FCB 20603HEATING & COOLING
LOAD
1FCB 20603 Heating & Cooling Load
COOLING LOAD
• PURPOSE OF DESIGN LOAD CALCULATIONSOutside weather conditions and the sun
combine to produce a cooling or heating load through the building envelope.
The load depends on :o The thermal characteristics of the walls, roof,
fenestrations (an opening in a surface of a structure), floor, interior building furnishings, and construction, and
o The driving force resulting from the difference between the outside conditions (including solar) and the inside conditions.
2FCB 20603 Heating & Cooling Load
COOLING LOAD
• For example, the heat transferred through a roof depends on the temperature of the top surface of the roofing, the temperature of the inside surface of the ceiling, how these temperatures vary with time, and the energy storage characteristics of the roof construction.
3FCB 20603 Heating & Cooling Load
COOLING LOAD
• The temperature of the outside surface depends on the ever-changing solar radiation absorbed by the surface.
• A similar analysis of the inside surface shows that the surface temperature depends on the amount of heat conducted from above and convection occurred to the inside air, the radiation exchange between the surface and room furnishings, and internal sources.
4FCB 20603 Heating & Cooling Load
COOLING LOAD
• Therefore, the heat flow through the roof construction will not be constant.
• This same phenomenon occurs for all other surfaces subjected to radiation effects and variable temperature environments.
5FCB 20603 Heating & Cooling Load
COOLING LOAD
• Under the conditions described above, the amount of insulation and the thermal mass of the roof, wall, or partition are critical in the heat transfer analysis.
• The heat transferred through transparent surfaces such as glass is more a function of the thermal radiation characteristics of the glass and less dependent on the thermal storage capacity of such materials due to very low mass and absorptance of the material.
6FCB 20603 Heating & Cooling Load
COOLING LOAD
• The heat gain due to lights, people, and equipment is independent of the outdoor environment and is a function of occupancy and operating schedule.
• Again, radiation effects are involved, and the thermal storage characteristics of the space are important in estimating the cooling load.
7FCB 20603 Heating & Cooling Load
COOLING LOAD
• Design load calculations provide the basic data for selecting an HVAC system and equipment and also provide the basic for sizing the associated ducts and piping.
• These data should be computed from times of peak load as well as partial load.
• Analysis and study of these conditions may then indicate possibilities for load reduction or other refinements of the system.
8FCB 20603 Heating & Cooling Load
COOLING LOAD
• It is usually desirable to carry out extensive load calculations (several different hours of the day or all 24 hours) if the system is to be complex, such as a large variable air volume (VAV) system. Further, it may be necessary to make calculations for two or more months.
• On the other hand, a small building using unitary equipment may require load calculations for only the peak time of day.
9FCB 20603 Heating & Cooling Load
Infiltration : When outdoor air enter a space through cracks on floors, walls, ceilings partition.10FCB 20603 Heating & Cooling Load
11FCB 20603 Heating & Cooling Load
COOLING LOAD
RULE OF THUMB
12FCB 20603 Heating & Cooling Load
13FCB 20603 Heating & Cooling Load
22.95 590.55
95.15
22.95
9.45
292.00
752.00
137.85
Unit measurement :meter
Sale
Food CourtShop 1Office
Surau
Shop 2
Calculation :1. Sale
Area = ==
2. Shop1Area =
==
3. Shop2Area =
==
4. Food courtArea =
==
5. OfficeArea =
==
6. SurauArea =
==
14FCB 20603 Heating & Cooling Load
15FCB 20603 Heating & Cooling Load
16FCB 20603 Heating & Cooling Load
17FCB 20603 Heating & Cooling Load
18FCB 20603 Heating & Cooling Load
COOLING LOAD
19FCB 20603 Heating & Cooling Load
COOLING LOAD
20FCB 20603 Heating & Cooling Load
COOLING LOAD
21FCB 20603 Heating & Cooling Load
22FCB 20603 Heating & Cooling Load
23FCB 20603 Heating & Cooling Load
24FCB 20603 Heating & Cooling Load
25FCB 20603 Heating & Cooling Load
26FCB 20603 Heating & Cooling Load
27FCB 20603 Heating & Cooling Load
< calculation Cooling Load>28FCB 20603 Heating & Cooling
Load
29FCB 20603 Heating & Cooling Load
30FCB 20603 Heating & Cooling Load
We set below experiment at room temperature and room pressure. Which one will will become heavier after 3 hrs?
t = 0 Water + bottle = 200 grm ice + bottle = 200 grm
t = 3 hrs
Water + bottle = 200 grm Water + bottle + condesation = 200 + grm
31FCB 20603 Heating & Cooling Load
Assuming below are 3 container place at room temperature and room pressure, which represent the vapor (gas), liquid and solid of water?
represent water molecules
represent water molecules speed 32FCB 20603 Heating & Cooling Load
Gas Liquid
Ice Liquid water
Solid
Water vapor
Assuming below are 3 container place at room temperature and room pressure, which represent the vapor (gas), liquid and solid of water?
represent water molecules
represent water molecules speed 33FCB 20603 Heating & Cooling Load
Assuming that the ice in the bottle is been heated, what can we say interm of the molecules and pressure and the density inside the bottle as time goes by?
t=0 t=10 t=20 34FCB 20603 Heating & Cooling Load
35FCB 20603 Heating & Cooling Load
< calculation Cooling Load>
7.5
m
Example 1:
1.6m
x 2
.5m
Next Room
Window with blind
1.5m x 3 m
window
DoorDoor
window
window window window window
2nd Floor
Passage
N
Ceiling height : 3.0 m
• Find the cooling load of a double-storey house based on the following conditions.– Specifications of construction
• Building: Five-storey building• Outside wall: Medium construction• Window glass: Normal (6mm thickness) with blind• Floor: Concrete with linoleum (a type of strong material with a hardy shiny
surface, used for covering floor)• Ceiling: Only concrete• Lights: Fluorescent light (40W x 20)• Persons: 15 (working)• Area: Standard temperature area*** Adjoined upper and lower rooms are not cooled
18 m
36FCB 20603 Heating & Cooling Load
COOLING LOAD• Example 2. Find the cooling load of a double-storey house based on the
following conditions.– Specifications of construction
• Building: Double-storey house• Outside wall: Light construction• Window glass: Normal (6mm thickness) with blind• Floor: Concrete with linoleum (a type of strong material with a hardy shiny
surface, used for covering floor)• Ceiling: Only concrete• Lights: Fluorescent light (60W x 17)• Persons: 7• Area: Standard temperature area• Roof: Light construction with ceiling
37FCB 20603 Heating & Cooling Load
38FCB 20603 Heating & Cooling Load
Ruang Tamu
Ruang makan
Dapur Utility
Bilik Mandi
Bilik tidur 2 Bilik tidur 3
Bilik Mandi
Ruang Tamu
Bilik tidur utama
Bilik Mandi
Balkoni
6096 mm 6096 mm
13715 mm
2133
6 m
m
1371
5 m
m
3000
mm
3000 mm
4300 mm
13715 mm
3000 mm
2000 mm
Ceiling Height = 3000mm< calculation Cooling Load>
N
39FCB 20603 Heating & Cooling Load
40FCB 20603 Heating & Cooling Load
41FCB 20603 Heating & Cooling Load