Catalogue Rccb
-
Upload
karikalan-jay -
Category
Documents
-
view
65 -
download
4
Transcript of Catalogue Rccb
Residual current devices
○ ○ ○ ○ ○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
Page
Bcontents
c RCCB
c electrical auxiliaries for RCCB
c 100/125 A RCCB
c Vigi C60 module
24
26
28
29
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
24 Mer lin Gerin
functions
residual current devices
instantaneous RCCB, selective RCCB30 mA to 300 mA instantaneous300 mA s selective and "si"IEC 61008 - EN 61008 - BS EN61008
description common technical datac power circuit:v voltage rating:- 240 to 415 V AC, +10, -20 %, 50 Hzv current rating: 40 to 100 Av disconnection with positive contactindicationv reinforced short-circuit current withstandv number of operating cycles (O-C): 20 000c release:v instantaneous or selective release:fixed sensitivities for all ratingsc manual control: handlec indication:v mechanical: the ear th leakage fault isdisplayed on the front face by mechanicalindicatorv electrical: using the SD indicating auxiliaryswitch (supplied separately)c environment:v tropicalisation: treatment 2(relative humidity 95% at 55 °C)v weight (g)type 2P 4P
230 380v connection- tunnel terminals for 35 mm2 supple cablesor 50 mm2 rigid cablesc compliance with standards:IEC 61008 and EN 61008
catalogue numbers
Residual current circuit-breakers combinethe following functions:- control- automatic circuit breaking in the event of aninsulation fault between phase and earthgreater than or equal to 30, 100 or 300 mA.
16204
type voltage rating sensitivity catalogue width(V AC) (A) (mA) number in mod.
of 9 mmAC class RCCB residual current circuit-breakers
2P 240 25 30 16201 4300 16202 4
40 30 16204 4100 16205 4300 16206 4
63 30 16208 4100 16209 4300 16210 4
80 30 16212 4100 16213 4300 16214 4
100 100 16217 4
specific data
instantaneous RCCBc instantaneous releasec provides protection against nuisancetripping due to transient overvoltage(stroke of lightning, switchgear switching onthe network, etc.).Level of immunity: 250 A peak accordingto 8/20 µs periodical wave
selective RCCB sssssv selective release allowing total ver ticaldiscrimination where the 30 mA RCDsare placed downstreamc provides protection against nuisancetripping due to transient overvoltage(stroke of lightning, switchgear switching onthe network, etc.).Level of immunity: 250 A peak according to8/20 µs periodical wave
type "si"the "si" range was designed to maintain anetwork with optimum safety and servicecontinuity in installations disturbed:v by extreme atmospheric conditionsv by harmonic generating loadsv by transient switching currentsc the "si" residual current circuit-breakersare used in the tertiary sector and industryalikec in the presence of equipment containingrectifying devices (diodes, thyristors, triarcs),a class A instantaneous residual currentcircuit-breaker should be used whichguarantees tripping if a direct component isdetectedc 8/20 µs current wave withstand:v 3 kÂ: I∆n i 30 mAv 5 kÂ: I∆n > 30 mA
R
N
N
1
2
T
Residual current circuit-breakers are used inthe residential, service and industrialsectors.The residual current release iselectromechanical and operates without anyauxiliary source of supply.
25Merlin Gerin
catalogue numbers
16256
type voltage rating sensitivity catalogue width(V AC) (A) (mA) number in mod.
of 9 mmAC class RCCB residual current circuit-breakers (continued)
4P 415 25 30 16251 8300 16252 8
40 30 16254 8100 16255 8300 16256 8
63 30 16258 8100 16259 8300 16260 8300 s 16265 8
80 30 16261 8300 16263 8300 s 16266 8
A class RCCB "si" residual current circuit-breakers
2P 240 25 30 16234 440 30 16237 463 30 16240 4
300 s 16246 4
4P 240 25 30 16321 840 30 16324 863 30 16327 8
300 s 16334 8
R
N
N
1
2
T
3
4
5
6
additionalinformation
electrical auxiliaries: page 26dimensions: page 86
16240
R
N
N
1
2
T
R
N
N
1
2
T
3
4
5
6
26 Mer lin Gerin
max. 54 mm
residual current devices
electrical auxiliariesfor RCCB
functions These electrical auxiliaries are used forremote indication or tr ipping of the residualcurrent circuit breakers.
description
remote trippingAn MX or MN release can be used for thispurpose.Tripping is shown by a red indicator on thefront face.
MX + OF shunt trip releasetrips and opens its associated circuit-breakerwhen energised:c equipped with a self-breaking switchc equipped with a switch (terminals 12and 14) to indicate whether the circuit-breaker is "open" or "closed" when the coil isenergised.
MN undervoltage releasetrips and opens its associated circuit-breakerwhen the supply voltage drops (between 70and 35%) and prevents reclosing until thesupply voltage is restored:c complies with standards IEC 6947-2c use:v push button emergency stopv safety on the supply circuits of severalmachines by disabling "uncontrolled" restartof all motors.
MN time delayed undervoltage release sThis undervoltage release controls theopening of its associated residual currentswitch. It allows a 0.2 second time delay onshort supply interruptions or voltage drops
characteristicsc consumption of releasestype voltage
(V AC or DC) (W or VA)
MX 415 V AC inrush 120220...240 V AC inrush 50110...130 V AC inrush 200
DC inrush 1048 V AC inrush 22
DC inrush 2224 V AC inrush 120
DC inrush 120MN 220...240 V AC hold 4.1
48 V AC hold 4.3DC hold 2,0
MNs 220...240 V AC hold 4.1
OF auxiliary switchSD fault indicatingswitch
auxiliary combinations
OFSauxiliaryswitch
remote indicationOFS switchc use of the OFS switch is compulsory foradding the MN, MX, SD and OF functions.c fixed on the lefthand side of the residualcurrent switch, it indicates whether theswitch is "open" or "closed".OF switchc fixed on the lefthand side of the residualcurrent switch, it indicates whether theswitch is "open" or "closed".SD fault indicating switchc this auxiliary switch installed to the left ofthe circuit-breaker indicates the "tr ipped onfault" position of the circuit-breaker.c visualisation of the fault on the front panelby mechanical indicator lamp.
characteristicsc breaking capacity of the auxiliary switchesvoltage breaking capacity(V AC or DC) (A)
415 V AC 3≤ 240 V AC 6130 V DC 1≤ 48 V DC 2≤ 24 V DC 6
common auxiliary characteristicsc connection by pad terminals for 2 cables1.5 mm2 or 1 cable 2.5 mm2.
operation simulationA test button on the front face of the OFswitches is used to simulate the OFfunctions without using the residual currentcircuit breaker.
+ +
residual currentcircuit breaker
MX shunt trip releaseMN undervoltage release
They are mounted on the lefthand side ofthe residual current circuit breaker within a54 mm width.
+
< >
27Merlin Gerin
type control voltage catalogue width(V AC) (V DC) number in mod.
of 9 mmOFS auxiliary switch
26923 1
MX + OF shunt trip release
220...415 110...130 26946 224 24 26948 2
MN undervoltage release
instantaneous 220...240 26960 2
delayeds 220…240 26963
SD fault indicating switch
26927 1
OF+SD/OF auxiliary contact
26929 1
catalogue numbers
C11214 C2
u >
D1 D2
u <
9294 91
26946
26960
26927
26923
1214 11
26929
14 12 11
2191
2294
2492
28 Mer lin Gerin
functions
description
catalogue numbers
residual current devices
special 100 / 125 A RCCB30 to 500 mA, AC classIEC 61008 - EN 61008 - BS EN61008
common functionsc the residual current circuit-breakerscombine the following functions:v controlv automatic breaking of a circuit in the eventof a phase-to-earth insulation faultc the 100/125 A ID residual currentcircuit-breakers are used in the tertiarysector and industry.
The residual current release iselectromagnetic and operates without anyauxiliary source of supply.
technical datac voltage rating: 240...415 V ACc current rating: 100 or 125 Ac protection against nuisance tripping,8/20 µs wave withstand:30 to 500 mA, 250 A peakc number of operating cycles (O-C): 10 000c manual control: handlec electrical indication: by OFsp indicatingauxiliary switch: catalogue number 16940c environment:v short-circuit withstand:10 kA with 125 A fusev mechanical withstand: 59 to 80 Hz / 30 mnv utilisation temperature:- AC class: -5 °C
v storage temperature:- AC class: -20 °C to +60 °Cc connection:v ID by tunnel terminal for 50 mm2
maximum flexible cablesv auxiliary by 2.5 mm2 maximum tunnelterminalc complies with standards:v EN 61008-2.1v BS EN 61008v IEC 1008.
type rating voltage sensitivity catalogue width(A) (V AC) (mA) number in mod.
of 9 mmAC class residual current circuit-breakers
4P 100 240/415 30 16900 10100 240/415 100 16901 10125 240/415 30 16905 10125 240/415 100 16906 10125 240/415 300 16907 10125 240/415 500 16908 10
type voltage current catalogue width(V) (A) number in mod.
of 9 mmOFsp auxiliary switch
230 V AC 5 16940 1230 V DC 0.5
specific functions
"instantaneous" typeEnsures instantaneous tripping(without time delay).
AC classID for which tripping is ensured by sinusoidalAC residual currents, whether they aresuddenly applied or slowly increase.
16901
14
13
22
21
16940
additionalinformation
dimensions: page 86
R
N
N
1
2
T
3
4
5
6
29Merlin Gerin
type rating sensitivity cat. no. width(A) (mA) in mod
of 9 mmAC class Vigi C60 module
2P i 25 30 26581 3100 26582 3300 26583 3
i 63 30 26611 4100 26612 4300 26613 4
4P i 25 30 26595 6100 26596 6300 26597 6
i 63 30 26643 7100 26644 7300 26645 7
catalogue numbers
residual current devices
Vigi C60 moduleinstantaneousIEC 61009 - EN 61009 - BS EN 61009-2-1
1 3
42
T➞
1 3
4226583
technical data
Vigi modulec operation:v electromechanicalv without auxiliary source of supplyc incorporates in the same unit:v a residual current relayv a toroidc total vertical discrimination with the I∆n300 mA "selective" or 1 A "selective"sensitivities, if installed:v upstream of an instantaneous residualcurrent devicev downstream of an index II time-delayedresidual current device, provided that inboth cases: I∆n of the downstream device≤ I∆n/2 of the upstream devicec protection against nuisance trippings:8/20 µs wave withstand:v AC and A class: 250 Âv "si" type: 3 kÂv s : 5 kÂc voltage rating:230…400 V AC -20…+10 %c frequency: 50…60 Hzc trip unit:v instantaneous or selective trip unit: fixedsensitivities for all ratingsc manual control: handle allowing 2 resetmodes:- either reset of the C60 + Vigi module in onesingle operation- or reset of the C60 + Vigi moduleseparately. The Vigi module is reset beforethe circuit-breaker
c mechanical indication: visualisation of theearth fault on the front face by redmechanical indicator on the Vigi moduleoperating handlec environment:v weight (g)type 2P 3P 4P
Vigi ≤ 25 A 120 180 180Vigi ≤ 63 A 150 210 210v connection- tunnel terminals for 16 mm2 flexible cablesor 25 mm2 rigid cables for Vigi modules with≤ 25 A ratings- tunnel terminals for 25 mm2 flexible cablesor 35 mm2 rigid cables for Vigi modules with≤ 63 A ratings.c the C60 + Vigi module combinationconstitutes a residual current device whichcomplies with EN 61009 standards
NB: the Vigi module range with ≤ 25 A ratings isequipped with a locating device to preventinstallation risks on circuit-breakers with > 25 Aratings.
screw shieldc single-polec sealable
description
82 4 6
1 3 5 7
82 4 6
1 3 5 7
➞T
26595