Use of Online Monitoring and Data Optimisation Drives Condition Assessment on Service‐Aged Generator Step Up (GSU) Transformers
Ami Singh, Ian Thompson, John Twiddle; SSE – Engineering Centre Brent Duder‐Findlay, Dynamic Ratings
![Page 2: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/2.jpg)
CCGT Site – 735MW
![Page 3: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/3.jpg)
SLD – Site Commissioned in 1995
![Page 4: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/4.jpg)
22 Year Asset(s) – 290MVA, 420/15kV
![Page 5: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/5.jpg)
Asset History
![Page 6: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/6.jpg)
Applying Loading Guide – Temperature Based Only
Loss of Life (Days)
HV LV
Tx 1 1.21 2.2Tx 2 1.14 1.77Tx 3 1.32 2.92
Based on 1 Year Data (Oct 2015‐Oct 2016)
For Asset Life – Lost of Life
![Page 7: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/7.jpg)
Average DP From Furans
![Page 8: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/8.jpg)
CO2/CO Ratio
![Page 9: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/9.jpg)
Acidity of Oil
![Page 10: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/10.jpg)
O2/N2 Ratio
![Page 11: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/11.jpg)
BDV and Moisture in Oil
![Page 12: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/12.jpg)
Installation of Additional Monitoring
![Page 13: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/13.jpg)
Equipment Details
Processing Unit HV Bushing Monitoring PD Monitoring
![Page 14: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/14.jpg)
Equipment Details
LV Couplers Tap Changer Monitoring Multi Gas Analyser (9 gas unit)
![Page 15: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/15.jpg)
Equipment Details
Temperature Monitoring Additional Temperature Probes
Cooling System Monitoring
![Page 16: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/16.jpg)
Equipment Details
Calibrations Bus Voltages, Power etc. Commissioning
![Page 17: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/17.jpg)
Harvesting the
2014 – System Commissioned
2016 – Post Review
Digital/per Tx 56 275Analogue/ per Tx 42 527Total 294 2406
![Page 18: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/18.jpg)
Block System of Predictive Analytical Tool
![Page 19: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/19.jpg)
Traditional Monitoring vs Predictive Analytical Tool
![Page 20: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/20.jpg)
System in Action
![Page 21: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/21.jpg)
System in Action
![Page 22: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/22.jpg)
High Level Interface
![Page 23: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/23.jpg)
![Page 24: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/24.jpg)
![Page 25: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/25.jpg)
![Page 26: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/26.jpg)
Maintenance History – Preventative or Corrective
1404 14171419
495 526279
0%10%20%30%40%50%60%70%80%90%
100%
CT1 CT2 ST
PM CM
![Page 27: CCGT Site – 735MW - INSUCON 9.4 - Brent Duder.pdf · CCGT Site – 735MW. SLD –Site Commissioned in 1995. 22 Year Asset(s) – 290MVA, 420/15kV. Asset ... Calibrations Bus Voltages,](https://reader030.fdocuments.us/reader030/viewer/2022020114/5b7078f47f8b9aad128d7de0/html5/thumbnails/27.jpg)
Conclusions
• The 3 GSU transformers have experienced significant ageing to date.
• Asset owner has taken/is taking proactive steps to slow the ageing process.
• A health index tool is providing transparency on asset integrity.