COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of...

24
COMMERCIAL REFRIGERATION CO 2 TRANSCRITICAL

Transcript of COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of...

Page 1: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

COMMERCIAL REFRIGERATION

CO2 TRANSCRITICAL

Page 2: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

2

The greatest care has been taken in the realization of this document. Notwithstanding Tewis Smart Systems, S.L.U. does not assume any liability arising from the use thereof. Tewis Smart Systems, S.L.U. reserves the right to make any changes to the data and features that appear in this document, at any time and without prior notice, in order to improve and update its content.

TEWIS CO2 TIMELINE

2005 2013

SUBCRITICAL

CO2 Subcritical

TEWIS Laboratory

NH3 + pumped CO2 Transcritical + AC

TEWIS LaboratoryINDUSTRIAL

RANGE TRANSCRITICAL

RETAILREFRIG. + AC

GMpack FULL GM FULL

INDUSTRIAL& High Power

Up to 950 kW

RECENT FACILITIES MAP

Refrigeración 100% CO2

Refrigeración + Clima 100% CO2

Refrigeración + Clima con eyector

Chiller NH3 + CO2 bombeado

CO2 bombeado

100% CO2 Refrigeration

Refrigeration + AC100% CO2

Refrigeration + AC with ejector

NH3 Chiller + Pumped CO2

Pumped CO2

Page 3: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

3

CO2 TRANSCRITICAL REFRIGERATION

FAMILY OF TRANSCRITICAL CYCLE MACHINES FOR POSITIVE COOLING (MEDIA), NEGATIVE (LOW) OR A COMBINATION OF BOTH IN COMMERCIAL APPLICATIONS.

CO2 IS THE ONLY REFRIGERANT PRESENT IN THE SALES ROOM.

IT COMPLIES 100% WITH THE F-GAS REGULATIONS.

Advantages of using R744 refrigerant

Not flammableNot toxicODP= 0 harmless to the ozone shield

GWP = 1low level of global warming

High density in suctionmore performance with small units

Requires a lower gas load

FULL power plants are equipped with compressors that stand out for their performance; Operability, robustness and reliability of operation.

The DORIN four-cylinder range stands out for its high volumetric displacement, highly optimized in its compact geometry. They are especially suitable for high power plants within the commercial range.

The BITZER compressors, historical reference of the Tewis power plants, offer excellent technical performance and proven reliability on every machine.

MHX/EHXUEM RHX RHX RHXPIHX

COMPRESSORS

All FULL units include at least one inverter compressor capable of reaching 70 Hz.

Emergency unit Parallel compression IHX LT MTMHX / EHX RHX GC

Heat recoveryavailable

Page 4: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

44

EFFICIENCY BY MODULATION (V.F.D.)

A frequency converter in the first compressor of each group, adapts its operation to the specific demand of each moment, saving energy and prolonging the life of the plant.

POWER AND COMPRESSORS

MINI

RACK

DUPLEX

MT

MT

70 kW

102 kW

59 + 8 kWMT + LT

94 + 8 kWMT + LT

230 + 22 kWMT + LT

Units and groups of compression between 2 and 9 compressors. In case of parallel compression, up to 2 specific compressors are used.

The services and maximum powers reached by each model are:

PLUG & PLAY

The power plants are prepared for a very agile implementation at mechanical and electronic level, with the built-in electrical panel.

FINISH

Bodywork in galvanized steel sheet painted in the oven.

Accessible 360º for easy maintenance.

Acoustic insulation (Optional).

THE ULTIMATE LEAP TOWARDS NATURAL REFRIGERATION

MHXEHX

PIHX

Q

HEAT RECOVERY

A smart way to take advantage of the heat generated by the plant, for example, in ACS applications, air conditioning ... (Optional)

RHX

Safety unitSwitchboard

ParallelCompressor(Option)

Internal Exchanger (Option)

Touch Screen and control

Exchangers(Option)

CO2 Container

Page 5: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

55

MHXEHX

LT

MT

P

IHX

Q

THE MOST COMPLETE SOLUTION OF THE MARKET. F GAS FREE.

LT

MT

By equipping the power plants with the optional MHX or with compressors in parallel, we can equate, also in hot climates, the performance of the transcritical cycle with that of traditionally efficient systems such as the cascade system.

MHX It reduces the outlet temperature of the cooler gas and minimizes the amount of gas generated in the container, improving the performance of the average compressors and the efficiency of the system. It is more efficient than the compressor itself in parallel, but requires an external cooling source (new freon or retrofit machine, chiller, etc.). EHX In case of suffering a heat wave, with abnormally high outside temperatures, it allows the unit not to decrease its refrigeration performance. Like the previous option, it requires an external cold source.

We also recommend the use of adiabatic gas coolers and Spray System

SPECIALLY DESIGNED FOR WARM CLIMATES

OPTIONAL EXCHANGERSMechanical/ Emergency Heat Exchanger. They keep the plant at its optimal operating point when the ambient temperatures are high.

LOW TEMPERATURE GROUPIt covers the freezing needs. Equipped with oil system, connections for gas cooler and all the necessary protection and safety elements.

MEDIUM TEMPERATURE GROUPCovers the cooling needs and allows the operation of the LT group. Equipped with oil system, connections for gas cooler and all the necessary protection and safety elements. Includes CO2 container that, depending on the model, can be remote.

PARALLEL COMPRESSIONImproves the performance of the MT compressors, eliminating the charge of the flash gas by-pass and improving the efficiency of the system. Especially suitable for hot climates.

OPTIONAL EXCHANGER INTERNALRecommended in installations with large distances between the plant and the evaporators. Prevents the presence of flash gas in the liquid line.

SWITCHBOARDIntegrated and easy to use by touch screen, it shows an exclusive control software (Rack and Duplex models).

Medium temperature compressors

Stainless steel in 100% of pipes

Exchangers(Option)

Low temperaturecompressors

Page 6: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

6

MINI

COOLING CAPACITY WITH GAS COOLER COOLING CAPACITY WITH GAS COOLER AND MOUNTED CONTAINER

MT (max) -- 18 kW 36 kW 63 kW 68 kW 70 kW 102 kW -- -- --

BOOSTER MT+LT (max) -- 14 + 4 kW 32 + 4 kW 40 + 4 kW 60 + 8 kW 59 + 8 kW 84 + 18 kW -- -- --

COOLING CAPACITY WITHOUT GAS COOLER COOLING CAPACITY WITHOUT GAS COOLER AND REMOTE CONTAINER

MT (max) 44 kW 36 kW 36 kW 63 kW -- 102 kW -- -- -- --

BOOSTER MT+LT (max) 40 + 4 kW 32 + 4 kW 32 + 4 kW 40 + 4 kW -- 94 + 8 kW -- 194 + 22 kW 230 + 22 kW 220 + 22 kW *

RECOVERY CAPACITY RECOVERY CAPACITY

RHX Optional 31 kW 13 kW 25 kW 40 kW 45 kW 50 kW 70 kW 150 kW 170 kW 170 kW

COMPOSITION COMPOSITION

Compressors (Total) 2 up to 3 1 up to 2 1 up to 3 2 up to 3 3 up to 4 2 up to 3 3 up to 4 5 up to 7 6 up to 8 7 up to 9

Fans (Axial / Radial) -- 2 2 3 3 2 3 -- -- --

Plant dimensions 1000 x 840 mm 1600 x 840 mm 1600 x 840 mm 2300 x 840 mm 3300 x 840 mm 2520 x 1350 mm 3460 x 1350 mm 3060 x 1350 mm 3600 x 1350 mm 4000 x 1350 mm

OPTIONAL OPTIONAL

EHX, IHX, RHX, MHX Maximum 1 RHX per machine MAX. 1 (RHX / IHX) Maximum 2 per machine Maximum 3 per machine

Page 7: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

7

RACK DUPLEX

COMMERCIAL REFRIGERATION IN A TRANSCRITICAL CYCLE

COOLING CAPACITY WITH GAS COOLER COOLING CAPACITY WITH GAS COOLER AND MOUNTED CONTAINER

MT (max) -- 18 kW 36 kW 63 kW 68 kW 70 kW 102 kW -- -- --

BOOSTER MT+LT (max) -- 14 + 4 kW 32 + 4 kW 40 + 4 kW 60 + 8 kW 59 + 8 kW 84 + 18 kW -- -- --

COOLING CAPACITY WITHOUT GAS COOLER COOLING CAPACITY WITHOUT GAS COOLER AND REMOTE CONTAINER

MT (max) 44 kW 36 kW 36 kW 63 kW -- 102 kW -- -- -- --

BOOSTER MT+LT (max) 40 + 4 kW 32 + 4 kW 32 + 4 kW 40 + 4 kW -- 94 + 8 kW -- 194 + 22 kW 230 + 22 kW 220 + 22 kW *

RECOVERY CAPACITY RECOVERY CAPACITY

RHX Optional 31 kW 13 kW 25 kW 40 kW 45 kW 50 kW 70 kW 150 kW 170 kW 170 kW

COMPOSITION COMPOSITION

Compressors (Total) 2 up to 3 1 up to 2 1 up to 3 2 up to 3 3 up to 4 2 up to 3 3 up to 4 5 up to 7 6 up to 8 7 up to 9

Fans (Axial / Radial) -- 2 2 3 3 2 3 -- -- --

Plant dimensions 1000 x 840 mm 1600 x 840 mm 1600 x 840 mm 2300 x 840 mm 3300 x 840 mm 2520 x 1350 mm 3460 x 1350 mm 3060 x 1350 mm 3600 x 1350 mm 4000 x 1350 mm

OPTIONAL OPTIONAL

EHX, IHX, RHX, MHX Maximum 1 RHX per machine MAX. 1 (RHX / IHX) Maximum 2 per machine Maximum 3 per machine

Calculation conditions: Ev. T. MT-8ºC LT-32ºC Tsgc +35ºC* with parallel compression

Page 8: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

8

MINIMini compact units, with a footprint of less than 1m2 and highly competitive for the generation of cold with CO2 in the transcritical cycle. It serves refrigeration services in one or two temperatures, working as a booster.Its design allows easy access to the components, streamlining maintenance tasks.

PS 120 / 70 / 52 /32 BAR

REDUCED FOOTPRINT

% BarCOMPACTDESIGN

SIDE DOOR ALSO ACCESSIBLE

DESIGN ADAPTED FOR BETTER LOADING AND

TRANSPORTATION

ELECTRICAL PANEL WITH CONTROL UNIT AND COMPLETE WIRING

COMPATIBLE WITH TEWIS REMOTE MANAGEMENT SYSTEMS

UP TO 2 MT COMPRESSORS AND 1 LT COMPRESSOR EASY ACCESS AND MAINTENANCE

VERTICAL LIQUID CONTAINER WITH

EXCHANGER PREPARED FOR ITS CONNECTION TO

THE EMERGENCY UNIT

FRONT DOOR OPENING THROUGH HINGES AND

HIGHLY ACCESSIBLE

OPTIONALSOUNDPROOFING

ACCESSIBLE ELECTRICAL PANEL

Page 9: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

Application MT +LTCooling capacity 40 + 4 kW 35 + 9 kW

Number of compressors 2 + 1 2 + 1Inverter compressors 1 + 0 (opt.) 2 + 1

Optional equipment RHX connection RHX connectionRecovery (max capacity) 31 kW 31 kW

9

COMMERCIAL REFRIGERATION IN A TRANSCRITICAL CYCLE

Application MTCooling capacity 25 kW 36 kW 44 kW

Number of compressors 2 2 2Inverter compressors 1 1 1

Optional equipment RHX connection RHX connection RHX connectionRecovery (max capacity) 18 kW 25 kW 31 kW

Application MT +LTCooling capacity 21 + 4 kW 32 + 4 kW

Number of compressors 2 + 1 2 + 1Inverter compressors 1 + 0 (opt.) 1 + 0 (opt.)

Optional equipment RHX connection RHX connectionRecovery (max capacity) 18 kW 25 kW

1000

195

3

836

Page 10: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

10

MINICompact units equipped for the generation of cold with CO2 in the transcritical cycle.It serves refrigeration services in one or two temperatures, working as a booster.Optionally it can include up to 1 exchanger.

1560

150

8

840

PS 120 / 70 / 52 / 32 BAR

REDUCED FOOTPRINT

BODYWORKMULTIOPTION

NV42 AXIAL NV42 RADIAL

% BarCOMPACTDESIGN

ErP2015

TWO INDEPENDENT MODULES TO HOUSE

THE COMPRESSORS AND THE GAS COOLER

ELECTRICAL PANEL WITH CONTROL UNIT AND DISCONNECTOR WITH EXTERNAL CONTROL

DOUBLE BATTERY V

GREATER EXCHANGE SURFACE THAT ALLOWS A LOWER FLOW

A BATTERY CAN ACT AS AN EVAPORATOR IN CASE OF HEAT DEMAND AND IF IT DOES NOT NEED COLD GENERATION (OPTIONAL RHX PLUS NV58)

EC NV58 DUCTED FANS

Page 11: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

11

AXIAL EC

RADIAL EC

COMMERCIAL REFRIGERATION IN A TRANSCRITICAL CYCLE

Fans NV42 2x Ø450 mm NV58 2x Ø500 mmAir flow NV42 8.400 m3/h NV58 16.400 m3/hSound pressure at 10 m NV42 46 up to 49 dB(A) NV58 48 up to 49 dB(A)

Silent version

available

Fans NV42 2x Ø310 mm NV58 2x Ø500 mmAir flow NV42 7.900 m3/h NV58 15.000 m3/hAvailable pressure NV42 100 Pa NV58 100 PaSound pressure at 10 m NV42 48 up to 53 dB(A) NV58 48 up to 53 dB(A)

1600

175

2

956

840

916

NV58 AXIAL

NV58 RADIAL

Application MT MT + LT Cooling capacity 18 kW 12 + 4 kW 18 + 4 kW

Number of compressors 1 1 + 1 1 + 1Inverter compressors 1 1 + 0 1 + 0

Optional equipment RHX RHX RHXRecovery (max capacity) 13 kW 13 kW 13 kW

Application MT MT + LTCooling capacity 32 Kw 36 kW 28 + 4 kW 32 + 4 kW

Number of compressors 1 2 1 + 1 2 + 1Inverter compressors 1 1 1 + 0 1 + 0

Optional equipment RHX RHX RHX RHXRecovery (max capacity) 23 kW 25 kW 23 kW 25 kW

111

0 1

150

840

836

1600

194

6

Page 12: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

RADIAL MODEL

3 AIR OUTPUT CONFIGURATIONS

3 AIR OUTPUT CONFIGURATIONS

AXIAL MODEL

3 FANS EC CONDUCIBLES

NV66+ MODEL

WITH EXTENDED FEATURES

12

MINICompact centrally equipped for the generation of cold with CO2 in the transcritical cycle.It serves refrigeration services in one or two temperatures, working as a booster.Optionally it can include up to 1 exchanger and 1 parallel compressor.

PS 120 / 70 / 52 /32 BAR

EMERGENCY UNIT

% Bar

ErP2015

BODYWORKMULTIOPTION

MULTIPLE CHOICES FOR LOADING AND TRANSPORTATION

ELECTRICAL PANEL WITH CONTROL UNIT AND DISCONNECTOR WITH EXTERNAL CONTROL

DOUBLE BATTERY V WITH GREATER EXCHANGE SURFACE THAT ALLOWS A LOWER FLOW

A BATTERY CAN ACT AS AN EVAPORATOR IN CASE OF HEAT DEMAND AND IF IT DOES NOT NEED COLD GENERATION (OPTIONAL RHX PLUS NV58)

TWO INDEPENDENT MODULES TO HOUSE COMPRESSORS AND GAS COOLER

Page 13: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

13

AXIAL EC

RADIAL EC

COMMERCIAL REFRIGERATION IN A TRANSCRITICAL CYCLE

Fans 3x Ø500 mmAir flow 24.000 m3/hSound pressure at 10 m 46 up to 57 dB(A)

Fans 3x Ø500 mmAir flow 22.500 m3/hAvailable pressure 100 PaSound pressure at 10 m 50 up to 56 dB(A)

Application MT MT + cp MT + LTCooling capacity 44 kW 54 kW 63 kW 40 + 4 kW

Number of compressors 2 3 2 + 1 2 + 1Inverter compressors 1 1 1 + 1 1 + 0 (opt.)

Optional equipment IHX / RHX IHX / RHX IHX / RHX IHX / RHXRecovery (max capacity) 30 kW 38 kW 40 kW 30 kW

Application MT MT + LT MT + LT+ cpCooling capacity 68 kW 34 + 8 kW 60 + 8 kW 54 + 8 kW

Number of compressors 3 2 + 2 3 + 1 2 + 1 + 1Inverter compressors 1 1 + 0 1 + 0 1 + 0 + 1

Optional equipment IHX / RHX IHX / RHX IHX / RHX IHX / RHXRecovery (max capacity) 45 kW 30 kW 45 kW 40 kW

Silent version

available

2300

175

9

836

CUADRO ELECTRONICAPROFUNDO 100 mm

CUADRO ESTANDARPREPARDOPARA VARIADOR EN TRASERA

A A

B B

C C

D D

E E

F F

8

8

7

7

6

6

5

5

4

4

3

3

2

2

1

1

NV-66-COMPAK-AX-01

2300

1290 836

195

3

CUADROOPCIONALELECTRONICA

CUADROESTANDARCON OPCIONVARIADORESTRASERA

604

701

308

A A

B B

C C

D D

E E

F F

8

8

7

7

6

6

5

5

4

4

3

3

2

2

1

1

NV-66-COMPAK-RAD-01

2300

1290 836

195

3

CUADROOPCIONALELECTRONICA

CUADROESTANDARCON OPCIONVARIADORESTRASERA

604

701

308

A A

B B

C C

D D

E E

F F

8

8

7

7

6

6

5

5

4

4

3

3

2

2

1

1

NV-66-COMPAK-RAD-01

Page 14: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

14

RACKWITHOUT GAS COOLER

MANOMETERS IN SIGHT

TOUCH SCREEN, LUMINOUS INDICATORS AND CUSTOMIZED PLANT SYNOPTIC FOR VISUALIZATION AND DIAGNOSTICS

CONTAINER UP TO 150 l

REINFORCED SOUNDPROOF

OPTION

CHASSIS IN PLATE GALVANIZED STEEL AND PAINTED IN THE OVEN

COMPRESSORS:

UP TO 4CTC-30K IN BITZER COMPRESSORS

UP TO CD3501M IN DORIN COMPRESSORS

OPTIONAL FINISHES WITH HIGH OUTDOOR PROTECTION

CONTAINER UP TO 150 L

OPTIONAL REINFORCED

SOUNDPROOFING

EMERGENCY UNIT

Compact units equipped for the generation of cold with CO2 in the transcritical cycle.It serves refrigeration services in one or two temperatures, working as a booster.They include emergency unit. Optionally it can include up to 2 exchangers and 1 parallel compressor.

UP TO 2 PLATE EXCHANGERS AS OPTIONAL EQUIPMENT IN BENCH: IHX / RHX / EHX

TOUCH SCREEN WITH ELECTRONIC AND HIGH

EFFICIENCY CONTROL

Page 15: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

15

COMMERCIAL REFRIGERATION IN A TRANSCRITICAL CYCLE

L 1350

1405

Chassis LCC4E 2520 mmCC4G 3460 mm

WITHOUT GAS COOLER

Application MT MT + LTCooling capacity 102 kW 70 kW 94 + 8 kW

Compressors qty. 2 3 2 + 1Inverter compr. 1 1 1 + 1

Recovery (max) 72 kW 50 kW 72 kW

Application MT MT + LT MT + LT+ cpCooling capacity 102 kW 92 kW 89 + 12 kW 84 + 18 kW 70+12 kW

Compressors qty. 3 4 3 + 1 2 + 2 2 + 1 + 1Inverter compr. 1 1 1 + 1 1 + 1 1 + 1 + 1

Recovery (max) 72 kW 65 kW 72 kW 72 kW 72 kW

Page 16: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

16

RACKWITH GAS COOLER

MANOMETERS IN SIGHT

GAS COOLER INDEPENDENT

FROM COMPRESSOR MODULE

CONTAINER UP TO 150 l

CONTROL WITH LUMINOUS INDICATORS AND WITH SYNOPTIC SCHEME

AXIAL EC DUCTED FANS

RADIAL MODEL

3 AIR OUTPUT CONFIGURATIONS

SUITABLE FOR OUTDOOR LOCATION

ADVANCEDUPS

EMERGENCY UNIT

TOUCH SCREEN WITH ELECTRONIC AND HIGH

EFFICIENCY CONTROL

SAI plus

ErP2015

Compact units equipped for the generation of cold with CO2 in the transcritical cycle.It serves refrigeration services in one or two temperatures, working as a booster.They include emergency unit. Optionally it can include up to 2 exchangers and 1 parallel compressor.

PS 120 / 70 / 52 /32 BAR

% Bar

Page 17: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

17

COMMERCIAL REFRIGERATION IN A TRANSCRITICAL CYCLE

EDICIÓN REALIZADO

TEWISSMARTSOLUTIONSS.L.U.sereservaatérminolegal lapropiedaddel presentedibujo,quedandoprohibidasucopiaoreproducciónsinautorización.

DESCRIPCIÓNDenominación

V1º

Resp.Producción

JAE

FECHA

Revisiones

A

B

C

D

E

F

1 2 3 4 5 6 7 8

CódigoNEXO

Fecha

ToleranciaV0,1mm

Escala

Referencia

Nºdeplano

Material Pintado

PesoUbicaciónplanoDirectorTécnico

Resp.Diseño

TipodedocumentoCJ_ZCC+ZCND-2613

21.04.2015

CONJUNTOCHASIS+CONDENSADOR2613JCC

1350

2483

L

FULL RACK CON GAS COOLER RADIAL

EDICIÓN REALIZADO

TEWISSMARTSOLUTIONSS.L.U.sereservaatérminolegal lapropiedaddel presentedibujo,quedandoprohibidasucopiaoreproducciónsinautorización.

DESCRIPCIÓNDenominación

V1º

Resp.Producción

JAE

FECHA

Revisiones

A

B

C

D

E

F

1 2 3 4 5 6 7 8

CódigoNEXO

Fecha

ToleranciaV0,1mm

Escala

Referencia

Nºdeplano

Material Pintado

PesoUbicaciónplanoDirectorTécnico

Resp.Diseño

TipodedocumentoCJ_ZCC+ZCND-2613

21.04.2015

CONJUNTOCHASIS+CONDENSADOR2613JCC

1350

2483

L

FULL RACK CON GAS COOLER RADIAL

u+ju

L jxFT

j

jguT

óRevisado por

DESCRIPCIÓNRE.LIZ.DO

Normativa aplicada

UNEóEN jTuj]UNEóEN ISO_[T[ój

UNEóEN ISO jxFhFuTjuVjº VTbjmm -

uuºTxºuTjh

J . E

MCR

Ubicación plano

Nº plano

Tolerancia Peso

j º

Conjunto CZg Condensador .xial M CC+FóE[u[[TxjxFTb Modelo Eg CE Exterior]

-

-

-

-

-

-

-

-

-

-

-

-

Fecha

EDICIÓN

.cabado

.x

CZ.ó+F_E

Escala

Denominación Código NEXO

Material

FECH.

Director Técnico

TEWIS se reserva a término legal la propiedad del presente dibujob quedando prohibida su reproducción sin autorizaciónn

Realizado por

A A

B B

C C

D D

E E

F F

8

8

7

7

6

6

5

5

4

4

3

3

2

2

1

1

FULL RACK CON GAS COOLER AXIAL

u+ju

L jxFT

j

jguT

óRevisado por

DESCRIPCIÓNRE.LIZ.DO

Normativa aplicada

UNEóEN jTuj]UNEóEN ISO_[T[ój

UNEóEN ISO jxFhFuTjuVjº VTbjmm -

uuºTxºuTjh

J . E

MCR

Ubicación plano

Nº plano

Tolerancia Peso

j º

Conjunto CZg Condensador .xial M CC+FóE[u[[TxjxFTb Modelo Eg CE Exterior]

-

-

-

-

-

-

-

-

-

-

-

-

Fecha

EDICIÓN

.cabado

.x

CZ.ó+F_E

Escala

Denominación Código NEXO

Material

FECH.

Director Técnico

TEWIS se reserva a término legal la propiedad del presente dibujob quedando prohibida su reproducción sin autorizaciónn

Realizado por

A A

B B

C C

D D

E E

F F

8

8

7

7

6

6

5

5

4

4

3

3

2

2

1

1

FULL RACK CON GAS COOLER AXIAL

AXIAL EC

RADIAL EC

Chassis LCZ4E 2520 mmCZ4G 3460 mm

Fans CZ4EP 2x Ø630 mm CZ4GP 3x Ø630 mmAir flow CZ4EP 32.000 m3/h CZ4GP 51.300 m3/hSound pressure at 10 m CZ4EP 63 dB(A) CZ4GP 64 dB(A)

Fans CZ4EN 2x Ø630 mm CZ4GN 3x Ø630 mmAir flow CZ4EN 34.200 m3/h CZ4GN 47.100 m3/hAvailable pressure CZ4EN 100 Pa CZ4GN 100 PaSound pressure at 10 m CZ4EN 50 a 51 dB(A) CZ4GN 49 a 51 dB(A)

Application MT MT+ LTCooling capacity 67 kW 70 kW 41 + 8 kW 59 + 8 kW

Compressors qty. 2 3 1 + 1 2 + 1Inverter compr. 1 1 1 + 1 1 + 1

Recovery (max) 45 kW 45 kW 35 kW 45 kW

Application MT MT + LT MT + LT + cpCooling capacity 102 kW 92 kW 89 + 12 kW 89 + 12 kW 84 + 18 kW 70 + 12 kW

Compressors qty. 3 4 2+1 3+1 2+2 2+1+1Inverter compr. 1 1 1+1 1+1 1+1 1+1+1

Recovery (max) 70 kW 65 kW 70 kW 70 kW 70 kW 55 kW

Page 18: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

HEAT RECOVERY UP TO 190 KW

RHX

18

DUPLEXThe FULL Duplex exchanges offer the highest power for the commercial cold range with CO2 in 2 MT and LT temperatures.

They are double-deck transcritical cycle booster machines, which reduces the space required for assembly while ensuring modulation and operational reliability thanks to the number of compressors they house.

Optionally it can include up to 3 exchangers and 1 parallel compressor.

Software developed to measure data and send alarms both in plant and by telemanagement.

Compatible with Televis System and open protocol for the integration of Modbus RTU / TCP or BACnet MS / TP systems (optional).

Intuitive interface with graphs and historical data tables.

Management of parameters and performance with selectors and light indicators.

ELECTRONICS AND HIGH EFFICIENCY CONTROL

CONTAINER UP TO 400 l

PS 120 / 70 / 52 /32 BAR

% Bar

EMERGENCY UNIT

ADVANCEDUPS

SAI plus

>> CUADRO ELÉCTRICO MONTADO EN BANCADA, INCLUYENDO CABLEADO COMPLETO.

>> ALIMENTACIÓN ELÉCTRICA A 400V/3F+N/50HZ.>> VARIADOR DE FRECUENCIA EN EL PRIMER COMPRESOR EN LAS SECCIONES

LT, MT Y PARALELO.>> COMPONENTES DEL BOOSTER Y GAS COOLERS REMOTOS PROTEGIDOS

ELÉCTRICAMENTE CONTRA SOBRECARGAS Y CORTOCIRCUITOS.>> CONEXIONES ELÉCTRICAS DE ALIMENTACIÓN A LA UNIDAD AUXILIAR. (OPC.)

MANOMETERSIN SIGHT

IHXPARALLELCOMPRESSOR

STAINLESS STEEL AISI 304L

SWITCHBOARD,TOUCH SCREEN AND MANAGEMENT SYNOPTIC

VARIABLE FREQUENCY DRIVE

Page 19: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

19

COMMERCIAL REFRIGERATION IN A TRANSCRITICAL CYCLE1600

2109

1000

L

853 876 876 895

1350

1250

1

1:16

JAERevisado por

DESCRIPCIÓNREALIZADO

Normativa aplicada

UNE-EN 10217UNE-EN ISO9606-1

UNE-EN ISO 135852012V1º V0,1mm 05_02_01_01_02_ZCC-HIGH

21/03/2018

J A E

MCR

Ubicación plano

Nº plano

Tolerancia Peso

1 /

CHASIS DOBLE PISO 3600X1350 - Cuadro Eléctrico 1000

-

-

-

-

-

-

-

-

-

-

-

-

Fecha

Revision

es

EDICIÓN

Blanco al hornoAcabado

A3

S235JRG2

758.24 Kg

ZCC-3613-HIGH-Q1000 (Q4H1)

Escala

Denominación Código NEXO

Material

FECHA

Director Técnico

TEWIS se reserva a término legal la propiedad del presente dibujo, quedando prohibida su reproducción sin autorización.

Realizado por

A A

B B

C C

D D

E E

F F

8

8

7

7

6

6

5

5

4

4

3

3

2

2

1

1

Chassis LCD4G 3060 mmCD4H 3600 mmCD4J 4000 mm

Application MT + LT MT + LT + cpCooling capacity 194 + 22 kW 191 + 25 kW 183 + 32 kW 230 + 22 kW 228 + 25 kW 240 + 32 kW

Compressors qty. 3 + 2 3 + 3 3 + 4 2 + 2 + 1 2 + 3 + 1 2 + 4 + 1Inverter compr. 1 + 1 1 + 1 1 + 1 1 + 1 + 1 1 + 1 + 1 1 + 1 + 1Recovery (max) 150 kW 150 kW 150 kW 170 kW 170 kW 190 kW

Application MT + LT MT + LT + cpCooling capacity 230 + 22 kW 184 + 25kW 176 + 32 kW 200 + 22 kW 193 + 25 kW 185 + 32 kW

Compressors qty. 4 + 2 4 + 3 4 + 4 3 + 2 + 1 3 + 3 + 1 3 + 4 + 1Inverter compr. 1 + 1 1 + 1 1 + 1 1 + 1 + 1 1 + 1 + 1 1 + 1 + 1Recovery (max) 170 kW 150 kW 150 kW 150 kW 150 kW 150 kW

Application MT + LT + cpCooling capacity 220 + 22 kW 217 + 25 kW 209 + 32 kW

Compressors qty. 4 + 2 + 1 4 + 3 + 1 4 + 4 + 1Inverter compr. 1 + 1 + 1 1 + 1 + 1 1 + 1 + 1Recovery (max) 170 kW 170 kW 170 kW

Without gas cooler

Page 20: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

20

PERIPHERALS

GAS COOLER GZ Tewis, Alfa Laval and Nova

Tewis GZ models have a battery developed to withstand the high demands of transcritical CO2, the range includes: copper battery, aluminum fins, body in steel sheet with galvanized painted in the oven; of horizontal installation and Ø 560 and 630 mm fans. PS 120 bar.

Available in axial and radial versions, both with EC technology as standard.

Capacities between 75 and 161 kW*

Air temp. 35°C; Disch. Pr. CO2 92 bar; Gas Temp. in/out 115/37°C

Alfa LavalAlfa Laval equipment offers different configurations that can be adapted to each installation; horizontal or vertical airflow, one or two rows of fans, even V-battery design for very high capacities. PS 120 bar.

Capacities from 15 to 1000 kW*

Air temp. 35°C; Disch. Pr. CO2 90 bar;

Gas Temp. in/out 120/38°C

NovaConstructed with copper battery, aluminum fins and body in galvanized steel sheet, they have been designed for horizontal installation in transcritical CO2 systems. The range stands out for its high dissipation capacity and its small size thanks to the dual V-battery system. EC technology is standard on both axial and radial versions, with Ø 310, 450 and 500 mm fans. PS 120 bar.

Capacities from 30 to 88 kW*

Air temp. 35°C; Disch. Pr. CO2 92 bar; Gas Temp. in/out 115/37°C

They are condensing units that, working with HFC refrigerants, generate the additional cold required by the optional plate exchanger systems, EHX / MHX, in search of the most efficient point.

They are equipment bodied and with axial fans to locate outdoors.

Capacities from 8 to 51 kW

Evap. T. 20°C; Out. Temp. 40°C; R134a

AUXILIARY REFRIGERATION UNITS

Do you have your own gas cooler?

The electrical panel included in the central can protect it.

Do you have any condensing unit in the installation?

You can combine it in retrofit mode, like air conditioning equipment, chiller...

Page 21: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

21

SAFETY MODES

DESUPERHEATERS

SAFETY VALVES (DETAIL)

HEAT RECOVERY / GENERATION

They protect the compressors of medium temperature against the high temperatures generated by the low compressors.

They are aerocoolers with a battery designed to withstand a PS 60 bar avoiding the maximum loss of fluid load. They can be arranged in a horizontal or vertical air flow.

Capacities from 4,5 to 50 kW

Air temp. 35°C; P. T. in/out gas 72/40°C

Systems against power cuts. The entire FULL range incorporates an uninterruptible power supply (UPS) that will allow the electronic control unit and its devices to prepare to shut down the system safely.

If the lack of supply persists in time and the pressure of the liquid container rises too high, the emergency equipment will come into service which, with independent connection and connected to a generator set (not included), will allow to maintain stable the pressure of the unit.

Double function of the parallel compressors. In case of including the optional of parallel compression, in case of failure of some compressor of average temperature, these can attend the services of MT avoiding the stop of the system.

Electronic valves back pressure and gas flash. Each of these valves can include, for safety, another pressostatic valve in parallel ensuring its operation even in cases of emergency (Option).

Valve with electric actuator. This valve allows that in the event of a failure in the electronic control unit or any of its components, the refrigeration unit continues to operate electro-mechanically without interrupting the service. (Optional equipment of the units).

All CO2 refrigeration systems generate high discharge temperatures, which is an excellent source of heat from which you can take advantage. Working in a transcritical cycle, in fact, the discharge temperatures easily exceed 100ºC, and in the subcritical cycle, 60ºC. That is why from Tewis we propose to use this inherent energy to the facilities and take advantage of it in the form of heat for services such as ACS, air conditioning or other annexed industrial processes. The optional RHX uses a heat exchanger plate thermoweld located in the discharge of the refrigerating unit and that, through electronic control, can transfer the heat of discharge to a secondary fluid. The RHX system uses a proportional three-way valve that maintains the outlet temperature of the exchanger constant. Depending on the associated parameterization from the electronic control, the exchanger can work in these modes:

Heat recovery: the RHX recovers the heat produced by the plant, without altering its operation in any way.

Heat generation: if the heat recovery is insufficient, the RHX will interact with the regulation of the discharge pressure to increase the heat production.

Heat generation plus: without demand of cold there is no generation of heat, therefore, in this last option, the generation of cold in a support evaporator is forced to generate heat.

Page 22: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

22

NH3 + CO2

Chiller NH3

Pumped CO2

Hybrid units

INDUSTRIAL RANGE

In Tewis we also work with the range of industrial products, which include the most powerful cold machines, designed for machine rooms of large establishments, as well as for logistics, storage or any other industrial process that may require generation of cold above 250 kW of power.

We develop customized projects that use refrigerants such as CO2 or NH3 in different configurations.

The most innovative solutions of Tewis are included in the GM Full family with which, in addition to the cooling in MT / MT + LT, the air conditioning services are taken care of. All this using only CO2 as refrigerant for the installation.

The GM FULL Duplex are great machines for high powers, while the GMpack FULL represent the most compact version for this technology.

The combination Cold + Air Conditioning is especially optimal for supermarkets and franchises since they have great demand for both services and this ensures greater efficiency when interconnecting both cycles.

Booster MT + LTOne temperature

Frozen tunnels

COLD + AC RANGE

Page 23: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

23

CONTROL AND SWITCHBOARD FOR EFFICIENCY

>> Available with Danfoss control electronics.

>> Compatible with Danfoss management systems.

>> In this solution, the touch screen is not available.

Compatible with the GM SMART system, which expaAnds your configuration options and solutions.

Touch screen with synoptic and data in real time. (Mod. RACK and DUPLEX).

Selectors and light indicators.

Management of parameters and performance.

Data and alarm software with intuitive interface both on site and via remote management.

Monitoring with graphs and tables of historical data.

It represents the best option for CO2 solutions with Booster circuit and allows managing up to two circuits for heat recovery.

Compatible with Televis System and open for the integration of Modbus RTU / TCP or BACnet MS / TP systems (optional).

SWITCHBOARD

FULLY

COMPATIBLE

ELECTRONIC CONTROL

ELECTRONIC CONTROL

>> ELECTRIC PANEL MOUNTED ON BENCH, INCLUDING COMPLETE WIRING.

>> POWER SUPPLY AT 400V / 3F + N / 50HZ.

>> FREQUENCY INVERTER IN THE FIRST COMPRESSOR IN SECTIONS LT, MT AND PARALLEL.

>> BOOSTER COMPONENTS AND REMOTE GAS COOLERS PROTECTED ELECTRICALLY AGAINST OVERLOADS AND SHORT CIRCUITS.

>> ELECTRICAL CONNECTIONS OF POWER TO THE AUXILIARY UNIT. (OPT.)

Page 24: COMMERCIAL REFRIGERATION CO2 TRANSCRITICAL … · 2 transcritical refrigeration family of transcritical cycle machines for positive cooling (media), negative (low) or a combination

Certificates2014/68/UE2014/30/UE2006/42/UE2014/35/UE2016/364/UE2012/27/UEwww.tewis.com

[email protected]

MKT

2-30

7ENV