Chint 17th Edition Consumer Units

3
CHINT EUROPE (UK) LTD THE WORLD APPROVED MANUFACTURER Chint Consumer Units and the 17th Edition New Chint 17th Edition Products Various Configurations MCBs UK Approved by ASTA Up to 18 Modules

description

Chint 17th Edition Consumer Units

Transcript of Chint 17th Edition Consumer Units

Page 1: Chint 17th Edition Consumer Units

CHINT EUROPE (UK) LTD

THEWORLD APPROVED MANUFACTURER

Chint Consumer Unitsand the 17th Edition

New Chint 17th Edition Products

� Various Configurations

� MCBs UK Approved by ASTA

� Up to 18 Modules

Page 2: Chint 17th Edition Consumer Units

NX2-18D

SLNX2-18A

NX2-14A

NX2-14M

18 Module Consumer Unit supplied complete with 2* 63A, 2 PoleRCDs, 1* 100A Isolator and 2* 6 module Bus Bars. This modelallows a maximum of 12 MCB modules to be fitted, 6 on each RCD.

18 Module Consumer Unit supplied complete with a 100A Isolator,1* 80A RCD and 2* 7 module Bus Bars. This allows half of theboard to be controlled through the RCD and the other half withindividual SP RCBOs.

14 Module Consumer Unit supplied complete with a 100A Isolator,1* 80A RCD and 2* 5 Module Bus Bars. This allows one half of theboard to be controlled through the RCD and the other half withindividual SP RCBOs.

14 Module Consumer Unit supplied complete with 100A Isolatorand 1* 12 module Bus Bar allowing a maximum of 12 SP RCBOs tobe fitted next to the Isolator.

Chint Dual Split Load Units

Page 3: Chint 17th Edition Consumer Units

THE APPROVED MANUFACTURER

Summary Table

Circuit Protection and the 17thEdition of the IEE Regulations

With the introduction of the 17th editionmajor changes come in to force,particularly in the area of Earth LeakageProtection. The following can only be asummary, full and detailed informationshould be obtained from the regulations.

Installations should be so designed as tooffer proper circuit discrimination so as toensure maximum safety/convenience inthe event of 1 circuit failure, this isparticularly important in the case oflighting circuits.

Summary� Regulation 411.3.3:All socket outlets meant for use by anordinary person with a rated current notexceeding 20Amps should be protectedby a 30mA RCD.

� Regulation 701.411.3.3:All circuits in a room with a fixed bath orshower should be protected by 1 or more30mA RCDs.

� Regulation 522.6.6, 522.6.7 and 522.6.8:All cables buried beneath the plaster surfaceof a wall at less than 50mmshould be protected by 30mA RCDs.

� Regulation 411.3.3:All cables installed in metal stud partitionwalls should be protected by 30mA RCDs.

The following summary table refers toadditional protection, generally this isadditional to MCBs – Fuses, i.e., earthleakage protection. Today SP RCBOs areseen as a convenient method of offeringboth overload and Earth leakage protectionfrom one device.

REGULATIONS RELATING TO: EXAMPLES ADDITIONAL PROTECTION

411.3.3Sockets up to 20Arating for general useby ordinary persons

• Upstairs Sockets• Downstairs Sockets• Kitchen Sockets• Cooker Outlet with Integral 13A Socket• Garage Sockets• Plus any other sockets up to 20A rated

30mA RCD

701.411.3.3All circuits in aroom with a fixedbath or shower

• Shower Circuit• Lighting Circuit• Heating Circuit• Ventilation Circuit• Shaver Socket• Plus other circuits

30mA RCDs

522.6.6522.6.7and

522.6.8

All circuits buried ina wall or partition atless than 50mm andwithout mechanicalprotection

• Downstairs Lighting• Upstairs Lighting• Immersion Heater• Burglar Alarm• Smoke Alarms

30mA RCD