Code of Practice for the Application of Coating
-
Upload
ugoribeiro -
Category
Documents
-
view
215 -
download
0
Transcript of Code of Practice for the Application of Coating
-
7/29/2019 Code of Practice for the Application of Coating
1/17
1
A
RCHIVE
Code of Practice
for the application of
coatings by spraying of
electrostatic powders
-
7/29/2019 Code of Practice for the Application of Coating
2/17
Published by the
Occupational Safety and Health Service
Department of Labour
New Zealand
Code first issued 1975
Code revised 1980
Reformatted 2004
-
7/29/2019 Code of Practice for the Application of Coating
3/17
TABLE OF CONTENTS
1 GENERAL 4
1.1 Introduction 4
1.2 Legislative Requirements 51.3 Spray Booths and Collection Units 5
1.4 Fire and Explosion Hazards 5
1.5 Toxicity Hazard 6
1.6 Electrostatic Powder Coating Guns 6
2 PLANT DESIGN AND OPERATION 7
2.1 Principles of Hazard Reduction in Plant Design 7
2.2 Design of Spray Booth 8
2.3 Design and Operation of Powder Extraction and Collection Systems 82.4 Explosion Prevention Using Single-Factor Method 8
2.5 Explosion Prevention Using Double-Factor Method 9
2.6 Protection of Plant from Effect of Dust Explosions 10
2.7 Ovens 11
2.8 Protection of Operators Health 11
2.9 Cleaning 11
2 10 General 11
3 ELECTRICAL EQUIPMENT 12
3.1 General 12
3.2 Electrical Equipment in the Hazardous Area 12
3.3 Earthing in the Hazardous Area 13
3.4 Electrostatic Powder Coating Guns 13
APPENDIXA Examples of Powder Concentration and Lower
Explosive Limit Calculations 14
APPENDIX B Explosive Characteristics of Plastic Powders(Representative Values) 15
APPENDIX C Examples of Possible Arrangements for Powder
Collection Units 15
APPENDIX D 17
-
7/29/2019 Code of Practice for the Application of Coating
4/17
4
ARCH
IVE1. GENERAL
1.1 Introduction
1.1.1 The purpose of this Code is to indicate the potential hazards in electrostatic
powder coating and to specify the means by which these hazards may be
minimised.
1.1.2 The Code is divided into three parts:
(1) A general section;
(2) A section which gives mainly special details for compliance with the
Factories Act 1946 and the Spray Coating Regulations 1962; and
(3) A section which gives mainly special details for compliance with the
Electrical Wiring Regulations 1976.
1.1.3 Electrostatic powder coating is a process whereby particles are charged
electrostatically to a high voltage and then deposited upon the surface of an
earthed object.
Coating with powder by the electrostatic spraying technique is similar in
principle to electrostatic spray coating with paint. The primary difference is the
absence of solvent; paint is sprayed as a suspension in a solvent base, whereas
powders are applied as fine particles in a dry condition.
1.1.4 The absence of solvent in dry powder applications removes the problems of
paint overspray, solvent fumes and odours, and the risk of fire from flammable
liquids. However, it does not eliminate hazards. Fine plastic powders in
suspension in air can give rise to dust explosions, and can be injurious to health
if inhaled in sufficient quantities. Precautions must be taken to reduce these
hazards to an acceptable level. If adequate precautions are adopted at the
outset, costly modifications to equipment will be avoided later.
1.1.5 Powder should only be sprayed in a booth, as for spray painting, but unlike
wet paint overspray, the oversprayed powder can be recovered and re-used.
For powder spraying the booth is backed up by powder collection units, to
which the powder is conveyed in the ventilating air stream via connecting
ducting.
1.1.6 Not all plastic powders are combustible or provide the same hazards from fire
and explosion. The majority of powders used at present in New Zealand are
epoxy resins and these powders have the greatest explosion hazard. Polyester
powders have a similar explosion hazard rating and other powders such as
acrylic and polythene have lower explosibilities.
1.1.7 Although a dust cloud of polyvinyl chloride (PVC) powder is not explosive,
PVC may give rise to toxic fumes during curing in ovens. Polyurethane
powders may also give rise to irritant fumes during curing, hence ovens using
these powders must be ventilated.
1.1.8 As with paint, electrical equipment which sparks or has a hot surface could bea hazard, but it requires a higher energy spark and a higher temperature than
that for a flammable vapour in order to ignite a dust cloud. The electrical
-
7/29/2019 Code of Practice for the Application of Coating
5/17
5
A
RCHIVE
equipment also requiries a different construction than that for flammable
vapours in order to protect against the risk of a dust explosion or fire.
1.2 Legislative Requirements
1.2.1 For electrostatic powder coating compliance with this Code will be accepted
by the Department of Labour as satisfactory in meeting the requirements ofSection 48A of the Factories Act 1946, which requires all practicable steps
to be taken to eliminate the hazards from explosible dusts.
1.2.2 Regulation 37 of the Spray Coating Regulations 1962 requires spray coating
by electrostatic means to be authorised in writing by the Chief Inspector of
Factories. Compliance with this Code provides the conditions under which the
Chief Inspector will issue authorisation. Any alteration such as the use of a
different electrostatic powder coating gun requires a new approval.
1.2.3 Compliance with this Code will be accepted as meeting Regulations 67 and 94
of the Electrical Wiring Regulations 1976.
1.2.4 Emissions from the powder collector to the outside air must comply with the
Clean Air Act 1972. An efficient cyclone would normally be sufficient to meet
this requirement.
1.3 Spray Booths and Collection Units
1.3.1 Spray booths are normally either cabinet or tunnel booths. Cabinet booths
may either have an opening in the front of the booth and some method of
suspending objects from the roof of the booth or have openings in each end as
well as the front to allow a conveyor to transport objects through the booth.
Tunnel booths are always open at each end and may also have an opening inthe side to allow for the operator, or may be automatic with only a small
opening to convey the feed-line, or may have an operator located inside the
booth.
1.3.2 The powder is collected from the bottom of the booth so that there is little
powder accumulation in the booth.
1.3.3 The collection unit usually consists of an efficient cyclone, or two or more such
cyclones in parallel.
1.3.4 The small amount of powder escaping from the cyclone/cyclones may also be
collected using one of the following methods:
(i) a fabric filter,
(ii) a second cyclone, and
(iii) a wet (water spray) collector.
1.3.5 A fabric filter may also be used for powder collection without a cyclone, but
because of size and other requirements (i.e. explosion venting) this normally
would be much more expensive.
1.4 Fire and Explosion Hazards
1.4.1 Most of the powder used will burn in any concentration and will present a firehazard in all situations.
1.4.2 The particle size of the powders is in the range which produces dust
explosions.
-
7/29/2019 Code of Practice for the Application of Coating
6/17
6
ARCH
IVE1.4.3 The concentration of powder in air must be above a minimum value termed the
lower explosive limit (LEL) in order for an explosion to occur. The LEL
value changes with the type of powder in use (see Appendix B), but will be in
the range 20 - 60 g/m3for explosible powders.
1.4.4 There is also a maximum concentration of powder in air above which
explosions will not occur. This figure is of the order of several kilograms per
cubic metre, but is very ill-defined and in practice could not be stated with any
degree of accuracy. It is safer, therefore, to assume that the powder can
explode at all concentrations above the minimum value.
1.4.5 A cloud of powder in air, which is of sufficient concentration, will explode only
if an ignition source is present.
1.4.6 The source of ignition must be of the required energy for it to ignite a dust
cloud. This is referred to as the minimum ignition energyand is normally
expressed in joules or millijoules. Most values fall in the 10 to 40 millijoules
range (see Appendix B).
1.4.7 The source of ignition must be at a certain minimum temperature to ignite adust cloud. This is referred to as the ignition temperature. Typical values for
a dust cloud range from 4000C to 5500C (see Appendix B). It should be
noted that a layer of dust will ignite at considerably lower temperatures than a
dust cloud; the thicker the layer of dust the lower the ignition temperature.
1.4.8 There are a number of possible sources of ignition such as electrical
equipment, cigarettes and matches, unearthed conductors producing static
electricity, naked flames and hot surfaces.
1.4.9 The whole workroom containing the powder spraying and collection
equipment can be at great risk if accumulations of powder are allowed to arise
in this area.
1.5 Toxicity Hazard
1.5.1 Generally powders used in coating operations have a low order of toxicity and
there is little risk to health in handling and using of powders. As with all dusts,
inert or otherwise, inhalation must be avoided (especially for particles of 10
micron diameter or less), and concentrations of powder in the working
environment should not exceed 10mg per cubic metre.
1.5.2 There are no known instances of skin dermatitis resulting from contact with
epoxy powder used in the coating industry.1.5.3 The irritant fumes given off during curing of polythene powders have a TLV
of 5ppm (TWA) and 10ppm (STEL).
1.6 Electrostatic Powder Coating Guns
1.6.1 The electrostatic powder coating guns may be manual or automatic.
1.6.2 The electrostatic powder gun can, in certain cases, produce a spark when
brought into the proximity of an earthed object and the gun design must ensure
a limited spark energy.
1.6.3 The high voltage electrostatic field generated by the spray guns can build up a
charge of static electricity on any nearby object which is not earthed and which
is capable of accumulating a charge. Unearthed conductors, such as metallic
-
7/29/2019 Code of Practice for the Application of Coating
7/17
7
A
RCHIVE
objects, are the most likely to accumulate charge, although poor conductors,
such as plastics, can also accumulate a charge but not to a level which is
dangerous for combustible dusts.
1.6.4 Because there is no New Zealand authority for testing electrostatic spray guns,
reliance must be placed on overseas specifications.
2. PLANT DESIGN AND OPERATION
2.1 Principles of Hazard Reduction in Plant Design
2.1.1 The fire risk of stored powder can be treated in the same way as for any other
combustible solid.
2.1.2 The risk of injury from suspended powder explosions or flash fires can be
eliminated by using at least one of three techniques:(1) by providing one means of preventing explosions where all possible
causes of failure have been considered and protection provided against
each possible cause of failure (see Section 2.4 single-factor
method);
(2) by providing two means of preventing explosions, where failure of
either of those means would be extremely rare (see Section 2.5
double-factor method); and
(3) by protecting the plant and surroundings from the effects of a dust
explosion (see Section 2.6).
Most plants do not simply use one of these techniques but use different techniques in
different parts of the plant (see Appendix C).
2.1.3 Eliminating all sources of ignition is not suitable as the sole means of protection
for a single-factor method. Controlling the powder concentration below 25%
of LEL is suitable for the single-factor. method. Collecting the powder in a
water spray would also be suitable (if powder collection was not required say
for one-off operations).
2.1.4 The two means of protection for the double-factor method, which can be
provided with extremely rare failure of either means, are:
(a) by keeping the powder concentration below 50% of the LEL; and
(b) by eliminating all sources of ignition.
2.1.5 There are three methods used to protect plant from the effectsof a dust
explosion:
(a) by providing a lightweight door or bursting panel designed to release at
a low pressure,
(b) by constructing the plant or enclosing the plant in a structure so that it
can sustain the full explosion pressure, and
(c) by using an explosion suppression system i.e. using early-sensing
detectors and rapid-acting extinguishers which contain chemical
suppressant.
2.1.6 Accumulations of powder in the workroom must be prevented by good work
methods and regular cleaning.
-
7/29/2019 Code of Practice for the Application of Coating
8/17
8
ARCH
IVE2.1.7 Inhalation of powder is avoided by providing sufficient air movement in the
breathing zone of operators. When this is not practical suitable protective
equipment must be provided and worn.
2.2 Design of Spray Booth
2.2.1 The booth shall be of substantial construction and must comply with theconstruction provisions of the Spray Coating Regulations 1962.
2.2.2 Walls, ceilings and floors shall be smooth and without any projections, so that
powder cannot easily collect in the booth and surfaces are easy to clean.
2.2.3 Floors of booths shall be designed to facilitate the movement of powder
towards exhaust points.
2.2.4 The oversprayed powder shall not be collected in the booth, but shall be
removed continuously from the booth and collected in a properly designed
powder collection system.
2.3 Design and Operation of Powder Extraction and Collection Systems
2.3.1 Each spray booth shall be provided with a powder collection system, which
shall continuously and effectively remove oversprayed powder from the booth
whilst spraying is in progress.
2.3.2 Powder collection units shall be designed to prevent any powder escaping into
the workroom. With manual booths an average air velocity of not less than 0.4
m/s through the main opening shall be maintained during spraying, while the
velocity in the breathing zone of the operator must be at least 0.3 m/s. The air
velocity through openings in the ends of a booth must be at least 0.2 m/s. For
completely automatic booths the air velocity must be at least 0.2 m/s throughany openings in a booth.
2.3.3 Air exhausted from collection systems shall be exhausted to the exterior of the
factory at a point not less than 3 metres above ground level, in a manner that
prevents its re-entry into the factory, unless all powder is effectively removed
from the returning air and explosion venting is not necessary in the plant item
which exhausts the air, e.g. a water wash system.
2.3.4 Air velocity through extraction ducting shall be sufficient to prevent settling of
powder in the ducting. There shall also be no sharp change of direction or of
cross-section in the ducting as this could cause powder to settle out at this
point.
2.3.5 In wholly automatic systems the booth shall contain a fire detection device
which will switch off the powder flow, high-voltage supply and ventilation
system in the event of a fire or explosion.
2.4 Explosion Prevention Using Single-Factor Method
2.4.1 The average concentration of powder in the extracted air from the booth shall
not exceed 25% of the LEL for that powder.
2.4.2 Values of LEL for various powders are given in Appendix B. For powders
whose LEL is not known then the value will be taken as 20 g/m . Where more
than one powder is used then the lowest LEL will become the design criteria.
-
7/29/2019 Code of Practice for the Application of Coating
9/17
9
A
RCHIVE
2.4.3 The average concentration of the coating powder in the booth is determined
from the maximum rate of powder that can be discharged from the guns in
relation to the volume of air extracted by the ventilation system at its lowest
capacity under operating conditions. See Appendix A for sample calculation.
2.4.4 A plate must be affixed to the booth showing the minimum air volume rate (see
Appendix A) and the design (actual) air volume rate. This plate shall conform
to the pattern shown in Figure 1 and be situated in a conspicuous position.
Markings on the plate shall be legible and permanent. If a new or additional
gun is used giving a different maximum powder flow rate, then the plate must
be altered to give the new minimum air flow rate (see also Section 1.2.2.).
2.4.5 Some means must be provided so that, in the event of the air rate falling below
the minimum, the powder supply to the spray gun will be cut off. An air flow
switch or a switch operating on a pressure differential can be used for this
purpose. If an air flow switch is installed, it must be on the clean side.
2.4.6 Although the concentration may be above the explosive limit close to the gun,
any explosion in this region would not be sustained outside and only a minorpuff would result from a source of ignition existing very close to the gun.
2.5 Explosion Prevention Using Double-Factor Method
2.5.1 The average concentration of powder in the extracted air from the booth shall
not exceed 50% of the LEL for that powder.
2.5.2 The criteria and details given in Sections 2.4.2, 2.4.3 and 2.4.4 will also apply
here.
2.5.3 The powder gun must be interlocked with the fan so that the powder gun
cannot be used without the fan also operating.2.5.4 The spray booth shall be constructed of, or lined with, a material which cannot
accumulate significant amounts of static electricity. Non-conductive and
earthed conductive materials are suitable. Painted conductive materials must
be earthed to protect against any damage to the paint film (see also
Section 3.3.1).
2.5.5 The hazardous area for any sources of ignition is the area within 2 m in any
direction of any opening in the spray booth. Only electrical equipment suitable
for Class II Division I hazardous locations will be allowed in the hazardous
area (see Section 3.2).
2.5.6 No naked flames or other source of ignition shall be permitted within thehazardous area. Earthing and other provisions are given in Section 3.3 and
3.4. If it is necessary to perform any welding on any part of the booth or
powder collection system, all traces of powder shall be removed from the
system prior to commencement.
2.5.7 No person shall smoke or be allowed to smoke in the hazardous area. A sign
stating No Smoking within 2 m in clear lettering shall be prominently
displayed on the spray booth.
2.5.8 Preheating of articles before entry to the spray booth shall not exceed 3000C.
2.5.9 Ovens operating within 2 m of the spray booth shall not have elements, orother heating device, situated within 2 m of the booth if the temperature of the
elements or device exceeds 3000C.
-
7/29/2019 Code of Practice for the Application of Coating
10/17
10
ARCH
IVE2.5.10 All fans in the collection system shall be situated on the clean side of the
collection units, and shall be of a type where the motor is fitted external to the
ducting. Downstream from the primary dust collector is considered to be on
the clean side.
2.6 Protection of Plant from Effect of Dust Explosions
2.6.1 If explosion suppression is used as the means to protect the plant, then it must
be designed and supplied by a firm with recognised expertise in this area.
2.6.2 If the plant is designed to withstand a pressure of 700 kPa, then no other
means of protection is necessary. Details of the plant design must be provided
when seeking approval. A flame arrestor or fast-acting valve must be installed
in the ducting close to the booth in order to prevent the flame front from any
explosion returning to the booth. The fast-acting valve should be activated by a
pressure or temperature detector located in the powder collector (or for a
suppression system).
2.6.3 If the plant is explosion vented, then either the plant should be located outsidethe building or the relief vent must be ducted to outside the building. The
explosion vents must discharge at least 3 m above the ground or be located in
an unfrequented place.
2.6.4 The explosion venting standard accepted by the Department of Labour is
National Fire Protection Association (N.F.P.A.) Code No. 68,Explosion
Venting Guide 1978.
If the plant is required to withstand pressure above 20 kPa, then details must
be provided, when seeking approval, to confirm that the plant can withstand
the design pressure. Suppliers of the collection system will also need to specify
the explosion venting area, the volume of the collecting vessel, the pressure at
which the vents release, and the length of the explosion relief ducting.
2.6.5 If the length of the explosion relief vent ducting is longer than 2 m, or if it
contains any bends greater than 10, then either the vessel and ducting must be
capable of withstanding a higher pressure than 20 kPa or the cross-section of
the explosion relief vent must be increased. A distance of 6 m is the maximum
allowable length for an explosion relief vent duct when either the cross-section
of the duct must be twice the area of the vent or the vessel must be capable of
withstanding twice the pressure required for that vent area based on N.F.P.A.
Code No. 68. The requirement for distances between 2 m and 6 m is found
by proportion, e.g. for 4 m the area or pressure must be increased by 50%.
2.6.6 If the dust collector has an unobstructed channel between where the powder is
collected and the rest of the collector, then the whole powder collector must
be explosion vented. A flame arrestor or fast-acting valve must also be
installed close to the booth.
2.6.7 If a cyclone uses a rotary valve or an automatically operated double-flap valve
to separate the collecting vessel from the rest of the collector, then only the
collecting vessel needs to be explosion vented or built to withstand 700 kPa.
This criteria also applies to a filter bag unit when it is used in addition to a
cyclone.
-
7/29/2019 Code of Practice for the Application of Coating
11/17
11
A
RCHIVE
2.7 Ovens
2.7.1 Powder shall not be allowed to escape into an oven from any source.
2.7.2 The temperature in the oven shall be kept below that at which the plastic will
degrade and produce fumes of the products of decomposition (i.e. normally
2400C). To achieve this a temperature controlling device shall be fitted to
control the temperature in the oven. The temperature controller mustincorporate a fail-safe device, e.g. a fusible link.
2.7.3 Ovens used to cure PVC or polyurethane powder must be vented to outside
the factory. At least 10 m of air per kg of polyurethane powder must be
provided in continuous ovens. Ovens used to cure other powders may not
need to be vented outside the factory depending on the size and operation of
the curing process.
2.8 Protection of Operators Health
2.8.1 No operator shall work, or be allowed to work, within a booth in such aposition that oversprayed powder is present in his breathing zone. The use of
respirators or airline helmets is not a substitute for adequate ventilation but an
approved airline helmet may be used in exceptional circumstances with the
written consent of the Chief Inspector of Factories.
2.8.2 A dust respirator of disposable or cartridge type (approved as suitable by the
Department of Health) shall be provided for use when filling feed hoppers, or
when handling powder in such a manner as is likely to raise a dust cloud.
Preferably cartridge type respirators should be issued individually.
2.8.3 For an automatic system entry to the spray booth shall be prohibited during
operation.
2.9 Cleaning
2.9.1 The spray booth, ducting, powder collection units and the surrounding
workroom area shall be effectively cleaned at regular intervals to prevent
accumulations of powder.
2.9.2 Cleaning shall preferably be carried out with an industrial vacuum cleaner, of a
type powered by compressed air or dust-excluding ignition-proof type of
electrical equipment. If the vacuum cleaning is not of this type, then it cannot
go into the hazardous area while spraying is in operation. A centralised vacuumcleaning system utilising a cyclone or bag filter unit is also acceptable provided
it has adequate protection against dust explosions.
2.9.3 Cleaning shall not be carried out by brushing, although sweeping deposits from
the inside of the booth directly into the collection system is permissible
provided the extraction system is kept in operation.
2.9.4 Powder which is not to be recovered for re-use shall be wetted before
disposal.
2.10 General
2.10.1 Operators of electrostatic powder spraying equipment shall be adequately
trained in the use of the equipment and this training shall be the responsibility of
the occupier.
-
7/29/2019 Code of Practice for the Application of Coating
12/17
12
ARCH
IVE2.10.2 Operators shall be made aware of the provisions of the Code where they
relate to the operator or to the operation of the booth. Such provisions shall be
made known to the operator by the occupier, before the equipment is used.
2.10.3 No flammable paints or solvents shall be used or kept within 2 metres of the
booth in a container made of conductive material unless they are earthed in
accordance with Section 3.3.2.
2.10.4 It is recommended that the inside surface of the booth, ducting and cyclone be
painted or coated with a nonconductor as then powder will be less likely to
stay on these surfaces. This will both reduce the explosion hazard and increase
the ease with which colour changes can be carried out. Two cyclones in
parallel may be used to make possible more rapid changes in colour.
Fig. 1 Plate to be affixed to spray booth indicating its air extraction capacity
DESIGN AIR VOLUME RATE m3/s
MINIMUM AIR VOLUME RATE m3/s
3. ELECTRICAL EQUIPMENT
3.1 General
3.1.1 All electrical equipment must comply with the Electrical Wiring Regulations
1976. An extract from the Australian SAA Wiring Rules published by SANZ,
MP 6105: 1976Electrical Wiring in Hazardous Locations, is also to be
used for guidance as it is intended to include most of this material in theElectrical Wiring Regulations.
3.1.2 When the average powder concentration in the spray booth be above 25% of
the LEL, then the concentration is sufficient to require designation of a
hazardous area. The area inside the spray booth and within 2 m of any
openings in the spray booth will be inside the hazardous area.
3.1.3 If because of poor housekeeping or other reasons there are considerable
quantities of explosive dust in the work area, this area shall also be designated
a hazardous area.
3.2 Electrical Equipment in the Hazardous Area
3.2.1 All electrical equipment, including portable equipment, used in the hazardous
area shall be installed with one or a combination of the following requirements:
(a) The equipment and circuitry shall be contained in a continuous
dust-excluding ignition-proof enclosure.
(b) The equipment is totally enclosed fan-cooled or totally enclosed
pipe-vented with no pipe opening within the hazardous area.
(c) The equipment has a special design which has been approved by the
above authorities.
3.2.2 The maximum surface temperature of all electrical equipment in the hazardous
area will not exceed 3000 C.
-
7/29/2019 Code of Practice for the Application of Coating
13/17
13
A
RCHIVE
3.2.3 Light fittings used to illuminate the interior of the booth and any other light
fittings within the hazardous area must comply with Section 3.2.1.
Alternatively, the fittings can be mounted outside the booth and separated from
the interior by dust-tight panels or wired or reinforced glass.
3.2.4 Plugs and plug sockets used in the hazardous area shall be provided with an
interlocking switch so arranged that the plug cannot be inserted or withdrawn
with the switch in the on position and that the switch cannot be in the on
position unless the plug is in the socket. The plug and plug socket shall be so
constructed and installed that powder will not accumulate in the socket.
3.3 Earthing in the Hazardous Area
3.3.1 The booth and powder collection unit if constructed of conductive material
shall be adequately earthed so that the resistance to earth does not exceed
10 ohm and this shall be checked at intervals not exceeding 6 months by a
competent person. A register shall be kept which is open to inspection.
3.3.2 The article being coated and all metallic equipment in and within 2 m of thebooth shall be adequately earthed while spraying is in progress. The resistance
to earth shall not exceed one megohm.
3.3.3 The earthing of articles being coated depends on the effectiveness of the hooks
carrying or holding the articles, and it may be necessary to carry out a regular
cleaning programme for the hooks to scrape or burn off any plastic coating.
Most electrostatic sprayguns will not work effectively once the resistance to
earth is above 50,000 ohms, hence this will indicate when the hooks need
cleaning.
3.3.4 A powder coating system manufactured by one company uses a technique
which overcomes the poor earthing of articles, hence where this system is
installed an earthing control unit must also be installed to prevent high energy
static discharges. At least one of the known suppliers of these earthing control
units has an agent in New Zealand (See Appendix D).
3.3.5 Operators of hand held spray guns shall wear conductive footwear* and shall
not wear gloves of an insulating nature, nor stand on insulating material.
3.3.6 Personnel approaching within 2 m of the booth during operation shall wear
conductive footwear* unless the powder used has a minimum energy which is
guaranteed to be above 25 mJ.
* Footwear which complies with NZS 5808Electrically conducting andantistatic rubber footwearis satisfactory.
3.4 Electrostatic Powder Coating Guns
3.4.1 Electrostatic powder coating guns must be interlocked with the fan in such a
manner that they cannot operate without the fan also operating (see Sections
2.4.5 and 2.5.3).
3.4.2 Electrostatic powder guns must be classified as instrinsically safe by some
recognised overseas authority such as BASEEFA (British Approvals Service
for Electrical Equipment in Flammable Atmospheres).3.4.3 Of the high voltage equipment only spray guns and the cables connected to
them may be sited inside spray booths. The high voltage generators, or any
-
7/29/2019 Code of Practice for the Application of Coating
14/17
14
ARCH
IVE
motor driven devices, shall be excluded from the interior of booths, except in
the case of approved spray-guns where the high-voltage generator is sealed
into the gun.
3.4.4 The high tension cables leading to guns shall be protected against damage
during operation.
APPENDIX A
Examples of Powder Concentration and Lower Explosive Limit Calculations
Suppose a booth is equipped with two spray guns both capable of a maximum
discharge rate of 5 g/s, then the total maximum discharge rate = 5 + 5 = 10 g/s.
If the air flow rate is 0.8 m3/s then the average powder concentration
= 10 (g/s,) = 12.5 g/m3
0.8 (m3 /s)
Suppose the powder being sprayed is epoxy, then the minimum air volume rate
for 50% of LEL
10 (g/s)
= = 0.38 m3/s
0.5 x 53 (g/m3) (see Appendix B)
and the minimum air volume rate for 25% of LEL
10 (g/s)
= = 0.76 m3/s
0.25 x 53 (g/m3) (see Appendix B)
-
7/29/2019 Code of Practice for the Application of Coating
15/17
15
A
RCHIVE
APPENDIX B
Explosion Characteristics of Plastic Powders (Representative Values)
(1) Results on a scale 0-100. 100 indicates severest hazard, 0 - no ignition under test conditions
APPENDIX C
Examples of Possible Arrangements for Powder Collection Units
Example A. In this example the booth uses the single-factor method while the cyclone
has both the single-factor method and protection against the effect of an
explosion (see Fig. 2).
Example B. In this example the booth uses the double-factor method while the
cyclone has protection against the effect of an explosion (see Fig. 3).
Example C. This type of cabinet is portable and has protection against the effect of an
explosion (see Fig. 4).
Type of
Powder
Epoxy
Polyester
Polyester
Modified Epoxy
Polyurethane
Polyvinyl
Chloride
Polythylene
Polyvinyl
Acetate
Nylon
Polypropylene
AcrylonitrilePolymer
Lower
Explosive
Limit
(g/m3)
53
40
45
25
Not ignitable
20
35
30
20
25
Minimum
Ignition
Energy
(mJ)
10-40
Not ignitable
10-40
Ignition
Temperature
Cloud of
Powder (00)
540
500
520
510
Not ignitable
410
520
500
420
500
Maximum
Explosion
Pressure
(kPa)
648
675
660
648
Not ignitable
552
517
655
524
620
Explosibility
Index
DSIR (1)
80
80
65
648
Not ignitable
20-66
0-10
50
Explosive
Dust
Class
2
2
2
Not ignitable
1 or 2
1
1
1
1 or 2
-
7/29/2019 Code of Practice for the Application of Coating
16/17
16
ARCH
IVE
Fig. 2 Example A
Fig. 3 Example B
KEY
1. Average concentration below 25%
of LEL (see 2.4.1)
2. Pressure-differential switch installed
(see 2.4.5)
3. Rotary valve installed (see 2.6.7)
4. Vessel built to withstand 700 kPa
(see 2.6.2 and 2.6.7)
5. Air exhausted outside factory (see 2.3.3)
6. No earthing of object required as special
type of gun used (see 3.3.4)
1
2
3
4
5
6
KEY
1. Hazardous area a set distance from
booth opening (see 2.5.5)
2. Average concentration below 50% of
LEL (see 2.5.1)
3. Object in booth earthed (see 3.3.2)
4. Booth constructed of nonconductive
material (see 2.5.4)
5. A flame arrestor or fast-acting valve
installed (see 2.6.6)
6. Powder gun interlocked with fan
(see 2.5.3)
7. Explosion vent installed (see 2.6.3)
8. Air exhausted outside factory (see 2.3.3)
1
2
3
4
56
7
8
-
7/29/2019 Code of Practice for the Application of Coating
17/17
A
RCHIVE
Fig. 4 Example C
APPENDIX D
At the time that this code was printed the following information was available:
Sames Company manufactures a gun which uses a technique which overcomes
poor earthing; and
Gema manufactures an earthing control unit (Nz agents - Gunn-Gollin Limited).
KEY
1. Average concentration below 50% of LEL
2. Electrodes installed - source of
ignition permissible as below LEL
3. Concentration above LEL
4. Explosion vent installed (see 2.6.3) - not
vented outside but has flame arrestor
(special case for portable unit)
5. Object in booth earthed (see 3.3.2)
6. Cabinet constructed of conductivematerial and therefore earthed
(see 2.5.4)
1
2
3
4
5
6