Control of Multiple-Input, Multiple-Output Processes

Multiloop controllers• Modeling the interactions• Relative Gain Array (RGA)• Singular Value Analysis (SVA)• Decoupling strategiesC

hapt

er 1

8

Page 2: Chapter 18

Control of multivariable processes

In practical control problems there typically are a number of process variables which must be controlled and a number which can be manipulated

Example: product quality and through put must usually be controlled.

• Several simple physical examples are shown in Fig. 18.1.

Note "process interactions" between controlled and manipulated variables.

Cha

pter

18

Page 3: Chapter 18

SEE FIGURE 18.1in text.

Cha

pter

18

Page 4: Chapter 18

Cha

pter

18

Page 5: Chapter 18

• Controlled Variables:

• Manipulated Variables:

BDBD hhPxx and ,,,,

BD Q and ,Q,R,B,D

Cha

pter

18

Page 6: Chapter 18

In this chapter we will be concerned with characterizing process interactions and selecting an appropriate multiloop control configuration.

If process interactions are significant, even the best multiloop control system may not provide satisfactory control.

In these situations there are incentives for considering multivariable control strategies

Definitions:

•Multiloop control: Each manipulated variable depends on only a single controlled variable, i.e., a set of conventional feedback controllers.

•Multivariable Control: Each manipulated variable can depend on two or more of the controlled variables.

Examples: decoupling control, model predictive control

Cha

pter

18

Page 7: Chapter 18

Multiloop Control Strategy•Typical industrial approach•Consists of using n standard FB controllers (e.g. PID), one for

each controlled variable.

•Control system design1. Select controlled and manipulated variables.2. Select pairing of controlled and manipulated variables.3. Specify types of FB controllers.

Example: 2 x 2 system

Two possible controller pairings:U1 with Y1, U2 with Y2 …orU1 with Y2, U2 with Y1

Note: For n x n system, n! possible pairing configurations.

Cha

pter

18

Page 8: Chapter 18

Transfer Function Model (2 x 2 system)

Two controlled variables and two manipulated variables(4 transfer functions required)

Thus, the input-output relations for the process can be written as:

)()()(),(

)()(

)()()(),(

)()(

222

221

1

2

122

111

1

1

sGsUsYsG

sUsY

sGsUsYsG

sUsY

PP

PP

)()()()()()()()()()(

2221212

2121111

sUsGsUsGsYsUsGsUsGsY

PP

PP

Cha

pter

18

Page 9: Chapter 18

Or in vector-matrix notation as,

where Y(s) and U(s) are vectors,

And Gp(s) is the transfer function matrix for the process

)()()( sUsGsY P

)()(

)(,)()(

)(2

1

2

1

sUsU

sUsYsY

sY

)s(G)s(G)s(G)s(G

)s(G22P21P

12P11PP

Cha

pter

18

Page 10: Chapter 18

Cha

pter

18

Page 11: Chapter 18

Control-loop interactions

• Process interactions may induce undesirable interactions between two or more control loops.

Example: 2 x 2 systemControl loop interactions are due to the presence

of a third feedback loop.• Problems arising from control loop interactions

i) Closed -loop system may become destabilized.ii) Controller tuning becomes more difficult

Cha

pter

18

Page 12: Chapter 18

Block Diagram Analysis

For the multiloop control configuration the transfer function between a controlled and a manipulated variable depends on whether the other feedback control loops are open or closed.

Example: 2 x 2 system, 1-1/2 -2 pairingFrom block diagram algebra we can show

Note that the last expression contains GC2 .

),()()(

111

1 sGsUsY

P

222

2211211

1

1

1)()(

PC

CPPP GG

GGGGsUsY

Cha

pter

18

(second loop open)

(second loop closed)

Page 13: Chapter 18

Cha

pter

18

Page 14: Chapter 18

Cha

pter

18

Page 15: Chapter 18

Cha

pter

18

Figure 18.6 Stability region for Example 18.2 with 1-1/2-2 controller pairing

Page 16: Chapter 18

Cha

pter

18

Figure 18.7 Stability region for Example 18.2 with 1-2/2-1 controller pairing

Page 17: Chapter 18

Relative gain array

• Provides two useful types of information:1) Measure of process interactions2) Recommendation about best pairing of controlled and manipulated variables.

• Requires knowledge of s.s. gains but not process dynamics.

Cha

pter

18

Page 18: Chapter 18

Example of RGA Analysis: 2 x 2 system• Steady-state process model,

The RGA is defined as:

where the relative gain, ij, relates the ith controlled variable and the jth manipulated variable

2221212

2121111

UKUKYUKUKY

2221

1211RGA

gain loop-closedgain loop-open

ij

Cha

pter

18

Page 19: Chapter 18

Scaling Properties:

i) ij is dimensionless

ii)

For 2 x 2 system,

Recommended Controller Pairing

Corresponds to the ij which has the largest positive value.

0.1j

iji

ij

211112

2211

211211 1,

KKKK1

1

Cha

pter

18

Page 20: Chapter 18

In general:1. Pairings which correspond to negative pairings should not be selected.2. Otherwise, choose the pairing which has ij closest

to one.

Examples:Examples: Process Gain Relative Gain Matrix, : Array, :

22

11

K00K

0K

K0

21

12

22

1211

K0KK

2221

11

KK0K

1001

0110

1001

1001

K

Cha

pter

18

Page 21: Chapter 18

211112

2211

211211 1,

KKKK1

1

Recall, for 2X2 systems...

2221212

2121111

UKUKYUKUKY

EXAMPLE:EXAMPLE:

29.229.129.129.2

25.15.12

KKKK

K2221

1211

Recommended pairing is Y1 and U1, Y2 and U2.

EXAMPLE:EXAMPLE:

64.036.036.064.0

25.15.12

K

Recommended pairing is Y1 with U1, Y2 with U2.

Cha

pter

18

Page 22: Chapter 18

EXAMPLE: Thermal Mixing SystemEXAMPLE: Thermal Mixing System

The RGA can be expressed in terms of the manipulated variables:

Note that each relative gain is between 0 and 1. Recommendedcontroller pairing depends on nominal values of W,T, Th, and Tc.

See Exercise 18.16

ch

hc

c

hc

h

hc

h

hc

c

WW

WWW

WWW

WWW

WWW

T

W

Cha

pter

18

Page 23: Chapter 18

EXAMPLE: Ill-conditioned Gain Matrix

y = Ku

2 x 2 process y1 = 5 u1 + 8 u2

y2 = 10 u1 + 15.8 u2

specify operating point y, solve for u

-1

Adjdet

K= =K

u K y y

11 22 11 2211

11 22 12 21

RGA : det

K K K KK K K K K

effect of det K → 0 ?

Cha

pter

18

Page 24: Chapter 18

RGA for Higher-Order Systems:

For and n x n system,

Each ij can be calculated from the relation

Where Kij is the (i,j) -element in the steady-state gain matrix,

And Hij is the (i,j) -element of the .

Note that,

1 2

1 11 12 1

2 21 22 2

1 1

n

n

n

n n n nn

U U UYY

Y

ijijij HK

UKY

T1KH

HK

:KCha

pter

18

Page 25: Chapter 18

EXAMPLE: HydrocrackerEXAMPLE: Hydrocracker

The RGA for a hydrocracker has been reported as,

Recommended controller pairing?

4321

4

3

2

1

919.1900.0030.2215.0910.1270.0314.3135.0

154.1286.0429.0011.0164.0080.0150.0931.0UUUU

YYYY

Cha

pter

18

Page 26: Chapter 18

Singular Value AnalysisK = W VT

is diagonal matrix of singular values(1, 2, …, r)

The singular values are the positive square roots of the eigenvalues of

KTK (r = rank of KTK)W,V are input and output singular vectors Columns of W and V are orthonormal. Also

WWT = IVVT = I

Calculate , W, V using MATLAB (svd = singular value decomposition)Condition number (CN) is the ratio of the largest to the smallest singular value and indicates if K is ill-conditioned.

Cha

pter

18

Page 27: Chapter 18

CN is a measure of sensitivity of the matrix properties to changes in a specific element.Consider

(RGA) = 1.0If K12 changes from 0 to 0.1, then K becomes a singular matrix, which corresponds to a process that is hard to control. RGA and SVA used together can indicate whether a process is easy (or hard) to control.

K is poorly conditioned when CN is a large number (e.g., > 10). Hence small changes in the model for this process can make it very difficult to control.

1 010 1

K

10.1 0( ) = CN = 101

0 0.1K

Cha

pter

18

Page 28: Chapter 18

Selection of Inputs and Outputs

• Arrange the singular values in order of largest to smallest and look for any σi/σi-1 > 10; then one or more inputs (or outputs) can be deleted.

• Delete one row and one column of K at a time and evaluate the properties of the reduced gain matrix.

• Example:0.48 0.90 0.0060.52 0.95 0.0080.90 0.95 0.020

K

Cha

pter

18

Page 29: Chapter 18

CN = 166.5 (σ1/σ3)

The RGA is as follows:

Preliminary pairing: y1-u2, y2-u3,y3-u1.

CN suggests only two output variables can be controlled. Eliminate one input and one output (3x3→2x2).

0.5714 0.3766 0.7292 0.6035 0.4093 0.6843

0.5561 0.8311 0.0066

W

1.618 0 00 1.143 00 0 0.0097

0.0541 0.9984 0.0151 0.9985 0.0540 0.0068

0.0060 0.0154 0.9999

V

2.4376 3.0241 0.4135 1.2211 0.7617 0.5407 2.2165 1.2623 0.0458

Cha

pter

18

Cha

pter

18

Page 30: Chapter 18

Cha

pter

18

Page 31: Chapter 18

Cha

pter

18

Page 32: Chapter 18

Alternative Strategies for Dealing with Undesirable Control Loop Interactions

1. "Detune" one or more FB controllers.2. Select different manipulated or controlled variables. e.g., nonlinear functions of original variables3. Use a decoupling control scheme.4. Use some other type of multivariable control scheme.

Decoupling Control Systems

Basic Idea: Use additional controllers to compensate for processinteractions and thus reduce control loop interactions

Ideally, decoupling control allows setpoint changes to affect onlythe desired controlled variables.

Typically, decoupling controllers are designed using a simple process model (e.g. steady state model or transfer function model)

Cha

pter

18

Page 33: Chapter 18

Cha

pter

18

Page 34: Chapter 18

Design Equations:We want cross-controller, GC12, to cancel out the effect of U2 on Y1.Thus, we would like,

Since U2 0 (in general), then

Similarly, we want G21 to cancel the effect of M1 on C2. Thus, werequire that...

cf. with design equations for FF control based on block diagramanalysis

12 11 2 12 2 0P PT G U G U

1212

11

P

P

GTG

21 22 1 21 1

2121

22

0P P

P

P

T G U G UGTG

Cha

pter

18

Page 35: Chapter 18

Process Interaction

Corrective Action (via “cross-controller” or “decoupler”).Ideal Decouplers:

1212

11

2121

22

( )( )( )( )( )( )

P

P

P

P

G sT sG sG sT sG s

Cha

pter

18

Alternatives to Complete Decoupling

• Static Decoupling (use SS gains)• Partial Decoupling (either GC12 or GC21 is set equal to zero)

Page 36: Chapter 18

Variations on a Theme:

•Partial Decoupling:Use only one “cross-controller.”

•Static Decoupling:Design to eliminate SS interactionsIdeal decouplers are merely gains:

•Nonlinear DecouplingAppropriate for nonlinear processes.

1212

11

2121

22

P

P

P

P

KTKKTK

Cha

pter

18