CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings...

37
CERTIFICATE OF APPROVAL No CF 456 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of PPG Coatings Europe BV Oceanenweg 2, 1047 BB Amsterdam, The Netherlands Tel: + 31 (0) 204075050 Fax: +31 (0) 204075059 Tel: + 44 (0) 1773 837300 Fax: + 44 (0) 1773 837303 Have been assessed against the requirements of the Technical Schedule(s) denoted below and are approved for use subject to the conditions appended hereto: ______________________________________________________________________________ CERTIFIED PRODUCT TECHNICAL SCHEDULE Steelguard FM 550, TS15 Intumescent Coatings FM 549 and FM 560 for Steelwork Signed and sealed for and on behalf of CERTIFIRE Sir Ken Knight Issued: 30 th May 2006 Chairman - Management Council Reissued: 3 rd June 2011 Valid to: 2 nd June 2016 Page 1 of 37

Transcript of CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings...

Page 1: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

CERTIFICATE OF APPROVAL No CF 456

This is to certify that, in accordance with

TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of

PPG Coatings Europe BV

Oceanenweg 2, 1047 BB Amsterdam, The Netherlands Tel: + 31 (0) 204075050 Fax: +31 (0) 204075059

Tel: + 44 (0) 1773 837300 Fax: + 44 (0) 1773 837303

Have been assessed against the requirements of the Technical Schedule(s) denoted below and are approved for use subject to the conditions

appended hereto:

______________________________________________________________________________

CERTIFIED PRODUCT TECHNICAL SCHEDULE

Steelguard FM 550, TS15 Intumescent Coatings FM 549 and FM 560 for Steelwork

Signed and sealed for and on behalf of CERTIFIRE

Sir Ken Knight Issued: 30th May 2006 Chairman - Management Council Reissued: 3rd June 2011

Valid to: 2nd June 2016 Page 1 of 37

Page 2: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 2 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use of STEELGUARD FM 550, FM 549 and FM 560 for the

fire protection of I-shaped, circular hollow and rectangular hollow steel sections. The precise scope is given in Tables 1 to 10 which show the total dry film thickness of STEELGUARD FM 550, FM 549 and FM 560 (excluding primer and top sealer) required to provide fire resistance periods in accordance with BS476: Part 21: 1987. The scope includes periods of fire resistance of between 15 and 120 minutes for differing sections and section factors (A/V).

2. This certification is designed to demonstrate compliance of the product or system

specifically with Approved Document B (England and Wales), Section 2 of the Technical Standards (Scotland), Technical Booklet E (N. Ireland). If compliance is required to other regulatory or guidance documents there may be additional considerations or conflict to be taken into account.’

3. The products are approved on the basis of: i) Initial type testing. ii) A design appraisal against TS15. iii) Certification of quality management system to ISO 9001: 2008.

iv) Inspection and surveillance of factory production control v) Audit testing

4. The data referring to three-sided fire exposure of beams relate to beams supporting

concrete floor slabs. Separate consideration is required where this is not the case. 5. The data shown are applicable to steel sections blast cleaned to ISO 8501-1 Sa2½ or

equivalent and primed with a suitable and compatible primer. Specifications of surface preparations, primers and top sealers is available from PPG INDUSTRIES BV whose responsibility is to ensure that STEELGUARD FM 550, FM 549 and FM 560 is compatible for use in respect of both ambient and fire conditions. The total dry film thickness of primer should be nominally 0.05mm, with a maximum of 0.15mm.

6. The data shown is applicable to STEELGUARD FM 550, FM 549 and FM 560 applied by

spray to horizontal, vertical, flexural and compression members supporting loads up to the maximum design loads specified in BS449: Part 2.

7. The approval relates to on going production. Product and/or its immediate packaging is

identified with the manufacturers’ name, the product name or number, the CERTIFIRE name or name and mark, together with the CERTIFIRE certificate number and application where appropriate.

Page 3: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 3 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 1

Three Sided Protection to I-Section Beams : 375oC : Steelguard FM 550, FM 549 & FM 560

30 minutes 60 minutes

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

85 0.297 205 1.150 30 1.059 90 0.314 210 1.218 35 1.186 95 0.338 215 1.286 40 1.313

100 0.361 220 1.355 45 1.439 105 0.385 225 1.423 50 1.566 110 0.408 230 1.465 55 1.692 115 0.432 235 1.489 60 1.819 120 0.455 240 1.514 65 1.946 125 0.479 245 1.538 70 2.072 130 0.502 250 1.563 75 2.199 135 0.526 255 1.588 80 2.325 140 0.549 260 1.612 85 2.452 145 0.573 265 1.637 90 2.578 150 0.596 270 1.661 155 0.620 275 1.686 160 0.644 280 1.710 165 0.667 285 1.735 170 0.691 290 1.760 175 0.741 295 1.784 180 0.809 300 1.809 185 0.877 305 1.833 190 0.945 310 1.858 195 1.014 315 1.882 200 1.082 320 1.907

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 4: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 4 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 2

Three Sided Protection to I-Section Beams : 400oC : Steelguard FM 550, FM 549 & FM 560

30 minutes 60 minutes

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

90 0.297 210 0.719 30 0.684 95 0.300 215 0.767 35 0.743

100 0.318 220 0.814 40 0.802 105 0.335 225 0.862 45 0.861 110 0.353 230 0.910 50 0.919 115 0.371 235 0.957 55 0.978 120 0.388 240 1.005 60 1.037 125 0.406 245 1.052 65 1.096 130 0.424 250 1.100 70 1.155 135 0.450 255 1.235 75 1.214 140 0.459 260 1.369 80 1.273 145 0.477 265 1.457 85 1.332 150 0.495 270 1.475 90 1.391 155 0.512 275 1.493 95 1.450 160 0.530 280 1.511 100 1.592 165 0.548 285 1.529 105 1.733 170 0.565 290 1.547 110 1.875 175 0.583 295 1.565 115 2.017 180 0.601 300 1.583 120 2.158 185 0.619 305 1.601 125 2.300 190 0.636 310 1.619 130 2.442 195 0.654 315 1.636 135 2.583 200 0.672 320 1.654 205 0.689

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 5: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 5 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 3

Three Sided Protection to I-Section Beams : 450oC : Steelguard FM 550, FM 549 & FM 560

30 minutes 60 minutes

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

110 0.297 220 0.591 30 0.579 150 1.589 115 0.325 225 0.599 35 0.620 155 1.635 120 0.356 230 0.607 40 0.662 160 1.681 125 0.388 235 0.616 45 0.703 165 1.727 130 0.419 240 0.624 50 0.745 170 1.773 135 0.445 245 0.632 55 0.786 175 1.820 140 0.458 250 0.640 60 0.828 180 1.866 145 0.467 255 0.649 65 0.869 185 1.912 150 0.475 260 0.657 70 0.911 190 1.958 155 0.483 265 0.665 75 0.952 195 2.004 160 0.491 270 0.674 80 0.994 200 2.051 165 0.500 275 0.682 85 1.035 205 2.097 170 0.508 280 0.690 90 1.077 210 2.143 175 0.516 285 0.698 95 1.118 215 2.189 180 0.525 290 0.734 100 1.160 220 2.235 185 0.533 295 0.777 105 1.201 225 2.282 190 0.541 300 0.819 110 1.243 230 2.328 195 0.549 305 0.862 115 1.284 235 2.374 200 0.558 310 0.904 120 1.326 240 2.420 205 0.566 315 0.947 125 1.367 245 2.466 210 0.574 320 0.989 130 1.409 250 2.513 215 0.582 135 1.450 255 2.559

140 1.496 260 2.605 145 1.542

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 6: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 6 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 3 Continued

Three Sided Protection to I-Section Beams : 450oC :

Steelguard FM 550, FM 549 & FM 560

90 minutes

Section factor m-1

Thickness mm

Up to 25 0.840 30 0.905 35 0.969 40 1.034 45 1.099 50 1.164 55 1.229 60 1.294 65 1.359 70 1.424 75 1.489 80 1.554 85 1.619 90 1.684

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 7: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 7 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 4

Three Sided Protection to I-Section Beams : 475oC : Steelguard FM 550, FM 549 & FM 560

30 minutes 60 minutes

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

115 0.297 220 0.535 30 0.551 175 1.620 120 0.306 225 0.543 35 0.588 180 1.657 125 0.321 230 0.551 40 0.625 185 1.694 130 0.337 235 0.559 45 0.662 190 1.731 135 0.352 240 0.567 50 0.698 195 1.768 140 0.367 245 0.575 55 0.735 200 1.805 145 0.383 250 0.583 60 0.772 205 1.842 150 0.398 255 0.591 65 0.809 210 1.879 155 0.413 260 0.599 70 0.846 215 1.916 160 0.429 265 0.607 75 0.883 220 1.953 165 0.444 270 0.615 80 0.919 225 1.990 170 0.455 275 0.623 85 0.956 230 2.027 175 0.463 280 0.631 90 0.993 235 2.063 180 0.471 285 0.639 95 1.030 240 2.100 185 0.479 290 0.647 100 1.067 245 2.137 190 0.487 295 0.655 105 1.104 250 2.174 195 0.495 300 0.663 110 1.141 255 2.211 200 0.503 305 0.671 115 1.177 260 2.248 205 0.511 310 0.679 120 1.214 265 2.285 210 0.519 315 0.687 125 1.251 270 2.322 215 0.527 320 0.695 130 1.288 275 2.359

135 1.325 280 2.396 140 1.362 285 2.433 145 1.398 290 2.470 150 1.435 295 2.507 155 1.472 300 2.544 160 1.509 305 2.581 165 1.546 310 2.618 170 1.583

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 8: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 8 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 4 Continued

Three Sided Protection to I-Section Beams : 475oC :

Steelguard FM 550, FM 549 & FM 560

90 minutes

Section factor m-1

Thickness mm

Up to 30 0.716 35 0.781 40 0.845 45 0.909 50 0.974 55 1.038 60 1.102 65 1.167 70 1.231 75 1.296 80 1.360 85 1.424 90 1.489 95 1.553

100 1.617 105 1.682

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 9: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 9 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 5

Three Sided Protection to I-Section Beams : 500oC : Steelguard FM 550, FM 549 & FM 560

30 minutes 60 minutes

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

125 0.297 225 0.420 60 0.297 195 1.613 130 0.304 230 0.426 65 0.322 200 1.642 135 0.310 235 0.432 70 0.377 205 1.671 140 0.316 240 0.438 75 0.433 210 1.700 145 0.322 245 0.444 80 0.488 215 1.729 150 0.328 250 0.450 85 0.543 220 1.759 155 0.334 255 0.463 90 0.599 225 1.788 160 0.340 260 0.476 95 0.654 230 1.817 165 0.346 265 0.489 100 0.709 235 1.846 170 0.352 270 0.503 105 0.764 240 1.875 175 0.359 275 0.516 110 0.820 245 1.904 180 0.365 280 0.529 115 0.875 250 1.933 185 0.371 285 0.542 120 0.930 255 1.962 190 0.377 290 0.555 125 0.986 260 1.991 195 0.383 295 0.568 130 1.041 265 2.021 200 0.389 300 0.582 135 1.096 270 2.050 205 0.395 305 0.595 140 1.151 275 2.079 210 0.401 310 0.608 145 1.207 280 2.108 215 0.407 315 0.621 150 1.262 285 2.137 220 0.413 320 0.634 155 1.317 290 2.166

160 1.373 295 2.195 165 1.428 300 2.224 170 1.467 305 2.253 175 1.497 310 2.283 180 1.526 315 2.312 185 1.555 320 2.341 190 1.584

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 10: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 10 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 5 Continued

Three Sided Protection to I-Section Beams : 500oC : Steelguard FM 550, FM 549 & FM 560

90 minutes

Section factor

up to m-1

Thickness mm

30 0.684 35 0.743 40 0.802 45 0.861 50 0.919 55 0.978 60 1.037 65 1.096 70 1.155 75 1.214 80 1.273 85 1.332 90 1.391 95 1.450 100 1.509 105 1.568 110 1.627

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 11: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 11 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 6

Three Sided Protection to I-Section Beams : 525oC : Steelguard FM 550, FM 549 & FM 560

30 minutes 60 minutes Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

135 0.297 230 0.394 65 0.297 195 1.526 140 0.303 235 0.399 70 0.330 200 1.555 145 0.308 240 0.404 75 0.380 205 1.584 150 0.313 245 0.409 80 0.430 210 1.613 155 0.318 250 0.414 85 0.480 215 1.642 160 0.323 255 0.419 90 0.530 220 1.671 165 0.328 260 0.424 95 0.580 225 1.700 170 0.333 265 0.429 100 0.630 230 1.729 175 0.338 270 0.434 105 0.680 235 1.759 180 0.343 275 0.439 110 0.730 240 1.788 185 0.348 280 0.444 115 0.780 245 1.817 190 0.353 285 0.449 120 0.830 250 1.846 195 0.358 290 0.459 125 0.880 255 1.875 200 0.363 295 0.470 130 0.930 260 1.904 205 0.368 300 0.481 135 0.980 265 1.933 210 0.373 305 0.492 140 1.030 270 1.962 215 0.379 310 0.503 145 1.080 275 1.991 220 0.384 315 0.514 150 1.130 280 2.021 225 0.389 320 0.525 155 1.180 285 2.050

160 1.230 290 2.079 165 1.280 295 2.108 170 1.330 300 2.137 175 1.380 305 2.166 180 1.430 310 2.195 185 1.467 315 2.224 190 1.497 320 2.253

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 12: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 12 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 6 Continued

Three Sided Protection to I-Section Beams : 525oC : Steelguard FM 550, FM 549 & FM 560

90 minutes 120 minutes Section factor

up to m-1

Thickness mm

Section factor

up to m-1

Thickness mm

30 0.647 30 0.778 35 0.700 35 0.853 40 0.753 40 0.927 45 0.805 45 1.002 50 0.858 50 1.077 55 0.911 55 1.151 60 0.964 60 1.226 65 1.017 65 1.301 70 1.070 70 1.375 75 1.122 75 1.450 80 1.175 80 1.525 85 1.228 85 1.599

90 1.281 95 1.334 100 1.387 105 1.439 110 1.605 115 1.798 120 1.991 125 2.184 130 2.377 135 2.570

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 13: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 13 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 7

Three Sided Protection to I-Section Beams : 550oC : Steelguard FM 550, FM 549 & FM 560

30 minutes 60 minutes Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 210 0.25 Up to 65 0.297 195 1.18 215 0.28 70 0.33 200 1.20 220 0.30 75 0.38 205 1.25 230 0.30 80 0.43 210 1.30 235 0.30 85 0.48 215 1.35 240 0.30 90 0.53 220 1.40 245 0.33 95 0.58 225 1.43 250 0.35 100 0.60 230 1.45 255 0.35 105 0.63 235 1.53 260 0.35 110 0.65 240 1.60 265 0.35 115 0.65 245 1.65 270 0.35 120 0.65 250 1.70 275 0.35 125 0.68 255 1.73 280 0.35 130 0.70 260 1.75 285 0.38 135 0.73 265 1.78 290 0.40 140 0.75 270 1.80 295 0.40 145 0.78 275 1.80 300 0.40 150 0.80 280 1.80 305 0.40 155 0.85 285 1.83 310 0.40 160 0.90 290 1.85 315 0.40 165 0.93 295 1.88 320 0.40 170 0.95 300 1.90

175 1.00 305 1.93 180 1.05 310 1.95 185 1.10 315 1.98 190 1.15 320 2.00

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 14: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 14 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 7 Continued

Three Sided Protection to I-Section Beams : 550oC : Steelguard FM 550, FM 549 & FM 560

90 minutes 100 minutes 120 minutes Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Up to 40 0.50 160 2.55 Up to 80 1.22 Up to 30 0.778 45 0.58 165 2.63 85 1.26 35 0.853 50 0.65 170 2.70 90 1.41 40 0.927 55 0.73 175 2.78 95 1.55 45 1.002 60 0.80 180 2.85 100 1.70 50 1.077 65 0.85 185 2.90 105 1.80 55 1.151 70 0.90 190 2.95 110 1.90 60 1.226 75 0.98 195 2.98 115 2.00 65 1.301 80 1.05 200 3.00 120 2.10 70 1.375 85 1.13 205 3.05 125 2.20 75 1.450 90 1.20 210 3.10 130 2.30 80 1.525 95 1.28 215 3.13 135 2.37 85 1.599

100 1.35 220 3.15 140 2.44 90 2.000 105 1.40 225 3.18 145 2.51 95 2.070 110 1.45 230 3.20 150 2.59 100 2.150 115 1.53 235 3.23 105 2.220 120 1.60 240 3.25 110 2.300 125 1.68 245 3.30 115 2.380 130 1.75 250 3.35 120 2.450 135 1.90 255 3.38 125 2.530 140 2.05 260 3.40 145 2.18 265 3.43 150 2.30 270 3.45 155 2.43 275 3.50

280 3.55 Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 15: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 15 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 8

Four Sided Protection to I-Section Columns : 550oC : Steelguard FM 550, FM 549 & FM 560

15 minutes 30 minutes 45 minutes Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.25 Up to 40 0.35 50 0.25 50 0.25 50 0.38 60 0.25 60 0.25 60 0.38 70 0.25 70 0.25 70 0.41 80 0.25 80 0.25 80 0.45 90 0.25 90 0.25 90 0.45

100 0.25 100 0.25 100 0.48 110 0.25 110 0.25 110 0.51 120 0.25 120 0.25 120 0.51 130 0.25 130 0.25 130 0.54 140 0.25 140 0.25 140 0.58 150 0.25 150 0.25 150 0.61 160 0.25 160 0.25 160 0.67 170 0.25 170 0.25 170 0.71 180 0.25 180 0.25 180 0.77 190 0.25 190 0.25 190 0.84 200 0.25 200 0.25 200 0.87 210 0.25 210 0.25 210 0.93 220 0.25 220 0.30 220 1.02 230 0.25 230 0.30 230 1.05 240 0.25 240 0.30 240 1.15 250 0.25 250 0.35 250 1.23 260 0.25 260 0.35 260 1.26 270 0.25 270 0.35 270 1.29 280 0.25 280 0.35 280 1.29 290 0.25 290 0.40 290 1.34 300 0.25 300 0.40 300 1.38 310 0.25 310 0.40 310 1.41 320 0.25 320 0.40 320 1.44

Coating thickness refers to intumescent only Table also applies to beams with 4 sided protection and to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 16: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 16 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 8 Continued

Four Sided Protection to I-Section Columns : 550oC : Steelguard FM 550, FM 549 & FM 560

60 minutes 90 minutes Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.40 325 3.05 Up to 40 0.50 50 0.45 330 3.07 50 0.65 60 0.45 335 3.08 60 0.80 70 0.50 340 3.09 70 0.90 80 0.55 345 3.10 80 1.05 90 0.55 350 3.11 90 1.20

100 0.60 355 3.13 100 1.35 110 0.65 360 3.14 110 1.45 120 0.65 365 3.15 120 1.60 130 0.70 370 3.16 130 1.75 140 0.75 375 3.17 140 2.05 150 0.80 380 3.18 150 2.30 160 0.90 385 3.19 160 2.55 170 0.95 390 3.20 170 2.70 180 1.05 395 3.21 180 2.85 190 1.15 400 3.22 190 2.95 200 1.20 200 3.00 210 1.30 210 3.10 220 1.40 220 3.15 230 1.45 230 3.20 240 1.60 240 3.25 250 1.70 250 3.35 260 1.75 260 3.40 270 1.80 270 3.45 280 1.80 280 3.55 290 1.85 300 1.90 310 1.95 320 2.00

Coating thickness refers to intumescent only Table also applies to beams with 4 sided protection and to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 17: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 17 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 8 Continued

Four Sided Protection to I-Section Columns : 550oC : Steelguard FM 550, FM 549 & FM 560

100 minutes 120 minutes Section factor

m-1 Thickness

mm Section factor

m-1 Thickness

mm Up to 80 1.22 Up to 70 1.71

85 1.26 75 1.77 90 1.41 80 1.85 95 1.55 85 1.92

100 1.70 90 2.00 105 1.80 95 2.07 110 1.90 100 2.15 115 2.00 105 2.22 120 2.10 110 2.30 125 2.20 115 2.38 130 2.30 120 2.45 135 2.37 125 2.53 140 2.44 130 2.60 145 2.51 135 2.68 150 2.59 140 2.75 155 2.66 145 2.80 160 2.73 150 2.91 165 2.80 170 2.87 175 2.94

Coating thickness refers to intumescent only Table also applies to beams with 4 sided protection and to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 18: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 18 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 9

Three Sided Protection to I-Section Beams : 620oC : Steelguard FM 550, FM 549 & FM 560

15 minutes 30 minutes 45 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.25 Up to 40 0.25 50 0.25 50 0.25 50 0.25 60 0.25 60 0.25 60 0.25 70 0.25 70 0.25 70 0.28 80 0.25 80 0.25 80 0.28 90 0.25 90 0.25 90 0.32

100 0.25 100 0.25 100 0.32 110 0.25 110 0.25 110 0.35 120 0.25 120 0.25 120 0.38 130 0.25 130 0.25 130 0.38 140 0.25 140 0.25 140 0.41 150 0.25 150 0.25 150 0.41 160 0.25 160 0.25 160 0.45 170 0.25 170 0.25 170 0.45 180 0.25 180 0.25 180 0.50 190 0.25 190 0.25 190 0.50 200 0.25 200 0.25 200 0.53 210 0.25 210 0.25 210 0.56 220 0.25 220 0.30 220 0.59 230 0.25 230 0.30 230 0.68 240 0.25 240 0.30 240 0.71 250 0.25 250 0.35 250 0.77 260 0.25 260 0.35 260 0.84 270 0.25 270 0.35 270 0.87 280 0.25 280 0.35 280 0.94 290 0.25 290 0.35 290 0.97 300 0.25 300 0.35 300 1.03 310 0.25 310 0.40 310 1.12 320 0.25 320 0.40 320 1.18

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 19: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 19 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 9 Continued

Three Sided Protection to I-Section Beams : 620oC : Steelguard FM 550, FM 549 & FM 560

60 minutes 70 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 325 1.62 Up to 40 0.25 50 0.25 330 1.73 50 0.25 60 0.25 335 1.78 60 0.25 70 0.30 340 1.83 70 0.30 80 0.30 345 1.88 80 0.30 90 0.35 350 1.93 90 0.35

100 0.35 355 1.98 100 0.40 110 0.40 360 2.03 110 0.45 120 0.45 365 2.09 120 0.45 130 0.45 370 2.14 130 0.50 140 0.50 375 2.19 140 0.55 150 0.50 380 2.24 150 0.60 160 0.55 385 2.30 160 0.65 170 0.55 390 2.34 170 0.65 180 0.60 395 2.39 180 0.75 190 0.60 400 2.44 190 0.85 200 0.65 200 1.00 210 0.70 210 1.15 220 0.75 220 1.30 230 0.85 230 1.40 240 0.90 240 1.55 250 1.00 250 1.60 260 1.10 260 1.70 270 1.15 270 1.80 280 1.25 280 1.90 290 1.30 290 1.95 300 1.40 300 2.05 310 1.50 310 2.15 320 1.60 320 2.25

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 20: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 20 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 9 Continued

Three Sided Protection to I-Section Beams : 620oC :

Steelguard FM 550, FM 549 & FM 560

80 minutes 90 minutes

Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Up to 40 0.30 Up to 40 0.40 50 0.40 50 0.48 60 0.45 60 0.56 70 0.55 70 0.65 80 0.60 80 0.73 90 0.70 90 0.81

100 0.80 100 0.89 110 0.85 110 0.97 120 0.95 120 1.06 130 1.00 130 1.14 140 1.10 140 1.22 150 1.20 150 1.30 160 1.25 160 1.39 170 1.35 170 1.49 180 1.45 180 1.59 190 1.55 190 1.69 200 1.60 200 1.79 210 1.70 210 1.90 220 1.80 220 2.00 230 1.85 230 2.10 240 1.95 240 2.20 250 2.05 250 2.30 260 2.10 260 2.35 270 2.20 270 2.45 280 2.25 280 2.50 290 2.35 300 2.45

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 21: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 21 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 9 Continued

Three Sided Protection to I-Section Beams : 620oC : Steelguard FM 550, FM 549 & FM 560

100 minutes 120 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 35 0.646 155 1.848 Up to 25 0.778 40 0.687 160 1.923 30 0.778 45 0.727 165 1.998 35 0.853 50 0.768 170 2.074 40 0.90 55 0.808 175 2.149 45 0.95 60 0.849 180 2.225 50 1.00 65 0.889 185 2.300 55 1.06 70 0.929 190 2.375 60 1.11 75 0.970 195 2.451 65 1.16 80 1.010 200 2.526 70 1.21 85 1.051 205 2.602 75 1.27 90 1.091 80 1.32 95 1.132 85 1.40 100 1.172 90 1.54 105 1.213 95 1.68 110 1.253 100 1.82 115 1.293 105 1.95 120 1.334 110 2.09 125 1.395 115 2.23 130 1.471 120 2.36 135 1.546 125 2.50 140 1.621 145 1.697 150 1.772

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 22: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 22 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 10

Three Sided Protection to I-Section Beams : 655oC : Steelguard FM 550, FM 549 & FM 560

15 minutes 30 minutes 45 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.25 Up to 40 0.25 50 0.25 50 0.25 50 0.25 60 0.25 60 0.25 60 0.25 70 0.25 70 0.25 70 0.25 80 0.25 80 0.25 80 0.28 90 0.25 90 0.25 90 0.28

100 0.25 100 0.25 100 0.32 110 0.25 110 0.25 110 0.32 120 0.25 120 0.25 120 0.35 130 0.25 130 0.25 130 0.35 140 0.25 140 0.25 140 0.38 150 0.25 150 0.25 150 0.38 160 0.25 160 0.25 160 0.41 170 0.25 170 0.25 170 0.41 180 0.25 180 0.25 180 0.45 190 0.25 190 0.25 190 0.45 200 0.25 200 0.30 200 0.50 210 0.25 210 0.30 210 0.50 220 0.25 220 0.30 220 0.53 230 0.25 230 0.30 230 0.53 240 0.25 240 0.30 240 0.56 250 0.25 250 0.30 250 0.59 260 0.25 260 0.35 260 0.68 270 0.25 270 0.35 270 0.71 280 0.25 280 0.35 280 0.74 290 0.25 290 0.35 290 0.77 300 0.25 300 0.35 300 0.84 310 0.25 310 0.35 310 0.90 320 0.25 320 0.35 320 0.97

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 23: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 23 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 10 Continued

Three Sided Protection to I-Section Beams : 655oC : Steelguard FM 550, FM 549 & FM 560

60 minutes 90 minutes 120 minutes Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.45 Up to 25 0.778 50 0.25 50 0.55 30 0.778 60 0.25 60 0.60 35 0.85 70 0.25 70 0.70 40 0.85 80 0.30 80 0.75 45 0.95 90 0.30 90 0.85 50 1.00

100 0.35 100 0.95 55 1.06 110 0.35 110 1.00 60 1.11 120 0.40 120 1.10 65 1.16 130 0.40 130 1.15 70 1.21 140 0.45 140 1.25 75 1.27 150 0.45 150 1.30 80 1.32 160 0.50 160 1.40 85 1.40 170 0.50 170 1.50 90 1.54 180 0.55 180 1.55 95 1.68 190 0.55 190 1.65 100 1.82 200 0.60 200 1.70 105 1.95 210 0.60 210 1.80 110 2.09 220 0.65 220 1.90 115 2.23 230 0.65 230 1.95 120 2.36 240 0.70 240 2.05 125 2.50 250 0.75 250 2.10 260 0.85 260 2.20 270 0.90 270 2.30 280 0.95 280 2.35 290 1.00 290 2.45 300 1.10 310 1.20 320 1.30

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 24: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 24 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 11

Three Sided Protection to I-Section Beams : 680oC : Steelguard FM 550, FM 549 & FM 560

15 minutes 30 minutes 45 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.25 Up to 40 0.25 50 0.25 50 0.25 50 0.25 60 0.25 60 0.25 60 0.25 70 0.25 70 0.25 70 0.25 80 0.25 80 0.25 80 0.25 90 0.25 90 0.25 90 0.28

100 0.25 100 0.25 100 0.32 110 0.25 110 0.25 110 0.32 120 0.25 120 0.25 120 0.35 130 0.25 130 0.25 130 0.35 140 0.25 140 0.25 140 0.38 150 0.25 150 0.25 150 0.38 160 0.25 160 0.25 160 0.38 170 0.25 170 0.25 170 0.41 180 0.25 180 0.25 180 0.41 190 0.25 190 0.25 190 0.45 200 0.25 200 0.25 200 0.45 210 0.25 210 0.25 210 0.48 220 0.25 220 0.30 220 0.50 230 0.25 230 0.30 230 0.50 240 0.25 240 0.30 240 0.53 250 0.25 250 0.30 250 0.53 260 0.25 260 0.30 260 0.56 270 0.25 270 0.30 270 0.59 280 0.25 280 0.30 280 0.66 290 0.25 290 0.35 290 0.77 300 0.25 300 0.35 300 0.84 310 0.25 310 0.35 310 0.90 320 0.25 320 0.35 320 0.97

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 25: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 25 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 11 Continued

Three Sided Protection to I-Section Beams : 680oC : Steelguard FM 550, FM 549 & FM 560

60 minutes 90 minutes 120 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.45 Up to 40 0.70 50 0.25 50 0.50 45 0.78 60 0.25 60 0.55 50 0.85 70 0.25 70 0.60 55 0.95 80 0.25 80 0.70 60 1.05 90 0.30 90 0.75 65 1.13

100 0.35 100 0.80 70 1.20 110 0.35 110 0.85 75 1.27 120 0.40 120 0.95 80 1.32 130 0.40 130 1.00 85 1.40 140 0.45 140 1.05 90 1.54 150 0.45 150 1.15 95 1.65 160 0.45 160 1.20 100 1.75 170 0.50 170 1.25 105 1.83 180 0.50 180 1.35 110 1.90 190 0.55 190 1.55 115 2.00 200 0.55 200 1.60 120 2.10 210 0.60 210 1.70 125 2.18 220 0.60 220 1.75 130 2.25 230 0.60 230 1.85 135 2.35 240 0.65 240 1.95 140 2.45 250 0.65 250 2.00 260 0.70 260 2.10 270 0.75 270 2.15 280 0.85 280 2.25 290 1.00 290 2.35 300 1.10 300 2.40 310 1.20 320 1.30

Coating thickness refers to intumescent only Table to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 26: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 26 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 12

Three Sided Protection to I-Section Beams : 700oC : Steelguard FM 550, FM 549 & FM 560

15 minutes 30 minutes 45 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.25 Up to 40 0.25 50 0.25 50 0.25 50 0.25 60 0.25 60 0.25 60 0.25 70 0.25 70 0.25 70 0.25 80 0.25 80 0.25 80 0.25 90 0.25 90 0.25 90 0.28

100 0.25 100 0.25 100 0.28 110 0.25 110 0.25 110 0.32 120 0.25 120 0.25 120 0.32 130 0.25 130 0.25 130 0.35 140 0.25 140 0.25 140 0.35 150 0.25 150 0.25 150 0.38 160 0.25 160 0.25 160 0.38 170 0.25 170 0.25 170 0.41 180 0.25 180 0.25 180 0.41 190 0.25 190 0.25 190 0.41 200 0.25 200 0.25 200 0.45 210 0.25 210 0.25 210 0.45 220 0.25 220 0.25 220 0.45 230 0.25 230 0.25 230 0.48 240 0.25 240 0.30 240 0.50 250 0.25 250 0.30 250 0.53 260 0.25 260 0.30 260 0.53 270 0.25 270 0.30 270 0.53 280 0.25 280 0.30 280 0.59 290 0.25 290 0.30 290 0.63 300 0.25 300 0.30 300 0.72 310 0.25 310 0.30 310 0.82 320 0.25 320 0.35 320 0.94

Coating thickness refers to intumescent only Table also to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 27: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 27 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 12 Continued

Three Sided Protection to I-Section Beams : 700oC : Steelguard FM 550, FM 549 & FM 560

60 minutes 90 minutes 120 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.35 Up to 40 0.50 50 0.25 50 0.45 50 0.65 60 0.25 60 0.50 60 0.80 70 0.25 70 0.55 70 0.90 80 0.25 80 0.60 80 1.05 90 0.30 90 0.65 90 1.20

100 0.30 100 0.65 100 1.30 110 0.35 110 0.70 110 1.45 120 0.35 120 0.75 120 1.60 130 0.40 130 0.80 130 1.70 140 0.40 140 0.85 140 1.85 150 0.45 150 0.90 150 2.00 160 0.45 160 0.95 160 2.10 170 0.50 170 1.00 170 2.25 180 0.50 180 1.05 180 2.40 190 0.50 190 1.30 200 0.55 200 1.50 210 0.55 210 1.60 220 0.55 220 1.65 230 0.60 230 1.75 240 0.60 240 1.80 250 0.65 250 1.90 260 0.65 260 2.00 270 0.65 270 2.05 280 0.75 280 2.15 290 0.80 290 2.20 300 0.95 300 2.30 310 1.10 310 2.35 320 1.25 320 2.45

Coating thickness refers to intumescent only Table also to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 28: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 28 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 13

Three Sided Protection to I-Section Beams : 725oC : Steelguard FM 550, FM 549 & FM 560

15 minutes 30 minutes 45 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.25 Up to 40 0.25 50 0.25 50 0.25 50 0.25 60 0.25 60 0.25 60 0.25 70 0.25 70 0.25 70 0.25 80 0.25 80 0.25 80 0.25 90 0.25 90 0.25 90 0.25

100 0.25 100 0.25 100 0.28 110 0.25 110 0.25 110 0.28 120 0.25 120 0.25 120 0.32 130 0.25 130 0.25 130 0.32 140 0.25 140 0.25 140 0.35 150 0.25 150 0.25 150 0.35 160 0.25 160 0.25 160 0.38 170 0.25 170 0.25 170 0.38 180 0.25 180 0.25 180 0.41 190 0.25 190 0.25 190 0.41 200 0.25 200 0.25 200 0.41 210 0.25 210 0.25 210 0.41 220 0.25 220 0.25 220 0.45 230 0.25 230 0.25 230 0.45 240 0.25 240 0.25 240 0.45 250 0.25 250 0.25 250 0.45 260 0.25 260 0.25 260 0.45 270 0.25 270 0.25 270 0.48 280 0.25 280 0.25 280 0.48 290 0.25 290 0.30 290 0.50 300 0.25 300 0.30 300 0.56 310 0.25 310 0.30 310 0.63 320 0.25 320 0.30 320 0.69

Coating thickness refers to intumescent only Table also to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 29: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 29 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560 Table 13 Continued

Three Sided Protection to I-Section Beams : 725oC :

Steelguard FM 550, FM 549 & FM 560

60 minutes 90 minutes 120 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.35 Up to 40 0.45 50 0.25 50 0.40 50 0.55 60 0.25 60 0.45 60 0.70 70 0.25 70 0.45 70 0.80 80 0.25 80 0.50 80 0.95 90 0.25 90 0.50 90 1.05

100 0.30 100 0.50 100 1.15 110 0.30 110 0.55 110 1.30 120 0.35 120 0.55 120 1.40 130 0.35 130 0.55 130 1.55 140 0.40 140 0.60 140 1.65 150 0.40 150 0.60 150 1.75 160 0.45 160 0.65 160 1.90 170 0.45 170 0.65 170 2.00 180 0.50 180 0.65 180 2.10 190 0.50 190 0.90 190 2.20 200 0.50 200 1.20 200 2.20 210 0.50 210 1.45 210 2.25 220 0.55 220 1.55 220 2.30 230 0.55 230 1.60 230 2.40 240 0.55 240 1.70 250 0.55 250 1.75 260 0.55 260 1.85 270 0.60 270 1.90 280 0.60 280 2.00 290 0.60 290 2.05 300 0.70 300 2.15 310 0.80 310 2.20 320 0.90 320 2.30

Coating thickness refers to intumescent only Table also applies to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 30: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 30 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560 Table 14

Four Sided Protection to I-Section Beams : 700oC :

Steelguard FM 550, FM 549 & FM 560

30 minutes 60 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 210 0.25 Up to 71 0.40 200 0.73 240 0.30 75 0.41 204 0.74 280 0.35 80 0.42 210 0.79 320 0.40 85 0.44 215 0.83

90 0.45 220 0.87 95 0.46 225 0.90 100 0.47 230 0.94 105 0.49 235 0.98 110 0.50 240 1.02 115 0.51 245 1.06 120 0.53 250 1.10 125 0.54 255 1.14 130 0.55 260 1.18 135 0.56 265 1.22 140 0.58 270 1.26 145 0.59 275 1.30 150 0.60 280 1.34 155 0.61 285 1.37 160 0.63 290 1.41 165 0.64 295 1.45 170 0.65 300 1.49 175 0.67 305 1.53 180 0.68 310 1.57 185 0.69 315 1.61 190 0.70 320 1.65 195 0.72

Coating thickness refers to intumescent only Table also applies to beams with 4 sided protection and to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 31: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 31 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 14 Continued

Four Sided Protection to I-Section Beams : 700oC : Steelguard FM 550, FM 549 & FM 560

90 minutes 120 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 43 0.40 185 1.41 Up to 71 1.75 45 0.41 190 1.46 75 1.79 50 0.43 195 1.51 80 1.83 55 0.45 200 1.57 85 1.88 60 0.47 205 1.62 90 1.92 65 0.49 210 1.67 95 1.97 70 0.51 217 1.75 100 2.01 75 0.54 220 1.77 105 2.06 80 0.56 225 1.81 110 2.11 85 0.58 230 1.85 115 2.15 90 0.60 235 1.88 120 2.20 95 0.62 240 1.92 125 2.24

100 0.64 245 1.96 130 2.29 105 0.66 250 2.00 135 2.33 110 0.68 255 2.03 140 2.38 115 0.71 260 2.07 145 2.43 120 0.73 265 2.11 150 2.47 123 0.74 270 2.14 155 2.52 130 0.82 275 2.18 160 2.56 135 0.87 280 2.22 165 2.61 140 0.92 285 2.26 170 2.64 145 0.98 290 2.29 150 1.03 295 2.33 155 1.08 300 2.37 160 1.14 305 2.40 165 1.19 310 2.44 170 1.25 315 2.48 175 1.30 320 2.52 180 1.35

Coating thickness refers to intumescent only Table also applies to beams with 4 sided protection and to other sections with re-entrant details, including structural channels, angles and ‘T’s.

Page 32: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 32 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 15

Protection to Circular Hollow Section Columns : 550oC

Steelguard FM 550, FM 549 & FM 560

15 minutes 30 minutes 45 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.25 Up to 40 0.37 50 0.25 50 0.25 50 0.43 60 0.25 60 0.25 60 0.49 70 0.25 70 0.30 70 0.60 80 0.25 80 0.30 80 0.66 90 0.25 90 0.35 90 0.74

100 0.25 100 0.40 100 0.85 110 0.27 110 0.45 110 0.93 120 0.30 120 0.50 120 1.01 130 0.33 130 0.55 130 1.12 140 0.36 140 0.60 140 1.23 150 0.36 150 0.60 150 1.35 160 0.39 160 0.65 160 1.49 170 0.42 170 0.70 170 1.63 180 0.45 180 0.75 180 1.77 190 0.48 190 0.80 190 1.88 200 0.51 200 0.85 200 2.17 210 0.54 210 0.90 210 2.46 220 0.54 220 0.90 220 2.70 230 0.57 230 0.95 230 2.96 240 0.60 240 1.00 240 3.19 250 0.63 250 1.05 260 0.69 260 1.15 270 0.75 270 1.25 280 0.81 280 1.35 290 0.87 290 1.45 300 0.93 300 1.55 310 0.99 310 1.65 320 1.05 320 1.75

Coating thickness refers to intumescent only

Page 33: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 33 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 15 Continued

Protection to Circular Hollow Section Columns : 550oC

Steelguard FM 550, FM 549 & FM 560

60 minutes 90 minutes 120 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.45 Up to 40 1.60 Up to 15 1.20 50 0.55 50 2.05 20 1.60 60 0.65 60 2.45 25 1.99 70 0.80 70 2.75 30 2.18 80 0.90 80 3.10 35 2.54 90 1.00 90 3.40 40 2.90

100 1.15 100 3.75 50 3.60 110 1.25 110 4.05 60 4.35 120 1.35 120 4.40 130 1.50 140 1.65 150 1.85 160 2.05 170 2.25 180 2.45 190 2.60 200 3.05 210 3.50 220 3.90 230 4.30 240 4.65

Coating thickness refers to intumescent only

Page 34: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 34 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560 Table 16

Protection to Rectangular Hollow Section Columns : 500oC

Steelguard FM 550, FM 549 & FM 560

15 minutes 30 minutes

Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Up to 40 0.25 150 0.42 Up to 40 0.25 150 0.70 42 0.25 160 0.45 42 0.25 160 0.75 45 0.25 170 0.48 45 0.25 170 0.80 48 0.25 180 0.51 48 0.25 180 0.85 50 0.25 190 0.54 50 0.25 190 0.90 55 0.25 200 0.57 55 0.25 200 0.95 60 0.25 210 0.60 60 0.25 210 1.00 65 0.25 220 0.66 65 0.28 220 1.10 70 0.25 230 0.72 70 0.30 230 1.20 75 0.25 240 0.78 75 0.33 240 1.30 80 0.25 250 0.84 80 0.35 250 1.40 85 0.25 260 0.90 85 0.38 260 1.50 90 0.25 270 0.96 90 0.40 270 1.60 95 0.26 280 1.02 95 0.43 280 1.70

100 0.27 290 1.11 100 0.45 290 1.85 110 0.30 300 1.17 110 0.50 300 1.95 120 0.33 310 1.23 120 0.55 310 2.05 130 0.36 320 1.29 130 0.60 320 2.15 140 0.39 140 0.65

Coating thickness refers to intumescent only Table also applies to hollow section beams with 4 sided protection up to a maximum thickness of 2.15 mm

Page 35: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 35 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 16 Continued

Protection to Rectangular Hollow Section Columns : 500oC

Steelguard FM 550, FM 549 & FM 560

45 minutes 60 minutes 90 minutes 120 minutes

Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Up to 40 0.46 Up to 40 0.60 Up to 40 2.00 15 1.02 42 0.51 42 0.68 42 2.05 20 1.36 45 0.51 45 0.68 45 2.05 25 1.70 48 0.55 48 0.75 48 2.17 30 1.86 50 0.55 50 0.75 50 2.17 35 2.17 55 0.60 55 0.83 55 2.26 42 2.60 60 0.64 60 0.90 60 2.34 45 2.90 65 0.70 65 0.98 65 2.45 48 2.90 70 0.75 70 1.05 70 2.51 75 0.81 75 1.13 75 2.60 80 0.86 80 1.20 80 3.00 85 0.92 85 1.28 85 3.40 90 0.97 90 1.35 90 3.80 95 1.03 95 1.43 95 4.20

100 1.08 100 1.50 100 4.60 110 1.19 110 1.65 120 1.30 120 1.80 130 1.41 130 1.95 140 1.52 140 2.10 150 1.66 150 2.30 160 1.77 160 2.45 170 1.88 170 2.60 180 1.99 180 2.75 190 2.13 190 2.95 200 2.48 200 3.50 210 2.92 210 4.20

Coating thickness refers to intumescent only Table also applies to hollow section beams with 4 sided protection up to a maximum thickness of 2.15 mm and a maximum period of 90 minutes

Page 36: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 36 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 17

Protection to Rectangular Hollow Section Beams : 575oC Steelguard FM 550, FM 549 & FM 560

15 minutes 30 minutes 45 minutes

Section factor

m-1

Thickness mm

Section factor

m-1

Thicknessmm

Section factor

m-1

Thickness mm

Up to 40 0.25 Up to 40 0.25 Up to 40 0.25 50 0.25 50 0.25 50 0.28 60 0.25 60 0.25 60 0.34 70 0.25 70 0.25 70 0.37 80 0.25 80 0.25 80 0.40 90 0.25 90 0.25 90 0.46

100 0.25 100 0.25 100 0.49 110 0.25 110 0.25 110 0.52 120 0.25 120 0.25 120 0.58 130 0.25 130 0.30 130 0.63 140 0.25 140 0.30 140 0.69 150 0.25 150 0.35 150 0.77 160 0.25 160 0.35 160 0.98 170 0.25 170 0.40 170 1.12 180 0.25 180 0.40 180 1.15 190 0.27 190 0.45 190 1.20 200 0.27 200 0.45 200 1.23 210 0.30 210 0.50 210 1.28 220 0.30 220 0.50 220 1.31 230 0.33 230 0.55 230 1.36 240 0.36 240 0.60 240 1.41 250 0.39 250 0.65 250 1.46 260 0.42 260 0.70 260 1.51 270 0.45 270 0.75 270 1.56 280 0.48 280 0.80 280 1.61 290 0.51 290 0.85 300 0.54 300 0.90 310 0.57 310 0.95 320 0.60 320 1.00

Coating thickness refers to intumescent only Table applies to beams with a concrete slab on their top face

Page 37: CERTIFICATE OF APPROVAL No CF 456 - Warrington Certification · CERTIFICATE No CF 456 PPG Coatings Europe BV STEELGUARD FM 550, FM 549 and FM 560 1. This approval relates to the use

Page 37 of 37 Signed

Issued: 30th May 2006 Reissued: 3rd June 2011 Valid to: 2nd June 2016

CERTIFICATE No CF 456 PPG Coatings Europe BV

STEELGUARD FM 550, FM 549 and FM 560

Table 17 Continued

Protection to Rectangular Hollow Section Beams : 575oC

Steelguard FM 550, FM 549 & FM 560 60 minutes 90 minutes

Section factor

m-1

Thicknessmm

Section factor

m-1

Thicknessmm

Up to 40 0.25 Up to 40 0.55 50 0.30 50 0.65 60 0.40 60 0.80 70 0.45 70 0.95 80 0.50 80 1.10 90 0.60 90 1.20

100 0.65 100 1.35 110 0.70 110 1.50 120 0.80 120 1.65 130 0.85 130 1.75 140 0.95 140 1.85 150 1.05 150 1.95 160 1.40 160 2.00 170 1.60 170 2.10 180 1.65 180 2.15 190 1.70 200 1.75 210 1.80 220 1.85 230 1.90 240 1.95 250 2.00 260 2.05 270 2.10 280 2.15

Coating thickness refers to intumescent only Table applies to beams with a concrete slab on their top face