CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

42
CO CO 2 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice 22 April 2008 SANYO Air Conditioners Europe Kjell Lundén Maarud gård, Norge

description

CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice. Maarud gård, Norge. 22 April 2008. SANYO Air Conditioners Europe Kjell Lundén. Looking at the house you have to consider:. Which year the house was built and ev. improvements. - PowerPoint PPT Presentation

Transcript of CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Page 1: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

COCO22 Heat pump Kick Off MeetingThe Natural Refrigerant, The Natural Choice

22 April 2008

SANYO Air Conditioners Europe Kjell Lundén

Maarud gård, Norge

Page 2: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Looking at the house you have to consider:

• Which year the house was built and ev. improvements

• Number of residents

• Living area (heated area)• Energy consumption

• Plot of land and its location

Page 3: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Windows

2-glass windows

Standard 3-glass windows

Energy effective 3-glass windows

-5°

+5°

-10°

-15°

Page 4: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Where goes the energy?

Outer walls 15%

Floor & Basement 15%

Windows 25%

Roof 15%

Ventilation 30%

Page 5: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Old plankhouse with extreme highenergy consumption

Outer walls U=1.0

Base U=1.0

Windows U=3.0

Roof U=0.5

Page 6: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Usage of energy

Household electricity

5000 kWh/year

Heating of the house

15000 kWh/year or around 60%

Hot water

5000 kWh/year

Page 7: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Energy for heating / year

-30°

50 100 150 200 250 300 350

Days

Maximum power requirement at lowest temperature

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 60% of the highest power requirment

T e m p e r a t u r e / e f f e c t

Page 8: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Kostnadseffektivitet

• - 1990: Vedeldning

• 1990 - 2005: Bergvärme

• 2005 - ? : Sanyos CO-2 teknik

Borrhål

Page 9: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

• Tidigare energiförbrukning ska kunna motsvaras av värmepumpen.

• Viktigt att kunden håller en så låg framledningstemperatur som möjligt.

• Fler radiatorer eller luftkonvektor sänker framledningstemperaturen.

• Tumregel: Framledningstemperaturen bör aldrig överstiga 50°C, för optimal besparing.

• Rekommendera alltid markstativ.

Att tänka på

Page 10: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Plumbing 01 Sanyo CO2 Eco02 Mixing valve, automatized03 Circulation pump, radiator system04 Adjustment valve for radiator coils05 Radiators06 Radiator thermostatic valves07 Shut off valve for the radiator system08 System/boiler pressure,install on the return pipe09 Expansion vessel, closed(recommended)10 Expansion vessel, open (alternative)11 Filling valve for radiator system12 Safety valve (factory mounted)13 Safety valve for hot water coil14 Mixing valve for hot water15 Non-return valve for incoming cold water16 Taps17 Incoming cold water18 Load circulation pump19 Insulated pipes20 Flexible houses21 Heat pump unit22 Shut-off valves23 Drain valve

Page 11: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Installation of systems with radiators

TankUnit

Mix.V

Radiator

Outdoor IndoorHP Unit

597

931

12

30

Water Supply

Heatingcircuit

Circulationbetween HP and tank

Page 12: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Installation of systems with radiators and floor heating

TankUnit

Mix.V

Radiator

ND10

OutdoorIndoor

HP Unit

597

931

12

30

Water Supply

Heatingcircuit

Circulationbetween HP and tank

Floor heatingMix.V

Page 13: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

?????????

Page 14: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice
Page 15: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Övre skiktplåt

Nedre skiktplåt

Returledning tillNedre skikt

Till VP ifrånNedre skikt

Ifrån VP tilltankensmellanskikt

Tank structure

Page 16: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Domestic cold water inlet (Ø22 mm out)

Domestic hot water outlet (Ø22 mm out)

Waste water pipe connection (Ø22 mm in)

Expansion pipe connection (DN 20 in)

Primary flow out connection (Ø22 mm in)

Primary flow return connection (Ø22 mm out)

Lifting device (DN 20 in). Not a water connection.

From heat pump. Connection (Ø22 mm out)

To heat pump. Connection (Ø22 mm out)

Tank Structure 2

Page 17: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Limitations

Pipe maximum length 15 m

Page 18: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Limitations

Page 19: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Rörchema

Page 20: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Electric box

Electronic

PCB

Electronic

PCB

Main power

supply

connectors Lower

electrical

immersion

heater Cable intake

Cable fixing

Cable fixings

Electrical parts

Page 21: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Wiring

Page 22: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Wiring

Page 23: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Wiring

Page 24: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Connections

Page 25: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Elinkoppling

Page 26: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

PANEL

Page 27: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

CO2 ECORUM 21 °C (21.5 °C)Tanktemp. 50 °CUte temp. 3 °CStatus:Måndag 20:45Manuell avfrostning Nej

Display normalläge

Page 28: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

LoggDiagnosInställningarInställningar kodadManuell drift(Inställning tid)

Huvudmeny

Page 29: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Total drifttid 15351 hTotal kompressor 7350 hKompressor/24 h17:32 hStart komp./24 h 2Senast larm:1. Utegivare2. -3. -

Meny Logg

Page 30: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Kompr effekt 82 HzElpanna 0 kwElpanna temp (55°C) 55°CEl nedre 0 kWEl nedre temp 45°C Rumstemp (21,5 °C) 21 °CUtetemp 3 °CTanktemp (50 °C) 44 °C Radiator temp (40 °C) 40 °C

Meny Diagnos sid 1

Page 31: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Ström (25A) 12AShuntventil +Laddpump 99%VP vatten in 37 °CVP vatten ut 55 °CKompr temp 90 °C Utetemp VP 1 °CFördröjn. El Ej aktiv

Meny Diagnos sid 2

Page 32: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Kommunikation OK

Program ID XXXXXXXProgram datum XX-XX-XX

Meny Diagnos sid 3

Page 33: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Språk SweVärmepump JaHuvudsäkring 20 AFördröjning elpanna 3 hElpanna 50 °C Max elpanna 6 kwEl nedre 45°CMax el nedre 6 kW

Meny Inställningar sid 1

Page 34: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Sommargräns 17°CRumsgivare JaMax framledning 55 °CMin framledning AvHuskurva 50 °CJustering Huskurva 0 °C Temp sänkning NejRum / Framl ändras 0 °C

Meny Inställningar sid 2

Page 35: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

TiderMåndag ▲06▼--▲--▼22Tisdag ▲06▼--▲--▼22Onsdag ▲06▼--▲--▼22Torsdag ▲06▼--▲--▼22Fredag ▲06▼--▲--▼22Lördag ▲06▼--▲--▼22Söndag ▲06▼--▲--▼22

Meny Inställningar sid 3

Page 36: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Kod 276Tank Max 65 °CTank Min A 43 °CTank Min B 50 °CTank min gräns 5 °CMin Pump hast 10%Diff Start / Stopp 5 °C Frysgräns 2 °C

Meny Inställningar kodad 276

Page 37: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Värmepump ( )Pumphast 0%Relä 1.5( ) 3( ) 4,5( ) 6( ) 7,5( ) 9( )

Relä nedre 3() 6()

Shuntventil ( )Rumsgivare fel ( )

Meny Manuell

Page 38: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Inställning Tid

MåndagTimme 00:Minut 00:

Meny Inställning tid

Page 39: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice
Page 40: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice
Page 41: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice
Page 42: CO 2 Heat pump Kick Off Meeting The Natural Refrigerant, The Natural Choice

Let’s go with the natural choice!Let’s go with the natural choice!