CERTIFICATE OF COMPLIANCE Certificate Number 20130813 E10848 Report Reference E10848, 2006 January 16 Issue Date 2013 August 13 William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.com/contactus Page 1 of 1 Issued to: Siemens Industry, Inc. 5400 Triangle Parkway NW Norcross, GA 30092 USA This is to certify that representative samples of Molded-Case Circuit Breakers LG Frame, Types NLGB, HLGB and LLGB. These are two and three pole circuit breakers with non-interchangeable thermal magnetic and electronic trip units. They are uncompensated 40 o C construction rated 400-600 A, 600 V ac, 250 V dc (two pole) and 500 V dc (three pole for ungrounded UPS systems). Circuit breakers with electronic trip units are not marked with dc ratings. Circuit breakers, rated 400-500A, may be marked for 100% continuous current. These breakers may be marked “HACR Type”. Current interrupting ratings are as follows: Voltage Poles Ratings Type NLGB Type HLGB Type LLGB 240 ac, 50/60 Hz 2,3 65 kA 100 kA 200 kA 480 ac, 50/60 Hz 2,3 35 kA 65 kA 100 kA 600 ac. 50/60 Hz 2,3 18 kA 18 kA 18 kA 250 dc 2 30 kA 30 kA 30 kA 500 dc 3 25 kA 35 kA 35 kA Have been investigated by UL in accordance with the Standard(s) indicated on this Certificate. Standard(s) for Safety: ANSI/UL 489, Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures. Additional Information: See the UL Online Certifications Directory at www.ul.com/database for additional information Only those products bearing the UL Listing Mark should be considered as being covered by UL's Listing and Follow-Up Service. The UL Listing Mark generally includes the following elements: the symbol UL in a circle: with the word “LISTED”; a control number (may be alphanumeric) assigned by UL; and the product category name (product identifier) as indicated in the appropriate UL Directory. Look for the UL Listing Mark on the product. .

Transcript of CERTIFICATE OF COMPLIANCE - SiemensCertificate Number 20130813 ... Issued to: Siemens Industry, Inc....

Page 1: CERTIFICATE OF COMPLIANCE - SiemensCertificate Number 20130813 ... Issued to: Siemens Industry, Inc. 5400 Triangle Parkway NW Norcross, GA 30092 USA ... covered by UL's Recognition

C E R T I F I C A T E O F C O M P L I A N C E

Certificate Number 20130813 – E10848

Report Reference E10848, 2006 January 16

Issue Date 2013 August 13

William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.com/contactus

Page 1 of 1

Issued to: Siemens Industry, Inc.

5400 Triangle Parkway NW

Norcross, GA 30092 USA

This is to certify that

representative samples of

Molded-Case Circuit Breakers

LG Frame, Types NLGB, HLGB and LLGB.

These are two and three pole circuit breakers with non-interchangeable thermal magnetic and electronic trip units. They are uncompensated 40

oC construction rated 400-600 A,

600 V ac, 250 V dc (two pole) and 500 V dc (three pole for ungrounded UPS systems). Circuit breakers with electronic trip units are not marked with dc ratings. Circuit breakers, rated 400-500A, may be marked for 100% continuous current. These breakers may be marked “HACR Type”.

Current interrupting ratings are as follows:

Voltage Poles Ratings

Type NLGB Type HLGB Type LLGB

240 ac, 50/60 Hz 2,3 65 kA 100 kA 200 kA

480 ac, 50/60 Hz 2,3 35 kA 65 kA 100 kA

600 ac. 50/60 Hz 2,3 18 kA 18 kA 18 kA

250 dc 2 30 kA 30 kA 30 kA

500 dc 3 25 kA 35 kA 35 kA

Have been investigated by UL in accordance with the

Standard(s) indicated on this Certificate.

Standard(s) for Safety: ANSI/UL 489, Molded-Case Circuit Breakers, Molded-Case Switches and

Circuit-Breaker Enclosures.

Additional Information: See the UL Online Certifications Directory at

www.ul.com/database for additional information

Only those products bearing the UL Listing Mark should be considered as being covered by UL's Listing and Follow-Up Service.

The UL Listing Mark generally includes the following elements: the symbol UL in a circle: with the word “LISTED”; a control number (may be alphanumeric) assigned by UL; and the product category name (product identifier) as indicated in the appropriate UL Directory. Look for the UL Listing Mark on the product. .

Page 2: CERTIFICATE OF COMPLIANCE - SiemensCertificate Number 20130813 ... Issued to: Siemens Industry, Inc. 5400 Triangle Parkway NW Norcross, GA 30092 USA ... covered by UL's Recognition

C E R T I F I C A T E O F C O M P L I A N C E

Certificate Number 20130813 – E10848

Report Reference E10848, 2006 February 20

Issue Date 2013 August 13

William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.com/contactus

Page 1 of 1

Issued to: Siemens Industry, Inc.

5400 Triangle Parkway NW

Norcross, GA 30092 USA

This is to certify that

representative samples of

Circuit Breakers, Adjustable Instantaneous Trip Type - Component

LG Frame, Type HLMB.

Three pole, rated 600A, 600 V ac, 250 V dc

Have been investigated by UL in accordance with the

Standard(s) indicated on this Certificate.

Standard(s) for Safety: ANSI/UL 489, Molded-Case Circuit Breakers, Molded-Case Switches and

Circuit-Breaker Enclosures

Additional Information: See the UL Online Certifications Directory at

www.ul.com/database for additional information

Only those products bearing the UL Recognized Component Mark should be considered as being covered by UL's Recognition and Follow-Up Service.

The UL Recognized Component Mark generally consists of the manufacturer’s identification and catalog number, model number or other product designation as specified under “Marking” for the particular Recognition as published in the appropriate UL Directory. As a supplementary means of identifying products that have been produced under UL’s Component Recognition Program, UL’s Recognized Component Mark: , may be used in conjunction with the required Recognized Marks. The Recognized Component Mark is required when specified in the UL Directory preceding the recognitions or under “Markings” for the individual recognitions.

The final acceptance of the component is dependent upon its installation and use in complete equipment submitted to UL LLC. Look for the UL Recognized Component Mark on the product.

Page 3: CERTIFICATE OF COMPLIANCE - SiemensCertificate Number 20130813 ... Issued to: Siemens Industry, Inc. 5400 Triangle Parkway NW Norcross, GA 30092 USA ... covered by UL's Recognition

C E R T I F I C A T E O F C O M P L I A N C E

Certificate Number 20130813 – E68312

Report Reference E68312, 2006 February 17

Issue Date 2013 August 13

William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.com/contactus

Page 1 of 1

Issued to: Siemens Industry, Inc.

5400 Triangle Parkway NW

Norcross, GA 30092 USA

This is to certify that

representative samples of

Molded Case Switch

LG Frame, Type HLGB and LLGB.

Two and Three pole, rated 600A, 600V ac, 250 V dc.

Does not provide overcurrent protection. This switch is suitable for use on a circuit capable of delivering not more than:

Voltage Max RMS Symm. Amp

Type HLGB Type LLGB

240 ac, 50/60 Hz 100 kA 200 kA

480 ac, 50/60 Hz 65 kA 100 kA

600 ac. 50/60 Hz 18 kA 18 kA

250 dc 30 kA 30 kA

When protected by a fuse or circuit breaker, rated 600A maximum.

May open circuit above 6500 A.

Have been investigated by UL in accordance with the

Standard(s) indicated on this Certificate.

Standard(s) for Safety: ANSI/UL 489, Molded-Case Circuit Breakers, Molded-Case Switches and

Circuit-Breaker Enclosures.

Additional Information: See the UL Online Certifications Directory at

www.ul.com/database for additional information

Only those products bearing the UL Listing Mark should be considered as being covered by UL's Listing and Follow-Up Service.

The UL Listing Mark generally includes the following elements: the symbol UL in a circle: with the word “LISTED”; a control number (may be alphanumeric) assigned by UL; and the product category name (product identifier) as indicated in the appropriate UL Directory. Look for the UL Listing Mark on the product.

Page 4: CERTIFICATE OF COMPLIANCE - SiemensCertificate Number 20130813 ... Issued to: Siemens Industry, Inc. 5400 Triangle Parkway NW Norcross, GA 30092 USA ... covered by UL's Recognition

C E R T I F I C A T E O F C O M P L I A N C E

Certificate Number 20130813 – E10848

Report Reference E10848, 2006 January 16

Issue Date 2013 August 13

William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.com/contactus

Page 1 of 1

Issued to: Siemens Industry, Inc.

5400 Triangle Parkway NW

Norcross, GA 30092 USA

This is to certify that

representative samples of

Molded-Case Circuit Breakers

LG Frame, Types HLGC.

These are two and three pole circuit breakers with non-interchangeable thermal magnetic trip units. They are uncompensated 40

° C construction rated 400-600 A, 600 V ac. These

circuit breakers may be marked “HACR Type”. These circuit breakers, rated 400-500A, may be marked for 100% continuous current.

Current interrupting ratings are as follows:

Voltage Poles Ratings

Type HLGC

600 ac. 50/60 Hz 2,3 25 kA

Have been investigated by UL in accordance with the

Standard(s) indicated on this Certificate.

Standard(s) for Safety: ANSI/UL 489, Molded-Case Circuit Breakers, Molded-Case Switches and

Circuit-Breaker Enclosures.

Additional Information: See the UL Online Certifications Directory at

www.ul.com/database for additional information

Only those products bearing the UL Listing Mark should be considered as being covered by UL's Listing and Follow-Up Service.

The UL Listing Mark generally includes the following elements: the symbol UL in a circle: with the word “LISTED”; a control number (may be alphanumeric) assigned by UL; and the product category name (product identifier) as indicated in the appropriate UL Directory. Look for the UL Listing Mark on the product. .

Page 5: CERTIFICATE OF COMPLIANCE - SiemensCertificate Number 20130813 ... Issued to: Siemens Industry, Inc. 5400 Triangle Parkway NW Norcross, GA 30092 USA ... covered by UL's Recognition

C E R T I F I C A T E O F C O M P L I A N C E

Certificate Number 20130813 – E10848

Report Reference E10848, 2006 January 16

Issue Date 2013 August 13

William R. Carney, Director, North American Certification Programs UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at www.ul.com/contactus

Page 1 of 1

Issued to: Siemens Industry, Inc.

5400 Triangle Parkway NW

Norcross, GA 30092 USA

This is to certify that

representative samples of

Molded-Case Circuit Breakers

LG Frame, Type HLGD.

These are complete three pole circuit breakers with thermal magnetic trip units. They are uncompensated 40

oC construction rated 400-600 A, 600 V dc. These circuit breakers may

be marked “HACR Type”.

Current interrupting ratings are as follows

65 kA, 600 Vdc

Have been investigated by UL in accordance with the

Standard(s) indicated on this Certificate.

Standard(s) for Safety: ANSI/UL 489, Molded-Case Circuit Breakers, Molded-Case Switches and

Circuit-Breaker Enclosures and CAN/CSA-C22.2 No. 5, Molded-Case

Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures

Additional Information: See the UL Online Certifications Directory at

www.ul.com/database for additional information

Only those products bearing the UL Listing Mark for the US and Canada should be considered as being covered by UL's Listing and Follow-Up Service meeting the appropriate requirements for US and Canada. The UL Listing Mark for the US and Canada generally includes: the UL in a circle symbol with “C” and

“US” identifiers: the word “LISTED”; a control number (may be alphanumeric) assigned by UL; and the product category name (product identifier) as indicated in the appropriate UL Directory. Look for the UL Listing Mark on the product.