Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine...

11

Transcript of Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine...

Page 1: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,
mfalcon
Image
mfalcon
Arrow
mfalcon
Text Box
Columbine Hall - Third Floor Classrooms AV Upgrade
mfalcon
Text Box
1420 Austin Bluffs Parkway, Colorado Springs, CO 80918
mfalcon
Text Box
Vicinity Map
Page 2: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,
Page 3: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,
Page 4: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,

COMPONENT

ENTITYNOTES APPLY

TO ALL ENTITIESFURNISH INSTALL

COMMON WORK

CONDUIT SLEEVES EC EC 1

PENETRATION GC GC 5,7

HANGER SUPPORTS FOR CONDUITS EC EC 1

HANGER SUPPORTS FOR CABLE SUPPORTS TC TC 2

WIDE BASE CABLE SUPPORTS (J-HOOKS) TC TC 2

STRAPS/SLINGS TC TC 2

ELECTRICAL FOR COMMUNICATIONS SYSTEMS

CONDUIT, FITTINGS, PULL STRINGS EC EC 1

JUNCTION BOXES EC EC 1

DEVICE BOXES EC EC 1

PULL BOXES EC EC 1

TABLE-TOP INTERFACE (ROUGH IN) AVC AVC 4

TABLE-TOP INTERFACE (DEVICE) AVC AVC

TELECOMMUNICATIONS (COMMUNICATIONS CABLING SYSTEM) TC TC

AUDIOVISUAL SYSTEM(S)

LOUDSPEAKERS AVC AVC

HANGER WIRE SUPPORTS FOR LOUDSPEAKERS WITHIN LAYING CEILINGS AVC AVC

MICROPHONES AVC AVC

EQUIPMENT RACKS AVC AVC

ANTENNA AVC AVC

PROJECTION SCREEN AVC AVC

INTERFACE PLATES AVC AVC

PROJECTORS AVC AVC

CAMERAS AVC AVC

PODIUM AVC AVC

VOLUME CONTROL AVC AVC

CONTROL PANEL AVC AVC

SCREEN SWITCH AVC AVC

STRUCTURAL SUPPORTS FOR AV EQUIPMENT GC GC 9

GENERAL NOTES

A. COMPONENTS, ENTITY, AND FURNISH AND INSTALL RESPONSIBILITIES INDICATED ARE RECOMMENDATIONS ONLY AND PROVIDED ASA COURTESY TO CONTRACTOR.

B. SOME COMPONENTS AND ASSOCIATED FURNISH AND INSTALL RESPONSIBILITIES MAY NOT BE INDICATED ON THIS MATRIX.

C. THE DETAIL FURNISH / INSTALL CALLOUT ANNOTATION PROVIDES SPECIFIC RECOMMENDATIONS THAT SUPERSEDE GENERALRECOMMENDATIONS FOUND IN THE TECHNOLOGY RESPONSIBILITY MATRIX.

D. EQUIPMENT SCHEDULES MAY CONTAIN ADDITIONAL FURNISH OR INSTALL RESPONSIBILITY RECOMMENDATIONS. THESE SUPERSEDERECOMMENDATIONS FOUND IN DETAIL ANNOTATIONS AND THE TECHNOLOGY RESPONSIBILITY MATRIX.

E. CONTRACTOR IS RESPONSIBLE FOR FINAL DETERMINATION OF ALL COMPONENTS AND ASSOCIATED FURNISH AND INSTALLRESPONSIBILITIES REQUIRED FOR PROVISION OF COMPLETE TECHNOLOGY SYSTEMS READY FOR OWNER'S USE. DETERMINATIONOF SUCH SHALL OCCUR PRIOR TO BID.

F. DETERMINATION AND EXECUTION OF ALL NECESSARY COMPONENTS AND ASSOCIATED FURNISH AND INSTALL RESPONSIBILITIESSHALL CONFORM TO PROJECT SCHEDULE.

G. CABLING FOR COMPONENTS SHALL BE PROVIDED BY ENTITY INSTALLING COMPONENT UNLESS OTHERWISE INDICATED.

H. EACH TRADE SHALL COORDINATE ROUGH-IN REQUIREMENTS (INCLUDING SLEEVES) WITH ELECTRICAL CONTRACTOR PRIOR TOROUGH-IN.

I. DEVICES AND HORIZONTAL CABLING OF DEVICES (INCLUDING CABLE TERMINATIONS) WITHIN ASSEMBLIES (FLOOR BOXES,POKE-THROUGHS, TABLE TOP INTERFACES, WALL BOXES, FURNITURE FEEDS, UTILITY POLES, SURFACE RACEWAYS, ETC.) SHALL BEBY RESPECTIVE TRADES.

MATRIX NOTES

1. EACH RESPECTIVE TRADE SHALL COORDINATE EXTENT OF WORK WITH ELECTRICAL CONTRACTOR PRIOR TO ROUGH IN.

2. EACH TRADE SHALL COORDINATE PROVISION OF THIS COMPONENT WITH TELECOMMUNICATIONS CONTRACTOR.TELECOMMUNICATIONS CONTRACTOR SHALL PROVIDE THIS COMPONENT UNLESS DETERMINED OTHERWISE IN CONJUNCTION WITHTELECOMMUNICATIONS CONTRACTOR.

4. FURNISHING CONTRACTOR TO PROVIDE ROUGH IN DIMENSIONS / TEMPLATE AND DESIRED LOCATION FOR TABLE TOP INTERFACE.INSTALLING CONTRACTOR SHALL CUT-OUT SURFACE OF TABLE, IDENTIFYING AND COORDINATING ANY POTENTIAL CONFLICTS WITHDESIRED LOCATION PRIOR TO PERFORMING ANY WORK.

5. EACH TRADE SHALL COORDINATE PROVISION OF THIS COMPONENT WITH GENERAL CONTRACTOR. GENERAL CONTRACTOR SHALLPROVIDE THIS COMPONENT UNLESS DETERMINED OTHERWISE IN CONJUNCTION WITH GENERAL CONTRACTOR.

7. ELECTRICAL CONTRACTOR SHALL COORDINATE EXTENT OF WORK WITH GENERAL CONTRACTOR.

9. AUDIOVISUAL CONTRACTOR SHALL COORDINATE EXTENT OF WORK WITH GENERAL CONTRACTOR.

TITLESHEET#

SHEET LISTSHEET LIST

*

KEYNOTE

DRAWING NOTE

EQUIPMENT SCHEDULE ID

REVISION NUMBER

SECTION OR ELEVATION CALLOUT

DESCRIPTIONSYMBOL

OR (XX###)

#REFERENCE INDICATORREFERENCE SHEET NUMBER

ENLARGED FLOOR PLAN, SCHEDULE, OR DETAIL CALLOUT

*#

REFERENCE INDICATORREFERENCE SHEET NUMBER

ROOM WALL ELEVATION CALLOUT

A,B,C,D#

WALL ELEVATION REFERENCEREFERENCE SHEET NUMBER

BREAK LINE

DETAIL FURNISH / INSTALL CALLOUT (ON DETAILS WHERE CALLOUTSARE USED, ASSUME EC FOR X AND Y WHERE NOT INDICATED FORCOMPONENTS) UON IN TECHNOLOGY RESPONSIBILITY MATRIX)

X INDICATES ENTITY (ABBREVIATED) RIMROCK RECOMMENDS BE RESPONSIBLE FOR FURNISHING

Y INDICATES ENTITY (ABBREVIATED) RIMROCK RECOMMENDS BE RESPONSIBLE FOR INSTALLING

X Y

CONTINUANCE LINE

TELECOM AREA BOUNDARY LINE

TELECOM ROOM BOUNDARY LINE

XY

TYPICAL WALL MOUNTED DEVICE NOTATION. EXAMPLE:

CEILING-MOUNTED SPEAKER

WALL-MOUNTED SPEAKER

TYPICAL STATION CALLOUT

X INDICATES NUMBER OF VOICE/DATA PORTS/CABLES

Y INDICATES NUMBER OF COAX PORTS/CABLES (ASSUME 0 IF BLANK)

TYPICAL POLE OR BOOM MOUNTED DEVICE NOTATION. EXAMPLE:

WALL-MOUNTED SECURITY CAMERA

POLE-MOUNTED SECURITY CAMERA

+H

TYPICAL DEVICE OR EQUIPMENT NON-STANDARD HEIGHT(TELECOM OUTLET EXAMPLE SHOWN)

H INDICATES DIMENSION OF DEVICE OR EQUIPMENT CENTERLINE (UON) ABOVE FINISHED FLOOR

IF

TYPICAL ASSEMBLY NOTATION, INCLUDES:

- INFRASTRUCTURE: FLOOR BOX, POKE-THRU, WALL BOX, SURFACE RACEWAY, ENCLOSURE, HOUSING, RACK, ETC.

- SERVICES: DEVICES AND/OR CABLING AS SHOWN ASSOCIATED WITH INFRASTRUCTURE.

(FLOORBOX WITH INTERFACE PLATE AND TELECOM OUTLET EXAMPLE SHOWN).

2

A

X

WALL

SYMBOL/DEVICE CONGESTION NOTATION INCLUDES:

LEADER INDICATOR: USED TO IDENTIFY INTENDED LOCATION OF SYMBOL(S) THAT WOULD OTHERWISE OVERLAP OR CREATE CONGESTION WITH OTHER SYMBOLOGY.

TARGET INDICATOR: USED TO IDENTIFY INTENDED LOCATION OF LEADER ARROWHEAD TERMINATION THAT WOULD OTHERWISE OVERLAP OR CREATE CONGESTION WITH OTHER SYMBOLOGY.

CONGESTION INDICATOR: USED TO IDENTIFY ARRANGEMENT OF CONGESTED DEVICES.

X INDICATES CONGESTION TYPE: H HORIZONTAL V VERTICAL (ALONG SAME STUD OR STUD CAVITY) B BOTH HORIZONTAL AND VERTICAL -- SINGLE ITEM (NOT ALIGNED)

2

A

X

FUTURE EQUIPMENT, RACK, OR ENCLOSURE OUTLINE

#

XX##

XX###

#

OR #

*

#

A

B

C

D #

* #

DRAWING ANNOTATIONS

S

A

A

S

SYMBOL

SYMBOL

DESCRIPTIONDESCRIPTIONSYMBOL SYMBOL

STRUCTURAL BLOCKOUT

CABLE PATHWAY FIRESTOPPING DEVICE

FIRE-RATED FLOOR PENETRATION ASSEMBLY

CABLE SUPPORT PATHWAY(J-HOOKS / STRAPS / SLINGS)

GROUNDING BUSBAR

GROUND

WxH

CS

CONDUIT UNDERGROUND / FLOOR / SLAB

CONDUIT WITH BUSHING

CONDUIT WITH CAP

CONDUIT DOWN

CONDUIT / CABLE HOME RUN

PULL BOXP

DEVICE BOX EMPTY (CEILING)

FLOOR BOX

POKE THRU

U UTILITY POLE

ENCLOSURE

WALL BOX

CABLE TRAY

SURFACE RACEWAYSR

MAINTENANCE HOLE

OSP UNDERGROUND DUCTBANKOSP

DEVICE BOX EMPTY

CT

DESCRIPTIONSYMBOL

CABLE RUNWAY

CABLE - END LOOP

CABLE - CONTINUOUS LOOP

TELECOM OUTLET

TELECOM OUTLET (CEILING)

CR

AUDIOVISUAL EQUIPMENT LOCATION

A LOUDSPEAKER

FIXED CAMERA

VIDEO DISPLAY

PROJECTION SCREEN

INTERFACE PLATE

PROJECTOR

A

A

IF

LECTERN

PAN - TILT - ZOOM CAMERA

A AUDIOVISUAL DEVICE

AUDIOVISUAL CEILING DEVICE

AUDIOVISUAL FIELD LOCATED DEVICE

A

A

NOT ALL ITEMS LISTED IN THIS LEGEND ARE USED ON TECHNOLOGY DRAWINGS.

SUBSCRIPTS ADJACENT SYMBOLS ELSEWHERE ON DRAWINGS INDICATE ADDITIONAL INFORMATION REGARDING APPLICATIONOF DEVICE OR EQUIPMENT. REFER TO ABBREVIATIONS, DRAWING ANNOTATIONS, SCHEDULES, AND SPECIFICATIONS FORADDITIONAL SYMBOL SUBSCRIPT INFORMATION.

MULTIPLE SUBSCRIPTS ADJACENT A SYMBOL SIGNIFY MULTIPLE DEVICE TYPES OR MULTIPLE INSTALLATION REQUIREMENTSFOR ONE OR MORE DEVICES. MULTIPLE SUBSCRIPTS REPRESENTING DIFFERENT DEVICE TYPES ADJACENT A SYMBOL ISEQUIVALENT TO MULTIPLE DEVICES LOCATED AT THE SAME OR APPROXIMATE PLAN LOCATION, BUT AT DIFFERENTELEVATIONS. THE FIRST SUBSCRIPTS (STARTING FROM THE LEFT OR TOP) IS ASSOCIATED WITH THE DEVICE AT THE HIGHESTELEVATION, THE SECOND SUBSCRIPT IS ASSOCIATED WITH THE DEVICE AT THE NEXT HIGHEST ELEVATION, ETC.

1.

2.

3.

CONTROL PANELCP

EA

FSD

FPA

COMMUNICATIONS EQUIPMENT LOCATIONET

CONDUIT UP

LEGEND

LEGEND NOTES

COMMUNICATIONS

AUDIOVISUAL COMMON WORK / ELECTRICAL

T COMMUNICATIONS DEVICE

COMMUNICATIONS CEILING DEVICE

COMMUNICATIONS FIELD LOCATED DEVICE

T

T

EQUIPMENT RACK

E

ABBREV. DEFINITIONABBREV. DEFINITION

ABBREVIATIONSTECHNOLOGY RESPONSIBILITY MATRIX

© Copyright BCER Engineering Inc.

Copyright reserved. All parts of this drawing are the exclusive

property of BCER Engineering and shall not be used or

reproduced in any manner without express written consent.

Client:

Project #:

Designed By:

Drawn By:

Approved By:

Scale:

No DateDescription

ISSUE RECORD

100% CONSTRUCTION DOCUMENTS

10/23/2015

NONE

TECHNOLOGY TITLESHEET

UCCS

CO

LO

MB

INE

HA

LL A

UD

IOV

I SU

AL U

PG

RA

DE

S

RIMROCK

RIMROCK

81515004

UN

IV

ER

SIT

Y O

F C

OL

OR

AD

O C

OLO

RA

DO

SP

RIN

GS

RIMROCK

T0.00

AU

ST

IN B

LU

FF

S P

KW

Y, C

OLO

RA

DO

SP

RIN

GS

, C

O 8

091

8

T0.00 TECHNOLOGY TITLE SHEET

T0.01 TECHNOLOGY PROJECT NOTES

T0.02 TECHNOLOGY SCHEDULES

T2.01 TECHNOLOGY PLAN - LEVEL 03

T4.01 TECHNOLOGY SPACE PLANS

T4.02 TECHNOLOGY SPACE PLANS

T5.01 TECHNOLOGY DETAILS

T5.02 TECHNOLOGY DETAILS

ML MONITORED LATCH

MM MULTIMODE FIBER OPTIC CABLE

MREX MOTION REQUEST TO EXIT

MS MONITORED STRIKE

(N) NEW

(NL) NEW LOCATION

NA NOT APPLICABLE

NACLGS NON ACCESSIBLE CEILING SPACE

NC NORMALLY CLOSED CONTACT

NEC NATIONAL ELECTRIC CODE

NO NORMALLY OPEN CONTACT

NS NETWORK SWITCH

NTS NOT TO SCALE

NVR NETWORK VIDEO RECORDER

O OWNER

OB OVERRIDE BUTTON

OC ON CENTER

OD OUTSIDE DIAMETER

OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

OFOI OWNER FURNISHED, OWNER INSTALLED

OHM RESISTIVE NETWORK

OPE OWNER PROVIDED EQUIPMENT

OR OPERATING ROOM

ORI OPERATING ROOM INTEGRATION

OSP OUTSIDE PLANT

OXY OXYGEN

PA PUBLIC ADDRESS

PDS PROTECTIVE DISTRIBUTION SYSTEM

POE POWER OVER ETHERNET

PP PATCH PANEL(S)

PR PAIR

PRJ PROJECTOR

PS POWER SUPPLY

PWR POWER

(RL) REMOVE AND RELOCATE

(RE) REMOVE

R RISER

REV REVISION

REX REQUEST TO EXIT SWITCH

RF RADIO FREQUENCY

RFG RAISED FLOOR GROMMET

RI READER INTERFACE

RM ROOM

RMC RIGID METALLIC CONDUIT

RNC RIGID NONMETALLIC CONDUIT

RS-232 TWO WAY SERIAL DATA STREAM

S STATION

SATV SATELLITE TELEVISION

SC SECURITY CONTRACTOR

SCC SECURITY CAMERA

SCHED SCHEDULE

SCNS SECURITY CAMERA NETWORK SWITCH

SCP SECURITY CONTROL PANEL

SCPP SECURITY CAMERA PATCH PANEL

SCPS SECURITY CAMERA POWER SUPPLY

SH SURFACE HOUSING

SM SINGLEMODE FIBER OPTIC CABLE

SMR SURFACE METAL RACEWAY

SMT SURFACE MOUNT

SN SERIAL NETWORK MODULE

SP SURGE PROTECTOR

SPEC SPECIFICATION

SPKR LOUDSPEAKER LEVEL AUDIO

SPR SURFACE PLASTIC RACEWAY

SR SURFACE RACEWAY

SRR SERVER ROOM

STP SHIELDED TWISTED PAIR

SUS SUSPENDED

SV S-VIDEO

TB TERMINATION BLOCK(S)

TBB TELECOMMUNICATIONS BONDING BACKBONE

TBD TO BE DETERMINED

TC TELECOMMUNICATIONS CONTRACTOR

TCP TEMPERATURE CONTROL PANEL

TEL TELEPHONE

TGB TELECOMMUNICATIONS GROUNDING BUSBAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TP TWISTED PAIR

TR TELECOMMUNICATIONS ROOM (IDF, FD)

TYP TYPICAL

U UNIT

UGND UNDERGROUND

UON UNLESS OTHERWISE NOTED

UPP UNSHIELDED TWISTED PAIR PATCH PANEL

UPS UNINTERRUPTIBLE POWER SUPPLY

USB UNIVERSAL SERIAL BUS

UTP UNSHIELDED TWISTED PAIR

VB VOICE BACKBONE

VE VOICE

VGA HD ANALOG VIDEO TYP 15 PIN D-SUB

VGA+A HD ANALOG VIDEO TYP 15 PIN D-SUB & 3.5MM TRS

VGCB VOICE-GRADE COPPER BACKBONE

VLAN VIRTUAL LOCAL AREA NETWORK

VMS VIDEO MANAGEMENT STATION

VOIP VOICE OVER INTERNET PROTOCOL

VSS VIDEO SURVEILLANCE SYSTEM

VTC VIDEO TELE-CONFERENCING

VW VIDEO WALL

W WALL TELEPHONE

WM WALL MOUNTED

WP WEATHER PROOF

WAP WIRELESS ACCESS POINT

AC ABOVE COUNTER

ACEG ALTERNATING CURRENT ELECTRICAL GROUND

ACLGS ACCESSIBLE CEILING SPACE

ACP ACCESS CONTROL PANEL

ACS ACCESS CONTROL SYSTEM

ACT ACOUSTIC CEILING TILE

AFF ABOVE FINISHED FLOOR

AHJ AUTHORITY HAVING JURISDICTION

AO AUTOMATIC OPERATOR

AOC AUTOMATIC OPENER CONTROLLER

APC ANGLE POLISHED CONNECTOR

APP AUDIO PATCH PANEL

APPROX APPROXIMATELY

AR AUXILIARY RELAY

ARCH ARCHITECT

ATEL ADMINISTRATIVE TELEPHONE

AV AUDIOVISUAL

AVC AUDIOVISUAL CONTRACTOR

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BB BACKBONE

BC BARE COPPER

BEP BUILDING ENTRANCE PROTECTOR

BI BIOMETRIC INTERFACE

BLDG BUILDING

BO BY OTHERS

C CONDUIT

CAB CABINET

CAN CONTROLLED AREA NETWORK

CAT3 CATEGORY 3 COPPER CABLE

CAT5E CATEGORY 5E COPPER CABLE

CAT6 CATEGORY 6 COPPER CABLE

CAT6A CATEGORY 6 AUGMENTED COPPER CABLE

CATV CABLE TELEVISION

CC CONTACT CLOSURE

CCTV CLOSED CIRCUIT TELEVISION

CER CYLINDER ELECTRIC RETRACTION

CLG CEILING

CNL COULD NOT LOCATE

CO CONDUIT ONLY (NO CABLE)

COAX COAX CABLE

COM COMMON

COMM COMMUNICATION

CON CONDUCTOR

CPU COMPUTER PROCESSING UNIT

CPV COMPONENT VIDEO

CR CARD READER

CT COUNT

CV COMPOSITE VIDEO

DB DIRECT BURIAL

(D) DEMOLISH

DD DEAD

DEA DELAYED EGRESS ALARM

DGCB DATA-GRADE COPPER BACKBONE

DIA DIAMETER

DM DIGITAL MULTIMEDIA (SIGNAL)

DP DISPLAYPORT

DPDT DOUBLE POLE DOUBLE THROW

DPS DOOR POSITION SWITCH

DS DIGITAL SIGNAGE

DVI DIGITAL VIDEO INTERFACE

DVR DIGITAL VIDEO RECORDER

DWG DRAWING

(E) EXISTING TO REMAIN

EB EXIT BUTTON

EC ELECTRICAL CONTRACTOR

ECL ELECTRIC CYLINDER LOCK

ECP ELEVATOR CONTROL PANEL

EF ENTRANCE FACILITY (DEMARC)

EIB EMERGENCY INFORMATION BOARD

EL ELECTRIC LATCH

ELEC ELECTRICAL

ELM ELECTRIC LATCH WITH LATCH MONITOR SWITCH

ELR ELECTRICAL LATCH RETRACTION

ELV ELEVATOR

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EQPMT EQUIPMENT

ER EQUIPMENT ROOM

ES ELECTRIC STRIKE

ESO ELECTRICAL SOLENOID

EXIST EXISTING

(F) FUTURE

FAC FIRE ALARM CONTRACTOR

FACP FIRE ALARM CONTROL PANEL

FB FIBER BACKBONE, FLOOR BOX

FD FLOOR DISTRIBUTOR

FL FLUSH

FLEX FLEXIBLE CONDUIT

FPA FLOOR PENETRATION ASSEMBLY

FPD FLAT PANEL DISPLAY

FS FURNITURE SUPPLIER

FSD FIRE STOP DEVICE

G GROUND

GC GENERAL CONTRACTOR

HB HANDICAP BUTTON

HC HORIZONTAL CABLE

HD HIGH DEFINITION

HDBT HDBASET (AV SIGNALS OVER TP)

HDMI HIGH DEFINITION MULTIMEDIA INTERFACE

HO HOLD OPEN

ID INSIDE DIAMETER OR IDENTIFIER

IDS INTRUSION DETECTION SYSTEM

IF INTERFACE PLATE

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IP INTERNET PROTOCOL

IR INFRARED

ISP INSIDE PLANT

IVW IN VARIANCE WITH

IWC IN-BUILDING WIRELESS CONTRACTOR

KIT KITCHEN EQUIPMENT

LAB LABORATORY EQUIPMENT

LC LOW VOLTAGE/SPECIALITY CONTRACTOR

LL LINE LEVEL LEFT CHANNEL AUDIO

LM LINE LEVEL MONO AUDIO

LPS LOCK POWER SUPPLY

LR LINE LEVEL RIGHT CHANNEL AUDIO

MAG MAGNETIC LOCK

MECH MECHANICAL

MED MEDICAL EQUIPMENT

MFR MANUFACTURER

MIC MICROPHONE (CONNECTION)

MIN MINIMUM

RIMROCK CONTACTS

Arvada Office5420 Ward Road, Suite 200Arvada, CO 80002Phone: 303.422.7400

Colorado Springs Office10807 New Allegiance Drive, Suite 400Colorado Springs, CO, CO 80921Phone: 719.533.1112

PROJECT MANAGER

Andy [email protected]

CONSTRUCTION ADMINISTRATOR

Andy [email protected]

Page 5: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,

A PROJECT NOTES INDICATE GENERAL REQUIREMENTS FOR WORK INDICATED ON THEDRAWINGS. APPLICABLE PROJECT NOTES SHALL BE CONSIDERED PART OF GENERAL NOTESFOR EACH SHEET.

B REVIEW ALL NOTES FOR ALL TRADES TO ASSURE FULL COORDINATION BETWEEN ALL TRADES.

C SPEAKER LOCATIONS SHOWN ARE APPROXIMATE. COORDINATE SPEAKER LOCATIONS WITHOTHER CEILING DEVICES. ENSURE THAT FINAL SPEAKER LOCATIONS MEET THE SOUNDREINFORCEMENT INTENT FOR THE TARGET AREA.

A PROJECT NOTES INDICATE GENERAL REQUIREMENTS FOR WORK INDICATED ON THEDRAWINGS. APPLICABLE PROJECT NOTES SHALL BE CONSIDERED PART OF GENERAL NOTESFOR EACH SHEET.

B EVERY CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE GENERAL NOTES - GENERALSECTION FOR PROJECT NOTES THAT APPLY TO MORE THAN ONE TRADE AS WELL AS ALLOTHER NOTES PROVIDED FOR OTHER TRADES FOR FULL COORDINATION BETWEEN ALLTRADES.

A PROJECT NOTES INDICATE GENERAL REQUIREMENTS FOR WORK INDICATED ON THEDRAWINGS. APPLICABLE PROJECT NOTES SHALL BE CONSIDERED PART OF GENERAL NOTESFOR EACH SHEET.

B UNLESS OTHERWISE NOTED IN THE PROJECT NOTES, THE GENERAL REQUIREMENTS OF THEPROJECT NOTES SHALL GOVERN WORK INDICATED ON THE DRAWINGS, UNLESS SPECIFICNOTATION ELSEWHERE ON THE DRAWINGS INDICATES DIFFERENT REQUIREMENTS, IN WHICHCASE THE DIFFERENT REQUIREMENTS INDICATED ELSEWHERE SHALL GOVERN.

C EXAMINE THE CONTRACT DOCUMENTS IN THEIR ENTIRETY, INCLUDING BUT NOT LIMITED TOGENERAL AND SUPPLEMENTAL REQUIREMENTS, DRAWINGS AND SPECIFICATIONS OF OTHERDIVISIONS, AND ADDENDA, FOR EQUIPMENT OR WORK WHICH MAY AFFECT WORK UNDER THISSECTION, REGARDLESS OF WHETHER SUCH REQUIREMENTS OR WORK ARE SPECIFICALLYINDICATED IN THIS SECTION.

D WORK SHALL COMPLY WITH THE GOVERNING REQUIREMENTS LISTED IN THE SPECIFICATIONS.

E IF DISCREPANCIES OR CONFLICTS ARE DISCOVERED IN THE CONSTRUCTION DOCUMENTS, THECONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING AND WAIT FOR INSTRUCTION PRIOR TOPROCEEDING WITH WORK RELATED TO DISCREPANCIES OR CONFLICTS.

F SUBSTITUTIONS OF PRODUCT AND DEVIATIONS FROM METHODS OF CONSTRUCTION SPECIFIEDSHALL BE CONSIDERED AT SUBMITTAL REVIEW. SUCH SUBSTITUTIONS USED FOR BID SHALL BEAT THE SOLE RISK OF CONTRACTOR, AND AS SUCH ARE SUBJECT TO REJECTION WITHOUTCONSIDERATION.

G RECORD DRAWINGS SHALL BE MAINTAINED ON SITE PER SPECIFICATIONS SHOWINGADDITIONS, CHANGES, DELETIONS THROUGHOUT CONSTRUCTION.

H PROVIDE SEISMIC BRACING AS REQUIRED BY THE GOVERNING REQUIREMENTS.

I DRAWING ELEMENTS SHOWN IN GRAY ARE TO BE INSTALLED AS PART OF A DIFFERENT BIDPACKAGE OR PROVIDED BY OTHERS. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORSWORK, COORDINATE DEPENDENCIES WITH APPLICABLE OTHERS IN A TIMELY MANNER, BEFORESUCH DEPENDENCIES ARISE IN THE FIELD.

J THIS PROJECT SHALL BE ACTIVELY MANAGED BY THE CONTRACTOR'S PROJECT MANAGERWHICH SHALL NOT ALSO BE THE CONTRACTOR'S FOREMAN OR BE INVOLVED IN TECHNICALWORK IN THE FIELD. DOWNTIME, DELAYS OR NON-SCHEDULED OUTAGES DUE TO THECONTRACTOR'S FAILURE TO ACTIVELY MANAGE THE WORK, INCLUDING BUT NOT LIMITED TOEFFECTIVELY PLANNING, SEQUENCING, SCHEDULING, AND EXECUTING THE WORK WILL NOT BEACCEPTABLE AT ANY TIME.

K WORK REQUIRING UTILITY AND/OR TECHNOLOGY SYSTEM OUTAGES SHALL BE COORDINATEDWITH THE OWNER IN ADVANCE AND PRE-APPROVED IN WRITING.

L COORDINATION IS REQUIRED PRIOR TO ROUGH-IN. DRAWINGS ARE DIAGRAMMATIC AND SHALLNOT BE SCALED FOR BOX, DEVICE AND/OR EQUIPMENT LOCATIONS. LOCATIONS INDICATEDARE APPROXIMATE AND DO NOT REPRESENT THE ACTUAL FIELD CONDITION OR FINALLOCATION. FURTHERMORE, REQUIREMENTS FOR ROUGH-IN BOXES, EQUIPMENT DIMENSIONS,MOUNTING/HEIGHTS, SUPPORTS, FACEPLATES, CONDUIT ROUTING, AND/OR INTERFACES MAYVARY. COORDINATE FINAL LOCATIONS AND REQUIREMENTS WITH ACTUAL FIELD CONDITIONS,SHOP DRAWINGS, RESPECTIVE TRADE(S), ARCHITECT, AND/OR OWNER PRIOR TO ROUGH-IN.

M WHERE COORDINATION DICTATES THAT FINAL LOCATIONS VARY SIGNIFICANTLY FROM THATSHOWN ON THE DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND AWAITAPPROVAL PRIOR TO ELECTRICAL ROUGH-IN.

N IDENTIFY AND COORDINATE WITH OTHER TRADES LOCATION AND SIZE OF REQUIRED OPENINGSIN NEW CONCRETE OR MASONRY PRIOR TO THE FORMING AND POURING OF CONCRETE ORCONSTRUCTION OF MASONRY. OPENINGS MAY NOT BE INDICATED ON DRAWINGS.

O CONTRACTOR SHALL COORDINATE ALL PENETRATIONS, OPENINGS, FASTENERS,CONNECTIONS, HANGERS, AND SUPPORTS WITH STRUCTURAL DRAWINGS AND ENGINEERPRIOR TO COMMENCEMENT OF WORK. WHEN LOCATING AND SIZING ALL PENETRATIONSTHROUGH THE STRUCTURAL SLABS REFER TO THE STRUCTURAL DETAILS DEPICTINGALLOWABLE LOCATIONS AND OPENINGS. THE CONTRACTOR SHALL PREPARE A DRAWING(S) OFALL PENETRATIONS AND COORDINATE THIS DRAWING(S) WITH THE GENERAL CONTRACTORAND ALL OTHER TRADES TO VERIFY THAT THE LOCATIONS OF TECHNOLOGY REQUIREDPENETRATIONS DO NOT CONFLICT WITH PENETRATIONS REQUIRED BY ALL OTHER TRADES.

P PENETRATION OF CONCRETE AND STRUCTURAL ELEMENTS SHALL BE AVOIDED WHEREPOSSIBLE. OBTAIN WRITTEN APPROVAL FROM STRUCTURAL ENGINEER/ARCHITECT PRIOR TOSUCH NECESSARY PENETRATIONS.

Q PROVIDE SLEEVES FOR LOCATIONS WHERE CABLE PASSES THROUGH WALLS, FLOORS, ORFOUNDATIONS. SLEEVES SHALL BE SIZED TO SUPPORT CABLES PER NEC FILL RATIOS ANDTIA/EIA 569 CABLE CAPACITY STANDARDS PLUS <25 PERCENT> FUTURE EXPANSION.

R PROVIDE CABLE PATHWAY FIRESTOPPING DEVICES FOR LOCATIONS WHERE CABLE WILLPENETRATE FIRE RATED BARRIERS. REFER TO ARCHITECTURAL DRAWINGS FOR WALL TYPEINFORMATION. PROVIDE CABLE PATHWAY FIRESTOPPING DEVICE(S) IN SUFFICIENT QUANTITYSUCH THAT THE COMBINED USEABLE CROSS SECTIONAL AREA OF THE DEVICE(S) MATCHES OREXCEEDS THE CROSS SECTIONAL AREA OF CABLE TRAY TO BE SERVED.

S FOR EACH CABLE PATHWAY FIRESTOPPING LOCATION SHOWN FEEDING CABLE TRAY, PROVIDECABLE PATHWAY FIRESTOP DEVICE(S) IN SUFFICIENT QUANTITY SUCH THAT THE COMBINEDUSEABLE CROSS-SECTIONAL AREA OF THE DEVICE(S) IS GREATER THAN OR EQUAL TO THECROSS-SECTIONAL AREA OF CABLE TRAY TO BE SERVED. FOR ALL OTHER FIRESTOPLOCATIONS, PROVIDE CABLE PATHWAY FIRESTOP DEVICE(S) IN SUFFICIENT QUANTITY SUCHTHAT THE COMBINED USEABLE CROSS-SECTIONAL AREA OF THE DEVICE(S) IS GREATER THANTHE CROSS-SECTIONAL AREA OF ALL CABLES TO PASS THROUGH THE DEVICES, PLUS THEADDITIONAL AMOUNT (PERCENTAGE) REQUIRED BY THE SPECIFICATIONS OR ELSEWHERE FORFUTURE EXPANSION.

T PER NEC REQUIREMENTS, TECHNOLOGY ITEMS SHALL NOT BE SECURED TO OR SUPPORTED BYSUSPENDED CEILING SYSTEM (INCLUDING SUPPORTS WIRES), HANGERS FOR CABLESUPPORTS SHALL BE INDEPENDENT (DEDICATED). PER NEC REQUIREMENTS, WIRE HANGERSSHALL BE SUPPORTED AT BOTH ENDS AND DISTINGUISHABLE FROM SUSPENDED CEILINGSYSTEM SUPPORT WIRE. IN EXPOSED STRUCTURAL CEILING SPACES, WIRE SHALL NOT BEUSED AS A HANGER FOR SUPPORT.

U HANGERS AND SUPPORTS SHALL BE PROVIDED AT INTERVALS PER THE NEC, SHALL BEATTACHED TO STRUCTURE AND NOT BE ATTACHED TO OTHER BUILDING SYSTEMS AND THEIRASSOCIATED SUPPORTS. CABLE SUPPORTS SHALL BE MOUNTED AT VARYING INTERVALS NOTTO EXCEED 5 FEET AND ROUTED PARALLEL AND PERPENDICULAR TO BUILDING LINES. CABLESUPPORTS SHALL NOT SHARE CABLES OF DIFFERENT TECHNOLOGY SYSTEMS OR EXCEED 50PERCENT OF THE MANUFACTURER'S RECOMMENDED FILL. INCLUDE CABLE SUPPORT ROUTINGON RECORD DRAWINGS.

V CABLE DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR WITHIN 4HOURS OF THE DAMAGING EVENT, AT NO ADDITIONAL COST TO THE OWNER.

W COORDINATE WITH AUDIOVISUAL EQUIPMENT SUPPLIER AND SHOP DRAWINGS TO FINALIZE ALLSTRUCTURAL SUPPORT REQUIREMENTS AND LOCATIONS FOR DISPLAYS, PROJECTORS ANDPROJECTION SCREENS PRIOR TO ROUGH-IN.

X SPEAKER LOCATIONS SHOWN ARE APPROXIMATE. COORDINATE SPEAKER LOCATIONS WITHOTHER CEILING DEVICES. ENSURE THAT FINAL SPEAKER LOCATIONS MEET THE SOUNDREINFORCEMENT INTENT FOR THE TARGET AREA.

GENERAL NOTES

COMMON WORK / ELECTRICAL

AUDIOVISUALGENERAL

© Copyright BCER Engineering Inc.

Copyright reserved. All parts of this drawing are the exclusive

property of BCER Engineering and shall not be used or

reproduced in any manner without express written consent.

Client:

Project #:

Designed By:

Drawn By:

Approved By:

Scale:

No DateDescription

ISSUE RECORD

100% CONSTRUCTION DOCUMENTS

10/23/2015

NONE

TECHNOLOGY PROJECTNOTES

UCCS

CO

LO

MB

INE

HA

LL A

UD

IOV

I SU

AL U

PG

RA

DE

S

RIMROCK

RIMROCK

81515004

UN

IV

ER

SIT

Y O

F C

OL

OR

AD

O C

OLO

RA

DO

SP

RIN

GS

RIMROCK

T0.01

AU

ST

IN B

LU

FF

S P

KW

Y, C

OLO

RA

DO

SP

RIN

GS

, C

O 8

091

8

Page 6: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,

A ACCESSIBLE: EASY ACCESS. ACCESS ATTAINED WITHOUT REQUIRING EXTENSIVE REMOVALOF OTHER MATERIALS TO GAIN ACCESS.

B ACCESSIBLE CEILING: ACOUSTICAL TILE HANGING CEILINGS (“HARD-LID” CEILINGS (CONCEALEDSPINE OR SHEETROCK/GYPSUM CEILINGS), EVEN WHEN PROVIDED WITH ACCESS PANELS, ARENOT CONSIDERED AN ACCESSIBLE CEILING.)

C BY OTHERS: A PARTY OR ENTITY OTHER THAN THE CONTRACTOR. THE CONTRACTOR SHALLENGAGE THE GENERAL CONTRACTOR, ARCHITECT, AND/OR OWNER TO DETERMINE THIS PARTYOR ENTITY FOR CONSIDERATION OF PRICING AND/OR EXECUTION OF THE WORK.

D COMMUNICATIONS (OR TECHNOLOGY) GROUNDING SYSTEM: INCLUDES (BUT IS NOT LIMITEDTO) PROVIDING A PERMANENT GROUNDING AND BONDING INFRASTRUCTURE FOR THECOMMUNICATIONS CABLING SYSTEM.

E ELECTRICAL FOR COMMUNICATIONS SYSTEMS ALSO REFERED TO AS COMMUNICATIONS (ORTECHNOLOGY) PATHWAY SYSTEM: INCLUDES (BUT IS NOT LIMITED TO) DEVICE BOXES, PULLBOXES, CONDUIT, CABLE TRAY, DUCT/DUCTBANK, AND OTHER PATHWAY AND RACEWAYCOMPONENTS NECESSARY TO PROVIDE PATHWAY FOR, SUPPORT, AND ROUTECOMMUNICATIONS CABLES.

F CONCEALED: HIDDEN FROM SIGHT IN INTERSTITIAL BUILDING SPACES, CHASES, FURREDSPACES, SHAFTS, CRAWL SPACES, ETC.

G CONSTRUCTION DOCUMENTS: COLLECTIVE TERM FOR THE ENTIRE SET OF BOUND ORUNBOUND MATERIAL DESCRIBING THE CONSTRUCTION AND SERVICES REQUIRED, INCLUDINGALL DRAWINGS, SPECIFICATIONS, ADDENDA ISSUED PRIOR TO EXECUTION OF THE CONTRACT,AND MODIFICATIONS ISSUED AFTER EXECUTION OF THE CONTRACT (SUCH AS CHANGEORDERS, CONSTRUCTION CHANGE DIRECTIVES, SUPPLEMENTAL INSTRUCTIONS, ETC.).

H CONTRACT DOCUMENTS: THE AGREEMENT (INCLUDING OTHER DOCUMENTS LISTED IN THEAGREEMENT), CONDITIONS OF THE CONTRACT (GENERAL, SUPPLEMENTARY AND OTHERCONDITIONS), AND THE CONSTRUCTION DOCUMENTS.

I EXPOSED: NOT CONCEALED AND NOT INSTALLED UNDERGROUND.

J FURNISH: TO PURCHASE, SUPPLY, AND DELIVER TO THE PROJECT MATERIALS IN NEW ANDOPERABLE CONDITION, READY FOR INSTALLATION.

K GOVERNING AUTHORITY: ENTITIES OR THEIR REPRESENTATIVES CHARGED WITH FORMATIONAND/OR ENFORCEMENT OF GOVERNING REQUIREMENTS, SUCH AS THE AUTHORITY HAVINGJURISDICTION (AJH).

L INSTALL: TO PLACE IN FINAL POSITION IN FULLY OPERABLE, TESTED CONDITION.

M PROVIDE: TO FURNISH AND INSTALL, COMPLETE, TESTED AND READY FOR INTENDED USE.

N ROUGH-IN: PROVIDE THE COMMUNICATIONS PATHWAY SYSTEM, INCLUDING (BUT NOT LIMITEDTO) DEVICE BOXES, PULL BOXES, WALL BOXES, FLOOR BOXES, POKE-THROUGH DEVICES,CONDUIT, ENCLOSURES, CABLE TRAY, DUCTS/DUCTBANKS, MAINTENANCE HOLES, HANDHOLES, AND OTHER PATHWAYS AND ITEMS INDICATED (OR AS REQUIRED) FOR ROUTING,SUPPORTING, AND INSTALLING COMMUNICATIONS CABLES, DEVICES, OR EQUIPMENT WHICHSHALL BE PROVIDED BY OTHERS OR PROVIDED UNDER A SUBSEQUENT SET OF CONTRACTDOCUMENTS.

PROJECT PHASING SCHEDULE

PHASE DATES ROOMS NOTES

1 12/21/15 THRU 1/8/16 317

2 3/21/16 THRU 3/27/16 322, 325 SCD 3/23/16 4PM

3 5/16/16 THRU 6/12/16 323, 324, 333

3A 5/16/16 THRU 5/21/16 334 SCD 5/18/16 4PM

3B 6/6/16 THRU 6/11/16 329 SCD 6/8/16 4PM

NOTES:

1) CONFIRM ALL DATES WITH UCCS PROJECT MANAGEMENT.

2) SIGNIFICANT COMPLETION DATE (SCD) SHALL BE 5 BUSINESS DAYS PRIOR TO END OF GIVENPROJECT PHASE UNLESS OTHERWISE NOTED.

SYMBOL

SYMBOL

SYMBOL

CR-X

ET

WxH

SR

U

CS

OSP

CT-DxW

FSD

FPA

A

A

IF

A

A

A

CP

EA

T

T

T

DEVICE SCHEDULE

A

A

A

AUDIOVISUAL COMMON WORK / ELECTRICAL

COMMUNICATIONS

P

SUBSCRIPT DESCRIPTION DETAILS ID

E

SHEETDETAIL

DETAIL INDEXTERMS AND DEFINITIONS

GENERAL

PHASING SCHEDULE

© Copyright BCER Engineering Inc.

Copyright reserved. All parts of this drawing are the exclusive

property of BCER Engineering and shall not be used or

reproduced in any manner without express written consent.

Client:

Project #:

Designed By:

Drawn By:

Approved By:

Scale:

No DateDescription

ISSUE RECORD

100% CONSTRUCTION DOCUMENTS

10/23/2015

NONE

TECHNOLOGYSCHEDULES

UCCS

CO

LO

MB

INE

HA

LL A

UD

IOV

I SU

AL U

PG

RA

DE

S

RIMROCK

RIMROCK

81515004

UN

IV

ER

SIT

Y O

F C

OL

OR

AD

O C

OLO

RA

DO

SP

RIN

GS

RIMROCK

T0.02

AU

ST

IN B

LU

FF

S P

KW

Y, C

OLO

RA

DO

SP

RIN

GS

, C

O 8

091

8

CABLE SUPPORT PATHWAY

(NO SUBSCRIPT) TE-CR JS001

J J-HOOKS JS010

CABLE TRAY (DEPTH x WIDTH)

(NO SUBSCRIPT) TE-BJ, TE-CT,TE-CTUB,

TE-CR

CT201

GROUNDING BUSBAR

TGB GROUND BUS GB020

TMBG MAIN GROUND BUS GB010

DEVICE BOX EMPTY

(NO SUBSCRIPT) TE-CR

AV AUDIOVISUAL TE-CR,TA-DETAILS

FF FURNITURE FEED TE-CR

S SECURITY TS-SD

SEP SITE EMERGENCY PHONE TE-CR

DEVICE BOX EMPTY (CEILING)

(NO SUBSCRIPT) TA-IFB

AV AUDIOVISUAL TE-CR,TA-DETAILS

S SECURITY TS-SD

FLOOR BOX

(NO SUBSCRIPT) TE-FB CB001

FB4 4-GANG TE-FB CB004

FB6 6-GANG TE-FB CB006

FB8 8-GANG TE-FB CB008

FB10 10-GANG TE-FB CB010

FBF FURNITURE FEED TE-FB CB015

POKE THRU

PT6 6-INCH CB023

PT8 8-INCH CB025

PTF FURNITURE FEED

ENCLOSURE

AUDIOVISUAL CEILING BOX TA-PE

S SECURITY CEILING ENCLOSURE TS-SD

WALL BOX

VIDEO DISPLAY TA-DWB

EQUIPMENT RACK

AUDIOVISUAL (FLOOR) TA-IFER

W AUDIOVISUAL (WALL) TA-IFWR

HAND HOLE

(NO SUBSCRIPT)

MAINTENANCE HOLE

(NO SUBSCRIPT) TE-MH,TE-MHCE

MH100

SUBSCRIPT DESCRIPTION DETAILS ID

AUDIOVISUAL EQUIPMENT LOCATION

SHARED RACK SPACE (TYP TR) TC SERIES

LOUDSPEAKER

STANDARD (WALL) TA-IFWB

A TYPE A

B TYPE B

C TYPE C

LOUDSPEAKER (CEILING)

STANDARD ACT (REPLACEMENTOR CUT-IN)

N NON-ACCESSIBLE CEILING TA-CSD

P PENDANT TA-CSD

S SUB-WOOFER

VIDEO DISPLAY

STANDARD (WALL)

DS DIGITAL SIGNAGE

VIDEO DISPLAY (CEILING)

PLENUM ACT CEILING TA-PMD

A ACT CEILING TA-PMD

DS DIGITAL SIGNAGE

E EXPOSED TA-PMD

N NON-ACCESSIBLE CEILING TA-PMD

PROJECTION SCREEN

STANDARD (WALL) TA-WMS

PROJECTION SCREEN (CEILING)

RECESSED TA-CRS

C SUSPENDED TA-CSS

CONTROL PANEL

STANDARD (BACKBOX) TA-IFCP

A TYPE A TA-IFCP

T TABLE TOP / TOUCH PANEL

INTERFACE PLATE

STANDARD (WALL) TA-IFW

B TYPE B

C TYPE C

F STANDARD, FLOOR TA-FIF

T TABLE TOP / FURNITURE TA-TIF

PROJECTOR

SHORT THROW (INTERACTIVE) TA-WPD

A SHORT THROW (PRESENTATION)

B TYPE B

PROJECTOR (CEILING)

PLENUM ACT CEILING TA-PMD

A ACT CEILING TA-PMD

E EXPOSED TA-PMD

N NON-ACCESSIBLE CEILING TA-PMD

PROJECTOR LIFT

CEILING MOUNTED TA-PL

FIXED CAMERA (CEILING)

(NO SUBSCRIPT)

A TYPE A

PAN - TILT - ZOOM CAMERA

(NO SUBSCRIPT) TA-IFB

A TYPE A TA-IFB

PAN - TILT - ZOOM CAMERA (CEILING)

(NO SUBSCRIPT)

A TYPE A

LECTERN

(NO SUBSCRIPT)

AUDIOVISUAL DEVICE

ALS ASSISTIVE LISTENING

AP WIRELESS ACCESS POINTTRANSCEIVER

S SCREEN SWITCH

VC VOLUME CONTROL

WM WIRELESS MIC ANTENNA

AUDIOVISUAL CEILING DEVICE

ALS ASSISTIVE LISTENING

AP WIRELESS ACCESS POINTTRANSCEIVER

M MICROPHONE

WM WIRELESS MIC ANTENNA

AUDIOVISUAL FIELD LOCATED DEVICE

DM DUAL-ELEMENT BOUNDARYMICROPHONE

M MICROPHONE

TM TRI-ELEMENT BOUNDARYMICROPHONE

WC WEB CAM

SUBSCRIPT DESCRIPTION DETAILS ID

COMMUNICATIONS EQUIPMENT LOCATION

(NO SUBSCRIPT)

CABLE RUNWAY (X INDICATES MINIMUM WIDTH IN INCHES)

(NO SUBSCRIPT) TC-CR,TC-CRAD

ER200

A ALTERNATE SPACING TC-CR,TC-CRAD

ER201

CABLE - END LOOP

(NO SUBSCRIPT)

CABLE - CONTINUOUS LOOP

(NO SUBSCRIPT)

TELECOM OUTLET

(NO SUBSCRIPT) TE-CR

AC ABOVE COUNTER TE-CR

AV AUDIOVISUAL TE-CR,TA-DETAILS

DS DIGITAL SIGNAGE TE-CR,TA-DETAILS

E EMERGENCY INFORMATIONBOARD

TE-CR

ELEC ELECTRICAL EQUIPMENT TE-CR

ELV ELEVATOR EQUIPMENT TE-CR

EP EMERGENCY BLUE PHONE TE-CR

F FURNITURE MOUNTED

FACP FIRE ALARM CONTROL PANEL TE-CR

K KIOSK TE-CR

LCP LIGHTING CONTROL PANEL TE-CR

MECH MECHANICAL/HVAC EQUIPMENT TE-CR

POS POINT OF SALE TE-CR

S SECURITY CAMERA TS-CD

SR SURFACE RACEWAY

VND VENDING MACHINE TE-CR

W WALL TELEPHONE TE-CR

WAP WIRELESS ACCESS POINT TE-CR

TELECOM OUTLET (CEILING)

(NO SUBSCRIPT) TE-CR

AV AUDIOVISUAL TE-CR,TA-DETAILS

DS DIGITAL SIGNAGE TE-CR,TA-DETAILS

E EMERGENCY INFORMATIONBOARD

TE-CR

S SECURITY CAMERA TS-CD

WAP WIRELESS ACCESS POINT TE-CR

COMMUNICATIONS DEVICE

(NO SUBSCRIPT)

COMMUNICATIONS CEILING DEVICE

(NO SUBSCRIPT)

COMMUNICATIONS FIELD LOCATED DEVICE

(NO SUBSCRIPT)

TA-CRS - CEILING RECESSED SCREEN DETAIL T5.01

TA-CSD - CEILING SPEAKER DETAILS T5.01

TA-IFB - BACK BOX DETAIL FOR AV WALL INTERFACE REQUIRING BACKING T5.01

TA-IFER - BACK BOX DETAIL FOR AV EQUIPMENT RACK T5.01

TA-IFW - BACK BOX DETAIL FOR AV WALL INTERFACE T5.01

TA-PMD - PROJECTOR MOUNT DETAILS T5.02

TA-TTIF - TABLE TOP INTERFACE DETAIL T5.01

TA-VCW - BACK BOX DETAIL FOR AV DEVICE CONTROL T5.01

STRUCTURAL BLOCKOUT (WIDTH x HEIGHT)

CABLE PATHWAY FIRESTOPPING DEVICE TE-WFS FS102

FIRE-RATED FLOOR PENETRATION ASSEMBLY TE-FFS FS110

GROUND

CONDUIT WITH BUSHING

CONDUIT WITH CAP

CONDUIT UP

CONDUIT DOWN

CONDUIT / CABLE HOME RUN

SURFACE RACEWAY SR100

CONDUIT UNDERGROUND / FLOOR / SLAB

OSP UNDERGROUND DUCTBANK

PULL BOX MH400

UTILITY POLE

Page 7: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,

326326

312B

325

327

324

330

329

322 323

321

320

317

328 331

333

334

318

335

310

308

304A

316B316A

316

337

315

312C

312A

305 301

307

304

302300A

303

312E

312

312D 312F

314

312G 312H

313

320

337

338

DN

UP

DN

DN

UP

T-4.01

T-4.02

T-4.01

T-4.01 T-4.01

T-4.01 T-4.01

T-4.01

A ABANDON ALL EXISTING COPPER AND FIBER AUDIOVISUAL CABLING. PROVIDE STAINLESSSTEEL BLANK COVER FOR OUTLET BOX AT LECTERN. REMOVE CABLING FROM EXISTINGPROJECTOR POLE MOUNT AND AMX TELEVISION MANAGER AND LEAVE NEATLY COILED ATPROJECTOR LOCATION ABOVE CEILING. REMOVE AND RETURN AUDIO AMPLIFIER (LOCATEDNEAR PROJECTOR ABOVE CEILING), CEILING SPEAKERS, AMX TELEVISION MANAGER,PROJECTOR, AND SCREEN TO OWNER. REUSE EXISTING PROJECTOR POLE AND PROJECTORMOUNTING HARDWARE. REMOVE AND DISPOSE OF PODIUM.

T4.01

1

T4.02

1

T4.01

1

T4.01

1T4.01

1

T4.01

1

T4.01

1

T4.01

1

TE04 TE04TE04 TE04

TE04

TE04

TE04

DEMOLITION NOTES

© Copyright BCER Engineering Inc.

Copyright reserved. All parts of this drawing are the exclusive

property of BCER Engineering and shall not be used or

reproduced in any manner without express written consent.

Client:

Project #:

Designed By:

Drawn By:

Approved By:

Scale:

No DateDescription

ISSUE RECORD

100% CONSTRUCTION DOCUMENTS

10/23/2015

As indicated

TECHNOLOGY PLAN -LEVEL 03

UCCS

CO

LO

MB

INE

HA

LL A

UD

IOV

I SU

AL U

PG

RA

DE

S

RIMROCK

RIMROCK

81515004

UN

IV

ER

SIT

Y O

F C

OL

OR

AD

O C

OLO

RA

DO

SP

RIN

GS

RIMROCK

T2.01

AU

ST

IN B

LU

FF

S P

KW

Y, C

OLO

RA

DO

SP

RIN

GS

, C

O 8

091

8

N

0 8'8' 4'

T2.01

1/8" = 1'-0"

1 TECHNOLOGY PLAN - LEVEL 03

KEYNOTES

TE04 PROVIDE OUTLET BOXES FOR AUDIOVISUAL, TELECOMMUNICATIONS, ANDELECTRICAL SERVICES TO LECTERN AT THIS LOCATION. REFER TO DETAIL TA-IFERFOR RECOMMENDED LAYOUT AND ASSUMED TELECOMMUNICATION AND ELECTRICALREQUIREMENTS TO BE CONFIRMED BY OWNER. REFER TO RISER DIAGRAM ONTECHNOLOGY SPACE PLAN FOR ADDITIONAL INFORMATION AND REQUIREMENTS FORAUDIOVISUAL OUTLET BOXES.

Page 8: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,

IF

A

IF

A

TYPE DESCRIPTION MANUFACTURER PART NUMBER SPECIAL RQMTS

2 CHANNEL AUDIO AMPLIFIER CROWN DCi 2 | 300

WALL SURFACE LOUDSPEAKER MARTIN CDD5x MOUNTING BRACKET AS REQ.

DOCUMENT CAMERA WOLFVISION VZ-3

DIGITALMEDIA PRESENTATION SYSTEM CRESTRON DMPS3-4k-150-C

HDMI DA & EXTRACTOR CRESTRON HD-DA-2

A PROJECTOR EPSON G6470WU

APPLE TV APPLE APPLE TV

16:10 ELECTRIC RECESSED SCREEN DA-LITE 60" x 96" TENSIONED ADVANTAGE 113" DIAGONAL

S SCREEN SWITCH DA-LITE AS REQUIRED

TOUCHPANEL 7" CRESTRON TSW-752

TABLE STAND KIT FOR TSW-750 CRESTRON TSW-750-TTK-X-S

POE SWITCH 5 PORT CRESTRON CEN-SW-POE-5

SMART LECTERN ATF MT-400-UCCS-MAPLE-NATURAL-7302

POWER CONDITIONER FURMAN P-8 PRO II AS REQUIRED

INTERFACE PLATE CUSTOM RCI CUSTOM As Required

SPEAKON NEUTRIK As Required

ETHERCON CAT6A SHIELDED NEUTRIK As Required For Digital Media

Net Connect Cable XG620 4pr 23 AWG CMP Yellow Jacket AMP 4-1499416-7 For Digital Media

DISPLAY POLE MOUNTING HARDWARE CHIEF AS REQUIRED REUSE EXISTING

PROJECTOR MOUNT CHIEF RPAU (5) REUSE EXISTING, (2) NEW

ASSISTEDLISTENING

SYSTEM(OFOI)

COMPUTER(OFCI)

SMARTLECTURN

CABLE POCKET

DETAILAV-D1

TO NETWORKBY OTHERS

TO NETWORKBY OTHERS

TO NETWORKBY OTHERS

TO NETWORKBY OTHERS

TO NETWORKBY OTHERS

TO NETWORKBY OTHERS

8 OHM

HDMI

MIC

VGA

LL LR

CV

LL LR

HDBT

HDMI

HDMI

CC

USB

CC CC

LM

IP

POE

IP

IP

IP

IP

LM

HDMI

LM

HDMIIP

SPKR

SMART LECTERN

MT-400-UCCS-MAPLE-NATURAL -7302

DIGITALMEDIA

PRESENTATION

SYSTEM

*

DMPS3-4k-150-C

TOUCHPANEL 7"

*

TSW-752

TABLE STAND KIT

FOR TSW-750

TSW-750-TTK-X-S

DOCUMENT

CAMERA

*

VZ-3

POE SWITCH 5

PORT

CEN-SW-POE-5

16:10 ELECTRIC

RECESSED

SCREEN

*

60" x 96"

TENSIONED

ADVANTAGE 113"

DIAGONAL

PROJECTOR

*

G6470WU

SCREEN SWITCH

*

AS REQUIRED

HDMI DA &

EXTRACTOR

*

HD-DA-2

INTERFACE

PLATE

CUSTOM

As Required

HDBT

APPLE TV

*

APPLE TV

AUDIO AMPLIFIER

*

DCi 2 | 300

WALL SURFACE

LOUDSPEAKER

*

CDD5x

A REVIEW ALL CONTRACT DOCUMENTS FOR PROJECT REQUIREMENTS. TECHNOLOGY SPACEPLANS MAY NOT BE PROVIDED FOR ALL SYSTEMS AND ARE NOT EXHAUSTIVE. INFORMATIONPROVIDED IS PROGRAMMATIC; SOME ANCILLARY EQUIPMENT MAY BE SHOWN HEREIN FORCLARITY, BUT NOT ALL ANCILLARY EQUIPMENT IS SPECIFIED. PROVIDE ALL COMPONENTSNECESSARY FOR A FULLY FUNCTIONAL SYSTEM(S) READY FOR THE OWNERS USE.REQUIREMENTS FOR POWER, MOUNTING, CABLE MANAGEMENT, COOLING, AND OTHERMISCELLANEOUS COMPONENTS REQUIRED FOR A FULLY FUNCTIONING SYSTEM ARE ASSUMEDAND SHALL BE PROVIDED BY THE CONTRACTOR.

T4.01

2

S

TE03

A

B

6

1 W

2

TE05

TA02

FLOOR

CEILING

IF

(2) 1 1/4-INCH CONDUITS

A.

B.

C.

ALL MEASUREMENTS ARE TO CENTER UNLESS OTHERWISE NOTED.

STUB ALL CONDUITS TO ACCESSIBLE CEILING SPACE OF SAME ROOMUNLESS OTHERWISE ILLUSTRATED/NOTED IN RISER DIAGRAM.

ADDITIONAL CONDUITS FOR TELECOMM OR POWER MAY BE REQUIRED.REFERENCE DEVICE DETAILS AND TELECOMM AND ELECTRICAL PLANS.

RISER GENERAL NOTES

+18"

(2) 1-INCH CONDUITS

A S

+48"

+90"

(2) 1-INCH CONDUITS

IF+18"

(2) 1 1/4-INCH CONDUITS

(REF. DETAIL TA-IFER)

1

1. REFERENCE DETAIL TA-IFER FOR GENERAL LAYOUT INFORMATION ANDASSUMED ELECTRICAL AND TELECOMM REQUIREMENTS TO BE CONFIRMEDBY OWNER. LOCATE OUTLET BOXES SERVING LECTERN LOCATION PERKEYNOTE ON TECHNOLOGY FLOOR PLANS. PROVIDE A BLANK PLATE FORONE OF THE BOXES TO BE LEFT AS SPARE FOR FUTURE USE.

RISER DRAWING NOTES

EQUIPMENT SCHEDULE

GENERAL NOTES

© Copyright BCER Engineering Inc.

Copyright reserved. All parts of this drawing are the exclusive

property of BCER Engineering and shall not be used or

reproduced in any manner without express written consent.

Client:

Project #:

Designed By:

Drawn By:

Approved By:

Scale:

No DateDescription

ISSUE RECORD

100% CONSTRUCTION DOCUMENTS

10/23/2015

As indicated

TECHNOLOGY SPACEPLANS

UCCS

CO

LO

MB

INE

HA

LL A

UD

IOV

I SU

AL U

PG

RA

DE

S

RIMROCK

RIMROCK

81515004

UN

IVE

RS

ITY

OF C

OL

OR

AD

O C

OLO

RA

DO

SP

RIN

GS

RIMROCK

T4.01

AU

ST

IN B

LU

FF

S P

KW

Y, C

OLO

RA

DO

SP

RIN

GS

, C

O 8

091

8

N

0 4'4' 2'

T4.01

1/4" = 1'-0"

1 CLASSROOM ENLARGED FLOOR PLAN

0 4'4' 2'

T4.01

1/4" = 1'-0"

2 CLASSROOM PRESENTATION WALL ELEVATION

T4.01

3 CLASSROOM RISER DIAGRAM

T4.01

5 CLASSROOM AUDIOVISUAL ONE-LINE DIAGRAM

KEYNOTES

TA02 CENTER PROJECTOR SCREEN AND SPEAKER ON EXISTING PROJECTOR MOUNTLOCATION. AS ROOM LAYOUTS VARY, LOCATIONS SHALL BE REVIEWED ANDCONFIRMED DURING THE MANDATORY CONSTRUCTION KICKOFF MEETING PRIOR TOPERFORMING ANY WORK. TYPICAL LOCATION SHALL BE APPROXIMATELY FIVE FEETFROM PRESENTATION WALL. USE CEILING MOUNT WITH TILE BRIDGE AND SAFETYCABLE AS REQUIRED.

TE03 PROVIDE EMPTY 4 11/16" DEVICE BOX WITH SINGLE GANG MUD RING AND BLANKCOVER PLATE FOR FUTURE CAMERA INTERFACE ADJACENT TO SCREEN. LOCATEIMMEDIATELY ABOVE WRITING SURFACE APPROXIMATELY (7) SEVEN FEET (6) SIXINCHES AFF. LOCATE TO SIDE OF SCREEN NEAREST LECTERN APPROXIMATELY (1)ONE FOOT FROM EDGE OF SCREEN.

TE05 AS ROOM LAYOUTS VARY, LOCATIONS SHALL BE REVIEWED AND CONFIRMED DURINGTHE MANDATORY CONSTRUCTION KICKOFF MEETING PRIOR TO PERFORMING ANYWORK. REFER TO RISER DIAGRAM ON TECHNOLOGY SPACE PLAN AND DETAILTA-IFER FOR GENERAL INFORMATION AND REQUIREMENTS. THE TYPICAL ORDER OFOUTLET BOXES FROM FRONT TO BACK OF THE ROOM SHALL BE: SCREEN SWITCH,TELEPHONE OUTLET, DATA OUTLET, AV INTERFACE PLATES, THEN ELECTRICALOUTLET.

mfalcon
Text Box
ADD ALTERNATE #1
mfalcon
Text Box
PROVIDE HARD CONDUITS FOR NEW AV, TELECOM AND POWER OUTLETS
mfalcon
Rectangle
mfalcon
Text Box
BASE BID:
mfalcon
Text Box
PROVIDE FLEX CONDUITS FOR NEW AV, TELECOM AND POWER OUTLETS
mfalcon
Rectangle
Page 9: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,

A

A

A

A

A

IF IF IF

AA

A

A

A REVIEW ALL CONTRACT DOCUMENTS FOR PROJECT REQUIREMENTS. TECHNOLOGY SPACEPLANS MAY NOT BE PROVIDED FOR ALL SYSTEMS AND ARE NOT EXHAUSTIVE. INFORMATIONPROVIDED IS PROGRAMMATIC; SOME ANCILLARY EQUIPMENT MAY BE SHOWN HEREIN FORCLARITY, BUT NOT ALL ANCILLARY EQUIPMENT IS SPECIFIED. PROVIDE ALL COMPONENTSNECESSARY FOR A FULLY FUNCTIONAL SYSTEM(S) READY FOR THE OWNERS USE.REQUIREMENTS FOR POWER, MOUNTING, CABLE MANAGEMENT, COOLING, AND OTHERMISCELLANEOUS COMPONENTS REQUIRED FOR A FULLY FUNCTIONING SYSTEM ARE ASSUMEDAND SHALL BE PROVIDED BY THE CONTRACTOR.

TO NETWORKBY OTHERS

TO NETWORKBY OTHERS

TO NETWORKBY OTHERS

TO NETWORKBY OTHERS

8 OHM

8 OHM

(EXISTING) (EXISTING)

SMARTLECTURN

CABLE POCKET

DETAILAV-D1

TO NETWORKBY OTHERS

L/R/C & SURROUND(QTY. 7)

TO NETWORKBY OTHERS

CC

16:10 ELECTRIC

RECESSED

SCREEN

*

57.5" x 92"

TENSIONED

ADVANTAGE 109"

DIAGONAL

SCREEN SWITCH

*

AS REQUIRED

COMPUTER(OFCI)

ASSISTEDLISTENING

SYSTEM(OFOI)

SMART LECTERN

MT-400-UCCS-MAPLE-NATURAL -7302

BLU-RAY PLAYER

*

DN-500BD

DIGITALMEDIA

PRESENTATION

SYSTEM

*

DMPS3-4k-150-C

TOUCHPANEL 7"

*

TSW-752

TABLE STAND

KIT

FOR TSW-750

TSW-750-TTK-X-S

DOCUMENT

CAMERA

*

VZ-3

POE SWITCH 5

PORT

CEN-SW-POE-5PROJECTOR

*

G6470WU

CEILING

SUBWOOFER

*

CONTROL 312CS

SURROUND

SOUND

PROCESSOR

*

HD-XSP

8 CHANNEL AUDIO

AMPLIFIER

*

DCi 8 | 300

WALL SURFACE

LOUDSPEAKER

*

CDD5x

CEILING SUB WOOFER -

BACKBOX

MTC-300BB12

CEILING SUB WOOFER -

GRILLE

MTC-300SG12

HDBT

INTERFACE

PLATE

CUSTOM

As Required

HDMI SWITCHER -

4K

*

HD-MD4X1-4K-3

APPLE TV

*

APPLE TV

SPKR

HDBT

HDMI

HDMI

CC

USB

CC

HDMI

RS232

IP

POE

IP

IP

IP

LM (QTY. 8)

SPKR

HDMI

MIC

LM (FROM HD-XSP)

VGA

LL LR

CV

LL LR

LM

IP

HDMI

HDMI

HDMI IP

IP

TYPE DESCRIPTION MANUFACTURER PART NUMBER SPECIAL RQMTS

SURROUND SOUND PROCESSOR CRESTRON HD-XSP

8 CHANNEL AUDIO AMPLIFIER CROWN DCi 8 | 300

S

CEILING SUBWOOFER JBL CONTROL 312CS

CEILING SUB WOOFER - BACKBOX JBL MTC-300BB12

CEILING SUB WOOFER - GRILLE JBL MTC-300SG12

WALL SURFACE LOUDSPEAKER MARTIN CDD5x MOUNTING BRACKET AS REQ.

DOCUMENT CAMERA WOLFVISION VZ-3

BLU-RAY PLAYER DENON DN-500BD

HDMI SWITCHER - 4K CRESTRON HD-MD4X1-4K-3

DIGITALMEDIA PRESENTATION SYSTEM CRESTRON DMPS3-4k-150-C

A PROJECTOR EPSON G6470WU

APPLE TV APPLE APPLE TV

TOUCHPANEL 7" CRESTRON TSW-752

TABLE STAND KIT FOR TSW-750 CRESTRON TSW-750-TTK-X-S

POE SWITCH 5 PORT CRESTRON CEN-SW-POE-5

SMART LECTERN ATF MT-400-UCCS-MAPLE-NATURAL-7302

POWER CONDITIONER FURMAN P-8 PRO II AS REQUIRED

INTERFACE PLATE CUSTOM RCI CUSTOM As Required

SPEAKON NEUTRIK As Required

ETHERCON CAT6A SHIELDED NEUTRIK As Required For Digital Media

Net Connect Cable XG620 4pr 23 AWG CMP Yellow Jacket AMP 4-1499416-7 For Digital Media

DISPLAY POLE MOUNTING HARDWARE CHIEF AS REQUIRED REUSE EXISTING

PROJECTOR MOUNT CHIEF RPAU REUSE EXISTING

T4.022

TE02

TE03

A

TE02

TE02

TE02S

B

61W

2

STA03

TA03

TE01

TE01

TE01

TA01

TE05

TA01

FLOOR

CEILING

A.

B.

C.

ALL MEASUREMENTS ARE TO CENTER UNLESS OTHERWISE NOTED.

STUB ALL CONDUITS TO ACCESSIBLE CEILING SPACE OF SAME ROOMUNLESS OTHERWISE ILLUSTRATED/NOTED IN RISER DIAGRAM.

ADDITIONAL CONDUITS FOR TELECOMM OR POWER MAY BE REQUIRED.REFERENCE DEVICE DETAILS AND TELECOMM AND ELECTRICAL PLANS.

RISER GENERAL NOTES

(1) 3/4-INCH CONDUIT

+90"(2) 1-INCH CONDUITS

IF

(2) 1 1/4-INCH CONDUITS

+18" IF+18"

(2) 1 1/4-INCH CONDUITS

(REF. DETAIL TA-IFER)

2

IF+18"

A

(2) 1 1/4-INCH CONDUITS

1.

2.

REFER TO ENLARGED FLOOR PLAN AND RELEVENT KEYNOTES FORSPEAKER OUTLET BOX QUANTITY AND LOCATION INFORMATION.AUDIOVISUAL CONTRACTOR SHALL REVIEW SPEAKER MOUNTING BRACKETAND WIRE MANAGEMENT AND COORDINATE EXACT REQUIREMENTS WITHOWNER.

REFERENCE DETAIL TA-IFER FOR GENERAL LAYOUT INFORMATION ANDASSUMED ELECTRICAL AND TELECOMM REQUIREMENTS TO BE CONFIRMEDBY OWNER. PROVIDE A BLANK PLATE FOR ONE OF THE BOXES TO BE LEFTAS SPARE FOR FUTURE USE.

RISER DRAWING NOTES

A

1

(1) 3/4-INCH CONDUIT

GENERAL NOTES

EQUIPMENT SCHEDULE

© Copyright BCER Engineering Inc.

Copyright reserved. All parts of this drawing are the exclusive

property of BCER Engineering and shall not be used or

reproduced in any manner without express written consent.

Client:

Project #:

Designed By:

Drawn By:

Approved By:

Scale:

No DateDescription

ISSUE RECORD

100% CONSTRUCTION DOCUMENTS

10/23/2015

As indicated

TECHNOLOGY SPACEPLANS

UCCS

CO

LO

MB

INE

HA

LL A

UD

IOV

I SU

AL U

PG

RA

DE

S

RIMROCK

RIMROCK

81515004

UN

IVE

RS

ITY

OF C

OL

OR

AD

O C

OLO

RA

DO

SP

RIN

GS

RIMROCK

T4.02

AU

ST

IN B

LU

FF

S P

KW

Y, C

OLO

RA

DO

SP

RIN

GS

, C

O 8

091

8

N

0 4'4' 2'

T4.02

1/4" = 1'-0"

1 FILM SCREENING CLASSROOM ENLARGED FLOOR PLAN

0 4'4' 2'

T4.02

1/4" = 1'-0"

2 FILM SCREENING CLASSROOM PRESENTATION WALL ELEVATION

T4.02

3 FILM SCREENING CLASSROOM RISER DIAGRAM

T4.02

4 FILM SCREENING CLASSROOM ONE-LINE DIAGRAM

KEYNOTES

TA01 CENTER SPEAKER ON SCREEN AND LOCATE SPEAKER OUT OF LINE OF SIGHT FROMSEATED POSITION IN BACK ROW TO THE TOP OF PROJECTION SCREEN.

TA03 PROJECTOR SCREEN AND SWITCH ARE EXISTING TO REMAIN.

TE01 PROVIDE SPEAKER OUTLET BOXES WITH APPROPRIATE BACKING (AS REQUIRED)FOR CEILING SURFACE MOUNTED SPEAKERS. CENTER MIDDLE OUTLET BOXHORIZONTALLY ON SCREEN. LOCATE ALL THREE OUTLET BOXES (4) FOUR FEETFROM WEST (PRESENTATION) WALL. LOCATE LEFT AND RIGHT OUTLET BOXES (4)FOUR FEET FROM SIDE WALL. PROVIDE BACKING (AS REQUIRED) IMMEDIATELYADJACENT TO BOX AND EXTEND EAST (TOWARD CENTER OF ROOM) AS FAR ASDRYWALL SLOPE CONTINUES, APPROXIMATELY (7) SEVEN FEET FROM WEST(PRESENTATION) WALL.

TE02 LOCATE OUTLET BOX AS HIGH AS POSSIBLE ON WALL. COORDINATE LOCATION WITHAV CONTRACTOR PRIOR TO PERFORMING ANY WORK.

TE03 PROVIDE EMPTY 4 11/16" DEVICE BOX WITH SINGLE GANG MUD RING AND BLANKCOVER PLATE FOR FUTURE CAMERA INTERFACE ADJACENT TO SCREEN. LOCATEIMMEDIATELY ABOVE WRITING SURFACE APPROXIMATELY (7) SEVEN FEET (6) SIXINCHES AFF. LOCATE TO SIDE OF SCREEN NEAREST LECTERN APPROXIMATELY (1)ONE FOOT FROM EDGE OF SCREEN.

TE05 AS ROOM LAYOUTS VARY, LOCATIONS SHALL BE REVIEWED AND CONFIRMED DURINGTHE MANDATORY CONSTRUCTION KICKOFF MEETING PRIOR TO PERFORMING ANYWORK. REFER TO RISER DIAGRAM ON TECHNOLOGY SPACE PLAN AND DETAILTA-IFER FOR GENERAL INFORMATION AND REQUIREMENTS. THE TYPICAL ORDER OFOUTLET BOXES FROM FRONT TO BACK OF THE ROOM SHALL BE: SCREEN SWITCH,TELEPHONE OUTLET, DATA OUTLET, AV INTERFACE PLATES, THEN ELECTRICALOUTLET.

mfalcon
Text Box
ADD ALTERNATE #1
mfalcon
Text Box
PROVIDE HARD CONDUITS FOR NEW AV, TELECOM AND POWER OUTLETS
mfalcon
Rectangle
mfalcon
Text Box
BASE BID:
mfalcon
Text Box
PROVIDE FLEX CONDUITS FOR NEW AV, TELECOM AND POWER OUTLETS
mfalcon
Rectangle
Page 10: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,

EXTRON AAP SCHEDULE

Qty Part # Model Name1 60-300-02 AAP 102

1 70-103-18 One XLR 3-pin Male to Solder Cups, One XLR 3-pin Female to Solder Cups - Neutrik

1 60-1346-02 USB PowerPlate 200 AAP (Single-space)

1 70-092-72 Three RCA Female to Solder Cup (Silkscreen)

SCALE:

BACK BOX DETAIL FOR AV LECTERN LOCATIONSNONE

TA-IFER

INSULATED THROATBUSHING

BEND RADIUS = 6x INTERNALDIAMETER

2 GANGMUDRING

STUB CONDUIT6-INCHES INTOACCESSIBLECEILING UNLESSOTHERWISENOTED

FLOOR(REF:ARCHITECTURAL)

AV OUTLET BOX4 11/16 - INCH SQUAREMIN 2 1/8 - INCH DEEP BOX

SEE AVRISER

DIAGRAM

TELECOM OUTLET BOX4 11/16 - INCH SQUAREMIN 2 1/8 - INCH DEEP BOX

DUPLEX POWERRECEPTACLE(REF: ELECTRICAL)

1 GANGMUDRING

16" O.C.TYP.

FRAMING

CEILING LEVEL(REF:ARCHITECTURAL)

WALL(REF:ARCHITECTURAL)

#

MATCH TOLIGHT

SWITCHMOUNTING

HEIGHT

A. LOCATIONS SHALL BE REVIEWED ANDCONFIRMED DURING THE MANDATORYCONSTRUCTION KICKOFF MEETING. REFERTO RISER DIAGRAM AND TECHNOLOGYFLOOR PLAN FOR ADDITIONALINFORMATION AND REQUIREMENTS.

DETAIL GENERAL NOTES

TELECOM OUTLET BOX4 11/16 - INCH SQUAREMIN 2 1/8 - INCH DEEP BOX

#

INSULATED THROATBUSHING

BEND RADIUS = 6x INTERNALDIAMETER

2 GANGMUDRING

STUB CONDUIT6-INCHES INTOACCESSIBLE CEILINGUNLESS OTHERWISENOTED

AV CABLING

SCALE:

BACK BOX DETAIL FOR AV WALL INTERFACENONE

TA-IFW

AV OUTLET BOX4 11/16 - INCH SQUAREMIN 2 1/8 - INCH DEEP BOX

AVC AVC

IF

SEE AVRISER

DIAGRAM

FLOOR(REF:ARCHITECTURAL)

CEILING LEVEL(REF:ARCHITECTURAL)

WALL(REF:ARCHITECTURAL)

SCALE:

CEILING SPEAKER DETAILSNONE

TA-CSD

TRIM RING

LOUDSPEAKERCUTOUT AREA

LOUDSPEAKER

AVC AVCAVC AVC

AVC AVC

CONDUIT

4" x 4"ELECTRICAL BOX

LOUDSPEAKERCABLE

EC EC

EC EC

A

A.

B.

C.

LOCATE ELECTRICAL BOX AND CONDUITOUTSIDE OF LOUDSPEAKER CUTOUT AREA.COORDINATE WITH AUDIO VISUAL CONTRACTORPRIOR TO CONDUIT INSTALLATION.

MOUNT EYE BOLT ONTO CUSTOMMANUFACTURED DEVICE BOX FACEPLATE.FACEPLATE MADE OF 1/8-INCH ALUMINUM WITH1/2-INCH PASS THRU HOLE FOR CABLE SET OFFCENTER.

UTILIZE THEATER GRADE RIGGING HARDWAREINCLUDING BUT NOT LIMITED TO: AIRCRAFTCABLE, CABLE CLIPS, CABLE THIMBLES AND EYEBOLTS.

DETAIL GENERAL NOTES

FORGEDEYE BOLT

AIRCRAFT CABLE

THREADED ROD

FACEPLATE

CEILING FANTYPE DEVICEBOX

CONDUIT

CEILING(REF: ARCHITECTURAL)LOUDSPEAKER

CABLE

LOUDSPEAKERCABLE

TO STRUCTURE

HANGER WIRE

TILE BRIDGE

LOUDSPEAKERCUTOUT AREA

AVC AVC

AVC AVC

ACCESSIBLE CEILING(REF: ARCHITECTURAL)

LOUDSPEAKER

AVC AVC

LOUDSPEAKER

AVC AVC

AVC AVC

AVC AVC

AVC AVC

AVC AVC

ACCESSIBLE CEILING NON-ACCESSIBLE CEILING

PENDANT CEILING

PA NA

NON-ACCESSIBLE CEILING(REF: ARCHITECTURAL)

A A

A

N

P

EC EC

AIRCRAFT CABLETO STRUCTURE

AVC AVC

SCALE:

CEILING RECESSED SCREEN DTL.NONE

TA-CRS

UNISTRUTSTRUCTURALSUPPORT ONEFOOT LONGERTHAN CASE

THREADEDROD

MOUNT TOUNISTRUTSUPPORT

CONNECTPOWER TOSCREEN OR LOWVOLTAGECONTROLLER ASREQUIRED(REF:ELECTRICAL)

CEILING(REF:ARCHITECTURAL)

ATTACH TOSTRUCTURE

SCREEN -BOTTOM OFVIEWABLEAREA SHALLBE 48" AFFUON. PROVIDEEXTRA DROPAS REQUIRED.

AVC AVC

AVC AVC

INSULATED THROATBUSHING

BEND RADIUS = 6x INTERNALDIAMETER

MUDRING(REF: TABLE FOR SIZE)

STUB CONDUIT6-INCHES INTOACCESSIBLE CEILINGUNLESS OTHERWISENOTED

AV CABLING

SCALE:

BACK BOX DETAIL FOR AV WALL INTERFACE REQUIRING BACKINGNONE

TA-IFB

AV OUTLET BOXMIN 2 1/8 - INCH DEEP BOX

AVC AVC

16" O.C.TYP.

FRAMING(REF: ARCHITECTURAL)

BACKINGBOARD

AA A

TYPE BOX

-- 2

A 2

-- --

MUDRING

2

1

--

GANG SIZE

SEE AVRISER

DIAGRAM

GC GC

FLOOR(REF:ARCHITECTURAL)

CEILING LEVEL(REF:ARCHITECTURAL)

WALL(REF:ARCHITECTURAL)

SCALE:

BACK BOX DETAIL FOR AV DEVICE CONTROLNONE

TA-VCW

MATCH TOLIGHT

SWITCHMOUNTING

HEIGHT

FLOOR(REF:ARCHITECTURAL)

CEILING LEVEL(REF:ARCHITECTURAL)

WALL(REF:ARCHITECTURAL)

INSULATED THROATBUSHING

BEND RADIUS = 6x INTERNALDIAMETER

1 GANGMUDRING

STUB CONDUIT6-INCHES INTOACCESSIBLE CEILINGUNLESS OTHERWISENOTED

AV CABLING

AV OUTLET BOX4 11/16 - INCH SQUAREMIN 2 1/8 - INCH DEEP BOX

AVC AVC

A VCA S

SCALE:

TABLE TOP INTERFACE DETAILNONE

TA-TTIF IF T

© Copyright BCER Engineering Inc.

Copyright reserved. All parts of this drawing are the exclusive

property of BCER Engineering and shall not be used or

reproduced in any manner without express written consent.

Client:

Project #:

Designed By:

Drawn By:

Approved By:

Scale:

No DateDescription

ISSUE RECORD

100% CONSTRUCTION DOCUMENTS

10/23/2015

As indicated

TECHNOLOGY DETAILS

UCCS

CO

LO

MB

INE

HA

LL A

UD

IOV

I SU

AL U

PG

RA

DE

S

RIMROCK

RIMROCK

81515004

UN

IV

ER

SIT

Y O

F C

OL

OR

AD

O C

OLO

RA

DO

SP

RIN

GS

RIMROCK

T5.01

AU

ST

IN B

LU

FF

S P

KW

Y, C

OLO

RA

DO

SP

RIN

GS

, C

O 8

091

8

mfalcon
Text Box
ADD ALTERNATE #1
mfalcon
Text Box
PROVIDE HARD CONDUITS FOR NEW AV, TELECOM AND POWER OUTLETS
mfalcon
Rectangle
mfalcon
Text Box
BASE BID:
mfalcon
Text Box
PROVIDE FLEX CONDUITS FOR NEW AV, TELECOM AND POWER OUTLETS
mfalcon
Rectangle
Page 11: Columbine Hall - Third Floor Classrooms AV Upgrade1420 Austin … · 2018. 4. 18. · Columbine Hall - Third Floor Classrooms AV Upgrade. 1420 Austin Bluffs Parkway, Colorado Springs,

SCALE:

PROJECTOR MOUNT DETAILSNONE

TA-PMD

FRONT VIEW

FRONT VIEW FRONT VIEWFRONT VIEW

PLENUM CEILING

ACCESSIBLE CEILING EXPOSED CEILINGNON-ACCESSIBLE CEILING

CEILING TILE(REF: ARCHITECTURAL)

POLE

AVC AVC

PROJECTOR MOUNT

AVC AVC

PROJECTOR

AVC AVC

CEILING GRID(REF: ARCHITECTURAL)

POWER(REF: ELECTRICAL)

AV CABLING

AVC AVC

TELECOM OUTLET BOX4 11/16 - INCH SQUARE1 GANG MUD RINGMIN 2 1/8 - INCH DEEP BOX

DUPLEX POWERRECEPTACLE(REF: ELECTRICAL)

E

A.

B.

C.

D.

E.

F.

UNI-STRUT FRAMEWORK SHOULD BE PROVIDED TOALLOW PROJECTOR TO BE MOUNTED ANYWHERE INFRONT HALF OF THROW RANGE OF SPECIFIEDPROJECTOR AND LENS.

COORDINATE WITH ARCHITECT AND AUDIOVISUALCONTRACTOR FOR PROJECTOR PLACEMENT PRIORTO INSTALLING PROJECTOR STRUCTURAL SUPPORT.

USE RIGID CONDUIT FOR ALL OUTLET BOXES.

MOUNT PROJECTOR IN SUCH A WAY AS NOT TO BEOBSTRUCTED BY LIGHT FIXTURES, SPRINKLERHEADS, ETC.

DIGITAL KEYSTONE CORRECTION SHALL NOT BEUSED. PROJECTOR SHALL BE LOCATED ANDADJUSTED FIRST BY MOUNT THEN BY OPTICALADJUSTMENT(S) SO THE IMAGE IS FREE OF ANYKEYSTONING OR OTHER DISTORTION AND FILLSPROJECTION SCREEN/AREA.

MOUNT PROJECTOR AS CLOSE TO THE CEILING ASPOSSIBLE. REFER TO GENERAL NOTES D AND EAND ARCHITECTURAL DRAWINGS.

DETAIL GENERAL NOTES

N

CEILING TILE(REF: ARCHITECTURAL)

POLE MOUNT

AVC AVC

THREADEDROD

CEILING GRID(REF: ARCHITECTURAL)

DUPLEX POWERRECEPTACLE(REF: ELECTRICAL)

POLE

ESCUTCHEON RING

AVC AVC

AVC AVC

AV OUTLET BOX4 11/16 - INCH SQUARE2 GANG MUD RINGMIN 2 1/8 - INCH DEEP BOX

TELECOM OUTLET BOX4 11/16 - INCH SQUARE1 GANG MUD RINGMIN 2 1/8 - INCH DEEP BOX

THREADED ROD

FIXED CEILING(REF: ARCHITECTURAL)

POLE MOUNT

AVC AVC

AV OUTLET BOX4 11/16 - INCH SQUARE2 GANG MUD RINGMIN 2 1/8 - INCH DEEP BOX

TELECOM OUTLET BOX4 11/16 - INCH SQUARE1 GANG MUD RINGMIN 2 1/8 - INCH DEEP BOX

THREADEDROD

DUPLEX POWERRECEPTACLE(REF: ELECTRICAL)

POLE

ESCUTCHEON RING

AVC AVC

AVC AVC

PROJECTOR MOUNTNOT SHOWN

PROJECTOR MOUNTNOT SHOWN

PROJECTOR MOUNTNOT SHOWN

A N E

A

THREADED RODMOUNTING KIT

EDGE-PROTECTEDBUNDLED CABLE INLETCAVITY ON EACH SIDEOF BOX, FILLED WITHFLAME RETARDANTFOAM SEAL

KNOCKOUTFOR TELECOM UNI-STRUT

STRUCTURALSUPPORT FRAME

POLE

UNI-STRUTSTRUCTURALSUPPORT FRAME

POLE MOUNT

AVC AVC

AVC AVC

AV CABLING

AVC AVC

UNI-STRUTSTRUCTURALSUPPORT FRAME

ATTACH TOSTRUCTURE

ATTACH TOSTRUCTURE

ATTACH TOSTRUCTURE

ATTACH TOSTRUCTURE

ATTACH TOSTRUCTURE

ATTACH TOSTRUCTURE

ATTACH TOSTRUCTURE

ATTACH TOSTRUCTURE

#

#

THREADED ROD

#

# # #

#

#

# ###

EC EC

PLENUM ENCLOSURE(REF AV TECHNOLOGY PLANS)

BOTTOM VIEW BOTTOM VIEW BOTTOM VIEWSCREEN SCREEN SCREEN

CEILINGPLATE

AVC AVC

1

1. REUSE EXISTING PROJECTOR MOUNTINGSTRUCTURE. PROVIDE NEW TELECOM OUTLETBOX.

DETAIL DRAWING NOTES

© Copyright BCER Engineering Inc.

Copyright reserved. All parts of this drawing are the exclusive

property of BCER Engineering and shall not be used or

reproduced in any manner without express written consent.

Client:

Project #:

Designed By:

Drawn By:

Approved By:

Scale:

No DateDescription

ISSUE RECORD

100% CONSTRUCTION DOCUMENTS

10/23/2015

NONE

TECHNOLOGY DETAILS

UCCS

CO

LO

MB

INE

HA

LL A

UD

IOV

I SU

AL U

PG

RA

DE

S

Author

Designer

81515004

UN

IV

ER

SIT

Y O

F C

OL

OR

AD

O C

OLO

RA

DO

SP

RIN

GS

Approver

T5.02

AU

ST

IN B

LU

FF

S P

KW

Y, C

OLO

RA

DO

SP

RIN

GS

, C

O 8

091

8