CE1.11 - 22x34 · O WELLO WELL O WELL. F F. SHEET NO. DRAWN BY: DATE: JOB #: DESIGNED BY: CHECKED...
3
O WELL O WELL O WELL O WELL STOP STOP STOP SHEET NO. DRAWN BY: DATE: JOB #: DESIGNED BY: CHECKED BY: NO. DATE DES'D REVISION DESCRIPTION D'WN SCHOOL DISTRICT 27J - HIGH SCHOOL #3 2071c CONSTRUCTION PLANS - ONSITE 4/8/2016 C JVA INC JVA, Incorporated 1319 Spruce Street Boulder, CO 80302 Phone: 303.444.1951 www.jvajva.com E-mail: [email protected]CONSULTING ENGINEERS THORNTON, COLORADO KAT JPC XT HORIZONTAL CONTROL PLAN C3.0 MATCHLINE SEE SHEET C3.1 J:\2071c\Drawings\2071c-C3.0.dwg, 4/8/2016 1:23:36 PM
"FIRE LINE NO PARKING" SIGN PER CITY OF THORNTON STDS
AutoCAD SHX Text
3
AutoCAD SHX Text
CD3.0
AutoCAD SHX Text
1
AutoCAD SHX Text
CD3.0
AutoCAD SHX Text
6
AutoCAD SHX Text
CD3.0
AutoCAD SHX Text
FUTURE MODULAR CLASSROOMS (RE: ARCH)
AutoCAD SHX Text
RESERVED
AutoCAD SHX Text
PARKING
AutoCAD SHX Text
R7-8
AutoCAD SHX Text
R7-8P6
AutoCAD SHX Text
PARKING
AutoCAD SHX Text
VAN
AutoCAD SHX Text
RESERVED
AutoCAD SHX Text
PARKING
AutoCAD SHX Text
R7-8
AutoCAD SHX Text
9
AutoCAD SHX Text
CD3.0
AutoCAD SHX Text
YOSEMITE STREET (80' ROW)
AutoCAD SHX Text
R1-1
AutoCAD SHX Text
R1-1
AutoCAD SHX Text
R3-5
AutoCAD SHX Text
ONLY
AutoCAD SHX Text
ASPHALT PATCH (TYP)
AutoCAD SHX Text
0
AutoCAD SHX Text
SCALE IN FEET
AutoCAD SHX Text
50
AutoCAD SHX Text
50
AutoCAD SHX Text
100
AutoCAD SHX Text
WORK SHALL BE CONSTRUCTED TO CITY OF THORNTON STANDARDS AND STANDARDS AND SPECIFICATIONS. THIS APPROVAL IS FOR CONFORMANCE TO THESE . THIS APPROVAL IS FOR CONFORMANCE TO THESE STANDARDS AND SPECIFICATIONS AND OTHER CITY REQUIREMENTS. THE AND OTHER CITY REQUIREMENTS. THE DESIGN AND CONCEPT REMAINS THE RESPONSIBILITY OF THE PROFESSIONAL ENGINEER OR LANDSCAPE PROFESSIONAL.
tsemones
Callout
Sign should say "VAN ACCESSIBLE" R7-8P
tsemones
Callout
Sign should say "VAN ACCESSIBLE" R7-8P
tsemones
Callout
Use R3-2 NO LEFT TURN instead
tsemones
Callout
Recommend adding a second R6-1 sign here to prevent wrong way drivers leaving from the loading dock area. Alternatively, both of the R6-1 signs could be replaced with R6-4 signs.
tsemones
Callout
R5-1 DO NOT ENTER signs missing
tsemones
Line
tsemones
Callout
If placed on the back of the R1-1 STOP sign, attention must be paid to the size of the signs. The octagon outline of the STOP sign must not be overlapped with a larger sign on the back. To avoid this the STOP sign can be oversized. Otherwise the two signs will need to be on separate sign posts.
tsemones
Callout
LANE, not LINE
tsemones
Callout
Is this section of sidewalk depressed? If not, how is the accessible route provided to the school. Don't see any curb ramps from the accessible parking spaces.
tsemones
Callout
Recommend installing curb ramps at these ends. This isn't the accessible route to the school, but ramps will be helpful for anyone needing to move anything wheeled through this area, which is a likely use.
WORK SHALL BE CONSTRUCTED TO CITY OF THORNTON STANDARDS AND STANDARDS AND SPECIFICATIONS. THIS APPROVAL IS FOR CONFORMANCE TO THESE . THIS APPROVAL IS FOR CONFORMANCE TO THESE STANDARDS AND SPECIFICATIONS AND OTHER CITY REQUIREMENTS. THE AND OTHER CITY REQUIREMENTS. THE DESIGN AND CONCEPT REMAINS THE RESPONSIBILITY OF THE PROFESSIONAL ENGINEER OR LANDSCAPE PROFESSIONAL.
tsemones
Callout
Curb ramp missing. A rolled curb is not accessible.
tsemones
Line
tsemones
Callout
Curb ramp called out, but not shown.
tsemones
Line
tsemones
Callout
Sign should say "VAN ACCESSIBLE" R7-8P
tsemones
Callout
Accessible parking signs not called out
tsemones
Callout
What width is being used for the accessible parking spaces? Current ADA standards require a minimum width of 8 feet for a standard accessible parking space. This 8 foot width does not include any adjacent curb and gutter. i.e. you can't count the gutter pan as part of the 8 foot width.
Recommend a gate be installed at this location to prevent eastbound traffic in the morning (if needed). This will allow the ability to force all traffic south and extend the length of the drop off loop.