Chapter 06
-
Upload
benewberry1 -
Category
Business
-
view
1.220 -
download
1
description
Transcript of Chapter 06
Chapter Six
Installation of Fire Protection Systems
2
Learning Objectives
• List four classes of fire
• Identify fire suppression system agents compatible with each class
• Describe method of extinguishment
• List and describe the four basic types of sprinkler systems
3
Learning Objectives
• Describe differences between NFPA 13, 13D, and 13R standards and applications
• Describe function of standpipe pressure reducing valves and potential hazards
4
Learning Objectives
• Describe the purpose for UL-300 standard
5
Fire Protection Systems
• Extinguishing systems for structural protection and life safety
• Detection and alarm devices
• Smoke control and removal systems
• Extinguishing systems for industrial process
• Portable first aid extinguishing devices
6
Fire Protection Systems
• Engineered systems
• Designed for a specific hazard
• Any change in hazard requires reevaluation of the system to determine its effectiveness
7
Fire Protection Systems
• A primary responsibility of the inspector is to verify system maintenance
• No change to hazard classification
8
Fire Extinguishing Systems
• Agents used in extinguishing systems must be appropriate for the hazard
• Compatible with one another
• Water extinguishers are not appropriate for fires in energized electrical equipment
• ABC and BC types of dry chemical are not compatible
9
Fire Classes
A - Common combustibles
B - Flammable liquids and gases
C - Energized electrical equipment
D - Combustible metals
10
Extinguishing Agent Classes
A - Water, dry chemical, foam, some halon
B - CO², dry chemical, halon, foam
C - CO², dry chemical, halon
D - Dry powder
11
Fire Triangle
12
Fire Tetrahedron
13
NFPA 13
• Property protection system
• Provides a high level of safety
• All areas of building are protected
• Including combustible void spaces
14
Occupancy Classifications
• Light Hazard
• Ordinary Hazard Group 1
• Ordinary Hazard Group 2
• Extra Hazard Group 1
• Extra Hazard Group 2
15
Light Hazard Occupancies
• Occupancies where quantity and combustibility is low
• Fires develop a low rate of heat release
• Stock piles do not exceed 8 feet
16
Light Hazard Occupancies
• Churches
• Schools
• Libraries
• Offices
• Theaters
17
Light Hazard Occupancies
• Clubs
• Hospitals
• Museums
• Residential
• Restaurants
18
Ordinary Hazard Group 1
• Occupancies where quantity and combustibility is low
• Fires develop a moderate rate of heat release
• Stock piles do not exceed 8 feet
19
Ordinary Hazard Group 1
• Automobile parking
• Bakeries
• Canneries
• Dairies
• Restaurant service areas
20
Ordinary Hazard Group 2
• Occupancies where quantity and combustibility is moderate
• Fires develop a moderate rate of heat release
• Stock piles do not exceed 12 feet
21
Ordinary Hazard Group 2
• Cereal mills
• Chemical plants
• Distilleries
• Dry cleaners
• Machine shops
• Repair garages
22
Extra Hazard Group 1
• Occupancies where quantity and combustibility is very high
• Fires develop a high rate of heat release
• May contain a small amount of flammable liquids
23
Extra Hazard Group 1
• Aircraft hangars
• Plywood manufacturing
• Saw mills
• Textile picking
• Upholstering with plastic foam
24
Extra Hazard Group 2
• Occupancies where quantity and combustibility is very high
• Fires develop a high rate of heat release
• May contain a large amount of flammable liquids
25
Extra Hazard Group 2• Flammable liquid spraying
• Manufactured home assembly
• Plastics processing
26
Sprinkler Standards
• NFPA 13R Standard – Installation of sprinkler systems in residential
occupancies up to four stories
27
NFPA 13R
• Residential occupancies 4 stories
• Sprinklers may be omitted from:– Bathrooms 55 ft²– Closets 24 ft²– Garages, carports, porches, attics, crawl
spaces, and combustible voids
28
NFPA 13R
• Provide a high level of life safety
• Designed to prevent or delay flashover and permit escape
• Does not provide property protection
• Building may sustain fire damage
29
NFPA 13D
• One- and two-family dwellings
• Sprinklers may be omitted from:– Bathrooms 55 ft²– Closets 24 ft²– Garages, carports, porches, attics, crawl
spaces, and combustible voids
30
NFPA 13D
• One- and two-family dwellings
• Designed to prevent or delay flashover and permit escape
• Does not provide property protection
• Building may sustain considerable damage
31
Sprinkler System Types
• Wet Pipe Systems
• Dry Pipe Systems
• Preaction Systems
• Deluge Systems
32
Wet Pipe Systems
• Most common
• Most reliable
• Water > 7 psi
• Most economical
• For areas not subject to freezing
33
Dry Pipe Systems750 gallons per dry pipe valve
• Quick opening device > 500 gallons
• Dry pipe valve in room that is heated, lighted room
34
Differential
• Ratio of air pressure to water pressure necessary to balance the dry pipe valve
• Maintaining it in the closed position
35
Dry Pipe Systems
750 gallons per dry pipe valve
• Quick opening device > 500 gallons
• Dry pipe valve in room that is heated and lighted
36
Preaction Systems
• Closed heads
• Detection devices control valve
• Activation charges system– Wet
• > 20 heads require 7 psi air for supervision
37
Deluge Systems
• Used where fire may outrun sprinkler system
• High hazard areas
• Hangars
• Loading racks
• Explosives
38
ESFR Sprinklers
• Early Suppression Fast Response– Flow rates up to 125 pm– Designed to extinguish not control– Protect rack storage up to 35 feet with
sprinklers at ceiling only
39
Standpipe Classes
• Class I– Fire department– 500 gpm for 30 minutes– 250 gpm for additional standpipes
• Class II– For use by building occupants– 100 gpm for 30 minutes
40
Standpipe Classes
• Class III– FD and building occupants
41
Types of Standpipe Systems
• Wet with constant water supply
• Dry with automatic actuation
• Dry with manual actuation
• Dry without fixed water supply
42
Standpipe Pressure Reducing Devices
• Prevent overpressure on lower floors
• Fire pumps must overcome head pressure of .434 psi per foot or 5 lbs per floor– Achieves correct pressure at topmost outlet
43
Standpipe Pressure Reducing Devices
• Pressure on lower floors is higher by about 5 lbs per floor
44
Dry Chemical Extinguishing Systems
• Designed and installed per NFPA 17
• Automatic and manual actuation
• Warning signs and alarms
• Acceptance tests
• Discharge tests
45
Wet Chemical Fire Extinguishing Systems
• Designed and installed per NFPA 17A
• Automatic and manual actuation
• Warning signs and alarms
• Acceptance tests
• Discharge tests
46
Halogenated Extinguishing Systems
• Designed and installed per NFPA 12A
• Automatic and manual actuation
• Warning signs and alarms
• Acceptance tests
47
Halogenated Extinguishing Systems
• Agent names based on chemical formula– Chlorine 1 1– Flourine 3 2– Bromine 0 1– Iodine 1 1
48
Clean Agent Fire Extinguishing Systems
• Designed and installed per code and manufacturers instructions
• Automatic and manual actuation
• Warning signs and alarms
• Acceptance tests
49
Carbon Dioxide Extinguishing Systems
• Designed and installed per NFPA 12
• Automatic and manual actuation
• Warning signs and alarms
• Acceptance tests
50
Foam Extinguishing Systems
• Designed and installed per NFPA 11, 11A, 16
• Automatic and manual actuation
• Warning signs and alarms
• Acceptance tests
51
Water Spray Fixed Systems• Designed and installed per NFPA 15
• Automatic actuation
• Acceptance tests
52
Fire Department Connections
• Required by – NFPA 13 – Standard for the Installation of
Sprinklers
– NFPA 13R – Residential Occupancies up to 4 Stories
53
Fire Department Connections
• Required for all sprinklers systems except:– Limited area systems off domestic water
supply– Systems < 20 heads
54
Fire Department ConnectionRequirements
• Connection will supply all sprinklers or all standpipes
• Street front or location approved by the FD
• 18-42” above ground, w/sign
• No obstructions
55
Fire Alarm and Detection Systems
• Notification of occupants
• Activation of fire protection systems
• NFPA 72 National Fire Alarm Code
56
Fire Alarm System Components
• Detection devices– Smoke, heat, water flow, UV flame
• Signaling or notification devices– Bells, horns, AV devices
• Control panel– System “brain”
57
Summary
• Fire protection systems are hazard-specific
• Sprinkler system standards 13, 13D, and 13R provide different levels of protection
58
Summary
• Passive fire protection features, rated and (or) noncombustible construction
• Active features, sprinklers, alarms, etc, are complimentary