ComEd LBNL ‘Beyond Widgets’ Project Automated Shading Integrated with Lighting and HVAC Controls System Program Manual 26 September 2017 Lawrence Berkeley National Laboratory Berkeley CA 94720

Transcript of ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several...

Page 1: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

ComEd–LBNL‘BeyondWidgets’Project

AutomatedShadingIntegratedwithLightingandHVACControls

SystemProgramManual

26September2017

LawrenceBerkeleyNationalLaboratoryBerkeleyCA94720

Page 2: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

2

DisclaimerThisdocumentwaspreparedasanaccountofworksponsoredbytheUnitedStatesGovernment.Whilethisdocumentisbelievedtocontaincorrectinformation,neithertheUnitedStatesGovernmentnoranyagencythereof,norTheRegentsoftheUniversityofCalifornia,noranyoftheiremployees,makesanywarranty,expressorimplied,orassumesanylegalresponsibilityfortheaccuracy,completeness,orusefulnessofanyinformation,apparatus,product,orprocessdisclosed,orrepresentsthatitsusewouldnotinfringeprivatelyownedrights.Referencehereintoanyspecificcommercialproduct,process,orservicebyitstradename,trademark,manufacturer,orotherwise,doesnotnecessarilyconstituteorimplyitsendorsement,recommendation,orfavoringbytheUnitedStatesGovernmentoranyagencythereof,orTheRegentsoftheUniversityofCalifornia.TheviewsandopinionsofauthorsexpressedhereindonotnecessarilystateorreflectthoseoftheUnitedStatesGovernmentoranyagencythereoforTheRegentsoftheUniversityofCalifornia

Page 3: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

3

AcknowledgementsThisworkwassupportedbytheAssistantSecretaryforEnergyEfficiencyandRenewableEnergy,BuildingTechnologiesOffice,oftheU.S.DepartmentofEnergyunderContractNo.DE-AC02-05CH11231.LBNLisespeciallygratefulfortheguidanceandsupportofthefollowingComEdpersonnelaswellasprojectmanagersintheBuildingTechnologiesOfficeattheU.S.DepartmentofEnergy.

ComEdRogerBakerMichaelBrandtNoelCorralMarkRHamannArturoHernandezTravisNelsonGeorgeMalekToddThornburgWilliamBurnsU.S.DOEAmyJironStephanieJohnsonKristenTaddonio

Reportauthors:PaulMathew,CindyRegnier,TravisWalter,JordanShackelford

Page 4: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

4

TableofContents

EXECUTIVESUMMARY......................................................................................................6

1 INTRODUCTION...........................................................................................................7

2 SYSTEMSELECTIONANDMARKETANALYSIS...............................................................72.1 SystemFeatures:AutomatedShadingwithDaylight-basedDimming 72.2 MarketAnalysis 8

2.2.1 Literaturereviewhighlights 82.2.2 ComEdmarketanalysis 9

3 SYSTEMFUNCTIONALPERFORMANCEREQUIREMENTS...............................................93.1 AutomatedShading 103.2 AutomatedLightingControls 113.3 HVACControls 12

4 FLEXLABTESTINGANDANALYSIS..............................................................................134.1 Approach 134.2 TestandMeasurementPlan 174.3 LightingSavings–TestPeriod 194.4 LightingSavings-Annualized 314.5 WholeBuildingSavingsEstimates 354.6 VisualComfortAnalysis 36

4.6.1 Illuminance 364.6.2 Glare 41

5 SAVINGSESTIMATIONFORCUSTOMERSITES............................................................465.1 CandidateSiteRequirements 465.2 CandidateSiteSavingsEstimates 46

6 M&VCONSIDERATIONS.............................................................................................476.1 OperationVerification 476.2 M&VOptions 486.3 SavingsUncertainty–FLEXLABDataAnalysis 49

6.3.1 Reliabilityoflightingpowerreportedbycontrolsystem. 496.3.2 Measurementperiod 50

7 SAVINGSPERSISTENCE..............................................................................................52

8 REFERENCES..............................................................................................................54

Page 5: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

5

APPENDIXA:MARKETSEGMENTATIONANALYSIS

APPENDIXB:CANDIDATESITESAVINGSESTIMATOR

APPENDIXC:INSTALLATIONVERIFICATIONCHECKLIST

Page 6: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

6

ExecutiveSummary

This program manual contains detailed technical information for developing an incentiveprogramforautomatedshadingintegratedwithlightingandHVACcontrols.Themanualwasdeveloped by Lawrence Berkeley National Laboratory, in collaboration with ComEd as apartner in the ‘BeyondWidgets’ project funded by the U.S. Department of Energy BuildingTechnologiesOffice.

ComEdconsidereda listofseveralsystemsandselectedautomatedshading integratedwithlighting and HVAC controls. Daylight-based dimming is a proven but underutilized energy-efficiencytechnology,particularlywithinthecontextofutilityprogramswhichmostlycatertoprescriptivecomponent-basedefficiencymeasures.

LBNL’sFLEXLABtestfacilitywasusedtomeasuretheenergyperformanceandvisualcomfortofthesystem.FLEXLABallowsenergy-efficientbuildingsystemstobetestedindividuallyorasan integrated system, under real-world conditions. The test case (i.e. automated shadingintegrated with lighting and HVAC controls) and the baseline case (i.e. manually operatedvenetianblindsandnodaylight-baseddimming)weretestedatthesametimeunderidenticalconditions using the two cells of the FLEXLAB rotating testbed. In order to obtain anassessment of HVAC loads in Chicago climate, the internal temperature setpoints wereadjusted in real time to match the indoor-outdoor temperature difference in Chicago.FLEXLABtestingwasconductedovera6-monthperiodandcoveredvariousconfigurationsoforientation,daylightzonesize,window-to-wall-ratio(WWR),andlightingtype.

Testperiodsavingswereextrapolated toannual savingsusing regressionmodelsof the testperioddata.

• Southorientationshowsameanof19%annual lightingenergysavings,witharangeof12-26%(at95%confidence).

• Westorientationshowsameanof24%annuallightingsavings,witharangeof19-30%(at95%confidence).

It is important to reiterate that these savings are exclusively attributable to automatedshadinganddimming andwillbeadditional to savings from lightingupgrades. Inparticular,thesesavingsdonotincludethesavingsfromtuning.

WeestimatedwholebuildingsavingsforfourbuildingtypesusingtheDOEreferencebuildingEnergyPlus simulation models in combination with the FLEXLAB lighting savings results,adjusted to account for savings from institutional tuning. The tablebelow shows thewholebuildingsavingsestimatesforthereferencebuildings.

TableES-1.WholebuildingsavingsfromdimmingandtuningReference building Whole Building

Lighting Svg % Whole Building Total Elec Svg %

Whole Building Site Energy Svg %

Large Office 16% 5.0% 2.6% Medium Office 22% 4.5% 3.5% Primary School 20% 9.0% 4.8% Secondary School 14% 6.2% 2.7%

The visual comfort analysis showed that the systemmaintainedworkplane illuminance anddaylightglareprobabilityatsatisfactorylevelsthroughoutthetestperiod.

Page 7: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

7

1 Introduction

This program manual contains detailed technical information for developing an incentiveprogramforautomatedshadingintegratedwithlightingandHVACcontrols.Thismanualwasdeveloped by Lawrence Berkeley National Laboratory, in collaboration with ComEd as apartner in the ‘BeyondWidgets’ project funded by the U.S. Department of Energy BuildingTechnologiesOffice. The primary audience for thismanual is the ComEd incentive programstaff. It may also be used by other utilities to develop a similar incentive program. It isanticipated that the content of this manual will also be utilized by the ComEd staff fordevelopingrelateddocumentssuchastheTechnicalResourceManualandotherfilings.

This manual covers a range of information needed by various stakeholders involved indevelopingautilityincentiveprogram.Itisnotnecessarilyintendedtobereadcovertocoverby any one stakeholder. Beyond section 2,which describes the key features of the system,readersmaywishtoreadonlythosesectionsrelevanttotheirinterest.

Section2presentsanoverviewofthesystemandinitialmarketanalysis.

Section3describesthefunctionalperformancerequirementsofthesystem.

Section4presentstheFLEXLABtestingapproachandresults,includingmeasuredsavingsfromFLEXLAB and estimates of whole building savings based on FLEXLAB results. Visual comfortanalysisresultsarealsopresentedinthissection.

Section5describesthemethodologyforestimatingpotentialsavingsatcandidatesites.

Section6addressesmeasurementandverification(M&V)optionsandconsiderations.

Section7provides guidelinesonoperationsandmaintenancepractices tomaximize savingspersistence,basedonindustryexperienceaswellasfindingsfromFLEXLABoperation.

Section8providespreliminaryrecommendationsontrainingforprogramimplementers.

2 SystemSelectionandMarketAnalysis

2.1 SystemFeatures:AutomatedShadingwithDaylight-basedDimming

ComEdconsidereda listofseveralsystemsandselectedautomatedshading integratedwithlightingandHVACcontrols.Thekeyfeaturesofthissystemare:

Automated Shading: The automated interior shading element will be roller shades. Thefunctionalrequirementisfortheshadestocontrolsolargainthroughperimeterwindowssothat envelope-related thermal loads areminimizedwhilemeetingdaylighting requirements.Asanadditionaloption,duringunoccupiedperiodstheshadesmaybedeployedaccordingtothe prevailing HVAC mode of operation (deployed in cooling mode, retracted in heatingmode).

Lighting Controls: The lighting control is in response to occupancy and illuminance levels.Occupancy-driven control will switch lights on/off or dim to minimum background levels.Illuminance-drivencontrolwilldimlightscontinuouslybasedondaylightavailability.

HVAC Controls: The primary HVAC control is in response to thermostatic setpoints, withscheduledsetupandsetbackforunoccupiedperiods.Additionally,occupancysensorsusedfor

Page 8: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

8

the shading/lighting system may be used for setup/setback in response to vacancy duringoccupiedperiods,aswellasreducingventilationair.

2.2 MarketAnalysis

2.2.1 Literaturereviewhighlights

Daylight-based dimming is a proven but underutilized energy-efficiency technology,particularly within the context of utility programs which mostly cater to prescriptivecomponent-based efficiency measures. An LBNL meta analysis study (Williams et al. 2011)showed that daylighting alone yielded an average lighting energy savings of 27% (N=18projects)forofficesand29%(N=7projects)foreducation(Table2).

Table1. EnergysavingsfromLBNLmeta-analysisoflightingcontrolsstudies(Williamsetal.2011)

IntegratingautomatedshadingwithdaylightdimmingandHVACcontrolshasthepotentialtoyieldhighersavings,abettervisualenvironment,andhighersavingsrealization.Forexample,post-occupancy LBNL study of the New York Times headquarters building (Lee et al. 2013)showed 38% lighting energy savings compared to code,with a simple payback of 4.1 years(Figure 1). The automated shades caused daylight to be well managed irrespective ofdifferences in daylight availability – for lower floors with greater urban obstructions, theshades were automatically raised more often and for upper floors with less urbanobstructions,theshadeswereloweredmoreoftentocontrolsunandglare.Theseandothernon-energybenefits(e.g.lowercostforreconfiguringlightingsystemcomparedtohardwiredsystems)serveasanaddedincentivetoincreaseadoption.

Page 9: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

9

Figure1. LightingenergyusesavingsintheNewYorkTimesheadquartersbuilding

(Leeetal.2013)

2.2.2 ComEdmarketanalysis

ComEd identified two targetmarket segments for this systempackage: offices and schools.Foroffices,thefocuswillbeonmediumandlargesizebuildings.Thepackagewilltargetbothretrofitandnewconstruction.

LBNLcommissionedamarketanalysistoestimatethesavingsacrossvariousmarketsegmentsin theComEd service territory. Themarketanalysisestimated technicalpotential, economicpotential and adoption potential as separate outputs. The key inputs applicable floor area,baselineenergyuse,andpotentialbuilding-levelsavingsasapercentageofthebaseline.Themarket impact analysis was conducted prior to FLEXLAB testing. The building-level savingsestimateswerebasedonliteraturereviewandsimulationanalysis.

The market segments considered for this analysis included offices and schools. The totaltechnicalpotential for thesesegments is519-633GWhof savings. TheTotalResourceCost(TRC) criterionwas0.25-0.28 for a retrofit scenarioand0.44-0.53 for aReplaceonBurnout(ROB)scenario.UsingTRCcriteria,thissystemiscost-effectiveonlyforspecificsub-segmentsandonlywhenevaluatedusingincrementalsystemcosts(ROBscenario).Thisisprimarilydueto the low avoided cost rates in Illinois, which are about $0.04/kWh. However, from acustomer perspective these systems are cost effective with the average rates of about$0.10/kWh.

AppendixAincludestheexecutivesummaryofthemarketanalysisreport.

3 SystemFunctionalPerformanceRequirements

The intent is toallowarangeofdifferentcomponenttechnologyoptions for this integratedsystem. The program incentives would be paid based on system performance rather thancomponent performance or features. The functional performance requirements for eachcomponentaresummarizedbelow.

Page 10: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

10

3.1 AutomatedShading

An automated interior shading and shade control system should comprise the followingelements:

• Shadingelement–rollershades(variousfabricoptions).• Motorforshades/blindsoperation,andhousingforblindswhenretracted.• Keypadstoenableusercontrolandoverrideofautomaticoperation.• Routers,controllers,processorsandservers.• Control system that utilizes an automated, computer server-based control system

withtheabilitytoreceiveinputsfrommultipleoccupancysensorsandphotosensors.• Sensorsforcontrolinputs.• Programmingsoftware.

The primary control objective is to control glare while maximizing daylight availability.Setpointsforglarecontrolandmaximizingdaylightshouldbesetbasedonusecharacteristicsanduserpreferences.Additionally,occupantsshouldalwayshavemanualoverridecapability.Primary control shall be in response to solar conditions, based on real-time solar radiationsensorinput.Inaddition,acombinationofoneormoreofthefollowinginputsmaybeused:

• Sunposition• Directsolarradiation• Diffusesolarradiation• Façadeazimuth• Interiorand/orexteriorsurfaceluminance• Interiorand/orexteriorilluminance

Additional secondary control may include a combination of vacancy and HVAC mode, asfollows:

• WhenthezoneisvacantandHVACisincoolingmode,shadesarefullydeployed.• WhenthezoneisvacantandHVACisinheatingmode,shadesarefullyretracted.

Additionalspecificrequirements:• Rollershadesshouldhaveanopennessfactorbetween1-3%.Theexteriorreflectance

should be greater than 60%. Interior reflectance should be lower than exteriorreflectance.

• The control system should allow for at least 3 shade height settings, including fullyraisedandfullylowered.

• Thetypes,locationsandnumberofsensorsshallbedeterminedbytheShadeControlsSystemSupplier.

• The shades shall block direct sun so that the depth of direct sun penetration is nogreater thana specifiedhorizontal depth from the faceof thewindowwall at floorlevel.Thespecifiedmaximumpenetrationdistancemayvary fordifferentperimeterareas based on user requirements. The deployment of shades should considerblockingofthesunbyexternalobstructionssuchassurroundingbuildings.

• Response to variable luminance should be limited so as to avoid shademovementhysteresis.Responsetovariableskyconditionsshouldbeimmediatewhengoingfromcloudytosunny,anddelayedwhengoingfromsunnytocloudy.

• Theshadesshallcontrolglaresothattheaveragewindowluminanceviewedfromanyangle within the work space is no greater than a specified level (e.g. 2000 cd/m2)

Page 11: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

11

duringtheday.Thisincludesallperiodsthroughoutthedaywhetherthereisorisnotdirectsunintheplaneofthewindow.

• ThecontrolsystemshouldhavethecapabilitytointerfacewithHVACcontrolsystemorBMS.

• Theshadecontroldatabaseshouldmaintainarchivedlogfilesofkeyparameterssuchaspositionofshades,glarephotosensordata,profileangles,radiometerreadingsandsystemcontrolmode.

All control inputs shall be configured to reflect each site’s specific characteristics andrequirements.

3.2 AutomatedLightingControls

Thelightingcontrolsystem,ofwhichdaylightdimmingisapart,maycomprisesomeorallofthefollowingequipment:

• Digitally addressable ballasts or LED drivers; ballast and lamp combinationscompatiblewithdimmingcontrols.

• Panelandremotemountedloadcontrolrelaysanddimmers.• Powersupplies.• Routers,controllers,processorsandservers.• Analoganddigitalinputandoutputmodules.• Group/sceneandmanualzonecontrols.• Occupancy/vacancysensors.• Photosensors.• Integraltimeclockcontrol.• Emergencylightingcontrol.• Utility“demandresponse”control.

The functional performance requirement is that daylight photo sensors shall monitor lightlevelsandenabledimmingofelectriclightingupordowninresponsetochangesinavailablenatural light as required by user type. Additionally, lights shall be turned off or dimmed tominimumlevelsinunoccupiedzones.

Additionalspecificrequirements:• Daylightingsensorsandcontrolsshallbeprogrammedtoensureminimallampcycling

(andassociatedreducedlamplifeandoccupantdistraction)andshouldbecapableofeasyrecalibrationtoaccommodatechangesinenvironment/preferences.TheyshouldbecalibratedtoensurethatIESguidelinesaremaintained.Thecontrolsystemshouldbecapableofcontrollingmultiplezonesusingtheinputfromasinglesensor,allowingseparate adjustable settings for each control zone. The system should allow forvariable target setpoints. The location and number of the photo sensors should beoptimizedbythecontrolsystemsupplier.

• Occupantsensorsmaycontrollightingatthezoneorindividualworkerlevel.Lightingoutput should be adjusted to the requirements of the user (tuning of lamp outputrelative to maximum rated output). Occupancy sensors should be dual-technology.Sensors should allow remote control adjustments of operational parameters(sensitivity,timedelay).

• Group/scene controllers shall be compatible with other components of the lightingcontrol system. Devices shall contain on/off group, preset scene functions, or dim

Page 12: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

12

up/dim down interface through front panel. Programming of new scenes or zoneassignments must be easily accomplished by authorized personnel from the spacebeingcontrolled.

• Daylightingsensorsshouldnotbeinthesamehousingorlocationwithoccupancyandvacancy sensors if proper location for one compromises the successful operationoftheother.

• Thelightingcontrolsystemshouldprovideremotemonitoringandreporting.Itshouldprovide report and trends on the following: energy usage, target setpoint map,switchingevents,lamphours,commandsusage,systemfailures.

• Database management system that logs all commands from the LCS. The log fileshould provide deterministic values including, but not limited to: photosensor data,occupancysensorstateandsystemcontrolmode(auto,manualandmaintenance).

• Lightingsystemenergyuseshouldpreferablybemeasuredatthepanellevelforeachzone.

• Self-diagnosticandself-correctivefeatures.

Allcontrolinputsshallbeconfiguredtoreflecteachsite’sspecificcharacteristics.

3.3 HVACControls

Foroptional integratedHVACcontrol,HVACzonesshallbeconsistentwiththosedefinedforthelightingsystem.Allcontrolinputsshallbeimplementedaccordingtosystemconfiguration,andeachsite’sspecificcharacteristicsandrequirements.

IntegratedHVACcontrols/equipmentshallincludeoneormoreofthefollowing:• BACnetcontrolcommunications• Variablefrequencydrivesonfanandpumpmotors• Modulatingvalvesonheating/coolingloops• Outdoorairtemperaturereset• Networkedmechanicalequipmentcontrollers

Optionalcontrolinput:• Occupancysensorsatthesub-zone(i.e.individualprivateoffice/cubicle)level

The functional performance requirement is to maintain stable thermal conditions withinbuilding HVAC zones,whichmay be defined according to location (perimeter/core) or type(openoffice/privateoffice).

Primarycontrolshallbetosetpointtemperatureduringoccupiedhoursandtosetup/setbacktemperatures during unoccupied hours. Secondary control may account for variation inthermal comfort preferences relative to the prevailing outdoor weather conditions(setup/setback)andoccupancy(whereappropriate/desired).

Controlpoints/variablesshallbeoneoracombinationofthefollowing:• Thermalsetpoint• Airflowrate• Supplyairtemperature• Economizerutilization/mixedairtemperature• Predicted/actualthermalload• Occupancysensorsignals• CO2sensorsignals

Page 13: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

13

4 FLEXLABTestingandAnalysis

4.1 Approach

LBNL’s FLEXLAB test facility allows building systems to be tested individually or as anintegrated system, under real-world conditions. FLEXLAB test beds can test HVAC, lighting,windows,buildingenvelope,controlsystems,andplugloads,inanycombination.

ThekeyobjectivesoftheFLEXLABtestingforthissystemwereto:• Analyze lighting and HVAC energy savings from automated shading integratedwith

lightingandHVACcontrols,forChicagoclimateconditions.• Evaluatevisualcomfortparameters.• Evaluate level of effort and uncertainty associated with different levels of

measurement.

Side-by-side “controlled” testing: The test case (i.e. automated shading integrated withlighting)andthebaselinecase(i.e.manuallyoperatedvenetianblindsandnodaylight-baseddimming)weretestedatthesametimeunder identicalconditionsusingthetwocellsoftheFLEXLABrotatingtestbed.Figures2and3showthefloorplanandexternalviewrespectivelyoftherotatingtestbed.Eachtestcellisapproximately20’wideand30’deep.

Figure2. FloorplanoftheFLEXLABrotatingtestbedshowingtwotestcellsusedforthetest

case(CellB)andbaselinecase(cellA).

Page 14: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

14

Figure3. ExternalviewoftheFLEXLABrotatingtestbed

Testduration:Theintentwastoconductsolstice-to-solsticetestinginordertocapturethefullrange of solar positions. However, the project schedule did not allow for this. Testing wasconductedintwostages:thefirstthree-monthperiodwasfromMay9toAugust10,2016;thesecondwasfromOctober3,2016toJanuary4,2017.

Automated shading system specification: LBNL selected an automated shading system fromMechoSystemsthatmetthespecificationsdescribed insection3.Theshadefabricwasdarkgrey in color,with anopenness factorof 3%.Ordinarily, someaspectsof the shade controlwouldbecustomizedbytheuserbasedontheirpreferences.Forthistest,whichisdesignedtobebroadlyapplicable,theseshadecontrolsweresettorepresenta‘standard’application.Therewere six discrete shade settings, not allowingdirect solar penetrationmore than36”intothespaceatfloorlevel.

Baseline shading control: For the baseline case, venetian blinds were in the deployedhorizontalpositionforalltestconfigurations.

Multipleconfigurations:Inordertomakethetestresultsasbroadlyapplicableaspossible,thefollowingfiveparameterswerevariedtoevaluatetheirimpactontheresults:

• Orientation:southandwest.Thiswasaccomplishedbyrotatingthetestbed.• Window-to-wall ratio: 0.4 (default) and0.3. The smallerWWRwasaccomplishedby

placingfoamcorepanelsinthewindow(Figure4).

Page 15: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

15

Figure4. Foamcorepanelswereusedtotestsmallerwindow-to-wallratio.

• Daylight-dimmingzone:Threedepthsweretested.A10’zonethatwouldrepresenta

smaller single occupant perimeter closed office; a 15’ zone that would represent alargermulti-occupantperimeteroffice;anda25’zonethatwouldrepresentanopenofficeextendingtotheperimeter.Moveablewallswereusedtochangethezonesize(Figure5).

Figure5. Moveablewallsusedtochangedaylight-zonedepth.

Page 16: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

16

• Lighting type: Two Lighting types were tested: LED (default) and T-8. Both lighting

typeswerependantmounted,with three rows locatedparallel to thewindowwall.Thespacingbetween fixtureswas8 feetoncenter. Light levelswere tuned tomeet500lux(~50fc)workplaneilluminance.Thelightswereturnedoffduringunoccupiedhours (7pm to 7am). For this test,which is designed to be broadly applicable, thedimming controlswere set to represent a ‘standard’ applicationwithout aggressivedimmingstrategies.Forthe25’zone,thedefaultcontrolsettingonlydimmedthefirstandsecondrowof lights fromthewindowwall. LBNLalso testedamoreaggressivecontrolsettingwhichalsodimmedthethirdrowoflights.

Section 4.2 providesmore detail on the configuration and testing schedule for each of theparametric variations. These parametric variations were applied identically in the test caseand baseline case. All other parameters of the testbed remained fixed over the course oftestingandaresummarizedintable2.Figure6showsaninternalviewofthetestcasecell.

Table2. Fixedparametersoftestcells.Feature Description Glazing PPG SolarBan 70XL. visible transmittance = 64%; U-value = 0.24;

Solar heat gain coefficient = 0.27. Wall insulation R-11 on window wall and rear wall. R-25 on side walls. Roof insulation R-22 HVAC Variable air volume system with electric reheat. Occupancy loads Four occupant heat generators per test cell, approximately 130 W

per generator, following occupancy schedule. Plug loads Four computers and monitors per test cell. About 0.75W/sf peak,

controlled to approximate schedule in ASHRAE 90.1 user guide. Occupancy schedule Occupied hours 7am-7pm.

Figure6. Internalviewoftestcellandkeyfeatures

EachrowofLEDfixturesdimmedseparatelytomeetilluminancesetpoint

Automa:cshadingcontrolledbyglaresensor

Occupantheatgenerators

Plugloads

Illuminancesensorsat3’intervalsatworkplane

HDRcamerasforglareassessment

Page 17: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

17

Adjusting for Chicago climate: ComEd is interested in savings estimates for their serviceterritory located in northern Illinois. FLEXLAB is located in Berkeley, California, which hassignificantly different climate. In order to obtain an assessment of HVAC loads in Chicagoclimate, the internal temperaturesetpointswereadjusted in real timetomatch the indoor-outdoor temperature difference in Chicago, using the Typical Meteorological Year (TMY)temperaturedataforChicago.

Visualcomfortmetrics:Whilethefocusofthisanalysiswasonenergysavings,thetestingalsoincludedabasicevaluationofvisualcomfort,includingworkplaneilluminanceandglare.

4.2 TestandMeasurementPlan

FLEXLAB testing provided savings data based on controlled side-by-side testing over thecourseof6months.Asmentionedabove,FLEXLABtestingcoveredvariousconfigurationsoforientation,daylightzonesize,window-to-wall-ratio(WWR),andlightingtype.

Table 3 describes the each of the configurations that were tested. Table 5 indicates thatnumber of test days eachmonth for each configuration. In general, the intentwas to haveeachmajorconfigurationtestedforatleast3dayseachmonth.4Sand4Wwerenottestedinthefirsttestingperiod,duetolatearrivalofequipment.

Table3. Configurationstested.Thesesettingswereappliedidenticallytothetestcaseandbaselinecase.

ID Orient. WWR Zone depth

Lighting type

Description

1S S 0.4 25’ LED ‘Default’ settings for all parameters 1W W 0.4 25’ LED ‘Default’ settings for all parameters 1Sx S 0.4 25’ LED 1S + dimming 3rd row of lights 1Wx W 0.4 25’ LED 1W + dimming 3rd row of lights 2S S 0.3 25’ LED 1S with smaller windows 2W W 0.3 25’ LED 1W with smaller windows 3S15 S 0.4 15’ LED 1S with 15’ zone 3W15 W 0.4 15’ LED 1W with 15’ zone 3S10 S 0.4 10’ LED 1S with 10’ zone 3W10 W 0.4 10’ LED 1W with 10’ zone 4S S 0.4 25’ T-8 1S with T-8 4W W 0.4 25’ T-8 1W with T-8 4Sx S 0.4 25 T-8 4S + dimming 3rd row of lights 4Wx W 0.4 25 T-8 4W + dimming 3rd row of lights 4S10 S 0.4 10’ T-8 4S with 10’ zone 4W10 W 0.4 10’ T-8 4W with 10’ zone

Page 18: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

18

Table4. NumberoftestdaysforeachconfigurationID May June July August Oct Nov Dec Jan 1S 7.5 5 5 0 4 4.5 0 0 1W 6.5 6 5 0 5 4.5 0 0 1Sx 0 0 3.5 0 0.5 5.5 0 0 1Wx 0 0 4 0 0 4.5 0 0 2S 5 5 3 0 0 4 0 0 2W 3.5 4 3 0 0 3 0 0 3S15 0 4 4 3 3 0 0 0 3W15 0 5.5 2.5 0 4 0 0 0 3S10 0 0 0 4 4 0 0 0 3W10 0 0 0 3 0 0 0 0 4S 0 0 0 0 0 0 5 0 4W 0 0 0 0 0 0 5 0 4Sx 0 0 0 0 0 0 3 0 4Wx 0 0 0 0 0 0 9 2.5 4S10 0 0 0 0 0 0 0 3.5 4W10 0 0 0 0 0 0 0 5.5

Datacollection

FLEXLABoffersextensiveandhighlygranulardatacollectioncapabilities. Table5showstheprimary data collected for this test and the associated measurement equipment. DatacollectionwascheckedonadailybasisusingFLEXLAB’ssMapdatacollectionsystem.

Table5. Primarydatacollectedfortest.Metric Measurement Lighting power per fixture FLEXLAB infrastructure Shade position MechoSystem Shade controller Brightness at window MechoSystem brightness sensor located inside window Exterior horizontal illuminance MechoSystem Shade controller Workplane illuminance LiCor sensors on workplane at 3’ intervals from window wall Daylight glare probability HDR cameras oriented parallel and perpendicular to window Plug loads FLEXLAB infrastructure Occupant loads FLEXLAB infrastructure Set point temperature FLEXLAB infrastructure Supply air temperature FLEXLAB infrastructure Return air temperature FLEXLAB infrastructure Thermal load FLEXLAB infrastructure Heating energy use FLEXLAB infrastructure Cooling energy use FLEXLAB infrastructure Ventilation energy use FLEXLAB infrastructure

Datacleansing

ThedatawereplottedinsMapandcheckedforcompletenessandreasonableness.Datawerenotusedforperiodsthatwereknowntohavemeasurementissuesandperiodswhenthetestcellswerebeingreconfigured.

Page 19: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

19

Dataanalysis

Theprimarymetricsofinterestwere:

• Lightingenergysavings–calculatedfromthelightingpowermeasurements;

• Thermalloadsavings–calculatedfromthermalloadmeasurements;

• HVACenergysavings–calculatedfromthermalloadsavingsandequipmentefficiencyassumptionsforvariousequipmentscenarios;

• Workplaneilluminance–profilesgeneratedfromilluminancemeasurements;

• Daylightglareprobability–profilesgeneratedfromDGPdata.

4.3 LightingSavings–TestPeriod

Figures7-22present the lightingenergysavings foreachconfiguration foreachhour (blue),day (green) and over the multi-day test period (red) for each configuration. The lightingsavingsarecalculatedasapercentagereductioninlightingenergyuseofthetestcaserelativetothebaselinecase.Table6providesasummaryofthesavingsforeachconfiguration.

Figure7. Lightingenergysavingsforconfiguration1S(Fullzone,South,NormalWWR)

Page 20: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

20

Figure8. Lightingenergysavingsforconfiguration1W(25’,West,NormalWWR)

Figure9. Lightingenergysavingsforconfiguration1Sx

(25’,South,NormalWWR,Rearrowdim)

Page 21: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

21

Figure10. Lightingenergysavingsforconfiguration1Wx(25’,West,NormalWWR,Rearrow

dim)

Figure11. Lightingenergysavingsforconfiguration2S(25’,South,SmallWWR)

Page 22: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

22

Figure12. Lightingenergysavingsforconfiguration2W(25’,West,SmallWWR)

Figure13. Lightingenergysavingsforconfiguration3S15(15’zone,South,NormalWWR)

Page 23: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

23

Figure14. Lightingenergysavingsforconfiguration3W15(15’zone,West,NormalWWR)

Figure15. Lightingenergysavingsforconfiguration3S10(10’zone,South,NormalWWR)

Page 24: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

24

Figure16. Lightingenergysavingsforconfiguration3W10(10’zone,West,NormalWWR)

Figure17. Lightingenergysavingsforconfiguration4S(25’zone,South,NormalWWR,T8)

Page 25: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

25

Figure18. Lightingenergysavingsforconfiguration4W(25’zone,West,NormalWWR,T8)

Figure19. Lightingenergysavingsforconfiguration4Sx(25’zone,South,NormalWWR,T8,

rearrowdim)

Page 26: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

26

Figure20. Lightingenergysavingsforconfiguration4Wx(25’zone,West,NormalWWR,T8,

rearrowdim)

Figure21. Lightingenergysavingsforconfiguration4S10(10’zone,South,NormalWWR,T8)

Page 27: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

27

Figure22. Lightingenergysavingsforconfiguration4W10(10’zone,West,NormalWWR,T8)

Table6. Lightingsavingsovertestperiodforeachconfiguration.

ID Description SummerTestPeriod(May–Aug)

WinterTestPeriod(Oct–Jan)

Length(days)

Savings(%)

Length(days)

Savings(%)

1S 25’,South,NormalWWR 17 44 8.5 6

1W 25’,West,NormalWWR 17 29 9.5 19

1Sx 25’,South,NormalWWR,Rearrowdim 3.5 49 6.5 4

1Wx 25’,West,NormalWWR,Rearrowdim 4 30 4.5 19

2S 25’,South,SmallWWR 13 44 4 4

2W 25’,West,SmallWWR 10 26 3 17

3S15 15’zone,South,NormalWWR 11 66 3 22

3W15 15’zone,West,NormalWWR 8 48 4 37

3S10 10’zone,South,NormalWWR 4 88 4 29

3W10 10’zone,West,NormalWWR 3 58 0

Page 28: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

28

4S 25’,South,NormalWWR,T8 0 5 9

4W 25’,West,NormalWWR,T8 0 5 14

4Sx 25’, South,NormalWWR, T8, Rear rowdim 0 3 9

4Wx 25’, West, NormalWWR, T8, Rear rowdim 0 11.5 21

4S10 10’,South,NormalWWR,T8 0 3.5 39

4W10 10’,West,NormalWWR,T8 0 5.5 23

Dailyprofileswerealsoanalyzedtoidentifyhowsavingsvariedwithdifferentskyconditions.Asanillustrativeexample,Figure23showstwoadjacentdaysinwhichthesavingsvariedfrom41%to45%justduetovariableskyconditions,allotherparametersbeingidentical.

Figure23. LightingenergyprofileforMay14-152016forconfiguration1S.

Keyobservationsfromthetestperiodresults:• Savingsaresignificantbutcanvarywidelyoverthecourseoftheyear,duetochange

insunanglesandassociateddeploymentofshades.Insummer,savingsarehigherforsouthfacingconfigurationsthanwest-facingconfigurationsallotherparametersbeingequal.Analysisof the shadeoperationandsolar conditions indicate that theshadesare deployed for longer periods in thewest facing orientation in the afternoons tominimize direct solar radiation, resulting in the lights being turned on for longerperiods (Figure 24). Also, thewest orientation has less dimming in themorning. Inwinter,savingsinthesouthfacingconfigurationsaregenerallyverylowbecauselowsunangles cause the shades tobedeployedduringmostdaylighthours. Savings for

front row

middle row

Back row

May 14 Savings = ~41%

May 15 Savings = ~45%

Less dimming ~7-9 am and ~5-7pm on May 14 vs. May 15

Page 29: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

29

thewestorientationinwinterarenotaslowasthesouthbecausethereisnodirectsunonthefaçadeduringthemorninghours,allowingshadestoberetractedduringthosehours.

Figure24. LightingenergyprofilesfortwodaysinMayforconfiguration1W.

• Asexpectedthelightfixturesclosertothewindowshowgreatersavings.• Asexpected,savingsarehigherforsmallerzonesclosertothewindowwall.Thiscan

beseenbycomparingconfigurations1S,1S15,and1S10whichrepresent25’,15’,and10’zonesforsouthorientationwithallotherparametersbeingequal.

• Reducing the window-to-wall-ratio from 0.4 to 0.3 has a small impact on daylightpenetration and lighting energy savings. Figure 25 shows illuminance profiles forsensorslocatedat3’ intervalsfromthewindowwall.Thewindowssizewaschangedbetween8:00amand8:10am.The reduction in illuminance isnoticeable.However,theneteffectonlightingsavingsissmall(SeeagainTable6).

• Forconfigurationswiththe25’zone,dimmingtherearrowoflightsappearstohaveminimaleffectonincreasingsavings.

Shades fully deployed, no dimming after ~3pm

Less dimming in morning compared to south facing

Page 30: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

30

Figure25. Impactofreducingwindow-to-wallratiofrom0.4to0.3.

Figure26showsthesetpointtrackingtoemulatetheindoor-outdoortemperaturedifferenceforChicagoTMYclimatedata. Itshowsthatbothtestcellswereabletomaintainverygoodtrackingoverawiderangeofindoorsetpoints,from10C(50F)to33C(91F).However,analysisof the HVAC load data showed that with LED systems the change in HVAC loads due todimmingisminimalandnotobservablewiththeaccuracyrangeofFLEXLABloadmonitoring.

Figure26. IndoortemperaturesetpointtrackingtoemulateChicagoTMYclimate.Redlineis

setpoint.Lightanddarkgreenlinesareactualindoortemperaturesfortestcells.

South Facing

Change to smaller window. Impact:

~200 lux at 3-6’ from window ~100 lux ~9-12’ from window

Workplane Illuminance at 3’ intervals from window

Page 31: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

31

4.4 LightingSavings-Annualized

We used a regression-based approach to determine annual lighting savings based on themeasurementperiodsavings.Separateregressionequationsweredeterminedfor1Sand1Wconfigurations.

Savings are a function of shade deployment and daylight availability. Shade deployment isdriven by sun position and horizontal radiation. In general lighting savings increase withdaylightavailability,unlessshadesaredeployedtocontrolforsunpenetrationandglare.

We first developed a series of bivariate charts to analyze the relationship between lightingsavings and global horizontal illuminance, global horizontal radiation, vertical illuminance,solarazimuthandsolaraltitude.Wealsoexploredtheimpactofusingdifferenttimesteps–5minutes,10minutes,60minutes,and24hours–fortheanalysis.

Basedon thebivariateanalysis,weexploredvarious forms for the regressionequation.Theregressionmodelwhichprovidedthebestfitcomputeslightingsavingsonanygivendayasafunction of solar altitude and horizontal radiation. The model has a constant offset, twopiecewiselineartermsforaltitude(foraltitude<=53degreesandaltitude>53degrees),anda linear term for horizontal radiation.Table 7 lists the variables and their and coefficientvaluesforeachmodel.

Table7. Regressionmodelvariablesandcoefficientsforconfiguration1SVariable 1S model coefficient value 1W model coefficient value Si (dependent variable): % lighting energy savings on day i from 7am to 7pm

- -

Constant -3.010 13.01 Ai: peak solar altitude on day i 0.2087 (alt <= 53 degrees)

1.7280 (alt > 53 degrees) 0.3878 (alt <= 53 degrees) -0.08165 (alt > 53 degrees)

Ri: sum of global horizontal radiation on day i between 7am to 7pm when it is below 50 kBtu/hr-sf

0.05196

-0.06622

Thethresholdvalues forRi (50kBtu/hr-sf)andaltitude(53degrees)are ineffectproxies forthepointatwhichshadesgetdeployedandthesavingschangesignificantly.

Figures27and28comparepredictedtomeasuredvaluesfor1Sand1WrespectivelyandalsoshowtheR2valuesforbothcases.

Page 32: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

32

Figure27. Comparisonofpredictedandmeasuredvaluesofdailysavingsforconfiguration1S.

Figure28. Comparisonofpredictedandmeasuredvaluesofdailysavingsforconfiguration1W.

WethencalculatedannualsavingsbycalculatingsavingsforeachdayoftheyeardrivingtheregressionequationwithTMY(TypicalMetrologicalYear)dataforAiandRiforeachday.WedidthisusingTMYdataforOakland(torepresentBerkeley)andChicago.

Figure29and30showthedailyandannuallightingsavingsforOaklandforconfigurations1Sand1Wrespectively.Figures31and32showthesameforChicago.Thefiguresalsoshowthesavingsrangeforthe95%confidencelevel.

Page 33: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

33

Figure29. Annuallightingsavingsforconfiguration1SusingOaklandTMYdata

Figure30. Annuallightingsavingsforconfiguration1WusingOaklandTMYdata

Page 34: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

34

Figure31. Annuallightingsavingsforconfiguration1SusingChicagoTMYdata

Figure32. Annuallightingsavingsforconfiguration1WusingChicagoTMYdata

Forboth1Sand1W,savingsaresignificantlylowerinwintermonths.Asexplainedearlierthisbecause lower sun angles cause the shade to be deployedmuchmore of the time than insummer.Nevertheless,theannuallightingsavingsaresignificant.ForChicago:

• Southorientation showsameanof 19%annual savings,with a rangeof 12-26% (at95%confidence).

• West orientation shows amean of 24% annual savings,with a range of 19-30% (at95%confidence).

It should also be noted that more aggressive dimming strategies would result in highersavings.Asnotedearlier,weintentionallyused‘standardpractice’settingsfortheshadesanddimming,inordertoreflectbroaddeploymentinthecontextofautilityprogram.

Page 35: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

35

It is important to reiterate that these savings are exclusively attributable to automatedshadinganddimming andwillbeadditional to savings from lightingupgrades. Inparticular,these savingsdonot include the savings from tuning i.e. the savingsare relative toa tunedbaseline.

4.5 WholeBuildingSavingsEstimates

Wholebuilding(WB)savingsestimatesincludelightingenergysavingsaswellasHVACenergysavings (or penalties). It is difficult to generalize WB savings because they are highlydependentontwokeybuildingfeatures: impactedarea(i.e. the%of total floorareathat isimpactedby shadinganddimming) andHVAC system type.Buildingswith smaller impactedareaswillnaturallyhavesmallerWBsavingsallotherthingsbeingequal.HVACenergysavingscan vary quite differently for different HVAC system types and efficiencies for the samereductioninthermalload.

WeestimatedWBsavings for fourbuildingtypes- largeandmediumoffice;primaryschool,secondary school–using theDOE referencebuildingEnergyPlus simulationmodels. Table8summarizesthekeyfeaturesofthesemodels.

Table8. KeyfeaturesofreferencebuildingsReference building Gross floor area (sf) % Area impacted HVAC system type Large Office 498,588 42% Central electric chiller and gas boiler.

Hot water reheat. Medium Office 53,628 62% Packaged units with electric reheat. Primary School 73,959 59% Packaged units with gas heating Secondary School 210,886 39% Air cooled chillers and packaged units

with gas heating

We used the following approach to determine WB savings using the reference modelsimulationsinconjunctionwithFLEXLABmeasurementresults:

• Simulatereferencemodelswithbaselineandretrofittedsystem.

• CalculateHVACsavingsratiofromsimulationresults.HVACsavingsratioistheHVACenergy saved per unit of lighting energy saved. Separate ratios are calculated forelectricityandgas.

• Apply FLEXLAB lighting savings percentages to the baseline lighting energy todetermine lighting savings. The lighting savings percentages from the FLEXLAB testswere incremented to account for savings from institutional tuning, assuming theuntunedbaselineis30%higherthanthetunedbaseline1.

• ApplyHVACsavingsratiotodeterminetheadjustedHVACsavings.

• CalculatethetotalWBsavingsandWBsavingspercentagefromthelightingandHVACsavings.

Table9presentstheresults.

1 Theextentofsavingsfromtuningvariesbasedontheextenttowhichthelightingisright-sizedandinstallationpractices.TheLBNLmetaanalysis(Williamsetal.)showedinstitutionalsavingsof36%(N=11).Morerecentanecdotalevidenceshowssavingsaround30%.Weusedamoreconservativeestimateforthisanalysis.

Page 36: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

36

Table9. WholebuildingsavingspercentagesforreferencebuildingsReference building Whole Building

Lighting Svg % Whole Building Total Elec Svg %

Whole Building Site Energy Svg %

Large Office 16% 5.0% 2.6% Medium Office 22% 4.5% 3.5% Primary School 20% 9.0% 4.8% Secondary School 14% 6.2% 2.7%

4.6 VisualComfortAnalysis

Our visual comfort analysis was comprised of two primary metrics: workplane illuminance(lux)andglare(daylightglareprobability).Belowwediscussthemeasurementapproachandresultsforeachmetric.

4.6.1 Illuminance

In the FLEXLAB cells where the reference and test lighting and shade system packages areinstalled, we monitor average illuminance at the task plane (2.5’) from an array ofphotometric sensors (Figure 33). Most lighting design criteria are centered aroundrecommendationsforilluminancelevelsatthetaskplane.

Figure33. Licorphotometricsensor

Licorphotometricsensorsarearrangedinamonitoringarrayinthetestcellstomeasurelightlevels in high-time resolution (1-min. average illuminance) at selected locations throughoutthetestspace(Figures34and35).TheFLEXLABdataacquisitionsystemrecordsandreportsthesevaluesinnear-realtime.

Page 37: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

37

Figure34. Licorphotosensorconfiguration.BluedotsindicatelocationoftheLicorphotosensors,showingthemarrayedprimarilyalongoneaxistomeasureilluminanceatdifferentdepthswithinthecell.CameraiconsdenotelocationofHDRcameraset-upsfor

DGPdatacollection.

Figure35. PhotoofLicorphotosensorarrayondesksintestcell

Page 38: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

38

Figures36 to41showthe rangeof illuminanceatdifferentdepths fromthewindowduringthe measurement period, for selected configurations. As expected, sensors closer to thewindow show higher illuminance values. The plots show that the test system maintainedilluminanceatorabove500luxthroughoutthemeasurementperiod,asintended.

Figure36. Illuminancerangesforconfiguration1S.Boxplotmarkersarefor5th,25th,50th,75th

and95thpercentiles.

Figure37. Illuminancerangesforconfiguration1W.Boxplotmarkersarefor5th,25th,50th,75th

and95thpercentiles.

Page 39: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

39

Figure38. Illuminancerangesforconfiguration1Sx(rearrowdimming).Boxplotmarkersare

for5th,25th,50th,75thand95thpercentiles.

Figure39. Illuminancerangesforconfiguration1Wx(rearrowdimming).Boxplotmarkersare

for5th,25th,50th,75thand95thpercentiles.

Page 40: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

40

Figure40. Illuminancerangesforconfiguration2S(0.3WWR).Boxplotmarkersarefor5th,

25th,50th,75thand95thpercentiles.

Figure41. Illuminancerangesforconfiguration2W(0.3WWR).Boxplotmarkersarefor5th,

25th,50th,75thand95thpercentiles.

Page 41: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

41

4.6.2 Glare

Glarewascharacterizedusingthedaylightglareprobability(DGP)index,whichreliesonhighresolution,field-of-viewhighdynamicrange(HDR)luminanceimagestoassessglare.TheHDRcamerapackageswere locatedatselectpositionswithinthetestcell tocharacterizesurfaceluminances and DGP through time at viewing angles consistent with those that could beexperienced by an office worker in the space. Typically, thesewere set up in “worst-case”scenarios, nearer the window wall and either facing the window or perpendicular to thewindow(Figure42).ThepremiseofmeasuringglareattheselocationsisthatifalightingandshadesystemmeetsminimumcriteriaforDGPattheselocations,itislikelythatthosecriteriaaremetelsewhereinthespaceaswell.

Figure42. PhotoofHDRcamera,sensor,andprocessorpackagesforglareanalysisinFLEXLAB

Hemisphericalfield-of-viewluminancemeasurementsweretakenthroughouteachstudydayatfive-minuteintervals.Measurementsweretakenatseatedeyeheight4ftabovethefloor,at locationsbothparallel andperpendicular to thewindow.The imagesprocessed for glareanalysis are taken with commercial-grade digital cameras (Canon 60D) equipped with anequidistant fisheye lens (Sigma Ex 4.5 mm f/2.8) controlled by Mac CPUs. Bracketed lowdynamicrange(LDR)imagesareautomaticallytakenwithafixedf-stopof5.6usingin-housemodifiedsoftware(hdrgen).Fourtosevenimagesweretakenpertimeintervaldependingonthebrightnessofthescene.

The hdrgen software compiles the LDR images into a single HDR image with the cameraresponse functiondeterminedbythesoftware.Avertical illuminancemeasurement is takenbytheHDRcamerasetuptakenadjacenttoeachcamera’slens,immediatelybeforeandafter

Page 42: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

42

thebracketedsetofimages,andusedinthehdrgencompositingprocesstoconvertpixeldatatophotometricdata.HDR images (Figures43,44)are thenanalyzedautomatically toassessdiscomfortglarefromdaylightandidentifyglaresourceswithinthefieldofview.

The Daylight Glare Probability (DGP) index relies on these high resolution HDR images toassessglare.TheindexwasderivedthroughacomprehensivestatisticalanalysisofHDRdataandsubjectiveresponseinafull-scaleprivateofficetestbedthatwasretrofitwithavarietyofdaylighting measures (Weinold and Christoffersen 2006). DGP was calculated using theevalglare software (Weinold 2009) and default software settings. DGP does not reflect themagnitudeofglareperceivedbytheobserver.Insteaditgetsaroundtheproblemofperson-to-personvariabilityinresponsetoperceivedglarebyestimatingtheprobabilitythatapersonis“disturbed”byglare(theDGPformulationdefined“disturbed”basedonthesubjectratingthedaylight glare source to be “disturbing” or “intolerable”).Wienold derived amethod toaccount for the frequency of glare over a time period,wherewithin a defined category ofcomfort, 3-5% exceedance of a threshold limit is allowed. Glare ratings ranging from“imperceptible”to“intolerable”wererelatedtoDGPvaluesinadescriptiveone-wayanalysisofthestudy’suserassessmentdata.

Figure43. Time-stampedimagefromanHDRcameraset-uppositionedperpendiculartothe

windowwall.ThecalculatedDGPforthistimeisdenotedinthelowerrightcorner,andtheHDRcamerafacingthewindowwallisvisibleinthecenteroftheimage.

Page 43: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

43

Figure44. Exampleofafalse-colorimagefromtheHDRcameraset-upthatprovidesaluminancemapofthecamera’sviewingangle.ThisparticularHDRcameraispositionedat

therearofthetestcell,facingthewindowwall,withthepixelofhighestluminancelabeled.

Figures45-48showtheDGPforvariousconfigurations. Thedatashowthatthetestsystem(cell B) maintained daylight glare probability (DGP) within acceptable levels. For the viewparallel to the window plane, DGP was imperceptible almost all the time. For the viewperpendicular to thewindowplane,DGPwasoccasionally in theperceptible rangeandveryrarely in the disturbing or intolerable range. For the baseline case (cell A) there weresignificantperiodswhereDGPwasinthedisturbingorintolerablerangebecausethevenetianblindswereinafixedhorizontalposition,allowingfordirectsunlightatlowersunangles.

Page 44: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

44

Figure45. DGPrangesforconfiguration1S.CellAisbaselinecell.CellBistestcell.Windowreferstocamerafacingwindow.Monitorreferstocamerafacingparalleltowindowplane.

Figure46. DGPrangesforconfiguration1W.CellAisbaselinecell.CellBistestcell.Windowreferstocamerafacingwindow.Monitorreferstocamerafacingparalleltowindowplane.

Page 45: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

45

Figure47. DGPrangesforconfiguration2S.CellAisbaselinecell.CellBistestcell.Windowreferstocamerafacingwindow.Monitorreferstocamerafacingparalleltowindowplane.

Figure48. DGPrangesforconfiguration2W.CellAisbaselinecell.CellBistestcell.Windowreferstocamerafacingwindow.Monitorreferstocamerafacingparalleltowindowplane.

Page 46: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

46

5 SavingsEstimationforCustomerSites

This section describes technical criteria for targeting customer sites and assessing thepotentialsavingsatthesesites.

5.1 CandidateSiteRequirements

Customersiterequirementstoapplyfortheincentiveprogramshouldincludethefollowingataminimum:

• 10ft.floor-to-ceilingheightswithdroppedceiling/plenumforroutingofpowerandcommunications.

• Moderatetolargewindows(window-wallratio>30%).• Clearorlowtintglazing.• DigitallyaddressabledimmingballastsorLEDdrivers.Thisrequirementmaybemetif

thissystemiscombinedwithalightingupgrade.• Perimeter areas constitute significant proportion of total floor area (>25%). It is

preferabletohaveopenofficeonperimeterratherthanclosedofficeasthisincreasestheimpactedarea.

Additionalconsiderationsthatwouldlikelyimproveapplicability:• Minimumof8hoursaveragedailyoccupiedhours.• Openofficepartitions4ft.orless.• BMSwithtrendcapability.

5.2 CandidateSiteSavingsEstimates

Asnotedearlier,thewholebuildingsavingsforanygivensitewillvarysignificantlybasedonthe impacted area. Buildings with a larger proportion of perimeter area will see greatersavingsthanthosewithless,allotherparametersbeingequal.Likewise,savingsvarybasedontherelativeproportionoffloorareaineachorientation.

Savings also vary based on factors such as rear-row dimming, window area, glazingspecifications, but these factors are secondary for first order analysis of savings for thepurposeoftargetingsites.

Wedevelopedasimpleestimatortoassessthepotential lightingandwholebuildingsavingsfor a candidate site based on the FLEXLAB testing results. It should be noted that thismethodologyisonlyforassessingpotentialsavingsinthecontextoftargeting,akintoa“backoftheenvelope”analysis.ItdoesnothavethelevelofrigortypicallyneededforM&V,whichisdiscussedinthenextsection.

Theestimatorinvolvesthefollowingsteps.1. Determine impacted perimeter area for each orientation. If the perimeter has closed

offices,theimpactedareaislimitedtothedepthoftheclosedoffice.Iftheperimeterhasopenoffices,theimpactedareacanbeassumedtobeupto25’depthfromthewindow,assumingnopartitionsgreaterthan4’highparalleltothewindowwall.

2. Determinelightingpowerdensitywhenlightsarefullyoni.e.notdimmed.3. Calculate area-weighted whole building lighting energy savings %, based on regression

modeldescribedearlier.4. CalculateHVACsystemsavings,assumingsavingsfactorsperunitoflightingsavings.5. CalculatewholebuildingsavingsassumoflightingandHVACsavings.

Page 47: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

47

6. Calculate whole building % savings based on annual whole building consumption fromutilitybills.

Screenimagesofthespreadsheet-basedestimatorareincludedinappendixB.

6 M&VConsiderations

6.1 OperationVerification

According to the InternationalPerformanceMeasurementandVerificationProtocol (IPMVP)operational verification “consists of a set of activities that help to ensure that the ECM isinstalled,commissionedandperformingitsintendedfunction.”IPVMPstatesthatoperationalverificationshouldbeincludedinM&Vplans.IPMVPdescribesfourapproachestooperationalverification: visual inspection, sample spotmeasurements, short-term performance testing,anddatatrendingandcontrollogicreview.

The performance of automated shading and daylight dimming its strongly dependent oncorrectprogrammingandoperationofcontrolsinresponsetochanginginternalandexternalilluminance and solar parameters. Given that, we strongly recommend that operationalverification utilize data trending and control logic review. In particular,we recommend thefollowingataminimum:

Shadingsystem:

• Verifythattheshadecontrollogicisprogrammedasintendedforeachorientation.

• Trendtheshadepositionandshadecontrolinputs(e.g.solarradiation,sunposition)andverifythatshadepositionisasintendedpercontrollogic.Trendperiodshouldbeseveraldaysandincludearangeofcloudcoverconditions.

Daylightdimmingsystem:

• Verifythatat100%dimmingthatthelightfixtureactuallyproducesnolightoutput.Ithasbeenobservedthatsomelightingcontrolssystemshaveapreprogrammedlowerlimit on their dimming controls so that the lights do not actually turn off at fulldimming.

• Verify the lightoutput (lux)of the fixture at 100% (on) is at theminimum lux levelmeasuredattheworkplane.Thistestshouldbeconductedatnight,withaminimumofotherartificiallightsourcesimpactingtheareabeingverified.

• Trendthelightingpoweroverthecourseofseveraldaysandverifythatthedimmingprofile isasexpected foreach rowof fixtures. Forexample, the rowclosest to thewindow would dim more than rows further from the window. Dimming shouldincreasewhen shades are raised and vice versa. If lighting power is not available,dimmingstatusmaybeusedasaproxy.

• Measureworkplane illuminance to ensure that itmeetsminimum requirements. Itacceptable to use spot measurements but they should cover a range of dimmingconditionsanddistancesfromwindow.

The verification for both systems maybe done as part of routine commissioning for thesesystems,andmaybeincludedinthescopeofworkfortheinstaller.

Page 48: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

48

6.2 M&VOptions

IPMVPdescribes fouroptions forM&V. Belowwediscuss theapplicabilityand implicationsforeachoftheoptions.Theprogramcoulduseatieredapproach-stipulatesavingsbasedonFLEXLAB results aboveandprovide limited incentivebasedondiscounted savings andbasicoperational verification. Additional incentives may be provided based on the uncertaintyreductionassociatedwitheachoftheM&Voptionsdescribedabove.

OptionA:

Giventhedynamicnatureofthissystemanditsdependenceonchangingsolarconditions,wegenerallydonotrecommendusingoptionA.

OptionB:

Thismethodprovidesthemostdirectmeasurementofsavingsattributabletothemeasure.ItmaybetheonlyoptionifthewholebuildingoptionCisnotviableduetotheretrofittedareabeing too small relative to total area. There are two components to the savings: lightingsavingsandHVACsavings.

Lightingenergymetering: Post retrofitmeasurementmaypossible from the lighting controlsystem. Some systems measure power directly, while others calculate power based ondimmingstatus.Inthelattercase,itiscriticaltoensurethatthecommissioningwasdoneandthe calculated power was verified with direct measurements. (see section 6.3.1 for moreinformation)

Pre-retrofit lighting energy use could be estimated using temporarymeasurements of loadandthesamescheduleaspost-retrofit. If theretrofit includedachange in lampsor fixturesand the intent is to determine savings attributable only to the automated shading anddimming, the baseline can be determined from the post-retrofit peak wattage withoutdimming. Installing a permanent EIS that includes lighting energy usewould have the dualbenefitofM&Vaswellascontinuouscommissioning.

AreaSampling:Savingscanvarybyorientationduetodifferentsolarandexternalconditions.Ifsampling,itiscriticaltoensurethatthesamplespacescovertherangeoforientationsandexternal conditions as well as internal occupancy conditions. For tall buildings, orientationalone does not address external conditions as the obstructions at lower floors may besignificantlydifferentthanthoseonhigherfloors.

Measurementperiod:Duetosignificantseasonalvariationsinsavings,itisimportanttohavemeasurementscoverarangeofseasonalconditions.Theidealperiodwouldbefromsolsticetosolstice.Ifthatisnotviable,itcouldbedoneforshorterperiodse.g.aweekeachmonth,asdoneinFLEXLAB.Savingsextrapolationcouldbedoneinamannersimilartotheassessmentmethodologydescribedearlier.(Seesection6.3.2formoreinformation.)

HVACmeteringforoptionBwouldbeimpossibleinmostcasesbecausetheHVACsystemwilllikelyservemorethanjusttheretrofittedarea.HVACsavingscouldbecomputedfromlightingsavingsusingtheassessmentmethodologydescribedearlier.

OptionC:

Thekeycriterion forusingoptionC iswhether thewholebuilding savingsare largeenoughrelative to thevolatility inwholebuildingenergyusedue toweatherandoperations.Whilethelightingsavingsintheimpactedarea(perimeterzones)arelarge(~20-25%)thesavingsat

Page 49: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

49

thewholebuildingaremuchlower,becausetheimpactedareamayonlybe40-60%oftotalfloor area of the building and lighting energy use is only 20-40% of total energy use anddroppingwithmoreefficientlighting.Asdiscussedearlier,thewholebuildingsavingsforthereferencebuildingswerelessthan5%.

AswithoptionB,itisimportanttohavemeasurementscoverarangeofseasonalconditionsduetosignificantseasonalvariationsinsavings.Ifsavingsneedtobeextrapolated,theycouldusethesamesetofvariablesastheassessmentmethod.

OptionD:

Calibrated simulation could, in theory, be used. However it takes considerable effort andessentiallyrepresentsacustomapproach.Also,itrequiresconsiderableexpertisetocorrectlymodel automated shades and their control logic. As such, we do not think Option D is ascalableapproachforthissystem.

6.3 SavingsUncertainty–FLEXLABDataAnalysis

AuniqueadvantageofthedensityofdataavailablefromFLEXLAB®testingisthatitispossibletoassesstheeffectsonmeasuredenergyperformanceassociatedwiththeabsenceofspecificdata–whichmayreflectcasesofincompleteinformationunderaprescribedM&VapproachoranM&Vapproachthathaslesssite-specificintelligenceordatagranularityassociatedwithit.

Inthisparticularcase,weusedFLEXLABdatatoassesstheimpactoftwoissues:• Reliabilityofcontrolsystemcalculatedlightingpower• Savingsuncertaintywithdifferentmeasurementperiods

6.3.1 Reliabilityoflightingpowerreportedbycontrolsystem.

Forone testwhichuseda lightingcontrols systemthatactuallymeasures lightingenergyatthe control point, the total controls-reported energy for the evaluated periodwaswithin ahalf%ofmeasuredenergy,asshowninfigure49.

Figure49. Comparisonoflightingenergyfromcontrolsystemthatmeasuredactuallighting

energyvs.lightingenergymeasuredbyFLEXLABinstrumentation.

-20%

-15%

-10%

-5%

0%

5%

10%

15%

20%

0

1,000

2,000

3,000

4,000

5,000

6,000

7,000

8,000

9,000

1-Dec

3-Dec

5-Dec

7-Dec

9-Dec

11-Dec

13-Dec

15-Dec

17-Dec

19-Dec

21-Dec

23-Dec

25-Dec

27-Dec

29-Dec

31-Dec

Differen

ceovera

veragesM

APdailyvalue

TotalW

a>-Hou

rs

FLEXLABdata ControlsSystemData difference

Page 50: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

50

For another test which used a lighting controls system that for energy reporting purposesrelies on user-inputs for controlled loads (e.g. nameplate fixture wattage) and dimmingbehaviors (e.g. slope of dimming curve), controls-reported energy for the evaluated periodwasnot close enough tomeasuredenergy to rely on forM&V (solid redbars in figure50).Since the system did not actually measure fixture power for reports, energy reportingaccuracy was entirely dependent on the load information entered during commissioning.However,detailedcommissioningof thecontrolled loadsduring setupwasnot in the scopeforthecontrolssetupandcommissioning.Itispossiblethatwithmoreattentiontothisdetailthe reported energy could be more accurate. This finding is not unique to the particularcontrolssystemdeployedforthisexperiment.Infact,itwasnotedthatthevariationsinwatt-hoursreportedforthefixturescorrespondedtovariationsinthemeasurementsandthatthatthe difference in the data seemed mostly due to scaling. A scaling factor derived from aregressionofthedatawasappliedto"adjust"thecontrolssystemdata,andthetotalenergyforthescaledcontrolsdatasetwaswithin0.03%ofmeasureddata(dashedredbarsinfigure50).

Figure50. Comparisonoflightingenergyfromcontrolsystemthatcalculateslightingenergyvs.

lightingenergymeasuredbyFLEXLABinstrumentation.

Thekeyfindingisthatifthecontrolsystemisnotmeasuringactuallightingenergy,itshouldbecarefullycommissioned,calibratedandcomparedtoactualmeasuredvaluestoensurethatthecalculatedvaluesarewithintheboundsofdesiredaccuracyforM&Vorotherpurposes.

6.3.2 Measurementperiod

As noted earlier, due to significant seasonal variations in savings, it is important to havemeasurementscoverarangeofseasonalconditions.WeanalyzedFLEXLABdatatodetermine

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

2-De

c3-De

c4-De

c5-De

c6-De

c7-De

c8-De

c9-De

c10-Dec

11-Dec

12-Dec

13-Dec

14-Dec

15-Dec

16-Dec

17-Dec

18-Dec

19-Dec

20-Dec

21-Dec

22-Dec

23-Dec

24-Dec

25-Dec

26-Dec

27-Dec

28-Dec

29-Dec

30-Dec

31-Dec

DailyLigh*

ngW

a--Hou

rs

FLEXLABdata ControlsSystemData AdjustedControlsSystemData

Page 51: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

51

howerroranduncertaintyinsavingswouldincreasewithlessdata.Inparticular,welookedattwoeffects:lessrangeofseasonalvariationandfewerdayswithineachseason.

We used configuration 1S for this analysis. Figure 51 shows the savings results using fewerdayspermonth,foratotalof15days,comparedtothe20daysinthefulldataset.Figure52showsthesavings results ifonewere tousedata from just thesummermonths. (Seeagainfigure 29 to compare to savings results from full data set.) Table 10 summarizes thedifferences, which are largely as expected. Reducing the number of days increases theuncertainty range from +/- 6% to +/-7%. Limiting measurements to one season (summer)significantlychangesthesavingsestimates.Theseasonalvariationinsavingsclearlyshowstheneedforsummerandwintermeasurements.

Figure51. Annuallightingsavingsforconfiguration1SusingOaklandTMYdata,usingsubset

ofdata(3dayspermonth)forregressionmodel.

Figure52. Annuallightingsavingsforconfiguration1SusingOaklandTMYdata,usingonly

summermonthdataforregressionmodel.

Page 52: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

52

Table10. Impactofmeasurementperiodonannualsavingsforconfiguration1SusingOaklandTMYdata

Case Savings estimate Uncertainty range Full dataset (20 days over 5 months) 22% +/-6% Less days per month (15 days over 5 months) 21% +/-7% Summer months only 33% +/-23%

7 SavingsPersistence

AnLBNLstudy(Hoffmanetal.2015)explainsefficiencymeasurelifetimeasafunctionoftheequipment lifetime(theaverageyearstheequipmentwilloperate)andthemeasuresavingspersistence: "the time that an energy-consumingmeasure actually lasts taking into accountbusinessturnover,earlyretirementofinstalledequipment,andotherreasonsthatmeasuresmight be removed, damaged or discontinued". Savings persistence from a measure likeadvanced lighting controls could include changes in expected energy usage resulting fromchanges in operating hours, space configurations, and user interactions with the system(controlsoverridesforexample).

Theauthorsidentifysavingspersistenceasanissueforefficiencymeasuresthatamongotherthings, have significant behavioral or operational variability over time and in differentapplications, and represent very different technologies from the baseline or standardmeasures they replace. Both issues are applicable to advanced lighting controls measures,whichrepresentasignificantchangefrombasicwallswitchesandlightingschedules,andaredeployed for particular populations and space configurations thatmay change over time. Ifthe user group (for whom the controls system is commissioned) changes, lighting controlsoperationsmay not be appropriate for the next occupants,which can lead to deactivation,overrides, ormisapplication of the controls from an energy savings standpoint. It has beenpointedoutbyefficiencyexperts thatutilityexperiencewith lighting controlsmeasureshasnot always been positive, with instances of poor persistence and unreliable energy savings(not designed, installed, commissioned properly, not used properly by building operators,difficultieswithreconfiguring)(DOE2015).

However,akeystrengthofadvanced,networkedandcentrallymanagedlightingcontrols,aswell as fixtureswith embeddedprogrammable sensors and controls, is the flexibility of thesystems to reconfiguration and recommissioning to adapt to new users and spaceconfigurations. Lighting system zoning through programmable interface, or remote control,allows advanced lighting controls to adapt to changes more easily than legacy hard-wiredsystems,whichshouldimprovemeasurepersistence.

Keytorealizingthisbenefitwillbeoperatorfamiliarity, facility,andengagementwithuseofthe lighting controls hardware and interfaces so that changes can easily be effected whennecessary, allowing the controls to provide expected service (and energy savings) for theiruseful lifetime.Often the commissioning agent that sets the system up initially is a vendoremployeeortechnician,withalltheknowledgeandfamiliarityofinteractingwiththesystemcontrols.Thetransferoftheknowledgeandskillstofacilitypersonneliscriticalifthefacilityis

Page 53: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

53

going to take ownership of controls operation and keep them operating in line withexpectationsanduserdesiresgoingforward.

Examplesofspacereconfigurationimpactsonlightingcontrolsoperation:

• Dimmablelightingsystemsaretypically"tuned"fromfulloutputdowntoalowerlevelthatresultsinthedesiredaveragelightlevelatthetaskplane.Thistunedvalueneedstobecustomizedforgivenspacesandadjustedwhenspaceschange,topreventover-lightingorunder-lightingspaces.

• Reconfigurationofspaceandofficepopulationscan impact lightingcontrolsdaylightdimmingfunction,whichisnormallycommissionedatinstallationbyturningthelightson in a given space, in the absence of daylight. The resulting controls photosensorreading isthenusedastheset-pointthatthesystemcontrolstofromthatpointon.Duringthiscommissioningprocess,thedaylightsensor"sees"theintendedlightlevel,basedonelectriclightingsystemdesignforthatspaceasconfiguredatthattime.Thelights then dim in proportion to any "extra" light sensed by the photosensorthroughouttheday,ataresponserateandsensitivityprogrammedintothecontrolssystemlogic. Issuesarise ifthespace isreconfigured-desksmoved,fixturesmoved,partitions addedor subtracted. If the lighting system is not re-commissioned, itwillcontinue to control to a set-point that may no longer reflect intended light levels,whichcouldimpactsavingspersistence.

• Occupancy sensors: savings persistence can be impacted by occupancy sensoroperation as well due to space configuration changes. Lighting controls systemstypicallyzoneseveralfixturestooneoccupancysensor.Ifthespaceisreconfiguredintheareaofthesensor, itmayendupcontrollingfixturesnolongerin logicalgroups,either leaving unoccupied areas lit or occupied areas dark. A major benefit of theintegrated sensors and controls approach is that fixtures and space can bereconfigured without necessarily detrimentally affecting lighting controls operation;eachfixturecanactautonomouslybasedontheoccupancyinitsownzone.

Wehavetwokeyrecommendationstoimprovesavingspersistence:

1. Rigorous formalized training requirement during acquisition and installation of lightingcontrolssystem,sothatthefacilitydevelopstheinstitutionalknowledgeandskillstonotonlyoperatethenewcontrolsascommissioned,buttoperiodicallyverifysystemoperationandre-commissionasspacesanduserschangethroughtime.

2.Periodic(annualorbi-annual)lightingcontrolsreview:

• Measurement of light levels in representative locations within lighting zones;recommissioning of "tuned" setting and daylight dimming setpoint if out of desiredrange;

• Checkoperationoflights,switchesandsensors;

• Solicitoccupantfeedbackonlightingoperation,concerns;

• Checkzoningofoccupancysensorstoensurethatlogicalgroupsoffixturesrespondtotherightsensorsinaspace,andre-zoningofoccupancysensorsifnecessary.

Refer to Appendix C for a verification checklist process that can be periodically applied toensurethatlightlevelsandcontrolsoperationaresettodesiredlevels.

Page 54: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

54

8 References

DOE2015.LightingSystemOptimization:LeveragingtheNewTechnologyParadigm.DOESSLTechnologyDevelopmentWorkshop.November17,2015

Hoffman,I.M.,S.Schiller,A.Todd,M.A.Billingsley,C.A.Goldman,L.C.Schwartz.2015.EnergySavings Lifetimes and Persistence: Practices, Issues and Data. Lawrence Berkeley NationalLaboratory.Technicalreport.May2015.

Lee,E.S.,L.L.Fernandes,B.Coffey,A.McNeil,R.Clear,T.Webster,F.Bauman,D.Dickerhoff,D. Heinzerling, T. Hoyt. 2013. A Post-Occupancy Monitored Evaluation of the DimmableLighting,AutomatedShading,andUnderfloorAirDistributionSysteminTheNewYorkTimesBuilding.TechnicalReport.LawrenceBerkeleyNationalLaboratory.LBNL-6023E

Wienold J. 2009. Dynamic daylight glare evaluation, Building Simulation 2009, 11thInternationalIBPSAConference,Glasgow,Scotland,July27-30,2009.

Wienold J, J. Christoffersen. 2006. Evaluation methods and development of a new glareprediction model for daylight environments with the use of CCD cameras, Energy andBuildings38(7):743-757,2006.

Williams,A.,B.Atkinson,K.Garbesi, F.Rubinstein.2011.AMeta-Analysisof EnergySavingsfromLightingControlsinCommercialBuildings.Technicalreport.LawrenceBerkeleyNationalLaboratory.LBNL-5095E.

Page 55: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

AppendixA:MarketSegmentationAnalysis

The followingexcerpt includes theexecutive summaryof themarket segmentation report.The fullreportisavailableontheprojectwebsite:https://cbs.lbl.gov/beyond-widgets-for-utilities

Page 56: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

“BEYOND WIDGETS” SYSTEMS ENERGY EFFICIENCY – MARKET SEGMENTATION

Potential for Adoption of System-Based Utility Energy Efficiency Programs Lawrence Berkeley National Laboratory

Date: November 25, 2015

Document No.:

Page 57: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

DNV GL - Energy – www.dnvgl.com/energy

Copyright © 2015, DNV GL (KEMA, Inc.)

This document, and the information contained herein, is the exclusive, confidential and proprietary property of DNV GL and is protected under the trade secret and copyright laws of the United States and other international laws, treaties and conventions. No part of this work may be disclosed to any third party or used, reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage or retrieval system, without first receiving the express written permission of DNV GL. Except as otherwise noted, all trademarks appearing herein are proprietary to DNV GL.

Page 58: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

DNV GL – www.dnvgl.com November 25, 2015 Page i

Table of contents

1 EXECUTIVE SUMMARY .................................................................................................... 11.1 Study Approach 11.2 Key Findings 21.3 Conclusions 5

2 INTRODUCTION ............................................................................................................ 62.1 Background and Objectives 62.2 Study Approach 6

3 METHODS AND ASSUMPTIONS ........................................................................................ 83.1 Market Segmentation 83.1.1 Criteria for Market Segmentation 83.1.2 Data Sources for Market Segmentation 93.1.3 Developing Square Footage and Consumption by Sub-Segment 103.2 Estimating the Technical, Economic, and Achievable Potential 113.2.1 Technical Potential 123.2.2 Economic Potential 133.2.3 Achievable Potential 143.3 Interviews with Subject Matter Experts 153.3.1 Sample 163.3.2 Analysis 17

4 FINDINGS ................................................................................................................... 184.1 Estimated Market Size 184.1.1 Technical Potential 184.1.2 Economic Potential 204.2 System Achievable Potential 234.2.1 Adoption Curves 244.3 Energy Savings Achievable Potential 244.3.1 RET 254.3.2 ROB 294.4 Market Perspectives 314.4.1 Awareness 314.4.2 Penetration 314.4.3 Barriers 324.4.4 Opportunities 33

5 CONCLUSIONS AND RECOMMENDATIONS ....................................................................... 35

SYSTEM DETAILED DESCRIPTIONS ...................................................................... A-1APPENDIX A.

LISTING OF INTERVIEW PARTICIPANTS ................................................................ B-1APPENDIX B.

MARKET ACTOR INTERVIEW GUIDE ..................................................................... C-2APPENDIX C.

SYSTEM ASSUMPTIONS USED IN THIS STUDY ....................................................... D-1APPENDIX D.

TECHNICAL POTENTIAL SUB-SEGMENTS ............................................................... E-1APPENDIX E.

ECONOMIC POTENTIAL SUB-SEGMENTS ................................................................ F-4APPENDIX F.

Page 59: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

DNV GL – www.dnvgl.com November 25, 2015 Page ii

ACHIEVABLE POTENTIAL KWH (PACKAGE 2) ......................................................... G-5APPENDIX G.

ACHIEVABLE POTENTIAL KW (PACKAGE 2) ............................................................ H-8APPENDIX H.

ACHIEVABLE POTENTIAL (COMED & XCEL MN) ....................................................... I-1APPENDIX I.

List of figures Figure 1. Relationship between economic, technical, and adoption potential ........................................... 12Figure 2. Technical potential estimation equation ................................................................................ 12Figure 3. Achievable potential overview ............................................................................................. 15Figure 4: Technical potential in kWh ................................................................................................. 19Figure 5: Technical potential in kW ................................................................................................... 19Figure 6: Economic potential kWh (RET) ............................................................................................ 22Figure 7: Economic potential kWh (ROB) ........................................................................................... 23Figure 8: Northern California office RET lower and upper achievable kWh ............................................... 26Figure 9: Southern California office RET lower and upper achievable kWh .............................................. 26Figure 10: Adoption curves for Northern California (kWh RET) .............................................................. 27Figure 11: Adoption curves for Southern California (kWh RET) ............................................................. 27Figure 12: Xcel Colorado office RET lower and upper achievable kWh .................................................... 28Figure 13:Xcel Colorado adoption curves (kWh RET) ........................................................................... 28Figure 14: Northern California office ROB lower and upper achievable kWh ............................................ 29Figure 15: Southern California office ROB lower and upper achievable kWh ............................................ 30Figure 16: Xcel office ROB lower and upper achievable kWh ................................................................. 30Figure 17. Lighting energy use savings in the New York Times headquarters building (Lee et al. 2013) .. A-13Figure 18. Typical recessed 2’x4’ fluorescent luminaire layout (8’x8’) ................................................ A-19Figure 19. Average energy savings (%) by control strategy (Williams, et al. 2012) .............................. A-20Figure 20. Lighting energy use savings in the New York Times headquarters building (Lee, et al. 2013) . A-20Figure 21: Northern California adoption curve kWh (ROB) .................................................................. G-6Figure 22: Southern California adoption curve kWh (ROB) ................................................................. G-6Figure 23: Xcel Colorado adoption curve kWh (ROB) ......................................................................... G-7Figure 24: Economic Potential RET ................................................................................................... I-1Figure 25: Economic Potential ROB .................................................................................................. I-2

List of tables Table 1. Study targets ..................................................................................................................... 1Table 2: Technical potential (GWh savings) ......................................................................................... 3Table 3: TRC values (RET average) .................................................................................................... 3Table 4: TRC values (ROB average) ................................................................................................... 4Table 5: Economic Potential for RET (GWh savings) ............................................................................. 4Table 6: Economic Potential for ROB (GWh savings) ............................................................................. 4Table 7: Cumulative Adoption for RET (GWh savings at 10 years) .......................................................... 5Table 8: Cumulative Adoption for ROB (GWh savings at 10 years) ......................................................... 5Table 9. Study targets ..................................................................................................................... 6Table 10. Sequence of potential categories ........................................................................................ 12Table 11. Total Square Feet Physically Available by Segment ............................................................... 18Table 12: TRC values (RET average) ................................................................................................. 20Table 13: TRC values (ROB average) ................................................................................................ 21Table 14. Total Building Square Feet Available and Considered Cost Effective ......................................... 21Table 15. Cumulative achievable market penetration (upper bound) ...................................................... 24Table 16. Cumulative achievable market penetration (lower bound) ...................................................... 24Table 17. Technology packages that will be tested in FLEXLAB .......................................................... A-11Table 18. Energy savings from LBNL meta-analysis of lighting controls studies (Williams et al. 2011) .... A-13

Page 60: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

DNV GL – www.dnvgl.com November 25, 2015 Page iii

Table 19. DNV GL internal respondents ........................................................................................... B-1Table 20. External subject matter experts ....................................................................................... B-1Table 21: Technical potential for California POUs by sub-segment ....................................................... E-1Table 22: Technical potential for ComEd by sub-segment .................................................................. E-2Table 23: Technical Potential for Xcel Colorado sub-segments ............................................................ E-2Table 24: Technical potential for Xcel Minnesota by sub-segment ....................................................... E-3Table 25: Economic potential for California POUs by sub-segment ....................................................... F-4Table 26: Economic potential for Xcel Colorado by sub-segment ......................................................... F-4Table 27: California POU achievable kWh (Package 2) ....................................................................... G-5Table 28: Xcel Colorado achievable kWh (Package 2) ........................................................................ G-7Table 29: California POU achievable kW (Package 2) ......................................................................... H-8Table 30: Xcel Colorado kW achievable potential .............................................................................. H-9Table 31: Cumulative Adoption for RET (GWh savings at 10 years) ...................................................... I-2Table 32: Cumulative Adoption for ROB (GWh savings at 10 years) ...................................................... I-2

Page 61: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

DNV GL – www.dnvgl.com November 25, 2015 Page 1

1 EXECUTIVE SUMMARY This report presents findings from research commissioned by Lawrence Berkeley National Laboratory (LBNL) to identify energy savings potential for systems based energy efficiency in individual market segments (e.g., offices) and sub-segments (e.g., large offices owned by the tenant).

Conducted by DNV GL, this study is part of a larger “Getting beyond Widgets” research project aimed at identifying the most appropriate methods to promote systems-based energy savings in US commercial buildings via utility incentive programs.

1.1 Study Approach LBNL worked with three utility partners to define the systems for this study and the best building types (i.e., market segments) applicable to these systems. The systems and segments are shown in Table 1.

Table 1. Study targets

Utility Partner Segment System Packages

California Publicly Owned Utilities throughout the state (CA POUs)

Offices

Package 1. Plug-and-play overhead lighting and automated plug load control system Package 2. Overhead lighting and / or networked controls change out and automated plug load control system

Commonwealth Edison in Illinois (ComEd)

Offices and Schools

Package 1. Automated shading (roller) with integrated lighting controls

Xcel Energy in Minnesota and Colorado (Xcel)

Offices

Package 1. Zonal HVAC controls with integrated zone-level daylighting and lighting controls Package 2. Integrated, enterprise-level networked lighting controls, daylight redirecting film, and HVAC controls

Once the systems and primary market segments were defined, DNV GL further segmented the market into sub-segments using data from the utility partners and CoreLogic, a commercial real estate database. We then estimated the technical, economic, and achievable potential for each system within the chosen market segments using both replace on burnout (ROB) and retrofit (RET) applications. We conducted expert interviews to obtain a greater understanding of the target markets and to refine the estimates of achievable market potential.

Technical potential refers to the complete penetration of lighting systems in all segments deemed technically feasible from an engineering perspective.

Economic potential is that portion of the technical potential that the utility considers cost-effective when compared to supply-side alternatives.

Achievable potential is the portion of economic potential that can realistically be achieved based on customers’ likelihood to adopt the systems in response to specific marketing approaches and incentive levels.

Page 62: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

DNV GL – www.dnvgl.com November 25, 2015 Page 2

Based on this research and analysis, we identified the market segments that provide the greatest potential for cost-effective energy savings from the selected energy-efficient systems. See Section 2.2 for a more comprehensive discussion of the study approach.

1.2 Key Findings The most notable findings of this study include the following:

§ Systems tend to be cost-effective from the utility Total Resource Cost (TRC => 1.0) perspective for office building applications for the Northern and Southern California POUs and in larger office buildings for Xcel Colorado. These systems (as defined for this study) are not cost effective for Xcel Minnesota. For ComEd, these systems are cost-effective, but only for specific sub-segments and only when evaluated using incremental system costs.

§ The differences in cost-effectiveness, and thus economic potential, are due more to levels of utility avoided costs1 rather than the system costs or their savings on a per square foot basis. For example, the avoided cost stream average was $0.22 per kWh in California and $0.15 per kWh for Xcel Colorado. ComEd in Illinois and Xcel Minnesota were much lower with an average of $0.04 per kWh.

§ From the customer perspective, the simple payback for these systems (depending on application and location) ranged from approximately 7 years to 35 years in the retrofit scenario and 6 years to 22 years in the replace-on-burnout scenario.

o Some of this difference is due to the wide variation in customer energy rates. Over the analysis period of 20 years, commercial rates in California average approximately $0.20 per kWh2. For ComEd in Illinois, rates in the analysis averaged $0.10 per kWh. Xcel CO and MN have average rates of about $0.09 per kWh.

§ DNV GL interviews of subject matter experts found sufficient general market awareness of these systems but their benefits in terms of energy savings and operational efficiency improvement are not well understood by facility managers and building owners. Since benefits in terms of energy savings, maintenance and operations savings, and building operational control are key drivers of adoption; a lack of knowledge in these areas implies that adoption will be slower than that of well-understood widget equipment.

§ The adoption decisions and installation of these systems are much more involved and disruptive to building tenants than typical widget replacement projects. As a result, experts interviewed for this study asserted that, given the longer paybacks of these systems and with no program intervention, only 13% to 20% of the market would adopt these over the next 10 years. This is comparable to market studies, in the northeast for example, that estimated approximately 13% adoption of high efficiency LED lighting and controls over 10 years.3

§ Shorter payback times, through market cost reductions or utility intervention saturation may range between 24% and 43% over 10 years.

The total technical potential of energy savings for each utility partner in GWh is in Table 2.

1 Avoided costs are the proxy used to reflect the benefits to the utility. In this study, they refer to eliminating, or significantly delaying utility

expenditures for infrastructure upgrades and fuel costs due to a reduction of energy consumption by customers. 2 California electric retail rates for POUs reflect California Energy Commission forecast averages. Avoided costs reflect costs developed for California

Investor Owned Utilities. 3 The analysis does not include any potential changes in building codes for future years.

Page 63: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

DNV GL – www.dnvgl.com November 25, 2015 Page 3

Table 2: Technical potential (GWh savings)

Utility Partner Package 1 – low

Package 1 - high

Package 2 - low

Package 2 - high

Northern California 412 752 833 883 Southern California 479 876 1,028 1,028

ComEd 519 633 NA4 NA Xcel Colorado 370 370 743 908

Xcel Minnesota 148 148 296 962

Values are the same for packages with the same energy reduction values. There may be package differences however due to system cost, demand reduction or both.

In both the RET and ROB scenarios economic potential is from the perspective of the utility and is considered cost-effective if the TRC ratio is greater than or equal to 1.0. In service areas with TRC threshold requirements at the resource program portfolio level (rather than equipment level) a low TRC, by itself, does not preclude inclusion into the utility EE portfolio. Similarly, the utility may offer a program to “jump start” market adoption with a goal of transforming how integrated systems are marketed and priced. For these instances, exceeding a TRC threshold may not be necessary. For the most part TRC values remain the prime criterion for by which regulators judge utility programs. The TRC values for determining the economic potential of systems in RET and ROB applications are reported in Table 3 and Table 4.

Table 3: TRC values (RET average)

Utility Partner Package 1 – low

Package 1 - high

Package 2 - low

Package 2 - high

Northern California 1.13 1.04 1.19 1.98

Southern California 1.23 1.11 1.28 2.17 ComEd 0.25 0.28 NA NA

Xcel Colorado 1.10 0.80 1.09 0.68 Xcel Minnesota 0.37 0.28 0.36 0.24

For retrofit scenarios, the calculation uses the full cost of the integrated system equipment. RET uses full cost because the customer’s equipment is working. Cost of the system is the difference between installing the system and leaving the existing system as is.

For replace on burn out scenarios the TRC are higher because the equipment cost used in the test lower. ROB uses an incremental cost. Since the customer must take some action to replace failed equipment the ROB cost is the difference between the cost of an integrated system and the cost of widget based equipment.

4 No package 2 was specified for ComEd.

Page 64: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

DNV GL – www.dnvgl.com November 25, 2015 Page 4

Table 4: TRC values (ROB average)

Utility Partner Package 1 – low

Package 1 - high

Package 2 - low

Package 2 - high

Northern California 1.35 1.42 1.32 2.38 Southern California 1.48 1.54 1.43 2.63

ComEd 0.44 0.52 NA NA Xcel Colorado 1.59 1.15 1.26 0.79

Xcel Minnesota 0.54 0.40 0.42 0.27

The total economic potential of energy savings (as filtered by a TRC ≥ 1.0) for each utility partner is presented in Table 5 (RET) and Table 6 (ROB).

Table 5: Economic Potential for RET (GWh savings)

Utility Partner Package 1 – low

Package 1 - high

Package 2 - low

Package 2 - high

Northern California 412 752 883 883 Southern California 479 876 1,028 1,028

ComEd 0 0 NA NA Xcel Colorado 0 370 0 908

Xcel Minnesota 0 0 0 0

Economic potential of zero in these tables means that as defined, these lighting systems are not cost-effective from a utility program perspective. The technical potential to install them still exists, but utilities need to use other criteria to justify including them in an energy efficiency portfolio. See appendix I for a discussion of these programs.

Table 6: Economic Potential for ROB (GWh savings)

Utility Partner Package 1 – low

Package 1 - high

Package 2 - low

Package 2 - high

Northern California 412 752 883 883 Southern California 479 876 1,028 1,028

ComEd 0 0 NA NA Xcel Colorado 370 370 0 908

Xcel Minnesota 0 0 0 0

Note: (lower bound / upper bound)

An estimate of program savings can be derived once economic potential is calculated. The lower and upper bound forecast of adoption potential for the RET and ROB scenarios are presented in Table 7 and Table 8. These tables represent the minimum estimated level of savings achievable for a systems based utility programs over a 10-year period.

Page 65: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

DNV GL – www.dnvgl.com November 25, 2015 Page 5

Table 7: Cumulative Adoption for RET (GWh savings at 10 years)

Utility Partner Package 1 – low

Package 1 - high

Package 2 - low

Package 2 - high

Northern California 98/136 178/250 209/294 209/294 Southern California 113/159 207/291 244/342 244/342

ComEd 0/0 0/0 NA NA Xcel Colorado 0/0 88/123 0/0 215/302

Xcel Minnesota 0/0 0/0 0/0 0/0

Note: (lower bound / upper bound)

Table 8: Cumulative Adoption for ROB (GWh savings at 10 years)

Utility Partner Package 1 – low

Package 1 - high

Package 2 - low

Package 2 - high

Northern California 7/9 12/17 14/20 14/20

Southern California 8/11 14/19 16/23 16/23 ComEd 0/0 0/0 NA NA

Xcel Colorado 0/0 6/8 0/0 14/20 Xcel Minnesota 0/0 0/0 0/0 0/0

Note: (lower bound / upper bound)

A detailed discussion of study findings are in Chapter 4 of this report.

1.3 Conclusions The most notable conclusions of this study are:

§ Ample technical potential exists to deploy systems-based energy efficiency programs for lighting in commercial office buildings.

§ Applications also exist for schools and medical facilities, but factors such as utility cost-effectiveness and customer payback thresholds limit these opportunities.

§ Even though the components of these systems exist today and are “off-the-shelf”, combining them into a complete system is not common practice.

§ To increase uptake of the systems approach, utility programs should consider including an educational component to increase awareness among designers and contractors of lighting systems.

§ The system packages in this study had energy savings reduction estimates ranging from 9% to 33% and full systems costs ranging from $1.37 to $7.70 per square foot. The relationship between system costs and the utility benefit from system savings determines economic potential. Across service areas however, differences in utility benefits (due to avoided costs differentials) rather than differences in installed system costs or savings drove the economic potential.

Section 5 of this report provides a more complete discussion of study conclusions and recommendations.

Page 66: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

AppendixB:CandidateSiteSavingsEstimator

Thespreadsheetcanbedownloadedfrom:https://cbs.lbl.gov/beyond-widgets-for-utilities

Belowarescreenimagesofthemainpageandthesavingsfactorspage

AutomatedShadingandDaylightDimming-SiteSavingsEstimatorChicagoClimate

Usethisworksheettoestimatetherangeofwholebuildinglighting,HVACandsiteenergysavingsfromautomatedshadinganddimming.Thisestimatorisintendedtosupportsitescreening.ItisNOTintendedforincentivecalculationorM&V.Seenotesbelowforkeyassumptionsandlimitations.Seecellcommentsforadditionalguidance.

Inputcellsshadedblue

Step1:Calculateannuallightingenergysavings

OrientationImpactedArea(sf)

Dimmingzone

LightingPowerDensity(W/sf)

Annual"occupiedmode"hours

LightingkWhImpactedbaseline

Lighting%savings(avg)

Lighting%savings(low)

Lighting%savings(high)

LightingkWhsavings(avg)

LightingkWhsavings(low)

LightingkWhsavings(high)

N 20,000 25'threerowsdim1.00 3120 62,400 49% 42% 58% 30,720 26,352 36,336NE - - 3120 - 0% 0% 0% - - -E 20,000 25'threerowsdim1.00 3120 62,400 44% 38% 51% 27,360 23,616 31,728SE - - 3120 - 0% 0% 0% - - -S 20,000 25'threerowsdim1.00 3120 62,400 40% 32% 48% 24,960 19,968 29,952SW - - 3120 - 0% 0% 0% - - -W 20,000 25'threerowsdim1.00 3120 62,400 44% 38% 51% 27,360 23,616 31,728NW - - 3120 - 0% 0% 0% - - -Total 80,000 249,600 110,400 93,552 129,744

Step2:CalculateannualHVACenergysavings

Metric Average Low HighAnnuallightingenergysavings 110,400 93,552 129,744HVACelecfactor(kWhchange/kWhlightingsaved) 0.14 0.14 0.14HVACgasfactor(kWhchange/kWhlightingsaved) -0.3 -0.3 -0.3Annualelecenergysavings(kWh) 15,456 13,097 18,164Annualgasenergysavings(kWh) (33,120) (28,066) (38,923)

Step3:Calculateannualsiteenergysavings

Metric Average Low HighAnnualelectricityuse(kWh) 800,000 800,000 800,000Annualgasuse(kWh) 200,000 200,000 200,000Annualsiteenergy(kWh) 1,000,000 1,000,000 1,000,000Annualsiteenergysavings 92,736 78,584 108,985Siteenergysavings% 9.3% 7.9% 10.9%

Assumptionsandlimitations1.Seethe"Factors"tabforlightingandHVACsavingsfactorsandassumptions2.Lightingsavingsissolelyfromdimmingandincludesinstitutionaltuning.Tuningbaselineassumptionscanbemodifiedon"Factiors"tab.3.HVACsavingsarebasedonDOEprototypemodels.Besuretoreviewsystemtypeandassociatedfuelsourceassumptions4.SavingsfactorsareforChicagoclimate,usingTMYdata.5.Savingsfactorsforotherlocationsmaybecalculatedusingthemethodologydocumentedinthetechnicalreport.

Page 67: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

SavingsFactors-ChicagoClimate

Lightingsavingsfactors-withouttuningsavingsDataarebasedonFLEXLABmeasuredsavings

Avg Low High Avg Low HighN 31% 25% 39% 34% 27% 43%NE 28% 22% 35% 31% 24% 39%E 24% 19% 30% 27% 21% 34%SE 22% 16% 28% 25% 18% 32%S 19% 12% 26% 22% 14% 30%SW 22% 16% 28% 25% 18% 32%W 24% 19% 30% 27% 21% 34%NW 28% 22% 35% 31% 24% 39%

Lightingsavingsfactors-withtuningsavingsDataarederivedfromthesavingsfactorswithouttuning(above)andtuningbaselineassumption,whichcanbeadjusted.

Untunedbasline(as%oftunedbaseline) 130%

Avg Low High Avg Low HighN 47% 41% 55% 49% 42% 58%NE 44% 39% 51% 47% 40% 55%E 42% 37% 48% 44% 38% 51%SE 40% 34% 46% 42% 35% 49%S 38% 31% 45% 40% 32% 48%SW 40% 34% 46% 42% 35% 49%W 42% 37% 48% 44% 38% 51%NW 44% 39% 51% 47% 40% 55%

HVACfactorsDataarederivedfromEnergyplussimulationsoftheDOEprototypemodels

Electricity Gas

LargeOffice 0.14 -0.30MediumOffice 0.01 -0.13PrimarySchool 0.14 -0.04

SecondarySchool 0.20 -0.11

Packagedunitswithgasheating.Aircooledchillersandpackagedunitswithgasheating.

Orientation

Orientation

HVACenergyfactor(kWhchange/kWhlightingsaved)

BuildingPrototype

25'tworowsdim 25'threerowsdim

25'tworowsdim 25'threerowsdim

SystemTypeCentralelectricchillerandgasboiler.Hotwaterreheat.Packagedunitswithelectricreheat.

Page 68: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

AppendixC:InstallationVerificationChecklist

The following checklists document several of the important features of the workstationspecificlightingsystemtobeawareofandverifiedinordertohelpensuretheenergysavingslevels are realizedwith the system as expected. The following checklists are notmeant toreplaceacompletecommissioningsetofchecklists(e.g.Pre-functionalandfunctionaltests).

SpotMeasurementVerification

Testingconductedatnight,withminimalexteriorlightpenetration.

Lightmeterusedforspotmeasurementverification

Manufacturer:

ModelNo.:

Accuracy:

LastCalibrationDate(attachcertificate):

RoomNo. LightFixtureInstallation LightOutput(lux)withSettingto100%ON

LightOutput(lux)withSettingto100%OFF

QtyandType

Expected

Observed Expected(Lux)(e.g.

300,500luxatworkplane)

Measured(Lux)

Expected(Lux)(e.g.

0lux)

Measured(Lux)

Addrowsasnecessarytoprovideanadequatesamplingthroughouttheinstallation.

Page 69: ComEd-LBNL System Program Manual 9-26-17 · 26/09/2017  · ComEd considered a list of several systems and selected automated shading integrated with lighting and HVAC controls. Daylight-based

TrendAnalysisVerification

Trendthelightingpoweroverthecourseofseveraldaysandverifythatthedimmingprofileisasexpectedforeachrowoffixtures.Forexample,therowclosesttothewindowwoulddimmorethanrowsfurtherfromthewindow.

Trenddatasourceusedforverification

Softwaresource:

Trenddatafilenames:

Trenddates:

RoomNo. TrendDates

Performance Notes

Expected Observed

Addrowsasnecessarytoprovideanadequatesamplingthroughouttheinstallation.