rack, etc. These are thescrews with the larger diameter heads that are accessible when the access coversfitted and open.

IF THE TOP AND BOTTOM ACCESS COVERS HAVE BEEN REMOVED, DO NOTREMOVE THE SCREWS WITH THE SMALLER DIAMETER HEADS WHICH AREACCESSIBLE. THESE SCREWS HOLD THE FRONT PANEL ON THE RELAY.

Withdraw the relay from the panel, rack, etc. carefully because it will be heavy dueto the internal transformers.

To reinstall the repaired or replacement relay follow the above instructions inreverse, ensuring that each terminal block is relocated in the correct position andthe case earth, IRIG-B and fibre optic connections are replaced.

Once reinstallation is complete the relay should be recommissioned using theinstructions in sections 1 to 7 inclusive of this chapter.

8.3.2 Replacing a PCB

If the relay fails to operate correctly refer to Chapter 4, Problem Analysis, to helpdetermine which PCB has become faulty.

To replace any of the relays PCBs it is necessary to first remove the front panel.

Before removing the front panel to replace a PCB the auxiliary supply mustbe removed. It is also strongly recommended that the voltage and currenttransformer connections and trip circuit are isolated.

Open the top and bottom access covers. With size 60TE cases the access covershave two hinge-assistance T-pieces which clear the front panel moulding when theaccess covers are opened by more than 90°, thus allowing their removal.

If fitted, remove the transparent secondary front cover. A description of how to dothis is given in Chapter 1, Introduction.

By slightly bending the access covers at one end, the end pivot can be removedfrom its socket and the access cover removed to give access to the screws thatfasten the front panel to the case.

The size 40TE case has four crosshead screws fastening the front panel to the case,one in each corner, in recessed holes. The size 60TE case has an additional twoscrews, one midway along each of the top and bottom edges of the front plate.Undo and remove the screws.

DO NOT REMOVE THE SCREWS WITH THE LARGER DIAMETER HEADS WHICHARE ACCESSIBLE WHEN THE ACCESS COVERS ARE FITTED AND OPEN. THESESCREWS HOLD THE RELAY IN ITS MOUNTING (PANEL OR CUBICLE).

When the screws have been removed, the complete front panel can be pulledforward and separated from the metal case. Caution should be observed at thisstage because the front panel is connected to the rest of the relay circuitry by a 64-way ribbon cable.

The ribbon cable is fastened to the front panel using an IDC connector; a socket onthe cable itself and a plug with locking latches on the front panel. Gently push thetwo locking latches outwards which will eject the connector socket slightly. Removethe socket from the plug to disconnect the front panel.

!

!

Page 32: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 28

Figure 3 P441 PCB/Module Locations (Viewed from front)

Figure 4 P442 PCB/Module Locations (Viewed from front)

The PCBs within the relay are now accessible. Figures 3 and 4 show the PCBlocations for the distance relays in size 40TE (P441) and size 60TE (P442) casesrespectively.

The 64-way ribbon cable to the front panel also provides the electrical connectionsbetween PCBs with the connections being via IDC connectors.

The slots inside the case to hold the PCBs securely in place each correspond to arear terminal block. Looking from the front of the relay these terminal blocks arelabelled from right to left.

Note: To ensure compatibility, always replace a faulty PCB with one of an identicalpart number. Table 14 lists the part numbers of each PCB type.

PCB Part Number

Power Supply Board (24/54V dc)(48/125V dc)(110/250V dc)

ZN0001 001ZN0001 002ZN0001 003

Relay ET OPTO Board ZN0002 001

Page 33: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 29

Input ET OPTO Board ZN0005 001

Opto Board ZN0005 002

IRIG-B Board (IRIG-B input only)(Fibre optic port only)(Both)

ZN0007 001ZN0007 002ZN0007 003

Co-processor board ZN0003 003

Table 14 PCB Part Numbers

8.3.2.1 Replacement of the main processor board

The main processor board is located in the front panel, not within the case as withall the other PCBs.

Place the front panel with the user interface face-down and remove the six screwsfrom the metallic screen, as shown in Figure 5. Remove the metal plate.

There are two further screws, one each side of the rear of the battery compartmentmoulding, that hold the main processor PCB in position. Remove these screws.

The user interface keypad is connected to the main processor board via a flex-stripribbon cable. Carefully disconnect the ribbon cable at the PCB-mounted connectoras it could easily be damaged by excessive twisting.

Figure 5 Front Panel Assembly

Page 34: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 30

The front panel can then be re-assembled with a replacement PCB using thereverse procedure, ensuring that the ribbon cable is reconnected to the mainprocessor board and all eight screws are re-fitted.

Refit the front panel using the reverse procedure to that given in section 8.3.2.After refitting and closing the access covers on case sizes 60TE, press at thelocation of the hinge-assistance T-pieces so that they click back into the front panelmoulding.

After replacement of the main processor board, all the settings required for theapplication will need to be re-entered. Therefore, it is useful if an electronic copyof the application-specific settings is available on disk. Although this is notessential, it can reduce the time taken to re-enter the settings and hence the timethe protection is out of service.

Once the relay has been reassembled after repair, it should be recommissioned inaccordance with the instructions in sections 1 to 7 inclusive of this chapter.

8.3.2.2 Replacement of the IRIG-B board

Depending on the model number of the relay, the IRIG-B board may haveconnections for IRIG-B signals, IEC60870-5-103 (VDEW) communications, both ornot be present at all.

To replace a faulty board, disconnect all IRIG-B and/or IEC60870-5-103connections at the rear of the relay.

The module is secured in the case by two screws accessible from the rear of therelay, one at the top and another at the bottom, as shown in Figure 6. Removethese screws carefully as they are not captive in the rear panel of the relay.

Figure 6 Location of Securing Screws for IRIG-B Board

Gently pull the IRIG-B board forward and out of the case.

To help identify that the correct board has been removed, Figure 7 illustrates thelayout of the IRIG-B board with both IRIG-B and IEC60870-5-103 options fitted(ZN0007 003). The other versions (ZN0007 001 and ZN0007 002) use the samePCB layout but with less components fitted.

Page 35: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 31

Figure 7 Typical IRIG-B Board

The replacement PCB should be carefully slotted into the appropriate slot, ensuringthat it is pushed fully back on to the rear terminal blocks and the securing screwsare re-fitted.

Reconnect all IRIG-B and/or IEC60870-5-103 connections at the rear of the relay.

Refit the front panel using the reverse procedure to that given in section 8.3.2.After refitting and closing the access covers on case sizes 60TE, press at thelocation of the hinge-assistance T-pieces so that they click back into the front panelmoulding.

Once the relay has been reassembled after repair, it should be recommissioned inaccordance with the instructions in sections 1 to 7 inclusive of this chapter.

8.3.2.3 Replacement of the input module

The input module comprises of two boards fastened together, the transformerboard and the input board.

The module is secured in the case by two screws on its right-hand side, accessiblefrom the front of the relay, as shown in Figure 8. Remove these screws carefully asthey are not captive in the front plate of the module.

Page 36: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 32

Figure 8 Location of Securing Screws for Input Module

On the right-hand side of the analogue input module there is a small metal tabwhich brings out a handle. Grasping this handle firmly, pull the module forward,away from the rear terminal blocks. A reasonable amount of force will be requiredto achieve this due to the friction between the contacts of two terminal blocks, onemedium duty and one heavy duty.

Note: Care should be taken when withdrawing the input module as it will suddenlycome loose once the friction of the terminal blocks has been overcome. Thisis particularly important with loose relays as the metal case will need to beheld firmly whilst the module is withdrawn.

Remove the module from the case, taking care as it is heavy because it contains allthe relays input voltage and current transformers.

The replacement module can be slotted in using the reverse procedure, ensuringthat it is pushed fully back on to the rear terminal blocks and the securing screwsare re-fitted.

Note: The transformer and input boards within the module are calibrated togetherwith the calibration data being stored on the input board. Therefore it isrecommended that the complete module is replaced to avoid on-siterecalibration having to be performed.

Refit the front panel using the reverse procedure to that given in section 8.3.2.After refitting and closing the access covers on case sizes 60TE, press at thelocation of the hinge-assistance T-pieces so that they click back into the front panelmoulding.

Once the relay has been reassembled after repair, it should be recommissioned inaccordance with the instructions in sections 1 to 7 inclusive of this chapter.

8.3.2.4 Replacement of the power supply board

The power supply board is fastened to a relay board to form the power supplymodule and is located on the extreme left-hand side of all MiCOM distance relays.

Pull the power supply module forward, away from the rear terminal blocks and outof the case. A reasonable amount of force will be required to achieve this due tothe friction between the contacts of the two medium duty terminal blocks.

The two boards are held together with push-fit nylon pillars and can be separatedby pulling them apart. Care should be taken when separating the boards to avoid

Page 37: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 33

damaging the inter-board connectors located near the lower edge of the PCBstowards the front of the power supply module.

The power supply board is the one with two large electrolytic capacitors on it thatprotrude through the other board that forms the power supply module. To helpidentify that the correct board has been removed, Figure 9 illustrates the layout ofthe power supply board for all voltage ratings.

Figure 9 Typical Power Supply Board

Re-assemble the module with a replacement board ensuring the inter-boardconnectors are firmly pushed together and the four push-fit nylon pillars aresecurely located in their respective holes in each PCB.

Slot the power supply module back into the relay case, ensuring that it is pushedfully back on to the rear terminal blocks.

Refit the front panel using the reverse procedure to that given in section 8.3.2.After refitting and closing the access covers on case sizes 60TE, press at thelocation of the hinge-assistance T-pieces so that they click back into the front panelmoulding.

Once the relay has been reassembled after repair, it should be recommissioned inaccordance with the instructions in sections 1 to 7 inclusive of this chapter.

8.3.2.5 Replacement of the relay board in the power supply module

Remove and replace the relay board in the power supply module as described in8.3.2.4 above.

The relay board is the one with the board with holes cut in it to allow thetransformer and two large electrolytic capacitors to protrude through. To helpidentify that the correct board has been removed, Figure 10 illustrates the layout ofthe relay board.

Page 38: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 34

Figure 10 Typical Relay Board

Ensure the setting of the link (located above IDC connector) on the replacementrelay board is the same as the one being replaced before replacing the module inthe relay case.

Once the relay has been reassembled after repair, it should be recommissioned inaccordance with the instructions in sections 1 to 7 inclusive of this chapter.

8.3.2.6 Replacement of the extra relay board (P442 1 P444 only)

The P442 distance relay has two additional boards to the P441 and the P444 fouradditional boards to the P441. Some of these boards provides extra output relaysand optically-isolated inputs.

To remove it, gently pull the faulty PCB forward and out of the case.

If the relay board is being replaced, ensure the setting of the link (located aboveIDC connector) on the replacement relay board is the same as the one beingreplaced. To help identify that the correct board has been removed, Figures 10and 11 illustrate the layout of the relay and opto boards respectively.

The replacement PCB should be carefully slotted into the appropriate slot, ensuringthat it is pushed fully back on to the rear terminal blocks.

Refit the front panel using the reverse procedure to that given in section 8.3.2.After refitting and closing the access covers on case sizes 60TE, press at thelocation of the hinge-assistance T-pieces so that they click back into the front panelmoulding.

Page 39: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 35

Figure 11 Typical Opto Board

Once the relay has been reassembled after repair, it should be recommissioned inaccordance with the instructions in sections 1 to 7 inclusive of this chapter.

8.4 Recalibration

Recalibration is not usually required when a PCB is replaced unless it happens tobe one of the two boards in the input module, the replacement of which directlyaffect the calibration.

Although it is possible to carry out recalibration on site, this requires test equipmentwith suitable accuracy and a special calibration program to run on a PC. It istherefore recommended that the work is carried out by the manufacturer, orentrusted to an approved service centre.

8.5 Changing the battery

Each relay has a battery to maintain status data and the correct time when theauxiliary supply voltage fails. The data maintained include event, fault anddisturbance records and the thermal state at the time of failure.

This battery will periodically need changing, although an alarm will be given aspart of the relays continuous self-monitoring in the event of a low batterycondition.

If the battery-backed facilities are not required to be maintained during aninterruption of the auxiliary supply, the steps below can be followed to remove thebattery, but do not replace with a new battery.

8.5.1 Instructions for Replacing The Battery

Open the bottom access cover on the front of the relay.

Gently extract the battery from its socket. If necessary, use a small screwdriver toprize the battery free.

Page 40: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 36

Ensure that the metal terminals in the battery socket are free from corrosion, greaseand dust.

The replacement battery should be removed from its packaging and placed intothe battery holder, taking care to ensure that the polarity markings on the batteryagree with those adjacent to the socket.

Note: Only use a type ½AA Lithium battery with a nominal voltage of 3.6V.

Ensure that the battery is securely held in its socket and that the battery terminalsare making good contact with the metal terminals of the socket.

Close the bottom access cover.

8.5.2 Post Modification Tests

To ensure that the replacement battery will maintain the time and status data if theauxiliary supply fails, check cell [0806: DATE and TIME, Battery Status] readsHealthy.

8.5.3 Battery Disposal

The battery that has been removed should be disposed of in accordance with thedisposal procedure for Lithium batteries in the country in which the relay isinstalled.

!

Page 41: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 37

SECTION 9 . COMMISSIONING TEST RECORD

Date Engineer

Station Circuit

System Frequency

Front Plate Information

Distance protection relay P441/P442/P444*

Model number

Serial number

Rated Current In

Rated Voltage Vn

Auxiliary Voltage Vx

*Delete as appropriate

Have all relevant safety instructions been followed? Yes/No*

9.1 Product Checks

9.1.1 With the Relay De-energised

9.1.1.1 Visual Inspection

Relay damaged? Yes/No*

Rating information correct for installation? Yes/No*

Case earth installed? Yes/No*

9.1.1.2 Current transformer shorting contacts close? Yes/No/Not checked*

9.1.1.3 External Wiring

Wiring checked against diagram? Yes/No*

Test block connections checked? Yes/No/na*

9.1.1.4 Insulation resistance >100MΩ at 500V dc Yes/No/Not tested*

Page 42: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 38

9.1.1.5 Watchdog Contacts (auxiliary supply off)

Terminals 11 and 12 Contact closed? Yes/No*

Contact resistance ___Ω/Not measured*

Terminals 13 and 14 Contact open? Yes/No*

9.1.1.6 Measured Auxiliary Supply ______V ac/dc*

9.1.2 With the Relay Energised

9.1.2.1 Watchdog Contacts (auxiliary supply on)

Terminals 11 and 12 Contact open? Open/Closed*

Terminals 13 and 14 Contact closed? Open/Closed*

Contact resistance ____Ω/Not measured*

9.1.2.2 Date and Time

Clock set to local time? Yes/No*

Time maintained when auxiliary supply removed? Yes/No*

9.1.2.3 Light Emitting Diodes

Relay healthy (green) LED working? Yes/No*

Alarm (yellow) LED working? Yes/No*

Out of service (yellow) LED working? Yes/No*

Trip (red) LED working? Yes/No*

All 8 programmable LEDs working? Yes/No*

9.1.2.4 Field supply voltage

Value measured between terminals 7 and 9 ______V dc

Value measured between terminals 8 and 10 ______V dc

Page 43: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 39

9.1.2.5 Input Opto-isolators

Opto input 1 working? Yes/No*

Opto input 2 working? Yes/No*

Opto input 3 working? Yes/No*

Opto input 4 working? Yes/No*

Opto input 5 working? Yes/No*

Opto input 6 working? Yes/No*

Opto input 7 working? Yes/No*

Opto input 8 working? Yes/No*

Opto input 9 working? Yes/No/na*

Opto input 10 working? Yes/No/na*

Opto input 11 working? Yes/No/na*

Opto input 12 working? Yes/No/na*

Opto input 13 working? Yes/No/na*

Opto input 14 working? Yes/No/na*

Opto input 15 working? Yes/No/na*

Opto input 16 working? Yes/No/na*

Opto input 17 working? Yes/No/na*

Opto input 18 working? Yes/No/na*

Opto input 19 working? Yes/No/na*

Opto input 20 working? Yes/No/na*

Opto input 21 working? Yes/No/na*

Opto input 22 working? Yes/No/na*

Opto input 23 working? Yes/No/na*

Opto input 24 working? Yes/No/na*

9.1.2.6 Output Relays

Relay 1 Working? Yes/No*

Contact resistance ____Ω/Not measured*

Relay 2 Working? Yes/No*

Contact resistance ____Ω/Not measured*

Relay 3 Working? Yes/No*

Contact resistance ____Ω/Not measured*

Relay 4 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 5 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 6 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Page 44: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 40

Relay 7 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 8 Working? Yes/No*

Contact resistance ____Ω/Not measured*

Relay 9 Working? Yes/No*

Contact resistance ____Ω/Not measured*

Relay 10 Working? Yes/No*

Contact resistance ____Ω/Not measured*

Relay 11 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 12 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 13 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 14 Working? Yes/No*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 15 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 16 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 17 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 18 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 19 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 20 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Page 45: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 41

Relay 21 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 22 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 23 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 24 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 25 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 26 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 27 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 28 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 29 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 30 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 31 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Relay 32 Working? Yes/No/na*

Contact resistance (N/C) ____Ω/Not measured*

(N/O) ____Ω/Not measured*

Page 46: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 42

9.1.2.7 Rear Communications Port

Communication standard K-Bus/Modbus/IEC60870-5-103*

Communications established? Yes/No*

Protocol converter tested? Yes/No/na*

9.1.2.8 Current Inputs

Displayed Current Primary/Secondary*

Phase CT Ratio

y]Sec'CT Phase [

Primary]CT Phase [ _______A/na*

Mutual CT Ratio

y]Sec'CT Mutual [Primary]CT Mutual [ _______A/na*

Input CT Applied value Displayed value

IA _______A _______A

IB _______A _______A

IC _______A _______A

IM _______A _______A

9.1.2.9 Voltage Inputs

Displayed Voltage Primary/Secondary*

Main VT Ratio

y]Sec'VT Main [Primary]VT Main [ _______V/na*

C/S VT Ratio

Secondary]VT C/S [Primary]VT C/S [ _______V/na*

Input VT Applied value Displayed value

Va _______V _______V

Vb _______V _______V

Vc _______V _______V

C/S Voltage _______V/na* _______V

Page 47: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 43

9.2 Setting Checks

9.2.1 Application-specific function settings applied? Yes/No*

Application-specific programmable scheme logic settings applied? Yes/No/na*

If settings applied using a portable computer and software, whichsoftware and version was used? ___________________

9.2.2 Application-specific function settings verified? Yes/No/na*

Application-specific programmable scheme logic tested? Yes/No/na*

9.2.3 Protection Function Timing Tested? Yes/No*

Overcurrent type (cell [3502 I>1 Direction]) Directional/Non-directional*

Applied voltage _________V/na*

Applied current _________A

Expected operating time _________s

Measured operating time _________s

9.2.4 Trip and Auto-Reclose Cycle Checked Yes/No/na*

9.3 On-load Checks

Test wiring removed? Yes/No/na*

Disturbed customer wiring re-checked? Yes/No/na*

On-load test performed? Yes/No*

9.3.1 VT wiring checked? Yes/No/na*

Phase rotation correct? Yes/No*

Displayed Voltage Primary/Secondary*

Main VT Ratio

y]Sec'VT [MainPrimary]VT [Main _______V/na*

C/S VT Ratio

Secondary]VT [C/SPrimary]VT [C/S _______V/na*

Page 48: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 44

Voltages: Applied value Displayed value

Va _______V _______V

Vb _______V _______V

Vc _______V _______V

C/S Voltage _______V/na* _______V

9.3.2 CT wiring checked ? Yes/No/na*

CT polarities correct ? Yes/No*

Displayed Current Primary/Secondary*

Phase CT Ratio

y]Sec'CT [PhasePrimary]CT [Phase _______A/na*

Mutual CT Ratio

y]Sec'CT [MutualPrimary]CT [Mutual _______A/na*

Currents : Applied value Displayed value

IA _______A _______A

IB _______A _______A

IC _______A _______A

IM _______A _______A

9.4 Final Checks

Test wiring removed ? Yes/No/na*

Disturbed customer wiring re-checked ? Yes/No/na*

Circuit breaker operations counter reset ? Yes/No/na*

Current counters reset ? Yes/No/na*

Event records reset ? Yes/No*

Fault records reset ? Yes/No*

Disturbance records reset ? Yes/No*

Alarms reset ? Yes/No*

LEDs reset ? Yes/No*

Commissioning Engineer Customer Witness

Date Date

Page 49: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 45

SECTION 10 . SETTING RECORD

Date Engineer

Station Date

Circuit System Frequency

Front Plate Information

Distance protection relay P441/P442/P444*

Model number

Serial number

Rated Current In

Rated Voltage Vn

Auxiliary Voltage Vx

Setting Groups Used

Group 1 Yes/No*

Group 2 Yes/No*

Group 3 Yes/No*

Group 4 Yes/No*

0000 SYSTEM DATA F E D C B A 9 8 7 6 5 4 3 2 1 0

0001 Language English/Francais/Deutsch/Español*

0003 Sys Fn Links 0 0 0 0 0 0 0 0

0004 Description

0005 Plant Reference

0006 Model Number

0008 Serial Number

0009 Frequency 50 Hz/60 Hz

000A Comms Level

000B Relay Address

000E Active Group 1/2/3/4*

0011 Software Ref. 1

* Delete as appropriate

Page 50: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 46

0000 SYSTEM DATA F E D C B A 9 8 7 6 5 4 3 2 1 0

0012 Software Ref. 2

0013 Software Ref. 3

0014 Software Ref. 4

00D1 Password Control Level 0/Level 1/Level 2*

00D2 Password Level 1

00D3 Password Level 2

0100 VIEW RECORDS

01F0 Select Event 0/1/2/3/4*

0600 CB CONDITION

0601 CB Operations A _______ B _______ C _______

0602 Total IA Broken

0603 Total IB Broken

0604 Total IC Broken

0605 CB Operate Time secs

0607 Total 1P Reclosures

0608 Total 3P Reclosures

0700 CB CONTROL

0701 CB Control by Disabled/Local/Remote/Local+Remote/Opto/Opto+Local/Opto+Remote/Opto+Rem+Local*

0702 Manual Close PulseTime

secs

0703 Trip Pulse Time secs

0704 Man Close Delay secs

0705 Healthy Window secs

0706 C/S Window secs

0707 A/R Single Pole Disabled/Enabled*

0707 A/R Three Pole Disabled/Enabled*

0800 DATE AND TIME

0804 IRIG-B Sync Disabled/Enabled*

* Delete as appropriate

Page 51: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 47

0805 IRIG-B Status Inactive/Active*

0806 Battery Status Dead/Healthy*

0900 CONFIGURATION

0902 Setting Group Select via Menu/Select via Optos*

0903 Active Settings Group 1/Group 2/Group 3/Group 4*

0907 Setting Group 1 Disabled/Enabled*

0908 Setting Group 2 Disabled/Enabled*

0909 Setting Group 3 Disabled/Enabled*

090A Setting Group 4 Disabled/Enabled*

090D Distance Protection Disabled/Enabled*

0910 Power-Swing Disabled/Enabled*

0911 Back-up I> Disabled/Enabled*

0912 Neg Sequence O/C Disabled/Enabled*

0913 Broken Conductor Disabled/Enabled*

0914 Earth Fault O/C Disabled/Enabled*

0915 Aided D.E.F. Disabled/Enabled*

0916 Volt Protection Disabled/Enabled*

0917 CB Fail & I< Disabled/Enabled*

0918 Supervision Disabled/Enabled*

0919 System Checks Disabled/Enabled*

0924 Internal Auto-Reclose Disabled/Enabled*

0925 Input Labels Invisible/Visible*

0926 Output Labels Invisible/Visible*

0928 CT & VT Ratios Invisible/Visible*

0929 Recorder Control Invisible/Visible*

092A Disturb Recorder Invisible/Visible*

092B Measurement Setup Invisible/Visible*

092C Comms Settings Invisible/Visible*

092D Commission Tests Invisible/Visible*

092E Setting Values Primary/Secondary*

0A00 VT AND CT RATIOS

0A01 Main VT Primary V

0A02 Main VT Secondary V

0A03 C/S VT Primary V

0A04 C/S VT Secondary V

Page 52: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 48

0A00 VT AND CT RATIOS

0A07 Phase CT Primary A

0A08 Phase CT Secondary A

0A0B Mcomp CT Primary A

0A0C Mcomp CT Secy A

0A0F C/S Input A-N/B-N/C-N/A-B/B-C/C-A*

0A10 Main VT Location Line/Bus*

0C00 DISTURBANCE RECORDER

0C01 Duration secs

0C02 Trigger Position %

0C03 Trigger Mode Single/Extended*

0C04 Analog Channel 1 VA/VB/VC/VN/IA/IB/IC/IN/IM/VCHECKSYNC*

0C05 Analog Channel 2 VA/VB/VC/VN/IA/IB/IC/IN/IM/VCHECKSYNC*

0C06 Analog Channel 3 VA/VB/VC/VN/IA/IB/IC/IN/IM/VCHECKSYNC*

0C07 Analog Channel 4 VA/VB/VC/VN/IA/IB/IC/IN/IM/VCHECKSYNC*

0C08 Analog Channel 5 VA/VB/VC/VN/IA/IB/IC/IN/IM/VCHECKSYNC*

0C09 Analog Channel 6 VA/VB/VC/VN/IA/IB/IC/IN/IM/VCHECKSYNC*

0C0A Analog Channel 7 VA/VB/VC/VN/IA/IB/IC/IN/IM/VCHECKSYNC*

0C0B Analog Channel 8 VA/VB/VC/VN/IA/IB/IC/IN/IM/VCHECKSYNC*

0C0C Digital Input 1

0C0D Input 1 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C0E Digital Input 2

0C0F Input 2 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C10 Digital Input 3

0C11 Input 3 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C12 Digital Input 4

0C13 Input 4 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C14 Digital Input 5

0C15 Input 5 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C16 Digital Input 6

0C17 Input 6 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C18 Digital Input 7

0C19 Input 7 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C1A Digital Input 8

0C1B Input 8 Trigger No Trigger/Trigger L-H/Trigger H-L*

* Delete as appropriate

Page 53: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 49

0C00 DISTURBANCE RECORDER

0C1C Digital Input 9

0C1D Input 9 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C1E Digital Input 10

0C1F Input 10 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C20 Digital Input 11

0C21 Input 11 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C22 Digital Input 12

0C23 Input 12 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C24 Digital Input 13

0C25 Input 13 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C26 Digital Input 14

0C27 Input 14 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C28 Digital Input 15

0C29 Input 15 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C2A Digital Input 16

0C2B Input 16 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C2C Digital Input 17

0C2D Input 17 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C2E Digital Input 18

0C2F Input 18 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C30 Digital Input 19

0C31 Input 19 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C32 Digital Input 20

0C33 Input 20 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C34 Digital Input 21

0C35 Input 21 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C36 Digital Input 22

0C37 Input 22 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C38 Digital Input 23

0C39 Input 23 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C3A Digital Input 24

0C3B Input 24 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C3C Digital Input 25

0C3D Input 25 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C3E Digital Input 26

* Delete as appropriate

Page 54: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 50

0C00 DISTURBANCE RECORDER

0C3F Input 26 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C40 Digital Input 27

0C41 Input 27 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C42 Digital Input 28

0C43 Input 28 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C44 Digital Input 29

0C45 Input 29 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C46 Digital Input 30

0C47 Input 30 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C48 Digital Input 31

0C49 Input 31 Trigger No Trigger/Trigger L-H/Trigger H-L*

0C4A Digital Input 32

0C4B Input 32 Trigger No Trigger/Trigger L-H/Trigger H-L*

0D00 MEASURET SETUP

0D01 Default Display Date and Time/Description/Plant Reference/Frequency*

0D02 Local Values Primary/Secondary*

0D03 Remote Values Primary/Secondary*

0D04 Measurement Ref VA/VB/VC/IA/IB/IC*

0D05 Measurement Mode

0D06 Demand Interval mins

0D07 Distance Unit Kilometres/Miles*

0D08 Fault Location Distance/Ohms/% of Line*

0E00 COMMUNICATIONS

0E01 Rear Protocol Courier/IEC60870-5-103/Modbus*

0E02 Remote Address

0E03 Inactivity Timer mins

0E04 Baud Rate 9600/19200/38400*

0E05 Parity* Odd/Even/None*

0E06 Measuret Period* secs

0E09 Physical Link RS485/Fibre Optic*

* Delete as appropriate

Page 55: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 51

0F00 COMMISSION TESTS F E D C B A 9 8 7 6 5 4 3 2 1 0

0F05 Monitor Bit 1

0F06 Monitor Bit 2

0F07 Monitor Bit 3

0F08 Monitor Bit 4

0F09 Monitor Bit 5

0F0A Monitor Bit 6

0F0B Monitor Bit 7

0F0C Monitor Bit 8

0F0D Test Mode Disabled/Enabled*

0F0E Test Pattern Register 1 0 0 0 0 0 0 0 0 0 0 0

Register 2

1000 CB MONITOR SETUP

1001 Broken I^

1002 I^ Maintenance Alarm Disabled/Alarm Enabled*

1003 I^ Maintenance A

1004 I^ Lockout Alarm Disabled/Alarm Enabled*

1005 I^ Lockout A

1006 No. CB Ops Maint Alarm Disabled/Alarm Enabled*

1007 No. CB Ops Maint

1008 No. CB Ops Lock Alarm Disabled/Alarm Enabled*

1009 No. CB Ops Lock

100A CB Time Maint Alarm Disabled/Alarm Enabled*

100B CB Time Maint secs

100C CB Time Lockout Alarm Disabled/Alarm Enabled*

100D CB Time Lockout secs

100E Fault Freq Lock Alarm Disabled/Alarm Enabled*

100F Fault Freq Count

1010 Fault Freq Time

1012 Reset Lockout by USER Interface/CB Close*

1013 Man Close RstDly secs

GROUP 1 PROTECTION SETTINGS

3000 GROUP 1DISTANCE ELEMENTS

F E D C B A 9 8 7 6 5 4 3 2 1 0

3001 Line Setting

Page 56: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 52

3000 GROUP 1DISTANCE ELEMENTS

F E D C B A 9 8 7 6 5 4 3 2 1 0

30023003

Line Length metres / miles*

3004 Line Impedance Ω

3005 Line Angle °

3006 Zone Setting

3007 Zone Status 0 0 0

Z1x Enabled/Z2 Enabled/Zp Enabled/Z3 Enabled/Z4Enabled*

3008 kZ1 Res Comp

3009 kZ1 Angle °

300A Z1 Ω

300B Z1X Ω

300C R1G Ω

300D R1Ph Ω

300E tZ1 secs

300F kZ2 Res Comp

3010 kZ2 Angle °

3011 Z2 Ω

3012 R2G Ω

3013 R2Ph Ω

3014 tZ2 secs

3015 kZ3/4 Res Comp

3016 kZ3/4 Angle °

3017 Z3 Ω

3018 R3G - R4G Ω

3019 R3Ph - R4Ph Ω

301A tZ3 secs

301B Z4 Ω

301C tZ4 secs

301D Zone P - Direct. Directional Fwd/Directional Rev*

301E kZp Res Comp

301F kZp Angle °

3020 Zp Ω

3021 RpG Ω

* Delete as appropriate

Page 57: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 53

3000 GROUP 1DISTANCE ELEMENTS

F E D C B A 9 8 7 6 5 4 3 2 1 0

3022 RpPh Ω

3023 tZp secs

3024 Fault Locator

3025 kZm Mutual Comp

3026 kZm Angle °

3100 GROUP 1DISTANCE SCHEMES

F E D C B A 9 8 7 6 5 4 3 2 1 0

3101 Program Mode Standard Scheme/Open Scheme*

3102 Standard Mode Basic+Zone 1X /P.O.P. Z1/P.O.P. Z2/ P.U.P. Z2/P.U.P.Fwd/B.O.P. Z1/B.O.P. Z2

3103 Fault Type Fault Detection Disabled/Phase-to-Ground Fault Enabled/

Phase-to-Phase Fault Enabled/Both Enabled*

3104 Trip Mode Force 3 Pole/1Pole Z1&CR/1 Pole Z1, Z2&CR*

3105 Sig. Send Zone None/CsZ1/CsZ2/CsZ4*

3106 DistCR None/None+Z1x/PermZ1/PermZ2/PermFwd/BlkZ1/BlkZ2*

3107 Tp secs

3108 tReversal Guard secs

3109 Unblocking Logic None/Loss of Guard/Loss of Carrier*

310A TOR-SOTF Mode 0

TOR Z1 Enabled/TOR Z2 Enabled/TOR Z3 Enabled/TOR All Zones /

TOR Distance Schemes/SOTF All Zones/SOTF Level Detectors *

310B Z1 Ext On Chan Fail Disabled/Enabled*

310C Weak Infeed

310D WI :Mode Status Disabled/Echo/WI Trip & Echo*

310E WI : Single Pole Trip Disabled/Enabled*

310F WI : V< Thres. V

3110 WI : Trip Time Delay secs

3111 Loss Of Load

3112 LoL: Mode Status Disabled/Enabled*

3113 LoL: Chan. Fail Disabled/Enabled*

3114 LoL: I< A

* Delete as appropriate

Page 58: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 54

3100 GROUP 1DISTANCE SCHEMES

F E D C B A 9 8 7 6 5 4 3 2 1 0

3115 LoL: Window secs

3200 GROUP 1 POWER-SWING

F E D C B A 9 8 7 6 5 4 3 2 1 0

3201 Delta R Ω

3202 Delta X Ω

3203 IN > Status Disabled/Enabled*

3204 IN > (% Imax) %Imax

3205 I2 > Status Disabled/Enabled*

3206 I2 > (% Imax) %Imax

3207 Imax Line > Status Disabled/Enabled*

3208 Imax Line > A

3209 Unblocking Time Delay secs

320A Blocking zones 0 0 0 0

Z1&Z1X blocking/Z2 Blocking/Z3 Blocking/ Zp Blocking*

3500 GROUP 1 BACK-UP I>

3501 I>1 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

3502 I>1 Directional Non-Directional/Directional Fwd/Directional Rev*

3503 I>1 VTS Block Block/Non-Directional*

3504 I>1 Current Set A

3505 I>1 Time Delay secs

3506 I>1 Time VTS secs

3507 I>1 TMS

3508 I>1 Time Dial

3509 I>1 Reset Char DT/Inverse*

350A I>1 tRESET

350B I>2 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

350C I>2 Directional Non-Directional/Directional Fwd/Directional Rev*

350D I>2 VTS Block Block/Non-Directional

* Delete as appropriate

* Delete as appropriate

Page 59: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 55

3500 GROUP 1 BACK-UP I>

350E I>2 Current Set A

350F I>2 Time Delay secs

3510 I>2 Time VTS secs

3511 I>2 TMS

3512 I>2 Time Dial

3513 I>2 Reset Char DT/Inverse*

3514 I>2 tRESET

3515 I>3 Status Disabled/Enabled*

3516 I>3 Current Set A

3517 I>3 Time Delay secs

3518 I>4 Status Disabled/Enabled*

3519 I>4 Current Set A

351A I>4 Time Delay secs

3600 GROUP 1 NEG SEQUENCE O/C

3601 I>2 Status Disabled/Enabled*

3602 I>2 Directional Non-Directional/Directional Fwd/Directional Rev*

3603 I>2 VTS Block/Non-Directional*

3604 I>2 Current Set A

3605 I>2 Time Delay secs

3606 I>2 Char Angle °

3700 GROUP 1 BROKEN CONDUCTOR

3701 Broken Conductor Disabled/Enabled*

3702 I2/I1 Setting

3703 I2/I1 Time Delay secs

3800 GROUP 1 EARTH FAULT O/C

3801 IN>1 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

3802 IN>1 Directional Non-Directional/Directional Fwd/Directional Rev*

3803 IN>1 VTS Block Block/Non-directional*

3804 IN>1 Current Set A

3805 IN>1 Time Delay secs

* Delete as appropriate

Page 60: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 56

3806 IN>1 Time VTS secs

3807 IN>1 TMS

3808 IN>1 Time Dial

3809 IN>1 Reset Char DT/Inverse*

380A IN>1 tRESET secs

380B IN>2 Status Disabled/Enabled*

380C IN>2 VTS Block Block/Non-directional*

380D IN>2 Directional Non-Directional/Directional Fwd/Directional Rev*

380E IN>2 Current Set A

380F IN>2 Time Delay secs

3810 IN>2 Time VTS secs

3811 IN> Directional

3812 IN> Char Angle °

3813 Polarisation Zero Sequence/Neg Sequence*

3900 GROUP 1 - AIDED DEF

3901 Aided D.E.F. Status Disabled/Enabled*

3902 Polarisation Zero Sequence/Neg Sequence*

3903 V> Voltage Set V

3904 IN Forward A

3905 Time Delay secs

3906 Scheme Logic Shared/Blocking/Permissive*

3907 Tripping Any Phase/Three Phase*

4200 GROUP 1VOLT PROTECTION

F E D C B A 9 8 7 6 5 4 3 2 1 0

4201 UNDERVOLTAGE

4202 V< & V> MODE 0 0 0 0

V<1 Trip/V<2 Trip/V>1 Trip/V>2 Trip*

4203 V< Measurt Mode Phase-Phase/Phase-Neutral*

4204 V<1 Function Disabled/DT/IDMT*

4205 V<1 Voltage Set V

4206 V<1 Time Delay secs

4207 V<1 TMS

4208 V<2 Status Disabled/Enabled*

4209 V<2 Voltage Set V

420A V<2 Time Delay secs

420B OVERVOLTAGE

Page 61: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 57

4200 GROUP 1VOLT PROTECTION

F E D C B A 9 8 7 6 5 4 3 2 1 0

420C V> Measurt Mode Phase-Phase/Phase-Neutral*

420D V>1 Function Disabled/DT/IDMT*

420E V>1 Voltage Set V

420F V>1 Time Delay secs

4210 V>1 TMS

4211 V>2 Status Disabled/Enabled*

4212 V>2 Voltage Set V

4213 V>2 Time Delay secs

4500 GROUP 1 CB FAIL & I<

4501 BREAKER FAIL

4502 CB Fail 1 Status Disabled/Enabled*

4503 CB Fail 1 Timer secs

4504 CB Fail 2 Status Disabled/Enabled*

4505 CB Fail 2 Timer secs

4506 CBF Non I Reset I< Only/CB Open & I</Prot Reset & I<*

4507 CBF Ext Reset I< Only/CB Open & I</Prot Reset & I<*

4508 UNDER CURRENT

4509 I< Current Set A

4600 GROUP 1 SUPERVISION

4601 VT SUPERVISION

4602 VTS Time Delay secs

4603 VTS I2>&I0> Inhibit A

4604 Detect 3P Disabled/Enabled*

4605 Threshold 3P V

4606 Delta I> A

4607 CT SUPERVISION

4608 CTS Status Disabled/Enabled*

4609 CTS VN< Inhibit V

460A CTS IN> Set A

460B CTS Time Delay secs

* Delete as appropriate

Page 62: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 58

4800 GROUP 1 SYSTEM CHECKS

F E D C B A 9 8 7 6 5 4 3 2 1 0

4801 Chk Scheme A/R 0 0 0 0 0

Live Bus-Dead Line/Dead Bus-Live Line/Live Bus-Live Line*

4802 Chk Scheme Man CB 0 0 0 0 0

Live Bus-Dead Line/Dead Bus-Live Line/Live Bus-Live Line*

4803 V< Dead Line V

4804 V> Live Line V

4805 V< Dead Bus V

4806 V> Live Bus V

4807 Diff Voltage V

4808 Diff Frequency Hz

4809 Diff Phase °

480A Bus-Line Delay secs

4900 GROUP 1 AUTORECLOSE

4901 AUTORECLOSE MODE

4902 1P Trip Mode 1 / 1-3 / 1-3-3 / 1-3-3-3*

4903 3P Trip Mode 3 / 3-3 / 3-3-3 / 3-3-3-3*

4904 1P - Dead Time 1 secs

4905 3P - Dead Time 1 secs

4906 Dead Time 2 secs

4907 Dead Time 3 secs

4908 Dead Time 4 secs

4909 Reclaim Time secs

490A Reclose Pulse Time secs

490B A/R Inhibit Window secs

490C C/S on 3P Rcl DT1 Disabled/Enabled*

490D AUTORECLOSELOCKOUT

490E Block A/R

4A00 GROUP 1 INPUT LABELS

4A01 Opto Input 1

* Delete as appropriate

Page 63: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 59

4A00 GROUP 1 INPUT LABELS

4A02 Opto Input 2

4A03 Opto Input 3

4A04 Opto Input 4

4A05 Opto Input 5

4A06 Opto Input 6

4A07 Opto Input 7

4A08 Opto Input 8

4A09 Opto Input 9

4A0A Opto Input 10

4A0B Opto Input 11

4A0C Opto Input 12

4A0D Opto Input 13

4A0E Opto Input 14

4A0F Opto Input 15

4A10 Opto Input 16

4A11 Opto Input 17

4A12 Opto Input 18

4A13 Opto Input 19

4A14 Opto Input 20

4A15 Opto Input 21

4A16 Opto Input 22

4A17 Opto Input 23

4A18 Opto Input 24

4A19 Opto Input 25

4A1A Opto Input 26

4A1B Opto Input 27

4A1C Opto Input 28

4A1D Opto Input 29

4A1E Opto Input 30

4A1F Opto Input 31

4A20 Opto Input 32

4B00 GROUP 1 OUTPUT LABELS

4B01 Relay 1

4B02 Relay 2

4B03 Relay 3

Page 64: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 60

4B00 GROUP 1 OUTPUT LABELS

4B04 Relay 4

4B05 Relay 5

4B06 Relay 6

4B07 Relay 7

4B08 Relay 8

4B09 Relay 9

4B0A Relay 10

4B0B Relay 11

4B0C Relay 12

4B0D Relay 13

4B0E Relay 14

4B0F Relay 15

4B10 Relay 16

4B11 Relay 17

4B12 Relay 18

4B13 Relay 19

4B14 Relay 20

4B15 Relay 21

4B16 Relay 22

4B17 Relay 23

4B18 Relay 24

4B19 Relay 25

4B1A Relay 26

4B1B Relay 27

4B1C Relay 28

4B1D Relay 29

4B1E Relay 30

4B1F Relay 31

4B20 Relay 32

Page 65: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 61

GROUP 2 PROTECTION SETTINGS

5000 GROUP 2DISTANCE ELEMENTS

F E D C B A 9 8 7 6 5 4 3 2 1 0

5001 Line Setting

5002-5003

Line Length metres / miles*

5004 Line Impedance Ω

5005 Line Angle °

5006 Zone Setting

5007 Zone Status 0 0 0

Z1x Enabled/Z2 Enabled/Zp Enabled/Z3 Enabled/Z4Enabled*

5008 kZ1 Res Comp

5009 kZ1 Angle °

500A Z1 Ω

500B Z1X Ω

500C R1G Ω

500D R1Ph Ω

500E tZ1 secs

500F kZ2 Res Comp

5010 kZ2 Angle °

5011 Z2 Ω

5012 R2G Ω

5013 R2Ph Ω

5014 tZ2 secs

5015 kZ3/4 Res Comp

5016 kZ3/4 Angle °

5017 Z3 Ω

5018 R3G - R4G Ω

5019 R3Ph - R4Ph Ω

501A tZ3 secs

501B Z4 Ω

501C tZ4 secs

501D Zone P - Direct. Directional Fwd/Directional Rev*

501E kZp Res Comp

501F kZp Angle °

* Delete as appropriate

Page 66: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 62

5000 GROUP 2DISTANCE ELEMENTS

F E D C B A 9 8 7 6 5 4 3 2 1 0

5020 Zp Ω

5021 RpG Ω

5022 RpPh Ω

5023 tZp secs

5024 Fault Locator

5025 kZm Mutual Comp

5026 kZm Angle °

5100 GROUP 2DISTANCE SCHEMES

F E D C B A 9 8 7 6 5 4 3 2 1 0

5101 Program Mode Standard Scheme/Open Scheme*

5102 Standard Mode Basic+Zone 1X /P.O.P. Z1/P.O.P. Z2/ P.U.P. Z2/P.U.P.Fwd/B.O.P. Z1/B.O.P. Z2

5103 Fault Type Fault Detection Disabled/Phase-to-Ground Fault Enabled/

Phase-to-Phase Fault Enabled/Both Enabled*

5104 Trip Mode Force 3 Pole/1Pole Z1&CR/1 Pole Z1, Z2&CR*

5105 Sig. Send Zone None/CsZ1/CsZ2/CsZ4*

5106 DistCR None/None+Z1x/PermZ1/PermZ2/PermFwd/BlkZ1/BlkZ2*

5107 Tp secs

5108 tReversal Guard secs

5109 Unblocking Logic None/Loss of Guard/Loss of Carrier*

510A TOR-SOTF Mode 0

TOR Z1 Enabled/TOR Z2 Enabled/TOR Z3 Enabled/TOR All Zones /

TOR Distance Schemes/SOTF All Zones/SOTF Level Detectors *

510B Z1 Ext On Chan Fail Disabled/Enabled*

510C Weak Infeed

510D WI :Mode Status Disabled/Echo/WI Trip & Echo*

510E WI : Single Pole Trip Disabled/Enabled*

510F WI : V< Thres. V

5110 WI : Trip Time Delay secs

5111 Loss Of Load

5112 LoL: Mode Status Disabled/Enabled*

* Delete as appropriate

Page 67: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 63

5100 GROUP 2DISTANCE SCHEMES

F E D C B A 9 8 7 6 5 4 3 2 1 0

5113 LoL: Chan. Fail Disabled/Enabled*

5114 LoL: I< A

5115 LoL: Window secs

5200 GROUP 2 POWER-SWING

F E D C B A 9 8 7 6 5 4 3 2 1 0

5201 Delta R Ω

5202 Delta X Ω

5203 IN > Status Disabled/Enabled*

5204 IN > (% Imax) %Imax

5205 I2 > Status Disabled/Enabled*

5206 I2 > (% Imax) %Imax

5207 Imax Line > Status Disabled/Enabled*

5208 Imax Line > A

5209 Unblocking Time Delay secs

520A Blocking zones 0 0 0 0

Z1&Z1X blocking/Z2 Blocking/Z3 Blocking/ Zp Blocking*

5500 GROUP 2 BACK-UP I>

5501 I>1 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

5502 I>1 Directional Non-Directional/Directional Fwd/Directional Rev*

5503 I>1 VTS Block Block/Non-Directional*

5504 I>1 Current Set A

5505 I>1 Time Delay secs

5506 I>1 Time VTS secs

5507 I>1 TMS

5508 I>1 Time Dial

5509 I>1 Reset Char DT/Inverse*

550A I>1 tRESET

550B I>2 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

550C I>2 Directional Non-Directional/Directional Fwd/Directional Rev*

* Delete as appropriate

Page 68: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 64

5500 GROUP 2 BACK-UP I>

550D I>2 VTS Block Block/Non-Directional

550E I>2 Current Set A

550F I>2 Time Delay secs

5510 I>2 Time VTS secs

5511 I>2 TMS

5512 I>2 Time Dial

5513 I>2 Reset Char DT/Inverse*

5514 I>2 tRESET

5515 I>3 Status Disabled/Enabled*

5516 I>3 Current Set A

5517 I>3 Time Delay secs

5518 I>4 Status Disabled/Enabled*

5519 I>4 Current Set A

551A I>4 Time Delay secs

5600 GROUP 2 NEG SEQUENCE O/C

5601 I>2 Status Disabled/Enabled*

5602 I>2 Directional Non-Directional/Directional Fwd/Directional Rev*

5603 I>2 VTS Block/Non-Directional*

5604 I>2 Current Set A

5605 I>2 Time Delay secs

5606 I>2 Char Angle °

5700 GROUP 2 BROKEN CONDUCTOR

5701 Broken Conductor Disabled/Enabled*

5702 I2/I1 Setting

5703 I2/I1 Time Delay secs

5800 GROUP 2 EARTH FAULT O/C

5801 IN>1 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

5802 IN>1 Directional Non-Directional/Directional Fwd/Directional Rev*

5803 IN>1 VTS Block Block/Non-directional*

5804 IN>1 Current Set A

* Delete as appropriate

Page 69: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 65

5805 IN>1 Time Delay secs

5806 IN>1 Time VTS secs

5807 IN>1 TMS

5808 IN>1 Time Dial

5809 IN>1 Reset Char DT/Inverse*

580A IN>1 tRESET secs

580B IN>2 Status Disabled/Enabled*

580C IN>2 VTS Block Block/Non-directional*

580D IN>2 Directional Non-Directional/Directional Fwd/Directional Rev*

580E IN>2 Current Set A

580F IN>2 Time Delay secs

5810 IN>2 Time VTS secs

5811 IN> Directional

5812 IN> Char Angle °

5813 Polarisation Zero Sequence/Neg Sequence*

5900 GROUP 2 - AIDED DEF

5901 Aided D.E.F. Status Disabled/Enabled*

5902 Polarisation Zero Sequence/Neg Sequence*

5903 V> Voltage Set V

5904 IN Forward A

5905 Time Delay secs

5906 Scheme Logic Shared/Blocking/Permissive*

5907 Tripping Any Phase/Three Phase*

6200 GROUP 2VOLT PROTECTION

F E D C B A 9 8 7 6 5 4 3 2 1 0

6201 UNDERVOLTAGE

6202 V< & V> MODE 0 0 0 0

V<1 Trip/V<2 Trip/V>1 Trip/V>2 Trip*

6203 V< Measurt Mode Phase-Phase/Phase-Neutral*

6204 V<1 Function Disabled/DT/IDMT*

6205 V<1 Voltage Set V

6206 V<1 Time Delay secs

6207 V<1 TMS

* Delete as appropriate

Page 70: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 66

6200 GROUP 2VOLT PROTECTION

F E D C B A 9 8 7 6 5 4 3 2 1 0

6208 V<2 Status Disabled/Enabled*

6209 V<2 Voltage Set V

620A V<2 Time Delay secs

620B OVERVOLTAGE

620C V> Measurt Mode Phase-Phase/Phase-Neutral*

620D V>1 Function Disabled/DT/IDMT*

620E V>1 Voltage Set V

620F V>1 Time Delay secs

6210 V>1 TMS

6211 V>2 Status Disabled/Enabled*

6212 V>2 Voltage Set V

6213 V>2 Time Delay secs

6500 GROUP 2 CB FAIL & I<

6501 BREAKER FAIL

6502 CB Fail 1 Status Disabled/Enabled*

6503 CB Fail 1 Timer secs

6504 CB Fail 2 Status Disabled/Enabled*

6505 CB Fail 2 Timer secs

6506 CBF Non I Reset I< Only/CB Open & I</Prot Reset & I<*

6507 CBF Ext Reset I< Only/CB Open & I</Prot Reset & I<*

6508 UNDER CURRENT

6509 I< Current Set A

6600 GROUP 2 SUPERVISION

6601 VT SUPERVISION

6602 VTS Time Delay secs

6603 VTS I2>&I0> Inhibit A

6604 Detect 3P Disabled/Enabled*

6605 Threshold 3P V

6606 Delta I> A

6607 CT SUPERVISION

6608 CTS Status Disabled/Enabled*

* Delete as appropriate

Page 71: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 67

6600 GROUP 2 SUPERVISION

6609 CTS VN< Inhibit V

660A CTS IN> Set A

660B CTS Time Delay secs

6800 GROUP 2 SYSTEM CHECKS

F E D C B A 9 8 7 6 5 4 3 2 1 0

6801 Chk Scheme A/R 0 0 0 0 0

Live Bus-Dead Line/Dead Bus-Live Line/Live Bus-Live Line*

6802 Chk Scheme Man CB 0 0 0 0 0

Live Bus-Dead Line/Dead Bus-Live Line/Live Bus-Live Line*

6803 V< Dead Line V

6804 V> Live Line V

6805 V< Dead Bus V

6806 V> Live Bus V

6807 Diff Voltage V

6808 Diff Frequency Hz

6809 Diff Phase °

680A Bus-Line Delay secs

6900 GROUP 2 AUTORECLOSE

6901 AUTORECLOSE MODE

6902 1P Trip Mode 1 / 1-3 / 1-3-3 / 1-3-3-3*

6903 3P Trip Mode 3 / 3-3 / 3-3-3 / 3-3-3-3

6904 1P - Dead Time 1 secs

6905 3P - Dead Time 1 secs

6906 Dead Time 2 secs

6907 Dead Time 3 secs

6908 Dead Time 4 secs

6909 Reclaim Time secs

690A Reclose Pulse Time secs

690B A/R Inhibit Window secs

690C C/S on 3P Rcl DT1 Disabled/Enabled**

690D AUTORECLOSELOCKOUT

* Delete as appropriate

Page 72: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 68

6900 GROUP 2 AUTORECLOSE

690E Block A/R

6A00 GROUP 2 INPUT LABELS

6A01 Opto Input 1

6A02 Opto Input 2

6A03 Opto Input 3

6A04 Opto Input 4

6A05 Opto Input 5

6A06 Opto Input 6

6A07 Opto Input 7

6A08 Opto Input 8

6A09 Opto Input 9

6A0A Opto Input 10

6A0B Opto Input 11

6A0C Opto Input 12

6A0D Opto Input 13

6A0E Opto Input 14

6A0F Opto Input 15

6A10 Opto Input 16

6B00 GROUP 2 OUTPUT LABELS

6B01 Relay 1

6B02 Relay 2

6B03 Relay 3

6B04 Relay 4

6B05 Relay 5

6B06 Relay 6

6B07 Relay 7

6B08 Relay 8

6B09 Relay 9

6B0A Relay 10

6B0B Relay 11

6B0C Relay 12

6B0D Relay 13

6B0E Relay 14

Page 73: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 69

6B00 GROUP 2 OUTPUT LABELS

6B0F Relay 15

6B10 Relay 16

6B11 Relay 17

6B12 Relay 18

6B13 Relay 19

6B14 Relay 20

6B15 Relay 21

Page 74: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 70

GROUP 3 PROTECTION SETTINGS

7000 GROUP 3DISTANCE ELEMENTS

F E D C B A 9 8 7 6 5 4 3 2 1 0

7001 Line Setting

7002-7003

Line Length metres / miles*

7004 Line Impedance Ω

7005 Line Angle °

7006 Zone Setting

7007 Zone Status 0 0 0

Z1x Enabled/Z2 Enabled/Zp Enabled/Z3 Enabled/Z4Enabled*

7008 kZ1 Res Comp

7009 kZ1 Angle °

700A Z1 Ω

700B Z1X Ω

700C R1G Ω

700D R1Ph Ω

700E tZ1 secs

700F kZ2 Res Comp

7010 kZ2 Angle °

7011 Z2 Ω

7012 R2G Ω

7013 R2Ph Ω

7014 tZ2 secs

7015 kZ3/4 Res Comp

7016 kZ3/4 Angle °

7017 Z3 Ω

7018 R3G - R4G Ω

7019 R3Ph - R4Ph Ω

701A tZ3 secs

701B Z4 Ω

701C tZ4 secs

701D Zone P - Direct. Directional Fwd/Directional Rev*

701E kZp Res Comp

701F kZp Angle °

* Delete as appropriate

Page 75: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 71

7000 GROUP 3DISTANCE ELEMENTS

F E D C B A 9 8 7 6 5 4 3 2 1 0

7020 Zp Ω

7021 RpG Ω

7022 RpPh Ω

7023 tZp secs

7024 Fault Locator

7025 kZm Mutual Comp

7026 kZm Angle °

7100 GROUP 3DISTANCE SCHEMES

F E D C B A 9 8 7 6 5 4 3 2 1 0

7101 Program Mode Standard Scheme/Open Scheme*

7102 Standard Mode Basic+Zone 1X /P.O.P. Z1/P.O.P. Z2/ P.U.P. Z2/P.U.P.Fwd/B.O.P. Z1/B.O.P. Z2

7103 Fault Type Fault Detection Disabled/Phase-to-Ground Fault Enabled/

Phase-to-Phase Fault Enabled/Both Enabled*

7104 Trip Mode Force 3 Pole/1Pole Z1&CR/1 Pole Z1, Z2&CR*

7105 Sig. Send Zone None/CsZ1/CsZ2/CsZ4*

7106 DistCR None/None+Z1x/PermZ1/PermZ2/PermFwd/BlkZ1/BlkZ2*

7107 Tp secs

7108 tReversal Guard secs

7109 Unblocking Logic None/Loss of Guard/Loss of Carrier*

710A TOR-SOTF Mode 0

TOR Z1 Enabled/TOR Z2 Enabled/TOR Z3 Enabled/TOR All Zones /

TOR Distance Schemes/SOTF All Zones/SOTF Level Detectors *

710B Z1 Ext On Chan Fail Disabled/Enabled*

710C Weak Infeed

710D WI :Mode Status Disabled/Echo/WI Trip & Echo*

710E WI : Single Pole Trip Disabled/Enabled*

710F WI : V< Thres. V

7110 WI : Trip Time Delay secs

7111 Loss Of Load

7112 LoL: Mode Status Disabled/Enabled*

* Delete as appropriate

Page 76: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 72

7100 GROUP 3DISTANCE SCHEMES

F E D C B A 9 8 7 6 5 4 3 2 1 0

7113 LoL: Chan. Fail Disabled/Enabled*

7114 LoL: I< A

7115 LoL: Window secs

7200 GROUP 3 POWER-SWING

F E D C B A 9 8 7 6 5 4 3 2 1 0

7201 Delta R Ω

7202 Delta X Ω

7203 IN > Status Disabled/Enabled*

7204 IN > (% Imax) %Imax

7205 I2 > Status Disabled/Enabled*

7206 I2 > (% Imax) %Imax

7207 Imax Line > Status Disabled/Enabled*

7208 Imax Line > A

7209 Unblocking Time Delay secs

720A Blocking zones 0 0 0 0

Z1&Z1X blocking/Z2 Blocking/Z3 Blocking/ Zp Blocking*

7500 GROUP 3 BACK-UP I>

7501 I>1 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

7502 I>1 Directional Non-Directional/Directional Fwd/Directional Rev*

7503 I>1 VTS Block Block/Non-Directional*

7504 I>1 Current Set A

7505 I>1 Time Delay secs

7506 I>1 Time VTS secs

7507 I>1 TMS

7508 I>1 Time Dial

7509 I>1 Reset Char DT/Inverse*

750A I>1 tRESET

750B I>2 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

750C I>2 Directional Non-Directional/Directional Fwd/Directional Rev*

* Delete as appropriate

Page 77: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 73

7500 GROUP 3 BACK-UP I>

750D I>2 VTS Block Block/Non-Directional

750E I>2 Current Set A

750F I>2 Time Delay secs

7510 I>2 Time VTS secs

7511 I>2 TMS

7512 I>2 Time Dial

7513 I>2 Reset Char DT/Inverse*

7514 I>2 tRESET

7515 I>3 Status Disabled/Enabled*

7516 I>3 Current Set A

7517 I>3 Time Delay secs

7518 I>4 Status Disabled/Enabled*

7519 I>4 Current Set A

751A I>4 Time Delay secs

7600 GROUP 3 NEG SEQUENCE O/C

7601 I>2 Status Disabled/Enabled*

7602 I>2 Directional Non-Directional/Directional Fwd/Directional Rev*

7603 I>2 VTS Block/Non-Directional*

7604 I>2 Current Set A

7605 I>2 Time Delay secs

7606 I>2 Char Angle °

7700 GROUP 3 BROKEN CONDUCTOR

7701 Broken Conductor Disabled/Enabled*

7702 I2/I1 Setting

7703 I2/I1 Time Delay secs

7800 GROUP 3 EARTH FAULT O/C

7801 IN>1 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

7802 IN>1 Directional Non-Directional/Directional Fwd/Directional Rev*

7803 IN>1 VTS Block Block/Non-directional*

7804 IN>1 Current Set A

* Delete as appropriate

Page 78: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 74

7805 IN>1 Time Delay secs

7806 IN>1 Time VTS secs

7807 IN>1 TMS

7808 IN>1 Time Dial

7809 IN>1 Reset Char DT/Inverse*

780A IN>1 tRESET secs

780B IN>2 Status Disabled/Enabled*

780C IN>2 VTS Block Block/Non-directional*

780D IN>2 Directional Non-Directional/Directional Fwd/Directional Rev*

780E IN>2 Current Set A

780F IN>2 Time Delay secs

7810 IN>2 Time VTS secs

7811 IN> Directional

7812 IN> Char Angle °

7813 Polarisation Zero Sequence/Neg Sequence*

7900 GROUP 3 - AIDED DEF

7901 Aided D.E.F. Status Disabled/Enabled*

7902 Polarisation Zero Sequence/Neg Sequence*

7903 V> Voltage Set V

7904 IN Forward A

7905 Time Delay secs

7906 Scheme Logic Shared/Blocking/Permissive*

7907 Tripping Any Phase/Three Phase*

8200 GROUP 3VOLT PROTECTION

F E D C B A 9 8 7 6 5 4 3 2 1 0

8201 UNDERVOLTAGE

8202 V< & V> MODE 0 0 0 0

V<1 Trip/V<2 Trip/V>1 Trip/V>2 Trip*

8203 V< Measurt Mode Phase-Phase/Phase-Neutral*

8204 V<1 Function Disabled/DT/IDMT*

8205 V<1 Voltage Set V

8206 V<1 Time Delay secs

8207 V<1 TMS

* Delete as appropriate

Page 79: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 75

8200 GROUP 3VOLT PROTECTION

F E D C B A 9 8 7 6 5 4 3 2 1 0

8208 V<2 Status Disabled/Enabled*

8209 V<2 Voltage Set V

820A V<2 Time Delay secs

820B OVERVOLTAGE

820C V> Measurt Mode Phase-Phase/Phase-Neutral*

820D V>1 Function Disabled/DT/IDMT*

820E V>1 Voltage Set V

820F V>1 Time Delay secs

8210 V>1 TMS

8211 V>2 Status Disabled/Enabled*

8212 V>2 Voltage Set V

8213 V>2 Time Delay secs

8500 GROUP 3 CB FAIL & I<

8501 BREAKER FAIL

8502 CB Fail 1 Status Disabled/Enabled*

8503 CB Fail 1 Timer secs

8504 CB Fail 2 Status Disabled/Enabled*

8505 CB Fail 2 Timer secs

8506 CBF Non I Reset I< Only/CB Open & I</Prot Reset & I<*

8507 CBF Ext Reset I< Only/CB Open & I</Prot Reset & I<*

8508 UNDER CURRENT

8509 I< Current Set A

8600 GROUP 3 SUPERVISION

8601 VT SUPERVISION

8602 VTS Time Delay secs

8603 VTS I2>&I0> Inhibit A

8604 Detect 3P Disabled/Enabled*

8605 Threshold 3P V

8606 Delta I> A

8607 CT SUPERVISION

8608 CTS Status Disabled/Enabled*

* Delete as appropriate

Page 80: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 76

8600 GROUP 3 SUPERVISION

8609 CTS VN< Inhibit V

860A CTS IN> Set A

860B CTS Time Delay secs

8800 GROUP 3 SYSTEM CHECKS

F E D C B A 9 8 7 6 5 4 3 2 1 0

8801 Chk Scheme A/R 0 0 0 0 0

Live Bus-Dead Line/Dead Bus-Live Line/Live Bus-Live Line*

8802 Chk Scheme Man CB 0 0 0 0 0

Live Bus-Dead Line/Dead Bus-Live Line/Live Bus-Live Line*

8803 V< Dead Line V

8804 V> Live Line V

8805 V< Dead Bus V

8806 V> Live Bus V

8807 Diff Voltage V

8808 Diff Frequency Hz

8809 Diff Phase °

880A Bus-Line Delay secs

8900 GROUP 3 AUTORECLOSE

8901 AUTORECLOSE MODE

8902 1P Trip Mode 1 / 1-3 / 1-3-3 / 1-3-3-3*

8903 3P Trip Mode 3 / 3-3 / 3-3-3 / 3-3-3-3

8904 1P - Dead Time 1 secs

8905 3P - Dead Time 1 secs

8906 Dead Time 2 secs

8907 Dead Time 3 secs

8908 Dead Time 4 secs

8909 Reclaim Time secs

890A Reclose Pulse Time secs

890B A/R Inhibit Window secs

890C C/S on 3P Rcl DT1 Disabled/Enabled**

890D AUTORECLOSELOCKOUT

* Delete as appropriate

Page 81: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 77

8900 GROUP 3 AUTORECLOSE

890E Block A/R

8A00 GROUP 3 INPUT LABELS

8A01 Opto Input 1

8A02 Opto Input 2

8A03 Opto Input 3

8A04 Opto Input 4

8A05 Opto Input 5

8A06 Opto Input 6

8A07 Opto Input 7

8A08 Opto Input 8

8A09 Opto Input 9

8A0A Opto Input 10

8A0B Opto Input 11

8A0C Opto Input 12

8A0D Opto Input 13

8A0E Opto Input 14

8A0F Opto Input 15

8A10 Opto Input 16

8B00 GROUP 3 OUTPUT LABELS

8B01 Relay 1

8B02 Relay 2

8B03 Relay 3

8B04 Relay 4

8B05 Relay 5

8B06 Relay 6

8B07 Relay 7

8B08 Relay 8

8B09 Relay 9

8B0A Relay 10

8B0B Relay 11

8B0C Relay 12

8B0D Relay 13

8B0E Relay 14

Page 82: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 78

8B00 GROUP 3 OUTPUT LABELS

8B0F Relay 15

8B10 Relay 16

8B11 Relay 17

8B12 Relay 18

8B13 Relay 19

8B14 Relay 20

8B15 Relay 21

Page 83: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 79

GROUP 4 PROTECTION SETTINGS

9000 GROUP 4DISTANCE ELEMENTS

F E D C B A 9 8 7 6 5 4 3 2 1 0

9001 Line Setting

9002-9003

Line Length metres / miles*

9004 Line Impedance Ω

9005 Line Angle °

9006 Zone Setting

9007 Zone Status 0 0 0

Z1x Enabled/Z2 Enabled/Zp Enabled/Z3 Enabled/Z4Enabled*

9008 kZ1 Res Comp

9009 kZ1 Angle °

900A Z1 Ω

900B Z1X Ω

900C R1G Ω

900D R1Ph Ω

900E tZ1 secs

900F kZ2 Res Comp

9010 kZ2 Angle °

9011 Z2 Ω

9012 R2G Ω

9013 R2Ph Ω

9014 tZ2 secs

9015 kZ3/4 Res Comp

9016 kZ3/4 Angle °

9017 Z3 Ω

9018 R3G - R4G Ω

9019 R3Ph - R4Ph Ω

901A tZ3 secs

901B Z4 Ω

901C tZ4 secs

901D Zone P - Direct. Directional Fwd/Directional Rev*

901E kZp Res Comp

901F kZp Angle °

* Delete as appropriate

Page 84: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 80

9000 GROUP 4DISTANCE ELEMENTS

F E D C B A 9 8 7 6 5 4 3 2 1 0

9020 Zp Ω

9021 RpG Ω

9022 RpPh Ω

9023 tZp secs

9024 Fault Locator

9025 kZm Mutual Comp

9026 kZm Angle °

9100 GROUP 4DISTANCE SCHEMES

F E D C B A 9 8 7 6 5 4 3 2 1 0

9101 Program Mode Standard Scheme/Open Scheme*

9102 Standard Mode Basic+Zone 1X /P.O.P. Z1/P.O.P. Z2/ P.U.P. Z2/P.U.P.Fwd/B.O.P. Z1/B.O.P. Z2

9103 Fault Type Fault Detection Disabled/Phase-to-Ground Fault Enabled/

Phase-to-Phase Fault Enabled/Both Enabled*

9104 Trip Mode Force 3 Pole/1Pole Z1&CR/1 Pole Z1, Z2&CR*

9105 Sig. Send Zone None/CsZ1/CsZ2/CsZ4*

9106 DistCR None/None+Z1x/PermZ1/PermZ2/PermFwd/BlkZ1/BlkZ2*

9107 Tp secs

9108 tReversal Guard secs

9109 Unblocking Logic None/Loss of Guard/Loss of Carrier*

910A TOR-SOTF Mode 0

TOR Z1 Enabled/TOR Z2 Enabled/TOR Z3 Enabled/TOR All Zones /

TOR Distance Schemes/SOTF All Zones/SOTF Level Detectors *

910B Z1 Ext On Chan Fail Disabled/Enabled*

910C Weak Infeed

910D WI :Mode Status Disabled/Echo/WI Trip & Echo*

910E WI : Single Pole Trip Disabled/Enabled*

910F WI : V< Thres. V

9110 WI : Trip Time Delay secs

9111 Loss Of Load

9112 LoL: Mode Status Disabled/Enabled*

* Delete as appropriate

Page 85: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 81

9100 GROUP 4DISTANCE SCHEMES

F E D C B A 9 8 7 6 5 4 3 2 1 0

9113 LoL: Chan. Fail Disabled/Enabled*

9114 LoL: I< A

9115 LoL: Window secs

9200 GROUP 4 POWER-SWING

F E D C B A 9 8 7 6 5 4 3 2 1 0

9201 Delta R Ω

9202 Delta X Ω

9203 IN > Status Disabled/Enabled*

9204 IN > (% Imax) %Imax

9205 I2 > Status Disabled/Enabled*

9206 I2 > (% Imax) %Imax

9207 Imax Line > Status Disabled/Enabled*

9208 Imax Line > A

9209 Unblocking Time Delay secs

920A Blocking zones 0 0 0 0

Z1&Z1X blocking/Z2 Blocking/Z3 Blocking/ Zp Blocking*

9500 GROUP 4 BACK-UP I>

9501 I>1 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

9502 I>1 Directional Non-Directional/Directional Fwd/Directional Rev*

9503 I>1 VTS Block Block/Non-Directional*

9504 I>1 Current Set A

9505 I>1 Time Delay secs

9506 I>1 Time VTS secs

9507 I>1 TMS

9508 I>1 Time Dial

9509 I>1 Reset Char DT/Inverse*

950A I>1 tRESET

950B I>2 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

950C I>2 Directional Non-Directional/Directional Fwd/Directional Rev*

* Delete as appropriate

Page 86: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 82

9500 GROUP 4 BACK-UP I>

950D I>2 VTS Block Block/Non-Directional

950E I>2 Current Set A

950F I>2 Time Delay secs

9510 I>2 Time VTS secs

9511 I>2 TMS

9512 I>2 Time Dial

9513 I>2 Reset Char DT/Inverse*

9514 I>2 tRESET

9515 I>3 Status Disabled/Enabled*

9516 I>3 Current Set A

9517 I>3 Time Delay secs

9518 I>4 Status Disabled/Enabled*

9519 I>4 Current Set A

951A I>4 Time Delay secs

9600 GROUP 4 NEG SEQUENCE O/C

9601 I>2 Status Disabled/Enabled*

9602 I>2 Directional Non-Directional/Directional Fwd/Directional Rev*

9603 I>2 VTS Block/Non-Directional*

9604 I>2 Current Set A

9605 I>2 Time Delay secs

9606 I>2 Char Angle °

9700 GROUP 4 BROKEN CONDUCTOR

9701 Broken Conductor Disabled/Enabled*

9702 I2/I1 Setting

9703 I2/I1 Time Delay secs

9800 GROUP 4 EARTH FAULT O/C

9801 IN>1 Function Disabled/DT/IEC S Inverse/IEC V Inverse/IEC E Inverse/UK LT Inverse/IEEE M Inverse/IEEE V Inverse/

IEEE E Inverse/US Inverse/US ST Inverse*

9802 IN>1 Directional Non-Directional/Directional Fwd/Directional Rev*

9803 IN>1 VTS Block Block/Non-directional*

9804 IN>1 Current Set A

* Delete as appropriate

Page 87: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 83

9805 IN>1 Time Delay secs

9806 IN>1 Time VTS secs

9807 IN>1 TMS

9808 IN>1 Time Dial

9809 IN>1 Reset Char DT/Inverse*

980A IN>1 tRESET secs

980B IN>2 Status Disabled/Enabled*

980C IN>2 VTS Block Block/Non-directional*

980D IN>2 Directional Non-Directional/Directional Fwd/Directional Rev*

980E IN>2 Current Set A

980F IN>2 Time Delay secs

9810 IN>2 Time VTS secs

9811 IN> Directional

9812 IN> Char Angle °

9813 Polarisation Zero Sequence/Neg Sequence*

9900 GROUP 4 - AIDED DEF

9901 Aided D.E.F. Status Disabled/Enabled*

9902 Polarisation Zero Sequence/Neg Sequence*

9903 V> Voltage Set V

9904 IN Forward A

9905 Time Delay secs

9906 Scheme Logic Shared/Blocking/Permissive*

9907 Tripping Any Phase/Three Phase*

A200 GROUP 4VOLT PROTECTION

F E D C B A 9 8 7 6 5 4 3 2 1 0

A201 UNDERVOLTAGE

A202 V< & V> MODE 0 0 0 0

V<1 Trip/V<2 Trip/V>1 Trip/V>2 Trip*

A203 V< Measurt Mode Phase-Phase/Phase-Neutral*

A204 V<1 Function Disabled/DT/IDMT*

A205 V<1 Voltage Set V

A206 V<1 Time Delay secs

A207 V<1 TMS

* Delete as appropriate

Page 88: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 84

A200 GROUP 4VOLT PROTECTION

F E D C B A 9 8 7 6 5 4 3 2 1 0

A208 V<2 Status Disabled/Enabled*

A209 V<2 Voltage Set V

A20A V<2 Time Delay secs

A20B OVERVOLTAGE

A20C V> Measurt Mode Phase-Phase/Phase-Neutral*

A20D V>1 Function Disabled/DT/IDMT*

A20E V>1 Voltage Set V

A20F V>1 Time Delay secs

A210 V>1 TMS

A211 V>2 Status Disabled/Enabled*

A212 V>2 Voltage Set V

A213 V>2 Time Delay secs

A500 GROUP 4 CB FAIL & I<

A501 BREAKER FAIL

A502 CB Fail 1 Status Disabled/Enabled*

A503 CB Fail 1 Timer secs

A504 CB Fail 2 Status Disabled/Enabled*

A505 CB Fail 2 Timer secs

A506 CBF Non I Reset I< Only/CB Open & I</Prot Reset & I<*

A507 CBF Ext Reset I< Only/CB Open & I</Prot Reset & I<*

A508 UNDER CURRENT

A509 I< Current Set A

A600 GROUP 4 SUPERVISION

A601 VT SUPERVISION

A602 VTS Time Delay secs

A603 VTS I2>&I0> Inhibit A

A604 Detect 3P Disabled/Enabled*

A605 Threshold 3P V

A606 Delta I> A

A607 CT SUPERVISION

A608 CTS Status Disabled/Enabled*

* Delete as appropriate

Page 89: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 85

A600 GROUP 4 SUPERVISION

A609 CTS VN< Inhibit V

A60A CTS IN> Set A

A60B CTS Time Delay secs

A800 GROUP 4 SYSTEM CHECKS

F E D C B A 9 8 7 6 5 4 3 2 1 0

A801 Chk Scheme A/R 0 0 0 0 0

Live Bus-Dead Line/Dead Bus-Live Line/Live Bus-Live Line*

A802 Chk Scheme Man CB 0 0 0 0 0

Live Bus-Dead Line/Dead Bus-Live Line/Live Bus-Live Line*

A803 V< Dead Line V

A804 V> Live Line V

A805 V< Dead Bus V

A806 V> Live Bus V

A807 Diff Voltage V

A808 Diff Frequency Hz

A809 Diff Phase °

A80A Bus-Line Delay secs

A900 GROUP 4 AUTORECLOSE

A901 AUTORECLOSE MODE

A902 1P Trip Mode 1 / 1-3 / 1-3-3 / 1-3-3-3*

A903 3P Trip Mode 3 / 3-3 / 3-3-3 / 3-3-3-3

A904 1P - Dead Time 1 secs

A905 3P - Dead Time 1 secs

A906 Dead Time 2 secs

A907 Dead Time 3 secs

A908 Dead Time 4 secs

A909 Reclaim Time secs

A90A Reclose Pulse Time secs

A90B A/R Inhibit Window secs

A90C C/S on 3P Rcl DT1 Disabled/Enabled**

A90D AUTORECLOSELOCKOUT

* Delete as appropriate

Page 90: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 86

A900 GROUP 4 AUTORECLOSE

A90E Block A/R

AA00 GROUP 4 INPUT LABELS

AA01 Opto Input 1

AA02 Opto Input 2

AA03 Opto Input 3

AA04 Opto Input 4

AA05 Opto Input 5

AA06 Opto Input 6

AA07 Opto Input 7

AA08 Opto Input 8

AA09 Opto Input 9

AA0A Opto Input 10

AA0B Opto Input 11

AA0C Opto Input 12

AA0D Opto Input 13

AA0E Opto Input 14

AA0F Opto Input 15

AA10 Opto Input 16

AB00 GROUP 4 OUTPUT LABELS

AB01 Relay 1

AB02 Relay 2

AB03 Relay 3

AB04 Relay 4

AB05 Relay 5

AB06 Relay 6

AB07 Relay 7

AB08 Relay 8

AB09 Relay 9

AB0A Relay 10

AB0B Relay 11

AB0C Relay 12

AB0D Relay 13

AB0E Relay 14

Page 91: Commissioning & Maintenance Guide

OPERATION GUIDE OG 1.1671-BDISTANCE PROTECTION RELAYS Volume 2MiCOM P441, P442 & P444 Chapter 3

Page 87

AB00 GROUP 4 OUTPUT LABELS

AB0F Relay 15

AB10 Relay 16

AB11 Relay 17

AB12 Relay 18

AB13 Relay 19

AB14 Relay 20

AB15 Relay 21

Page 92: Commissioning & Maintenance Guide
Page 93: Commissioning & Maintenance Guide
Page 94: Commissioning & Maintenance Guide

ALSTOM T&D Protection & Contrôle – Avenue de Figuières – BP 75 – 34975 Lattes Cedex – FranceTel: +33 (0)4 67 20 54 54 – Fax: +33 (0)4 67 20 54 99 – Email: [email protected] – www.tde.alstom.com