Circuit Breakers For I-Line® Panelboards and SwitchboardsClass 650, 734, 820
F-Frame accessories. . . . . . . . . . . . . .Supplemental & Obsolescence DigestF-Frame optional lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-48F-Frame dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-53Q-Frame accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-37Q-Frame dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-53
Table 9.113: F-frame—100 A, Thermal-magnetic (600 Vac)
AmpereRating
AC MagneticTrip Settings Standard Interrupting High Interrupting Current Limiting Terminal
WireRangeHold Trip Catalog Number $ Price Catalog Number $ Price Catalog Number $ Price
1-pole, 277 Vac, 125 Vdc a
15
275 600
— — FH16015( )
507.
— —AL50FA
#14–#4 AWG Cu or#12–#4 AWG Al
20 — — FH16020( ) — —25 — — FH16025( ) — —30 — — FH16030( ) — —35
400 850
— — FH16035( )
507.
— —
AL100FA#14–#1/0 AWG Cu or
#12–#1/0 AWG Al
40 — — FH16040( ) — —45 — — FH16045( ) — —50 — — FH16050( ) — —60
800 1450— — FH16060( ) 507. — —
70 — — FH16070( ) 563. — —80 — — FH16080( ) — —90
900 1700— — FH16090( ) 563. — —
100 — — FH16100( ) — —2-pole, 600 Vac, 250 Vdc a
15
275 600
FA26015( )
780.
FH26015( )
1214.
— —AL50FA
#14–#4 AWG Cu or#12–#4 AWG Al
20 FA26020( ) FH26020( ) FI26020( ) 2763.25 FA26025( ) FH26025( ) — —30 FA26030( ) FH26030( ) FI26030( ) 2763.35
400 850
FA26035( )
780.
FH26035( )
1214.
— —
AL100FA#14–#1/0 AWG Cu or
#12–#1/0 AWG Al
40 FA26040( ) FH26040( ) FI26040( ) 2763.45 FA26045( ) FH26045( ) — —50 FA26050( ) FH26050( ) FI26050( ) 2763.60
800 1450FA26060( ) 780. FH26060( ) 1214. FI26060( )
2763.70 FA26070( ) 947. FH26070( ) 1452. FI26070( )80 FA26080( ) FH26080( ) FI26080( )90
900 1700FA26090( ) 947. FH26090( ) 1452. FI26090( ) 2763.
100 FA26100( ) FH26100( ) FI26100( )3-pole, 600 Vac, 250 Vdc
15
275 600
FA36015
971.
FH36015
1446.
— —AL50FA
#14–#4 AWG Cu or#12–#4 AWG Al
20 FA36020 FH36020 FI36020 3459.25 FA36025 FH36025 — —30 FA36030 FH36030 FI36030 3459.35
400 850
FA36035
971.
FH36035
1446.
— —
AL100FA#14–#1/0 AWG Cu or
#12–#1/0 AWG Al
40 FA36040 FH36040 FI36040 3459.45 FA36045 FH36045 — —50 FA36050 FH36050 FI36050 3459.60
800 1450FA36060 971. FH36060 1446. FI36060
3459.70 FA36070 1163. FH36070 1632. FI3607080 FA36080 FH36080 FI3608090
900 1700FA36090 1163. FH36090 1632. FI36090 3459.
100 FA36100 FH36100 FI36100
a 1- and 2-pole circuit breaker catalog numbers are completed by adding the required connection letters as a suffix, see 9-24.
Table 9.114: PowerPact® Q-frame a — 225 A, Thermal-magnetic (240 Vac)
AmpereRating
AC Magnetic Trip Settings "B" Interrupting "D" Interrupting "G" Interrupting "J" Interrupting
Hold Trip Catalog Number $ Price Catalog Number $ Price Catalog Number $ Price Catalog Number $ Price
2-pole, 240 Vac b
701000 1800
QBA22070( )600.
QDA22070( )1202.
QGA22070( )1593.
QJA22070( )1992.80 QBA22080( ) QDA22080( ) QGA22080( ) QJA22080( )
90 QBA22090( ) QDA22090( ) QGA22090( ) QJA22090( )100
1200 2400
QBA22100( )
600.
QDA22100( )
1202.
QGA22100( )
1593.
QJA22100( )
1992.
110 QBA22110( ) QDA22110( ) QGA22110( ) QJA22110( )125 QBA22125( ) QDA22125( ) QGA22125( ) QJA22125( )150 QBA22150( ) QDA22150( ) QGA22150( ) QJA22150( )175 QBA22175( ) QDA22175( ) QGA22175( ) QJA22175( )200 QBA22200( ) QDA22200( ) QGA22200( ) QJA22200( )225 QBA22225( ) QDA22225( ) QGA22225( ) QJA22225( )
3-pole, 240 Vac c
701000 1800
QBA32070( )1913.
QDA32070( )2069.
QGA32070( )2835.
QJA32070( )3245.80 QBA32080( ) QDA32080( ) QGA32080( ) QJA32080( )
90 QBA32090( ) QDA32090( ) QGA32090( ) QJA32090( )100
1200 2400
QBA32100( )
1913.
QDA32100( )
2069.
QGA32100( )
2835.
QJA32100( )
3245.
110 QBA32110( ) QDA32110( ) QGA32110( ) QJA32110( )125 QBA32125( ) QDA32125( ) QGA32125( ) QJA32125( )150 QBA32150( ) QDA32150( ) QGA32150( ) QJA32150( )175 QBA32175( ) QDA32175( ) QGA32175( ) QJA32175( )200 QBA32200( ) QDA32200( ) QGA32200( ) QJA32200( )225 QBA32225( ) QDA32225( ) QGA32225( ) QJA32225( )
a Replacement lugs are not available on QB, QD, QG, or QJ circuit breakers. Lugs for QB, QD, QG or QJ circuit breakers accept one #4 AWG–300 kcmil. For accessories, see page 7-37.
b 2-pole QB, QD, QG and QJ circuit breakers are completed by adding the required phasing numbers as indicated in the parentheses, see 9-24.c 3-pole QB, QD, QG and QJ circuit breakers for ABC phasing are complete without additional phasing number. For CBA phasing, complete the catalog
number by inserting the number “6” in the parentheses.
Table 9.115: Interrupt Ratings (kA)FA FH FI QB QD QG QJ a
240 V 25 25 (1P 35–100 A), 65 (1P 15–30 A, 2P, 3P)200
10 25 65 100480 V 18 25 (2, 3P) — — — —600 V 14 18 (2, 3P) 100 — — — —
a 3-pole QJ circuit breakers are rated at 208Y/120 Vac only.
FI361002- and 3-pole
4.5 in (114 mm)Mounting Height
QB/QD/QG/QJMounting Height:
2-pole—3 in (76 mm)3-pole—4.5 in (114 mm)
DE2 Discount Schedule
7-4 © 2009 Schneider ElectricAll Rights Reserved
www.schneider-electric.us
7M
INIA
TU
RE
AN
D M
OL
DE
D C
AS
E
CIR
CU
IT B
RE
AK
ER
S
Selection Information Molded Case Circuit BreakersClass 500, 600, 800
PowerPact100 A Frame
PowerPact150 A H-Frame 100 A Frame
Circuit Breaker Type GJL HD HG HJ HL FA (240 V) FA FH FHb FH
Number of Poles 3 2,3 2,3 2,3i 2,3i 1, 2, 3 1 2, 3 1 1 2, 3
Current Range 15–100 15–150 A 15–150 A 15–150 A 15–150 A 15–100 15–100 15–100 15–30 35–100 15–100
Interrupting Ratings
UL/CSA/NOMRating
(kA RMS)(50/60 Hz)
240 Vac 100 25 65 100 125 10k 25k 25 65 25 65
480Y/277 Vac 65 18 35 65 100 — 18 18 65 25 25
480 Vac 65 18 35 65 100 — — 18 — — 25
600Y/347 Vac 18 14 18 25 50 — — 14 — — 18
600 Vac — 14 18 25 50 — — 14 — — 18
DC Ratings250 Vdc — 20 20 20 20 5c 10c 10 10c 10c 50
500 Vdca — — — — — — — — — — 20
IEC Rating(kA RMS)Icu/lcsd
240 Vac 65/65 25/25 65/65 100/100 125/125 — 18/9 — 18/9 — —
415 Vac 65/65 18/18 35/35 65/65 100/100 10/2.5 10/2.5 10/2.5 10/2.5 10/2.5 10/2.5
IEC 50/60 Hz For additional IEC ratings, see the Supplemental Digest.
Special Ratings
Fed. Specs W-C-375B/GEN — X X X X X X X X X X
HACR (2P, 3P) X — — — — X — X — — —
Connections/Terminations
Unit Mount X X X X X X —
I-Line® — X X X X X X X X X —
Rear Connection — Xh Xh X X X X X — — —
Drawout — Xh Xh X X — — — — — —
Optional Lugs — Xh Xh X X X X X X X —
Accessories and Modifications
Shunt Trip X X X X X Xfe — Xf — — Xf
Undervoltage Trip X X X X X Xfe — Xf — — Xf
Auxiliary Switches X X X X X Xfe — Xf — — Xf
Alarm Switch X X X X X Xfe X f Xf Xf Xf Xf
Motor Operator — Xh Xh X X — — X — — X
Handle Operators X Xh Xh X X X — X X X X
Mechanical Interlocks (3P) — X X X X — — X — — X
Handle Padlock Attachment X Xh Xh X X X X X X X X
Cylinder Lock (3Pf) — Xh Xh X X — — X — — X
Handle Mechanical Interlocks — Xh Xh X X — — — — — —
Optional GF Protectiong — — — — — — — X — — X
Trip System Type
Thermal-magnetic X X X X X X X X X X X
Instantaneous-only (MCP) X — — Xj Xj — — X — — X
Molded Case Switch — X X X X — — — — — X
Electronic — — — — — — — — — — —
Enclosures (Pages 7-56–7-58)
General Purpose (NEMA 1) — X X X X X X X X X X
Raintight (NEMA 3R) — X X X X X X X X X X
Dust-tight (NEMA 12) — X X X X X X X X X X
Watertight (NEMA 4, 4X, 5) — X X X X X X X X X X
Explosion Proof (NEMA 7, 9) — — — — — X X X X X X
Dimensions(3P Unit Mount)
in. (mm)
Height 4.72 (120) 6.4 (163) 6 (152) 6 (152)
Width 3.54 (90) 4.1 (104) 4.5 (114) 4.5 (114)
Depth 3.94 (100) 3.4 (86) 4.13 (105) 4.13 (105)
Pages (Unit Mount)/(I-Line) Page 7-24 Pages 7-22, 7-23, 7-28, 7-33/9-25 Pages 7-49,/9-23 Pages 7-49/9-24Note: All circuit breakers on this chart are UL Listed and CSA Certified unless otherwise noted.a Ungrounded UPS systems only. See page 7-34.b 65 kA @120 Vacc 1Ø 125 Vdc rating only.d Dual UL and IEC ratings and CE markings on circuit breakers. For additional IEC ratings, see the
Supplemental Digest.e Not available on 1P FA (240 V).
f Factory-installed option only.g Requires factory-installed “G” Shunt trip and 3P module.h Not available in HD and HG 2P rating (2P module).i 2P in a 3P module.j 3P only.k 1P FA is 120 Vac.
www.schneider-electric.us
7M
INIA
TU
RE
AN
D M
OL
DE
D C
AS
E
CIR
CU
IT B
RE
AK
ER
S
7-54 © 2009 Schneider ElectricAll Rights Reserved
Dimensions and Shipping WeightsMiniature and Molded Case Circuit Breakers
g Dimensions E are 1.59 in at ON end and 0.63 in at OFF end.
h All weights are for 3P circuit breakers unless otherwise noted.
B E
AG
Figure 2
B E
AG
Figure 1
B E
AG
Figure 3
DC
QO, QOB
QO-GFI, QO-PLQO-EPD
DC
Figure 5
AG
BE
A
BE
G
Figure 4
B
AG
E
Figure 6
AG
B E
Figure 7
AG
B E
Figure 8
DC
F
QOU, QYULow Ampere
ADC
B
Figure 9QO-PLPS
Figure 10
A
B E
Figure 11
A
B E
Figure 12
A
B E
QOUHigh Ampere
CD
FB
Figure 13
A
B
Figure 14
A
B
Figure 15
A
B
Figure 16
A
B
CD
C60
E
Figure 17
A
B
Figure 18
A
B
Figure 19
A
B
Figure 20
A
B
C120
CD
EB
Figure 21
BE
FA
E
G
C/L
Figure 22
BE
E
FA
Figure 23
C/L
BD
CG
H HE
E
FA
BG
E
E
FA
DC
Figure 24
Table 7.140: QO®, QOU, Multi 9TM Circuit Breakers
Circuit BreakerCat. No. Prefix Poles Fig.
No.Dimensions—Inches
A B C D E F G
QO, QOB1 1 0.75 3.00a 2.31 2.91 2.25 — 0.592 2 1.50 3.00a 2.31 2.91 2.25 — 1.343 3 2.25 3.00a 2.31 2.91 2.25 — 2.09
QOB-VH 150 AQOB-VH 110–150 A
2 2 3.0 5.72 2.53 4.90 3.78 — 2.853 3 4.50 5.72 2.53 4.90 3.78 — 4.35
QO-PLQO-GFIQO-EPD
1 4 0.75 4.12b 2.31 2.91 2.25 — 0.592 5 1.50 4.12b 2.31 2.91 2.25 — 1.343 5 2.25 4.12b 2.31 2.91 2.25 — 2.09
QOUQYULow Ampere
1 6 0.75 4.05c 2.38 2.98 2.25 5.00d 0.622 7 1.50 4.05c 2.38 2.98 2.25 5.00d 1.373 8 2.25 4.05d 2.38 2.98 2.25 5.00f 2.12
QOUHigh Ampere
1 10 0.75 4.45 2.37 2.96 2.25 6.78 —2 11 1.50 4.45 2.37 2.96 2.25 6.78 —3 12 2.25 4.45 2.37 2.96 2.25 6.78 —
Multi 9™ C60N
1 13 0.71 3.19 1.73 2.76 1.77 — —2 14 1.42 3.19 1.73 2.76 1.77 — —3 15 2.13 3.19 1.73 2.76 1.77 — —4 16 2.84 3.19 1.73 2.76 1.77 — —
QO-PLPS Power Supply 2 9 1.45 4.35 2.42 3.11 — — —a 35–70 A is 3.12 in; 80–100 A 2P and 70–100 A 3P are 3.50 in.b QO-PL is 4.55 in.c 80–100 A 1P and 80–125 A 2P are 4.45 ind 80–100 A 1P and 80–125 A 2P are 6.78 in.e 70–100 A 4.45 in.f 70–100 A is 6.78 in.
Table 7.141: QB, QD, QG, QJ, Q4, FA, FI, KA, KC, KI, LA, LC, LI, LE, LX, LXI, MA Circuit Breakers
Circuit BreakerCat. No. Prefix Poles Fig.
No.Dimensions—Inches
A B C D E F G H
QB, QD, QG, QJ
2 22 6.47 3.00 3.02 3.93 g 4.25 — —3 23 6.47 4.50 3.02 3.93 g 4.25 1.50 0.75
FAL, FHL1 21 6.00 1.50 3.16 4.13 0.44 5.13 1.50 —2 22 6.00 3.00 3.16 4.13 0.44 5.13 — —3 23 6.00 4.50 3.16 4.13 0.44 5.13 1.50 0.75
FIL, KAL, KCL,KHL, KIL 2 & 3 23 8.00 4.50 3.66 4.75 0.44 7.13 1.50 0.75
Q4L, LAL, LHL 2 & 3 23 11.00 6.00 4.06 5.84 0.88 9.25 2.00 1.00LIL, LEL, LXL, LXIL, LCL 2 & 3 24 11.86 7.50 5.48 6.74 0.55 10.75 2.50
MAL, MHL 2 & 3 23 14.00 9.00 4.53 6.50 1.66 10.69 3.00 1.50
Table 7.142: Shipping Weightsh
Frame Size Approx. Shipping Weight (Lbs.) Frame Size Approx. Shipping
Weight (Lbs.)
FAL, FHL 1P 2 KIL 9
FAL, FHL 2P 3 LAL, LHL 15
FAL, FHL 3P 5 LEL, LIL, LXL, LXIL, LCL 25
FIL 8 Q4L 15
QB, QD, QG, QJ 4 MAL, MHL 34
KAL, KHL 7
9-1© 2009 Schneider ElectricAll Rights Reserved
9P
AN
ELB
OA
RD
S
Table of Contents
Section 9Panelboards
NQ PanelboardsPage 9-5
NF PanelboardsPage 9-13
I-Line® PanelboardsPage 9-20
QMB PanelboardsPage 9-34
Series Rated / Fully Rated TablesNQ 9-2NF 9-3I-Line® 9-3
Lighting and Appliance Panelboards
NF/NQ Pricing Procedures 9-5NQ Merchandised Main Lug Panelboards 9-6
Merchandised Main Circuit Breaker Panelboards 9-7Merchandised Main Lug & Main Circuit Breaker 9-8Merchandised Accessories 9-9QOB Branch Circuit Breakers 9-10Factory Assembled Panelboards and Circuit Breakers 9-11Factory Assembled Common Features 9-12
NF Merchandised Main Lugs Panelboards 9-13Merchandised Main Circuit Breaker Panelboards 9-13Merchandised Main Lug & Main Circuit Breaker Panelboards with TVSS 9-13Merchandised Accessories 9-14EDB, EGB, EJB Branch Circuit Breakers 9-15Factory Assembled Panelboards 9-18Factory Assembled Common Features 9-19
NF/NQColumn Width
Merchandised Single Row (Column Width) Panelboards 9-16
M NQ 14 inch Wide Panelboards 9-41
Power Distribution Panelboards—Circuit Breaker Type
I-Line® Pricing Procedure 9-20Merchandised Panelboards (HCN, HCM, HCP-SU) 9-21Merchandised Panelboards (HCP, HCR-U) 9-22Merchandised Accessories 9-23Circuit Breakers 9-24H-frame and J-frame Circuit Breakers 9-26K-frame and R-frame Circuit Breakers 9-27L-frame Circuit Breakers 9-28M-frame Circuit Breakers 9-29P-frame Circuit Breakers 9-30Factory Assembled Pricing 9-31Factory Assembled Branch Circuit Breakers 9-32Factory Assembled Common Features 9-33
Power Distribution Panelboards—Fusible Type
QMB Replacement Switches 9-34Factory Assembled Pricing 9-35Factory Assembled TVSS Units 9-36
Panelboard Special Features
Factory Assembled Modifications 9-37Terminal Data 9-38
CTC Cabinets—Wall Mounted Metering Equipment 9-40
New!
New!
www.schneider-electric.us
9P
AN
EL
BO
AR
DS
9-24 © 2009 Schneider ElectricAll Rights Reserved
Circuit Breakers for I-Line® Panelboards and SwitchboardsClass 650, 651
Accessories: Supplemental & Obsolescence DigestOptional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 7-48Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pages 7-53
Table 9.107: QO® Distribution Panel—240 Vac Max. Only Mounts in Type HCN, HCM, HCP, HCP-SU, or HCR-U I-Line panelboards, 30 A max. branch circuit breaker. Order QO plug-on circuit breakers from page 9-33.
Maximum No. 1-poleQO Circuit Breakers
Phase Connection
Mounting Height
2-poleCatalog Number
3-poleCatalog Number
$ Pricea
IN mm
6 AB 4.5 114 HQO206AB — 369.6 BC 4.5 114 HQO206BC — 369.6 AC 4.5 114 HQO206AC — 369.6 ABC 4.5 114 — HQO306 369.
a Includes (5) QO1DB dummy circuit breakers.
Table 9.108: Example: FJA, 20 A 1-pole, 277 Vac and 70 A 2- and 3-pole QB 240 Vac. Use phase option number for HD, HG, HJ, HL, JD, JG, JJ, JL, MG and MJ.
PhaseOption
Number
PhaseConnection 1-pole 2-pole 3-pole
1 A FJA140201 — —3 B FJA140203 — —5 C FJA140205 — —1 AB — QBA220701 —2 AC — QBA220702 —3 BA — QBA220703 —4 BC — QBA220704 —5 CA — QBA220705 —6 CB — QBA220706 —
Standarda ABC — — QBA320706 CBA — — QBA320706
a The absence of a phase option number after a 3-pole catalog number will result in an ABC phase connection.
Table 9.109: Example: FA, 30 A, 480 Vac. Use phase option letters for FH, FI, KI, LA, LH, LC, and LI.
PhaseOption Letter 1-pole 2-pole 3-pole
A FA14035A — —B FA14035B — —C FA14035C — —
AB — FA24030AB —AC — FA24030AC —BC — FA24030BC —
ABC — — FA34030CBA — — FA34030CBA
Table 9.110: Interrupt Ratings (kA)FA (240 V) FA (480 V) FJ
240 V 10 18 (1P), 25 (2, 3P) 65277 V — 18 65480 V — 18 —600 V — — —
FA/FH, 2-pole3 in (76 mm)
Mounting Height
FA/FH3-pole
4.5 in (114 mm) Mounting Height
FA/FH1-pole
1.5 in (38 mm) Mounting Height
Table 9.111: F-frame—100 A, Thermal-magnetic (240 Vac)
AmpereRating
AC MagneticTrip Settings Standard Interrupting Terminal
WireRangeHold Trip Catalog Number $ Price
2-pole, 240 Vac a
15
275 600
FA22015( )
398.
AL50FA#14–#4 AWG Cu or
#12–#4 AWG Al
20 FA22020( )25 FA22025( )30 FA22030( )35
400 850
FA22035( )
AL100FA#14–#1/0 AWG Cu
or #12–#1/0 AWG Al
40 FA22040( )45 FA22045( )50 FA22050( )60
800 1450FA22060( )
70 FA22070( )
617.80 FA22080( )90
900 1700FA22090( )
100 FA22100( )3-pole, 240 Vac
15
275 600
FA32015
572.AL50FA
#14–#4 AWG Cu or#12–#4 AWG Al
20 FA3202025 FA3202530 FA3203035
400 850
FA32035
572.AL100FA
#14–#1/0 AWG Cuor #12–#1/0 AWG Al
40 FA3204045 FA3204550 FA3205060
800 1450FA32060 572. AL100FA
#14–#1/0 AWG Cuor #12–#1/0 AWG Al
70 FA32070780.
80 FA3208090
900 1700FA32090
780.AL100FA
#14–#1/0 AWG Cu100 FA32100
a 1- and 2-pole circuit breaker catalog numbers are completed by adding the required phase connection letters as a suffix.
Table 9.112: F-frame—100 A, Thermal-magnetic (480 Vac)
AmpereRating
AC MagneticTrip Settings Standard Interrupting Extra High Interrupting Terminal Wire Range
Hold Trip Catalog Number $ Price Catalog
Number $ Price FY/FA Lugs FJ/FC Lugs
1-pole, 277 Vac, 125 Vdc a
15
275 600
FY14015( )b
149.
FJA14015( )
651.
AL50FA#14-#4
AWG Cu, or#12-#4 AWG Al
AL30FD#12–#6
AWG Al, or#14–#6
AWG Cu
20 FY14020( )b FJA14020( )25 FY14025( )b FJA14025( )30 FY14030( )b FJA14030( )35
400 850
FA14035( )c
302.
FJA14035( )
651.AL100FA#14–#1/0
AWG Cu or#12–#1/0 AWG Al
AL100FD#12–#2/0 AWG Al
or#14–#2/0 AWG Cu
40 FA14040( )c FJA14040( )45 FA14045( )c FJA14045( )50 FA14050( )c FJA14050( )60
800 1450FA14060( )c
302.FJA14060( ) 651.
70 FA14070( )c FJA14070( ) 720.80 FA14080( )c — —90
900 1700FA14090( )c 302. — —
100 FA14100( )c — —2-pole, 480 Vac, 250 Vdc abc
15
275 600
FA24015( )
651.
— — AL50FA#14–#4
AWG Cu or#12–#4 AWG Al
CU30FA4one #14–#10 AWGCu only
20 FA24020( ) — —25 FA24025( ) — —30 FA24030( ) — —35
400 850
FA24035( )
651.
— —
AL100FA#14–#1/0
AWG Cu or#12–#1/0 AWG Al
AL100FA4one #14–#3
AWG Cuor
one #12–#1 AWG Al
40 FA24040( ) — —45 FA24045( ) — —50 FA24050( ) — —60
800 1450FA24060( ) 651. — —
70 FA24070( ) 833. — —80 FA24080( ) — —90
900 1700FA24090( ) 833. — —
100 FA24100( ) — —3-pole, 480 Vac, 250 Vdc a
15
275 600
FA34015
833.
— — AL50FA#14–#4
AWG Cu or#12–#4 AWG Al
CU30FA4one #14–#10 AWGCu only
20 FA34020 — —25 FA34025 — —30 FA34030 — —35
400 850
FA34035
833.
— —
AL100FA#14–#1/0
AWG Cu or#12–#1/0 AWG Al
AL100FA4one #14–#3
AWG Cuor
one #12–#1 AWG Al
40 FA34040 — —45 FA34045 — —50 FA34050 — —60
800 1450FA34060 833. — —
70 FA34070 996. — —80 FA34080 — —90
900 1700FA34090 996. — —
100 FA34100 — —
a 1- and 2-pole circuit breaker catalog numbers are completed by adding the required phase connection letters as a suffix.
b Rated 277 Vac 15 and 20 ampere FY circuit breakers are rated for switching duty (SWD). 15, 20, 25 and 30 ampere FA I-LINE circuit breakers are also available (no SWD rating).
c Rated 277 Vac, 125 Vdc, except FY circuit breakers, which have no dc rating. 15–30 ampere circuit breakers suitable for use with 60oC or 75oC conductors. 35–100 ampere circuit breakers are suitable for use with 75oC conductors.
DE2 Discount Schedule
Square D Special ConstructionClass 690www.squared.com
FOR CURRENT INFORMATION
Special Magnetic or Thermal Calibration (20% Price Adder)Magnetic:
The magnetic trip ranges for standard circuit breakers are listed in the Square D Digest. Requirements outside this range are best accommodated byselecting another standard circuit breaker. In some cases where this is not practical, a circuit breaker may be ordered with special magnetic calibration.Special magnetic calibration is not possible in all cases. Circuit breakers with special magnetic calibration and an adjustable magnetic trip range are notUL Listed; those with a fixed magnetic trip setting are UL Listed. Consult Square D/Schneider Electric sales office for more information.
50 Degrees C:
UL 489 Listed molded case circuit breakers are calibrated for 40 degree C ambient temperature. To meet requirements of higher ambient conditions,circuit breakers can be factory calibrated for a 50 degree C ambient temperature. Circuit breakers with special thermal calibration are not UL Listed. Toorder, place the suffix "35" after the catalog number (e.g., KAL36225-35). No other special thermal calibrations are available.
Visi-blade Circuit Breakers (20% Price Adder)Visi-blade construction is a modification to the cover of a thermal-magnetic circuit breaker, a molded case switch, or a MAG-GARD® circuitbreaker which provides a "window" through which the position of themovable contacts can be verified. Luminescent paint is applied to themovable contact arms to clearly indicate their position. Gases producedduring high level interruption may cause clouding of the Visi-bladewindow. Visi-blade circuit breakers listed below are UL Listed except forFH circuit breakers. Visi-blade construction is not available on circuitbreakers not included in table below.
Add suffix letter 'V to the circuit breaker catalog number, i.e., FAL36100V.
Available Visi-blade Circuit BreakersCircuit Breaker Prefix
FA, FH*
KA, KH
LA, LH
MA, MH
Amperes
15-100
70-250
125-400
300-1000"
Price
20%Price Adder
Visi-blade Circuit Breaker
• FH circuit breaker is not UL Listed.• I-LINE® 800 A maximum, unit mount 1000A maximum.
Moisture and Fungus Resistant Treatment for Circuit Breakers (20% Price Adder)This treatment covers the application of moisture and fungus resistant varnish to circuit breakers and molded case switches.
• The varnish meets Military Specification MIL-V-173C VARNISH, MOISTURE AND FUNGUS RESISTANT.
• The treatment meets military Specification MIL-T-152E TREATMENT, MOISTURE AND FUNGUS-RESISTANT, OF COMMUNICATIONS, ELEC-TRONIC, AND ASSOCIATED ELECTRICAL EQUIPMENT.
The treatment of circuit breakers in accordance with said specifications is intended to protect them against the moisture and fungus condition encoun-tered in service by retarding the absorption of moisture and inhibiting the growth of fungi.
To order, place the suffix "FT" at the end of the circuit breaker catalog number, e.g., FAL36100 becomes FAL36100FT.
This treatment is not available on KD circuit breakers.
EDB, FDA, and GJL circuit breakers are inherently fungus resistant and need no further treatment.
Short Handle for LA/LH Circuit Breakers (No Additional Charge)Certain applications of the LA/LH circuit breakers (as mains in particular panelboards) require the use of a slightly shorter operating handle. For orderinginformation refer to the chart below.
Catalog Numbers for Short Handle LA/LH Circuit BreakersLug Configuration Desired
ON End
Lugs
No Lugs
Lugs
No Lugs
OFF End
Lugs
Lugs
No Lugs
No Lugs
Catalog"Prefix Indication"
"L'
"P"
"P"
"F
Catalog"Suffix Indication"
"MB"
"MB"
"MT'
"MB"
Circuit BreakerCatalog Number
LAL36400MB
LAP36400MB
LAP36400MT
LAF36400MB
MAG-GARD and I-LINE are Registered Trademarks of Square D Company or related companies.
3/00DE2 Discount
Schedule 5-9