chemical engineering June 2015

101
SYSTEMS The Leading Magazine for Pump Users Worldwide SYSTEMS JUNE 2015 PUMPSANDSYSTEMS.COM ® Trade Show Preview ACHEMA & EASA 2 Simple Steps to Choosing the Right Motor PLUS: Prevent System Failures In CHEMICAL PUMPING Applications

Transcript of chemical engineering June 2015

  • SYSTEMSThe Leading Magazine for Pump Users Worldwide

    SYSTEMS

    JUNE 2015

    PUMPSANDSYSTEMS.COM

    Trade Show

    Preview

    ACHEMA & EASA

    2 Simple Steps to

    Choosing the Right Motor

    PLUS: Prevent System Failures In CHEMICAL PUMPING Applications

  • """"

    """"""""""""""""

    Gzgewvkxg"uwooct{"Gpgti{"equvu"jcxg"dgeqog"cp"kpetgcukpi"eqpvtkdwvqt"vq"rworkpi"u{uvgou"Vqvcn"Equv"qh"Qypgtujkr"*VEQ+0"Kp"hcev."gpgti{"equv"tgrtgugpvu"62'"qh"vjg"VEQ"qh"c"v{rkecn"rwor0"Kv"ku"rquukdng"vq"tgfweg"vjg"gngevtkecn"eqpuworvkqp"d{"cv"ngcuv"52'"wvknkkpi"Xctkcdng"Urggf"Ftkxgu"yjkng"fgetgcukpi"ockpvgpcpeg"equvu"cuuqekcvgf"ykvj"vjg"ogejcpkecn"ftkxgp"u{uvgo0"Vjku"rcrgt"gzrnckpu"jqy"vq"tgfweg"VEQ"ykvj"c"nkokvgf"kpxguvogpv"hqewugf"qp"vjtgg"mg{"ctgcu

  • Circle 111 on card or visit psfreeinfo.com.

  • June 2015 | Pumps & Systems

    2

    From the EditorAs you know, Pumps & Systems is the only trade publication that covers motors and drives in every issue. is

    month, we head to San Antonio for the

    largest motor-related trade show of the

    year, the Electrical Apparatus Service

    Association (EASA) Convention &

    Exposition.

    We recently reported (March 2015)

    about how to prepare for the new

    Department of Energy Electric Motor

    Effi ciency Rule, which takes eff ect in

    June 2016. is will certainly be a topic

    of conversation at this years EASA event.

    Drop by Booth 262 at EASA to visit the Pumps & Systems team.

    Original equipment manufacturers and end users should contact their motor suppliers

    and prepare a plan to convert their motors to premium effi cient designs if they are not

    already being used. e performance of more effi cient motors may be slightly diff erent

    because they have less slip and operate at a higher speed. Impeller designs may need

    trimming to prevent overloading the motor from increased fl ow. We will continue to

    bring you information, and you can also access it quickly at pumpsandsystems.com.

    Be sure and see our cover series on motors and drives in this issue, beginning on page

    54, which features two simple steps to choosing the right motor.

    is month, Pumps & Systems also attends the largest chemical trade show in the

    world. ACHEMA is the premier world forum for chemical engineering and processing

    and takes place every three years in Frankfurt, Germany. More than 160,000 visitors

    from 111 countries attended the show in 2012, and 3,800 exhibitors are expected to

    showcase their products and services this year. We hope to see you there!

    e challenge for manufacturers and users of many dangerous chemicals is to

    construct, handle and transfer them in a way that eliminates any chance for their release

    into the atmosphere. Some of the solutions are addressed in this months Effi ciency

    Matters (page 84). You can also read about how sealless pumps with magnetic couplings

    are helping to solve chemical processing challenges (page 88).

    Best regards,

    EDITORIAL

    EDITOR-IN-CHIEF: Michelle [email protected] 205-314-8279

    MANAGING EDITOR: Savanna [email protected] 205-278-2839

    MANAGING EDITOR: Amelia Messamore [email protected] 205-314-8264

    MANAGING EDITOR: Michael Lambert [email protected] 205-314-8274

    ASSOCIATE EDITOR: Amy [email protected] 205-278-2826

    SENIOR EDITOR, PUMPS DIVISION: Alecia [email protected] 205-314-3878

    CONTRIBUTING EDITORS: Laurel Donoho, Lev Nelik, Ray Hardee, Jim Elsey

    CREATIVE SERVICES

    SENIOR ART DIRECTOR: Greg Ragsdale

    ART DIRECTORS: Jaime DeArman, Melanie Magee

    WEB DEVELOPER: Greg Caudle

    PRINT ADVERTISING TRAFFIC: Lisa [email protected] 205-212-9402

    CIRCULATION

    AUDIENCE DEVELOPMENT MANAGER: Lori Masaoay [email protected] 205-278-2840

    ADVERTISING

    NATIONAL SALES MANAGER: Derrell Moody [email protected] 205-345-0784

    ACCOUNT EXECUTIVES:

    Mary-Kathryn [email protected] 205-345-6036

    Mark [email protected] 205-345-6414

    Addison [email protected] 205-561-2603

    Garrick [email protected] 205-212-9406

    EUROPE-MIDDLE EAST: Maik [email protected] +1 205-567-1547+49 170 58299 59

    MARKETING ASSOCIATES:

    Ashley Morris [email protected] 205-561-2600

    Sonya [email protected] 205-314-8276

    PUBLISHER: Walter B. Evans Jr.VP OF SALES: Greg Meineke

    VP, EDITOR-IN-CHIEF PUMPS DIVISION: Michelle Segrest

    CREATIVE DIRECTOR: Terri J. Gray

    CONTROLLER: Brandon Whittmore

    P.O. Box 530067Birmingham, AL 35253

    EDITORIAL & PRODUCTION

    1900 28th Avenue South, Suite 200Birmingham, AL 35209205-212-9402

    ADVERTISING SALES

    2126 McFarland Blvd. East, Suite ATuscaloosa, AL 35404205-345-0784

    PUMPS & SYSTEMS (ISSN# 1065-108X) is published monthly by Cahaba Media Group, 1900 28th Avenue So., Suite 200, Birmingham, AL 35209. Periodicals postage paid at Birmingham, AL, and additional mailing offi ces. Subscriptions: Free of charge to qualifi ed industrial pump users. Publisher reserves the right to determine qualifi cations. Annual subscriptions: US and possessions $48, all other countries $125 US funds (via air mail). Single copies: US and possessions $5, all other countries $15 US funds (via air mail). Call 630-739-0900 inside or outside the U.S. POSTMASTER: Send changes of address and form 3579 to Pumps & Systems, Subscription Dept., 440 Quadrangle Drive, Suite E, Bolingbrook, IL 60440. 2015 Cahaba Media Group, Inc. No part of this publication may be reproduced without the written consent of the publisher. The publisher does not warrant, either expressly or by implication, the factual accuracy of any advertisements, articles or descriptions herein, nor does the publisher warrant the validity of any views or opinions offered by the authors of said articles or descriptions. The opinions expressed are those of the individual authors, and do not necessarily represent the opinions of Cahaba Media Group. Cahaba Media Group makes no representation or warranties regarding the accuracy or appropriateness of the advice or any advertisements contained in this magazine. SUBMISSIONS: We welcome submissions. Unless otherwise negotiated in writing by the editors, by sending us your submis-sion, you grant Cahaba Media Group, Inc., permission by an irrevocable license to edit, reproduce, distribute, publish and adapt your submission in any medium on multiple occasions. You are free to publish your submission yourself or to allow others to republish your submission. Submissions will not be returned. Volume 23, Issue 5.

    The Pumps & Systems and Upstream Pumping teams visiting the team from Accudyne at OTC in Houston

    Pumps & Systems is a member of the following organizations:

    Editor, Michelle Segrest

    [email protected]

  • Vaughans Rotamix System sets the standard for hydraulic mixing, providing the customer with

    lower operating and maintenance costs, more efficient breakdown of solids and Vaughans

    UNMATCHED RELIABILITY. Its perfect for digesters, sludge storage tanks, equalization basins

    and other process or suspension type mixing applications.

    - Over 1000 installations worldwide

    - Optimizes solids contact with its unique dual rotational zone mixing pattern

    - 10 Year Nozzle warranty

    See videos, drawings, and details at ChopperPumps.com or call 888.249.CHOP

    Circle 110 on card or visit psfreeinfo.com.

  • 4

    June 2015 | Pumps & Systems

    This issue 54 2 SIMPLE STEPS TO CHOOSING THE

    RIGHT MOTOR By Mike Stockman, Franklin Electric

    Consider more than the e ciency rating to select the most cost-e ective system for the pumping application.

    58 HOW TO PREVENT THE MOST FREQUENT CAUSES OF MOTOR FAILURE Last of Two Parts By Rob Amstutz, GE Power Conversion

    Protecting these two components can lead to longer equipment life.

    62 STAINLESS STEEL IDEAL FOR EQUIPMENT IN SANITARY ENVIRONMENTSBy David Steen, Baldor Electric Company

    is motor material provides an improved total cost of ownership for the food and beverage industry.

    64 BEARING PROTECTION FOR VFD-DRIVEN, EXPLOSION-PROOF

    MOTORS IMPROVES RELIABILITYBy Rick Munz & Adam Willwerth,

    Marathon Electric Motors

    In plants that process combustible materials, these motors avoid electrical bearing damage often caused by energy-saving inverters.

    68 DOC ENGINE TECHNOLOGY PROVIDES COST-EFFECTIVE TIER 4 COMPLIANCE By Anne Chalmers, Pioneer Pump

    Pumping packages that use a diesel oxidation catalyst can minimize cost, maintenance and equipment downtime.

    70 ENERGY-EFFICIENT MOTORS CURB ENVIRONMENTAL CRISISBy Zi Ning Chong, Frost & Sullivan

    e Chinese government is promoting greater automation and optimization of processes to improve the energy utilization rate.

    JUNEVolume 23 Number 6

    COVERS E R I E S

    PUMPING PRESCRIPTIONS

    14 By Lev Nelik, Ph.D., P.E. Pumping Machinery, LLC

    Handling Power Plant Transients

    PUMP SYSTEM IMPROVEMENT

    18 By Ray Hardee Engineered Software, Inc.

    Understand How Valves & Fittings A ect Head Loss

    Last of Two Parts

    COMMON PUMPING MISTAKES

    22 By Jim Elsey Summit Pump Company, Inc.

    What You Need to Know About Bearing Oil

    Last of Two Parts

    GUEST COLUMN

    32 By Heinz P. Bloch, P.E.

    How Oil Viscosity & Temperature In uence Bearing Function

    First of Two Parts

    2 FROM THE EDITOR

    8 NEWS

    91 PRODUCTS

    92 PUMP USERS MARKETPLACE

    96 PUMP MARKET ANALYSIS

    MOTORS & DRIVES

    SPECIALS P E C I A LS E C T I O N

    CHEMICAL PUMPS & EQUIPMENT

    84 SOLID-BODY AODD PUMPS WITHSTAND & CONTAIN DANGEROUS CHEMICALS EFFICIENCY MATTERS

    By Peter Schten, Almatec

    is equipment avoids the risk of leaks and pipe damage associated with injection mold pumps.

    88 STOP SEAL FAILURES IN CHEMICAL APPLICATIONS By James Gross, Dickow Pump Company

    Sealless pumps improve reliability and safety when pumping hazardous uids.

    54

    64

    88

    COLUMNS

    73 TRADE SHOW ELECTRICAL APPARATUS SERVICE ASSOCIATION CONVENTION

    90 TRADE SHOW ACHEMA

  • VR Series vertical multi-stage pumps are now available in 3, 5, 9, 15, 20, 30, 45, 65,

    and 95 m3/h options with all 316 stainless steel hydraulics for superior durability,

    eciency, and performance. The rugged components ensure long operating life in

    the toughest applications: water supply and pressure boosting; heating, ventilation

    and air conditioning; light industry; water treatment; irrigation and agriculture.

    Experience Innovation. Experience Franklin.

    franklinwater.com

    EXPANDING YOURPUMPINGCAPABILITIES

    Circle 108 on card or visit psfreeinfo.com.

  • 6

    June 2015 | Pumps & Systems

    SPECIALS P E C I A LS E C T I O N

    JUNEThis issue

    THOMAS L. ANGLE, P.E., MSC, Vice President Engineering, Hidrostal AG

    ROBERT K. ASDAL, Executive Director, Hydraulic Institute

    BRYAN S. BARRINGTON, Machinery Engineer, Lyondell Chemical Co.

    KERRY BASKINS, VP/GM, Milton Roy Americas

    WALTER BONNETT, Vice President Global Marketing, Pump Solutions Group

    R. THOMAS BROWN III, President, Advanced Sealing International (ASI)

    CHRIS CALDWELL, Director of Advanced Collection Technology, Business Area Wastewater Solutions, Sulzer Pumps, ABS USA

    JACK CREAMER, Market Segment Manager Pumping Equipment, Square D by Schneider Electric

    BOB DOMKOWSKI, Business Development Manager Transport Pumping and Amusement Markets/Engineering Consultant, Xylem, Inc., Water Solutions USA Flygt

    DAVID A. DOTY, North American Sales Manager, Moyno Industrial Pumps

    WALT ERNDT, VP/GM, CRANE Pumps & Systems

    JOE EVANS, Ph.D., Customer & Employee Education, PumpTech, Inc.

    DOUG VOLDEN, Global Engineering Director, John Crane

    LARRY LEWIS, President, Vanton Pump and Equipment Corp.

    TODD LOUDIN, President/CEO North American Operations, Flowrox Inc.

    JOHN MALINOWSKI, Sr. Product Manager, AC Motors, Baldor Electric Company, A Member of the ABB Group

    WILLIAM E. NEIS, P.E., President, Northeast Industrial Sales

    LEV NELIK, Ph.D., P.E., APICS, President, PumpingMachinery, LLC

    HENRY PECK, President, Geiger Pump & Equipment Company

    MIKE PEMBERTON, Manager, ITT Performance Services

    SCOTT SORENSEN, Oil & Gas Automation Consultant & Market Developer, Siemens Industry Sector

    ADAM STOLBERG, Executive Director, Submersible Wastewater Pump Association (SWPA)

    JERRY TURNER, Founder/Senior Advisor, Pioneer Pump

    KIRK WILSON, President, Services & Solutions, Flowserve Corporation

    JAMES WONG, Associate Product Manager Bearing Isolator, Garlock Sealing Technologies

    EDITORIAL ADVISORY BOARD

    INSTRUMENTATION, CONTROLS & MONITORING

    DEPARTMENTS

    74 MAINTENANCE MINDERSMonitoring Software Enables Scheduled Maintenance at Oil & Gas Facilities

    By Cynthia Stone

    GE Intelligent Platforms

    76 MOTORS & DRIVESMotor Automation Can Help Solve Industry Labor Shortage

    By William C. Livioti

    WEG

    78 SEALING SENSENew FSA/ESA Gasket Handbook O ers Guidance for Equipment Usage & Troubleshooting

    By Mike Shorts

    FSA Member

    82 HI PUMP FAQSCorrosion Prevention, Rotodynamic Pump Speed & How Harmonics A ect VFDs

    By Hydraulic Institute

    42 PROTECT PUMPS WITH ONE ESSENTIAL TOOL

    By Craig McIntyre, Endress+Hauser

    Pump sensors can improve system operation and detect dangerous faults.

    47 ELIMINATE CABLING COSTS THROUGH PROPRIETARY WIRELESS NETWORKING

    By Dave Eifert & Benjamin Fiene, Phoenix Contact

    A German municipal water utility optimized pressure booster stations with automated modules.

    36 NEW HI DOCUMENT PROVIDES GUIDANCE ON DYNAMIC ANALYSIS OF ROTODYNAMIC PUMPS

    By J. Claxton, P.E., Patterson Pump Company, a Gorman-Rupp company

    is 10-year project concluded with the recent publication of recommended guidelines for pump professionals.

    INDUSTRY UPDATESPECIAL REPORT

  • Circle 109 on card or visit psfreeinfo.com.

  • 8 NEWS

    June 2015 | Pumps & Systems

    NEW HIRES, PROMOTIONS & RECOGNITIONSTONY SWENDSRUD, PSG

    OAKBROOK TERRACE, Ill. (April 23, 2015) PSG, a Dover company, announced that Tony Swendsrud has joined the company as its new chief financial officer. In this role, Swendsrud will be responsible for all facets of PSGs financial functions and will report directly to PSG President Karl Buscher. Swendsrud joins PSG from the Honeywell Corporation, where he held the position of CFO Analytics Americas. Swendsrud holds a bachelors degree in accounting from St. Cloud State University in St. Cloud, Minnesota. He is also a certified public accountant. He will be based in PSGs headquarters office in Oakbrook Terrace, Illinois. psgdover.com

    HASAN AVCI, GRUNDFOS

    SINGAPORE (April 23, 2015) Pump manufacturer Grundfos has recently appointed Hasan Avci to head its Strategy, Commercial Excellence and Marketing functions in the Asia Pacific region. Avci has been with Grundfos since 2003. Before his posting to Grundfos Asia Pacific headquarters in Singapore, Avci was the director of sales and marketing for Turkey and the Middle East region. In his new role, Avcis main responsibility will be to formulate organizational strategies for performance improvements across the region. He will also implement commercial processes, undertake strategic corporate planning, evaluate new business opportunities and spearhead initiatives to promote business growth. grundfos.com

    MICHAEL RICHART, ESE, INC.

    MARSHFIELD, Wis. (April 21, 2015) ESE, Inc., has named Michael Richart as the companys director of business operations. Richart brings more than 20 years of experience as a versatile strategic executive. Richart will lead the sales and business operations areas of ESE. Throughout his career, Richart has helped companies succeed by optimizing the intersection of data, people, process and technology. Richart received his Bachelor of Sciences degree in industrial engineering from Purdue University and his MBA from the University of Wisconsin Oshkosh. ese1.com

    PAUL COOKE, BOSCH REXROTH

    CORPORATION U.S.

    CHARLOTTE, N.C. (April 20, 2015) Effective July 1, Paul Cooke has been appointed regional president Americas and president & CEO of Bosch Rexroth Corporation U.S. Cooke will continue as senior vice president sales within the Business Unit Industrial Applications at the headquarters in Lohr, Germany, until the end of June 2015. Cooke has more than 30 years of experience in both industrial technology and general management. He received his

    Bachelor with Honors Degree in mechanical engineering from The University of Newcastle in Tyne, England. Berend Bracht, current regional president Americas and president & CEO of Bosch Rexroth Corporation U.S., is resigning from the organization for personal reasons.

    JIM LAURIA, MAZZEI INJECTOR

    COMPANY, LLC

    BAKERSFIELD, Calif. (April 9, 2015) Mazzei Injector Company, LLC, has appointed Jim Lauria as vice president of sales and marketing. Lauria has been a leader in water and wastewater for more than 15 years and has had articles published in prominent water industry publications worldwide. Lauria holds a Bachelor of Chemical Engineering degree from Manhattan College. Lauria will be replacing Paul Overbeck who is retiring. mazzei.net

    PHIL CARLIN & MICHAEL SAVIGNAC, OPW

    HAMILTON, Ohio, & HODGKINS, Ill. (April 2, 2015) OPW, a Dover company, announced that, as part of its growth strategy and One OPW initiative, it has consolidated its OPW KPS, OPW Fibrelite and OPW Fluid Transfer Group Europe management teams to create a single business unit, named OPW EMEA. Phil Carlin has been appointed managing director of the new business unit and will report directly to OPW President David Crouse. Carlin joined OPW in 2000 and has held multiple positions with the company, including several senior executive positions. He will be based out of OPW EMEA headquarters in Kungsr, Sweden. In addition, Michael Savignac joined OPW as vice president and general manager for the OPW Electronic Systems business unit, succeeding Carlin. Savignac will provide leadership and overall management of the Electronic Systems business unit, which OPW formed in April 2014. Savignac will be based at the OPW facility in Hodgkins, Illinois, and will report to Crouse.

    To have a news item considered, please send the information to Amelia

    Messamore, [email protected].

    Hasan Avci

    Michael Richart

    Jim Lauria

    ACOEM Group acquired VibrAlign, Inc. April 30, 2015 ERIKS Seals and Plastics acquired Seals and Packings, Inc. April 21, 2015 Lewis-Goetz acquired Action Industrial Group April 9, 2015

    MERGERS & ACQUISITIONS

    Paul Cooke

    Michael Savignac

  • 9pumpsandsystems.com | June 2015Circle 118 on card or visit psfreeinfo.com.

  • 10 NEWS

    June 2015 | Pumps & Systems

    Danfoss Recognized for Impact on Technology, Jobs & Local Partnerships NORDBORG, Denmark (April 24, 2015) During a press conference on April 22, The Economic Development Council of Tallahassee/Leon County announced Danfoss as its featured business for the month of April as part of its Made in Tallahassee: Produced Regionally, Sold Globally initiative. The program is planned as a public awareness campaign that focuses on the important role that the research and development, manufacturing, software development and technology industries play in the success of the local economy. danfoss.com

    WERF & WEF Launch Projects to Further Water Sector Innovation ALEXANDRIA, Va. (April 22, 2015) The Water Environment Research Foundation (WERF) and the Water Environment Federation (WEF) are launching three new projects under the Leaders Innovation Forum for Technology (LIFT) program, a joint WERF/WEF initiative designed to promote innovation in the water sector.

    The first project, Genifuel Hydrothermal Processing Bench Scale Technology Evaluation (LIFT6T14), will evaluate a new biosolids to energy technology. The project is funded by WERF, the U.S. Environmental Protection Agency (EPA) and approximately 10 utilities participating in the LIFT program. The U.S. Department of Energy is also providing in-kind support.

    The next project, Creating the Space to Innovate (LIFT8C14), is co-funded by WERF and WEF to promote the adoption of innovative technologies and practices.

    WERF has also awarded The Canton Group with a contract to develop a LIFT Database (LIFT2R14), which is designed to support new water technology innovation, collaboration and implementation for the water sector. The platform will help deliver information on water technologies, facilitate collaboration for speeding innovation into practice, provide data from demonstrations and more. The development of the platform is supported in part with funding from the U.S. EPA. werf.org/lift

    Truckee Meadows Water Authority Wins National AwardRENO, Nev. (April 17, 2015) Truckee Meadows Water Authority (TMWA) has received the Presidents Award from the Partnership for Safe Water (PSW). With this award, TMWAs Chalk Bluff Water Treatment Plant ranks among the highest performing water treatment plants in the country for individual filter performance. Only 18 utilities across the country have achieved this award.

    The Presidents Award recognizes achieving Phase IVs stringent individual filter performance goals for turbidity. awwa.org

    POWER-GEN Europe Launches the Confidence Index to Build Industry ExpertiseLONDON (April 14, 2015) POWER-GEN Europe and its co-located event Renewable Energy World Europe has announced the launch of the POWER-GEN Confidence Indexa pan- European study of the regions power market which will allow power generation industry practitioners from across Europe to have their say on the industry. The results will be launched in September 2015, and they will allow industry decision makers across Europe to make well-informed choices as they navigate the next critical stages of the energy transition.

    The report will evaluate the industrys attitude toward new initiatives and give companies insight into how these changes are viewed by the industry.

    The survey that feeds into the Index will be carried out on an annual basis and allow the industry to track year-on-year trend analysis and comparison. powergeneurope.com

    Xylem Participates in U.S. Presidential Trade Mission to the Peoples Republic of ChinaRYE BROOK, N.Y. (April 13, 2015) Xylem Inc. participated in the U.S. Presidential Trade Mission to the Peoples Republic of China, April 12-17. U.S. Secretary of Commerce Penny Pritzker and Deputy Secretary of Energy Elizabeth Sherwood-Randall led this Smart Cities Smart Growth Business Development Mission, accompanied by representatives from 25 companies.

    The trade mission was intended to help U.S. companies launch or increase their business operations in China for sustainable products and services.

    Chris McIntire, Xylem senior vice president and president, analytics and treatment, and Shuping Lu, president of Xylem China, represented Xylem on this mission. xyleminc.com

    PTDA Welcomes Three New Distributor MembersCHICAGO (April 13, 2015) The Power Transmission Distributors Association (PTDA), an association for the industrial power transmission/motion control (PT/MC) distribution channel, welcomed three new distributor member companies: BK Industrial Solutions, LLC (Beaumont, Texas), SAECOWilson Limited (Auckland, New Zealand) and Warrior Industrial, LLC (McKinney, Texas). ptda.org

    SFPUC Completes New Seismic Upgrades to Drinking Water Treatment Plant SAN FRANCISCO (April 10, 2015) The San Francisco Public Utilities Commission (SFPUC) together with San Mateo Board of Supervisors Dave Pine and Peninsula water agencies stood on top of a new 11 million gallon treated water reservoir to celebrate the completion of a $278 million project improving the seismic and operational reliability of the Harry Tracy Water Treatment Plant located in San Bruno. The 43-year-old treatment plant is responsible for treating the drinking water for more than 1 million customers in San Mateo and San Francisco Counties.

    The project is part of the SFPUCs $4.8 billion Water System Improvement Program, which consists of 83 projects across seven counties designed to improve seismic and water supply reliability for 2.6 million people in the Bay Area. sfwater.org

    ABB Opens New Automation & Power Service Office in Louisiana SULPHUR, La. (April 8, 2015) ABB has opened a new local service office near Lake Charles, Louisiana. The office will provide services and support for ABBs automation and power

    AROUND THE INDUSTRY

  • 11

    pumpsandsystems.com | June 2015

    Those shiny new bearings you just installed

    could look like this in

    just 3 months!

    1-866-738-1857 | sales @ est-aegis.com

    BEARING PROTECTION RINGS

    Protect bearings from shaft voltage damage

    For more information aboutAEGIS Bearing Protection Ringsor for an informative guide toMotor Bearing Protection, visit:

    www.est-aegis.com/handbook

    EASA Show: Booth 630

    Visit us at

    Circle 107 on card or visit psfreeinfo.com.

  • 12

    June 2015 | Pumps & Systems

    NEWS

    portfolio including control systems, instrumentation, analytical products, low-voltage drives, and power systems and products. The new office will offer scheduled in-

    center training, as well as customized training courses. ABB has also announed several new investments in the area. abb.com

    Xylem Contributions Recognized at HIs 2015 Annual MeetingRYE BROOK, N.Y. (April 2, 2015) Five employees from the Applied Water Systems (AWS) business unit of Xylem were recognized by the Hydraulic Institute (HI) for their longtime service to and involvement in HI. Awards and the team members they

    were presented to are as follows: Mark Handzel, Vice President

    Product Regulatory Affairs and Director, HVAC Commercial Buildings, Americas Industry Leadership Award for U.S. Department of Energy pump efficiency regulations

    Mark Heiser, Test & Validation Manager Industry Leadership Award for development of HI Standard 40.7 and recognition for completion of standard development for DOE pump efficiency regulations

    Paul Ruzicka, Chief Mechanical Engineer Industry Leadership Award for development of HI Standard 40.6 and recognition for completion of standard development for DOE pump efficiency regulations

    Chris Johnson, Global Engineering Manager, Centrifugal Pumps Recognition for contributions to HI standards development

    Jim Roberts, Associate Principal Mechanical Engineer Recognition for 20 years of service to the development of HI standards

    xyleminc.com

    Powdersville Water District Receives National AwardDENVER (March 30, 2015) Powdersville Water is the first utility in South Carolina to achieve the Directors Award in the Partnership

    for Safe Waters Distribution System Optimization Program and one of only 11 nationwide. Powdersville Water received this award for successfully completing a comprehensive self-assessment of distribution system operations. Powdersville Water will be one of a

    select group of utilities recognized at the annual conference and exposition of the American Water Works Association in June. awwa.org

    AEP Ohio Offers New Energy Efficiency ProgramRALEIGH, N.C. (March 26, 2015) AEP Ohio, a unit of American Electric Power, in partnership with Advanced Energy, has launched the Emotor Rewind Pilot Program to promote energy efficient rewinds in the industrial/manufacturing sector and provide incentives to users and motor service centers. The program covers 300- to 5,000-HP, three-phase induction motors and is expected to achieve annual energy savings of 5,900 to 116,000 kWh, depending on the motor size. AEP Ohio customers located in Ohio will receive $2 per HP, and certified motor service centers will receive $1 per HP. aepohio.com

    ITTs Conoflow Brand Names Enertech Exclusive Global Nuclear Industry RepresentativeWESTMINSTER, S.C. (April 20,

    2015) ITTs Conoflow brand has appointed Enertech, a business unit of Curtiss-Wright Nuclear Division, as the exclusive nuclear industry representative for its valve and regulator products globally. ITTs Conoflow manufactures natural gas vehicle (NGV), low-pressure and high-pressure regulators along with filter and specialty regulators. Enertech has served the nuclear power industry for more than 40 years. In this partnership, Enertech will be the point of contact for technical inquiries, quotations and order entry/status, while Conoflow will retain its nuclear quality assurance program, along with certifications and documentation. conoflow.com

    EVENTSPump School Training: Centrifugal & Positive Displacement Pumps June 2-3, 2015One Midtown Plaza Atlanta, Ga. 770-310-0866pumpingmachinery.com/pump_school/pump_school.htm

    American Water Works Association Annual Conference & Exposition (AWWA-ACE) June 7-10, 2015 Anaheim Convention Center Anaheim, Calif. 800-926-7337 awwa.org

    EASAs 2015 Convention & Exhibition June 14-16, 2015 Grand Hyatt San Antonio & Henry B. Gonzalez Convention Center San Antonio, Texas easa.com/convention

    ACHEMAJune 1519, 2015Messe FrankfurtFrankfurt am Main, Germanyachema.de/en.html

    National Fire Protection Association (NFPA) Conference & ExpoJune 2225, 2015McCormick PlaceChicago, Ill.800-344-3555nfpa.org/training/conference

    5th Annual Pumps Hands-on Training: Maintenance, Energy and Reliability Conference (PumpTec-Israel)July 7, 2015Tel Aviv, Israel770-310-0866pumpingmachinery.com/pump_school/pump_school.htm

    IDA World CongressAug. 30 Sept. 4, 2015San Diego Convention CenterSan Diego, Calif.wc.idadesal.org/

  • 13

    pumpsandsystems.com | June 2015

    Demand ReliabilityBecause downtime is never on the schedule.

    www.alltestpro.comwww.bjmpumps.com

    The ideal instrumentsfor troubleshooting,quality control andtrending of electric

    motors, transformersand generators

    Complete Stator and

    Rotor Analysis Detect early

    faults in AC & DC motors,

    transformers and generators.

    Driven Load Analysis Evaluate

    and trend the condition of geared,

    belted and bladed equipment.

    Route-Based Testing and

    Trending Ideal for predictive

    maintenance.

    Comprehensive Reporting

    Includes bad connections, winding & turn faults, air gap,

    broken bar, contamination, ground faults and more.

    ALL-TEST Pro instruments providecomplete electric motor system

    health analysis in minutes!

    Electric SubmersiblePumps for DifficultWastewater Solids

    Patent Pending RAD-AX

    Dual Shredding Technology Radial and axial

    shredding elements. System efficiency alleviates

    potentially high surge load to the motor.

    High Efficiency Motor High-torque,

    4-pole motor - 2, 3 and 5HP.

    Impeller Design High solids passage impeller

    design expedites flow and hydraulic performance,

    preventing clogs.

    Robust Construction Chrome iron impeller

    and suction cover. All shredding elements

    are hardened 440C SS with a Rockwell hardness

    of 55C+.

    Superior Motor Insulation and SS Motor

    Housing Class F insulation and SS motor

    housing for superior corrosion resistance

    and longer life.

    Double Mechanical Seals

    Oil-lubricated (SIC x 2), with separate

    lip seal.

    Oversized Bearings and Shaft

    Handle extra torque and loads.

    Motor Overload Protection

    Defense against thermal and amperage

    overloads. Available in 208v, 230v,

    460v and 575v.

    33 Ft. Heavy-

    Duty SOOW

    Power and Seal

    Minder Cable

    For early warning

    moisture detection.

    The new SKG Series from BJM isdesigned to obliterate flushablewipes and other difficult solids inwastewater applications.

    Innovative features include:

    Test All Electric Motors, Regardlessof Location

    MotorTesters

    De-energizedtesting

    Predictive MaintenanceTroubleshooting

    Route-Based TestingTrending

    Quality Control

    Energized testing

    Circle 103 on card or visit psfreeinfo.com.

  • Letter from a Reader

    e following comments relate to

    scenarios described in Parts 1 and

    2 of Can Deaerators Create Pump

    Trips? (Pumps & Systems, March

    and April 2015), which discuss

    handling power plant transients.

    Steady fl ows to and from the

    deaerator (DA) and gradual

    isentropic thermodynamic changes

    from the high to low temperature/

    pressure conditions are assumed.

    A gradual power plant cool down

    period after a shutdown event may

    mitigate general or local fl ashing.

    From Part 1 at Point A:

    DA total tank volume V =

    20,000 gallons = 2,674 cubic

    feet (ft3).

    Tank liquid (water) volume

    (Vliq) = 10,000 gallons =

    1,337 ft3.

    Mass of tank liquid (mliq) =

    Vliq

    vf= 76,564 lbm.

    Mass of tank vapor (mvap) = 0

    lbm (all mass is saturated

    liquid at vf).

    Total mass of tank contents (M)

    = mliq + mvap = 76,564 lbm.

    Using the above values, the

    calculated specifi c volume

    (v) should agree with the

    temperature-specifi c volume

    (T-v) diagram at Point A.

    However, calculated v =

    V

    M= 0.03492 ft3/lbm.

    is value is greater than vf

    = 0.01746 ft3/lbm from the

    diagram. Since the vapor

    volume Vvap = mvap x vg =

    0 ft3, the analysis might be

    conducted by assuming that

    the total tank volume revV =

    Vliq + Vvap = 1,337 ft3. In other

    words, assume the total DA

    tank volume is 10,000 gallons

    and completely full of liquid

    (water) at Point A. en, at

    Point A on the diagram, v =

    revV

    M= 0.01746 ft3/lbm = vf.

    Using revV and v for

    calculations at Point B, X = 0.003%,

    vapor mass mvap = X x M = 2.3

    lbm, vapor volume Vvap = mvap

    x vg = 24.5 ft3, liquid mass mliq

    = (1-X) x M = 76,562 lbm, liquid

    volume Vliq = mliq x vf = 1,312.3

    ft3. erefore, the total volume and

    mass of the tank contents remain

    the same. However, the vapor

    volume has increased by the same

    amount that the liquid volume has

    decreased. e less dense vapor

    must occupy a larger space than

    the reduction in liquid volume.

    Because there is no additional tank

    space to occupy, some liquid may

    be expelled from the 10,000-gallon

    DA or excess vapor pressure might

    activate a relief valve.

    Expelled tank liquid may imply

    that the total mass of the DA tank

    contents decreases at Point B:

    Specifi c volume at Point B is greater

    than at Point A. Using vb = 0.018

    ft3/lbm at Point B, the calculated

    vapor volume is now about 66 ft3

    at Point B compared with 24.5 ft3

    if v = 0.01746 ft3/lbm. Since the

    new liquid volume is now 1,312 ft3,

    about 41 ft3 must be expelled from

    the tank at Point B: 66 + 1,312 41

    ft3 = 1,337 ft3 = the tank volume.

    However, I would not expect

    a DA tank to be either half full

    of liquid without any vapor or

    completely full of liquid. A more

    likely location for Point A might be

    to the right of the saturated liquid

    state where a two-phase liquid and

    vapor state existsPoint A1.

    e originally calculated specifi c

    volume, v = 0.03492 ft3/lbm,

    represents a liquid and vapor

    state at 302 F. If this value is

    chosen, a new set of values can be

    determined at Point A1 and Point

    B1: X = 0.17% at B1, Vvap = +23

    ft3, and Vliq = -23 ft3. In this case,

    the vapor has enough room for

    expansion going from a calculated

    1,341 ft3 at A1 to 1,363 ft3 at B1.

    However, while the calculated

    liquid volume has decreased at B1,

    the corresponding liquid mass has

    increased. is seems unlikely.

    After some trials, it was

    determined that reasonable

    changes in volume and mass occur

    if the specifi c volume is greater

    than about 0.29 ft3/lbm for the

    given data in this article. If another

    specifi c volume such as v = 0.5

    ft3/lbm is chosen, another set of

    liquid and vapor state values can

    be determined at Points A2 and B2:

    X = 4.52% at B2, Vvap = -1.33 ft3,

    and Vliq = +1.33 ft3. In this case,

    the vapor volume has contracted

    going from a calculated 2,587 ft3

    at A2 to 2,586 ft3 at B2. Now, the

    calculated liquid volume and mass

    have both increased at B2, while

    the calculated vapor volume and

    mass have decreased at B2. Vapor

    condensation, from state A2 to B2,

    Handling Power Plant Transients

    14 PUMPING PRESCRIPTIONS

    June 2015 | Pumps & Systems

    By Lev Nelik, Ph.D., P.E.

    Pumping Machinery, LLC,

    P&S Editorial Advisory Board

    Troubleshooting & repair challenges

  • is now the result. is seems to

    be a realistic outcome after slowly

    cooling. Although it should be

    noted that, with v = 0.5 ft3/lbm,

    there is a substantial diff erence in

    liquid and vapor mass and volume

    values when compared with the

    original calculations from above.

    After an emergency trip

    situation, there may be ongoing

    automatic and/or manual

    adjustments as various plant

    elements (DAs, pumps, etc.) react

    to changing system conditions. If

    the liquid+vapor mass (M) within a

    fi xed-volume DA tank can decrease

    or increase in response to some of

    these changes, maybe the specifi c

    volume is not necessarily constant

    at diff erent thermodynamic states.

    Besides the dynamics occurring

    inside the DA tank, I would expect

    that any major net positive suction

    head (NPSH) problem at the pump

    suction might be attributed to

    entrained air, not water vapor,

    being transferred from the DA

    liquid to the boiler feed pump.

    Before being shut down, the

    injected pegging steam might have

    removed most of this air.

    In Part 2, I would not expect

    a signifi cant problem at Pump 2

    from an interaction at the junction

    of its header and the hotter liquid

    in Header 1. If the liquid in Header

    2 is gradually cooling and fl owing

    past the junction, the temperature

    diff erence at a junction may be too

    gradual for a fl ashing reaction.

    However, for Pump 1, if it is again

    started with its header full of 302

    F liquid and only 39 psia available

    at the junction, there might be an

    insuffi cient NPSH condition as

    pointed out in the article. Perhaps

    Pump 1 would be able to pass

    the 50-ft header full of hotter

    liquid quick enough to avoid any

    signifi cant damage or pump trip.

    Of course, the above analysis

    is based on simplifi ed ideal

    conditions with gradual

    thermodynamic changes. Feedback

    from readers with experience in

    power plants and the eff ects of

    transients on pumps would be

    insightful.

    Lee Ruiz

    Oceanside, California

    Neliks Response

    ank you for your comments.

    ese are very diligent and

    methodical calculations. I have a

    few notes to your comments.

    Your assumption of the process

    being gradual and isentropic

    cannot be assumed, because it

    is highly transient. is is one

    of the reasons it is not easy to

    calculate. Several thermodynamic

    sub-processes that are highly

    time dependent are taking place:

    convection from hotter liquid

    to colder, phase transformation

    and cooling of the vapor that is

    evolving back into liquid phase as

    it tries to rise through the colder

    liquid layer. Perhaps the only safe

    assumption for the process is

    that it is adiabatic, assuming no

    heat loss through the pipe to the

    surroundings occurs as a result of

    thick insulation.

    My assumption that Point A is

    liquid that occupies half of the

    tank space with zero vapor above it

    is problematic. While the pressure

    is signifi cant, a complete absence

    of vapor in the space above the

    liquid is impossible, as it would

    p1 = 69 psi

    266 F

    302 F

    subcooled

    saturated

    subcooled

    ?

    1 FT3

    1 FT3

    p2 = 50 psiA

    266 F

    302 F

    Figure 1. Visualization of vaporization and re-condensation (Courtesy of the author)

    15

    pumpsandsystems.com | June 2015

  • imply full vacuum. Because the

    fl uid in the DA is at the saturation

    curve or in the subcooled region,

    something must be present above

    the liquid to maintain pressure.

    To explain what keeps the void

    above the liquid at pressure in this

    case, we would need to understand

    more precisely the specifi cs of the

    DA design.

    Your note is well-placed; if we

    instead make a slight adjustment to

    starting Point A to be slightly into

    a two-phase region, this diffi culty

    immediately disappears. e entire

    space above the liquid would be

    vapor, the combined volume in the

    tank could be treated as the entire

    tank (20,000 gallons) instead of

    half of it (10,000 gallons), and the

    total combined specifi c volume

    would be total tank volume divided

    by total mass (which at Point A is

    mostly liquid). at would make

    the total combined volume double

    that if we used only half the tank.

    It does not aff ect Point A but makes

    things easier when going to point

    B, as we now have a total volume

    of the entire 20,000 gallons fi lled

    with a mixturesome liquid and

    some vapor. From there, vapor

    mass fraction x and volume can

    be calculated.

    My assumption that the entire

    system is a constant volume is

    valid, because otherwise, it is

    impossible to make any other

    reasonable assumptions. For

    example, we cannot assume

    constant pressure at Point B (As an

    example, imagine that the tank had

    a free heavy lid that would apply

    constant pressure and that the

    expanding volume of vapor would

    move the lid up).

    e tank described in these

    articles does not have moveable

    boundaries. e only openings

    are to the condensate piping and

    through the running pumps, but

    those are essentially closed (by

    running water).

    As explained in Part 2, vapor

    wants to expand according to a new

    pressure to which the surface of the

    DA is now suddenly at (Point B).

    But it is not a steady state process,

    and things are very transient. As

    vapor tries to form and fl oat up,

    it encounters a colder layer above

    it and condenses back to liquid

    almost instantaneouslyat many

    orders of magnitude faster than it

    takes for vapor to travel through

    the suction header of the running

    (colder) pump to reach its entrance.

    Instead, what likely is happening is

    convective cooling of the hotter leg

    by the colder leg via this attempted

    vaporization and re-condensation

    (see Figure 1, page 15).

    Imagine that you have two layers

    of fl uid of equal volume, separated

    by a very thin membrane. Initially,

    69 psi is enough to keep both

    liquids subcooled (the lower layer

    is subcooled but not as subcooled

    as the upper layer). Suddenly,

    pressure at the surface drops to

    50 psi, at which the top layer is

    still subcooled, but the bottom

    layer enters the vapor phase. Will

    it immediately fl ash out to many

    times more vapor volume? If so,

    where will it go?

    Assume that the membrane is

    thin and raptures as vapor forms.

    e bubbles trying to form at the

    lower layer would have to meet

    the colder layer and return to

    liquid form. is would go on for

    some time and eventually both

    fl uids would mix at the average

    temperature (266+302)/2. If 50 psi

    is in a vapor region, the fl uids will

    turn to vapor and fi ll the entire

    can. If the can is very tall, there

    will be more space for vapor to

    form (if it corresponds to vapor

    condition). Initially, however, all

    was in two liquid layers. After the

    drop of pressure (and if the new

    condition is vapor phase), however,

    the vapor will expand to take up

    the complete volume.

    Part 2 shows that, for the

    conditions used in the example

    and at the resultant average

    temperature, no two-phase

    situationand thus no vapor

    exists. is means the system

    experiences no cavitation or NPSH

    problem. However, in reality, no

    vapor would reach the running

    pump because the colder column

    is not static and mixing with the

    hotter liquid. Instead, while vapor

    wants to form and transmit its

    energy to heat up cooler liquid,

    that liquid is actually in motion,

    taking a heated chunk and moving

    it toward the pump.

    By the time the chunk fl ows

    through the entire length of pipe,

    the resultant rise in temperature

    of the fl owing liquid is minuscule.

    As a result, it is not even close to

    heating the cooler leg substantially.

    In other words, it is the DA

    temperature that would dictate the

    temperature of fl uid reaching the

    running pump.

    Dr. Nelik (aka Dr. Pump)

    is president of Pumping

    Machinery, LLC, an Atlanta-

    based fi rm specializing in pump

    consulting, training, equipment

    troubleshooting and pump

    repairs. Dr. Nelik has 30 years

    of experience in pumps and

    pumping equipment. He may

    be reached at pump-magazine.

    com. For more information, visit

    pumpingmachinery.com/pump_

    school/pump_school.htm.

    16 PUMPING PRESCRIPTIONS

    June 2015 | Pumps & Systems

  • 17

    pumpsandsystems.com | June 2015Circle 113 on card or visit psfreeinfo.com.

  • This series discusses valves and fi ttings and evaluates how these devices aff ect the

    operation of piping systems. Part 1(Pumps & Systems, May 2015) covered head loss, K value and L/D coeffi cient.

    CV Coeffi cient

    e CV value is an indication of the capacity of a valve or fi tting and is often used to describe the performance of control valves. e CV coeffi cient is often used to describe the hydraulic characteristics of elements in a pipeline. e defi nition of CV is the number of U.S. gallons per minute (gpm) of 60 F water fl owing through a valve or fi tting results in a 1 pound per square inch (psi) pressure drop across the device. For example, if a device has a

    CV value of 200, then when 200 gpm fl ows through the device, a 1 psi pressure drop would occur. Equation 6 describes the CV value.

    CV = Q

    Pin - PoutSG

    Equation 6

    WhereCV = Flow coeffi cient (unitless)Q = Flow rate (gpm)P = Pressure (psi)SG = Specifi c gravity of the fl uid

    (unitless)

    e equation can be rearranged to allow for the solution of the fl ow

    rate for a given pressure drop and the pressure drop for a given fl ow rate.

    Q = CV dPSGEquation 6 gives the result of using C

    V in diff erential pressure instead

    of head. If a manufacturer provides information in C

    V, users must

    convert it to diff erential pressure, then convert the results to head loss. Equation 7 can be used to eliminate the need to convert from pressure to head. It allows for the conversion of a C

    V value to a

    K value.

    K = 890.3 x

    d4

    (CV)2

    Equation 7

    WhereK = Resistance coeffi cient

    (unitless)CV = Flow coeffi cient (unitless)d = internal diameter (inches)

    Calculating the Head Loss

    Using K Value

    Regardless of the method used to arrive at a K value for a valve or fi tting, Equation 8 is used to calculate the head loss resulting from valves and fi ttings.

    hL = 0.00259

    KQ2

    d4 Equation 8

    When multiple valves and fi ttings in a pipeline have the same diameter, the K values for each valve or fi tting can be added. e sum of the K values can be used to calculate the head loss for all the valves and fi ttings.To demonstrate, calculate

    the head loss for the valves and fi ttings in a pipeline when 600 gpm of water is fl owing through the following valves and fi ttings: a sharp-edged transition from a tank to pipeline, a full-seated globe valve and a strainer with a CV value of 450. ese full-seated devices are in a 6-inch pipe with a turbulent friction factor of 0.015 inches. e K values are listed in Table 1. e resulting head loss with 600 gpm going through the pipeline is shown in Equation 9.

    Cross Section of Valves &

    Fittings

    Reference 1 has cross sections of types of valves and fi ttings and the corresponding K values or L/D coeffi cients. ere are too many types of valves and fi ttings to present in this article, but some attributes can be generalized. For example, a full-seat ball valve

    A better understanding of complete system operation

    Understand How Valves & Fittings Affect Head Loss

    Last of Two Parts

    hL = 0.00259

    KQ2

    d4 = 0.00259

    11.55 x 6002

    6.0654 = 7.95 ft of fl uid

    Equation 9

    dP = Q2 x SG(CV)2

    18 PUMP SYSTEM IMPROVEMENT

    June 2015 | Pumps & Systems

    By Ray Hardee

    Engineered Software, Inc.

  • with its straight-through design has a much lower

    L/D value than a globe valve through which the

    fl uid must make four changes of direction and

    fl ow around the valve disk within the fl ow path.

    e type of valve employed is based on many

    factors. Leak tightness is an important factor,

    but when two types of valves meet the same

    requirements, it is recommended to use the one

    with the lower head loss.

    Another example of fi ttings with varied loss

    coeffi cients are elbows. A short radius 90-degree

    elbow has an L/D coeffi cient of 20, but a long radius

    90-degree elbow has a L/D coeffi cient of 14. is

    may not seem like a signifi cant loss, but it adds up.

    So do the associated costs. e pump must supply

    the energy that is lost across the valves and fi tting.

    Cost of Pipeline Operation

    To demonstrate the pumping cost associated with

    valves and fi ttings, calculate the operating costs for

    diff erent types of valves and fi ttings. Equation 10

    can determine the pumping cost.

    Item Method Coeffi cient Value K value

    Sharp-edged transition

    K 0.5 0.5

    Globe valve fT L/D 0.015 x 340 5.1

    Strainer Cv 450 5.95

    Total K for pipeline 11.55

    Table 1. Calculation of K value for different methods describing valves and fi ttings (Graphics courtesy of the author)

    Valve / Fitting Type K value

    Head Loss (ft)

    Annual Operating Cost ($)

    Elbow short radius 0.33 0.5 $53

    Elbow long radius 0.23 0.35 $37

    Entrance inward 0.78 1.23 $128

    Entrance sharp edge 0.50 0.79 $82

    Entrance rounded 0.04 0.06 $7

    Ball 0.05 0.08 $8

    Gate 0.13 0.20 $21

    Plug 0.29 0.45 $47

    Butterfl y 0.73 1.14 $118

    Globe 5.54 8.58 $893

    Table 2. The relationship between K values, head loss and annual operating cost for valves and fi ttings. The example is for 4-inch valves and fi ttings passing 400 gpm.

    19

    pumpsandsystems.com | June 2015

    AROzone.com/ACHEMA

    Automate Your ProcessesWith the ARO Controller and

    EXP Series Electronic Interface Pump

    Watch it!

    Learn about it!

    Experience it!

    Visit us at booth #E18 Hall 9 for a demonstration

    E i it!

    Cir

    cle

    12

    5 o

    n c

    ard

    or

    vis

    it p

    sfre

    ein

    fo.c

    om

    .

  • OC = .746 Q H 247,000 M

    OH x $/kWh

    Equation 10 WhereOC = Operating cost ($/time)Q = Flow rate (gpm)

    H = Head (feet of fl uid) = Density (lb/ft3) = Effi ciency, M motor, P pump,

    V variable speed drive (VSD) (percent)

    O = Operating hours in evaluation (hours)

    $/kWh = Electrical power cost ($/kWh)

    In this example, the pump effi ciency is 70 percent, and the motor effi ciency is 90 percent. No VSD is installed, the evaluation period is 8,000 hours, and the cost of power is $0.10/kilowatt-hour (kWh). is example evaluates 4-inch valves and fi ttings with a fl ow rate of 400 gpm. e results are presented in Table 2 (page 19).

    Every item placed in a piping system has an operating cost. is should be considered every time a user specifi es a valve time or adds elbows.

    Conclusion e often overlooked performance of the multitude of valves and fi ttings adds up. ey have a compounded eff ect on performance in a fl uid operation and need to be taken into consideration for effi ciency planning and optimization.

    Next months column will investigate how the control elements operate and the role that these devices play in piping systems and their associated cost.

    References1. Flow of uids through valves, ttings, and pipe.

    (1957). Chicago: Crane2. Flow of Fluids through Valves, Fittings and

    Pipe Technical Paper 410. 2013 Crane Co. Stamford CT 06902.

    Ray Hardee is a principal founder of Engineered Software, creators of PIPE-FLO and PUMP-FLO software. At Engineered Software, he helped develop two training courses and teaches these courses in the U.S. and internationally. He is a member of the ASME ES-2 Energy Assessment for Pumping Systems standards committee and the ISO Technical Committee 115/Working Group 07 Pumping System Energy Assessment. Hardee was a contributing member of the HI/Europump Pump Life Cycle Cost and HI/PSM Optimizing Piping System publications. He may be reached at [email protected].

    20 PUMP SYSTEM IMPROVEMENT

    June 2015 | Pumps & Systems pumpsandsystems.com | June 2015

    the #1 value in automation2UGHU7RGD\6KLSV7RGD\

    * See our Web site for details and restrictions. Copyright 2014 AutomationDirect, Cumming, GA USA. All rights reserved.

    Research, price, and buy at: www.automationdirect.com/ eldIO

    eXactly where you need it! 7KHH;DFW,2\RXQHHG

    $63.00(PX-248: 8-point DC

    Output)

    $36.00(PX-172-1: 2-point

    AC Input)

    $24.00(PX-970: AC Power

    Feed Terminal)

    $277.00(PX-334-K:

    Thermocouple)

    $384.00(PX-TCP2: 2-port

    Modbus TCP Coupler)

    5DFNOHVVGHVLJQIRUHDV\LQVWDOODWLRQLQDUHDVZLWKOLPLWHGVSDFH

    v %XV&RXSOHUVDYDLODEOHLQERWK0RGEXV578$6&,,DQG

    0RGEXV7&3SURWRFROVWRLQWHJUDWHZLWKDZLGHYDULHW\

    RIFRQWUROOHUVDQG6&$'$+0,SDFNDJHV

    v 'LVFUHWHWHUPLQDOVDYDLODEOHLQ$&DQG'&ZLWKDYDULHW\

    RISRLQWFRQoJXUDWLRQVLQFOXGLQJRUSRLQWV

    v DQGFKDQQHODQDORJWHUPLQDOVZLWKP$

    9'&DQG9'&FDSDELOLWLHVDVZHOODV57'

    DQG7KHUPRFRXSOHRSWLRQV

    v )XOO\H[SDQGDEOHXSWR,2WHUPLQDOV

    v )5((GRZQORDGDEOHHDV\WRXVHFRQoJXUDWLRQ

    VRIWZDUHWRRO

    v $YDULHW\RISRZHUVXSSO\DQGSRZHUGLVWULEXWLRQ

    RSWLRQVJLYH\RXDGGHGYHUVDWLOLW\

    Xpansion I/O has never been so practicalBuilt to be versatile in the eld, the new Protos X Field I/O system has a slim design with numerous I/O point con gurations. The small footprint lets you install Protos X I/O assemblies exactly where you need them, even in tight locations. No need for excess eld wiring, no need for unused I/O points and with the already low price, youll save money again and again with Protos X.

    TM

    Distributing I/O for your process saves space, wiring and

    money!

    1970 Dodge Super Bee

    Creating Value.Carver Pump Company2415 Park AvenueMuscatine, IA 52761563.263.3410Fax: 563.262.0510www.carverpump.com

    Do you have flows up to9,900 GPM (2,000 m3/hr), heads up to 720 Ft (220 M), speeds up to 3,500 RPM, and temperatures up to 500F (260C)? Then you need Carver Pump Process Maxum Series muscle!With an extended range of hydraulic coverage andrugged construction, the Process Maxum Series isideal for Industrial Process applications.Manufactured in 35 sizes, standard materialsinclude WCB, WCB/316SS, 316SS and CD4MCu,with others available upon request. A variety ofoptions include various types of mechanical sealsand bearing lubrication/cooling arrangements,auxiliary protection devices and certifiedperformance testing. Whatever your requirements, let us build the muscle you need!

    Process Maxum

    Circle 123 on card or visit psfreeinfo.com.

  • 21

    pumpsandsystems.com | June 2015

    the #1 value in automation

    Qtfgt"Vqfc{."Ujkru"Vqfc{#* See our Web site for details and restrictions. Copyright 2014 AutomationDirect, Cumming, GA USA. All rights reserved. 3/:22/855/2627

    Research, price, and buy at: www.automationdirect.com/ eldIO

    eXactly where you need it! Vjg"gZcev"K1Q"{qw"pggf

    $63.00(PX-248: 8-point DC

    Output)

    $36.00(PX-172-1: 2-point

    AC Input)

    $24.00(PX-970: AC Power

    Feed Terminal)

    $277.00(PX-334-K:

    Thermocouple)

    $384.00(PX-TCP2: 2-port

    Modbus TCP Coupler)

    Tcemnguu"fgukip"hqt"gcu{"kpuvcnncvkqp"kp"ctgcu"ykvj"nkokvgf"urceg

    " "Dwu"Eqwrngtu"cxckncdng"kp"dqvj"Oqfdwu"TVW1CUEKK"cpf"Oqfdwu"VER"rtqvqeqnu"vq"kpvgitcvg"ykvj"c"ykfg"xctkgv{"qh"eqpvtqnngtu"cpf"UECFC1JOK"rcemcigu

    " "Fkuetgvg"vgtokpcnu"cxckncdng"kp"CE"cpf"FE"ykvj"c"xctkgv{"qh"rqkpv"eqp"iwtcvkqpu"kpenwfkpi

  • COMMON PUMPING MISTAKES

    Most pump bearings fail

    long before their design

    life span. e American

    Petroleum Institute (API) typically

    requires a minimum bearing life

    (L10) of 25,000 hours, and ANSI

    B73.1 specifi cation for horizontal

    ANSI pumps specifi es a minimum

    L10 bearing life of 17,000 hours at

    maximum load and rated speed.

    Prudent end users frequently

    request bearings with more

    than 40,000 hours L10, but most

    bearings do not reach that many

    hours of operation before failure.

    More than half of pump bearings

    fail as a result of contamination,

    excess heat or both. Preventing

    this introduction of contaminates

    is easier and less expensive than

    removing them. Some studies

    suggest removing contaminates

    can be eight to 10 times more

    expensive than prevention.

    Oil Contamination

    is premature failure rate

    is typically the result of

    contamination of the oil not a

    fault of the bearing or pump

    manufacturer. Dirt, wear particles

    and other foreign debris as well

    as improper bearing installation

    procedures can contribute to

    contamination that leads to

    reduced bearing life.

    Other forms of contamination

    include heat and air in the form

    of air entrainment and aeration.

    Increased levels of heat and air lead

    to increased oxidation rates.

    One of the most common sources

    of contamination, however, is

    water, which is often introduced

    because of improper storage and

    handling. During pump operation,

    water can leak into the bearing

    housing from external sources

    such as area wash down, spray

    from failed mechanical seals (or

    packing) or leaks from equipment

    near or above the pump. Another

    common method of water

    introduction is condensation

    through machine aspiration

    (moisture laden air is drawn in due

    to pressure diff erentials).

    For example, a pump running

    steady state at a given temperature

    above ambient for fi ve days is shut

    down on Friday at 4 p.m. As the

    What You Need to Know About Bearing Oil

    Last of Two Parts

    By Jim Elsey

    Summit Pump, Inc.

    Figure 1. Oil level on bottom ball of the bearing (Graphics courtesy of the author)

    June 2015 | Pumps & Systems

    22

  • pump cools, the ambient air is drawn into the

    bearing housing where it cools and the moisture

    condenses, releasing the entrained water into the

    housing where it mixes with the oil.

    According to sources at the SKF Bearing

    Company, 250 parts per million (PPM) water in

    the lube oil will reduce bearing life by a factor

    of four, and another source states that 0.002

    percent water in the oil will reduce the bearing

    life by 48 percent. According to other sources, the

    reduction of oil contamination levels from the

    ISO 21/18 to the ISO 14/11 will increase bearing

    life by a factor of 7.

    Because water in the oil is invisible at low

    levels, a lab should test the oil using the Karl

    Fisher method or the end user should conduct

    a simple sizzle test in which the oil is quickly

    subjected to a hot surface temperature of 250 to

    300 degrees F. A hot plate is commonly used, but

    a metal spoon or aluminum foil with a butane

    lighter can also be used. If more than 800 to

    1,000 PPM water is present in the oil, a sizzle

    sound can be heard when the oil temperature

    exceeds 212 to 220 F. If the oil sizzles, too much

    water is present in the oil. Because the sizzle

    test can have dangerous side eff ects, always

    check with plant safety procedures before

    conducting the test.

    Companies that strive for longer mean time

    between failures (MTBF), mean time between

    repairs (MTBR) and improved plant reliability

    select their oil or grease based on equipment

    requirements and properly match them with the

    oil properties. ey also store and allocate the oil

    using controlled and clean methods.

    I have seen end users store oil drums upright,

    outside and unprotected with an open bung. I

    have also seen mechanics draw oil from drums

    into used paper coff ee cups or soft-drink cans.

    When confronted, they reply, at is the way we

    have always done it, and we are not having any

    bearing or oil problems, or I washed out the

    container fi rst.

    If a pumps bearings are not lasting three to

    eight years, the plants equipment lubrication

    practices should be questioned. Check with your

    oil supplier, or consult articles, books and other

    publications that discuss these subjects. e

    October 2006 issue of Pumps & Systems magazine

    explores this topic, and I highly recommend any

    pumpsandsystems.com | June 2015

    23

    Cir

    cle

    12

    2 o

    n c

    ard

    or

    vis

    it p

    sfre

    ein

    fo.c

    om

    .

  • COMMON PUMPING MISTAKES

    books and technical papers on this

    subject by Heinz Bloch (see page

    30), Alan Budris or Rojean omas.

    Bearing Lubrication Methods

    Selection of a bearing design

    for a specifi c service will, to a

    large degree, determine how it is

    lubricated. Depending on the pump

    speed, type of service, horsepower

    (HP) range and size, diff erent types

    of bearings are available.

    A properly selected oil-lubricated

    ball or roller bearing will work

    for most applications less than

    200 HP, 400 F (fl uid temperature)

    and 3,600 revolutions per minute

    (rpm). For some smaller and lower

    temperature applications (less than

    320 F), grease-lubricated bearings

    may also work well. Larger pumps

    at higher speeds and system

    temperatures will require line,

    sleeve or plain journal bearings

    for radial support (hydrodynamic

    journal bearings) and tilted shoe

    (pad) designs for thrust bearings.

    Methods and designs that are

    acceptable for ANSI specifi cation

    pumps may not be acceptable for

    API, process, marine and power

    generation applications where HP

    can often exceed 70,000 brake

    horsepower (BHP) with speeds in

    excess of 6,000 rpm.

    Because most end users at the

    high end of the HP and speed

    spectrum are aware of oil types,

    best practice lubrication techniques

    and bearing selection, this article

    will examine the middle and

    lower range.

    Oil splash lubrication may be the

    most common method of bearing

    lubrication for horizontal pumps

    from 5 to 250 BHP. e oil is

    contained in a sump in the housing

    with the bearings. e machine is

    designed so the oil level for proper

    operation is at the middle of the

    bottom ball in the bearings.

    Oil Levels

    Oil levels higher than the middle

    of the lowest ball bearing will

    have negative consequences and

    increase oil temperature and air

    entrainment. Both of these factors

    accelerate the oils oxidation rate

    and reduce oil and bearing life.

    For splash lubrication, the oil level

    should touch the very bottom of

    the bottom ball in the bearing.

    If the oil drops below the ball or

    the outer race, the bearings could

    be damaged. If the level is too

    24

    June 2015 | Pumps & Systems

    Circle 126 on card or visit psfreeinfo.com.

    WHY MONITOR POWER INSTEAD OF JUST AMPS?

    NO LOAD NO LOAD

    Power is Linear-Equal Sensitivity

    at Both Low and High Loads

    No Sensitivity

    For Low Loads

    FULL LOAD FULL LOAD

    PO

    WER

    AM

    PS

    WWW.LOADCONTROLS.COM

    CALL NOW FOR YOUR FREE 30-DAY TRIAL 888-600-3247

    PROTECT PUMPS$2925..).'s#A6)4!4)/.s"%!2).'&!),52%s/6%2,/!$MONITOR PUMP POWER

    s"EST3ENSITIVITYs$IGITAL$ISPLAY

    TWO ADJUSTABLE SET POINTS

    s2ELAY/UTPUTSs!DJUSTABLE$ELAY4IMERS

    4-20 MILLIAMP ANALOG OUTPUT

    COMPACT EASY MOUNTING

    /NLYXXs3TARTER$OOR s0ANELs2ACEWAY s7ALL

    UNIQUE RANGE FINDER SENSOR

    s7ORKSON7IDERANGEOF-OTORSs3IMPLIlES)NSTALLATION

    PUMP POWER

    PUMPING

    VALVE CLOSING

    VALVE OPENINGNO FLUID

  • low, the bearing could experience

    temperature runaway, which is

    when the bearing gets hot quickly

    and is permanently damaged.

    Variations on splash lubrication

    design include fl ingers, discs, oil

    rings and several other methods/

    types of lubrication.

    One note of caution is that

    rings must be close to perfectly

    concentric, and the pump shaft

    must be level for the rings to work

    correctly. I have rarely seen the

    ring remain round, especially after

    the fi rst maintenance overhaul. If

    not initially leveled, the pump may

    not remain level either. Problems

    may also arise if the design ratio

    of ring to shaft diameters is not

    correct. Critical speed can also be

    an issue. While the rotor may be

    above the fi rst critical speed, the oil

    ring speed is typically at 50 percent

    of the shaft speed and may be

    rotating close to critical frequency.

    Other types of lubrication

    include grease (with ball bearing

    variations of shielded/unshielded

    and sealed), oil mist, oil purge and

    forced oil feed (oil is pumped to the

    bearings for the larger HP pumps

    and some marine applications).

    Most motor bearings are grease-

    lubricated, so it is important to

    know if they are open, shielded,

    sealed or a combination of these

    options. If they are shielded on one

    side, the best practice is to place

    the shielded side toward the grease

    fi tting. I have seen many end users

    who order pumps with greased

    bearings still add oil to the housing

    simply because the installation,

    operation and maintenance manual

    (IOM) did not specifi cally say not

    to. Running the pump with greased

    bearings and splash oil lube at the

    same time is an incorrect solution.

    Oil Changes

    e fi rst oil change should be

    conducted at a shorter interval

    than subsequent changes to

    eliminate the contamination that

    occurs from startup and run-in

    operations. Most ANSI and some

    API pump manufacturers will

    state that the fi rst change should

    come at 200 operating hours and

    subsequent changes at 2,000 hours

    or 3 months, whichever comes

    fi rst. e intervals depend on

    operating temperatures and how

    contamination ingress is managed.

    Some operations will require more

    frequent oil changes, and others

    Ludeca

    1/2 horiz

    25

    pumpsandsystems.com | June 2015

    305.591.8935 | www.KeepItRunning.com

    Vibration hurts your equipment! Reducing vibration by just 15%

    can increase bearing life in your equipment by up to 72%.

    Theres no excuse to let high vibration levels cost you!

    Increase machine reliability and minimize costly downtime

    through proactive condition monitoring solutions.

    Our equipment and support are the industry benchmark.

    Keep it Running.

    305.591

    VibVibration hurts y

    can increase be

    Theres no excu

    Increase machi

    through proacti

    Our equipment

    Keep it Runnin

    VibXpert II

    A PRFTECHNIK product Vibration Analysis, Field Balancing and more!

    Circle 127 on card or visit psfreeinfo.com.

  • COMMON PUMPING MISTAKES

    can operate for several years. Oil sample analysis

    and experience will aid in decisions regarding oil

    change intervals.

    Consider how often oil is changed in a car. If a

    car was driven at 60 miles per hour for 24 hours a

    day and 7 days a week for one year (8,760 hours in a

    year), it would drive 525,600 miles.

    You would never drive a car that many miles

    without changing the oil.

    Automatic Oilers

    Several automatic oiler types and brands are on the

    market. e question to ask is whether the oiler is

    vented to atmosphere or to the housing. Old designs

    vented to atmosphere, but that is how moisture

    gets to the bearing housing and oil. e new best

    practices are to vent the oiler to the housing and

    keep the housing sealed.

    e old method was to also vent the housing,

    but that was a source of contamination. e

    vents should be eliminated or, at the very least,

    used with a desiccant breather or an equalizer

    expansion chamber.

    Lip Seals Versus Bearing Isolators

    For more than a hundred years, lip seals have

    served the industry well. While they are simple and

    inexpensive, end users should consider replacing

    them with the more modern and effi cient bearing

    Figure 2. Cross section of bearing isolator

    Tuthill

    1/2 vert

    26

    June 2015 | Pumps & Systems

    Cir

    cle

    13

    2 o

    n c

    ard

    or

    vis

    it p

    sfre

    ein

    fo.c

    om

    .

  • 27

    pumpsandsystems.com | June 2015

    Transforming energy into solutions.

    2013 WEG Electric Corp.

    Pump GeniusPump Process Control Software

    Pump Genius is designed to reduce system operation and maintenance costs

    while increasing process accuracy and protection. The software provides

    multiple pump control and protection, as well as system monitoring and

    protection. Pump Genius can be applied to any system that requires constant

    flow or pressure.

    To learn more about Pump Genius or to locate

    a WEG Distributor near you, please contact

    1-800-ASK-4WEG or visit www.weg.net/us

    Reduce your pump system operation and maintenance cost

    Increase accuracy and protection

    Control up to 6 pumps dynamically alternated and controlled

    Cir

    cle

    11

    2 o

    n c

    ard

    or

    vis

    it p

    sfre

    ein

    fo.c

    om

    .

  • COMMON PUMPING MISTAKES

    isolators. Lip seals, regardless of the

    manufacturer, will, at best, only last

    about 3,000 hours in service. After

    approximately four months of operation,

    they will fail and potentially allow

    water or other contaminants to enter

    the bearing housing. e advent of the

    bearing isolator is what has allowed

    many pump manufacturers to extend

    their warranties from one to fi ve years.

    e modern bearing isolator will, on

    average, last eight to 10 years and, if

    properly managed, even longer. During

    that time, the isolator will not wear/

    score a groove on the shaft and, for the

    most part, will prevent the introduction

    of contamination to the bearing housing

    at both operating and static conditions.

    Bearing isolators can be of the labyrinth

    or contacting face design, and there are

    numerous designs and manufacturers.

    e majority of bearing isolators

    are orientation specifi c; they normally

    have a drain hole (expulsion port) that

    should be in the 6 oclock position. If

    the port is not at the correct position,

    the isolator will not perform properly.

    For some types of ANSI pumps, the

    outboard isolator will have numerous

    evenly spaced expulsion ports because

    the housing it fi ts into can be rotated

    when setting the impeller clearance.

    e fi nal position will not be a fi xed

    parameter as it is in other designs, so the

    isolator incorporates numerous ports to

    satisfactorily operate in any position.

    Overfi lling the Bearing Housing

    One of the most common problems

    I see in the fi eld beyond not reading

    the instructions is the overfi lling of

    the bearing housings with oil. Bearing

    isolators (labyrinth style) will purge any

    excess oil from the housing. A common

    misconception is that the isolator

    The modern bearing isolator will, on average, last eight to 10 years

    and, if properly managed, even longer.

    MissionComm

    1/2 island

    28

    June 2015 | Pumps & Systems

    Mission managed SCADA systems aredesigned to get you up and running inhours, not days. Our packages start ataround $1,000 with a maintenance fee ofless than $1 a day. Mission strives forease in doing business. Give us a try nobureaucratic red tape, no huge commit-ment. If you like it, buy it. If not, send itback. Its that simple.

    Mission flexibility allows you to expandyour system as you are ready and on yourterms. Mix and match any of our productsone at a time or all at once, the choice isyours. That is why you will find MissionSCADA in over 1,400 municipalitiesacross the United States and Canada.

    Lift Station Tank and Well ControlIn Sewer Level Alarm

    Advanced Monitoring Low Cost Managed SCADA

    (877) 993-1911 www.123mc.com

    Mission SCADA Works Right Out Of The Box, But Wont Box You InMission SCADA Works Right Out Of The Box, But Wont Box You In

    Circle 128 on card or visit psfreeinfo.com.

  • DSI full page

    29

    pumpsandsystems.com | June 2015

    Cir

    cle

    10

    6 o

    n c

    ard

    or

    vis

    it p

    sfre

    ein

    fo.c

    om

    .

  • COMMON PUMPING MISTAKES

    has failed, but it is just doing its

    job. e oil will continue to be

    expelled until the level is below the

    expulsion port.

    Setting the automatic oiler

    level incorrectly is the next most

    common mistake in the industry.

    Please refer to the manufacturers

    instructions for the proper

    procedure. Hint: e level in the

    oil bulb is not the level of the oil

    in the pump housing nor is it the

    centerline of the connecting pipe.

    Conclusion

    Centrifugal pumps are shipped

    without oil in the bearing housings;

    consequently, the end user must

    ensure that oil is in the housing

    before startup. e oil must be

    of the proper viscosity. e oil

    viscosity selection is based on

    expected temperatures of the oil

    and bearings. e oil supply source

    should be clean, and the oil must

    remain uncontaminated between

    changes. In addition, the oil must

    be at the proper level in the bearing

    housing. Too much oil is just as

    bad, if not worse, than too little oil.

    Most bearings fail because of

    contamination from water and/or

    heat. Labyrinth or magnetic face

    type seals (bearing isolators) can

    help prevent water introduction

    and contamination. Desiccant

    breathers or automatic oilers that

    vent to the housing in lieu of the

    atmosphere can also reduce the

    introduction of water.

    Worldwide Electric

    1/2 horiz

    Jim Elsey is a mechanical engineer who has focused on rotating

    equipment design and applications for the military and several large

    original equipment manufacturers for 43 years in most industrial

    markets around the world. Elsey is an active member of the American

    Society of Mechanical Engineers, the National Association of Corrosion

    Engineers and the American Society for Metals. He is the general

    manager for Summit Pump, Inc., and the principle of MaDDog Pump

    Consultants LLC. Elsey may be reached at [email protected].

    Read more online

    pumpsandsystems.com/

    commonpumpingmistakes.

    30

    June 2015 | Pumps & Systems

    Circle 131 on card or visit psfreeinfo.com.

  • SPX

    31

    pumpsandsystems.com | June 2015Circle 119 on card or visit psfreeinfo.com.

  • Some will know from their

    experience with automobiles

    that thicker oils, such as

    Society of Automotive Engineers

    (SAE) 30, are more appropriate

    for warm summer months. But

    thinner oils, perhaps SAE 10, can

    help prepare a vehicle for winter

    driving. Figure 1 illustrates where

    these motor oils fi t in comparison

    to the industrial oil designations

    used today.

    ick oils are more viscous

    and may not readily fl ow into the

    bearings. Users can heat the oil

    or avoid oil rings and other risk-

    inducing lube application methods

    by using smarter means. ey can

    use a jet of oil (oil spray) or convey

    the oil mixed with compressed

    air in the form of an oil fogalso

    called oil mist. Whatever the user

    chooses, he or she must guard

    against using the thinnest oil

    found on the market to avoid the

    problem of inadequate oil fi lm

    strength and thickness.

    Lube Oils for Process Pumps

    e MRC Engineers Handbook

    states, In general, the oil

    viscosity should be about 100

    Saybolt Universal Seconds (SUS)

    at the operating temperature.1

    If for some reason a bearing was

    operating at 210 degrees F, Figure

    1 would call for a lubricant with

    an International Organization

    for Standardization (ISO)

    viscosity grade (VG) somewhere

    between 220 and 320. But that

    is unrealistically thick for most

    process pump bearings. Oil rings,

    if used, would probably slow down

    and malfunction in such viscous

    oils. Oil overheating may be an

    additional concern.

    Figure 2 shows a graph from

    SKF that is time-tested and widely

    applicable.3, 4 It depicts the required

    minimum (rated) viscosity v1 as

    a function of bearing dimension

    and shaft speed.3 A bearing with a

    mean diameter of 390 millimeters

    (mm) at a shaft speed of 500

    revolutions per minute (rpm) would

    require v1 = 13.2 centistokes (cSt).

    For another example, if a bearing

    was mounted on a 70-mm shaft

    rotating at 3,600 rpm, we might

    assume that the bearings outside

    diameter (OD) is twice its inner

    diameter (ID), or 140 mm. e

    How Oil Viscosity & Temperature Infl uence Bearing Function

    First of Two Parts

    By Heinz P. Bloch, P.E.

    Figure 1. Oil viscosity comparison chart per common industry conversion practice (Courtesy of the author)

    By Heinz P. Bloch, P.E.

    32 GUEST COLUMN

    June 2015 | Pumps & Systems

  • bearings mean diameter would be 105 mm. To

    simplify, consider it 100 mm, and travel up from

    100 to a location midway between the 3,000

    and 5,000 rpm lines in Figure 2. In this instance,

    one could operate with a lubricant which, at the

    bearing operating temperature, is somewhere

    between 8 and 9 cSt.

    Note that a bearings operating temperature

    must be known to determine what ISO VG is

    needed. e operating temperature derives its

    combined thermal input from bearing load and

    lube oil frictional drag. Unnecessarily viscous oils

    will become hot. Figure 3 (page 32) is helpful in

    this regard. Note that Figures 2 and 3 were drawn

    years ago and apply to mineral oils. If users choose

    premium grade synthetic oils, they will enjoy a

    sizeable safety factor in lube applications.

    Using lubricants with viscosities in excess of

    those needed may generate excess heat and actually

    work against operators. However, thicker oils have

    their place, and MRC had to cover all the bases with

    their 100 SUS rule-of-thumb.

    Figure 2. Required minimum (rated) viscosity v1 as a function of bearing

    dimension and shaft speed.3 A bearing with a mean diameter of 390 mm at a shaft speed of 500 r/min will require v

    1 = 13.2 cSt. (Courtesy of SKF)

    33

    pumpsandsystems.com | June 2015

    Dont Leave

    In TheProfits

    Pipeline

    PSGZI la Plaine de Isles, 2 rue des Caillottes

    F-89000 Auxerre, FranceTel: +33 (0) 3 86 49 86 [email protected]

    psgdover.com/en/product-recovery

    PSG Euro-Center 22069 Van Buren Street

    Grand Terrace, CA 92313 USA Tel: +1 (909) 512-1224

    [email protected]

    Di d you know:

    Manufacturers can save money by reducing energy costs, but product-recovery savings can be 110 times higher!

    Food and Beverage, Pharmaceutical, Chemical and Cosmetic/Personal Care product manufacturers leave expensive fluids (and thousands of dollars) in their piping every day.

    Eliminate these lost profits and recover up to 80% of your ingredients with Mouvex SLS Series Eccentric Disc Pumps.

    Compression effect clears lines

    Gentle handling, consistent flow

    Leak-free seal-less design

    Dry priming and strong negative suction lift

    Scan this to learn more about

    the Product Recovery benefits

    of Mouvex pumps, or go to

    www.youtube.com/MouvexGlobal.

    For more information, please go to: psgpumps.com/ps615m

    Circle 129 on card or visit psfreeinfo.com.

  • at said, a large bearing (200

    decimeters) in a slow speed gearbox

    (200 rpm) requires an operating v1

    of 40 cSt. Figure 3 shows that ISO

    VG 100 (or higher) oils would be

    needed here.

    Real-World Example

    In a recent case history, ISO VG

    100 was applied to a large pump

    where ISO VG 68 mineral oil or its

    equivalent ISO VG 32 would have

    suffi ced. An ISO VG 32 synthetic

    is the bearing life equivalent

    of an ISO VG 68 mineral oil.

    e synthetic ISO VG 32 runs

    considerably cooler than the

    mineral oil equivalent.

    With ISO VG 100 mineral oil, the

    oil-misted radial bearing ran a few

    degrees in temperature lower than

    it had with conventional sump and

    oil ring lube. e user was pleased

    but expressed disappointment at a

    triple-row thrust bearing running

    as hot as before190 F.

    A premium formulation

    synthetic ISO VG 32 would have

    been suffi cient and would have

    given the user everything a solid

    reliability professional could have

    asked for.

    Reliability professionals would

    like to see pump bearing housings

    with no oil rings, no need for

    constant level lubricators and

    few, if any, repeat failures. ey

    start with the right lubricant.

    Why, with all that, is the radial

    bearing cool? After all, it is also

    surrounded by the thick ISO VG

    100. It is cool because it has no

    load. e load is in the triple-row

    thrust bearing, and that creates

    temperature in addition to the

    frictional temperature mentioned

    earlier in this article.

    Part 2 of this series will examine

    which temperatures are reasonable,

    which are high and which are out of

    allowable range for rolling element

    bearing housings and pump

    bearing housings.

    References

    1. MRC Engineers Handbook, General

    Catalog 60, Copyright TRW, 1982

    2. Bloch, H.P.; Improving Machinery

    Reliability, Gulf Publishing Company,

    Houston, TX, 1983, 1993

    3. SKF America, General Catalog,

    Kulpsville, PA (2000)

    4. Bloch, H.P. Pump Wisdom: Problem

    Solving for Operators and Specialists,

    John Wiley and Sons, Hoboken, NJ, 2011

    Heinz P. Bloch has been a

    professional engineer for almost

    50 years. He holds a BSME and an

    MSME degree (cum laude) from

    New Jersey Institute of Technology

    and retired as Exxon Chemical

    Companys regional machinery

    specialist. He may be reached at

    [email protected].

    Figure 3. For a required viscosity (vertical scale), the permissible bearing operating temperatures (horizontal scale) increase as thicker oils are chosen (diagonal lines). Users enter the vertical scale near 9 cSt and move toward the right, where the line intersects with oils ranging from ISO VG 22 through ISO VG 320. If the user selects ISO VG 32, he or she might start the pump and verify that its oil temperature had leveled off at no greater than 75 C. Alternatively, the user might choose ISO VG 68 and verify that its operating temperature does not exceed 100 C (212 F). The information in this fi gure is per common rule of thumb, using average viscosity improvers. (Courtesy of the author)

    Reliability professionals would like to see pump bearing

    housings with no oil rings, no need for constant level lubricators and

    few, if any, repeat failures. They start with the right lubricant.

    34 GUEST COLUMN