Circuit-Breaker.ppt

10
Circuit Breaker Testing M.M. Meraat

description

cb

Transcript of Circuit-Breaker.ppt

Page 1: Circuit-Breaker.ppt

Circuit Breaker Testing

M.M. Meraat

Page 2: Circuit-Breaker.ppt

Classification of Testing

Type Test – Conducted on each prototype of CB.

Routine Test – Conducted on each CB. Reliability Test – Check the reliability in actual

operating condition. Commissioning Test – Conducted on CB after

installation.

Page 3: Circuit-Breaker.ppt

Type Test

Mechanical Test Withstand voltage or Dielectric Test Temperature Rise Test Short Circuit Test

Page 4: Circuit-Breaker.ppt

Type Test– Mechanical Test

Endurance Test – Circuit Breaker checked for 1000 open close operation.

Operating Limit Test – CB auxiliaries is tested.Lower value – CB perform properly without hesitationUpper Value – Energy input does not damage the auxiliary

equipment.

Component Testing – Special type of test done during early development or some other requirements.

Page 5: Circuit-Breaker.ppt

Type Test – Dielectric Test

Lighting Impulse Test – 1.2/50 uSec test waveform.5 shots of +ve polarity.5 shots of –ve polarity.

Switching Impulse Test – 50/2500 uSec waveform.5 shots of +ve polarity.5 shots of –ve polarity.Above 300kv should be in wet condition.

Power frequency withstand Test – Total of 15 shots Not more than 2 flashovers.Test frequency 100hz.Normal current, normal voltage.

Page 6: Circuit-Breaker.ppt

Type Test – Temperature rise test

Should me made on a new CB with clean contact parts.

Done in totally enclosed place. Control ckt. And auxiliaries are also undergo

through test. Reading of the various parts are taken at a

interval of 1 or half an hour. Max. temp. should not exceed the permissible

value.

Page 7: Circuit-Breaker.ppt

Type Test – Temperature rise test

Item Max. Temp.Copper contact

in air with silver plating

in air without silver plating

in oil with silver plating

in oil without silver plating

105

75

90

80 In oil CB 80Terminals of CB with silver plating

without silver plating105

90

Metal parts in contact with class E insulation 100

Page 8: Circuit-Breaker.ppt

Type Test – Short circuit Test

Breaking Test –Capacity of CB to open during a short circuit. The following factors are checked…….

1. Condition of CB before test2. Condition of CB during test3. Condition of CB after test4. Applied voltage before test5. TRV6. Test frequency

etc…..

Making Test – Capacity of CB to close during an existing fault. The same factors as above are checked during testing.

Page 9: Circuit-Breaker.ppt

Type Test – Operating Sequence Test

According to IEC – O-3minutes-CO-3minutes-CO for non-auto reclosing CB.

O-.3Sec-CO-3minutes-CO-CO for auto reclosing CB.

Test Duty 1: 10% of rated SC current<20% DC component

Test Duty 2: 30% of rated SC current

<20% DC component

Test Duty 3: 60% of rated SC current

<20% DC component

Test Duty 4: 100% of rated SC current

<20% DC component

Test Duty 5: 100% of rated SC current(Only the symmetrical component).

Page 10: Circuit-Breaker.ppt

Routine Test

No load mechanical operation test – to verify speed of travel, opening time, closing time.

Millivolt drop test – To measure the contact resistance.