Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

download Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

of 10

Transcript of Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

  • 7/21/2019 Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

    1/10

    696

    IEEE

    Transactionson Power Delivery

    Vol.

    6 No. 2, April 1991

    ELECTRICAL PERFORMANCE OF POLYMER HOUSED ZINC OXIDE

    ARRESTERS UNDER CONTAMINATED CONDITIONS

    V. Chaudhry and R. S Gorur

    Dept. of Electrical and Computer Engr.

    Arizona State University

    Tempe, AZ

    85287-5706

    ABSTRACT

    The electrical performance of polymer housed zinc oxide

    distribution arresters has been investigated in a fog

    chamber. Two types of housing materials, namely,

    copolymers of ethylene and propylene (commonly known

    as EPM rubber) and terpolymers

    of

    ethylene propylene and

    diene (commonly known as EPDM rubber), both containing

    alumina trihydrate (ATH) filler, have been examined. It has

    been demonstrated that under relatively low (250 pS/cm)

    and moderate

    (1000

    to 2000 pS/cm) fog conductivity,

    degradation in the form of tracking and erosion of the

    housing occurs. On some housings, degradation is

    dominant in the region of the mold line and is due to non-

    uniformity in filler dispersion. The electric field has been

    computed and a few electrode modifications to improve the

    surface electric field distribution are suggested.

    K e y words: polymer housing, EPM, EPDM, dry band

    arcing, tracking and erosion.

    1. INTRODUCTION

    Polymers have been in use for high voltage insulation

    applications, such as, line insulators and cable terminators,

    for the last

    20

    years. Their use as zinc oxide arrester

    housing for outdoor electr ical systems is very recent [l] The

    advantages of choosing polymer insteadof porcelain as the

    housing material for arresters are, light weight, shorter

    length of arrester possible due to the use of an insulated

    mounting bracket, reduced risk of shattering and explosion

    of the housing during arrester failure, improved resistance

    to moisture ingress due to the close fitting provided by the

    polymer, etc. [l] Presently, polymer housed arresters are

    available up to

    36

    kV rating, and there are plans to make

    them for higher voltages. Currently available arresters use

    either an EPM or an EPDM polymer, and it is expected that

    silicone rubber housed arresters will be available shortly

    PI.

    Considerable amount of service experience and laboratory

    tests have demonstrated that there are two types of

    polymers, namely silicone rubber and ethylene propylene

    rubber (EPR, which is the generic name for EPM and EPDM

    polymers), that are well suited for outdoor applications.

    Potential problems such as resistance of the material o UV,

    chemicals, moisture, etc have been overcome [3]. major

    concern which still remains in the use of these materials is

    M.

    Dyer and R. S hallam

    Salt River Project

    Phoenix

    Arizona,

    85072-2025

    their behavior under combined high electric stress, moisture

    and outdoor contamination. Corona and dry band arcing

    are promoted under such conditions

    [4].

    Unlike with

    porcelain, corona on polymers can cause degradation in

    the form of radial cracks, and pin holes, and dry band arcing

    can cause degradation in the form of tracking and erosion

    [3]

    racking is defined as the formation of a conducting

    layer of carbon deposit formed on the surface due

    to

    polymer degradation. Erosion is defined as the loss of

    material with time.

    Tracking and erosion can be minimized with the addition of

    inorganic filler, such as alumina trihydrate (ATH). Although

    the present materials use sufficient ATH filler (>50% by

    weight), tracking and erosion can still occur due

    to

    non-

    uniformity in the filler dispersion[5]. his can happen during

    mixing and molding operations. It would be important to

    establish limits on the filler dispersion such that premature

    housing degradation is prevented.

    Zinc oxide arresters for higher voltage ratings are made by

    stacking multiple low voltage sections

    [l]

    For a constant

    diameter, the electric field near the high voltage electrode

    will increase with the applied voltage, thereby increasing

    the risk for corona at operating voltage. It would be valuable

    to determine the highest voltage class that polymer housed

    arresters could be used without problems from corona.

    In polymer housed arresters, the housing fits more snugly

    and tightly to the zinc oxide column than is obtained with

    porcelain, hence providing the greater resistance to

    moisture ingress [l] However, this also increases the

    capacitance between the housing and the arrester column.

    Consequently, there is a concern by the users that under

    contaminated conditions the internal arrester current may

    be affected by the external leakage current

    [6].

    his could

    result in heating of the zinc oxide blocks and eventual

    failure of the arrester.

    If

    this is true, an evaluation of the

    effect of contamination on the internal current should be

    performed.

    Another problem with the use of polymers is the lack of a

    meaningful laboratory test to predict the performance in

    service. Dry band arcing is largely controlled by the surface

    electric stress, which varies for different devices. Although

    there is data available for polymer outdoor insulators

    [7]

    and cable terminators

    [a],

    his may not be applicable for

    polymer housed surge arresters. Therefore, it is essential to

    have sufficient laboratory data on polymer housed arresters

    such that a meaningful accelerated test can be developed

    for these devices as well.

    5 0 S 295-6 P? i.iRU

    A

    paper recorninended and approved 2. EXPERIMENTAL

    3 y t h e

    I G r :

    Surge Protective Devices Committee

    of

    t h e I % P o ue r E n g in e e r in g S o c i e t y f o r ; > r e s e n t a t i o n Fig. 1shows the schematic of the fog chamber used in the

    a t t h e I X E / E ; S

    1990

    Sumer vieeting, Kinneapolis ,

    present study. The chamber is made from stainless steel

    A.llnnesota, Ju t : 15-19, 1950. ?.:,muscr ipt subm itte d sheets and is 3.6mX3.05mX2.5m high. Four nozzles

    August

    2 2

    1987; made available f o r p r i n t i n g constructed according to IEC specification

    [9],

    nd located

    ;lay 15, 1990.

    one on each wall of the chamber, are used for fog

    generation. Distilled water, to which sodium chloride is

    added, is recycled from a 100

    I

    capacity reservoir. A fresh

    .- .

    0885-8977/9

    /O4OO-0696 0

    1 ooO 991

    IEEE

  • 7/21/2019 Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

    2/10

    697

    Sample

    ID

    A

    R EGU lMTOR

    a GAUGE

    Description Housing Leakage ATH

    Material Distance

    Level

    Complete EPDM

    395 mm ~ 5 0 %

    RE1URN

    PUMP

    Fig.

    1 :

    Schematic Diagram of Fog Chamber

    saline solution is prepared daily in order to limit the

    increase in the water conductivity to less than 10 of the

    initial value.

    I Arrester

    The high voltage is supplied from a 15 kVA, 50kVl120V

    transformer bank, located inside the chamber. The output

    voltage is controlled by a 0-120 V,

    50

    A variac, located

    outside the chamber. The maximum fluctuation in the

    voltage was less than

    5 .

    Table 1shows the details of the samples evaluated. Some

    of the samples, used were complete arresters with zinc

    oxide disks and some were polymer housing only. Easy

    availability of the housings was the reason for evaluating

    the housings only (Sample

    B).

    Both samples

    A

    and B had

    six skirts on the housing, and the shape of the skirts were

    similar. The central cavity diameter was 42mm for both

    samples.The complete arresters were tested along with the

    insulated mounting bracket. They were fixed to a wooden

    post and placed in the center of the chamber. The housings

    were attached to stainless steel electrodes and suspended

    from a plexiglass ring fixed to the roof of the chamber. The

    electrodes for the housing were carefully machined and

    Table 1 Details of Samples Evaluated

    I

    I

    B

    I Housing Only1 EPM

    I

    395 mm I >50

    inserted in the central cavity using silicone grease in order

    to prevent water from entering the cavity. The outside

    diameter of the electrodes were such that they were flush

    with the housing shank, as was the case with arrester

    sample A. At least three samples of each type A and B were

    evaluated and the dispersion in the reported data was

    within 10 .

    The complete arrester was evaluated in the normal mode,

    i.

    e., the top electrode being the high voltage and the bottom

    electrode, the ground. The housings were energized with

    the bottom electrode being the high voltage and the top

    electrode grounded. This change does not affect the

    tracking and erosion performance of the housing, as dry

    band arcing is dependent on the direction of the water flow

    on the surface. The samples were subjected continuously to

    electric stress and fog for 22 hours every day. The test was

    stopped for

    2

    hours in order to facilitate fresh saline solution

    preparation and visual examination of the samples.

    connected to

    channel measuri heavily greased

    Ground electrode

    connected to channel

    measuring internal

    arrester current

    Fig. 2: Schematic Diagram for Current Measurement

    The analog voltage signal which is proportional to the

    leakage current, is measured across

    a

    low value

    (100

    n)

    precision resistor connected in series with the sample on

    the grounded end. This signal is fed to a

    16

    channel,

    12

    bit

    A/D converter (Metra Byte DAS 16-G2), located in an IBM

    compatible computer. The computer is programmed to give

    the following information on an hourly basis: Peak and

    average value of current in the positive and negative parts

    of the ac wave, integral of the average current, which is the

    cumulative charge, and number of peak current pulses

    exceeding several preset current limits. Further details of

    the data acquisition system (DAS) can be found in an

    earlier paper

    [I

    01.

    The internal current of the complete arrester was also

    monitored continuously using the arrangement shown in

    Fig. 2. A metal band was inserted above the bottom skirt

    and connected to one

    of

    the channels of the

    DAS. The

    material between the metal band and the bottom electrode

    was heavily greased. In this manner, the channel

    connected to the ground electrode measured the internal

    current, where as, the channel connected to the metal band

    measured the external leakage current.

    3. RESULTS

    AND DISCUSSION

    The arresters and housings evaluated were rated for 9 kV.

    The samples were subjected to their maximum continuous

    operating voltage (MCOV), which is 7.65 kV for the 9 kV

    rated

    ANSI)

    class arresters. The severity of the test was

    varied by changing the water conductivity. The test was

    terminated at 500 hours, unless the samples failed earlier.

    This time of test has been found to be adequate in order to

    distinguish between different materials and designs of

    polymer insulating devices [I 1,121. The results reported are

    from evaluating at least two samples of the same type.

    Table 2 shows the results obtained at various water

    conductivities. The conductivity values were chosen such

    that it was representative of a wide range of contamination

    severity in service [13], and also encompassed the

    conductivity used in other accelerated tracking and erosion

    tests [14]. For example, conductivity of rain is less than

    50

    pS/cm, normal tap water is in the range of 200-400 pS/cm;

    conductivity used in the tracking wheel test i s 1600 @/Cm

  • 7/21/2019 Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

    3/10

    698

    [I 51, earlier fog chamber ests have used water in the range

    of 1000 to 4000 pS/cm [11,12], the German VDE test for

    polymer cable accessories uses water in the range of

    16000 pS/cm [16]. The following points can be noted from

    Table 2

    1) No degradation was not iced when the water conductivity

    is below 100 pS/cm and at higher values of 16000 pS/cm

    and higher.

    (2) Degradation in the form of tracking and erosion has

    been noticed on the sample

    B

    at a relatively low water

    conductivity of

    250

    pS/cm.

    (3)

    Degradation in the form of tracking and slight erosion

    has been noticed on both samples A and B at water

    conductivities

    of 1000

    and 2000 kS/cm.

    The degradation on both samples A and

    B

    was init iated at

    the bottom electrode, as can be observed from Figs. and

    4. This is believed

    o

    be due to the relative orientation of the

    samples with respect

    to

    the fog nozzles. In the present set-

    up, the water film runs down the surface causing dry band

    arcing across the tip of the water channel and the bottom

    electrode. Thus the difference in the location of the HV and

    ground electrodes on the complete arresters and the

    housings does

    not

    produce any difference i n the

    degradation pattern.

    Table

    2:

    Fog Chamber Test Observations at Various Water

    Conductivities.

    Note: T and

    E:

    Tracking and Erosion

    ~~

    ;ervation on

    Sample B

    T and E

    Fig. 3: Typical Degradation of sample A .

    Fig. 4: Typical Degradation of sample B.

    3.1

    FILLER DISPERSION

    The degradation on a few samples B was dominantly in the

    region of the mold line as shown in Fig.

    5,

    and was noticed

    in the first

    100

    hours of salt-fog exposure with fog

    conductivities of 250, 1000 and

    2000

    pS/cm. Such

    preferential premature degradation was first observed and

    explained in an earlier study with molded cylindrical rods

    [5]. he degradation was attr ibuted

    o

    non-uniformity of filler

    dispersion

    in the region of the mold line. In order to

    determine whether this could be the case with samples B,

    small sections were cut around the mold line of the

    degraded samples and examined under

    a

    scanning

    electron microscope (Model JEOL JXA-840 SEM) using an

    Energy Dispersive X-Ray Analysis (EDX) technique [I 71

    Fig. 6 shows the typical variation of the filler dispersion ratio

    at various locations (numbered

    I

    through 10 on the x-axis)

    on small sections (about

    1

    OmmXl OmmX2mm thick)

    removed from sample B . The filler dispersion was examined

    after the fog chamber test. The various locations represent

    different points on the small sections. The filler dispersion

    ratio is the ratio of the X-Ray count obtained at the location

    to

    the maximum X-Ray count obtained on the specimen.

    The X-Ray count is an indication of the amount of the ATH

    filler present in that location [5]. t is clear that there is a

    large filler dispersion on specimens removed from the mold

    line of sample B. t is important to note that such highly non-

    uniform filler dispersions have occurred even though the

    average filler concentration is relatively high (>50 by

    weight of the polymer). On specimens removed from other

    parts of sample

    B,

    the filler is dispersed more or less evenly,

    indicating adequate mixing of the compound.

    These results indicate that molding is responsible for the

    non-uniform filler dispersion. This is possible as the

    polymer is more mobile than the filler particles, and under

    the mold pressure, the more mobile polymer is pushed

    outward, leaving the filler behind.

    It

    would be important

    to

    determine

    if

    the filler dispersion along the mold line could

    perhaps be improved by the addition of suitable: additives

    which would make the polymer and filler mobile to the same

    degree.

    This study also suggests that a filler dispersion ratio of 0.8

    or higher could prevent preferential degradation. It is

    to

    be

    noted that degradation has occurred on housings with a

    more uniform filler dispersion, as shown in Figs. 3 and 4

    but this is due

    to

    the repeated dry band arcing caused by

    the water film flow pattern.

  • 7/21/2019 Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

    4/10

    699

    5

    d

    [r

    ._

    m

    a

    a

    .-

    ._

    80-1

    00

    80-100 0.4 NA

    90-1

    00

    90-1

    00 0.4

    NA

    1 o

    0.4

    Fig. 5: Degradation in the Mold Region on

    SampleB

    Mold Region I

    lse

    where

    0 .21

    1 , , , .

    , .

    I

    0

    2

    4

    6 8

    1 0

    Location

    Fig. 6. Filler Dispersion on sample

    B.

    3.2 LEAKAGE CURRENT AND INTERNAL

    CURRENT

    Table

    3

    shows the typical leakage current observed during

    the test at different water conductivities. The outer surface of

    all the samples was hydrophobic initially and the leakage

    current was less than

    3

    mA (peak). However, in less than

    20

    hours of exposure

    to

    dry band arcing in the fog chamber the

    surfaces became hydrophillic or wettable, and the leakage

    current increased

    to

    the values shown in Table 3. The

    following points can be noted from the Table:

    (1) Degradation occurs in the fog chamber tests only when

    the peak leakage current i s in the range of 10-20 mA.

    No

    degradation occurs when the leakage current is very small

    ( 4 0 mA) or very high (>80 mA).

    (2) The internal current is not affected by the leakage

    current. This suggests that external contamination for the

    low voltage arresters tested here has not altered the

    internal voltage distribution significantly. However, this may

    not be true for higher voltage rated arresters.

    The cumulative charge,which is indicative of the duration

    and frequency

    of

    leakage current pulses,was observed to

    be about 15% lower in Tests 5 and

    6

    when compared

    to

    Tests 3 and 4 . This was despite the fact that in Tests 5 and

    6,

    a higher magnitude of peak leakage current was

    recorded due to the higher water conductivity. This

    Table

    3:

    Typical Peak Leakage Current and Internal

    Current at Various Water Conductivities.

    Note: NA. Not Applicable.

    suggests that leakage current pulses in Tests 5 and

    6

    occur

    in a very random manner. Similar observations have been

    made in earlier studies with polymer insulators [18] and

    cable terminations [19].

    Degradation does not occur at very low values of current

    because the arc energy is insufficient

    to

    break the bonds

    in

    the polymer. With very high values of leakage current, the

    duration of the current pulses is very small and they occur at

    random, resulting in an arc energy which is again

    insufficient to break the bonds in the polymer. It is only with

    intermediate values of current (10

    to

    20 mA) that the pulse

    duration and frequency is sufficient for the arc energy to

    cause material degradation. This factor has

    to

    considered

    when analyzing the results from various accelerated

    laboratory tests.

    3.3

    RESISTANCE

    TO

    MOISTURE INGRESS

    A recent publication [20] indicated that zinc oxide arresters

    are not affected by moisture ingress because the zinc oxide

    material is dense and hence impervious to moisture. Even

    so,

    other materials inside the arrestor can be affected by

    moisture. For example, In the samples A evaluated, the zinc

    oxide blocks were wrapped in a fiber glass jacket. Fiber

    glass carbonizes under the combined presence of moisture

    and electric stress. Therefore, it is very important that the

    housing prevent moisture ingress into the zinc oxide

    column. A method of detecting moisture ingress

    is

    the Dissipation Factor or tan 3 measurement. A Phillips

    Model PM 6303 meter was used for measuring the

  • 7/21/2019 Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

    5/10

    700

    dissipation factor on the complete arresters. The tan a

    (measured at

    1

    kHz) recorded was between 0.04 to

    0.05

    on

    all the arresters evaluated before and after the 500 hour salt

    fog tests. This indicates that there was no ingress of

    moisture into the zinc oxide column.

    4. COMPARISON WITH OTHER TEST RESULTS

    At this time very little data on the tracking and erosion

    performance of polymer housed surge arresters is

    available. In a previous paper [I] it has been reported that

    EPM housed surge arresters showed no degradation even

    after several thousands hours of evaluat ion by the Tracking

    Wheel and Fog Chamber methods, which use water

    conductivity n the range of

    1000

    to

    2000

    pS/cm. However,

    the present fog chamber work illustrates hat degradationof

    the housing occurs with these values of water conductivity.

    This contradiction suggests that more work is required

    before a laboratory procedure can be recommended to

    evaluate the tracking and erosion performance of polymer

    housed arresters.

    The IEC contamination test [9] on porcelain housed zinc

    oxide arresters is usually performed using a salinity of 10

    kg/m3 or higher. This translates to a water conductivity of

    16,000 pS/cm and higher [9]. The IEEE/ANSI Contamination

    tests are performed with water conductivity in the range of

    2000-2500

    S/cm (400 to

    500

    ohm.cm)

    [21].

    he present

    study clearly demonstrates that lower values of water

    conductivity cause more degradation of the polymer

    housing than the higher values recommended in the

    standard tests. Therefore, the evaluation of the

    contamination performance of polymer housed arresters

    should consist of two parts. The first part, performed

    according to the above standards, will give information on

    the effect of contamination on the overall arrester

    contamination performance. The details of the second part,

    which will provide information on the tracking and erosion

    performance of the housing, needs further work.

    5. ELECTRIC FIELD COMPUTATION

    Corona on porcelain insulating devices, which is a result of

    local high electric stress, is responsible for undesirable

    effects such as radio and TV interference, audible noise

    and ozone production. With polymer insulating devices, in

    addition to the above undesirable effects, corona causes

    material degradation n the form of punctures, pin holes and

    radial cracks, which can lead to the ultimate failure of the

    device with time. The permissible RIV,

    TVI

    and audible

    noise for polymer devices has to be lower than for the

    corresponding porcelain insulated devices.

    The critical voltage for corona initiation on outdoor high

    voltage devices is affected by electric stress, surface

    contamination and moisture, and is significantly lower than

    under clean and dry conditions. As the surface

    contamination changes with time and location, it is difficult

    to

    estimate the corona inception voltage under

    contaminated conditions. A way to prevent degradation

    from corona is

    to

    ensure that under normal operating

    conditions, the corona inception voltage is much higher

    than the rated voltage. Corona is initiated when the electr ic

    field on the insulating surface or in air exceeds 15 kV/cm

    The electric field distribution was computed using a Finite

    Element method based computer program POISSON ,

    developed by

    Los

    Alamos National Laboratory [23]. The

    PI

    maximum number of mesh points allowed by the program is

    limited to

    60,000,

    which was adequate for the present study.

    To

    improve the accuracy of computation, a variable mesh

    size was used, the region near the HV electrode having a

    greater mesh density than other parts of the arrester.

    Fig. 7 shows the electric field distribution of the surge

    arrester in the presently available form. The insulated

    mounting bracket was omitted from the computation as it

    does not affect the electric field distribution under unfaulted

    conditions. It can be observed that the equipotential lines

    are more crowded near the high voltage electrode, thus

    increasing the electric field in this region. Due to rotational

    symmetry, only one half of the arrester is modelled.

    i

    1

    Fig. 7: Electric Field Distribut ion with Existing Design. Each

    Equipotential Line Corresponds to 5 of the Applied

    Voltage.

    About 27% of the applied voltage appears in the first

    centimeter along the surface of the top most skirt. For the

    electric field to be below 15 kV/cm, the maximum voltage

    that can be applied is 15/0.27=55 kV. Experimental

    determination of the corona inception voltage on housing

    B

    indicated that the computed value was accurate to within

    10 .

    This suggests that the 9 kV rated arresters evaluated

    here and arresters up to 36 kV rating with the same design

    will not experience any serious problem from corona.

    For higher voltage ratings, some type of electric field control

    device (corona rings) may be required. Corona rings are

    usually separate hardware attachments. It is also possible

    that suitable modification of the electrode configuration will

    produce the desired effect at a lower cost, at least for

    intermediate voltage class arresters.

    Fig. 8 shows two possible modifications of the HV electrode

    and the resulting electric field distribution. In both cases, the

    electric

    field on the surface of the top skirts, and in the air

    region surrounding the HV electrode is reduced when

    compared to Fig. 7. For example, the maximum surface

  • 7/21/2019 Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

    6/10

    701

    b

    a

    Fig. 8: Electric Field Distribution with Modification of the HV Electrode. Each Equipotential Line is 5 of the Applied

    voltage

    electric stress along any part of the housing is reduced

    to

    15 and

    12

    per cm of the applied voltage, in Figs 8a and

    8b, respectively. There is also a reduction by about 20 in

    the electr ic field in air along the line of maximum stress

    XY

    in Fig. 8, when compared to Fig. 7. This indicates that with

    suitable modification of the HV electrode, the same

    diameter arrester can be used for voltage ratings higher

    than 55 kV without corona. However, more work is needed

    to

    optimize the electrode configuration.

    6. CONCLUSIONS

    1. This study demonstrates that the polymer housings used

    presently for zinc oxide arresters can exhibit tracking and

    erosion at low and moderate values, but not at very low and

    moderate values of fog conductivity. This should be

    considered in the preparation of accelerated contamination

    tests for polymer housed surge arresters.

    2. Fil ler dispersion played an important part in the tracking

    and erosion of the polymer housings evaluated. It appears

    that this parameter could be used as a quality control

    measure by eliminating housings with gross filler

    dispersion.

    3. The polymer housing seems to adequately protect the

    arrester column from moisture ingress.

    4. Electric field computation indicates that the present

    arrester design will be corona free up to 55 kV. For higher

    voltage ratings, suitable modification of the HV electrode

    can significantly ncrease the safe operating voltage.

    7. REFERENCES

    [l ]. D. W. Lenk, F. R. Stockum and D.

    E.

    Grimes, A New

    Approach To Distr ibution Arrester Design , IEEE Trans. on

    Power Delivery, VOl-3, No, 2, pp 584-590, April 1988.

    [2]. IEEE Transmission and Distribution Exhibition, New

    Orleans, 1989.

    [3]. E. A. Cherney and D.

    J.

    Stonkus, Non-Ceramic

    Insulators for Contaminated Environments , IEEE

    Transactions on Power Apparatus and Systems, Vol. PAS-

    [4]. P.J. Lambeth, Effect of Pollution on High Voltage

    Outdoor Insulators , Proc

    IEE, IEE

    Reviews, Vol-118, pp

    [5].

    R .

    S. Gorur, E. A. Cherney and

    R.

    Hackam,

    performance of Polymeric Insulating Materials in Salt-Fog ,

    IEEE Trans on Power Delivery, Vol-2, No. 2 pp 486-492,

    April 1987.

    [6]. E. C. Saksburg,

    J.

    S. Kresge, D. A. Mark, G. G. Karady,

    Contamination and Hot Wash Performance

    of

    Zinc Oxide

    Station Arresters , IEEE Trans. on Power Apparatus and

    Systems, Vol. PAS-101, No. 5, 1095-1102, May 1982.

    [7]. M. Cojan et al. Polymeric Transmission Insulators-

    Their Experience in France, Italy and the UK , CIGRE 22-10,

    1980.

    100, pp131

    1

    42, 1981.

    1107-1130, 1971.

    [8]. L. Johnson and W. Osborne, Contamination Testing of

    Distribution Class Cable Terminations , IEEE Underground

    T and D conference, Pub 76 CH

    11

    9-7-PWR, pp383-389,

    1976.

    [9]. Artificial Pollution Tests on High Voltage Insulators to

    be used on AC System , IEC Report 507,1975.

  • 7/21/2019 Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

    7/10

    [ lo]. R. S Gorur, E. A. Cherney and

    R.

    Hackam, A

    Comparative Study of Polymer Insulating Materials Under

    Salt-Fog Conditions , IEEE Trans El, Vol El-21, No.2, pp

    [ l l ] . R. S Gorur, E. A. Cherney and

    R.

    Hackam, Polymer

    Insulator Profiles Evaluated n a Fog Chamber , IEEE Trans

    on Power Delivery, Paper No. 89 TD 405 2 PWRD.

    [12]. R. S Gorur,

    E.

    A. Cherney and

    R.

    Hackam, Evaluation

    of Polymeric Cable Terminations n a Fog-Chamber , IEEE

    Trans on Power Delivery, VOl-4, No. 2, pp 842-849, April

    1989.

    [13]. C. Gregoire, P. J. Lambeth, M. Sforzini and M. P.

    Verma, A Critical Comparison of Artificial Pollution Test

    Methods for HV Insulators , CIGRE 33-75, 1975.

    [14]. G.

    R.

    Mitchell, Present Status of ASTM Tracking Test

    Methods , Journal of Test ing and Evaluation, Vol-2, No.1,

    [15].

    M.

    Kurtz, Comparison of Tracking Test Methods ,

    IEEE Trans., Electrical Insulation, Vol. El-6, pp 76-81, 1971.

    [16]. VDE Guide for Power Cable Accessories with Rated

    Voltage to 30 kV , VDE 0278, October 1982.

    175-182, April 1986.

    pp 23-31, 1974.

    [17]. G. C. Allen and R. K. Wild, Probing the Secrets of

    Solid Surface , CEGB Research, No. 11,

    ppl l-30,

    1981.

    [18]. R.

    S.

    Gorur, S Sundhara Rajan and 0. G. Amburgey,

    Contamination Performance of Polymers Used for Outdoor

    Insulation Applications , IEEE Trans on Electrical Insulation,

    Aug 1989.

    [19]. R. S Gorur, L. A. Johnson and H. Hervig,

    Contamination Performance

    of

    Silicone Rubber

    Terminations , Paper No.

    90

    WM 074-5 PWRD, 1990 IEEE

    PES Winter Meeting.

    [20]. E. C. Sakshaug, J. Burke and J. Kresge, Metal Oxide

    Arresters on Distribution Systems-Fundamental

    Considerations , Paper 89 WM 071-2 PWRD, IEEE/PES

    Winter Meeting, New York, 1989.

    [21]. IEEE Standard for Metal Oxide Surge Arresters for AC

    Power Circuits , ANSVIEEE Std. C62.11-1987.

    [22].

    E.

    Kuffel and M. Abdullah, High Voltage Engineering ,

    Pergamon Press, 1970.

    [23]. Poisson/Superfish Group of Codes , Los Alamos

    National Laboratory, Report LA-UR-87-126.

    Vikrant Chaudhry was born in

    Ujjain, India on June 1, 1967. He

    graduated with a B S degree in

    Electrical Engineering from the

    Regional Engineering College in

    Bhopal, India in 1988. Since Aug

    1988, he is with the Arizona

    State University, persuing a MS

    degree in Electrical and

    Computer Engineering. Mr.

    Chaudhry's fields of interest are,

    high voltage engineering and

    semi-conductors.

    Ravi Gorur was born in

    Bangalore, India on July 31,

    1958. He graduated with a BS

    degree f rom Bangalore

    University in 1981, MS degree

    from the Indian Institute of

    Science in 1983, and a Ph. D

    degree from the University of

    Windsor, Canada in 1986. He

    worked as a Post Doctoral

    Fellow at the University of

    Windsor until Aug 1987. He

    joined the Department of

    Electrical and Computer Engineering at 'Arizona State

    University as an Assistant Professor, n Sept. 1987.

    Dr. Gorur is currently involved in research on polymer

    materials and insulating systems for power transmission

    and distribution and space applications. He is the chairman

    of

    the IEEE Dielectric and Electrical Insulation Society's

    Outdoor Service Environment Committee. He is a member

    of the IEEE working groups on Insulator Contamination,

    Non-Ceramic Insulators and Insulated Conductors. He has

    several publications both in the IEEE Transactions and

    Conference Proceedings.

    Michael Dyer was born in St.

    Louis, Missouri, on June 1, 1954.

    He graduated with a

    BS

    Degree

    in Electrical Engineering from the

    University of Il linois at Urbana-

    Champaign, in 1977. He joined

    Illinois Power Co. in 1977, where

    he worked in the Danville

    Service Area. In 1980, he joined

    Salt River Project in Phoenix,

    Arizona, where he is responsible

    for Distribution and Transmission

    equipment applications, for the Electrical Apparatus

    Section. Mr. Dyer is a member of the Western Underground

    Committee, and is a registered Professional Engineer.

    Rao Thallam received the BS

    and MS degrees in Electrical

    Engineering in India, and the

    Ph.D degree from the University

    of Waterloo, Canada. He joined

    General Electric Company in

    1975, where he worked on

    HVDC projects Engineering,

    Surge Arrestor Engineering, and

    Electr ic Ut i l i ty Systems

    Engineering Departments. In

    1985, he joined Salt River

    Project in Phoenix, Arizona, where he is responsible for

    conducting application, design and specification studies for

    the Electrical Apparatus Section.

    Dr. Thallam is active in IEEE, as a member of the Surge

    Protective Devices committee, DC Transmission and DC

    Converter Stations Subcommittees. He is the utility industry

    advisor to EPRl for research projects on HVDC

    transmission, insulation coordination, and metal oxide

    surge arrestors. He has published several papers in IEEE

    and other international journals and conferences, and was

    awarded one patent in 1982. He is a registered

    professional engineer, senior member of IEEE, and

    member of CIGRE.

  • 7/21/2019 Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

    8/10

    7 3

    Discussion

    JEFFRY P. MACKEVICH, Raychem Corporation, Menlo

    Park, CA

    This paper is an interesting initial investigation into the

    contaminated performance of pol er housed distribution

    arresters.

    A

    task group has been c E g e d by Working Group

    3.3.10

    of the Surge Protective Devices Committee to address

    accelerated aging testing of polymeric housings and this paper

    is very timely.

    The scope of the aper is limited in terms of the materials

    tested, the test metgods used, and the claims which result. The

    reader should note that this work should be viewed

    as

    only a

    preliminary investigation. It is agreed with the authors that

    there ...is the lack of a meaningful laboratory test to redict the

    performance (of polymeric materials) in service. A i s is true,

    however, do the authors suggest that the salt fog chamber

    testing presented is a more meaningful test than any other test?

    This topic has been under discussion in the Insulated

    Conductors Committee and various Insulator working groups,

    however, a standardized test method is not yet available.

    Introduction

    The authors claim that Considerable amount of service

    experience and laboratory tests have demonstrated that there

    are two types of pol ers, namely silicone rubber and ethylene

    propylene rubber EPR), that are well suited for outdoor

    applications. While it is well known that both silicone rubber

    and EPR are used

    as

    outdoor insulating materials, they are not

    the only polymeric materials used, and the reader

    is

    left to

    question the purpose of this statement, given the lack of

    references or data to support the claim. There are other

    materials known to perform well in outdoor applications. One

    such example is semi-crystalline heat-shrink materials, with a

    known service life in excess of twenty years, used in medium-

    voltage shielded power cable terminations.

    [ l ]

    Since both a

    shielded power cable termination and a surge arrester have

    stress-grading characteristics, it would appear that a

    termination more closely models the arrester than a n insulator,

    and experience with terminations is a plicable. Mak et a1 [2]

    and Gorur et

    al [3]

    have each shown tgat semi-crystalline heat-

    shrink termination designs had superior performance in

    contaminated environments, similar to the conditions described

    in this paper. Gubanski [4] eported

    on

    work performed with

    merry-go-round contaminated environment testing that silicone

    rubber, epoxy resin and EPDM had comparable results. Can

    the authors explain why they neglected to mention other known

    polymer materials besides silicone rubber and EPR?

    The broad sweeping statement regarding silicone rubber and

    EPR not only omits existing olymeric materials but it also

    implies that the base p o k e r

    alone

    determines the

    performance. This statement reduces all material formulations,

    product design and manufacturing processes to the simplest

    denominator, the base polymer. Such a simplification is

    completely incorrect.

    s

    any materials person or product

    designer knows, product performance is a combination

    of

    the

    compound formulation (base polymer(s) and additives to

    enhance performance), product design (wall thickness, shed

    geomet and orientation, Cree age distance, sealing system,

    etc.) anymanufacturing rocess fcumulative heat history during

    com ounding and manuracturing). This statement also ignores

    pro& design. A poor design with an excellent polymer

    material may not provide the desired service performance. Can

    the authors elaborate

    on

    their implicit assumptions?

    The authors also indicate that the capacitance between the

    arrester column and the polymer housing is increased, relative

    to a porcelain unit.

    No

    data or calculations are provided to

    support this statement. Can the authors provide data to

    support the statement?

    ExDerimental

    The salt fog chamber testing conducted

    on

    arrester housings

    has been previously run

    on

    polymeric insulators and polymenc

    cable terminations. Given the statement by the authors at the

    end of the Introduction, ...it is essential to have sufficient

    laboratory data

    on

    polymer housed arresters such that a

    meaningful accelerated test can be developed for these devices

    as well , it is unclear as to the authors' motivation for

    conducting this study. There does not appear to be a known

    correlat ion between the salt fog chamber testing conducted and

    a given field service environment. Without a known correlation

    to service conditions, was the sole purpose of the study to

    obtain data for one set of salt fo4 chamber conditions? What

    additional da ta or further testing is suggested by the authors in

    order to develop meaningful tests? Can the authors clarify

    what one is to infer from the data presented, with respect to

    predicted field performance, and, is it reasonable to make such

    an extrapolation?

    Although the authors note that silicon rubber and EPR are

    resistant to

    UV

    chemicals, moisture, etc., they present no data

    to

    support the resistance of the specific test samples to

    degradation from these other environmental factors. A

    meaningful accelerated test should include simulation of

    multiple stress aging factors and not rely

    on

    separate test data

    developed from different sample formulations.

    Results and Discussion

    The authors tested two different housings in different

    configurations. Sample set

    B

    was tested with an insulating core

    and without zinc oxlde which provides stress grading. Can the

    authors comment

    on

    the equivalency

    of

    the testing samples

    A

    and

    B

    with the differences

    in

    sample construction and electric

    field distribution?

    One explanation given for the possible cause of degradation

    about the bottom electrode was the positioning of the samples

    relative to the fo nozzles. Do

    the authors mean to imply that

    the same sampfes located in a different position and/or

    orientation relative to the nozzles would have resulted in

    different performance? How would the results differ if there

    had been

    no

    fog nozzles, i.e. service in a high fog are a? Why

    would the nozzles

    not

    represent actual service conditions?

    The authors did not define failure criteria for this test. Gorur

    [SI presented these data in an earlier publication and reported

    failures in less than

    100

    hours for tests 2 and

    3.

    Can the authors

    explain the inconsistency between

    no

    reported failures in this

    paper and the reporting of these data with failures in reference

    S

    Other previous apers, which described testing in a salt fog

    chamber, claimed tl at a 5 hour test time was sufficient to

    discriminate the differences in performance among the samples

    evaluated. While that time may be valid for a comparative test,

    how should this data be used by others to test other materials

    and compare the results, if the testing was not taken to failure?

    Since previous papers (using the test chamber described in this

    paper) energized the polymer samples at voltages higher than

    rated line-ground voltage, why did the authors not run

    supplemental tests

    on

    Sam le

    B

    housings at elevated voltages to

    see what effect stress h a l o n performance? How severe of a

    test do the authors feel this was by only energizing the samples

    at operating voltage without accelerated stress aging? With

    tracking occurring at relatively moderate levels of conductivity,

    can the authors comment

    on

    the suitability of the two materials

    tested for use as arreste r housings for applications in polluted

    service environments?

    Was

    the variation in filler dis ersion reported obtained from

    one sample set only or did all tge samples tested have the same

    filler distribution at the mold line?

    Does Figure

    6

    represent

    one sample only or is it an average of a larger sample set?

    One aspect, not discussed in the paper, is what the possible

    effects of a contaminated test or semce environment might be

  • 7/21/2019 Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

    9/10

    704

    on the insulating mounting bracket. Arres ter designs vary, with

    some units having a ground-end metal sealing cap, while othe rs

    do not. For the latter ar rq em en t, all surface leakage currents

    must flow over the housing surface, across the insulating

    bracket and disconnector, collecting on the ground lead

    mounting stud. Can the authors speculate as to what might

    happen to the housing and bracket if there is no concentric

    leakage current collector (end cap) between the housing and

    bracket?

    Resistance To Moisture Ineress

    The au thors are correct in identifying the requirement

    to

    have a

    watertight interface between housing and internal components.

    Dissipation factor is a valid method for determinin the

    integrity of an interface, yet it would seem that 509 %ours

    exposure in a salt fog chamber may not be a ve ngoro us

    moisture seal test.

    Can

    he authors comment as to #e severity

    of this exposure

    as

    a moisture seal test. Would it not be more

    appropriate to conduct a thermal cycle freeze/thaw test as

    discussed by Bradwell[6] for polymeric insu lators?

    It is widely believed that moisture ingress is due to pumping

    action of the rmal excursions such as might occur as a result of

    a lightning discharge. The testing conducted was without any

    energy input and the samples remained at ambient temperatur e

    over the duration of the test. Can the authors comment on the

    adequacy of the sealing systems for those units tested with

    regar d to possible pumping ?

    Groeger [7] has presented data suggesting that grease along a

    separable EPDM elbow connector interface migrates

    as

    a

    function

    of

    time. Since arrester rubber housings rely on an

    inter feren ce fit and residual compression, rm@t not this

    henomenon also apply to arresters? Was this investigated?

    b id the au thors consider seal degradation and what impact this

    would have on long term performance? Can the authors

    comment on the need for sample a 'ng rior to seal testing to

    test expected performance over the B e o rt he device?

    This section contains an erroneous statement that should be

    corrected: Fiber glass carbonizes under the combined presence

    of moisture and electric stress. Glass fibers do not carbonize.

    The authors may have been trying to describe the effects of

    moisture and &h electrical stress on the epoxy resin binder in

    a fiber glass/epoxy matrix, or on a resinous coating of the glass

    fibers.

    Conclusiory

    1 The first sentence in conclusion number 1 appears to be

    missing a word: ... inc oxide arresters can exhibit tracking and

    erosion at low and moderate values,... The question is, at low

    and mod erate values of what? The reader is left dangling.

    2. In the second sentence of conclusion number two, the use of

    the word gross is inaccurat e and misleading.

    It appears that

    the authors means to say non-uniform or grossly uneven

    filler dispersion .

    3. Conclusion number three doe5 not appear to have a

    necessary basis. No long-term humidi cycling, therm al aging

    or temperature cycling was con duc ter in the re orted tests.

    Any of these factors could disrupt the integn o?the housing

    environmental seals, and the potential e z c t s should be

    investigated or, at least, considered, before the conclusion was

    made that the arrester column is adequately protected from

    moisture ingress.

    References

    [ l ]

    R.

    Penneck and D. Nyberg, Im rovements in non-trackin

    materials, presented at the 7th &EE PES Conference an8

    Exposition on Transmission and Distribution, Atlanta, GA,

    April 14,1979.

    [2]S.Mak and G. Lusk, Contaminated Environment Testing of

    Cable Terminations, presented at the 7th IEEE PES

    Conference and Exposition on Transmission and Distribution,

    [3] R. Gorur, E. Cherney and R. Hackam, Evaluation of

    Polymeric Cable Terminations in a Fog-Chamber , IEEE

    Transactions on Power Delivery, Vol. 4, No. 2, pp. 842-849,

    April 1989.

    [4]

    S.

    Gubanski , Experience with the Me o-round Test ,

    IEEE Transactions on electrical Insulation,vi&25, No. 2, pp.

    [5]

    R.

    Gorur, Polymers for Outdoor Insulation , presented at

    the 6th BEAMA International Electrical Insulation

    Conference, Brighton , May 22-24, 1990.

    [6]

    k

    Bradwell, Importance of preventing moisture ingress to

    polymeric insulators , IE E Proceedings, Vol.

    131,

    Pt. B,

    No.

    6,

    November 1984, pp. 245-251.

    [7]

    J.

    Groeger, presentation made at the 86th Meeting of the

    Insulated Conductors Committee, Sub-committee 10 Meeting,

    Dearborn, MI, May 1,1990.

    Atlanta, GA, April 1-6,1979.

    331-340, April 1990.

    Manuscript received J u l y 30, 1 9 9 0 .

    H.

    S.

    Brewer and D

    W. Lenk

    (The Ohio Brass Company, Wadsworth,

    Ohio): The authors are to be commended on their initial efforts to develop

    a test procedure to evaluate the contamination performance of polymer

    housed metal oxide arresters. This is obviously an area that deserves

    continuing examination.

    We have several questions regarding the Salt Fog Test Procedure and

    would appreciate clarifications. Salt fog

    tests

    were performed with salt-fog

    nozzles. What is the orientation of the test specimen relative to direction

    of the salt fog spray from the nozzles? Did the authors find this orientation

    critical to the rate

    of

    surface activity and possible degradation?

    ANSI C29.11-1989, Test Standard for Composite Suspension Insula-

    tors, specifies a 1OOOhour continuous salt fog test procedure utilizing a

    turbo sprayer or room humidifier to generate fog. Would you expect test

    results to vary significantly as a result of replacing spray nozzles with

    either of the above methods?

    The authors state that for the small distribution arresters the flow of

    internal current is not critical in evaluating the surface degradation charac-

    teristic. What are the authors' thoughts on performing tests with internal

    MOV disk elements replaced with insulating components? With MOV disk

    elements removed, the severity of the fog test is accelerated by increasing

    the applied voltage. On larger diameter housings, which would tend to be

    slower in developing dry band arcing activity, this might be helpful in

    generating surface arcing.

    The authors state that the salt fog chamber was shut off for two hours

    each day to allow examination of the test samples.

    Do

    they feel that the

    forced drying/wetting duty associated with reenergization was important

    to the surface degradation? Would they expect to be able to duplicate test

    results utilizing continuous fog energization?

    We do not agree with the authors conclusion that it is valid to perform

    tests on samples energized with high voltage applied at the bottom end of

    the arrester housing. They state . .dry band arcing is dependent on the

    direction of the water flow on the surface . Do they have a technical

    reference for this statement? If so, will the authors provide this reference?

    The authors conclude that poor filler dispersion may have contributed to

    the surface degradation protilem. When were the filler dispersion measure-

    ments taken? Were they taken on the sample units after completion of the

    salt fog exposure tests? If so, the disparity in dispersion ratio measure-

    ments could have been the result of intense surface activity, rather than the

    cause of the degradation.

    Polymer enclosed distribution class surge arresters have been installed

    since 1986. To date, more than 1 OOO OOO polymer units have been

    shipped, with no reported failures from surface tracking or erosion. Are

    the authors able to correlate the Salt Fog Test Procedure to actual service

    conditions?

    Manuscript

    received

    August

    3 1990.

  • 7/21/2019 Chaudhry Et Al. - 1991 - Electrical Performance of Polymer Housed Zinc Oxid

    10/10

    705

    R. S . GORUR (Arizona State University, Tempe, AZ): On behalf of

    all the authors,

    I

    would like to thank the discussers for their

    interesting comments which add to the value of the paper.

    To

    Mr. H.

    S. Brewer and

    D

    W.

    1 . d

    The test samples were

    located at about 0.5m below the horizontal plane of the fog nozzles.

    As long as the samples were located below the fog nozzles, the

    degradation rate was not too different. The main wetting mechanism

    is by droplet impingement as the type of fog used is the cold fog.

    This orientation was chosen as in the field, rain falls from above on

    to the devices.

    There is data published to show that the flashover voltage is

    dependent, to a certain extent, on the droplet size and temperature of

    the fog and test object

    [I].

    With polymeric cable terminations, the

    same

    type of termination has performed differently in several test

    methods, all using cold fog [Ref. [191 of paper]. The method of fog

    generation

    is

    an important parameter which could influence the test

    results, and is an area which needs further investigation.

    We have performed numerous tests where the de-energization time

    has been varied from zero to

    24

    hours. The end results were

    essentially identical for de-energization times of zero (continuous

    fog generation) and two hours.

    References 3 and

    4

    of the paper, provides the information on the

    effect of the water flow pattem on the degradation rate.

    The filler dispersion measurements were performed after the salt fog

    tests. We do not believe that the non-unifonh filler dispersion is the

    result of intense

    dry

    band activity,

    as

    the filler dispersion was fairly

    uniform in locations other than the mold lide, where tracking was

    visible. If the discussers statement were to be true, then a non-

    uniform filler dispersion should be expected at every location that

    showed tracking or erosion due to intense surface activity.

    We have not correlated the life in the salt-fog test to that in service.

    The fog chamber test used here and other laboratory tests are merely

    tools which

    are

    useful in identifying problems in the design and

    materials. It is extremely difficult to associate life in service with

    hours of exposure in a laboratory test as the wetting and

    contamination severities are not the

    same

    for any two locations.

    Based on experience with polymer insulators, any problems in the

    design and material are not visible in the first few years, but appear

    later.

    TOMr. J. P. Mackevi ch. We have made no claim that silicone and

    EPDM rubber are &e onlv tWO tvD of materials that are suited for

    outdoor insulation applications. The purpose of the introduction is to

    provide a brief background information on polymer housing used

    for surge arresters, and not mentioning other materials does not

    mean that they are unsuitable for outdoor applications.

    Valuable information regarding the details of the material

    composition and product design are trade secrets, which

    are

    not

    divulged

    to

    the user or to universities. Without the exact knowledge

    of these aspects, more mistakes in the sample description are

    possible and this is not desirable. One way of characterizing

    materials is by the public domain information, which is what has

    been done in this paper.

    Regarding the capacitance, Reference [6] of the paper provides the

    supporting data.

    The purpose of the present work was to provide information which

    can be used for the development of accelerated aging tests on

    polymer housed arresters, and not to develop THE STANDARD

    itself. There are many more aspects, some of which are mentioned

    by the discusser, which require further research.

    Regarding the resistance of silicone rubber and EPDM materials to

    UV, chemicals and moisture, the data is already available in many

    books and also in manufacturers' catalogs, and therefore was

    presumed to be well known information which need not be

    referenced.

    Although the electric field distribution is different for samples A and

    B

    in the

    dry

    conditidh, when the surface is covered by a water layer,

    the conducting surface wohld be the dominating factor and the

    difference in the electric field dismbution is expected to be similar

    for both samples.

    The type of fog, temperature, droplet size method of wetting are

    a l l

    known to

    affect the contaminriiionperformance of outdoor insulation

    [

    11.

    The study of fog parameters was not performed in this work,

    therefore, it is not possible

    io

    address the discusser's question.

    The data reported in Ref [5] of the discussion and in this paper is

    consistent, contrary tb the discusser's observation. The

    500

    hour

    test duration

    is

    only a beiichmark for comparison, each test

    procedure has a ceitain duration below which no failures can be

    expected. Comparison of results from various test methods is

    difficult and this

    has

    been well illustrated in Ref

    [191

    of the paper for

    polymeric cable terminatibns.

    As samples B showed deadation at the normal operating stress, it

    would not be surprising to see more degradation at higher than

    normal stresses, and ndt much information would be gained by

    doing the proposed tests.

    All the samples of type B which showed erosion along the mold

    release showed non-uniformities in the fil ler dispersion and fig. 6is

    the typical plot and not from just one sample.

    Without test data, it would ,not be possible to speculate the

    performanceof the device mentioned in the discussion.

    The

    paper mentions that based on the present results, the housing

    material showed good resistance to moisture ingress. The aspects

    mentioned by tht discusser should be considered

    for the

    development of a test shdard, and this was not the objective of the

    present paper.

    Regarding carbonization of glass fibers, this was an oversight, and

    it is

    true

    that it is not the glass fibers which carbonize but the organic

    resin which binds the fibers.

    The points mentioned in the first two points of the conclusion are editorial.

    The conclusions are based on the test results of the present work and

    conclusion number three is therefore valid.

    Reference

    [I]. G . Karady "The Effect of

    FOE

    Parameters on the Testine of

    Artificially Contaminated InsulaGrs in a Fog Chamber , IEEE

    Trans. PAS 1975, pp 378-387.

    Manuscript r e c e i v e d

    October

    5, 1 9 9 0 .