CABLE TIGHT™ SYSTEM CERTIFICATIONSUse this guide to aid in securing installation permits, passing regulator inspections, or obtaining a deviation for the Cable Tight™ wire management system in your local market.
STANDARDS FOR SAFETYCable Tight™ system conduit and fittings hold the UL Certificates of Compliance per the component diagram and table below. Copies of all Certificates of Compliance can be found at the end of this document.
Standard Description System Components Certificate #
UL6 & CSA C22.2 No. 45.1-07Standards for safety of electrical rigid metal conduit - steel
Rigid ferrous metal conduit primary zinc coated
20170809-E487208
UL971Standard for safety of nonmetallic underground piping for flammable liquids
Assembly of PE coated, PE spigotted rigid metal, HDPE conduit and HDPE Electrofusion fittings
20170809-E487208
UL651AStandard for safety for Schedule 40 and 80 HDPE conduit
HDPE conduit 20170512-E487209
FIBERGLASS SUMP ENTRY
POLYETHYLENE SUMP ENTRY
3
2
1
3
2
2
2
2
2
1
2
3
1
PRODUCT DESCRIPTIONSUse the diagram above and the descriptions below to identify the system components found in the UL Certificates of Compliance. Each set is available in both 1” and ¾” diameters. Copies of all Certificates of Compliance can be found at the end of this document.
• HDPE flexible conduit (1,000’ & 1,500’ coils)
• PE coated rigid metal conduit (6’ stick)
• PE spigotted rigid metal conduit (6’ stick)
• Polyethylene sump entry seal
A • Polyethylene sump entry seal reducer
• Fiberglass sump entry seal
• Reducing coupler
• Coupler
FC
H
A
B
C
D
E
F
G
H
D E B
GA
H
ALASKAHAWAII
CALIFORNIA
OREGON
WASHINGTON
IDAHO
MONTANA
WYOMING
UTAH COLORADO
ARIZONA NEWMEXICO
TEXAS
OKLAHOMA
KANSAS
NEBRASKA
SOUTHDAKOTA
NORTH DAKOTA MINNESOTA
WISCONSINMICHIGAN
IOWA
MISSOURI
ARKANSAS
MISSISSIPPI
ALABAMA GEORGIA
LOUISIANA FLORIDA
NEVADA
SOUTHCAROLINA
WESTVIRGINIA
NORTH CAROLINATENNESSEE
KENTUCKY
OHIOILLINOIS
INDIANA
PENNSYLVANIA
MARYLANDDELAWARE
RHODE ISLANDCONNECTICUT
MASSACHUSETTS
NEW HAMPSHIREVERMONT
VIRGINIA
NEW YORK
MAINE
NEW JERSEY
2017 NEC ADOPTION COMPLETE2017 NEC ADOPTION IN PROCESS
2014 NEC ADOPTIONNO STATEWIDE NEC ADOPTION
NATIONAL ELECTRICAL CODEThe electrofusion welding technology used with the Cable Tight™ system allows you to create seamless, watertight connections between electrical conduit and containment. This eliminates buried glued and threaded joints which can lead to liquid penetration. HDPE constructed components are used in the Cable Tight™ Electrofusion welding process. Before the NEC NFPA 70 2017 revision, HDPE was not listed in hazardous (classified) locations.
Specific NEC NFPA 70 2017 updates which allow the use of HDPE conduit include:
FFS-0629 10-17
franklinfueling.com3760 Marsh Rd. • Madison, WI 53718, USATel: +1 608 838 8786 • Fax: +1 608 838 6433Tel: USA & Canada +1 800 225 9787 • Tel: UK +44 (0) 1473 243300Tel: Mex 001 800 738 7610 • Tel: CH +86 10 8565 4566 © 2017 Franklin Fueling Systems. All Rights Reserved.
Please find copies of all Certificates of Compliance on the following pages.
Is the Cable Tight™ system approved in your state? What to do next.
Use the map below to determine if your state of operation has adopted the NEC NFPA 70 2017 (green states). If it has, it may be suitable to install the Cable Tight™ system without further action. Check your local regulatory contact for guidance. For all other states, use this certification packet to obtain a deviation to allow HDPE conduit per the NEC NFPA 70 2017 revision.
• 501.10(A)(1)(a) - Class I, Division 1, Underground Wiring
• 511.8 - Commercial Garages, Underground Wiring
• 514.8 - Motor Fuel Dispensing Facilities, Underground Wiring
Subject to change. See NFPA.org for latest map.
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20170809-E487208
Report Reference E487208-20170804
Issue Date 2017-AUGUST-09
Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 1
Issued to: FRANKLIN FUELING SYSTEMS LTD
OLYMPUS CLOSE, WHITEHOUSE INDUSTRIAL ESTATE
IPSWICH, IP1 5LN UNITED KINGDOM
This is to certify that
representative samples of
RIGID FERROUS METAL CONDUIT
Steel Electrical Rigid Metal conduit, Trade sizes 3/4 and 1, 1804+/-5 mm in length.
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: UL6 and CSA S22.2 No. 45.1-07 , standard for Electrical Rigid
Metal Conduit – steel
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20170809-E487208
Report Reference E487208-20170806
Issue Date 2017-AUGUST-09
Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 2
Issued to: FRANKLIN FUELING SYSTEMS LTD
OLYMPUS CLOSE, WHITEHOUSE INDUSTRIAL ESTATE
IPSWICH, IP1 5LN UNITED KINGDOM
This is to certify that
representative samples of
RIGID FERROUS METAL CONDUIT, PRIMARY ZINC COATED, WITH
OR WITHOUT SUPPLEMENTARY PE COATING, VERIFIED FOR
ADHESION PERFORMANCE AND/OR FACTORY-MOLDED-ON
HDPE FITTINGS AND/OR SPIGOTS VERIFIED FOR SECUREMENT
PERFORMANCE
See addendum page
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: UL6, standard for Electrical Rigid Metal Conduit – steel
UL 971, Standard for Safety for Nonmetallic Underground Piping
For Flammable Liquids
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20170809-E487208
Report Reference E487208-20170806
Issue Date 2017-AUGUST-09
Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 2 of 2
Electrical rigid metal conduit, primary zinc coated, with supplementary LDPE coating, Verified for adhesion performance, trade sizes ¾ and 1 1804 +/-5 mm maximum length, threaded on one end, no coupling provided.
Electrical rigid metal conduit, primary zinc coated, with supplementary HDPE coating, Verified for securement performance, trade sizes ¾ and 1 1804 +/-5 mm maximum length, threaded on one end, no coupling provided. Electrical rigid metal conduit, primary zinc coated, with factory-molded-on HDPE spigot Verified for securement performance, trade sizes ¾ and 1., 1850 +/-5 mm maximum length. Electrical rigid metal conduit, primary zinc coated, with supplementary HDPE coating, Verified for securement performance, trade sizes ¾ and 1, with factory-molded-on HDPE spigot Verified for securement performance. , 1850 +/-5 mm maximum length. Electrical rigid metal conduit, primary zinc coated, with supplementary LDPE coating, Verified for adhesion performance, trade sizes ¾ and 1, with factory-molded-on HDPE spigot Verified for securement performance. , 1850 +/-5 mm maximum length.
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20170809-E487208
Report Reference E487208-20170805
Issue Date 2017-AUGUST-09
Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 1
Issued to: FRANKLIN FUELING SYSTEMS LTD
OLYMPUS CLOSE, WHITEHOUSE INDUSTRIAL ESTATE
IPSWICH, IP1 5LN UNITED KINGDOM
This is to certify that
representative samples of
RIGID FERROUS METAL CONDUIT, PRIMARY ZINC COATED, WITH
OR WITHOUT SUPPLEMENTARY PE COATING, VERIFIED FOR
ADHESION PERFORMANCE AND/OR FACTORY-MOLDED-ON
HDPE FITTINGS AND/OR SPIGOTS VERIFIED FOR SECUREMENT
PERFORMANCE
Electrofused couplings Verified for Securement Performance, Cat No.
02-027 and 02-033.
Electrofused Reducer Verified for Securement Performances, Cat Nos.
49-031-027, 49-038-033, 49-063-031, and 49-063-038
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety: UL 971, Standard for Safety for Nonmetallic Underground Piping
For Flammable Liquids
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.
C E R T I F I C A T E O F C O M P L I A N C E
Certificate Number 20170512-E487209 Report Reference E487209-20170512
Issue Date 2017-MAY-12
Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 1
Issued to: FRANKLIN FUELING SYSTEMS LTD
OLYMPUS CLOSE WHITEHOUSE INDUSTRIAL ESTATE IPSWICH IP1 5LN UNITED KINGDOM
This is to certify that
representative samples of
Rigid Nonmetallic High-Density-Polyethylene Underground Conduit
Continuous length HDPE conduit, Schedule 40 3/4 and 1 trade sizes.
Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate.
Standard(s) for Safety: Standard for Safety for Schedule 40 and 80 High Density Polyethylene (HDPE) Conduit UL651A
Additional Information: See the UL Online Certifications Directory at www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's Certification and Follow-Up Service. Look for the UL Certification Mark on the product.