Code of Practice for the Application of Coating

download Code of Practice for the Application of Coating

of 17

Transcript of Code of Practice for the Application of Coating

  • 7/29/2019 Code of Practice for the Application of Coating

    1/17

    1

    A

    RCHIVE

    Code of Practice

    for the application of

    coatings by spraying of

    electrostatic powders

  • 7/29/2019 Code of Practice for the Application of Coating

    2/17

    Published by the

    Occupational Safety and Health Service

    Department of Labour

    New Zealand

    Code first issued 1975

    Code revised 1980

    Reformatted 2004

  • 7/29/2019 Code of Practice for the Application of Coating

    3/17

    TABLE OF CONTENTS

    1 GENERAL 4

    1.1 Introduction 4

    1.2 Legislative Requirements 51.3 Spray Booths and Collection Units 5

    1.4 Fire and Explosion Hazards 5

    1.5 Toxicity Hazard 6

    1.6 Electrostatic Powder Coating Guns 6

    2 PLANT DESIGN AND OPERATION 7

    2.1 Principles of Hazard Reduction in Plant Design 7

    2.2 Design of Spray Booth 8

    2.3 Design and Operation of Powder Extraction and Collection Systems 82.4 Explosion Prevention Using Single-Factor Method 8

    2.5 Explosion Prevention Using Double-Factor Method 9

    2.6 Protection of Plant from Effect of Dust Explosions 10

    2.7 Ovens 11

    2.8 Protection of Operators Health 11

    2.9 Cleaning 11

    2 10 General 11

    3 ELECTRICAL EQUIPMENT 12

    3.1 General 12

    3.2 Electrical Equipment in the Hazardous Area 12

    3.3 Earthing in the Hazardous Area 13

    3.4 Electrostatic Powder Coating Guns 13

    APPENDIXA Examples of Powder Concentration and Lower

    Explosive Limit Calculations 14

    APPENDIX B Explosive Characteristics of Plastic Powders(Representative Values) 15

    APPENDIX C Examples of Possible Arrangements for Powder

    Collection Units 15

    APPENDIX D 17

  • 7/29/2019 Code of Practice for the Application of Coating

    4/17

    4

    ARCH

    IVE1. GENERAL

    1.1 Introduction

    1.1.1 The purpose of this Code is to indicate the potential hazards in electrostatic

    powder coating and to specify the means by which these hazards may be

    minimised.

    1.1.2 The Code is divided into three parts:

    (1) A general section;

    (2) A section which gives mainly special details for compliance with the

    Factories Act 1946 and the Spray Coating Regulations 1962; and

    (3) A section which gives mainly special details for compliance with the

    Electrical Wiring Regulations 1976.

    1.1.3 Electrostatic powder coating is a process whereby particles are charged

    electrostatically to a high voltage and then deposited upon the surface of an

    earthed object.

    Coating with powder by the electrostatic spraying technique is similar in

    principle to electrostatic spray coating with paint. The primary difference is the

    absence of solvent; paint is sprayed as a suspension in a solvent base, whereas

    powders are applied as fine particles in a dry condition.

    1.1.4 The absence of solvent in dry powder applications removes the problems of

    paint overspray, solvent fumes and odours, and the risk of fire from flammable

    liquids. However, it does not eliminate hazards. Fine plastic powders in

    suspension in air can give rise to dust explosions, and can be injurious to health

    if inhaled in sufficient quantities. Precautions must be taken to reduce these

    hazards to an acceptable level. If adequate precautions are adopted at the

    outset, costly modifications to equipment will be avoided later.

    1.1.5 Powder should only be sprayed in a booth, as for spray painting, but unlike

    wet paint overspray, the oversprayed powder can be recovered and re-used.

    For powder spraying the booth is backed up by powder collection units, to

    which the powder is conveyed in the ventilating air stream via connecting

    ducting.

    1.1.6 Not all plastic powders are combustible or provide the same hazards from fire

    and explosion. The majority of powders used at present in New Zealand are

    epoxy resins and these powders have the greatest explosion hazard. Polyester

    powders have a similar explosion hazard rating and other powders such as

    acrylic and polythene have lower explosibilities.

    1.1.7 Although a dust cloud of polyvinyl chloride (PVC) powder is not explosive,

    PVC may give rise to toxic fumes during curing in ovens. Polyurethane

    powders may also give rise to irritant fumes during curing, hence ovens using

    these powders must be ventilated.

    1.1.8 As with paint, electrical equipment which sparks or has a hot surface could bea hazard, but it requires a higher energy spark and a higher temperature than

    that for a flammable vapour in order to ignite a dust cloud. The electrical

  • 7/29/2019 Code of Practice for the Application of Coating

    5/17

    5

    A

    RCHIVE

    equipment also requiries a different construction than that for flammable

    vapours in order to protect against the risk of a dust explosion or fire.

    1.2 Legislative Requirements

    1.2.1 For electrostatic powder coating compliance with this Code will be accepted

    by the Department of Labour as satisfactory in meeting the requirements ofSection 48A of the Factories Act 1946, which requires all practicable steps

    to be taken to eliminate the hazards from explosible dusts.

    1.2.2 Regulation 37 of the Spray Coating Regulations 1962 requires spray coating

    by electrostatic means to be authorised in writing by the Chief Inspector of

    Factories. Compliance with this Code provides the conditions under which the

    Chief Inspector will issue authorisation. Any alteration such as the use of a

    different electrostatic powder coating gun requires a new approval.

    1.2.3 Compliance with this Code will be accepted as meeting Regulations 67 and 94

    of the Electrical Wiring Regulations 1976.

    1.2.4 Emissions from the powder collector to the outside air must comply with the

    Clean Air Act 1972. An efficient cyclone would normally be sufficient to meet

    this requirement.

    1.3 Spray Booths and Collection Units

    1.3.1 Spray booths are normally either cabinet or tunnel booths. Cabinet booths

    may either have an opening in the front of the booth and some method of

    suspending objects from the roof of the booth or have openings in each end as

    well as the front to allow a conveyor to transport objects through the booth.

    Tunnel booths are always open at each end and may also have an opening inthe side to allow for the operator, or may be automatic with only a small

    opening to convey the feed-line, or may have an operator located inside the

    booth.

    1.3.2 The powder is collected from the bottom of the booth so that there is little

    powder accumulation in the booth.

    1.3.3 The collection unit usually consists of an efficient cyclone, or two or more such

    cyclones in parallel.

    1.3.4 The small amount of powder escaping from the cyclone/cyclones may also be

    collected using one of the following methods:

    (i) a fabric filter,

    (ii) a second cyclone, and

    (iii) a wet (water spray) collector.

    1.3.5 A fabric filter may also be used for powder collection without a cyclone, but

    because of size and other requirements (i.e. explosion venting) this normally

    would be much more expensive.

    1.4 Fire and Explosion Hazards

    1.4.1 Most of the powder used will burn in any concentration and will present a firehazard in all situations.

    1.4.2 The particle size of the powders is in the range which produces dust

    explosions.

  • 7/29/2019 Code of Practice for the Application of Coating

    6/17

    6

    ARCH

    IVE1.4.3 The concentration of powder in air must be above a minimum value termed the

    lower explosive limit (LEL) in order for an explosion to occur. The LEL

    value changes with the type of powder in use (see Appendix B), but will be in

    the range 20 - 60 g/m3for explosible powders.

    1.4.4 There is also a maximum concentration of powder in air above which

    explosions will not occur. This figure is of the order of several kilograms per

    cubic metre, but is very ill-defined and in practice could not be stated with any

    degree of accuracy. It is safer, therefore, to assume that the powder can

    explode at all concentrations above the minimum value.

    1.4.5 A cloud of powder in air, which is of sufficient concentration, will explode only

    if an ignition source is present.

    1.4.6 The source of ignition must be of the required energy for it to ignite a dust

    cloud. This is referred to as the minimum ignition energyand is normally

    expressed in joules or millijoules. Most values fall in the 10 to 40 millijoules

    range (see Appendix B).

    1.4.7 The source of ignition must be at a certain minimum temperature to ignite adust cloud. This is referred to as the ignition temperature. Typical values for

    a dust cloud range from 4000C to 5500C (see Appendix B). It should be

    noted that a layer of dust will ignite at considerably lower temperatures than a

    dust cloud; the thicker the layer of dust the lower the ignition temperature.

    1.4.8 There are a number of possible sources of ignition such as electrical

    equipment, cigarettes and matches, unearthed conductors producing static

    electricity, naked flames and hot surfaces.

    1.4.9 The whole workroom containing the powder spraying and collection

    equipment can be at great risk if accumulations of powder are allowed to arise

    in this area.

    1.5 Toxicity Hazard

    1.5.1 Generally powders used in coating operations have a low order of toxicity and

    there is little risk to health in handling and using of powders. As with all dusts,

    inert or otherwise, inhalation must be avoided (especially for particles of 10

    micron diameter or less), and concentrations of powder in the working

    environment should not exceed 10mg per cubic metre.

    1.5.2 There are no known instances of skin dermatitis resulting from contact with

    epoxy powder used in the coating industry.1.5.3 The irritant fumes given off during curing of polythene powders have a TLV

    of 5ppm (TWA) and 10ppm (STEL).

    1.6 Electrostatic Powder Coating Guns

    1.6.1 The electrostatic powder coating guns may be manual or automatic.

    1.6.2 The electrostatic powder gun can, in certain cases, produce a spark when

    brought into the proximity of an earthed object and the gun design must ensure

    a limited spark energy.

    1.6.3 The high voltage electrostatic field generated by the spray guns can build up a

    charge of static electricity on any nearby object which is not earthed and which

    is capable of accumulating a charge. Unearthed conductors, such as metallic

  • 7/29/2019 Code of Practice for the Application of Coating

    7/17

    7

    A

    RCHIVE

    objects, are the most likely to accumulate charge, although poor conductors,

    such as plastics, can also accumulate a charge but not to a level which is

    dangerous for combustible dusts.

    1.6.4 Because there is no New Zealand authority for testing electrostatic spray guns,

    reliance must be placed on overseas specifications.

    2. PLANT DESIGN AND OPERATION

    2.1 Principles of Hazard Reduction in Plant Design

    2.1.1 The fire risk of stored powder can be treated in the same way as for any other

    combustible solid.

    2.1.2 The risk of injury from suspended powder explosions or flash fires can be

    eliminated by using at least one of three techniques:(1) by providing one means of preventing explosions where all possible

    causes of failure have been considered and protection provided against

    each possible cause of failure (see Section 2.4 single-factor

    method);

    (2) by providing two means of preventing explosions, where failure of

    either of those means would be extremely rare (see Section 2.5

    double-factor method); and

    (3) by protecting the plant and surroundings from the effects of a dust

    explosion (see Section 2.6).

    Most plants do not simply use one of these techniques but use different techniques in

    different parts of the plant (see Appendix C).

    2.1.3 Eliminating all sources of ignition is not suitable as the sole means of protection

    for a single-factor method. Controlling the powder concentration below 25%

    of LEL is suitable for the single-factor. method. Collecting the powder in a

    water spray would also be suitable (if powder collection was not required say

    for one-off operations).

    2.1.4 The two means of protection for the double-factor method, which can be

    provided with extremely rare failure of either means, are:

    (a) by keeping the powder concentration below 50% of the LEL; and

    (b) by eliminating all sources of ignition.

    2.1.5 There are three methods used to protect plant from the effectsof a dust

    explosion:

    (a) by providing a lightweight door or bursting panel designed to release at

    a low pressure,

    (b) by constructing the plant or enclosing the plant in a structure so that it

    can sustain the full explosion pressure, and

    (c) by using an explosion suppression system i.e. using early-sensing

    detectors and rapid-acting extinguishers which contain chemical

    suppressant.

    2.1.6 Accumulations of powder in the workroom must be prevented by good work

    methods and regular cleaning.

  • 7/29/2019 Code of Practice for the Application of Coating

    8/17

    8

    ARCH

    IVE2.1.7 Inhalation of powder is avoided by providing sufficient air movement in the

    breathing zone of operators. When this is not practical suitable protective

    equipment must be provided and worn.

    2.2 Design of Spray Booth

    2.2.1 The booth shall be of substantial construction and must comply with theconstruction provisions of the Spray Coating Regulations 1962.

    2.2.2 Walls, ceilings and floors shall be smooth and without any projections, so that

    powder cannot easily collect in the booth and surfaces are easy to clean.

    2.2.3 Floors of booths shall be designed to facilitate the movement of powder

    towards exhaust points.

    2.2.4 The oversprayed powder shall not be collected in the booth, but shall be

    removed continuously from the booth and collected in a properly designed

    powder collection system.

    2.3 Design and Operation of Powder Extraction and Collection Systems

    2.3.1 Each spray booth shall be provided with a powder collection system, which

    shall continuously and effectively remove oversprayed powder from the booth

    whilst spraying is in progress.

    2.3.2 Powder collection units shall be designed to prevent any powder escaping into

    the workroom. With manual booths an average air velocity of not less than 0.4

    m/s through the main opening shall be maintained during spraying, while the

    velocity in the breathing zone of the operator must be at least 0.3 m/s. The air

    velocity through openings in the ends of a booth must be at least 0.2 m/s. For

    completely automatic booths the air velocity must be at least 0.2 m/s throughany openings in a booth.

    2.3.3 Air exhausted from collection systems shall be exhausted to the exterior of the

    factory at a point not less than 3 metres above ground level, in a manner that

    prevents its re-entry into the factory, unless all powder is effectively removed

    from the returning air and explosion venting is not necessary in the plant item

    which exhausts the air, e.g. a water wash system.

    2.3.4 Air velocity through extraction ducting shall be sufficient to prevent settling of

    powder in the ducting. There shall also be no sharp change of direction or of

    cross-section in the ducting as this could cause powder to settle out at this

    point.

    2.3.5 In wholly automatic systems the booth shall contain a fire detection device

    which will switch off the powder flow, high-voltage supply and ventilation

    system in the event of a fire or explosion.

    2.4 Explosion Prevention Using Single-Factor Method

    2.4.1 The average concentration of powder in the extracted air from the booth shall

    not exceed 25% of the LEL for that powder.

    2.4.2 Values of LEL for various powders are given in Appendix B. For powders

    whose LEL is not known then the value will be taken as 20 g/m . Where more

    than one powder is used then the lowest LEL will become the design criteria.

  • 7/29/2019 Code of Practice for the Application of Coating

    9/17

    9

    A

    RCHIVE

    2.4.3 The average concentration of the coating powder in the booth is determined

    from the maximum rate of powder that can be discharged from the guns in

    relation to the volume of air extracted by the ventilation system at its lowest

    capacity under operating conditions. See Appendix A for sample calculation.

    2.4.4 A plate must be affixed to the booth showing the minimum air volume rate (see

    Appendix A) and the design (actual) air volume rate. This plate shall conform

    to the pattern shown in Figure 1 and be situated in a conspicuous position.

    Markings on the plate shall be legible and permanent. If a new or additional

    gun is used giving a different maximum powder flow rate, then the plate must

    be altered to give the new minimum air flow rate (see also Section 1.2.2.).

    2.4.5 Some means must be provided so that, in the event of the air rate falling below

    the minimum, the powder supply to the spray gun will be cut off. An air flow

    switch or a switch operating on a pressure differential can be used for this

    purpose. If an air flow switch is installed, it must be on the clean side.

    2.4.6 Although the concentration may be above the explosive limit close to the gun,

    any explosion in this region would not be sustained outside and only a minorpuff would result from a source of ignition existing very close to the gun.

    2.5 Explosion Prevention Using Double-Factor Method

    2.5.1 The average concentration of powder in the extracted air from the booth shall

    not exceed 50% of the LEL for that powder.

    2.5.2 The criteria and details given in Sections 2.4.2, 2.4.3 and 2.4.4 will also apply

    here.

    2.5.3 The powder gun must be interlocked with the fan so that the powder gun

    cannot be used without the fan also operating.2.5.4 The spray booth shall be constructed of, or lined with, a material which cannot

    accumulate significant amounts of static electricity. Non-conductive and

    earthed conductive materials are suitable. Painted conductive materials must

    be earthed to protect against any damage to the paint film (see also

    Section 3.3.1).

    2.5.5 The hazardous area for any sources of ignition is the area within 2 m in any

    direction of any opening in the spray booth. Only electrical equipment suitable

    for Class II Division I hazardous locations will be allowed in the hazardous

    area (see Section 3.2).

    2.5.6 No naked flames or other source of ignition shall be permitted within thehazardous area. Earthing and other provisions are given in Section 3.3 and

    3.4. If it is necessary to perform any welding on any part of the booth or

    powder collection system, all traces of powder shall be removed from the

    system prior to commencement.

    2.5.7 No person shall smoke or be allowed to smoke in the hazardous area. A sign

    stating No Smoking within 2 m in clear lettering shall be prominently

    displayed on the spray booth.

    2.5.8 Preheating of articles before entry to the spray booth shall not exceed 3000C.

    2.5.9 Ovens operating within 2 m of the spray booth shall not have elements, orother heating device, situated within 2 m of the booth if the temperature of the

    elements or device exceeds 3000C.

  • 7/29/2019 Code of Practice for the Application of Coating

    10/17

    10

    ARCH

    IVE2.5.10 All fans in the collection system shall be situated on the clean side of the

    collection units, and shall be of a type where the motor is fitted external to the

    ducting. Downstream from the primary dust collector is considered to be on

    the clean side.

    2.6 Protection of Plant from Effect of Dust Explosions

    2.6.1 If explosion suppression is used as the means to protect the plant, then it must

    be designed and supplied by a firm with recognised expertise in this area.

    2.6.2 If the plant is designed to withstand a pressure of 700 kPa, then no other

    means of protection is necessary. Details of the plant design must be provided

    when seeking approval. A flame arrestor or fast-acting valve must be installed

    in the ducting close to the booth in order to prevent the flame front from any

    explosion returning to the booth. The fast-acting valve should be activated by a

    pressure or temperature detector located in the powder collector (or for a

    suppression system).

    2.6.3 If the plant is explosion vented, then either the plant should be located outsidethe building or the relief vent must be ducted to outside the building. The

    explosion vents must discharge at least 3 m above the ground or be located in

    an unfrequented place.

    2.6.4 The explosion venting standard accepted by the Department of Labour is

    National Fire Protection Association (N.F.P.A.) Code No. 68,Explosion

    Venting Guide 1978.

    If the plant is required to withstand pressure above 20 kPa, then details must

    be provided, when seeking approval, to confirm that the plant can withstand

    the design pressure. Suppliers of the collection system will also need to specify

    the explosion venting area, the volume of the collecting vessel, the pressure at

    which the vents release, and the length of the explosion relief ducting.

    2.6.5 If the length of the explosion relief vent ducting is longer than 2 m, or if it

    contains any bends greater than 10, then either the vessel and ducting must be

    capable of withstanding a higher pressure than 20 kPa or the cross-section of

    the explosion relief vent must be increased. A distance of 6 m is the maximum

    allowable length for an explosion relief vent duct when either the cross-section

    of the duct must be twice the area of the vent or the vessel must be capable of

    withstanding twice the pressure required for that vent area based on N.F.P.A.

    Code No. 68. The requirement for distances between 2 m and 6 m is found

    by proportion, e.g. for 4 m the area or pressure must be increased by 50%.

    2.6.6 If the dust collector has an unobstructed channel between where the powder is

    collected and the rest of the collector, then the whole powder collector must

    be explosion vented. A flame arrestor or fast-acting valve must also be

    installed close to the booth.

    2.6.7 If a cyclone uses a rotary valve or an automatically operated double-flap valve

    to separate the collecting vessel from the rest of the collector, then only the

    collecting vessel needs to be explosion vented or built to withstand 700 kPa.

    This criteria also applies to a filter bag unit when it is used in addition to a

    cyclone.

  • 7/29/2019 Code of Practice for the Application of Coating

    11/17

    11

    A

    RCHIVE

    2.7 Ovens

    2.7.1 Powder shall not be allowed to escape into an oven from any source.

    2.7.2 The temperature in the oven shall be kept below that at which the plastic will

    degrade and produce fumes of the products of decomposition (i.e. normally

    2400C). To achieve this a temperature controlling device shall be fitted to

    control the temperature in the oven. The temperature controller mustincorporate a fail-safe device, e.g. a fusible link.

    2.7.3 Ovens used to cure PVC or polyurethane powder must be vented to outside

    the factory. At least 10 m of air per kg of polyurethane powder must be

    provided in continuous ovens. Ovens used to cure other powders may not

    need to be vented outside the factory depending on the size and operation of

    the curing process.

    2.8 Protection of Operators Health

    2.8.1 No operator shall work, or be allowed to work, within a booth in such aposition that oversprayed powder is present in his breathing zone. The use of

    respirators or airline helmets is not a substitute for adequate ventilation but an

    approved airline helmet may be used in exceptional circumstances with the

    written consent of the Chief Inspector of Factories.

    2.8.2 A dust respirator of disposable or cartridge type (approved as suitable by the

    Department of Health) shall be provided for use when filling feed hoppers, or

    when handling powder in such a manner as is likely to raise a dust cloud.

    Preferably cartridge type respirators should be issued individually.

    2.8.3 For an automatic system entry to the spray booth shall be prohibited during

    operation.

    2.9 Cleaning

    2.9.1 The spray booth, ducting, powder collection units and the surrounding

    workroom area shall be effectively cleaned at regular intervals to prevent

    accumulations of powder.

    2.9.2 Cleaning shall preferably be carried out with an industrial vacuum cleaner, of a

    type powered by compressed air or dust-excluding ignition-proof type of

    electrical equipment. If the vacuum cleaning is not of this type, then it cannot

    go into the hazardous area while spraying is in operation. A centralised vacuumcleaning system utilising a cyclone or bag filter unit is also acceptable provided

    it has adequate protection against dust explosions.

    2.9.3 Cleaning shall not be carried out by brushing, although sweeping deposits from

    the inside of the booth directly into the collection system is permissible

    provided the extraction system is kept in operation.

    2.9.4 Powder which is not to be recovered for re-use shall be wetted before

    disposal.

    2.10 General

    2.10.1 Operators of electrostatic powder spraying equipment shall be adequately

    trained in the use of the equipment and this training shall be the responsibility of

    the occupier.

  • 7/29/2019 Code of Practice for the Application of Coating

    12/17

    12

    ARCH

    IVE2.10.2 Operators shall be made aware of the provisions of the Code where they

    relate to the operator or to the operation of the booth. Such provisions shall be

    made known to the operator by the occupier, before the equipment is used.

    2.10.3 No flammable paints or solvents shall be used or kept within 2 metres of the

    booth in a container made of conductive material unless they are earthed in

    accordance with Section 3.3.2.

    2.10.4 It is recommended that the inside surface of the booth, ducting and cyclone be

    painted or coated with a nonconductor as then powder will be less likely to

    stay on these surfaces. This will both reduce the explosion hazard and increase

    the ease with which colour changes can be carried out. Two cyclones in

    parallel may be used to make possible more rapid changes in colour.

    Fig. 1 Plate to be affixed to spray booth indicating its air extraction capacity

    DESIGN AIR VOLUME RATE m3/s

    MINIMUM AIR VOLUME RATE m3/s

    3. ELECTRICAL EQUIPMENT

    3.1 General

    3.1.1 All electrical equipment must comply with the Electrical Wiring Regulations

    1976. An extract from the Australian SAA Wiring Rules published by SANZ,

    MP 6105: 1976Electrical Wiring in Hazardous Locations, is also to be

    used for guidance as it is intended to include most of this material in theElectrical Wiring Regulations.

    3.1.2 When the average powder concentration in the spray booth be above 25% of

    the LEL, then the concentration is sufficient to require designation of a

    hazardous area. The area inside the spray booth and within 2 m of any

    openings in the spray booth will be inside the hazardous area.

    3.1.3 If because of poor housekeeping or other reasons there are considerable

    quantities of explosive dust in the work area, this area shall also be designated

    a hazardous area.

    3.2 Electrical Equipment in the Hazardous Area

    3.2.1 All electrical equipment, including portable equipment, used in the hazardous

    area shall be installed with one or a combination of the following requirements:

    (a) The equipment and circuitry shall be contained in a continuous

    dust-excluding ignition-proof enclosure.

    (b) The equipment is totally enclosed fan-cooled or totally enclosed

    pipe-vented with no pipe opening within the hazardous area.

    (c) The equipment has a special design which has been approved by the

    above authorities.

    3.2.2 The maximum surface temperature of all electrical equipment in the hazardous

    area will not exceed 3000 C.

  • 7/29/2019 Code of Practice for the Application of Coating

    13/17

    13

    A

    RCHIVE

    3.2.3 Light fittings used to illuminate the interior of the booth and any other light

    fittings within the hazardous area must comply with Section 3.2.1.

    Alternatively, the fittings can be mounted outside the booth and separated from

    the interior by dust-tight panels or wired or reinforced glass.

    3.2.4 Plugs and plug sockets used in the hazardous area shall be provided with an

    interlocking switch so arranged that the plug cannot be inserted or withdrawn

    with the switch in the on position and that the switch cannot be in the on

    position unless the plug is in the socket. The plug and plug socket shall be so

    constructed and installed that powder will not accumulate in the socket.

    3.3 Earthing in the Hazardous Area

    3.3.1 The booth and powder collection unit if constructed of conductive material

    shall be adequately earthed so that the resistance to earth does not exceed

    10 ohm and this shall be checked at intervals not exceeding 6 months by a

    competent person. A register shall be kept which is open to inspection.

    3.3.2 The article being coated and all metallic equipment in and within 2 m of thebooth shall be adequately earthed while spraying is in progress. The resistance

    to earth shall not exceed one megohm.

    3.3.3 The earthing of articles being coated depends on the effectiveness of the hooks

    carrying or holding the articles, and it may be necessary to carry out a regular

    cleaning programme for the hooks to scrape or burn off any plastic coating.

    Most electrostatic sprayguns will not work effectively once the resistance to

    earth is above 50,000 ohms, hence this will indicate when the hooks need

    cleaning.

    3.3.4 A powder coating system manufactured by one company uses a technique

    which overcomes the poor earthing of articles, hence where this system is

    installed an earthing control unit must also be installed to prevent high energy

    static discharges. At least one of the known suppliers of these earthing control

    units has an agent in New Zealand (See Appendix D).

    3.3.5 Operators of hand held spray guns shall wear conductive footwear* and shall

    not wear gloves of an insulating nature, nor stand on insulating material.

    3.3.6 Personnel approaching within 2 m of the booth during operation shall wear

    conductive footwear* unless the powder used has a minimum energy which is

    guaranteed to be above 25 mJ.

    * Footwear which complies with NZS 5808Electrically conducting andantistatic rubber footwearis satisfactory.

    3.4 Electrostatic Powder Coating Guns

    3.4.1 Electrostatic powder coating guns must be interlocked with the fan in such a

    manner that they cannot operate without the fan also operating (see Sections

    2.4.5 and 2.5.3).

    3.4.2 Electrostatic powder guns must be classified as instrinsically safe by some

    recognised overseas authority such as BASEEFA (British Approvals Service

    for Electrical Equipment in Flammable Atmospheres).3.4.3 Of the high voltage equipment only spray guns and the cables connected to

    them may be sited inside spray booths. The high voltage generators, or any

  • 7/29/2019 Code of Practice for the Application of Coating

    14/17

    14

    ARCH

    IVE

    motor driven devices, shall be excluded from the interior of booths, except in

    the case of approved spray-guns where the high-voltage generator is sealed

    into the gun.

    3.4.4 The high tension cables leading to guns shall be protected against damage

    during operation.

    APPENDIX A

    Examples of Powder Concentration and Lower Explosive Limit Calculations

    Suppose a booth is equipped with two spray guns both capable of a maximum

    discharge rate of 5 g/s, then the total maximum discharge rate = 5 + 5 = 10 g/s.

    If the air flow rate is 0.8 m3/s then the average powder concentration

    = 10 (g/s,) = 12.5 g/m3

    0.8 (m3 /s)

    Suppose the powder being sprayed is epoxy, then the minimum air volume rate

    for 50% of LEL

    10 (g/s)

    = = 0.38 m3/s

    0.5 x 53 (g/m3) (see Appendix B)

    and the minimum air volume rate for 25% of LEL

    10 (g/s)

    = = 0.76 m3/s

    0.25 x 53 (g/m3) (see Appendix B)

  • 7/29/2019 Code of Practice for the Application of Coating

    15/17

    15

    A

    RCHIVE

    APPENDIX B

    Explosion Characteristics of Plastic Powders (Representative Values)

    (1) Results on a scale 0-100. 100 indicates severest hazard, 0 - no ignition under test conditions

    APPENDIX C

    Examples of Possible Arrangements for Powder Collection Units

    Example A. In this example the booth uses the single-factor method while the cyclone

    has both the single-factor method and protection against the effect of an

    explosion (see Fig. 2).

    Example B. In this example the booth uses the double-factor method while the

    cyclone has protection against the effect of an explosion (see Fig. 3).

    Example C. This type of cabinet is portable and has protection against the effect of an

    explosion (see Fig. 4).

    Type of

    Powder

    Epoxy

    Polyester

    Polyester

    Modified Epoxy

    Polyurethane

    Polyvinyl

    Chloride

    Polythylene

    Polyvinyl

    Acetate

    Nylon

    Polypropylene

    AcrylonitrilePolymer

    Lower

    Explosive

    Limit

    (g/m3)

    53

    40

    45

    25

    Not ignitable

    20

    35

    30

    20

    25

    Minimum

    Ignition

    Energy

    (mJ)

    10-40

    Not ignitable

    10-40

    Ignition

    Temperature

    Cloud of

    Powder (00)

    540

    500

    520

    510

    Not ignitable

    410

    520

    500

    420

    500

    Maximum

    Explosion

    Pressure

    (kPa)

    648

    675

    660

    648

    Not ignitable

    552

    517

    655

    524

    620

    Explosibility

    Index

    DSIR (1)

    80

    80

    65

    648

    Not ignitable

    20-66

    0-10

    50

    Explosive

    Dust

    Class

    2

    2

    2

    Not ignitable

    1 or 2

    1

    1

    1

    1 or 2

  • 7/29/2019 Code of Practice for the Application of Coating

    16/17

    16

    ARCH

    IVE

    Fig. 2 Example A

    Fig. 3 Example B

    KEY

    1. Average concentration below 25%

    of LEL (see 2.4.1)

    2. Pressure-differential switch installed

    (see 2.4.5)

    3. Rotary valve installed (see 2.6.7)

    4. Vessel built to withstand 700 kPa

    (see 2.6.2 and 2.6.7)

    5. Air exhausted outside factory (see 2.3.3)

    6. No earthing of object required as special

    type of gun used (see 3.3.4)

    1

    2

    3

    4

    5

    6

    KEY

    1. Hazardous area a set distance from

    booth opening (see 2.5.5)

    2. Average concentration below 50% of

    LEL (see 2.5.1)

    3. Object in booth earthed (see 3.3.2)

    4. Booth constructed of nonconductive

    material (see 2.5.4)

    5. A flame arrestor or fast-acting valve

    installed (see 2.6.6)

    6. Powder gun interlocked with fan

    (see 2.5.3)

    7. Explosion vent installed (see 2.6.3)

    8. Air exhausted outside factory (see 2.3.3)

    1

    2

    3

    4

    56

    7

    8

  • 7/29/2019 Code of Practice for the Application of Coating

    17/17

    A

    RCHIVE

    Fig. 4 Example C

    APPENDIX D

    At the time that this code was printed the following information was available:

    Sames Company manufactures a gun which uses a technique which overcomes

    poor earthing; and

    Gema manufactures an earthing control unit (Nz agents - Gunn-Gollin Limited).

    KEY

    1. Average concentration below 50% of LEL

    2. Electrodes installed - source of

    ignition permissible as below LEL

    3. Concentration above LEL

    4. Explosion vent installed (see 2.6.3) - not

    vented outside but has flame arrestor

    (special case for portable unit)

    5. Object in booth earthed (see 3.3.2)

    6. Cabinet constructed of conductivematerial and therefore earthed

    (see 2.5.4)

    1

    2

    3

    4

    5

    6