CEAG History of self-contained emergency lighting. Month Day, Year 2 CEAG History of self-contained emergency lighting. ¾ In 1971: CEAG produced the worlds first explosion protected emergency light fitting based on eLLK 70 design. ¾ eLLK 70 series is still in use today. ¾ That represents a 34 years in operation . ¾ No spare parts or batteries available Replaced by eLLK 92 series, see page 7

Transcript of CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency...

Page 1: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

CEAG History of self-containedemergency lighting.

Month Day, Year

2

CEAG History of self-contained emergency lighting.

In 1971: CEAG produced the worlds first explosion protected emergency light fitting based on eLLK 70 design.

eLLK 70 series is still in use today.

That represents a 34 years in operation .

No spare parts or batteries available

Replaced by eLLK 92 series, see page 7

Page 2: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

1.1 Production period: 1982 - 1993

eLLK 81 020/20 N and eLLK 81 040/40 N

Emergency light fittings types:eLLK 81020/20 N (2 x 20 W T12-Fa6)eLLK 81040/40 N (2 x 40 W T12-Fa6)

No spare parts or batteries available Replaced by eLLK 92 series, see page 7

1. Maintenance

Practice

1.1 Production period: 1982 - 1993

eLLK 81 020/20 N and eLLK 81 040/40 N

1. Maintenance

Practice

Replacement type: CEAG eLLK 92018/18 NIB

Order No.: eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)Order No.: eLLK 92018/18Nib Bi-Pin (4 x M25 plastic)Order No.: eLLK 92018/18Nib Bi-Pin (4 x M20 metal)Order No.: eLLK 92318/18Nib Single-Pin (4 x M20 metal)

CEAG eLLK 92036/36 NIB.

Order No.: eLLK 92036/36Nib Bi-Pin (2 x M25 plastic)Order No.: eLLK 92036/36Nib Bi-Pin (4 x M25 plastic)Order No.: eLLK 92036/36Nib Bi-Pin (4 x M20 metal)Order No.: eLLK 92336/36Nib Single-Pin (4 x M20 metal)

Page 3: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

1.2 Production period: 1993 - 1995

eLLK 92018/18 N and eLLK 92036/36 N

Emergency light fittings types:eLLK 92018/18 N (2 x 18 W T8-Fa6/G13)eLLK 92036/36 N (2 x 36 W T8-Fa6/G13)

For direct replacement and batteriesavailable see page 7.

Red LED at thelampholder

Red lampholder= emergency lamp

1.2 Production period: 1993 - 1995

eLLK 92018/18 N and eLLK 92036/36 NInstalled Battery: 6 V 7 Ahemergency duration time: 1.5 h or 3.0 h

Charging duration: 24 h/ >90 % of rated capacity

Fault indicators: FIRST CHECK LAMPS ARE WORKINGNo red LED Failure in the change inverter/charging circuit ballast unitNo emergency Battery or inverter change battery/light fault change inverterNo mainslight/ emerg.light o.k. Ballast faulty change ballast

1. Maintenance

Practice

Page 4: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

Replacement type: CEAG eLLK 92018/18 NIBOrder No.: eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)Order No.: eLLK 92018/18Nib Bi-Pin (4 x M25 plastic)Order No.: eLLK 92018/18Nib Bi-Pin (4 x M20 metal)Order No.: eLLK 92318/18Nib Single-Pin (4 x M20 metal)

CEAG eLLK 92036/36 NIB.Order No.: eLLK 92036/36Nib Bi-Pin (2 x M25 plastic)Order No.: eLLK 92036/36Nib Bi-Pin (4 x M25 plastic)Order No.: eLLK 92036/36Nib Bi-Pin (4 x M20 metal)Order No.: eLLK 92336/36Nib Single-Pin (4 x M20 metal)

Fitting replacement type: Battery replacement:type 2710-2 (Ni) Order no. 2 2710 902 000

1. Maintenance

Practice1.2 Production period: 1993 - 1995eLLK 92 018/18 N and eLLK 92 036/36 N

Production period: 1995 - 2002

1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni

Emergency light fittings types:eLLK 92018/18 Ni (2 x 18 W T8-Fa6/G13)eLLK 92036/36 Ni (2 x 36 W T8-Fa6/G13)

For direct replacement and spare batteriesavailable see page 12.

1 red LED

5 green LEDs

grey battery box

1. Maintenance

Practice

Page 5: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

Installed Battery: 6 V 7 Ahemergency duration time: 1.5 h or 3.0 hCircuit diagram see page 10/11Charging duration: 14 h/>90 % capacity

Fault indicators: FIRST CHECK LAMPS ARE WORKING

Red LED flashing Last duration test start duration test for> 6 month or > 30 min.Emerg. duration fully charge (cycle!)< 30 min. start test again

No mains light/ Ballast fault change ballastemerg. light o.k.no green LED no charging faulty battery/inverter

change battery/inverter

1. Maintenance

PracticeProduction period: 1995 - 2002

1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni

1. Maintenance

PracticeProduction period: 1995 - 2002

1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni

WiringdiagrameLLK92018/18 Ni

Page 6: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

1. Maintenance

PracticeProduction period: 1995 - 2002

1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni

WiringdiagrameLLK92036/36 Ni

Replacement type: CEAG eLLK 92018/18 NIBOrder No.: eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)Order No.: eLLK 92018/18Nib Bi-Pin (4 x M25 plastic)Order No.: eLLK 92018/18Nib Bi-Pin (4 x M20 metal)Order No.: eLLK 92318/18Nib Single-Pin (4 x M20 metal)

CEAG eLLK 92036/36 NIB.Order No.: eLLK 92036/36Nib Bi-Pin (2 x M25 plastic)Order No.: eLLK 92036/36Nib Bi-Pin (4 x M25 plastic)Order No.: eLLK 92036/36Nib Bi-Pin (4 x M20 metal)Order No.: eLLK 92336/36Nib Single-Pin (4 x M20 metal)

Fitting replacement type: Battery replacement:type 2710-2 (Ni) Order no. 2 2710 902 000

Production period: 1995 - 2002

1.3 eLLK 92018/18 Ni and eLLK 92036/36 Ni

1. Maintenance

Practice

Page 7: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

Production period: 2002 - now

1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB

Emergency light fittings types:eLLK 92018/18 NIB (2 x 18 W T8-Fa6/G13)eLLK 92036/36 NIB (2 x 36 W T8-Fa6/G13)

Spare parts and batteries availableSee page 14

1 red LED

5 green LEDs

black battery box

1. Maintenance

Practice

Replacement fitting type:eLLK 92018/18 NIBCEAG. Bi-pin lamp single pin lampOrder No.: 1 2260 879 101 (2 x M25 plastic)Order No.: 1 2260 879 103 (4 x M25 plastic)Order No.: 1 2260 879 111 (4 x M20 metal) 1 2210 879 111

eLLK 92036/36 NIBCEAG. Bi-pin lamp single pin lampOrder No.: 1 2261 879 101 (2 x M25 plastic)Order No.: 1 2261 879 103 (4 x M25 plastic)Order No.: 1 2261 879 111 (4 x M20 metal) 1 2211 879 111Replacement battery type:type 2710-3 (NIB), Order no. 2 2710 904 000

Production period: 2002 - now1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB

1. Maintenance

Practice

Page 8: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

Production period: 2002 - Current

1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB

Installed Battery: 6 V 7 Ahoptional emergency duration time:1.5 h or 3.0 hCharging duration: 14 h/>90 % capacityAutomatic function test every week (< 5 minutes)Automatic duration test every 3 monthsAutomatic battery monitoring5 green LEDs for capacity monitoringCircuit Diagram see page 18/19

1. Maintenance

Practice

Production period: 2002 - Current

1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB

1. Maintenance

Practice

L

L1

L2

L3

N

PE

eBK 02

L

L1

L2

L3

N

PE

0

+

3

-

2

1

Notlampe/Emergency lamp

Netzlampe/Mains lamp

EVG..236

L1NLLLL

LLFSLL1LL2

VE97236

+B-BB1

B2B5B6

LNLLFS

NotLL1B4B3

Ersatzbruecke fuer Fernschaltermuss beim Anschluss einesSchalters entfernt werden

Remote Switch,to be removed for connection of inhibit switch

WiringdiagrameLLK92036/36NIB

Page 9: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

Production period: 2002 - Current

1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB

1. Maintenance

Practice

0

+

3

-

2

1WiringdiagrameLLK92018/18NIB

Fault indicators: FIRST ACTION CHECK LAMPS ARE WORKINGLED indication possible reason actionRed LED flashing Last duration test start duration test for

> 3 month or > 30 min.Emerg. duration fully charge (cycle!)< 30 min. start test again

Red LED cont. on Battery failure replace batteryNo mains light/ Ballast fault change ballastemerg. light o.k.No green LED not charging faulty battery/inverter

change battery/inverterless than 2 LEDs ageing of the cycle battery, start fullon after fully battery; duration test, if notcharged capacity loss more LED on, change

1. Maintenance

Practice

Production period: 2002 - now

1.4 eLLK 92018/18 NIB and eLLK 92036/36 NIB

Page 10: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

Automatic display of the remaining capacity

The eLLK 92 NIB series will continuously show the actual capacityof the installed battery:

With steps of 20 % displayed by 5 green LEDs, the residual capacitycan be monitored at the battery enclosure.

1.5 Visual capacity of the battery.

100 % rated capacity80 % rated capacity60 % rated capacity40 % rated capacity20 % rated capacity

a flashing LED indicates charging to the next step

Automatic display of fault conditions

The red LED shows a fault indication:

• continuously on.

Red LEDcontinuously on:Battery faultBattery must bereplaced

Red LED flashing:Function test/duration test

not passed

Last duration test morethan 3 month passed(Inhibit switch off?)

Charge battery at least24h Repeat function testmanually (cut off line)

If red LED is still flashing

Battery capacity too low

- Change battery -

Page 11: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

2.1 Setting of emergency durationTo select the rated emergency duration (1.5 or 3 h) thewire at terminal 1 is used.

2.1.1 1.5 h rated emergency durationboth wires have to be connected on terminal 1

2.1.2 3.0 h rated emergency durationthe wires have to be disconnected:

one to terminal 1one to terminal 0

eBK 02

0

+

3

-

2

1

Ersatzbruecke fuer Fernschaltermuss beim Anschluss einesSchalters entfernt werden

Remote Switch,to be removed for connection of inhibit switch

2. Installation

2.2 Connecting inhibit switch

Connect up to 10 eLLK92… NIB to one central inhibit switch(Ex-e circuit). This switch will block the emergency operationduring a power failure.Do not use it for maintenance work!Note:An open inhibit switch does not allow an automatic function- orduration test.This will cause a flashing red LED at the battery box.

0

+

3

-

2

1

Ersatzbruecke fuer Fernschaltermuss beim Anschluss einesSchalters entfernt werden

Remote Switch,to be removed for connection of inhibit switch

2. Installation

ELLK92NIB ELLK92NIBELLK92NIB ELLK92NIB ELLK92NIB

Page 12: CEAG History of self-contained emergency lighting. · CEAG History of self-contained emergency lighting. Month Day, Year 2 ... eLLK 92018/18Nib Bi-Pin (2 x M25 plastic)

3.1 Display of the NIB-BatteryThe 5 green LEDs shows the actual charging state ofthe NiCd-battery.

A new battery with nominal 7 Ah capacity will be theequivalent to 5 green LEDs. Each LED indicates approx.20 % of the nominal capacity (= 1.4 Ah)

By ageing of the battery the nominal capacity will bereduced over the years. The speed of deterioration isdependant of the operation- and ambient conditions.

Even a unused battery will deteriorate.An average working time of 9 - 10 years can beexpected under normal conditions. (25 °C ambient,duration test every 6 month, no deep discharge periods)

3. Calculation ofemergency

duration

3.2 Capacity of battery by LED-indicationThe inverter of the eLLK 92 series needs an operatingcurrent of approx. 3.4 A (1.5 h setting) or 1.7 A (3 hsetting).

A calculation of 1.5 h x 3.4 A results 5.1 Ah. This is thereason, why a new nominal 7.0 Ah battery will last morethen 1.5 h emergency operation.

Based on the 1.4 Ah/per LED this results a theoreticaltime of 24 minutes/LED.

When 3 LEDs are on, 1 h emergency duration can beexpected.

2. Calculation ofemergency

duration