Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water...

20
Pipe Design Lecture No.(2) By Badran M. Salem 1 Chilled Water system Introduction For large installations the Condenser, Evaporator, Compressor and Expansion device can be purchased as a package unit, known as a Chiller . The usual package consists of electrically driven compressor(s) mounted on top of two shell and tube heat exchangers, one for the evaporator and the other for the condenser. The cooling coil(s) are piped up to the chiller in the conventional manner as shown below. In some countries the Cooling tower is the preferred method of removing heat from the system. Cooling towers that are open to atmosphere are not often used since the water may become contaminated. A closed cycle cooling tower or evaporative cooler can be used to reduce contamination risk.

Transcript of Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water...

Page 1: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

1

Chilled Water system

Introduction

For large installations the Condenser, Evaporator, Compressor and

Expansion device can be purchased as a package unit, known as a

Chiller . The usual package consists of electrically driven

compressor(s) mounted on top of two shell and tube heat exchangers,

one for the evaporator and the other for the condenser.

The cooling coil(s) are piped up to the chiller in the conventional

manner as shown below.

In some countries the Cooling tower is the preferred method of removing heat from the system. Cooling towers that are open to atmosphere are not often used since the water may become contaminated. A closed cycle cooling tower or evaporative cooler can be used to

reduce contamination risk.

Page 2: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

2

Chiller Schematic Diagram with Air Cooled Condenser

Cooling Coil(s)

Condenser

Evaporator

Compressor

Heat Rejection

Heat Input

Expansion

valve

1

2

3

4

Refrigerant Gas

Refrigerant Liquid

+ Vapour

-

Pump

Control

Valve

Chilled

Water

flow

Chilled

Water

return

Fans

Chiller

Page 3: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

3

Cooling Coil(s)

Condenser

Evaporator

Compressor

Heat Rejection

Heat Input

Expansion

valve

1

2

3

4

Refrigerant Gas

Refrigerant Liquid

+ Vapour

-

Pump

Control

Valve

Chilled

Water

flow

Chilled

Water

return

Chiller

Cooling Tower

Condenser Water

Chiller Schematic Diagram with Cooling Tower

Page 4: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

4

Alternative arrangements are shown for smaller installations where the condenser may be mounted on the roof or external wall of a building and cooled by outside air. The evaporator may be installed directly into the ductwork or air handling unit (AHU) for smaller installations. This is known as a Direct Expansion (or DX) coil. A typical Direct Expansion (or DX) system is shown below. This avoids using condenser water and chilled water in the system and installing the accompanying plant.

Direct Expansion Cooling Coil

also known as DX coil in Air

Handling Unit (AHU)

Condenser

Compressor

Heat Rejection

Heat Input

Expansion

valve

1

2

3

4

Refrigerant

Gas

Refrigerant Liquid +

Vapour

-

Refrigerant

Flow

Refrigerant

Return

Fans

Air Cooled

Condenser

incorporating

Compressor(s)

Direct Expansion (DX) System

Page 5: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

5

Chilled-water System

In larger buildings and particularly in multi-story buildings, the split-system

approach begins to run into problems. Either running the pipe between the condenser and the air handler exceeds

distance limitations (runs that are too long start to cause lubrication difficulties in the compressor), or the amount of duct work and the length of ducts becomes

unmanageable. At this point, it is time to think about a chilled-water system.

In a chilled-water system, the entire air conditioner is situated on the roof or behind the building.

It cools water to between 4.0oC and 8.0

oC.

This chilled water is then piped throughout the building and connected to the

cooling coils in air handlers as needed. There is no practical limit to the length of a chilled-water pipe if it is well-insulated.

Page 6: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

6

Chilled Water Temperatures

Typically chilled water flow and return temperatures to cooling coils is generally between 7

oC and 12

oC, depending upon the dew point to be maintained.

When this water is pumped through the evaporator section of the chiller this water temperature will be lowered by about 4

oC to 6

oC.

In order that the necessary heat transfer may take place, the refrigerant must be at some temperature below that of the leaving water but, at the same time, it must

generally be slightly above freezing point.

In a typical case, the following water temperatures may be used:

Apparatus dew point 12°C Cooling coil outlet 10°C

Cooling coil inlet 6°C Water at evaporator outlet 5.5°C

The refrigerant in the evaporator would in this case be maintained at about 1°C

giving a differential for 4.5°C for heat transfer. As will be appreciated, this small temperature potential means that the cooling surface of a simple tubular type would need to be very extensive: a variety of

devices has been developed to augment the transfer rate.

Ethylene/glycol solutions may be used in cooling coils in order to allow lower air temperatures to be obtained.

The temperatures of the fluid circulating may be -7°C from the evaporator and -3°C returning to it, or lower as required.

In instances where cooling for an air-conditioning system is provided from a refrigeration machine by direct expansion, the refrigerant is piped directly to

cooling coils in the air stream which thus become the evaporator.

The surface temperature of the coils is a function of the leaving air temperature required, the form of the coil surface and the velocity of the air flow. Refrigerant temperatures much below freezing point are inadmissible owing to the

risk of build-up of ice on the coil surface when dehumidification is taking place. An apparatus dew point of 3°C is normally considered as the practical minimum for

such coils if frosting is to be avoided.

Page 7: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

7

Page 8: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

8

Page 9: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

9

Page 10: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

11

Page 11: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

11

Page 12: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

12

Page 13: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

13

Page 14: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

14

Page 15: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

15

Page 16: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

16

Page 17: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

17

Page 18: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

18

Page 19: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

19

Page 20: Chilled Water system - Donutsdocshare01.docshare.tips/files/17552/175529404.pdf · Chilled Water Temperatures Typically chilled water flow and return temperatures to cooling coils

Pipe Design Lecture No.(2) By Badran M. Salem

21