Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line...

275
Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue A2 - 50 Hz - 2009 A2

Transcript of Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line...

Page 1: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

Pumps in In-line Designand Accessories

Catalogue Heating, Air-conditioning Cooling

Glanded Pumps

Catalogue A2 - 50 Hz - 2009 A2

Page 2: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

1 Wilo-Katalog Mustertabellen Version 01

Programme overview and fields of applications

GGlandedd pumps

Pumpp type Mainn fieldd off application

Page

Energy-savingg pumps

Single pumps Wilo-VeroLine-IP-E • • • 28

Wilo CronoLine-IL-E • • • 43

Wilo-CronoLine-IL-E...BF • • • 49

Double pumps Wilo VeroTwin-DP-E • • • 61

Wilo CronoTwin-DL-E • • • 85

Wilo-CronoTwin-DL-E...BF • • • 93

Standardd pumps

Single pumps Wilo VeroLine-IPL • • • 108

Wilo-CronoLine-IL • • • 123

Double pumps Wilo VeroTwin-DPL • • • 147

Wilo CronoTwin-DL • • • 166

Speciall in-linee pumps

Single pumps Wilo VeroLine-IPS • • • – 200

Wilo-VeroLine-IPH-O/-W • • • – 204

Wilo-VeroLine-IP-Z • • • • 211

Monoblocc pumps

Single pumps Wilo BAC – • • –1)

Wilo-CronoBloc-BL • • • –

Key: Fieldss off application:

• Applicable- Cannot be used

can be used in special version1) See catalogue A3 - Monobloc and norm pumps,

axially split case pumps

Neww inn thee programmee orr seriess extensionorr modification

Heating Industrial applications

Air-conditioning/cooling Secondary hot water circulation

Page 3: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

3

Contents

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps

Standard

pum

psSpecial in-line pumps

Switc

hgears

and

control

devices

pump management s

ystems

General notes and abbreviations 5

Planning guide 7

Energy-saving pumps 116

Wilo-VeroLine-IP-EWilo-CronoLine-IL-EWilo-CronoLine-IL-E...BFWilo-VeroTwin-DP-EWilo-CronoTwin-DL-EWilo-CronoTwin-DL-E...BF

Standard pumps 102

Wilo-VeroLine-IPLWilo-CronoLine-ILWilo-VeroTwin-DPLWilo-CronoTwin-DL

Special in-line pumps 194

Wilo-VeroLine-IPSWilo-VeroLine-IPH-O/-WWilo-VeroLine-IP-Z

Switchgears and control devices 216Wilo-Control pump management 248

VR-HVAC, CR, CRn, CC-HVACIR-Modul, IR-Monitor, Protect-Modul-CWilo-Control AnaCon/DigiCon/DigiCon-AWilo-Control bus box, CAN bus line

Page 4: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

4 Subject to change 09/2008 WILO SE

Glanded pumpsContents

Energy-saving pumps

Single pumps, in-line Series overview 16

Wilo-VeroLine-IP-E 28

Wilo-CronoLine-IL-E 43

Wilo-CronoLine-IL-E...BF 49

Double pumps, in-line Wilo-VeroTwin-DP-E 61

Wilo-CronoTwin-DL-E 85

Wilo-CronoTwin-DL-E...BF 93

Standard pumps

Single pumps, in-line SSeries overview 102

Wilo-VeroLine-IPL 108

Wilo-CronoLine-IL 123

Double pumps, in-line Wilo-VeroTwin-DPL 147

Wilo-CronoTwin-DL 166

Special in-line pumps

Single pumps, in-line SSeries overview 194

Wilo-VeroLine-IPS 200

Wilo-VeroLine-IPH-O/-W 204

Wilo-VeroLine-IP-Z 211

Switchgears and control devices

Series overview 216

Wilo-VR-HVAC 231

Wilo-CR, Wilo-CRn 235

Signal transmitters and accessories 243

Wilo-Control pump management systems

Pump control Series overview 248

Wilo-IR-Modul, Wilo-Dia-Log 255

Wilo-IR-Monitor 259

Wilo-IF-Module 263

Building automation (BA) Wilo-Control AnaCon 267

Wilo-Control DigiCon 269

Wilo-Control DigiCon-A 271

Accessories Wilo-Control bus box, CAN bus line 273

Page 5: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

5

General notes and abbreviations

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps

Standard

pum

psSpecial in-line pumps

Switc

hgears

and

control

devices

pump managem

ent s

ystems

Abbreviations used and what they mean

Abbreviation Meaning

1~ 1-phase current

3~ 3-phase current

Autopilot Automatic adjustment of the pump output in set-back phases, e. g. boiler setback operation during the night.

blsf Blocking current-proof, no motor protection neces-sary

CAN CAN (Controller Area Network) - Multi master bus system, in which several equal CAN-devices may communicate via a 2-core bus within very short cycle times. The Wilo-CAN bus includes a CANopen Standard (EN 50325-4) which is independent of the supplier.

DM Three-phase motor, 3~

DN Nominal diameter of the flange connection

�p Pressure loss

�p-c Control mode for constant differential pressure

�p-T Control mode for differential pressure control de-pending on the fluid temperature

�p-v Control mode for variable differential pressure

�T Control mode for differential temperature

EBM Individual run signal

ECM technol-ogy

Electronically commutated motor with new damp-room enclosure, newly developed glandless drive concept for high-efficiency pumps

EM Single-phase motor, 1~

EnEV German Energy Conservation Legislation

ESM Individual fault signal

Ext. Off "Overriding Off" control input

Ext. Min Control input „Overriding Min“, e. g. for setback op-eration without Autopilot

FI Residual current-operated protective device

BA Building automation

GRD/GLRD Mechanical seal

°dH Degree of German water hardness; formerly used unit for assessing the water hardness. Is no longer used since the SI-unit mmol/l has been introduced. Conversion: 1 °dH = 0.1783 mmol/l

H Delivery head

IF Interface

Int. MS Internal motor protection: Pumps with internal pro-tection against unacceptably high winding tempera-tures

IR Infrared interface

Abbreviation Meaning

KDS Capacitor

KLF PTC thermistor sensor

KTL-coating Electrophoretic painting (cataphoretic coating): Painting with high adhesive strength for long-lasting corrosion protection

KTW Approval for products with plastics, for use in pota-ble water applications

LON Local Operating Network (open, standardised data bus system independent of manufacturer in LON-Works networks)

mmol/l Millimol per litre; SI-unit for assessing the water hardness (total hardness or concentration of alkaline earth ions)

MOT Motor module (drive motor + impeller+ terminal box/electronic module) for replacement of TOP-...-series

P1 Power consumption (power supplied from the grid)

PLR Pump master computer, Wilo-specific data interface

Q (=�) Volume flow

RMOT Spare motor (drive motor + impeller + terminal box/electronics module) for replacement

SBM Run signal or collective run signal

SSM Fault signal or collective fault signal

Control input0 - 10 V

Analogue input for external activation of functions

TrinkwV 2001 German Drinking Water Ordinance of 2001(valid from 01.01.2003)

VDI 2035 VDI guideline for preventing damage in hot-water heating installations

Wilo-Control Building automation management with pumps and accessories

WRAS Water Regulations Advisory Scheme (potable water approval for Great Britain and North-ern Ireland)

WSK Thermal winding contacts (in motor for monitoring the winding temperature, full motor protection by additional tripping unit)

� Operating mode of double pumps:Individual operation of the relevant operating pump

� Operating mode of double pumps:Parallel operation of both pumps

� Number of poles of electric motors:2-pole motor = approx. 2900 rpm at 50 Hz

� Number of poles of electric motors:4-pole motor = approx. 1450 rpm at 50 Hz

� Number of poles of electric motors:6-pole motor = approx. 950 rpm at 50 Hz

Page 6: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

6 Subject to change 09/2008 WILO SE

General notes and abbreviations

Material designations and their meaning Wear and tearPumps or parts of pumps are subject to wear in accordance with state-of-the-art technology (DIN 31051/DIN-EN 13306). This wear may vary depending on operating parameters (temperature, pressure, speed, water condition) and installation/usage situation and may re-sult in the malfunction or failure at different times of the above-mentioned products/components including their electrical/electroni-cal ciruitry.Wear parts are all components subject to rotary or dynamic strain in-cluding electronic components under tension, in particular:

- Seals (incl. mechanical seal), seal ring- Stuffing box - Bearing and shaft- Impellers and pump part- Ball race and wear ring-Wear ring / wear plate-Macerator- Capacitor-Relay / contactor / switch- Electronic circuits, semiconductor components etc.

Pumps and continuous-flow machines (lie submersible mixers and recirculation pumps), as well as their components with coatings (cat-aphoresis coating, 2K- or Ceram-coating) are subject to constant wear due to the abrasive fluid contents. It is for that reason that the coating is also listed with the wearing parts contained in these units!

We do not accept liability for faults or defects arising from natural tear and wear.

NoteIn accordance with German Energy Saving Ordinance [Energieein-spar-Verordnung EnEV] as of the 1.2.2002 at boiler outputs from 25 kW, heating pumps are to be equipped with switchgears for auto-matic performance control or electronically controlled pumps are to be installed.In accordance with TTrinkwV 2001 and DIN 50930-6, only circulating pumps with corrosion-resistant pump housings made of stainless steel or red brass (CC 499K) are to be utilised in secondary hot water circulation systems.

Pump replacementDetailed information on the subject of "Replacing heating pumps" can be found in the current Wilo replacement guide for heating pumps.

Wilo – General terms of delivery and serviceThe latest version of our general terms of delivery and service can be found on the Internet at

www.wilo.com/agb

Material Meaning

1.4021 Chrome steel X20Cr13

1.4034 Chrome steel X46Cr13

1.4057 Chrome steel X17CrNi16-2

1.4122 Chrome steel X39CrMo17-1

1.4301 Chromium nickel steel X5CrNi18-10

1.4305 Chromium nickel steel X8CrNiS18-9

1.4306 Chromium nickel steel X2CrNi19-11

1.4401 Chromium nickel molybdenum steel X5CrNiMo17-12-2

1.4408 Chromium nickel molybdenum steel GX5CrNiMo19-11-2

1.4462 Chromium nickel molybdenum steel X2CrNiMoN22-5-3

1.4541 Chromium nickel steel with titanium addition X6CrNiTi18-10

1.4542 Chromium nickel steel with copper and niobium ad-dition X5CrNiCuNb16-4

1.4571 Chromium nickel steel with titanium addition X6CrNiMoTi17-12-2

Abrasite Chilled cast iron for use with heavily abrasive fluids

Al Aluminium

Ceram Liquid ceramic coating; coating with very high adhe-sive strength for long-lasting corrosion protection

COMPOSITE High-strength plastic material

EN-GJL Cast iron (with lamellar graphite)

EN-GJS Cast iron (with spheroidal cast iron)

G-CuSn10 Zinc-free bronze

GfK Glass fibre reinforced plastic

GG see EN-GJL

GTW Special cast iron: white malleable cast iron

GGG see EN-GJS

Inox stainless steel

NiAl-Bz Nickel aluminium bronze

PPO Trade name: Noryl, fibreglass-reinforced plastic

PP-GF30 Polypropylene, reinforced with 30% fibreglass

PUR Polyurethane

SiC Silicon carbide

ST Steel

V2A Material group, e.g. 1.4301, 1.4306

V4A Material group, e.g. 1.4404, 1.4571

Page 7: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

7

Planning guide

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Planning guide Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsNote on range of applicationThis planning guide applies to:

- Electronically controlled in-line pumps of the series: IP-E, DP-E, IL-E, DL-E, IL-E .. BF, DL-E .. BF

-Uncontrolled in-line pumps of the series: IPL, DPL, IL, DL, IPs, IPH-O/-W, IP-Z

-Monobloc pumps of the BL series

Pump selectionGlanded pumps are ideally suited for use in conjunction with large plant systems covering a wide range of applications in the field of hot water and air conditioning/cooling. The technically correct selection of a pump involves a number of factors:

- The correct pump size to achieve the required duty point- The correct pump series to fulfil the process parameters (e.g. pres-sure and temperature)

- The right materials to fulfil endurance requirements.

The overview duty charts in the Program overviews section of the catalogue allow you to roughly select the pump series you need, helping you to select the most suitable size of pump within the re-spective series more quickly. Frequently, pumps of various series are found to be hydraulically suitable in the border area of the duty charts. Accurate selection of the required pump size is possible only with the aid of the individual pump curve. These are provided in this catalogue and in the Wilo planning software (available on CD-ROM and online at www.wilo-select.com).

The Technical data section of the catalogue provides information on the application limits with respect to pressure, temperature and ma-terial options. In addition, this section of the catalogue provides in-formation on the pump equipment.

Pump curveAn ideally dimensioned pump has its duty point in the region of max-imum efficiency. At the duty point, there is a balance between the performance capacity of the pump (figure 1, curve P) and the power consumption required to overcome the resistance of the pipe system (figure 1, curve A1). Tolerances in accordance with ISO 9906, Appen-dix 1, are to be taken into account for all of the pump curves illustrat-ed.

Figure 1

The point of highest efficiency is approximately in the upper third of the pump curve, or is indicated on the performance diagram. The planning engineer must find a duty point to match the maximum re-quirements of the pump.In the case of a heating pump, this is the capacity to meet the calcu-lated standard heating load of the building. All other duty points that occur in practice lie on the pump curve to the left of the duty point Qnominal. The pump thus operates within its highest efficiency range. If the actual resistance of the pipe system is lower than that on which the pump selection has been based, then the duty point may lie out-side the pump curve (figure 1, curve A2). This may lead to an unac-ceptably high power consumption and hence to an overload of the selected motor. In this case it is necessary to redetermine the duty point and, if necessary, use a more powerful pump. The minimum volume flow Qmin of a glanded pump is 10% of Qmax (figure 1). The incremental pump curves provided for pumps and, in particular, for power selection, are intended for use when there is reliable knowledge of the duty point. If reliable knowledge of the duty point is not available, our basic recommendation is to select the pump with the maximum electrical power.

CavitationThe selection of the right pump also includes the prevention of cavi-tation. This is particularly the case in open systems (e.g. cooling tow-er systems) and at very high temperatures and low system pressures.The pressure drop in a flowing fluid, e.g. due to frictional resistance in the pipe, a change in absolute velocity or the geodetic head, leads to the local formation of vapour bubbles when the static pressure falls to the vapour pressure of the fluid (Fig. 2).The vapour bubbles are carried along by the flow, collapsing suddenly if the static pressure increases again above the vapour pressure (Fig. 3).

This process is called cavitation. The collapse of the vapour bubbles causes micro-jets which, on hitting the surface of a wall, cause de-struction of the wall material.To avoid cavitation, special attention must therefore be given to the maintenance of the correct pressure. If the available intake pressure (or static pressure) in the pipe system is not high enough to meet the static head required for the pump (net positive suction head or NPSH), appropriate measures must be taken to increase the static head to at least achieve a balance. This can be done by:

- Increasing the static pressure (pump positioning).- Reducing the fluid temperature (reduced vapour pressure pD)- Selecting a pump with a lower net positive suction head (NPSH) (as a rule a larger pump)

Qnenn

Qmin

Qmax

Pmax

A 1

A 2

P2[kW]

H[m]

Q[m3/h]

Q[m3/h]

Fig. 2 Fig. 3

Negative pressure Positive pressure

Page 8: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

8 Subject to change 09/2008 WILO SE

Planning guide

Net positive suction head NPSHThe net positive suction head (NPSH) is pump-specific and is dis-played in the performance diagram for the pump (Fig.4). The NPSH values are based on the respective maximum impeller diameter. In or-der to allow for any uncertainty in the specification of the duty point, when selecting the pump, the values should be increased by a margin of safety of 0.5 m.

Fig. 4

SeriesA hydraulically suitable pump must also meet the required operating conditions. For this, it is necessary to check the maximum permissible operating temperature and pressure first.

Design

In-line pumpsWilo in-line pumps are single-stage, low-pressure centrifugal pumps in in-line design with suction and pressure ports of the same nominal diameter and with air-cooled IEC standard motors. PN 16 flanges with pressure measuring connections R 1/8. The pump housing is standard-equipped with feet.

Monobloc pumpsWilo monobloc pumps are single-stage, low-pressure centrifugal pumps in block design in accordance with EN 733 with air-cooled IEC standard motors. Spiral housing made of cast iron with axial suction port and radially arranged pressure port, PN 16 flanges with pressure measuring connections R 1/8. The pumps are standard-equipped with angled or motor feet.

MaterialsThe selection of materials for all parts that come in contact with the fluid is of importance for the chemical resistance of the pump.

The material selection table provides an overview of the most impor-tant components. In addition to the resistance of glanded pumps, particular significance is attached to the functional capability of the mechanical seal.

NPSH

H[m]

Q[m3/h]

Materials

Fluids

Application limitsMaterialsHousing/impeller

Shaft seal Mechanical seal

Housing seal

(The maximum permissi-ble operating tempera-tures and pressures of the pump series must be adhered to)

Gre

y cast

iron

/gre

y cast

iron

Gre

y cast

iron

/bronze or

plastic

1)

Standard

: AQ

1EGG

S1: Q

1Q1X

4GG

S2: A

Q1X

4GG

EPD

M

Viton

HN

BR

Heating water (in accordance with VDI 2035)(Conductivity <300 �s, silicates <10 mg/l, sol-id matter content <10 mg/l)

up to 140°C • – • – – • – –

Cooling and cold water up to -20 °C • – • – – • – –Cooling brine, inorganic, pH > 7.5, inhibited up to 30°C • – • – – • – –Water-glycol mixtures, 20-40 vol.% glycol -20 °C to 40 °C • – • – – • – –Water-glycol mixtures, 20-40 vol.% glycol 40°C to 90°C • – – � – – – �Water-glycol mixtures, 40-50 vol.% glycol -20 °C to 90 °C • – – � – – – �Water-glycol mixtures, 20-50 vol.% glycol 90°C to 120°C • – – � – – – �Water with oil in suspension 0 °C to 90 °C • – – – � – � –Mineral oil(Observe operating regulations with regard to explosion protection)

-20 °C to 140 °C • – – – � – � –

• = standard, � = special equipment1)for IPL, DPL, IP-E, DP-E standard plastic impellers, IPL and DPL in parts with grey cast iron impeller

Page 9: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

9

Planning guide

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Mechanical sealA mechanical seal is fitted as standard on all Wilo glanded pumps (ex-cept IPs) (Fig. 5). Mechanical seals are dynamic seals and are used to seal rotating shafts at medium to high pressures. The dynamic sealing area of the mechanical seal consists of two surface-ground, low-wearing faces (e.g. silicon carbide or carbon rings), which are pressed together by axial forces. The slip ring rotates with the shaft, while the counter ring remains stationary in the housing. The rings are pressed together by a spring and the fluid pressure.

Fig. 5

As a rule, there is little or no drip leakage during operation, and no maintenance work is necessary. The average service life, under aver-age operating and water conditions, is between 2 and 4 years. How-ever, extreme conditions (soiling, admixtures and overheating) may drastically reduce the service life.

Important:Mechanical seals are wearing parts. Dry running is not permissible as it will lead to the destruction of the sealing faces.The mechanical seal fitted as standard by Wilo can be used for water-glycol mixtures with 20 - 40 vol.% glycol and a fluid temperature of � 40°C.

Outside the limits of these parameters, silicate precipitation may oc-cur, which could damage the standard seals. Special versions are available on request for use outside these limits. When additives such as glycol are used, or if oil-polluted water is encountered, then in ad-dition to the suitability of the mechanical seal, it may also be neces-sary to check the performance of the pump (in the case of glycol ad-mixtures exceeding 20% volume proportion).The following formula can be applied to determine the power re-quirement P2 of a pump:

Mechanical seals – material identification codeThe materials of a mechanical seal are identified by means of a 5-part code. The "Technical data" tables for the glanded pumps contain the code for each series. The code characters relate to the following seal components:

Typical materials:

The standard seal on Wilo glanded pumps is AQ1EGG.

Cataphoretic coatingWilo glanded pumps are provided as standard with a cataphoretic coating (exceptions: IL 250, IPS, IPH-O, IPH-W, IP-Z series). External components which are susceptible to corrosion such as hexagon head bolts, couplings etc., are chromated. The advantages of these coatings lie in their resistance to corrosion caused by aggressive at-mospheres, such as humid air, condensation and an environment containing salt and chemicals. To prevent rust, pumps with cast com-ponents with a cataphoretic coating and chromated components are suitable for heating and air conditioning/cooling applications both indoors and outdoors (a special motor is required for outside applica-tions). These pumps also offer the advantage of low maintenance costs and a longer service life.

Swimming-pool water(Chloride <250 mg/l, install pump upstream of filter)

up to 35°C – � – – – – – �

Fire water up to 30°C – � – – – – – �

Materials

• = standard, � = special equipment1)for IPL, DPL, IP-E, DP-E standard plastic impellers, IPL and DPL in parts with grey cast iron impeller

P2 =ρ × Q × H367 × η

P2 Power requirement [kW]� Density [kg/dm3]Q Volume flow [m3/h]H Delivery head [m]� Pump efficiency (e.g. 0.8 at 80%)

1: Slip ring 2: Counter ring2: Secondary seals4: Spring5: Other components

1: A Carbon-graphite (antimony impregnated)

B Carbon-graphite (synthetic resin impregnated), approved for use with foods

Q1 Silicon carbide2: Q1 Silicon carbide

3: E EPDM

E3 EPDM, approved for use with foodsV VitonX4 HNBR

4: G Stainless steel

5: G Stainless steel

Page 10: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

10 Subject to change 09/2008 WILO SE

Planning guide

Thermal insulation of pumpsIn systems, which are heat-insulated, only the pump housing should be insulated, not the lantern or the motor.

Installation location/position of the pumpsThe standard pumps must be protected from the weather and in-stalled in a frost/dust-free, well-ventilated and non-explosive envi-ronment. Pipes and pumps are to be installed in a stress-free condi-tion. The pipes must be mounted in such a way that the pump does not bear the weight of the pipe.

In-line pumps are designed for direct horizontal and vertical installa-tion in a pipe. Installation with the motor and the terminal box facing downwards is not permitted. Sufficient space must be provided for the removal of motor, lantern and impeller. With a motor power in ex-cess of 18.5 kW, it is not permitted to install the pump with the pump shaft in a horizontal position. With a vertically mounted pump, the pipe must be stress-free and the pump must be supported on the pump feet.

The installation of monobloc pumps with the motor and terminal box facing downwards is not permitted. All other installation positions are possible. Monobloc pumps are to be mounted on a sufficiently strong base or brackets.

Anticipated noise levels for in-line and monobloc pumps (guideline values)

Electrical driveThe rated output values and operating values for the electrical drives specified in this catalogue for glanded pumps (in-line and monobloc) apply to a rated frequency of 50 Hz, a rated voltage of 230/400 V up to 3 kW or 400/690 V above 4 kW, a maximum coolant temperature (CT) of 40°C and an installation altitude of up to 1000 m above mean sea level. For cases outside these parameters a reduction of the rated output must be applied or a larger motor type or a higher insulation class must be selected.All Wilo glanded pumps are standard-equipped with electric motors, which meet the IEC standard in terms of output and design. A restric-tion only applies where, due to the design of the pump, coupling to a standard motor is not possible. In this case, motors with an extended shaft are used. The customary speed categories/operating speeds are as follows:

High-efficiency motor

�Wilo glanded pumps are available with EFF1 high-efficiency motors on, for a motor power in excess of 1.1 kW.

Use of explosion-protected pumps according to Directive 94/9/EG (ATEX100a)Potentially explosive areas are zones where an explosive atmosphere (gas/dust) can occur in sufficient measure to pose a risk.These areas are divided into zones. Decisions on the assignment of zones lie with the operator and the respective regulation authority.The testing of pumps (machines) and hence the approval for use in hazardous areas is governed in the EU on the basis of the relevant ex-plosion protection specification 94/9/EG (ATEX100a) by appropriate authorised institutes. Approval is granted by means of a prototype test certificate. Wilo glanded pumps of the IL, DL, BL, IPL (only version –N), DPL (only version -N), IPS and IPH series can be supplied accord-ing to the specifications for use in potentially explosive areas. These pumps have a prototype test certificate in accordance with Di-rective 94/9/EG (ATEX100a), which permits the following designa-tions to be applied:

Motor powerPN [kW]

Sound-pressure level pA (dB) 1)

Pump with motor

1450 rpm 2900 rpm< 0.55 52 550.75 53 581.1 54 581.5 54 612.2 57 623.0 58 644.0 58 675.5 63 707.5 64 7111.0 67 7415.0 68 7518.5 67 7622.0 67 7730.0 69 7837.0 68 7445.0 68 7455.0 68 7875.0 70 8090.0 70 80110.0 72 82

1)Spatial mean value of sound pressure levels on a square measuring surface at a distance of 1 m from the surface of the motor

132.0 72 82160.0 72 82

Number of poles 50 Hz 60 Hz

2 2900 rpm 3500 rpm4 1450 rpm 1750 rpm6 950 rpm 1150 rpm

II 2 G c b II A T3, T4 / II 2 G c b II C T3, T4

CE CE markingII Device group

Motor powerPN [kW]

Sound-pressure level pA (dB) 1)

Pump with motor

1)Spatial mean value of sound pressure levels on a square measuring surface at a distance of 1 m from the surface of the motor

Page 11: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

11

Planning guide

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Particular attention must be paid to ensure that for applications in the T4 temperature range, the pumps and mechanical seals are addi-tionally protected against dry running.This can take the form, for example, of monitoring the differential pressure or the nominal motor power.

The motors have their own specific designations, e.g. EEX eII T3which stands for:

and must also be approved in accordance with Directive 94/9/EG (ATEX100a). The approved operating conditions are listed in the following matrix:

Important:Attention must also be paid in each application case to the special features relating to the dependency on temperature, pressure, fluid and mechanical seal. The pumps may only be used for the permitted fluids listed in the following matrix (II B). However, outside the pump, the presence of gases according to the EX groups and temperature classes is permitted (II C).

G Explosive atmosphere due to gases, vapours and mistC Design safety (protection due to safe design)b Ignition source monitoring with T4

T1 - T4 Temperature class with maximum surface temperatureT1 450 °CT2 300 °CT3 200 °CT4 135 °C

E/D Motor ignition protection categorye Increased safetyd Pressure-proof enclosure

E Motor according to European standardEx Explosion protectione Ignition protection category "Increased safety"II Motor for potentially explosive areasT3 Temperature class

Matrix of permissible operating conditions

Mechanical seal

Number of motor poles

IL/DL/BL IPL/DPL

Maximum permissiblefluid temperature

Maximum permissiblefluid temperature

T41) T3 T41) T3

Fluid II A P = 10 bar P = 16 bar P = 10 bar P = 16 bar P = 10 bar P = 10 bar

Heating water in accordance with VDI 2035 Standard

2-pole 100 °C 90 °C 140 °C 120 °C 120 °C 120 °C

4-pole 115 °C 110 °C 140 °C 120 °C 120 °C 120 °C

Partially desalinated water with:conductivity > 80 �s, silicates < 10 mg/ l, pH value > 9

Standard

2-pole 100 °C 90 °C 140 °C 120 °C 120 °C 120 °C

4-pole 115 °C 110 °C 140 °C 120 °C 120 °C 120 °C

Mineral oilG2 / S2

2-pole 75 °C 50 °C 140 °C 115 °C 105 °C 120 °C

4-pole 95 °C 80 °C 140 °C 120 °C 115 °C 120 °C

Heating water with: conductivity < 850 �s, silicates < 10 mg/ l, solid matter content < 10 mg/ l

Standard

2-pole 100 °C 90 °C 120 °C 120 °C 120 °C 120 °C

4-pole 115 °C 110 °C 120 °C 120 °C 120 °C 120 °C

CondensateStandard

2-pole 100 °C 90 °C 100 °C 100 °C 100 °C 100 °C

4-pole 100 °C 100 °C 100 °C 100 °C 100 °C 100 °C

Cooling brine, inorganic; pH value > 7.5, inhibited Standard 20 °C 20 °C 20 °C 20 °C 20 °C 20 °C

Water with oil contamination G2 / S2 90 °C 90 °C 90 °C 90 °C 90 °C 90 °C

Cooling water with antifreeze (pH value: 7.5-10; no galvanised components)

Standard 40 °C 40 °C 40 °C 40 °C 40 °C 40 °C

Water-glycol mixture (20% - 40% glycol) Standard 40 °C 40 °C 40 °C 40 °C 40 °C 40 °C

1)Pumps and mechanical seals must be additionally protected against dry running in the T4 temperature range.This can be achieved by monitoring the differential pressure or the nominal power of the motor.

Page 12: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

12 Subject to change 09/2008 WILO SE

Planning guide

�The use of solvents is not permitted, since they could corrode the elastomers in the seals. In turn, this can lead to uncontrolled leakage!

Scope of deliveryPump, including packaging, installation and operating instructions

AccessoriesElectronically controlled in-line pumps:

- IF-Module: PLR or LON for the IP-E, DP-E, IL-E, DL-E series (also see catalogue section: "Switchgears and control systems").

- IR-Monitor for the IP-E, DP-E, IL-E, DL-E series. Interface converter along the same lines (also see catalogue section: "Switchgears and control systems").

-Digital interface converter (also see catalogue section: "Switchgears and control systems").

- Brackets for installation on a base- Blind flanges for double pumps

Uncontrolled in-line and monobloc pumps:-Wilo control system for infinitely variable speed control for pump op-eration according to requirements.

- Switchgears for the automatic control of duty pumps and standby pumps (also see catalogue section: "Switchgears and control sys-tems").

- Brackets for installation on a base- Blind flanges for double pumps

Pump duty splittingIn the context of infinitely variable output control, the "split solution" is available for optimisation, starting with the medium pump output range (1–1.5 kW), i.e. instead of using a large pump, the maximum output is split up between two smaller pump units or a double pump.In the normal case, i.e. for more than 85% of the heating season, one pump is adequate as the basic load unit. The second pump is available to fulfil peak-load requirements.

Important:The extra costs for the pumps are more than compensated for by power savings by the control device.

Advantages of pump duty splitting:- Electricity savings of between 50% and 70%-A second pump is always available on standby.With the so-called "split solutions", one pump is operated for basic load requirements, while the other pumps are cut in for parallel peak-load operation.This ensures that the design requirement is in accordance with DIN 4701. In conjunction with controlled units, continuous adjustment to the load demand can be achieved over the entire performance range.

Important:Wilo control systems for double-pump or multi-pump installations feature the peak-load cut-in option.

Fig.: Infinitely variable controlled peak-load operation of a double pump with two motor impeller units of equal power.

Key:

Investment costsThe total investment costs in heating systems can be reduced by al-most 1/4 using "split solutions". Particularly when use is made of dou-ble pumps instead of single pumps, with their very high installation costs (Y-pipes, etc.)

Important:Due to their low outlet velocities, Wilo double pumps are particularly suitable for parallel operation.

Operating costsConsiderable reductions in the operating costs also ensured as a re-sult of the significant savings in current of the low-output "split units", due to the improved utilisation in the partial load range and, in particular, in the low-load range.

StandbyFrom an operating point of view, there are other advantages, since in the event of a fault in the partial load range or the low-load range, a 100% standby option is available and in the peak-load range, on the few extremely cold days, there is a so-called emergency standby (75%).

PH Main pumpPS Peak-load pumpQV Full load volume flowQT Partial load volume flowP1V Full load power consumptionP1T Partial load power consumption

0

50

100

0

40

n = 60 %

n = 100 %

n = 2 x 100 %100

PH

QT

P1T

P1V

50 % QV 100 %

PSPH +

�p = constant

Del

iver

y he

ad H

[%]

Q[%]

Pow

er re

quire

men

t P[%

]

Page 13: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

13

Planning guide

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Principle of operationThe duty pump and base-load pump are speed-controlled. With the full stabilisation of this unit, i.e. with the nominal pump speed reached and at the start of the peak-load requirement, the peak-load unit is switched on at a fixed speed (nominal speed), while the power of the controlled base-load pump is directly reduced and adjusted to the load point. Resulting pressure fluctuations are relatively minor and in practice have no appreciable effect. During parallel operation, the output of the constant-speed peak-load unit and the controlled base-load unit are added according to the volume flow, which in this operating situation readjusts to the respective peak-load require-ment.The switch-point for cutting in the peak-load pump is determined by means of an internal electronic assessment logic.

Important:Peak-load switching of Wilo control systems is only possible with control modes according to the differential pressure or differential temperature.More information on pump controls is available in the catalogue sec-tion: "Switchgears and control systems".

Double pump switchingThere are two different operating modes for the operation of double pumps:

- Standby switching for the individual operation of the duty pump.- Peak-load switching for the parallel operation of both pumps, which are also overridden by a control option on the respective duty pump.

Operating modes

Duty pump uncontrolled

Duty pump controlled via Wilo control system

Operating functionsWilo switchgears feature the following operating functions:A Standby switching, fault-dependent or time-dependent operation switchover pump I <-> pump II.B Peak-load operation for load-dependent or time-dependent auto-matic power adjustment by activation or deactivation of the second pump.C Infinitely variable speed control of the duty pump for load-depend-ent or time-dependent automatic power adjustment when the sec-ond pump is cut in for infinitely variably controlled peak-load opera-tion.

S2R 3D/SD seriesSwitchgears for the automatic control of duty and standby pumps of double units. Automatic fault-actuated switchover from duty to standby pump. With clock timer for regular duty pump and standby pump cycling. Additional peak-load switching by standard cut-in op-tion for the 2nd pump.Short-term parallel operation is integrated into the changeover se-quence to avoid the occurrence of valve noise during uncontrolled switchover.Version in ISO housing, protection class: IP 41. Potential-free contact for collective fault signal.Connection options to three-phase current 400 V, 50 Hz, or three-phase current 230 V, 50 Hz.Other voltages and frequencies available as special version on request.

Standby mode Peak-load operation

Pump I or Pump II in operation Both pumps in operation

Pump I Pump II Pumps I + II

Investment costs: Lower Higher

Operating costs: High Low

Pump I Pump II Pumps I + II

IInvestment costs (including control):

Higher Lower

Operating costs: Higher Low

Switching function

Switchgear A B C

SD series (standby/cut-in) • • •S2R 3D (standby/cut-in) • • •CR system (infinitely variable) • • •

Technical data

Switchgear type Motor power [kW]S2R 3D 0.37-3SD 5.5 4-5.5SD 9 7.5-9SD 18.5 11-18.5SD 30 22-30SD 37 37

Page 14: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

14 Subject to change 09/2008 WILO SE

Planning guide

Pump controlWhen Wilo pumps are operated with control devices or module ac-cessories, the electrical operating conditions in accordance with VDE 0160 are to be complied with.When operating glandless and glanded pumps with brands of fre-quency converters other than those supplied by Wilo, output filters for reducing motor noise and for preventing harmful voltage peaks are to be used and the following limit values are to be complied with:Glandless pumps with P2 � 1.3 kW and glanded pumps with P2 � 1.1 kW

-Rate of voltage rise du/dt < 500 V/�s-Voltage peaks û < 650 V

For the noise reduction of glandless pump motors, it is recommended that sine filters (LC filters) be used rather than du/dt filters (RC fil-ters).

Glanded pumps with P2 > 1.1 kW-Rate of voltage rise du/dt < 500 V/�s-Voltage peaks û < 850 V

Installations with long cable lengths (l > 10 m) between converter and motor may increase the du/dt and û levels (resonance). The same applies to operation with more than 4 units at one power supply source. The output filters must be selected as recommended by the converter manufacturer or filter supplier.The pumps must be operated at a maximum of 95% of their nominal speed if the frequency converter causes motor losses. The following limit values at the pump connection terminals must not be fallen short of if glandless pumps of the TOP-S/-SD, TOP-D and TOP-Z se-ries are operated with a frequency converter: Umin = 150 Vfmin = 30 Hz.

Page 15: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

The knowledge database from Wilo.

500 answers to FAQs.Used 9000 times in 14 days.

1001 new suggestions.For even more expert knowledge.

Did you know? The knowledge database from Wilo will give you good and quickadvice: with approx. 500 responses to the most frequently asked questions (FAQs)all about pumps, installations and systems. It is already being visited extensively bymany skilled craftsmen.This is proven by 9000 utilisations in only 14 days, which werecently registered. The best thing: With every new question which you ask uswith the contact form, we all become wiser together. Because the correspondinganswer is naturally incorporated as soon as possible. Know-how? We call this Pumpen Intelligenz.

www.wilo.com

Page 16: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

16 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle in-line pumps, double in-line pumps

Series overview

Energy-saving pumps Single in-line pumps, double in-line pumps Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroLine-IP-E

>Design

Electronically controlled glanded single pump in in-line design with flange connec-tion and automatic power adjustment

>ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cool-ing water systems

Series: Wilo-CronoLine-IL-E

>Design

Electronically controlled glanded single pump in in-line design with flange connec-tion and automatic power adjustment

>ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cool-ing water systems

Series: Wilo-CronoLine-IL-E...BF

>Design

Electronically controlled glanded single pump in in-line design with flange connec-tion and automatic power adjustment

>ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cool-ing water systems

H[m

]

Q[m³/h]80 9040 6020 7030 501000

5

10

15

20

25

Wilo-VeroLine-IP-E

65/140-4/2

80/115-2,2/2

80/130-3/2

80/140-4/265/130-3/2

50/140-3/250/115-0,75/2

65/115-1,5/2

50/150-4/2

40/160-4/2

40/115-0,55/2

32/160-1,1/2

40/150-3/2

50/130-2

,2/2

40/120-1,5/2

40/130-2,2/2

32/110-0,75/232/100-0,55/2

H[m

]

Q[m³/h]1208040 100602000

5

10

15

20

25

30

Wilo-CronoLine-IL-E

80/140-7,5/265/150-5,5/2

50/170-7,5/2

40/170-5,5/2

H[m

]

Q[m³/h]400200 300 50010000

10

20

30

40

50

60Wilo-CronoLine-IL-E...BF

100/8-33100/6-29

80/9-48

80/8-42

100/5-26100/5-21

80/8-40

65/11-64

65/9-55

80/8-3

1

65/9-46

50/10-60

65/8-40

40/11-64

150/3-20150/3-18

150/2-15

100/4-2

3

200/4-19

200/2-15

150/5-23

50/9-52

200/3-18

Page 17: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

17

Energy-saving pumpsSingle in-line pumps, double in-line pumps

Energy-saving pumps

Series overview

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single in-line pumps, double in-line pumps Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroLine-IP-E

> Special features/product benefits• Improved functionality• Energy savings due to integrated electronic performance control• Control mode �p-c for constant and �p-v for variable differential pressure at the pump • Manual control mode (0–10 V/0–20 mA; 2–10 V/4–20 mA)• Volume flow tendency indication• Integrated full motor protection (PTC thermistor sensor) with trip electronics• Simple operation due to red-button technology, display and infrared interface (IR-Monitoring)• Optional interfaces due to retrofit IF-Modules for bus communication (LON or PLR)• Integrated dual pump management• High corrosion protection due to cataphoretic coating

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Equipment/function . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . . • Wilo Control pump management systems . . . . . . . . . . . . . . . . . . . . . . . . .

Page7202428303941216

248

Series: Wilo-CronoLine-IL-E

> Special features/product benefits• Reduced life cycle costs due to optimised efficiency• Improved functionality• Energy savings due to integrated electronic performance control• Control mode �p-c for constant and �p-v for variable differential pressure at the pump • Manual control mode (0–10 V/0–20 mA; 2–10 V/4–20 mA)• Volume flow tendency indication• Integrated full motor protection (PTC thermistor sensor) with trip electronics• Simple operation due to red-button technology, display and infrared interface (IR-Monitoring)• Optional interfaces due to retrofit LON or PLR IF-Modules for bus communication• Integrated dual pump management• High corrosion protection due to cataphoretic coating• Can be used flexibly in air-conditioning and cooling systems with application benefits due to the direct draining of condensate via optimised lantern design

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Equipment/function . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . . • Wilo Control pump management systems . . . . . . . . . . . . . . . . . . . . . . . . .

Page7202443454748216

248

Series: Wilo-CronoLine-IL-E...BF

> Special features/product benefits• Powerful, up to 22 kW• Control mode �p-c for constant differential pressure at the pump• Manual control mode (0–10 V/0–20 mA)• Integrated full motor protection (PTC thermistor sensor) with trip electronics• High corrosion protection due to cataphoretic coating

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Equipment/function . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . . • Wilo Control pump management systems . . . . . . . . . . . . . . . . . . . . . . . . .

Page7202449519959216

248

Page 18: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

18 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle in-line pumps, double in-line pumps

Series overview

Energy-saving pumps Single in-line pumps, double in-line pumps Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroTwin-DP-E

>Design

Electronically controlled glanded double pump in in-line design with flange connec-tion and automatic power adjustment

>ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cool-ing water systems

Series: Wilo-CronoTwin-DL-E

>Design

Electronically controlled glanded double pump in in-line design with flange connec-tion and automatic power adjustment

>ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cool-ing water systems

Series: Wilo-CronoTwin-DL-E...BF

>Design

Electronically controlled glanded double pump in in-line design with flange connec-tion and automatic power adjustment

>ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cool-ing water systems

H[m

]

Q[m³/h]80 12040 60 1002000

5

10

15

20

25 +Wilo-VeroTwin-DP-E

65/140-4/2

80/115-2,2/2

80/130-3/2

80/140-4/2

65/130-3/2

50/140-3/2

50/115-0,75/265/115-1,5/2

40/160-4/2

40/115-0,55/2

32/160-1,1/2 40/120-1,5/2

40/130-2,2/232/110-0,75/232/100-0,55/2

40/150-3/2 50/150-4/2

50/130-2,2

/2

H[m

]

Q[m³/h]1801601208040 140100602000

5

10

15

20

25

30+

Wilo-CronoTwin-DL-E

80/140-7,5/265/150-5,5/2

50/170-7,5/2

40/170-5,5/2

0

20

30

40

50

60

70

10

250 300

H[m

]

Q[m³/h]0 20015010050

Wilo-CronoTwin-DL-E...BF

+

DL-E 80/8-40 BF

DL-E 65/8-40 BF

DL-E 100/8-33 BF

DL-E 150/2-15 BF

DL-E

50/

10-6

0 BF

DL-E

50/

9-52

BF

DL-

E 40

/11-

64 B

F

Page 19: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

19

Energy-saving pumpsSingle in-line pumps, double in-line pumps

Energy-saving pumps

Series overview

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single in-line pumps, double in-line pumps Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroTwin-DP-E

> Special features/product benefits• Energy savings due to integrated electronic performance control• Control mode �p-c for constant and �p-v for variable differential pressure at the pump• Manual control mode (0–10 V/0–20 mA; 2–10 V/4–20 mA)• Simple operation due to red-button technology, display and infrared interface (IR-Monitoring)• Integrated full motor protection (PTC thermistor sensor) with trip electronics• Optional interfaces due to retrofit IF-Modules for bus communication, LON or PLR• Integrated dual pump management• High corrosion protection due to cataphoretic coating

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Equipment/function . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . . • Wilo Control pump management systems . . . . . . . . . . . . . . . . . . . . . . . . .

Page7202461638183216

248

Series: Wilo-CronoTwin-DL-E

> Special features/product benefits• Reduced life cycle costs due to optimised of efficiency• Energy savings due to integrated electronic performance control• Control mode �p-c for constant and �p-v for variable differential pressure at the pump• Manual control mode (0–10 V/0–20 mA; 2–10 V/4–20 mA)• Red-button technology for simplest operation• Integrated full motor protection (PTC thermistor sensor) with trip electronics• Simple operation due to infrared interface (IR-Monitoring)• Optional interfaces due to retrofit IF-Modules for bus communication, LON or PLR• Integrated dual pump management• High corrosion protection due to cataphoretic coating• Bidirectional mechanical seal with forced flushing• Easy to install due to pump housing with feet and threaded holes

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Equipment/function . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . . • Wilo Control pump management systems . . . . . . . . . . . . . . . . . . . . . . . . .

Page7202485879192216

248

Series: Wilo-CronoTwin-DL-E...BF

> Special features/product benefits• Control mode �p-c for constant differential pressure at the pump• Manual control mode (0–10 V/0–20 mA)• Integrated full motor protection (PTC thermistor sensor) with trip electronics• Powerful, up to 22 kW

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Equipment/function . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . . • Wilo Control pump management systems . . . . . . . . . . . . . . . . . . . . . . . . .

Page72024939599100216

248

Page 20: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

20 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Equipment/functionEnergy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Equipment/function Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo- VeroLine-IP-E Wilo- CronoLine-IL-E

Wilo- CronoLine-IL-E...BF

Wilo- CronoLine-IL-E...BF R1

Operating modes

�p-c for constant differential pressure

• • ••

(Differential pressure sensor required

onsite)

�p-v for variable differential pressure • • – –

Manual control mode (0 - 10 V) for connection to external control unit (DDC) • • – •

Manual control mode (2 - 10 V) for connection to external control unit (DDC) • • – –

Manual control mode (0 - 20 mA) for connection to external control unit (DDC) • • – •

Manual control mode (4 - 20 m) for connection to external control unit (DDC) • • – –

Manual functions

Differential-pressure setpoint setting• •

•(Pressure gauge re-

quired onsite)–

Pump ON/OFF setting • • – –

Speed setting (manual control mode) • • – –

Manual control panel • • • –

Automatic functions

Infinitely variable performance control �p-c • • • •

Infinitely variable performance control �p-v • • – –

Full motor protection with integrated trip electronics • • • •

External control functions

Overriding Off • • • •Analogue In 0 ... 10 V • • – •Analogue In 0 ... 20 mA • • – •

Signal and display functions

Collective fault signal (potential-free NC contact) • • • •Collective run signal • • • •Fault signal light • • • •Fault acknowledgement button • • • •LC display for indication of pump data and fault codes • • – –

Data exchange

Infrared interface for wireless data exchange with IR-Module/IR-Monitor (see IR-Module/IR-Monitor function table)

• • – –

Page 21: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

21

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Equipment/function

Energy-saving pumps

PLR serial digital interface for connection to BA via Wilo interface converter or company-specific cou-pling modules

•with 1 x IF-Module (accessory)

Serial digital LON interface for connection to a LON-WORKS network

•with 1 x IF-Module (accessory)

Dual pump management (double pump or 2 x single pump)

Main/standby mode (automatic fault-actuated switchover) • • – –

Main/standby mode pump cycling after 24 hours • • – –

Parallel operation • • – –

Parallel operation (efficiency-optimised peak-load cut-in and out) • • – –

• = available, - = not available

Wilo- VeroLine-IP-E Wilo- CronoLine-IL-E

Wilo- CronoLine-IL-E...BF

Wilo- CronoLine-IL-E...BF R1

Page 22: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

22 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Equipment/functionEnergy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Equipment/function Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo- VeroTwin-DP-E

Wilo- CronoTwin-DL-E

Wilo- CronoTwin-DL-E...BF

Wilo- CronoTwin-DL-E...BF R1

Operating modes

�p-c for constant differential pressure

• • ••

(Differential pressure sensor required

onsite)

�p-v for variable differential pressure • • – –

Manual control mode (0 - 10 V) for connection to external control unit (DDC) • • – •

Manual control mode (2 - 10 V) for connection to external control unit (DDC) • • – –

Manual control mode (0 - 20 mA) for connection to external control unit (DDC) • • – •

Manual control mode (4 - 20 m) for connection to external control unit (DDC) • • – –

Manual functions

Differential-pressure setpoint setting• •

•(Pressure gauge required onsite)

Pump ON/OFF setting • • – –

Speed setting (manual control mode) • • – –

Manual control panel • • • –

Automatic functions

Infinitely variable performance control �p-c • • • •

Infinitely variable performance control �p-v • • – –

Full motor protection with integrated trip electronics • • • •

External control functions

Overriding Off •(only on master

pump)

•(only on master

pump)• •

Analogue In 0 ... 10 V • • – •

Analogue In 0 ... 20 mA • • – •

Signal and display functions

Collective fault signal (potential-free NC contact) • • • •

Collective run signal • • • •

Fault signal light • • • •

Fault acknowledgement button • • • •

LC display for indication of pump data and fault codes • • – –

Page 23: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

23

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Equipment/function

Energy-saving pumps

Data exchange

Infrared interface for wireless data exchange with IR-Module/IR-Monitor (see IR-Module/IR-Monitor function table)

• • – –

PLR serial digital interface for connection to BA via Wilo interface converter or company-specific cou-pling modules

•with 1 x IF-Module (accessory)

Serial digital LON interface for connection to a LON-WORKS network

•with 1 x IF-Module (accessory)

Dual pump management (double pump or 2 x single pump)

Main/standby mode (automatic fault-actuated switchover) • • • •

Main/standby mode pump cycling after 24 hours • • – –

Parallel operation • • • •Parallel operation (efficiency-optimised peak-load cut-in and out) • • – –

• = available, - = not available

Wilo- VeroTwin-DP-E

Wilo- CronoTwin-DL-E

Wilo- CronoTwin-DL-E...BF

Wilo- CronoTwin-DL-E...BF R1

Page 24: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

24 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Technical dataEnergy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Technical data Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo- VeroLine-IP-E Wilo- CronoLine-IL-E

Wilo- CronoLine-IL-E...BF

Wilo- CronoLine-IL-E...BF R1

Approved fluids (other fluids on request)

Heating water (in accordance with VDI 2035) • • • •Water-glycol mixtures (for 20-40 vol.% glycol and fluid temperature � 40 °C) • • • •

Cooling and cold water • • • •Heat transfer oil Special version at additional charge

Permitted field of application

Standard version for operating pressure, pmax [bar]10

13 (up to +140°C)16 (up to +120°C)

Special version for operating pressure, pmax [bar] 16 - - -

Temperature range [°C] - 10 to + 120 - 20 to + 140 - 20 to + 140 - 20 to + 140

Max. ambient temperature [°C] 40 (50 on request) 40 40 40

Installation in closed buildings • • • •Outdoor installation – – – –

Pipe connections

Nominal connection diameters DN 32 - 80 40 - 80 40 - 200 40 - 200

Flanges (according to EN 1092-2) PN 16 (only flange fixing

holes in accordance with EN 1092-2)

PN 16 PN 16 PN 16

Materials

Pump housing EN-GJL-250 EN-GJL-250 (EN-GJS-400 on request)

Lantern EN-GJL-250 EN-GJL-250 (EN-GJS-400 on request)

Impeller (standard) PP, fibreglass-rein-forced EN-GJL-200

Impeller (special version) - G-CuSn10

Pump shaft 1.4021 1.4122

Mechanical seal AQEGG

Other mechanical seals On request (at additional charge)

Electrical connection

Mains connection 3~400 V, 50 Hz3~380 V, 60 Hz

Speed range [rpm] 1100 - 2900 750-2900 750-2900375-1450

Motor/electronics

Integrated full motor protection Standard PTC thermistor sensor (TRS)

Protection class IP 55 IP 55 IP 54 IP 54

Insulation class F F F F

Emitted interference EN 61800-3

Page 25: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

25

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Technical data

Energy-saving pumps

Interference resistance EN 61800-3

Residual-current protection device (RCD) • • • •

Installation options

Pipe installation (� 15 kW motor power) • • • •Support-bracket mounting • • • •

• = available, - = not available

Note on emitted interference and interference resistance for IL-E...BF and IL-E...BF R1:The standard version complies with the limit values for the first environment with limited availability.EMC radio interference suppression filter for mains-side interference EN 61800-3 Class B/1 - available as an accessory for switch cabinet installation

Wilo- VeroLine-IP-E Wilo- CronoLine-IL-E

Wilo- CronoLine-IL-E...BF

Wilo- CronoLine-IL-E...BF R1

Page 26: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

26 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Technical dataEnergy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Technical data Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo- VeroTwin-DP-E

Wilo- CronoTwin-DL-E

Wilo- CronoTwin-DL-E...BF

Wilo- CronoTwin-DL-E...BF R1

Approved fluids (other fluids on request)

Heating water (in accordance with VDI 2035) • • • •Water-glycol mixtures (for 20-40 vol.% glycol and fluid temperature � 40 °C) • • • •

Cooling and cold water • • • •Heat transfer oil Special version at additional charge

Permitted field of application

Standard version for operating pressure, pmax [bar]10

13 (up to +140°C)16 (up to +120°C)

Special version for operating pressure, pmax [bar] 16 - - -

Temperature range [°C] - 10 to + 120 - 20 to + 140 - 20 to + 140 - 20 to + 140

Max. ambient temperature [°C] 40 (50 on request) 40 40 40

Installation in closed buildings • • • •Outdoor installation – – – –

Pipe connections

Nominal connection diameters DN 32 - 80 40 - 80 40 - 200 40 - 200

Flanges (according to EN 1092-2) PN 16 (only flange fixing ho-les in accordance with

EN 1092-2)

PN 16 PN 16 PN 16

Materials

Pump housing EN-GJL-250 EN-GJL-250 (EN-GJS-400 on request)

Lantern EN-GJL-250 EN-GJL-250 (EN-GJS-400 on request)

Impeller (standard) PP, fibreglass-rein-forced EN-GJL-200

Impeller (special version) - G-CuSn10

Pump shaft 1.4021 1.4122

Mechanical seal AQEGG

Other mechanical seals On request (at additional charge)

Electrical connection

Mains connection 3~400 V, 50 Hz3~380 V, 60 Hz

Speed range [rpm] 1100 - 2900 750-2900 750-2900375-1450

Motor/electronics

Integrated full motor protection Standard PTC thermistor sensor (TRS)

Protection class IP 55 IP 55 IP 54 IP 54

Insulation class F F F F

Emitted interference EN 61800-3

Page 27: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

27

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Technical data

Energy-saving pumps

Interference resistance EN 61800-3

Residual-current protection device (RCD) • • • •

Installation options

Pipe installation (� 15 kW motor power) • • • •Support-bracket mounting • • • •

• = available, - = not available

Note on emitted interference and interference resistance for DL-E...BF and DL-E...BF R1:The standard version complies with the limit values for the first environment with limited availability.EMC radio interference suppression filter for mains-side interference EN 61800-3 Class B/1 - available as an accessory for switch cabinet installation

Wilo- VeroTwin-DP-E

Wilo- CronoTwin-DL-E

Wilo- CronoTwin-DL-E...BF

Wilo- CronoTwin-DL-E...BF R1

Page 28: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

28 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-VeroLine-IP-E

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroLine-IP-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignElectronically controlled glanded single pump in in-line design with flange connection and automatic power adjustment

ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive sub-stances in heating, cold water and cooling water systems

Scope of delivery• Pump • Installation and operating instructions

Type key

Technical data• Permissible temperature range -10°C to +120°C• Mains connection 3~400 V, 50 Hz; 3~380 V, 60 Hz• Protection class IP 55• Nominal diameter DN 32 to DN 80• Max. operating pressure 10 bar (special version: 16 bar)

Special features/product benefits• Improved functionality• Energy savings due to integrated electronic performance control• Control mode �p-c for constant and �p-v for variable differential pressure at the pump

• Manual control mode (0–10 V/0–20 mA; 2–10 V/4–20 mA)• Volume flow tendency indication• Integrated full motor protection (PTC thermistor sensor) with trip electronics

• Simple operation due to red-button technology, display and infrared interface (IR-Monitoring)

• Optional interfaces due to retrofit IF-Modules for bus communication (LON or PLR)

• Integrated dual pump management• High corrosion protection due to cataphoretic coating

Materials• Pump housing and lantern: EN-GJL-250• Impeller: PP, fibreglass-reinforced• Shaft: 1.4021• Mechanical seal: AQ1EGG; other mechanical seals on request

Description/designSingle-stage, low-pressure centrifugal pump in in-line design with

• Mechanical seal • Flange connection• Drive with integrated electronic speed control

Example IIP-E 40/160-4/2

IP-E In-line pump with electronic control

40 Nominal diameter DN of the pipe connection

160 Nominal impeller diameter

4 Nominal motor power P2 in kW

2 Number of poles

R1 Version without pressure sensor

Page 29: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

29

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Series description Wilo-VeroLine-IP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroLine-IP-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Q[m³/h]0 20 60 804010 50 7030 10090

H[m]

0

10

15

20

25

5

Wilo-VeroLine-IP-E

65/140-4/2

80/115-2,2/2

80/130-3/2

80/140-4/265/130-3/2

50/140-3/250/115-0,75/2

65/115-1,5/2

50/150-4/2

40/160-4/2

40/115-0,55/2

32/160-1,1/2

40/150-3/2

50/130-2

,2/2

40/120-1,5/2

40/130-2,2/2

32/110-0,75/2

32/100-0,55/2

Page 30: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

30 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroLine-IP-E

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-VeroLine-IP-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IP-E 32/100-0,55/2

�p-c (constant)

Wilo-VeroLine-IP-E 32/100-0,55/2

�p-v (variable)

Wilo-VeroLine-IP-E 32/110-0,75/2

�p-c (constant)

Wilo-VeroLine-IP-E 32/110-0,75/2

�p-v (variable)

0

2

4

6

8

10

12

14

H [

m]

0

5

10

0

0,2

0,4

0,6

0,8

P1

[k

W]

0 2 4 6 8 10 [m³/h]

NP

SH

[m

]

0 1 2 3 [l/s]

0 2 4 6 8 10 [m³/h]

Q

12

12

Wilo-VeroLine-IP-E

32/100-0,55/2

Δ p-c

max.

max.

8 m 6 m 5 m 4 m 2 m10 m

0

2

4

6

8

10

12

14

H [

m]

0

5

10

0

0 2 4 6 8 10

NP

SH

[m

]

0 1 2 3

0 2 4 6 8 10

0,2

0,4

0,6

0,8

P1

[k

W]

[m³/h]

[l/s]

[m³/h]

Q

max.

max.

Δ p-v

10 m

8 m

Wilo-VeroLine-IP-E

32/100-0,55/2

0

2

4

6

8

10

12

14

16

0 2 4 6 8 10 12

H [

m]

0

5

10

NP

SH

[m

]

0 1 2 3

00 2 4 6 8 10 12

P1

[k

W]

[m³/h]

[l/s]

[m³/h]

0,2

0,4

0,6

0,8

1,0

1,2Q

Wilo-VeroLine-IP-E

32/110-0,75/2

12 m 10 m8 m

max.

Δ p-c

max.

6 m

4 m

0 2 4 6 8 10

H [

m]

0

5

10

0 1 2 3

0 2 4 6 8 10

P1

[k

W]

0

2

4

6

8

10

12

14

16

NP

SH

[m

]

[m³/h]

[l/s]

[m³/h]0

0,2

0,4

0,6

0,8

1,0Q

Wilo-VeroLine-IP-E

32/110-0,75/2

max.

10 m 8 m

max.

Δ p-v

12 m

Page 31: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

31

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroLine-IP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IP-E 32/160-1,1/2

�p-c (constant)

Wilo-VeroLine-IP-E 32/160-1,1/2

�p-v (variable)

Wilo-VeroLine-IP-E 40/115-0,55/2

�p-c (constant)

Wilo-VeroLine-IP-E 40/115-0,55/2

�p-v (variable)

Wilo-VeroLine-IP-E32/160-1,1/2

max. N

PS

H [

m]

p-c

max.

8 m5 m

12 m 16 m 19 m 22 m

0 12 10 6 8 4 0

10

15

20

25

30

5

2

00,20,40,60,81,01,41,41,6

H [

m]

P1

[k

W]

Q

[m³/ h]

[m³/ h]10 126 840 2

[l/s]

0 2 4 6

2 32,5 3,51,510,50

Wilo-VeroLine-IP-E32/160-1,1/2

max.

NP

SH

[m

]

p-v

max.

12 m

10 m14 m 16 m

20 m 22 m

0 12 10 6 8 4 0

10

15

20

25

30

5

2

00,20,40,60,81,01,21,41,6

H [

m]

P1

[k

W]

Q

[m³/ h]

[m³/ h]10 126 840 2

[l/s]

0 2 4 6

2 32,5 3,51,510,50

Wilo-VeroLine-IP-E40/115-0,55/2

NP

SH

[m

]

max.

5 m7 m

9 m

4 m2 m

10 m

max.

p-c

0 0 20 10 15 5 0

6

8

10

12

14

4

2

4

0

0,3

0,6

0,9

653210

H [

m]

P1

[k

W]

Q

[m³/ h]

2010 155 [m³/ h]0

[l/s]

2 1

3 4

Wilo-VeroLine-IP-E40/115-0,55/2

NP

SH

[m

]

max.

max.

p-v

6 m8 m

4 m

10 m

0 0 20 10 15 5 0

6

8

10

12

14

4

2

4

0

0,3

0,6

0,9

653210

H [

m]

P1

[k

W]

Q

[m³/ h]

2010 155 [m³/ h]0

[l/s]

2 1

3 4

Page 32: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

32 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroLine-IP-E

Wilo-VeroLine-IP-E 40/120-1,5/2

�p-c (constant)

Wilo-VeroLine-IP-E 40/120-1,5/2

�p-v (variable)

Wilo-VeroLine-IP-E 40/130-2,2/2

�p-c (constant)

Wilo-VeroLine-IP-E 40/130-2,2/2

�p-v (variable)

0 5 10 15 20 25 30

H [

m]

0 2 4 6 8

0

0,5

1,0

1,5

2,0

0 5 10 15 20 25 30

P1

[k

W]

[m³/h]

[l/s]

[m³/h]

Q

35

35

10

0

2

4

6

8

10

12

14

16

18

20

0

5

10

NP

SH

[m

]

Wilo-VeroLine-IP-E

40/120-1,5/2

12 m 10 mm

ax.

Δ p-c

max.

5 m15 m 8 m

3 m

0 5 10 15 20 25 30

H [

m]

0 2 4 6 8

0

0,5

1,0

1,5

2,0

0 5 10 15 20 25 30

P1

[k

W]

[m³/h]

[l/s]

[m³/h]

Q

35

35

10

0

2

4

6

8

10

12

14

16

18

20

0

5

10

15

NP

SH

[m

]

Wilo-VeroLine-IP-E

40/120-1,5/2

16 m 14 m

max.

10 m12 m 8 m

max.

Δ p-v

0 5 10 15 20 25 30 35

H [

m]

0

5

10

0 2 4 6 8 10

0

1,0

2,0

3,0

0 5 10 15 20 25 30 35

P1

[k

W]

[m³/h]

[l/s]

[m³/h]

Q

40

40

0

2

4

6

8

10

12

14

16

18

20

22

NP

SH

[m

]

Wilo-VeroLine-IP-E

40/130-2,2/2

15 m 12 m

max.

max.

7 m17 m 9 m

4 m

Δ p-c

0 5 10 15 20 25 30 35

H [

m]

0

5

10

0 2 4 6 8 10

0

1,0

2,0

3,0

0 5 10 15 20 25 30 35

P1

[k

W]

[m³/h]

[l/s]

[m³/h]

Q

40

40

0

2

4

6

8

10

12

14

16

18

20

22

NP

SH

[m

]

Wilo-VeroLine-IP-E

40/130-2,2/2

16 m14 m

max.

max.

10 m18 m

12 m 8 m

Δ p-v

Page 33: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

33

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroLine-IP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IP-E 40/150-3/2

�p-c (constant)

Wilo-VeroLine-IP-E 40/150-3/2

�p-v (variable)

Wilo-VeroLine-IP-E 40/160-4/2

�p-c (constant)

Wilo-VeroLine-IP-E 40/160-4/2

�p-v (variable)

Wilo-VeroLine-IP-E40/150-3/2

5 m

8 m

12 m

15 m

NP

SH

[m

]

p-c

max.

22 m

18 m

max.

0 40 30 20 0

10

15

20

25

30

5

10

2

00,51,01,52,02,53,03,54,0

31 5 64 8 97 11100

H [

m]

P1

[k

W]

Q

[m³/ h]

4030200 10 [m³/ h]

[l/s]

0

4

8 6

2

Wilo-VeroLine-IP-E40/150-3/2

p-v

max.

NP

SH

[m

]

max.

22 m

18 m

10 m

14 m

0 40 30 20 0

10

15

20

25

30

5

10

2

00,51,01,52,02,53,03,54,0

31 5 64 8 97 11100

H [

m]

P1

[k

W]

Q

[m³/ h]

4030200 10 [m³/ h]

[l/s]

0

4

8 6

2

Wilo-VeroLine-IP-E40/160-4/2

NP

SH

[m

]

max.

max.

p-c

5 m 9 m

24 m

20 m

16 m

13 m

0 50 40 30 20 0

10

15

20

25

40

35

30

5

10

0

1,0

2,0

3,0

4,0

5,0

6 93 15120

H [

m]

P1

[k

W]

Q

[m³/ h]

504030200 10 [m³/ h]

[l/s]

0

10 15

5

Wilo-VeroLine-IP-E40/160-4/2

NP

SH

[m

]

max.

max.

p-v

28 m

25 m

22 m

18 m

14 m

10 m

0 50 40 30 20 0

10

15

20

25

40

35

30

5

10

0

1,0

2,0

3,0

4,0

5,0

6 93 15120

H [

m]

P1

[k

W]

Q

[m³/ h]

504030200 10 [m³/ h]

[l/s]

0

10 15

5

Page 34: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

34 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroLine-IP-E

Wilo-VeroLine-IP-E 50/115-0,75/2

�p-c (constant)

Wilo-VeroLine-IP-E 50/115-0,75/2

�p-v (variable)

Wilo-VeroLine-IP-E 50/130-2,2/2

�p-c (constant)

Wilo-VeroLine-IP-E 50/130-2,2/2

�p-v (variable)

Wilo-VeroLine-IP-E50/115-0,75/2

max.

p-c

10 m

5 m 7 m

4 m

2 m

max.

9 m

NP

SH

[m

]

0302515 20100

6

8

10

12

14

4

2

5

25 15 20 10 0 5 0

0,2

0,4

0,6

0,8

1,0

1,2

H [

m]

P1

[k

W]

Q

[m³/ h]

30 [m³/ h]

[l/s]

0

2

4

4 65 87 93210

Wilo-VeroLine-IP-E50/115-0,75/2

max.

p-v

NP

SH

[m

]

4 m 6 m8 m

10 m

max.

0 30 25 15 20 10 0

6

8

10

12

14

4

2

5

0

0,2

0,4

0,6

0,8

1,0

1,2

H [

m]

P1

[k

W]

Q

[m³/ h]

302515 20100 5 [m³/ h]

[l/s]

0

2

4

4 65 87 93210

0 10 20 30 40 50

H [

m]

0 2 4 6 8 10 12 14

0

1,0

2,0

3,0

0 10 20 30 40 50

P1

[k

W]

[m³/h]

[l/s]

[m³/h]

Q

0

2

4

6

8

10

12

14

16

18

20

0

5

10

NP

SH

[m

]

Wilo-VeroLine-IP-E

50/130-2,2/2

13 m10 m

max.

max.

6 m16 m

8 m

3 m

Δ p-c

0 10 20 30 40 50

H [

m]

0 2 4 6 8 10 12 14

0

1,0

2,0

3,0

0 10 20 30 40 50

P1

[k

W]

[m³/h]

[l/s]

[m³/h]

Q

0

2

4

6

8

10

12

14

16

18

20

0

5

10

Wilo-VeroLine-IP-E

50/130-2,2/2

14 m 12 m

max.

max.

8 m16 m 10 m

p-v

NP

SH

[m

]

Page 35: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

35

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroLine-IP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IP-E 50/140-3/2

�p-c (constant)

Wilo-VeroLine-IP-E 50/140-3/2

�p-v (variable)

Wilo-VeroLine-IP-E 50/150-4/2

�p-c (constant)

Wilo-VeroLine-IP-E 50/150-4/2

�p-v (variable)

Wilo-VeroLine-IP-E50/140-3/2

NP

SH

[m

]

max.

p-c

max.

5 m 7 m

18 m

15 m

12 m

10 m

0 50 40 30 20 0

10

15

20

25

5

10

0

1,0

2,0

3,0

4,0

6 93 15120

H [

m]

P1

[k

W]

Q

[m³/ h]

504030200 10 [m³/ h]

[l/s]

0

6 8

4 2

Wilo-VeroLine-IP-E50/140-3/2

NP

SH

[m

]

max.

p-v

max.

8 m

18 m

14 m

12 m

0 50 40 30 20 0

10

15

20

25

5

10

0

1,0

2,0

3,0

4,0

6 93 15120

H [

m]

P1

[k

W]

Q

[m³/ h]

504030200 10 [m³/ h]

[l/s]

0

6 8

4 2

Wilo-VeroLine-IP-E50/150-4/2

max.

NP

SH

[m

]

p-c

12 m16 m 19 m 22 m

8 m

max.

5 m

0 70 60 40 50 30 0

10

15

20

25

30

5

20 10

0

1,0

2,0

3,0

4,0

5,0

H [

m]

P1

[k

W]

Q

[m³/ h]

706040 50300 2010 [m³/ h]

[l/s]

0 2 4 6 8

9 1512 18630

Wilo-VeroLine-IP-E50/150-4/2

max.

NP

SH

[m

]

p-v

20 m 24 m

14 m

max.

10 m 18 m

12 m

0 70 60 40 50 30 0

10

15

20

25

30

5

20 10

0

1,0

2,0

3,0

4,0

5,0

H [

m]

P1

[k

W]

Q

[m³/ h]

706040 50300 2010 [m³/ h]

[l/s]

0 2 4 6 8

9 1512 18630

Page 36: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

36 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroLine-IP-E

Wilo-VeroLine-IP-E 65/115-1,5/2

�p-c (constant)

Wilo-VeroLine-IP-E 65/115-1,5/2

�p-v (variable)

Wilo-VeroLine-IP-E 65/130-3/2

�p-c (constant)

Wilo-VeroLine-IP-E 65/130-3/2

�p-v (variable)

Wilo-VeroLine-IP-E65/115-1,5/2

NP

SH

[m

]

max.

p-c

max.

2 m 4 m 7 m

9 m 12 m

0 50 40 30 20 0

6

8

10

12

18

16

14

4

2

10

0

0,5

1,0

1,5

2,0

2,5

6 93 15120

H [

m]

P1

[k

W]

Q

[m³/ h]

504030200 10 [m³/ h]

[l/s]

0

4 2

Wilo-VeroLine-IP-E65/115-1,5/2

NP

SH

[m

]

max.

p-v

max.

10 m 12 m

4 m 6 m 8 m

0 50 40 30 20 0

6

8

10

12

18

16

14

4

2

10

0

0,5

1,0

1,5

2,0

2,5

6 93 15120

H [

m]

P1

[k

W]

Q

[m³/ h]

504030200 10 [m³/ h]

[l/s]

0

4 2

Wilo-VeroLine-IP-E65/130-3/2

max.

p-c

4 m

10 m

7 m

15 m

12 m

max.

NP

SH

[m

]

0 70 60 40 50 30 0

10

12

14

16

18

20

2

4

6

8

20 10

0

1,0

2,0

3,0

4,0

H [

m]

P1

[k

W]

Q

[m³/ h]

706040 50300 2010 [m³/ h]

[l/s]

0 1 2 3 4

9 1512 18630

Wilo-VeroLine-IP-E65/130-3/2

max.

p-v

max.

8 m 12 m

10 m

16 m

14 m

NP

SH

[m

]

0 70 60 40 50 30 0

10

12

14

16

18

20

2

4

6

8

20 10

0

1,0

2,0

3,0

4,0

H [

m]

P1

[k

W]

Q

[m³/ h]

706040 50300 2010 [m³/ h]

[l/s]

0 1 2 3 4

9 1512 18630

Page 37: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

37

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroLine-IP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IP-E 65/140-4/2

�p-c (constant)

Wilo-VeroLine-IP-E 65/140-4/2

�p-v (variable)

Wilo-VeroLine-IP-E 80/115-2.2/2

�p-c (constant)

Wilo-VeroLine-IP-E 80/115-2,2/2

�p-v (variable)

Wilo-VeroLine-IP-E65/140-4/2

NP

SH

[m

]

max.

p-c

max.

4 m 7 m

19 m

16 m

13 m

10 m

0 50 60 40 80 90 70 30 20 0

10

15

20

25

5

10

0

1,0

2,0

4,0

5,0

3,0

6,0

10 155 25200

H [

m]

P1

[k

W]

Q

[m³/ h]

50 6040 80 907030200 10 [m³/ h]

[l/s]

0

5 4

2 3

1

Wilo-VeroLine-IP-E65/140-4/2

NP

SH

[m

]

max.

p-v

max.

18 m

16 m

14 m12 m

8 m 10 m

0 50 60 40 80 90 70 30 20 0

10

15

20

25

5

10

0

1,0

2,0

4,0

5,0

3,0

6,0

10 155 25200

H [

m]

P1

[k

W]

Q

[m³/ h]

50 6040 80 907030200 10 [m³/ h]

[l/s]

0

5 4

2 3

1

Wilo-VeroLine-IP-E80/115-2,2/2

max.

7 m

2 m

10 m 12 m14 m

p-c

NP

SH

[m

]

max.

0 70 60 40 50 30 0

10

12

14

16

18

2

4

6

8

20 10

0

1,0

2,0

3,0

H [

m]

P1

[k

W]

Q

[m³/ h]

706040 50300 2010 [m³/ h]

[l/s]

0 1 2 3 4

9 1512 18630

Wilo-VeroLine-IP-E80/115-2,2/2

max.

p-v

max.

8 m

6 m

12 m

10 m

4 m

NP

SH

[m

]

0 70 60 40 50 30 0

10

12

14

16

18

2

4

6

8

20 10

0

1,0

2,0

3,0

H [

m]

P1

[k

W]

Q

[m³/ h]

706040 50300 2010 [m³/ h]

[l/s]

0 1 2 3 4

9 1512 18630

Page 38: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

38 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroLine-IP-E

Wilo-VeroLine-IP-E 80/130-3/2

�p-c (constant)

Wilo-VeroLine-IP-E 80/130-3/2

�p-v (variable)

Wilo-VeroLine-IP-E 80/140-4/2

�p-c (constant)

Wilo-VeroLine-IP-E 80/140-4/2

�p-v (variable)

Wilo-VeroLine-IP-E80/130-3/2

NP

SH

[m

]

max.

p-c

max.

3 m 5 m

7 m 9 m

12 m

10 m

0 50 60 40 80 90 70 30 20 0

6

10

8

12

16

14

2

4

10

0

1,0

2,0

3,0

4,0

10 155 25200

H [

m]

P1

[k

W]

Q

[m³/ h]

50 6040 80 907030200 10 [m³/ h]

[l/s]

0

6

4

2

Wilo-VeroLine-IP-E80/130-3/2

NP

SH

[m

]

max.

p-v

max.

11 m

10 m

6 m 7 m 8 m 9 m

0 50 60 40 80 90 70 30 20 0

6

10

8

12

16

14

2

4

10

0

1,0

2,0

3,0

4,0

10 155 25200

H [

m]

P1

[k

W]

Q

[m³/ h]

50 6040 80 907030200 10 [m³/ h]

[l/s]

0

6

4

2

Wilo-VeroLine-IP-E80/140-4/2

max.

p-c

NP

SH

[m

]

6 m4 m

9 m11 m

13 m16 m

max.

0 100 60 80 40 0

10

12

14

16

18

20

2

4

6

8

20

0

1,0

2,0

3,0

5,0

4,0

H [

m]

P1

[k

W]

Q

[m³/ h]

10060 80400 20 [m³/ h]

[l/s]

0

2

4

6

2010 300

Wilo-VeroLine-IP-E80/140-4/2

max.

p-v

NP

SH

[m

]

max.

10 m8 m

12 m14 m

16 m

0 100 60 80 40 0

10

12

14

16

18

20

2

4

6

8

20

0

1,0

2,0

3,0

5,0

4,0

H [

m]

P1

[k

W]

Q

[m³/ h]

10060 80400 20 [m³/ h]

[l/s]

0

2

4

6

2010 300

Page 39: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

39

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Terminal diagram, motor data Wilo-VeroLine-IP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-VeroLine-IP-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram

L1 L2 L3 PE PESBM SSM

aux L H In2 In1 GNDGND

(1) (2) (3)

+24VMP

DDG

Ext. off

OFF ONO S

L1, L2, L3: Mains connection: 3~400 V AC/50 Hz; 3~380 V AC/60 Hz

PE: Protective conductor connection

DDG: Connection for differential pressure sensor

In1 (1): Actual value input 0-10 V/0-20 mA; 2-10 V/4-20 mA

GND (2): Ground connection for In1 and In2

+ 24 V (3): DC voltage output for an external consumer/sensor. Max load 60 mA

In2: Setpoint input 0-10 V/0-20 mA; 2-10 V/4-20 mA

MP: Multi-pump, interface for dual pump management

Ext. off: "Overriding Off" control inputThe pump can be switched on or off via an external, po-tential-free contact (24 V DC/10 mA).

SBM:* Potential-free collective run signal (changeover contact according to VDI 3814)

SSM:* Potential-free collective fault signal (changeover contact according to VDI 3814)

aux: no function

DIP switch:

1: Switchover between operation (O) and service mode (S)2: Activation/deactivation of menu access disable

Option: IF-Module (PLR/ LON) for connection to building automa-tion

* Load capacity of contacts for SBM and SSM:min.: 12 V DC/10 mAmax.: 250 V AC/1 A

Motor data

Wilo-VeroLine-IP-E ...

Nominal motor power Speed Power consumption Nominal current (approx.)

P2 n P1 IN 3~400 V

[kW] [rpm] [kW] [A]

32/100-0.55/2 0.55 1100 - 2900 0.8 1.8

32/110-0.75/2 0.75 1100 - 2900 1.1 2.9

32/160-1.1/2 1.1 1100 - 2900 1.3 3.6

40/115-0.55/2 0.55 1100 - 2900 0.8 1.8

40/120-1.5/2 1.5 1100 - 2900 1.9 4.8

40/130-2.2/2 2.2 1100 - 2900 2.6 6.8

40/150-3/2 3 1100 - 2900 3.6 7.5

40/160-4/2 4 1100 - 2900 4.7 9.6

50/115-0.75/2 0.75 1100 - 2900 1.1 2.9

50/130-2.2/2 2.2 1100 - 2900 2.6 6.8

50/140-3/2 3 1100 - 2900 3.5 7.8

50/150-4/2 4 1100 - 2900 4.9 10.1

65/115-1.5/2 1.5 1100 - 2900 1.9 4.8

65/130-3/2 3 1100 - 2900 3.7 7.9

65/140-4/2 4 1100 - 2900 5.0 10.1

80/115-2.2/2 2.2 1100 - 2900 2.6 6.8

80/130-3/2 3 1100 - 2900 3.5 7.7

Page 40: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

40 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Terminal diagram, motor data Wilo-VeroLine-IP-E

80/140-4/2 4 1100 - 2900 4.9 10.2

Three-phase motor (three-phase current), 2-pole - 3~400V, 50 Hz / 3~380V, 60 Hz

Motor data

Wilo-VeroLine-IP-E ...

Nominal motor power Speed Power consumption Nominal current (approx.)

P2 n P1 IN 3~400 V

[kW] [rpm] [kW] [A]

Page 41: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

41

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Dimensions, weights Wilo-VeroLine-IP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-VeroLine-IP-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing

Note:Housing with feet for installation on a base and drilled holes M10, brackets on request.

DN

nxd

Ød

ØK

ØD

L

c

fe

5050

Ø18

b 4

b b

b

1 2

3

m

l o

al 1x

Øg

M10x20

Th R1/8"

Dimensions, weights

Wilo-VeroLine-IP-E ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Thread-ed cable connec-tion

Weight approx.

DN l0 A b1 b2 b3 b4 c e f Ø g l1 m x Th M

– [mm] – [kg]

32/100-0.55/2 32 260 70 101 106 135 221 90 40 50 145 308 130 150

2xM121xM161xM201xM25

24

32/110-0.75/2 32 260 70 101 106 142 228 90 40 50 163 331 130 150 25

32/160-1.1/2 32 260 70 101 106 142 237 90 40 50 163 348 130 150 36

40/115-0.55/2 40 250 90 80 90 114 228 90 40 50 145 310 125 150 21

40/120-1.5/2 40 320 75 113 121 142 245 90 40 50 180 357 160 150 33

40/130-2.2/2 40 320 75 113 121 142 247 90 40 50 203 356 160 150 35

40/150-3/2 40 320 75 113 121 142 267 90 40 50 203 390 160 150 39

40/160-4/2 40 320 75 113 121 142 279 90 40 50 227 390 160 150 45

50/115-0.75/2 50 280 83 91 101 126 237 90 40 50 163 353 140 150 26

50/130-2.2/2 50 340 86 116 131 143 247 104 40 50 203 360 170 150 38

50/140-3/2 50 340 86 116 131 143 267 104 40 50 203 425 170 150 42

50/150-4/2 50 340 86 116 131 143 279 104 40 50 227 425 170 150 42

65/115-1.5/2 65 340 93 100 118 137 255 104 40 50 180 389 170 150 35

65/130-3/2 65 340 93 119 138 163 267 135 40 55 203 409 170 150 44

65/140-4/2 65 340 93 119 138 163 279 135 40 55 227 409 170 150 50

80/115-2.2/2 80 360 100 110 135 137 255 135 40 55 203 391 180 150 43

80/130-3/2 80 360 105 125 153 143 267 135 40 55 203 425 180 150 54

80/140-4/2 80 360 105 125 153 143 279 135 40 55 227 425 180 150 54

Page 42: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

42 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-VeroLine-IP-E

Flange dimensions

Wilo-VeroLine-IP-E ...

Nominal flange diameter Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

32... 32 140 78 100 4 x 19

40... 40 150 88 110 4 x 19

50... 50 165 102 125 4 x 19

65... 65 185 122 145 4 x 19

80... 80 200 138 160 8 x 19

Pump flange dimensions - drilled according to EN 1092-2 PN 16, n = number of drilled holes

Page 43: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

43

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Series description Wilo-CronoLine-IL-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoLine-IL-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignElectronically controlled glanded single pump in in-line design with flange connection and automatic power adjustment

ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive sub-stances in heating, cold water and cooling water systems

Scope of delivery• Pump • Installation and operating instructions

Type key

Technical data• Permissible temperature range -20°C to +140°C• Mains connection 3~400 V, 50 Hz; 3~380 V, 60 Hz• Protection class IP 55• Nominal diameter DN 40 to DN 80• Max. operating pressure 16 bar

Special features/product benefits• Improved functionality• Energy savings due to integrated electronic performance control• Control mode �p-c for constant and �p-v for variable differential pressure at the pump

• Manual control mode (0–10 V/0–20 mA; 2–10 V/4–20 mA)• Volume flow tendency indication• Integrated full motor protection (PTC thermistor sensor) with trip electronics

• Simple operation due to red-button technology, display and infrared interface (IR-Monitoring)

• Optional interfaces due to retrofit LON or PLR IF-Modules for bus communication

• Integrated dual pump management• High corrosion protection due to cataphoretic coating• Can be used flexibly in air-conditioning and cooling systems with ap-plication benefits due to the direct draining of condensate via opti-mised lantern design

• Long motor life due to standard condensate drainage holes in the motor housings

Materials• Pump housing and lantern: EN-GJL-250• Impeller- Standard version: EN-GJL-200- Special version: G-CuSn 10

• Shaft: 1.4122• Mechanical seal: AQ1EGG; other mechanical seals on request

Description/designSingle-stage, low-pressure centrifugal pump in in-line design with

• Mechanical seal • Flange connection• Lantern• Coupling • Drive with integrated electronic speed control

Example IIL-E 50/170-7.5/2 R1

IL-E In-line pump with electronic control

50 Nominal diameter DN of the pipe connection

170 Nominal impeller diameter

7.5 Nominal motor power P2 in kW

2 Number of poles

R1 Version without pressure sensor

Page 44: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

44 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-CronoLine-IL-E

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoLine-IL-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Q[m³/h]0 20 60 804010 50 7030 100 12090 130110

H[m]

0

10

15

20

25

30

35

5

Wilo-CronoLine-IL-E

80/140-7,5/265/150-5,5/2

50/170-7,5/2

40/170-5,5/2

Page 45: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

45

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-CronoLine-IL-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoLine-IL-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-CronoLine-IL-E 40/170-5,5/2

�p-c (constant)

Wilo-CronoLine-IL-E 40/170-5,5/2

�p-v (variable)

Wilo-CronoLine-IL-E 50/170-7,5/2

�p-c (constant)

Wilo-CronoLine-IL-E 50/170-7,5/2

�p-v (variable)

0 10 20 30 40

45

40

35

30

25

20

15

10

5

0

0 2 4 6 8 10 12 [l/s]

12

10

8

6

4

2

0

8

7

6

5

4

3

2

1

0

Q

0 10 20 30 40

P 1[kW

] H

[m]

[m3/h]

[m3/h]

NPS

H [m

]

Wilo-CronoLine-IL-E40/170-5,5/2

35 m

10 m

max.

max.

15 m 20 m 25 m 30 m

� p-c

P 1[kW

] H

[m]

45

40

35

30

25

20

15

10

5

0

0 2 4 6 8 10 12 [l/s]

8

7

6

5

4

3

2

1

0

Q

0 10 20 30 40

0 10 20 30 40

12

10

8

6

4

2

0 [m3/h]

[m3/h]

NPS

H [m

]

max.

36 m

24 m 18 m

28 m 32 m

max.

� p-v

Wilo-CronoLine-IL-E40/170-5,5/2

0 10 20 30 40 50 60 70

45

40

35

30

25

20

15

10

5

0

0 2 4 6 8 10 12 14 16 18 20 [l/s]

10

8

6

4

2

0

Q

12

10

8

6

4

2

0

0 10 20 30 40 50 60 70 [m3/h]

[m3/h]

NPS

H [m

]

30 m

10 m

max.

max.

15 m 20 m 25 m

P 1[kW

] H

[m]

� p-c

Wilo-CronoLine-IL-E50/170-7,5/2

0 2 4 6 8 10 12 14 16 18 20 [l/s]

45

40

35

30

25

20

15

10

5

0

10

8

6

4

2

0

Q

0 10 20 30 40 50 60 70

0 10 20 30 40 50 60 70

12

10

8

6

4

2

0

[m3/h]

[m3/h]

NPS

H [m

]

H[m

]P

1[k

W]

max.

34 m

24 m

20 m 28 m 32 m

max.

� p-v

Wilo-CronoLine-IL-E50/170-7,5/2

Page 46: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

46 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoLine-IL-E

Wilo-CronoLine-IL-E 65/150-5,5/2

�p-c (constant)

Wilo-CronoLine-IL-E 65/150-5,5/2

�p-v (variable)

Wilo-CronoLine-IL-E 80/140-7,5/2

�p-c (constant)

Wilo-CronoLine-IL-E 80/140-7,5/2

�p-v (variable)

0 10 20 30 40 50 60 70 80 90

28

24

20

16

12

8

4

0

0 4 8 12 16 20 24 [l/s]

8

7

6

5

4

3

2

1

0

Q

0 10 20 30 40 50 60 70 80 90

6

4

2

0

[m3/h]

[m3/h]

NPS

H [m

]

P 1[kW

]H

[m]

8 m

max.

max.

12 m 16 m 20 m

6 m

� p-c

Wilo-CronoLine-IL-E65/150-5,5/2

Q

28

24

20

16

12

8

4

0

8

7

6

5

4

3

2

1

0

0 4 8 12 16 20 24 [l/s]

6

4

2

00 10 20 30 40 50 60 70 80 90

0 10 20 30 40 50 60 70 80 90

P 1[kW

]H

[m]

[m3/h]

[m3/h]

NPS

H [m

]

max.

22 m

16 m

12 m 18 m 20 m

max.

14 m

� p-v

Wilo-CronoLine-IL-E65/150-5,5/2

28

24

20

16

12

8

4

0

0 5 10 15 20 25 30 35 40 [l/s]

10

8

6

4

2

0

Q

16

12

8

4

0 0 20 40 60 80 100 120 140

0 20 40 60 80 100 120 140

8 m

max.

max.

12 m 16 m

20 m

5 m

P 1[kW

]

[m3/h]

H[m

]

[m3/h]

NPS

H [m

]

� p-c

Wilo-CronoLine-IL-E80/140-7,5/2

Q

28

24

20

16

12

8

4

0

0 5 10 15 20 25 30 35 40 [l/s]

10

8

6

4

2

0

16

12

8

4

0

0 20 40 60 80 100 120 140

0 20 40 60 80 100 120 140

max.

16 m

10 m

18 m 20 m

max.

� p-v

14 m P 1[kW

]

[m3/h]

H[m

]

[m3/h]

NPS

H [m

] Wilo-CronoLine-IL-E80/140-7,5/2

Page 47: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

47

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Terminal diagram, motor data Wilo-CronoLine-IL-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-CronoLine-IL-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram

L1 L2 L3 PE PESBM SSM

aux L H In2 In1 GNDGND

(1) (2) (3)

+24VMP

DDG

Ext. off

OFF ONO S

L1, L2, L3: Mains connection: 3~400 V AC/50 Hz; 3~380 V AC/60 Hz

PE: Protective conductor connection

DDG: Connection for differential pressure sensor

In1 (1): Actual value input 0-10 V/0-20 mA; 2-10 V/4-20 mA

GND (2): Ground connection for In1 and In2

+ 24 V (3): DC voltage output for an external consumer/sensor. Max load 60 mA

In2: Setpoint input 0-10 V/0-20 mA; 2-10 V/4-20 mA

MP: Multi-pump, interface for dual pump management

Ext. off: "Overriding Off" control inputThe pump can be switched on or off via an external, po-tential-free contact (24 V DC/10 mA).

SBM:* Potential-free collective run signal (changeover contact according to VDI 3814)

SSM:* Potential-free collective fault signal (changeover contact according to VDI 3814)

aux: no function

DIP switch:

1: Switchover between operation (O) and service mode (S)2: Activation/deactivation of menu access disable

Option: IF-Module (PLR/ LON) for connection to building automa-tion

* Load capacity of contacts for SBM and SSM:min.: 12 V DC/10 mAmax.: 250 V AC/1 A

Motor data

Wilo-CronoLine-IL-E ...

Nominal motor power Speed Power consumption Nominal current (approx.)

P2 n P1 IN 3~400 V

[kW] [rpm] [kW] [A]

40/170-5.5/2 5.5 750 - 2900 7.2 11.5

50/170-7.5/2 7.5 750 - 2900 9.3 14.5

65/150-5.5/2 5.5 750 - 2900 7.2 11.5

80/140-7.5/2 7.5 750 - 2900 9.3 14.5

Three-phase motor (three-phase current), 2-pole - 3~400V, 50 Hz / 3~380V, 60 HzObserve motor name plate data

Page 48: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

48 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-CronoLine-IL-E

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-CronoLine-IL-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing

3xo

60

10 x

a

p

q

e e

c

f

f

50

m

III Th

Ø18

Øg

l 1

l 0

b 3

b 1 b 2

DN

nxd

Ød

ØK

ØD

L

Dimensions, weights

Wilo-CronoLine-IL-E ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Threaded cable con-nection

Weight ap-prox.

DN l0 A b1 b2 b3 c e f Ø g l1 m o p q x Th M

– [mm] – [mm] – [kg]

40/170-5.5/2 40 340 82 113 129 180 130 149 58 266 659 170 M10 20 303 95 1xM122xM161xM201xM25

89

50/170-7.5/2 50 340 103 120 138 180 164 143 48 266 666 170 M10 20 303 100 101

65/150-5.5/2 65 430 110 126 146 180 180 195 60 266 672 215 M12 20 303 120 97

80/140-7.5/2 80 400 105 123 151 180 180 173 57 266 686 200 M12 20 303 120 106

Flange dimensions

Wilo-CronoLine-IL-E ...

Nominal flange diameter Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

40... 40 150 84 110 4 x 19

50... 50 165 99 125 4 x 19

65... 65 185 118 145 4 x 19

80... 80 200 132 160 8 x 19

Pump flange dimensions - according to EN 1092-2 PN 16, n = number of drilled holes

Page 49: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

49

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Series description Wilo-CronoLine-IL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoLine-IL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignElectronically controlled glanded single pump in in-line design with flange connection and automatic power adjustment

ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive sub-stances in heating, cold water and cooling water systems

Scope of delivery• Pump • Installation and operating instructions

Type key

Technical data• Permissible temperature range -20°C to +140°C• Mains connection 3~400 V, 50 Hz; 3~380 V, 60 Hz• Protection class 54• Nominal diameter DN 40 to DN 200• Max. operating pressure 16 bar

Special features/product benefits• Powerful, up to 22 kW• Control mode �p-c for constant differential pressure at the pump• Manual control mode (0–10 V/0–20 mA)• Integrated full motor protection (PTC thermistor sensor) with trip electronics

• High corrosion protection due to cataphoretic coating

Materials• Pump housing and lantern: EN-GJL-250• Impeller: - Standard version: EN-GJL-200- Special version: G-CuSn 10

• Shaft: 1.4122• Mechanical seal: AQ1EGG; other mechanical seals on request

Description/designSingle-stage, low-pressure centrifugal pump in in-line design with

• Mechanical seal • Flange connection• Lantern• Coupling • Drive with integrated electronic speed control

Example IIL-E 100/5-21 BF R1

IL-E In-line pump with electronic control

100 Nominal diameter DN of the pipe connection

5-21 Adjustable delivery head range in m

BF Basic Function version with �p-c control

R1 Version without pressure sensor

Page 50: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

50 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-CronoLine-IL-E...BF

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoLine-IL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Q[m³/h]0 100 300 40020050 250 350150 500 600450 550

H[m]

0

10

20

30

40

50

60

Wilo-CronoLine-IL-E...BF

100/8-33100/6-29

80/9-48

80/8-42

100/5-26100/5-21

150/3-20150/3-18

150/2-15100/4-23 200/4-19

200/3-18200/2-15

150/5-23

80/8-40

65/11-64

65/9-55

80/8-3

1

65/9-46

50/10-60

65/8-40

50/9-52

40/11-64

Page 51: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

51

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-CronoLine-IL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoLine-IL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-IL-E 100/4-23 BF

4-pole, �p-c (constant)

Wilo-IL-E 150/2-15 BF

4-pole, �p-c (constant)

Wilo-IL-E 150/3-18 BF

4-pole, �p-c (constant)

Wilo-IL-E 150/3-20 BF

4-pole, �p-c (constant)

0

5

10

15

20

25

H[m]

0 20 40 60 80 100 120 140 160 Q[m³/h]

0

10

20

NP

SH

[m

]

0 5 10 15 20 25 30 35 40 45 Q[l/s]

0

2

4

6

8

10

12P1[kW]

0 20 40 60 80 100 120 140 160 Q[m³/h]

Wilo-CronoLine-IL-E

100/4-23 BF

p-c max.

7m12m

max.

14m19m

0

2,5

5

7,5

10

12,5

15

17,5

H[m]

0 50 100 150 200 250 Q[m³/h]0

5

10

NP

SH

[m

]

0 10 20 30 40 50 60 70 80 Q[l/s]

0

2

4

6

8

10

12P1[kW]

0 50 100 150 200 250 Q[m³/h]

max.

p-c

Wilo-CronoLine-IL-E

150/2-15 BF

2m

max.

5m

8m

11m13m

0

2

4

6

8

10

12

14

16

18

H[m]

0 50 100 150 200 250 300 350 Q[m³/h]

0

5

10

NP

SH

[m

]

0 10 20 30 40 50 60 70 80 90 100 Q[l/s]

02468

10121416

P1[kW]

0 50 100 150 200 250 300 350 Q[m³/h]

Wilo-CronoLine-IL-E

150/3-18 BF

max.

p-c

3m4m

7m10m

max.

12m15m

0

2,5

5

7,5

10

12,5

15

17,5

20

22,5

H[m]

0 50 100 150 200 250 300 350 Q[m³/h]0

5

10

NP

SH

[m

]

0 10 20 30 40 50 60 70 80 90 100 110 Q[l/s]

0

5

10

15

20

P1[kW]

0 50 100 150 200 250 300 350 Q[m³/h]

Wilo-CronoLine-IL-E

150/3-20 BF

5m

max.

7m

12m

10m

15m

18m

p-c

max.

Page 52: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

52 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoLine-IL-E...BF

Wilo-IL-E 150/5-23 BF

4-pole, �p-c (constant)

Wilo-IL-E 200/2-15 BF

4-pole, �p-c (constant)

Wilo-IL-E 200/3-18 BF

4-pole, �p-c (constant)

Wilo-IL-E 200/4-19 BF

4-pole, �p-c (constant)

0

5

10

15

20

25

H[m]

0 50 100 150 200 250 300 350 Q[m³/h]

0

5

NP

SH

[m

]

0 10 20 30 40 50 60 70 80 90 100 110 Q[l/s]

0

5

10

15

20

25

P1[kW]

0 50 100 150 200 250 300 350 Q[m³/h]

Wilo-CronoLine-IL-E

150/5-23 BF

p-c

max.

8m11m

14m17m

19m

22m

max.

5m

0

2

4

6

8

10

12

14

16

18

H[m]

0 50 100 150 200 250 300 350 400 450 500 Q[m³/h]

0

10

20

NP

SH

[m

]

0 20 40 60 80 100 120 140 Q[l/s]

0

5

10

15

P1[kW]

0 50 100 150 200 250 300 350 400 450 500 Q[m³/h]

3m

7m

10m

13m

max.

p-c max.

Wilo-CronoLine-IL-E

200/2-15 BF

0

2

4

6

8

10

12

14

16

18

H[m]

0 50 100 150 200 250 300 350 400 450 500 Q[m³/h]

0

5

10

NP

SH

[m

]

0 20 40 60 80 100 120 140 Q[l/s]

0

5

10

15

20

P1[kW]

0 50 100 150 200 250 300 350 400 450 500 Q [m³/h]

Wilo-CronoLine-IL-E

200/3-18 BF

p-c

max.

4m

12mmax.

7m

9m

15m

3m

0

2,5

5

7,5

10

12,5

15

17,5

20

22,5

H[m]

0 100 200 300 400 500 Q[m³/h]0

10

20

NP

SH

[m

]

0 20 40 60 80 100 120 140 160 Q[l/s]

0

5

10

15

20

25

P1[kW]

0 100 200 300 400 500 Q[m³/h]

Wilo-CronoLine-IL-E

200/4-19 BF

p-c

max.

6m

14m

11m

max.

8m

16m

Page 53: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

53

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-CronoLine-IL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoLine-IL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-IL-E 40/11-64 BF

2-pole, �p-c (constant)

Wilo-IL-E 50/9-52 BF

2-pole, �p-c (constant)

Wilo-IL-E 50/10-60 BF

2-pole, �p-c (constant)

Wilo-IL-E 65/8-40 BF

2-pole, �p-c (constant)

0

10

20

30

40

50

60

H[m]

0 10 20 30 40 50 Q[m³/h]

0

10

20

NP

SH

[m

]

0 2,5 5,0 7,5 10,0 12,5 Q[l/s]

0

2

4

6

8

10

12

P1[kW]

0 10 20 30 40 50 Q[m³/h]

Wilo-CronoLine-IL-E

40/11-64 BFp-c max.

max.

10m20m

26m34m

41m48m

55m

0

10

20

30

40

50

H[m]

0 10 20 30 40 50 60 Q[m³/h]

0

10

20

NP

SH

[m

]

0 2,5 5,0 7,5 10,0 12,5 15,0 17,5 Q[l/s]

0

2

4

6

8

10

12

P1[kW]

0 10 20 30 40 50 60 Q[m³/h]

36m

10m

max.

27m18m

Wilo-CronoLine-IL-E

50/9-52 BF

45m

p-c

max.

0

10

20

30

40

50

60

H[m]

0 10 20 30 40 50 60 70 Q[m³/h]

0

10

20

NP

SH

[m

]

0 5 10 15 20 Q[l/s]

0

5

10

15

P1[kW]

0 10 20 30 40 50 60 70 Q[m³/h]

p-c max.

Wilo-CronoLine-IL-E

50/10-60 BF

10m

max.

20m27m

41m48m

55m

0 10 20 30 40 50 60 70 80 90

0 10 20 30 40 50 60 70 80 90

40

35

30

25

20

15

10

5

0

0 4 8 12 16 20 24 Q[l/s]

8 6 4 2 0

12

10

8

6

4

2

0

Wilo-CronoLine-IL-E

65/8-40 BF

max.

max.

p-c

NP

SH

[m

]

Q[m³/h]

Q[m³/h]

H[m]

P1[kW]

8 m14 m

20 m28 m

Page 54: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

54 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoLine-IL-E...BF

Wilo-IL-E 65/9-46 BF

2-pole, �p-c (constant)

Wilo-IL-E 65/9-55 BF

2-pole, �p-c (constant)

Wilo-IL-E 65/11-64 BF

2-pole, �p-c (constant)

Wilo-IL-E 80/8-31 BF

2-pole, �p-c (constant)

0

10

20

30

40

50

H[m]

0 20 40 60 80 100 Q [m³/h]

0

5

10

NP

SH

[m

]

0 5 10 15 20 25 Q[l/s]

0

5

10

15

20

P1[kW]

0 20 40 60 80 100 Q[m/h]

p-c max.

Wilo-CronoLine-IL-E

65/9-46 BF

9m17m

max.

24m30m

35m42m

0

10

20

30

40

50

60

H[m]

0 20 40 60 80 100 Q[m³/h]

0

5

10

NP

SH

[m

]

0 5 10 15 20 25 Q[l/s]

0

5

10

15

20

P1[kW]

0 20 40 60 80 100 Q[m³/h]

max.

p-c

Wilo-CronoLine-IL-E

65/9-55 BF

42m

33m

50mmax.

16m9m

25m

0

10

20

30

40

50

60

70

H[m]

0 20 40 60 80 100 Q[m³/h]

0

5

10

0 5 10 15 20 25 Q[l/s]

0

5

10

15

20

25

P1[kW]

0 20 40 60 80 100 Q[m³/h]

p-c max.

NP

SH

[m

]

11m

max.

22m28m

36m43m

49m56m

Wilo-CronoLine-IL-E

65/11-64 BF

0 20 40 60 80 100 120

30

25

20

15

10

5

0

0 5 10 15 20 25 30 35

8

6

4

2

0

12

10

8

6

4

2

0

Wilo-CronoLine-IL-E

80/8-31 BF

26 m

8 m

max.

max.

p-c

14 m18 m

22 m

0 20 40 60 80 100 120

NPS

H [m

]

H[m]

P1[kW]

Q[m³/h]

Q[l/s]

Q[m³/h]

Page 55: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

55

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-CronoLine-IL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-IL-E 80/8-40 BF

2-pole, �p-c (constant)

Wilo-IL-E 80/8-42 BF

2-pole, �p-c (constant)

Wilo-IL-E 80/9-48 BF

2-pole, �p-c (constant)

Wilo-IL-E 100/5-21 BF

2-pole, �p-c (constant)

40

35

30

25

20

15

10

5

0

8

6

4

2

0

141210

86420

Wilo-CronoLine-IL-E

80/8-40 BF

0 20 40 60 80 100 120

0 5 10 15 20 25 30 35

0 20 40 60 80 100 120

NP

SH

[m

]

max.

14 m22 m

30 m

H[m]

P1[kW]

Q[l/s]

Q[m³/h]

Q[m³/h]

max.

p-c

36 m

8 m

40

30

20

10

0

12

8

4

0

20

16

14

12

8

4

0

max.

max.

Wilo-CronoLine-IL-E80/8-42 BF

0 40 80 120 160

0 8 16 24 32 40 48

0 40 80 120 160

NP

SH

[m

]

Q[l/s]

Q[m³/h]

Q[m³/h]

p-c

H[m]

P1[kW]

36 m30 m24 m18 m

8 m

36 m

50

40

30

20

10

0

12

8

4

0

20

15

10

5

09 m

max.

max.

Wilo-CronoLine-IL-E

80/9-48 BF

0 40 80 120 160

0 8 16 24 32 40 48 Q[l/s]

0 40 80 120 160 Q[m³/h]

Q[m³/h]

NP

SH

[m

]

p-c

H[m]

P1[kW]

18 m24 m

30 m

42 m

20

16

12

8

4

0

8

4

0

12

10

8

6

4

2

0

15 m

max.

max.

5 m8 m

12 m

0 40 80 120 160 2000 10 20 30 40 50 Q[l/s]

18 m

0 40 80 120 160 200 Q[m3/h]

Q[m3/h]

NP

SH

[m

]p-c

H[m]

P1[kW]

Wilo-CronoLine-IL-E

100/5-21 BF

Page 56: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

56 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoLine-IL-E...BF

Wilo-IL-E 100/5-26 BF

2-pole, �p-c (constant)

Wilo-IL-E 100/6-29 BF

2-pole, �p-c (constant)

Wilo-IL-E 100/8-33 BF

2-pole, �p-c (constant)

24

20

16

12

8

4

0

8

6

4

2

0

16

12

8

4

0

max.

max.

Wilo-CronoLine-IL-E

100/5-26 BF

0 40 80 120 160 200

0 40 80 120 160 200

0 10 20 30 40 50 Q[l/s]

Q[m3/h]

Q[m3/h]

NP

SH

[m

]

p-c

H[m]

P1[kW]

5 m10 m14 m

18 m22 m

p-c

0 40 80 120 160 200

0 40 80 120 160 200

30

25

20

15

10

5

0

0 8 16 24 32 40 48 56 64 Q[l/s]

16

12

8

4

0

20

16

12

8

4

0

Wilo-CronoLine-IL-E

100/6-29 BF

max.

max.

Q[m³/h]

Q[m³/h]

NP

SH

[m

]

P1[kW]

H[m]

24 m

6 m12 m

16 m20 m

0 50 100 150 200 250

35

30

25

20

15

10

5

0

0 10 20 30 40 50 60 70 Q[l/s]

16

12

8

4

0

24

20

16

12

8

4

0

Wilo-CronoLine-IL-E

100/8-33 BF

max.

max.

0 50 100 150 200 250 Q[m³/h]

Q[m³/h]

NP

SH

[m

]

p-c

H[m]

P1[kW]

28 m

8 m12 m

16 m22 m

Page 57: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

57

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Terminal diagram, motor data Wilo-CronoLine-IL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-CronoLine-IL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram

L1 L2 L3 PE PE

SBM SSM

DDG

1 32

31 3332 41 4342

(1) (3)

n=constant + Δp-cΔp-c

(2)

4 5 6 7 8 9 10 11 18 19 20

Ext. off

L1, L2, L3: Mains connection: 3~400 V AC/50 Hz; 3~380 V AC/60 Hz

PE: Protective conductor connection

DDG: Connection for differential pressure sensor

Ext. off: "Overriding Off" control inputThe pump can be switched on or off via an external, po-tential-free contact (24 V DC/10 mA).

SBM:* Potential-free collective run signal (changeover contact according to VDI 3814)

SSM:* Potential-free collective fault signal (changeover contact according to VDI 3814)

n=cons-tant:

Control mode with fixed motor speed

�p-c: Control mode with constant differential pressure

* Load capacity of contacts for SBM and SSM:42 V DC or 250 V AC/0.1-2 ANote for DL-E…BF: Detailed information on the controls for the dou-ble pumps are to be found in the installation and operating instruc-tions.

Motor data (4-pole)

Wilo-CronoLine-IL-E...BF

Nominal motor power Speed Power consumption Nominal current (approx.)

P2 n P1 IN 3~400 V

[kW] [rpm] [kW] [A]

100/4-23 11 375 - 1450 12.0 22.6

150/2-15 11 375 - 1450 13.0 22.6

150/3-18 15 375 - 1450 18.5 29.0

150/3-20 18.5 375 - 1450 22.0 34.9

150/5-23 22 375 - 1450 26.0 41.2

200/2-15 15 375 - 1450 18.0 29.0

200/3-18 18.5 375 - 1450 22.0 34.9

200/4-19 22 375 - 1450 26.0 41.2

150/2-15 11 375 - 1450 13.0 22.6

Three-phase motor (three-phase current), 4-pole - 3~400V, 50 Hz / 3~380V, 60 HzObserve motor name plate data

Page 58: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

58 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Terminal diagram, motor data Wilo-CronoLine-IL-E...BF

Motor data (2-pole)

Wilo-CronoLine-IL-E...BF

Nominal motor power Speed Power consumption Nominal current (approx.)

P2 n P1 IN 3~400 V

[kW] [rpm] [kW] [A]

40/11-64 11 750 - 2900 13.0 22.6

50/9-52 11 750 - 2900 13.0 22.6

50/10-60 15 750 - 2900 18.5 29.0

65/8-40 11 750 - 2900 13.0 22.6

65/9-46 15 750 - 2900 18.3 29.0

65/9-55 18.5 750 - 2900 21.5 34.9

65/11-64 22 750 - 2900 25.1 41.2

80/8-31 11 750 - 2900 13.0 22.6

80/8-40 15 750 - 2900 18.5 29.0

80/8-42 18.5 750 - 2900 21.5 34.9

80/9-48 22 750 - 2900 25.1 41.2

100/5-21 11 750 - 2900 13.0 22.6

100/5-26 15 750 - 2900 18.5 29.0

100/6-29 18.5 750 - 2900 21.5 34.9

100/8-33 22 750 - 2900 25.1 41.2

Three-phase motor (three-phase current), 4-pole - 3~400V, 50 Hz / 3~380V, 60 HzObserve motor name plate data

Page 59: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

59

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Dimensions, weights Wilo-CronoLine-IL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Single pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-CronoLine-IL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing

Øg

3 x o x pR1/8"

Th

x a

m

l1 b2 b1 b3

h

b 4

l 0

Ø18

Ød

ØK

ØD

DN

nxdL

5050

e

c

f

Dimensions, weights (4-pole)

Wilo-CronoLine-IL-E...BF

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Threaded cable

connec-tion

Weight approx.

DN l0 A b1 b2 b3 b4 c e f Ø g h l1 m o p x Th M

– [mm] – [mm] – [kg]

100/4-23 100 550 180 188 214 – 391 240 236 114 258 368 732 260 M12 20 120

2xM251xM40

204

150/2-15 150 700 200 202 249 – 391 260 284 116 258 368 757 310 M16 25 130 237

150/3-18 150 700 230 278 320 – 419 288 304 146 313 368 826 330 M16 25 135 339

150/3-20 150 700 230 278 320 – 419 288 304 146 313 400 826 330 M16 25 135 372

150/5-23 150 700 230 278 320 – 439 288 304 146 351 400 897 330 M16 25 135 379

200/2-15 200 800 245 281 362 – 419 330 270 165 313 368 851 370 M16 25 140 400

200/3-18 200 800 245 281 362 – 419 330 270 165 313 400 851 370 M16 25 140 434

200/4-19 200 800 245 281 362 – 439 330 270 165 351 400 922 370 M16 25 140 441

150/2-15 – 700 200 202 249 – 391 260 284 116 258 368 757 310 M16 25 130 237

Page 60: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

60 Subject to change 09/2008 WILO SE

Energy-saving pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-CronoLine-IL-E...BF

Dimensions, weights (2-pole)

Wilo-CronoLine-IL-E...BF

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Threaded cable

connec-tion

Weight approx.

DN l0 A b1 b2 b3 b4 c e f Ø g h l1 m o p x Th M

– [mm] – [mm] – [kg]

40/11-64 40 440 110 145 149 – 391 180 172 78 258 368 704 190 M10 20 100

2xM251xM40

181

50/9-52 50 440 120 145 150 – 391 160 170 70 258 368 705 190 M10 20 100 201

50/10-60 50 440 120 145 150 – 419 160 170 70 313 368 717 190 M10 20 100 213

65/8-40 65 430 110 126 146 370 – 180 195 60 258 368 723 215 M12 20 120 158

65/9-46 65 475 130 150 168 – 419 200 225 50 313 368 726 245 M12 20 110 218

65/9-55 65 475 130 150 168 – 419 200 225 50 313 400 764 245 M12 20 110 251

65/11-64 65 475 130 150 168 – 439 200 225 50 351 400 790 245 M12 20 110 283

80/8-31 80 440 120 136 162 370 – 180 173 72 258 368 721 200 M12 20 120 167

80/8-40 80 440 120 136 162 390 – 180 173 72 313 368 735 200 M12 20 120 184

80/8-42 80 500 145 157 182 – 419 220 208 62 313 400 772 230 M12 20 120 261

80/9-48 80 500 145 157 182 – 439 220 208 62 351 400 798 230 M12 20 120 292

100/5-21 100 500 120 159 197 370 – 200 226 60 258 368 756 250 M12 20 135 181

100/5-26 100 500 120 159 197 390 – 200 226 60 313 368 770 250 M12 20 135 218

100/6-29 100 500 120 159 197 410 – 200 226 60 313 400 803 250 M12 20 135 261

100/8-33 100 500 120 159 197 426 – 200 226 60 351 400 829 250 M12 20 135 292

Flange dimensions

Wilo-CronoLine-IL-E...BF

Nominal flange diameter Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

40... 40 150 84 110 4 x 19

50... 50 165 99 125 4 x 19

65... 65 185 118 145 4 x 19

80... 80 200 132 160 8 x 19

100... 100 220 156 180 8 x 19

150... 150 285 211 240 8 x 23

200... 200 340 266 295 12 x 23

Pump flange dimensions - according to EN 1092-2 PN 16, n = number of drilled holes

Page 61: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

61

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Series description Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroTwin-DP-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignElectronically controlled glanded double pump in in-line design with flange connection and automatic power adjustment

ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive sub-stances in heating, cold water and cooling water systems

Scope of delivery• Pump • Installation and operating instructions

Type key

Technical data• Permissible temperature range -10°C to +120°C• Mains connection 3~400 V, 50 Hz; 3~380 V, 60 Hz• Protection class IP 55• Nominal diameter DN 32 to DN 80• Max. operating pressure 10 bar (special version: 16 bar)

Special features/product benefits• Energy savings due to integrated electronic performance control• Control mode �p-c for constant and �p-v for variable differential pressure at the pump

• Manual control mode (0–10 V/0–20 mA; 2–10 V/4–20 mA)• Simple operation due to red-button technology, display and infrared interface (IR-Monitoring)

• Integrated full motor protection (PTC thermistor sensor) with trip electronics

• Optional interfaces due to retrofit IF-Modules for bus communica-tion, LON or PLR

• Integrated dual pump management

• High corrosion protection due to cataphoretic coating

Materials• Pump housing and lantern: EN-GJL-250• Impeller: PP, fibreglass-reinforced• Shaft: 1.4021• Mechanical seal: AQ1EGG; other mechanical seals on request

Description/designSingle-stage, low-pressure double pump in in-line design with

• Switchover valve• Mechanical seal • Flange connection• Drive with integrated electronic speed control

Example DP-E 40/160-4/2

DP-E In-line double pump with electronic control

40 Nominal diameter DN of the pipe connection

160 Nominal impeller diameter

4 Nominal motor power P2 in kW

2 Number of poles

R1 Version without sensor

Page 62: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

62 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-VeroTwin-DP-E

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroTwin-DP-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Q[m³/h]0 20 60 804010 50 7030 100 12090 130 140 150110

H[m]

0

10

15

20

25

5

Wilo-VeroTwin-DP-E +

65/140-4/2

80/115-2,2/2

80/130-3/2

80/140-4/2

65/130-3/250/140-3/2

50/115-0,75/265/115-1,5/2

50/150-4/2

40/160-4/2

40/115-0,55/2

32/160-1,1/2

40/150-3/2

40/120-1,5/2

40/130-2,2/2

32/110-0,75/2

32/100-0,55/2

50/130-2,2

/2

Page 63: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

63

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-VeroTwin-DP-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DP-E 32/100-0,55/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 32/100-0,55/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 32/100-0,55/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 32/100-0,55/2

�p-v (variable) parallel operation

0

10

12

8

6

0

0,30,20,1

0,5

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E32/100-0,55/2

max.

p-c

6 1040 [m³/ h]

4 1220

[l/s]

[m³/ h]

2 m

0,4

4

2

0,6

12

8

max.

10

2 8

6

0,80,7

0,9

4 m5 m

6 m8 m

10 m

8

NP

SH

[m

]

4

1 2 30Q

0

10

14

8

6

0

0,30,20,1

0,5

H [

m]

P1

[k

W]

Q

Wilo-VeroTwin-DP-E32/100-0,55/2

5 730 [m³/ h]

3 710

[l/s]

[m³/ h]

0

0,4

4

2

0,6

5 6

1 6

4

0,80,7

0,9

2 4

2

12

max.

max.p-v

2

NP

SH

[m

]

1

3

10 m

8 m

10,5 1,5

+

0

4

NP

SH

[m

]

2

6

0

10

12

8

6

0

0,60,40,2

1,0

H [

m]

P1

[k

W]

Q

Wilo-VeroTwin-DP-E32/100-0,55/2

15100 [m³/ h]

1050

[l/s]

[m³/ h]

4 620

0,8

4

2

1,2

20

5 20

15

1,41,6

p-c

max.

2 m4 m

5 m6 m

8 m

10 m

max.

1 3 5

+

0

10

14

8

6

0

0,6

0,4

0,2

1,0

H [

m]

P1

[k

W]

Q

Wilo-VeroTwin-DP-E32/100-0,55/2

10 1460 [m³/ h]

6 1420

[l/s]

[m³/ h]

3

0,8

4

2

1,2

10 12

2 12

8

1,4

4 8

4

12

8 m

max.

max.p-v

10 m

2

NP

SH

[m

]

1

3

1 2 40

Page 64: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

64 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DP-E

Wilo-VeroTwin-DP-E 32/110-0,75/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 32/110-0,75/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 32/110-0,75/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 32/110-0,75/2

�p-v (variable) parallel operation

0

12

16

8

6

0

0,2

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E32/110-0,75/2

max.

6 1040 [m³/ h]

4 1220

[l/s]

[m³/ h]

3 m0,4

4

2

0,6

12

8

max.

10

2 8

6

0,8

1,2

7 m5 m

9 m10 m

1 2 30

10

1,0

12 m

14

NP

SH

[m

]

8

4

Q

0

12

16

8

6

0

0,2

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E32/110-0,75/2

max.

6 1040 [m³/ h]

420

[l/s]

[m³/ h]

0,4

4

2

0,6

8

max.

10

2 8

6

0,8

1,2

8 m10 m

1 2Q

30

10

1,0

p-v14

12 m14 m

NP

SH

[m

]

8

4

+

0

10

12

14

16

8

6

0

1,5

1,0

0,5

2,5

H [

m]

P1

[k

W]

Q

0

4

8

NP

SH

[m

]

Wilo-VeroTwin-DP-E32/110-0,75/2

max.

p-c

2010 1550 [m³/ h]

2010 1550

[l/s]

[m³/ h]

max.

5 m 3 m

12 m

7 m

2 654310

2,0

4

2

9 m

10 m

0

10

12

14

16

8

6

0

0,5

H [

m]

P1

[k

W]

Q

0

2

4

NP

SH

[m

]

Wilo-VeroTwin-DP-E32/110-0,75/2

max.

10 1550 [m³/ h]

10 1550

[l/s]

[m³/ h]

max.

8 m

1 3 4 520

2,0

4

2

p-v

1,5

1,0

+

10 m12 m14 m

Page 65: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

65

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DP-E 32/160-1,1/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 32/160-1,1/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 32/160-1,1/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 32/160-1,1/2

�p-v (variable) parallel operation

0 12 10 6 8 4 0

10

15

20

25

30

5

2

0

0,5

1,0

1,5

2,0

H [

m]

P1

[k

W]

Q

[m³/ h]

[m³/ h]10 126 840 2

[l/s]

0

2

4

6

2 32,5 3,51,510,50

NP

SH

[m

]

Wilo-VeroTwin-DP-E32/160-1,1/2

max.

12 m

5 m9 m

16 m 20 m 23 m

max.

p-c

0 12 10 6 8 4 0

10

15

20

25

30

5

2

0

0,5

1,0

1,5

2,0

H [

m]

P1

[k

W]

Q

[m³/ h]

[m³/ h]10 126 840 2

[l/s]

0

2

4

6

2 32,5 3,51,510,50

NP

SH

[m

]

Wilo-VeroTwin-DP-E32/160-1,1/2

max.

max.

p-v

10 m

22 m

17 m

14 m

+

020105 150

10

15

20

25

30

5

00,51,01,5

4,03,53,02,52,0

H [

m]

P1

[k

W]

Q

[m³/ h]

[m³/ h]10 205 150

[l/s]

0

2

4

2 654310

NP

SH

[m

]

Wilo-VeroTwin-DP-E32/160-1,1/2

p-c

max.

5 m

14 m

10 m

16 m 20 m

24 m

max.

+

0 20 10 5 15 0

10

15

20

25

30

5

00,51,01,5

4,03,53,02,52,0

H [

m]

P1

[k

W]

Q

[m³/ h]

[m³/ h]10 205 150

[l/s]

0

2

4

2 654310

NP

SH

[m

] Wilo-VeroTwin-DP-E 32/160-1,1/2

p-v

max.

14 m10 m

17 m 22 m

max.

Page 66: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

66 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DP-E

Wilo-VeroTwin-DP-E 40/115-0,55/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 40/115-0,55/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 40/115-0,55/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 40/115-0,55/2

�p-v (variable) parallel operation

0

6

8

10

12

14

4

2

0

0,4

0,2

0,6

0,8

1,0

H [

m]

P1

[k

W]

Q

02 4

8 6

NP

SH

[m

]

Wilo-VeroTwin-DP-E 40/115-0,55/2

max.

p-c

20 10 5 15 0 [m³/ h]

[l/s]2 654310

[m³/ h]10 205 150

max.

4 m2 m

6 m 8 m 10 m

0

6

8

10

12

14

4

2

0

0,4

0,2

0,6

0,8

1,0

H [

m]

P1

[k

W]

Q

0 2 4

8 6

NP

SH

[m

]

Wilo-VeroTwin-DP-E 40/115-0,55/2

max.

p-v

20 10 5 15 0 [m³/ h]

[l/s]2 654310

[m³/ h]10 205 150

max.

4 m

10 m

8 m

6 m

+

0

6

8

10

12

14

4

2

0

0,5

1,0

1,5

2,0

H [

m]

P1

[k

W]

Q

0

1

3

2

NP

SH

[m

]

Wilo-VeroTwin-DP-E40/115-0,55/2

max.

p-c

40 30 20 10 0

403020100

[m³/ h]

[l/s]2 6 7 8 9 10 1154310

[m³/ h]

max.

2 m5 m 6 m

8 m

10 m

+

0

6

8

10

12

14

4

2

0

0,5

1,0

1,5

2,0

H [

m]

P1

[k

W]

Q

0

1

3

2

NP

SH

[m

]

Wilo-VeroTwin-DP-E40/115-0,55/2

max.

p-v

40 30 20 10 0

40 30 20 10 0

[m³/ h]

[l/s]2 6 7 8 9 10 1154310

[m³/ h]

max.

4 m

10 m

8 m

6 m

Page 67: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

67

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DP-E 40/120-1,5/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 40/120-1,5/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 40/120-1,5/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 40/120-1,5/2

�p-v (variable) parallel operation

0

12

18

8

6

0

0,5

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E40/120-1,5/2

max.

15 30100 [m³/ h]

1050

[l/s]

[m³/ h]

1,0

4

2

20 30

5 20

15

1,5

2,5

3 m

10 m

2 4 8 90

10

2,0

14

12 m

25

16

25

max.

5 m8 m

15 m

1 3 6 75

NP

SH

[m

]

8

4

Q

0

12

18

8

6

0

0,5

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E40/120-1,5/2

max.

15 30100 [m³/ h]

1050

[l/s]

[m³/ h]

1,0

4

2

20 30

5 20

15

1,5

2,5

10 m

10

2,0

14

12 m

25

16 p-v

25

max.

8 m

14 m16 m

2 4 8 90 1 3 6 75Q

NP

SH

[m

]

8

4

Wilo-VeroTwin-DP-E

40/120-1,5/2

0

10

12

14

16

8

6

0

1,51,00,5

2,5

H [

m]

P1

[k

W]

Q

0

4

8

NP

SH

[m

]

max.

p-c

20 30100 [m³/ h]

20100

[l/s]

[m³/ h]

3 m

2,0

4

2

20

3,53,0

4,0

40

30

max.

5 m

18+

40

8 m 10 m12 m15 m

0 42 6 8 1210

0

10

12

14

16

8

6

0

1,51,00,5

2,5

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E40/120-1,5/2

max.

20 30100 [m³/ h]

20 40100 [m³/ h]

2,0

4

2

20

3,53,0

4,0

40

30

max.

+18

p-v

Q

[m³/ h]

[l/s]0 42 6 8 1210

7,5 m9,5 m12 m14 m16 m

0

4

8

NP

SH

[m

]

Page 68: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

68 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DP-E

Wilo-VeroTwin-DP-E 40/130-2,2/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 40/130-2,2/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 40/130-2,2/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 40/130-2,2/2

�p-v (variable) parallel operation

Q

0

15

25

10

0

0,5

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E40/130-2,2/2

max.

15 35100 [m³/ h]

1050

[l/s]

[m³/ h]

1,0

5

20 35

5 25

15

1,5

3,0

4 m

12 m

2 4 90

2,0

15 m

30

25

max.

7 m9 m

17 m

1 3 6 75

20

2,5

20

30

8 10

NP

SH

[m

] 8

4

0

12

20

8

6

0

0,5

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E

40/130-2,2/2

max.

15 35100 [m³/ h]

1050 [m³/ h]

1,0

4

2

20

Q

35

5 25

15

1,5

3,0

10 m

10

2,0

14

12 m

30

18 p-v

25

max.

8 m

20

2,5

16

30

14 m16 m

18 m

[l/s]2 4 90 1 3 6 75 8 10

NP

SH

[m

]

10

0246

8

+

0

15

20

10

0

1,0

H [

m]

P1

[k

W]

Q

0

2

4

NP

SH

[m

]

Wilo-VeroTwin-DP-E

40/130-2,2/2

max.

20 30100 [m³/ h]

20 40100

[l/s]

[m³/ h]

4 m

0

2,0

5

25

4,0

3,0

5,0

40 50

30 50

max.

p-c

1

3

9 m12 m 15 m 17 m

7 m

2 4 6 8 10 12 14

+

0

15

20

10

0

1,0

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E

40/130-2,2/2

max.

20 30100 [m³/ h]

20 40100

[l/s]

[m³/ h]

7 m

2,0

5

25

4,0

3,0

5,0

40 50

30 50

max.

p-v

9 m

6420 1412108

11 m14 m

16 m18 m

Q

0

2

4

NP

SH

[m

]

1

3

Page 69: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

69

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DP-E 40/150-3/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 40/150-3/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 40/150-3/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 40/150-3/2

�p-v (variable) parallel operation

0

15

20

25

30

10

5

0

3,0

2,0

1,0

4,0

H [

m]

P1

[k

W]

Q

0

2

4

6

8

NP

SH

[m

]

Wilo-VeroTwin-DP-E40/150-3/2

max.

p-c

20 10 30 35155 250 [m³/ h]

2010 30 35155 250

[l/s]

[m³/ h]

max.

8 m5 m

12 m 16 m 19 m 22 m

2 6 7 8 9 1054310

0

15

20

25

30

10

5

0

3,0

2,0

1,0

4,0

H [

m]

P1

[k

W]

Q

0

2

4

6

8

NP

SH

[m

]

Wilo-VeroTwin-DP-E40/150-3/2

max.

p-v

20 10 30 35155 250 [m³/ h]

2010 30 35155 250

[l/s]

[m³/ h]

max.

8 m13 m 16 m 18 m 22 m

2 6 7 8 9 1054310

0

2,0

4,0

6,0

8,0

H [

m]

P1

[k

W]

Q

NP

SH

[m

]

max.

max.

p-c

402010 300 [m³/ h]

[l/s]2 6 8 10 12 1440

[m³/ h]

5035155 25 45

+

8 m5 m

12 m 16 m 19 m 22 m

0

402010 300 5035155 25 45

15

20

25

30

10

5

Wilo-VeroTwin-DP-E40/150-3/2

0

2

4

6

8

0

2,0

4,0

6,0

8,0

H [

m]

P1

[k

W]

Q

NP

SH

[m

]

max.

max.

p-v

402010 300 [m³/ h]

[l/s]2 6 8 10 12 1440

[m³/ h]

5035155 25 45

+

0

402010 300 5035155 25 45

15

20

25

30

10

5

Wilo-VeroTwin-DP-E40/150-3/2

0

2

4

6

8

9 m13 m 15 m 18 m 22 m

Page 70: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

70 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DP-E

Wilo-VeroTwin-DP-E 40/160-4/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 40/160-4/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 40/160-4/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 40/160-4/2

�p-v (variable) parallel operation

0

15

20

25

30

35

10

5

0

3,0

2,0

1,0

4,0

5,0

6,0

H [

m]

P1

[k

W]

Q

0

5

10

NP

SH

[m

]

Wilo-VeroTwin-DP-E 40/160-4/2

max.

p-c

40 20 10 30 0 [m³/ h]

[l/s]2 6 7 8 9 10 11 12 1354310

[m³/ h]20 4010 300

max.

9 m5 m

13 m 17 m 21 m 25 m

0

15

20

25

30

35

10

5

0

3,0

2,0

1,0

4,0

5,0

6,0

H [

m]

P1

[k

W]

Q

0

5

10

NP

SH

[m

]

Wilo-VeroTwin-DP-E 40/160-4/2

max.

p-v

40 20 10 30 0 [m³/ h]

[l/s]2 6 7 8 9 10 11 12 1354310

[m³/ h]20 4010 300

max.

14 m10 m

18 m 22 m 25 m 28 m

0

15

20

25

30

35

10

5

0

2,0

4,0

6,0

10,0

8,0

H [

m]

P1

[k

W]

Q

0

5

10

NP

SH

[m

]

Wilo-VeroTwin-DP-E40/160-4/2

max.

max.

p-c

60 40 20 10 30 0 [m³/ h]

[l/s]2 6 8 10 12 14 16 1840

[m³/ h]20 40

50

50 6010 300

+

9 m5 m

13 m 17 m 21 m 25 m

0

15

20

25

30

35

10

5

0

2,0

4,0

6,0

10,0

8,0

H [

m]

P1

[k

W]

Q

0

5

10

NP

SH

[m

]

Wilo-VeroTwin-DP-E40/160-4/2

max.

max.

p-v

60 40 20 10 30 0 [m³/ h]

[l/s]2 6 8 10 12 14 16 1840

[m³/ h]20 40

50

50 6010 300

+

28 m

14 m

10 m 18 m

25 m

22 m

Page 71: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

71

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DP-E 50/115-0,75/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 50/115-0,75/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 50/115-0,75/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 50/115-0,75/2

�p-v (variable) parallel operation

0

6

8

10

12

14

4

2

0

0,5

1,0

1,5

H [

m]

P1

[k

W]

Q

0

2

4

NP

SH

[m

]

Wilo-VeroTwin-DP-E50/115-0,75/2

max.

p-c

20 30 25 10 5 15 0

20 3025105 150

[m³/ h]

[l/s]2 7 8 9654310

[m³/ h]

4 m2 m

5 m 7 m

10 m

max.

9 m

0

6

8

10

12

14

4

2

0

0,5

1,0

1,5

H [

m]

P1

[k

W]

Q

0

2

4

NP

SH

[m

]

Wilo-VeroTwin-DP-E50/115-0,75/2

max.

p-v

20 30 25 10 5 15 0

20 3025105 150

[m³/ h]

[l/s]2 7 8654310

[m³/ h]

max.

6 m4 m

8 m 10 m

9

+

0

6

8

10

12

14

4

2

0,5

1,0

2,5

2,0

1,5

H [

m]

P1

[k

W]

Q

0

1

2

NP

SH

[m

]

Wilo-VeroTwin-DP-E 50/115-0,75/2

max.

p-c

30 50 40 10 20 0

30 504010 200

[m³/ h]

[l/s]12 159630

[m³/ h]

4 m2 m

5 m 7 m

10 m

max.

9 m

0

+

0

6

8

10

12

14

4

2

0,5

1,0

2,5

2,0

1,5

H [

m]

P1

[k

W]

Q

0

1

2

NP

SH

[m

] Wilo-VeroTwin-DP-E50/115-0,75/2

max.

p-v

30 50 40 10 20 0

30 504010 200

[m³/ h]

[l/s]12 159630

[m³/ h]

max.

6 m4 m

8 m 10 m

0

Page 72: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

72 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DP-E

Wilo-VeroTwin-DP-E 50/130-2,2/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 50/130-2,2/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 50/130-2,2/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 50/130-2,2/2

�p-v (variable) parallel operation

0

12

20

8

6

0

0,5

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E50/130-2,2/2

max.

15100 [m³/ h]

1050

[l/s]

[m³/ h]

1,0

4

2

20

5 25

15

1,5

3,0

10 m

2 4 110

10

2,0

14

12 m

30

18

25

max.

3 m

1 3 6 75

20

2,5

16

30

10

15 m

35

98

35

5 m8 m

8

4

NP

SH

[m

]

Q

0

12

20

8

6

0

0,5

H [

m]

P1

[k

W]

Wilo-VeroTwin-DP-E50/130-2,2/2

max.

15100 [m³/ h]

1050 [m³/ h]

1,0

4

2

20

5 25

15

1,5

3,0

10 m

10

2,0

14

12 m

30

18

25

max.

20

Q

2,5

16

30

35

p-v

35

8 m

14 m16 m

[l/s]2 4 110 1 3 6 75 1098

8

4

NP

SH

[m

]

+

0

10

12

14

16

8

6

0

3,0

2,0

1,0

5,0

H [

m]

P1

[k

W]

Q

0

5

10

NP

SH

[m

]

Wilo-VeroTwin-DP-E50/130-2,2/2

max.

p-c

30 50200 [m³/ h]

20 50100

[l/s]

[m³/ h]

3 m

2 10 12 14 16 188640

4,0

4

2

18

6,0

60

30 60

max.

15 m

12 m

10 m

40

10 40

5 m8 m

0

10

12

14

16

8

6

0

3,0

2,0

1,0

5,0

H [

m]

P1

[k

W]

max.

30 50200 [m³/ h]

20 50100

[l/s]

[m³/ h]

7 m

4,0

4

2

18

6,0

60

30 60

max.

40

10 40

p-v

2 10 12 14 16 188640

10 m12 m

14 m16 m

+

Wilo-VeroTwin-DP-E50/130-2,2/2

Q

0

5

10

NP

SH

[m

]

Page 73: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

73

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DP-E 50/140-3/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 50/140-3/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 50/140-3/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 50/140-3/2

�p-v (variable) parallel operation

0

10

15

20

25

5

0

1,0

3,0

5,0

2,0

4,0

H [

m]

P1

[k

W]

Q

0

5

10

NP

SH

[m

]

Wilo-VeroTwin-DP-E50/140-3/2

max.

p-c

40 60 50 20 10 30 0

40 60502010 300

[m³/ h]

[l/s]151050

[m³/ h]

max.

7 m4 m

10 m 12 m 15 m 18 m

0

10

15

20

25

5

0

1,0

3,0

5,0

2,0

4,0

H [

m]

P1

[k

W]

Q

0

5

10

NP

SH

[m

]

Wilo-VeroTwin-DP-E50/140-3/2

max.

p-v

40 60 50 20 10 30 0

40 60502010 300

[m³/ h]

[l/s]151050

[m³/ h]

max.

10 m8 m

12 m 14 m 16 m 18 m

+

0

10

15

20

25

5

0

2,0

6,0

8,0

4,0

H [

m]

P1

[k

W]

Q

0

10

20

NP

SH

[m

]

Wilo-VeroTwin-DP-E 50/140-3/2

max.

p-c

40 60 70 80 90 50 20 10 30 0 [m³/ h]

40 60 70 80 90502010 300 [m³/ h]

[l/s]20 25151050

max.

10 m8 m

12 m 14 m 16 m

18 m

+

0

10

15

20

25

5

0

2,0

6,0

8,0

4,0

H [

m]

P1

[k

W]

Q

0

10

20

NP

SH

[m

]

Wilo-VeroTwin-DP-E 50/140-3/2

max.

p-v

40 60 70 80 90 50 20 10 30 0 [m³/ h]

40 60 70 80 90502010 300 [m³/ h]

[l/s]20 25151050

max.

10 m8 m

12 m 14 m 16 m 18 m

Page 74: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

74 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DP-E

Wilo-VeroTwin-DP-E 50/150-4/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 50/150-4/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 50/150-4/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 50/150-4/2

�p-v (variable) parallel operation

0

15

20

25

30

35

10

5

2,0

1,0

3,0

6,0

5,0

4,0

H [

m]

P1

[k

W]

Q

02 4 6 8

NP

SH

[m

]

Wilo-VeroTwin-DP-E50/150-4/2

max.

p-c

30 50 40 10 20 0

30 504010 200

[m³/ h]

[l/s]12 159630

[m³/ h]

max.

0

5 m9 m

13 m 16 m 20 m 23 m

0

15

20

25

30

35

10

5

2,0

1,0

3,0

6,0

5,0

4,0

H [

m]

P1

[k

W]

Q

02 4 6 8

NP

SH

[m

]

Wilo-VeroTwin-DP-E50/150-4/2

max.

p-v

30 50 40 10 20 0

30 504010 200

[m³/ h]

[l/s]12 159630

[m³/ h]

max.

0

14 m9 m

20 m 23 m

+

0

15

20

25

30

35

10

5

2,0

4,0

10,0

8,0

6,0

H [

m]

P1

[k

W]

Q

0

2

4

6

8

NP

SH

[m

]

Wilo-VeroTwin-DP-E50/150-4/2

max.

p-c

30 70 40 10 20 0

30 70

80

80

60

60

50

504010 200

[m³/ h]

[l/s]1815 21129630

[m³/ h]

max.

0

23 m

9 m12 m

5 m

16 m 20 m

+

0

15

20

25

30

35

10

5

2,0

4,0

10,0

8,0

6,0

H [

m]

P1

[k

W]

Q

0

2

4

6

8

NP

SH

[m

]

Wilo-VeroTwin-DP-E50/150-4/2

max.

p-v

30 70 40 10 20 0

30 70

80

80

60

60

50

504010 200

[m³/ h]

[l/s]1815 21129630

[m³/ h]

max.

0

13 m8 m

18 m 20 m

24 m

Page 75: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

75

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DP-E 65/115-1,5/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 65/115-1,5/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 65/115-1,5/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 65/115-1,5/2

�p-v (variable) parallel operation

0

8

10

12

14

16

6

4

2

H [

m]

Q

0

1

2

3

NP

SH

[m

]

Wilo-VeroTwin-DP-E65/115-1,5/2

max.

p-c

30 50 40 10 20 0

30 504010 200

[m³/ h]

[l/s]12 159630

[m³/ h]

max.

4 m2 m

8 m

6 m 9 m

0

0,5

P1

[k

W]

1,0

1,5

2,5

2,0

0

8

10

12

14

16

6

4

2

H [

m]

Q

0

1

2

3

NP

SH

[m

]

Wilo-VeroTwin-DP-E65/115-1,5/2

max.

p-v

30 50 40 10 20 0

30 504010 200

[m³/ h]

[l/s]12 159630

[m³/ h]

max.

0

0,5

P1

[k

W]

1,0

1,5

2,5

2,0

4 m6 m

8 m10 m 12 m

+

0

8

10

12

14

16

6

4

2

H [

m]

Q

0 2

6 4

NP

SH

[m

]

Wilo-VeroTwin-DP-E65/115-1,5/2

max.

p-c

max.

0

P1

[k

W]

1

4

3

2

30 70 40 10 20 0

30 70

80

80

60

60

50

504010 200

[m³/ h]

[l/s]1815 21129630

[m³/ h]

4 m2 m

6 m 8 m 10 m 12 m

+

0

8

10

12

14

16

6

4

2

H [

m]

Q

0 2

6 4

NP

SH

[m

] Wilo-VeroTwin-DP-E65/115-1,5/2

max.

p-v

max.

0

P1

[k

W]

1

4

3

2

30 70 40 10 20 0

30 70

80

80

60

60

50

504010 200

[m³/ h]

[l/s]1815 21129630

[m³/ h]

12 m

6 m4 m

10 m

8 m

Page 76: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

76 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DP-E

Wilo-VeroTwin-DP-E 65/130-3/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 65/130-3/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 65/130-3/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 65/130-3/2

�p-v (variable) parallel operation

0

8

10

12

18

16

14

20

6

4

2

H [

m]

Q

0 1 2

4 3

NP

SH

[m

]

Wilo-VeroTwin-DP-E65/130-3/2

max.

p-c

30 70 60 50 40 10 20 0

30 7060504010 200

[m³/ h]

[l/s]12 18159630

[m³/ h]

max.

6 m4 m

9 m 12 m 16 m

14 m

P1

[k

W]

0

1

5

3

4

2

0

8

10

12

18

16

14

20

6

4

2 H

[m

]

Q

0 1 2

4 3

NP

SH

[m

]

Wilo-VeroTwin-DP-E65/130-3/2

max.

p-v

30 70 60 50 40 10 20 0

30 7060504010 200

[m³/ h]

[l/s]12 18159630

[m³/ h]

max.

8 m 10 m 14 m

12 m

P1

[k

W]

0

1

5

3

4

2

+

0

5

20

15

10

25

H [

m]

Q

0

1

2

3

NP

SH

[m

]

Wilo-VeroTwin-DP-E65/130-3/2

max.

p-c

100 60 80 40 20 0

10060 8040200

[m³/ h]

[l/s]10 30205 25150

[m³/ h]

max.

6 m4 m

9 m 12 m 16 m 14 m P

1 [

kW

]

0

2

10

6

8

4

+

0

5

20

15

10

25

H [

m]

Q

0

1

2

3

NP

SH

[m

]

max.

p-v

100 60 80 40 20 0

10060 8040200

[m³/ h]

[l/s]10 30205 25150

[m³/ h]

max.

P1

[k

W]

0

2

10

6

8

4 8 m10 m12 m14 m

Wilo-VeroTwin-DP-E65/130-3/2

Page 77: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

77

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DP-E 65/140-4/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 65/140-4/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 65/140-4/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 65/140-4/2

�p-v (variable) parallel operation

0

10

15

20

25

5

H [

m]

P1

[k

W]

0

1

6

5

3

4

2

Q

0

5 4 3 2 1 N

PS

H [

m]

Wilo-VeroTwin-DP-E 65/140-4/2

max.

p-c

40 60 70 80 90 50 20 10 30 0 [m³/ h]

40 60 70 80 90502010 300 [m³/ h]

[l/s]20 25151050

max.

7 m4 m

10 m 12 m 15 m 18 m

0

10

15

20

25

5

H [

m]

Q

0

5 4 3 2 1 N

PS

H [

m]

Wilo-VeroTwin-DP-E 65/140-4/2

max.

p-v

40 60 70 80 90 50 20 10 30 0 [m³/ h]

40 60 70 80 90502010 300 [m³/ h]

[l/s]20 25151050

max.

10 m8 m

12 m 14 m 16 m 18 m

P1

[k

W]

0

1

6

5

3

4

2

+

0

10

15

20

25

5

H [

m]

P1

[k

W]

0

2

10

6

8

4

Q

0

6

4

2

NP

SH

[m

]

Wilo-VeroTwin-DP-E65/140-4/2

max.

p-c

40 60 80 100 120 20 0

40 60 80 100 120200

[m³/ h]

[m³/ h]

[l/s]20 25 30 35151050

max.

7 m4 m

10 m 12 m 15 m 18 m

+

0

10

15

20

25

5

H [

m]

P1

[k

W]

0

2

10

6

8

4

Q

0

6

4

2

NP

SH

[m

] Wilo-VeroTwin-DP-E65/140-4/2

max.

p-v

40 60 80 100 120 20 0

40 60 80 100 120200

[m³/ h]

[m³/ h]

[l/s]20 25 30 35151050

max.

10 m8 m

12 m 14 m 16 m 18 m

Page 78: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

78 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DP-E

Wilo-VeroTwin-DP-E 80/115-2,2/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 80/115-2,2/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 80/115-2,2/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 80/115-2,2/2

�p-v (variable) parallel operation

0

8

10

12

14

16

6

4

2

H [

m]

Q

0

2

4

NP

SH

[m

]

Wilo-VeroTwin-DP-E80/115-2,2/2

max.

p-c

max.

30 70 40 10 20 0

30 70

80

80

60

60

50

504010 200

[m³/ h]

[l/s]1815 21129630

[m³/ h]

4 m2 m

13 m

11 m

9 m

6 m

0

0,5

P1

[k

W]

1,0

1,5

3,0

2,5

2,0

0

8

10

12

14

16

6

4

2 H

[m

]

Q

0

2

4

NP

SH

[m

]

Wilo-VeroTwin-DP-E80/115-2,2/2

max.

p-v

max.

30 70 40 10 20 0

30 70

80

80

60

60

50

504010 200

[m³/ h]

[l/s]1815 21129630

[m³/ h]

4 m6 m

8 m10 m 12 m

0

0,5

P1

[k

W]

1,0

1,5

3,0

2,5

2,0

+

0

8

10

12

14

18

16

6

4

2

H [

m]

Q

0

2 1

3

NP

SH

[m

]

Wilo-VeroTwin-DP-E80/115-2,2/2

max.

p-c

max.

40 60 80 100 120 20 0

40 60 80 100 120200

[m³/ h]

[m³/ h]

[l/s]20 25 30 35151050

2 m 4 m 6 m

9 m 11 m

13 m

P1

[k

W]

0

1

6

5

3

4

2

+

0

8

10

12

14

18

16

6

4

2

H [

m]

Q

0

2 1

3

NP

SH

[m

]

Wilo-VeroTwin-DP-E80/115-2,2/2

max.

p-v

max.

40 60 80 100 120 20 0

40 60 80 100 120200

[m³/ h]

[m³/ h]

[l/s]20 25 30 35151050

4 m6 m

8 m10 m 12 m

P1

[k

W]

0

1

6

5

3

4

2

Page 79: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

79

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DP-E 80/130-3/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 80/130-3/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 80/130-3/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 80/130-3/2

�p-v (variable) parallel operation

0

3

12

9

6

15

H [

m]

Q

0

2

4

6

NP

SH

[m

]

Wilo-VeroTwin-DP-E80/130-3/2

max.

p-c

100 60 80 40 20 0

10060 8040200

[m³/ h]

[l/s]10 30205 25150

[m³/ h]

max.

P1

[k

W]

0

1

5

3

4

2

5 m3 m

7 m 9 m 10 m 12 m

0

3

12

9

6

15

H [

m]

Q

0

2

4

6

NP

SH

[m

]

max.

p-v

100 60 80 40 20 0

10060 8040200

[m³/ h]

[l/s]10 30205 25150

[m³/ h]

max.

7 m6 m

8 m 9 m 10 m 11 m

Wilo-VeroTwin-DP-E 80/130-3/2

P1

[k

W]

0

1

5

3

4

2

+

0

3

12

9

6

15

H [

m]

Q

0

2

4

6

NP

SH

[m

]

Wilo-VeroTwin-DP-E80/130-3/2

max.

p-c

120 140 100 60 80 40 20 0

120 14010060 8040200

[m³/ h]

[l/s]10 403530205 25150

[m³/ h]

max.

P1

[k

W]

0

8

4

6

2 5 m3 m

7 m 9 m 10 m 12 m

+

0

3

12

9

6

15

H [

m]

Q

0

2

4

6

NP

SH

[m

] Wilo-VeroTwin-DP-E80/130-3/2

max.

p-v

120 140 100 60 80 40 20 0

120 14010060 8040200

[m³/ h]

[l/s]10 403530205 25150

[m³/ h]

max.

7 m6 m

8 m 9 m 10 m 11 m

P1

[k

W]

0

8

4

6

2

Page 80: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

80 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DP-E

Wilo-VeroTwin-DP-E 80/140-4/2

�p-c (constant) individual operation

Wilo-VeroTwin-DP-E 80/140-4/2

�p-v (variable) individual operation

Wilo-VeroTwin-DP-E 80/140-4/2

�p-c (constant) parallel operation

Wilo-VeroTwin-DP-E 80/140-4/2

�p-v (variable) parallel operation

0

2

4

12

10

6

8

20

14

16

18

H [

m]

Q

0

6

3

NP

SH

[m

]

Wilo-VeroTwin-DP-E80/140-4/2

max.

p-c

100 60 80 40 20 0

10060 8040200

[m³/ h]

[l/s]10 30205 25150

[m³/ h]

max.

6 m4 m

13 m 11 m

9 m

16 m

P1

[k

W]

0

1

6

5

3

4

2

0

2

4

12

10

6

8

20

14

16

18

H [

m]

Q

0

6

3

NP

SH

[m

]

Wilo-VeroTwin-DP-E80/140-4/2

max.

p-v

100 60 80 40 20 0

10060 8040200

[m³/ h]

[l/s]10 30205 25150

[m³/ h]

max.

P1

[k

W]

0

1

6

5

3

4

2 10 m8 m

12 m 16 m

14 m

+

0

2

4

12

10

6

8

20

14

16

18

H [

m]

Q

0

6

3

NP

SH

[m

]

Wilo-VeroTwin-DP-E 80/140-4/2

max.

p-c

140 120 100 60 80 40 20 0

14012010060 8040200

[m³/ h]

[l/s]12 36246 30180

[m³/ h]

max.

P1

[k

W]

0

2

10

6

8

4

6 m4 m

13 m

11 m

9 m

16 m

+

0

2

4

12

10

6

8

20

14

16

18

H [

m]

Q

0

6

3

NP

SH

[m

]

Wilo-VeroTwin-DP-E 80/140-4/2

max.

p-v

140 120 100 60 80 40 20 0

14012010060 8040200

[m³/ h]

[l/s]12 36246 30180

[m³/ h]

max.

P1

[k

W]

0

2

10

6

8

4 7 m10 m12 m

14 m16 m

Page 81: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

81

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Terminal diagram, motor data Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-VeroTwin-DP-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram

L1 L2 L3 PE PESBM SSM

aux L H In2 In1 GNDGND

(1) (2) (3)

+24VMP

DDG

Ext. off

OFF ONO S

L1, L2, L3: Mains connection: 3~400 V AC/50 Hz; 3~380 V AC/60 Hz

PE: Protective conductor connection

DDG: Connection for differential pressure sensor

In1 (1): Actual value input 0-10 V/0-20 mA; 2-10 V/4-20 mA

GND (2): Ground connection for In1 and In2

+ 24 V (3): DC voltage output for an external consumer/sensor. Max load 60 mA

In2: Setpoint input 0-10 V/0-20 mA; 2-10 V/4-20 mA

MP: Multi-pump, interface for dual pump management

Ext. off: "Overriding Off" control inputThe pump can be switched on or off via an external, po-tential-free contact (24 V DC/10 mA).

SBM:* Potential-free collective run signal (changeover contact according to VDI 3814)

SSM:* Potential-free collective fault signal (changeover contact according to VDI 3814)

aux: no function

DIP switch:

1: Switchover between operation (O) and service mode (S)2: Activation/deactivation of menu access disable

Option: IF-Module (PLR/ LON) for connection to building automa-tion

* Load capacity of contacts for SBM and SSM:min.: 12 V DC/10 mAmax.: 250 V AC/1 A

Motor data

Wilo-VeroTwin-DP-E ...

Nominal motor power Speed Power consumption Nominal current (approx.)

P2 n P1 IN 3~400 V

[kW] [rpm] [kW] [A]

32/100-0.55/2 0.55 1150 - 2800 0.8 2.4

32/110-0.75/2 0.75 1160 - 2850 1.2 3.2

32/160-1.1/2 1.1 1100 - 2900 1.5 3.5

40/115-0.55/2 0.55 1100 - 2900 0.9 1.8

40/120-1.5/2 1.5 1200 - 2860 2.2 5.4

40/130-2.2/2 2.2 1200 - 2880 2.8 6.4

40/150-3/2 3 1100 - 2900 3.9 8.4

40/160-4/2 4 1200 - 2900 4.5 9.5

50/115-0.75/2 0.75 1200 - 2900 1.2 2.4

50/130-2.2/2 2.2 1160 - 2880 2.9 6.7

50/140-3/2 3 1100 - 2890 4.0 8.5

50/150-4/2 4 1100 - 2900 5.5 11.0

65/115-1.5/2 1.5 1100 - 2900 2.1 4.7

65/130-3/2 3 1200 - 2900 4.0 8.7

65/140-4/2 4 1200 - 2890 5.0 10.2

80/115-2.2/2 2.2 1200 - 2900 2.9 6.7

80/130-3/2 3 1200 - 2890 3.8 8.4

Page 82: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

82 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Terminal diagram, motor data Wilo-VeroTwin-DP-E

80/140-4/2 4 1100 - 2900 5.3 10.6

Three-phase motor (three-phase current), 2-pole - 3~400V, 50 Hz / 3~380V, 60 Hz

Motor data

Wilo-VeroTwin-DP-E ...

Nominal motor power Speed Power consumption Nominal current (approx.)

P2 n P1 IN 3~400 V

[kW] [rpm] [kW] [A]

Page 83: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

83

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Dimensions, weights Wilo-VeroTwin-DP-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-VeroTwin-DP-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing A

Note:Housing with feet for installation on a base and drilled holes M10, brackets on request.

Dimension drawing B

Note:Housing with feet for installation on a base and drilled holes M10, brackets on request.

Dimension drawing C

Note:Housing with feet for installation on a base and drilled holes M10, brackets on request.

xa

b1

l 1

bmax

b2

Th

Øg

s

3 x o x p

m

h

b 4

Ø18

c

5050

fe

DN

nxd L

Ød

ØK

ØD

l 0

xa

Th

m

l 0

c

ef

50

Ø18

50

DN

nxd L

Ød

ØK

ØD

l 1

bmax

Øg

s

3 x o x p

h

b 4

b1 b2

Th

m

c

ef

50

50

Ø18

DN

nxd L

Ød

ØK

ØD

xa

l 1

bmax

Øg

s

3 x o x p

h

b 4

b1 b2

l 0

Page 84: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

84 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-VeroTwin-DP-E

Dimensions, weights

Wilo-VeroTwin-DP-E ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

Thread-ed cable connec-tion

Di-men-sion draw-ing

DN l0 A b1 b2 b4bma

xc e f Øg h l1 m o p s x M Th –

– [mm] – [mm] [kg] –

32/100-0.55/2 32 260 70 101 105 233 410 225 56 106 145 671 308 136 M10 20 205 150 42

2xM121xM161xM201xM25

C

32/110-0.75/2 32 260 70 101 105 240 410 225 56 106 163 685 332 136 M10 20 205 150 45 C

32/160-1.1/2 32 260 70 101 105 276 410 225 56 106 163 757 332 136 M10 20 205 150 58 C

40/115-0.55/2 40 250 75 85 91 275 350 225 35 97 145 478 303 135 M10 20 174 150 43 B

40/120-1.5/2 40 320 75 113 119 245 456 240 45 135 180 714 358 167 M10 20 224 150 53 C

40/130-2.2/2 40 320 75 113 119 245 456 240 45 135 180 714 358 167 M10 20 224 150 58 C

40/150-3/2 40 320 75 113 119 312 456 240 45 135 103 848 391 167 M10 20 224 150 79 C

40/160-4/2 40 320 75 113 119 272 456 240 45 135 203 768 411 167 M10 20 224 150 89 C

50/115-0.75/2 50 280 83 95 101 225 390 228 50 107 163 506 333 155 M10 20 194 150 48 B

50/130-2.2/2 50 340 86 120 130 250 500 240 48 132 180 750 360 190 M10 20 250 150 64 C

50/140-3/2 50 340 86 120 130 270 500 240 48 132 227 460 393 190 M10 20 250 150 79 A

50/150-4/2 50 340 86 120 130 279 500 240 48 132 227 460 413 190 M10 20 250 150 91 A

65/115-1.5/2 65 340 93 103 117 272 432 225 25 137 180 528 371 185 M10 20 212 150 67 B

65/130-3/2 65 340 93 125 135 255 550 240 43 137 203 500 399 185 M10 20 290 150 89 A

65/140-4/2 65 340 93 125 135 272 550 240 43 137 203 500 419 185 M10 20 290 150 98 A

80/115-2.2/2 80 360 100 113 132 255 480 240 43 137 180 551 373 205 M10 20 235 150 82 B

80/130-3/2 80 360 103 134 147 267 601 240 30 150 227 440 405 192 M10 20 320 150 89 A

80/140-4/2 80 360 103 134 147 279 601 240 30 150 227 530 425 192 M10 20 320 150 101 A

Flange dimensions

Wilo-VeroTwin-DP-E ...

Nominal flange diame-ter Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

32... 32 140 76 100 4 x 19

40... 40 150 84 110 4 x 19

50... 50 165 99 125 4 x 19

65... 65 185 118 145 4 x 19

80... 80 200 132 160 8 x 19

Pump flange dimensions - drilled according to EN 1092-2 PN 16, n = number of drilled holes

Page 85: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

85

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Series description Wilo-CronoTwin-DL-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoTwin-DL-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignElectronically controlled glanded double pump in in-line design with flange connection and automatic power adjustment

ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive sub-stances in heating, cold water and cooling water systems

Scope of delivery• Pump • Installation and operating instructions

Type key

Technical data• Permissible temperature range -20°C to +140°C• Mains connection 3~400 V, 50 Hz; 3~380 V, 60 Hz• Protection class IP 55• Nominal diameter DN 40 to DN 80• Max. operating pressure 16 bar

Special features/product benefits• Energy savings due to integrated electronic performance control• Control mode �p-c for constant and �p-v for variable differential pressure at the pump

• Manual control mode (0–10 V/0–20 mA; 2–10 V/4–20 mA)• Red-button technology for simplest operation• Integrated full motor protection (PTC thermistor sensor) with trip electronics

• Simple operation due to infrared interface (IR-Monitoring)• Optional interfaces due to retrofit IF-Modules for bus communica-tion, LON or PLR

• Integrated dual pump management

• High corrosion protection due to cataphoretic coating• Bidirectional mechanical seal with forced flushing• Easy to install due to pump housing with feet and threaded holes

Materials• Pump housing and lantern: EN-GJL-250• Impeller: - Standard version: EN-GJL-200- Special version: G-CuSn 10

• Shaft: 1.4122• Mechanical seal: AQ1EGG; other mechanical seals on request

Description/designSingle-stage, low-pressure double pump in in-line design with

• Switchover valve• Mechanical seal • Flange connection• Lantern• Coupling • Drive with integrated electronic speed control

Example DL-E 50/170-7.5/2 R1

DL-E In-line double pump with electronic control

50 Nominal diameter DN of the pipe connection

170 Nominal impeller diameter

7.5 Nominal motor power P2 in kW

2 Number of poles

R1 Version without pressure sensor

Page 86: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

86 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-CronoTwin-DL-E

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoTwin-DL-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Q[m³/h]0 20 60 804010 50 7030 100 140 16012090 130 150 180170 200190110

H[m]

0

10

15

20

25

30

35

5

Wilo-CronoTwin-DL-E+

80/140-7,5/265/150-5,5/2

50/170-7,5/2

40/170-5,5/2

Page 87: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

87

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-CronoTwin-DL-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoTwin-DL-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-CronoTwin-DL-E 40/170-5,5/2

�p-c (constant) individual operation

Wilo-CronoTwin-DL-E 40/170-5,5/2

�p-v (variable) individual operation

Wilo-CronoTwin-DL-E 40/170-5,5/2

�p-c (constant) parallel operation

Wilo-CronoTwin-DL-E 40/170-5,5/2

�p-v (variable) parallel operation

0 10 20 30 40 [m3/h]

45

40

35

30

25

20

15

10

5

0

0 2 4 6 8 10 12 [l/s]

8

6

4

2

0

8

7

6

5

4

3

2

1

0

Q

0 10 20 30 40

P 1[kW

] H

[m]

[m3/h]

NPS

H [m

]

35m

10m

max.

max.

� p-c

15m 20m 25m 30m

Wilo-CronoTwin-DL-E40/170-5,5/2

45

40

35

30

25

20

15

10

5

0

8

6

4

2

0

0 2 4 6 8 10 12 [l/s]

8

7

6

5

4

3

2

1

0

Q

0 10 20 30 40

0 10 20 30 40

P 1[kW

] H

[m]

[m3/h]

[m3/h]

NP

SH

[m

]

max.

36m

24m 18m

28m 32m

max.

� p-v

Wilo-CronoTwin-DL-E40/170-5,5/2

10m

max.

max.

15m 20m 25m 30m

0 10 20 30 40 50 60 70 80

45

40

35

30

25

20

15

10

5

0

0 2 4 6 8 10 12 14 16 18 20 22 [l/s]

20

10

0

14

12

10

8

6

4

2

0

Q

0 10 20 30 40 50 60 70 80 [m3/h]

[m3/h]

P 1[kW

] H

[m]

� p-c

+

NPS

H [m

]

Wilo-CronoTwin-DL-E40/170-5,5/2

max.

36m

24m

18m 28m 32m

max.

45

40

35

30

25

20

15

10

5

0

Q

20

10

0

0 2 4 6 8 10 12 14 16 18 20 22 [l/s]

14

12

10

8

6

4

2

0

0 10 20 30 40 50 60 70 80

0 10 20 30 40 50 60 70 80

P 1[kW

] H

[m]

[m3/h]

[m3/h]

� p-v

NPS

H [m

]+

Wilo-CronoTwin-DL-E40/170-5,5/2

Page 88: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

88 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL-E

Wilo-CronoTwin-DL-E 50/170-7,5/2

�p-c (constant) individual operation

Wilo-CronoTwin-DL-E 50/170-7,5/2

�p-v (variable) individual operation

Wilo-CronoTwin-DL-E 50/170-7,5/2

�p-c (constant) parallel operation

Wilo-CronoTwin-DL-E 50/170-7,5/2

�p-v (variable) parallel operation

0 10 20 30 40 50 60 70

45

40

35

30

25

20

15

10

5

0

0 2 4 6 8 10 12 14 16 18 20 [l/s]

16

12

8

4

0

10

8

6

4

2

0

Q

0 10 20 30 40 50 60 70

NPS

H [m

]

P 1[kW

]

[m3/h]

H[m

]

[m3/h]

30m

10m

max.

max.

� p-c

15m 20m 25m

Wilo-CronoTwin-DL-E50/170-7,5/2

0 2 4 6 8 10 12 14 16 18 20 [l/s]

45

40

35

30

25

20

15

10

5

0

10

8

6

4

2

0

Q

16

12

8

4

0

0 10 20 30 40 50 60 70

0 10 20 30 40 50 60 70

NPS

H [m

]

P 1[kW

]

[m3/h]

H[m

]

[m3/h]

max.

34m

24m

20m 28m 32m

max.

� p-v

Wilo-CronoTwin-DL-E50/170-7,5/2

0 10 20 30 40 50 60 70 80 90

45

40

35

30

25

20

15

10

5

0

0 5 10 15 20 25 [l/s]

16

12

8

4

0

16

12

8

4

0

Q

0 10 20 30 40 50 60 70 80 90

NPS

H [m

]

[m3/h]

[m3/h]

P 1[kW

] H

[m]

30m

10m

max.

max.

� p-c

15m 20m

25m

+

Wilo-CronoTwin-DL-E50/170-7,5/2

0 5 10 15 20 25 [l/s]

45

40

35

30

25

20

15

10

5

0

Q

16

12

8

4

0 0 10 20 30 40 50 60 70 80 90

0 10 20 30 40 50 60 70 80 90

16

12

8

4

0

NPS

H [m

]

P 1[kW

] H

[m]

[m3/h]

[m3/h]

34m

24m

20m

28m 32m

max.

� p-v

max.

+

Wilo-CronoTwin-DL-E50/170-7,5/2

Page 89: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

89

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-CronoTwin-DL-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-CronoTwin-DL-E 65/150-5,5/2

�p-c (constant) individual operation

Wilo-CronoTwin-DL-E 65/150-5,5/2

�p-v (variable) individual operation

Wilo-CronoTwin-DL-E 65/150-5,5/2

�p-c (constant) parallel operation

Wilo-CronoTwin-DL-E 65/150-5,5/2

�p-v (variable) parallel operation

0 10 20 30 40 50 60 70 80 90

28

24

20

16

12

8

4

0

0 4 8 12 16 20 24 [l/s]

7

6

5

4

3

2

1

0

Q

6

4

2

0

0 10 20 30 40 50 60 70 80 90

NPS

H [m

]

8m

max.

max.

� p-c

12m 16m

20m

6m

P 1[kW

] H

[m]

[m3/h]

[m3/h]

Wilo-CronoTwin-DL-E65/150-5,5/2

Q

28

24

20

16

12

8

4

0

7

6

5

4

3

2

1

0

0 4 8 12 16 20 24 [l/s]

0 10 20 30 40 50 60 70 80 90

0 10 20 30 40 50 60 70 80 90

6

4

2

0

NPS

H [m

]

max.

22m

12m 18m 20m

max.

� p-v

14m 16m P 1[k

W]

H[m

]

[m3/h]

[m3/h]

Wilo-CronoTwin-DL-E65/150-5,5/2

0 20 40 60 80 100 120 140 160

28

24

20

16

12

8

4

0

0 4 8 12 16 20 24 28 32 36 40 44 [l/s]

12

10

8

6

4

2

0

Q

20

10

0

0 20 40 60 80 100 120 140 160

P 1[kW

]

[m3/h]

NPS

H [m

]

[m3/h]

H[m

]

max.

max.

� p-c

8m 12m

16m 20m

6m

+

Wilo-CronoTwin-DL-E65/150-5,5/2

Q

28

24

20

16

12

8

4

0

12

10

8

6

4

2

0

20

10

0

0 4 8 12 16 20 24 28 32 36 40 44 [l/s]

0 20 40 60 80 100 120 140 160

0 20 40 60 80 100 120 140 160

P 1[kW

]

[m3/h]

NPS

H [m

]

[m3/h]

H[m

]

+

Wilo-CronoTwin-DL-E65/150-5,5/2

max.

max.

� p-v

20m 22m

12m 14m

16m 18m

Page 90: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

90 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL-E

Wilo-CronoTwin-DL-E 80/140-7,5/2

�p-c (constant) individual operation

Wilo-CronoTwin-DL-E 80/140-7,5/2

�p-v (variable) individual operation

Wilo-CronoTwin-DL-E 80/140-7,5/2

�p-c (constant) parallel operation

Wilo-CronoTwin-DL-E 80/140-7,5/2

�p-v (variable) parallel operation

28

24

20

16

12

8

4

0

0 5 10 15 20 25 30 35 40 [l/s]

10 8

6

4

2

0

Q

12

8

4

0 0 20 40 60 80 100 120 140

0 20 40 60 80 100 120 140 [m3/h]

[m3/h]

NPS

H [m

]

P 1[kW

] H

[m]

8m

max.

max.

� p-c

12m 16m

20m

5m

Wilo-CronoTwin-DL-E80/140-7,5/2

Q

28

24

20

16

12

8

4

0

0 5 10 15 20 25 30 35 40 [l/s]

10

8

6

4 2

0

12

8

4

0

0 20 40 60 80 100 120 140

0 20 40 60 80 100 120 140

P 1[kW

] H

[m]

[m3/h]

[m3/h]

NPS

H [m

]

max.

16m

10m 18m 20m

max.

� p-v

14m

Wilo-CronoTwin-DL-E80/140-7,5/2

28

24

20

16

12

8

4

0

0 10 20 30 40 50 60 [l/s]

18

16

14

12

10

8

6

4

2

0

Q

32

24

16

8

0

0 40 80 120 160 200

0 40 80 120 160 200 [m3/h]

[m3/h]

NPS

H [m

]

P 1[kW

] H

[m]

max.

max.

� p-c

10m 15m

20m

5m

+

Wilo-CronoTwin-DL-E80/140-7,5/2

Q

28

24

20

16

12

8

4

0

[l/s]

32

24

16

8

0

0 10 20 30 40 50 60

18

16

14

12

10

8

6

4

2

0

0 40 80 120 160 200

0 40 80 120 160 200 v

P 1[kW

] H

[m]

NPS

H [m

]

[m3/h]

[m3/h]

max.

16m

10m 18m 20m

max.

� p-v

14m

+

Wilo-CronoTwin-DL-E80/140-7,5/2

Page 91: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

91

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Terminal diagram, motor data Wilo-CronoTwin-DL-E

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-CronoTwin-DL-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram

L1 L2 L3 PE PESBM SSM

aux L H In2 In1 GNDGND

(1) (2) (3)

+24VMP

DDG

Ext. off

OFF ONO S

L1, L2, L3: Mains connection: 3~400 V AC/50 Hz; 3~380 V AC/60 Hz

PE: Protective conductor connection

DDG: Connection for differential pressure sensor

In1 (1): Actual value input 0-10 V/0-20 mA; 2-10 V/4-20 mA

GND (2): Ground connection for In1 and In2

+ 24 V (3): DC voltage output for an external consumer/sensor. Max load 60 mA

In2: Setpoint input 0-10 V/0-20 mA; 2-10 V/4-20 mA

MP: Multi-pump, interface for dual pump management

Ext. off: "Overriding Off" control inputThe pump can be switched on or off via an external, po-tential-free contact (24 V DC/10 mA).

SBM:* Potential-free collective run signal (changeover contact according to VDI 3814)

SSM:* Potential-free collective fault signal (changeover contact according to VDI 3814)

aux: no function

DIP switch:

1: Switchover between operation (O) and service mode (S)2: Activation/deactivation of menu access disable

Option: IF-Module (PLR/ LON) for connection to building automa-tion

* Load capacity of contacts for SBM and SSM:min.: 12 V DC/10 mAmax.: 250 V AC/1 A

Motor data

Wilo-CronoTwin-DL-E ...

Nominal motor power Speed Power consumption Nominal current (approx.)

P2 n P1 IN 3~400 V

[kW] [rpm] [kW] [A]

40/170-5.5/2 5.5 750 - 2900 7.2 11.5

50/170-7.5/2 7.5 750 - 2900 9.3 14.5

65/150-5.5/2 5.5 750 - 2900 7.2 11.5

80/140-7.5/2 7.5 750 - 2900 9.3 14.5

Three-phase motor (three-phase current), 2-pole - 3~400V, 50 Hz / 3~380V, 60 HzObserve motor name plate data

Page 92: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

92 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-CronoTwin-DL-E

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-CronoTwin-DL-E Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing

Øg

c

Ød

Øk

ØD

s

Th

DN

b 1

3xo

I

mf

e

q

Ix

a

6010

ef

p

Ø1850

nxd L

1

0

b 3

b 2

III

Dimensions, weights

Wilo-CronoTwin-DL-E ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Thread-ed ca-

ble con-nection

Weight ap-prox.

DN l0 A b1 b2 b3 c e f Ø g l1 m o p q s x Th M

– [mm] – [mm] – [kg]

40/170-5.5/2 40 340 100 120 127 288 400 52 145 266 646 170 M10 20 303 340 95 1xM122xM161xM201xM25

173

50/170-7.5/2 50 340 120 126 136 288 360 50 130 266 643 180 M10 20 303 340 100 203

65/150-5.5/2 65 430 153 134 144 288 440 55 185 266 662 215 M12 20 303 400 120 202

80/140-7.5/2 80 400 155 134 146 288 400 62 178 266 667 200 M12 20 303 350 120 210

Flange dimensions

Wilo-CronoTwin-DL-E ...

Nominal flange diameter Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

40... 40 150 84 110 4 x 19

50... 50 165 99 125 4 x 19

65... 65 185 118 145 4 x 19

80... 80 200 132 160 8 x 19

Pump flange dimensions - according to EN 1092-2 PN 16, n = number of drilled holes

Page 93: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

93

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Series description Wilo-CronoTwin-DL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoTwin-DL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignElectronically controlled glanded double pump in in-line design with flange connection and automatic power adjustment

ApplicationFor pumping heating water (in accordance with VDI 2035), water-glycol mixtures and cooling and cold water without abrasive sub-stances in heating, cold water and cooling water systems

Scope of delivery• Pump • Installation and operating instructions

Type key

Technical data• Permissible temperature range -20°C to +140°C• Mains connection 3~400 V, 50 Hz; 3~380 V, 60 Hz• Protection class 54• Nominal diameter DN 40 to DN 150• Max. operating pressure 16 bar

Special features/product benefits• Control mode �p-c for constant differential pressure at the pump• Manual control mode (0–10 V/0–20 mA)• Integrated full motor protection (PTC thermistor sensor) with trip electronics

• Powerful, up to 22 kW

Materials• Pump housing and lantern: EN-GJL-250• Impeller: - Standard version: EN-GJL-200- Special version: G-CuSn 10

• Shaft: 1.4122• Mechanical seal: AQ1EGG; other mechanical seals on request

Description/designSingle-stage, low-pressure centrifugal pump in in-line design with

• Mechanical seal • Flange connection• Lantern• Coupling • Drive with integrated electronic speed control

Example DL-E 100/5-21 BF R1

IL-E In-line double pump with electronic control

100 Nominal diameter DN of the pipe connection

5-21 Adjustable delivery head range in m

BF Basic Function version with �p-c control

R1 Version without pressure sensor

Page 94: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

94 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-CronoTwin-DL-E...BF

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoTwin-DL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Q[m³/h]0 100 250 35050 150 200 300

H[m]

0

5

40

50

60

30

20

10

45

55

65

35

25

15

Wilo-CronoTwin-DL-E...BF+

DL-E

40/

11-6

4 BF

DL-E

50/9-52

BF

DL-E

50/10-60

BF

DL-E 65/8-40 BF DL-E 100/8-33 BF

DL-E 80/8-40 BF

DL-E 150/2-15 BF

Page 95: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

95

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-CronoTwin-DL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoTwin-DL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-DL-E 150/2-15 BF

4-pole, �p-c (constant) - individual operation

Wilo-DL-E 150/2-15 BF

4-pole, �p-c (constant) - parallel operation

Wilo-CronoTwin-DL-E150/2-15 BF

p-c

max.

max.

2m

12m

10m

0

2

4

6

8

10

16

14

12

H[m]

0246

NP

SH

[m

]

3m5m

7m9m

Q min

14m

0 50 100 150

0

200

50 100 150 200

Q[m³/h]

0 403020 605010 Q[l/s]

Q[m³/h]0

2

4

6

8

10

12P1[kW]

Wilo-CronoTwin-DL-E150/2-15 BF

0

2

4

6

8

10

16

14

12

H[m]

NP

SH

[m

]

0 50 100 150 250 350300

0

200

50 100 150 250 350300200

Q[m³/h]

0 403020 7060 80 90 1005010 Q[l/s]

Q[m³/h]0

5

10

15

20

P1[kW]

+p-c

max.

max.

2m

12m

10m

3m5m

7m9m

14m

0246

Q min

Page 96: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

96 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL-E...BF

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoTwin-DL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-DL-E 40/11-64 BF

2-pole, �p-c (constant) - individual operation

Wilo-DL-E 40/11-64 BF

2-pole, �p-c (constant) - parallel operation

Wilo-DL-E 50/9-52 BF

2-pole, �p-c (constant) - individual operation

Wilo-DL-E 50/9-52 BF

2-pole, �p-c (constant) - parallel operation

Wilo-CronoTwin-DL-E40/11-64 BF

p-c

max.

max.

10m18m

25m34m

42m50m

58m

0

10

20

30

40

50

70

60

H[m]

0 10 20 30155 3525

10 20 30155 3525

Q[m³/h]0

10

20

NP

SH

[m

]

0 2 4 6 8 10 Q[l/s]

0

2

4

6

1

3

5

7P1[kW]

0 Q[m³/h]

Q minWilo-CronoTwin-DL-E40/11-64 BF

p-c

max.

max.

10m

25m34m

50m58m

0

10

20

30

40

50

70

60

H[m]

0 10 20 30 40 50 60 70

0 10 20 30 40 50 60 70

Q[m³/h]0

10

20

30

NP

SH

[m

]

0 4 8 12 16 20 Q[l/s]

0

5

10

15

20

25

P1[kW]

Q[m³/h]

+

42m

18m

Q min

Wilo-CronoTwin-DL-E50/9-52 BF

p-c max.

max.

8m

19m13m

25m

0

10

20

30

40

50

60

H[m]

0 10 20 30 40 50

0 10 20 30 40 50

Q[m³/h]0

5

10

NP

SH

[m

]

0 2 4 6 8 12 1410 Q[l/s]

0

2

4

1

3

5

6P1[kW]

Q[m³/h]

Q min

31m37m

44m50m

Wilo-CronoTwin-DL-E50/9-52 BF

p-c

max.

max.

8m19m

13m

25m

0

10

20

30

40

50

60

H[m]

0 20 40 60 80 100

0 20 40 60 80 100

Q[m³/h]0

10

20

NP

SH

[m

]

0 4 8 12 16 24 2820 Q[l/s]

Q[m³/h]

Q min

31m37m

44m50m

+

0

5

10

15

20

25

P1[kW]

Page 97: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

97

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Pump curves Wilo-CronoTwin-DL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-DL-E 50/10-60 BF

2-pole, �p-c (constant) - individual operation

Wilo-DL-E 50/10-60 BF

2-pole, �p-c (constant) - parallel operation

Wilo-DL-E 65/8-40 BF

2-pole, �p-c (constant) - individual operation

Wilo-DL-E 65/8-40 BF

2-pole, �p-c (constant) - parallel operation

Wilo-CronoTwin-DL-E50/10-60 BF

p-c

max.

max.

10m16m

0

10

20

30

40

50

60

70

H[m]

0 10 20 30 40 60

0 10 20 30 40 60

50

50

Q[m³/h]0

10

20

NP

SH

[m

]

0 2 4 6 8 12 14 1610 Q[l/s]

0

8

16

4

12

P1[kW]

Q[m³/h]

Q min

33m41m

50m58m

25m

Wilo-CronoTwin-DL-E50/10-60 BF

p-c

max.

max.

0

10

20

30

40

50

60

70

H[m]

0 20 40 60 80 120

0 20 40 60 80 120

100

100

Q[m³/h]0

10

20

30

NP

SH

[m

]

0 4 8 12 16 24 28 3220 Q[l/s]

0

152025

3530

510

P1[kW]

Q[m³/h]

Q min

41m49m

57m

25m

+

10m16m

33m

Wilo-CronoTwin-DL-E65/8-40 BF

p-c max.

max.

6m

20m25m

36m

0

5

10

20

30

40

15

25

35

45

H[m]

0 10 20 30 40 50 60

0 10 20 30 40 50 60

70

70

Q[m³/h]0

5

10

NP

SH

[m

]

0 4 8 12 16 20 Q[l/s]

0

4

8

12

2

6

10

P1[kW]

Q[m³/h]

31m

11m

Q min

Wilo-CronoTwin-DL-E65/8-40 BF

p-c

max.

max.

6m

20m25m

36m

0

5

10

20

30

40

15

25

35

45

H[m]

0 25 50 75 100 125 150 175

0 25 50 75 100 125 150 175

Q[m³/h]0

30

15

NP

SH

[m

]

0 10 20 30 40 50 Q[l/s]

Q[m³/h]

+

31m

11m

Q min

0

5

10

15

20

25

P1[kW]

Page 98: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

98 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL-E...BF

Wilo-DL-E 80/8-40 BF

2-pole, �p-c (constant) - individual operation

Wilo-DL-E 80/8-40 BF

2-pole, �p-c (constant) - parallel operation

Wilo-DL-E 100/8-33 BF

2-pole, �p-c (constant) - individual operation

Wilo-DL-E 100/8-33 BF

2-pole, �p-c (constant) - parallel operation

Wilo-CronoTwin-DL-E80/8-40 BF

p-c

max.

max.

6m

23m28m

0

5

10

20

30

40

15

25

35

45

H[m]

0

5

10

NP

SH

[m

]

P1[kW]

34m

12m

Q min

0 20 40 60 80 120

0 20 40 60 80 120

100

100

Q[m³/h]

0 4 8 12 16 24 28 3220 Q[l/s]

Q[m³/h]

39m

17m

0

5

10

15

Wilo-CronoTwin-DL-E80/8-40 BF

p-c

max.

max.

6m

23m28m

0

5

10

20

30

40

15

25

35

45

H[m]

0

5

10

15

NP

SH

[m

]

34m

12m

Q min

0 40 80 120 160 240

0 40 80 120 160 240

200

200

Q[m³/h]

0 403020 70605010 Q[l/s]

Q[m³/h]

39m

17m

+

0

152025

3530

510

P1[kW]

Wilo-CronoTwin-DL-E100/8-33 BF

p-c

max.

max.

5m

19m25m

0

5

10

20

30

15

25

35

H[m]

0

20

10

NP

SH

[m

]

31m

9m

Q min

14m

0 50 100 150 250 300

0

200

50 100 150 250 300200

Q[m³/h]

0 403020 7060 805010 Q[l/s]

Q[m³/h]0

5

10

15

20

25

P1[kW]

Wilo-CronoTwin-DL-E100/8-33 BF

p-c max.

max.

5m

17m

24m

21m

28m

0

5

10

20

30

15

25

35

H[m]

0

20

10

NP

SH

[m

]

31m

Q min

14m10m

0 50 100 150 250 300

0

200

50 100 150 250 300200

Q[m³/h]

0 403020 7060 805010 Q[l/s]

Q[m³/h]05

10152025303540

P1[kW]

+

Page 99: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

99

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Terminal diagram, motor data Wilo-CronoTwin-DL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-CronoTwin-DL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram

L1 L2 L3 PE PE

SBM SSM

DDG

1 32

31 3332 41 4342

(1) (3)

n=constant + Δp-cΔp-c

(2)

4 5 6 7 8 9 10 11 18 19 20

Ext. off

L1, L2, L3: Mains connection: 3~400 V AC/50 Hz; 3~380 V AC/60 Hz

PE: Protective conductor connection

DDG: Connection for differential pressure sensor

Ext. off: "Overriding Off" control inputThe pump can be switched on or off via an external, po-tential-free contact (24 V DC/10 mA).

SBM:* Potential-free collective run signal (changeover contact according to VDI 3814)

SSM:* Potential-free collective fault signal (changeover contact according to VDI 3814)

n=cons-tant:

Control mode with fixed motor speed

�p-c: Control mode with constant differential pressure

* Load capacity of contacts for SBM and SSM:42 V DC or 250 V AC/0.1-2 ANote for DL-E…BF: Detailed information on the controls for the dou-ble pumps are to be found in the installation and operating instruc-tions.

Motor data (4-pole)

Wilo-CronoTwin-DL-E...BF

Nominal motor power Speed Power consumption Nominal current (approx.)

P2 n P1 IN 3~400 V

[kW] [rpm] [kW] [A]

150/2-15 11 375 - 1450 13.0 22.6

Three-phase motor (three-phase current), 4-pole - 3~400V, 50 Hz / 3~380V, 60 HzObserve motor name plate data

Motor data (2-pole)

Wilo-CronoTwin-DL-E...BF

Nominal motor power Speed Power consumption Nominal current (approx.)

P2 n P1 IN 3~400 V

[kW] [rpm] [kW] [A]

40/11-64 11 750 - 2900 13.0 22.6

50/9-52 11 750 - 2900 13.0 22.6

50/10-60 15 750 - 2900 18.5 29.0

65/8-40 11 750 - 2900 13.0 22.6

80/8-40 15 750 - 2900 18.5 29.0

100/8-33 22 750 - 2900 25.1 41.2

Three-phase motor (three-phase current), 4-pole - 3~400V, 50 Hz / 3~380V, 60 HzObserve motor name plate data

Page 100: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

100 Subject to change 09/2008 WILO SE

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-CronoTwin-DL-E...BF

Energy-saving pumps Double pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-CronoTwin-DL-E...BF Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing A

l 1x

Øg

a

Th

b1 s b23xoxp

l 0m

hs

b 4

50

fe

c

Ø18

50

DN

nxd L

Ød

ØD

ØK

III

DDimensions, weights (4-pole)

Wilo-CronoTwin-DL-E...BF

Nomi-nal

flange dia-meter

Overall lengt

h

Dimensions

Threaded ca-ble con-nec-tion

Weight ap-prox.

Di-men-sion drawing

DN l0 A b1 b2 b4 c e f Ø g h l1 m o p q s x Th M –

– [mm] – [mm] – [kg] –

150/2-15

150 700 210 215 241 391 640 91 309 258 918 818 365 M16 25 – 550 130

2xM251x

M40

474 A

Dimensions, weights (2-pole)

Wilo-CronoTwin-DL-E...BF

Nomi-nal

flange diame-ter

Over-all lengt

h

Dimensions

Thread-ed ca-

ble con-nection

Weight approx.

Di-men-sion drawing

DN l0 A b1 b2 b4 c e f Ø g h l1 m o p q s x Th M –

– [mm] – [mm] – [kg] –

40/11-64 40 440 110 145 147 391 500 38 192 258 768 699 220 M10 20 – 400 100

2xM251xM40

364 A

50/9-52 50 440 120 145 148 391 500 50 200 258 768 705 220 M10 20 – 400 100 362 A

50/10-60 50 440 120 145 148 419 500 50 200 313 768 717 220 M10 20 – 400 100 421 A

65/8-40 65 430 153 134 144 – 440 55 185 258 1140 710 215 M12 20 370 400 120 355 B

80/8-40 80 440 155 144 160 – 440 62 188 313 1180 727 220 M12 20 390 400 120 423 B

100/8-33 100 500 180 173 188 – 580 80 250 351 1292 804 226 M12 20 426 440 135 570 B

Page 101: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

101

Energy-saving pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Energy-saving pumps

Dimensions, weights Wilo-CronoTwin-DL-E...BF

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Flange dimensions

Wilo-CronoTwin-DL-E...BF

Nominal flange diame-ter Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

40... 40 150 84 110 4 x 19

50... 50 165 99 125 4 x 19

65... 65 185 118 145 4 x 19

80... 80 200 132 160 8 x 19

100... 100 220 156 180 8 x 19

150... 150 285 211 240 8 x 23

Pump flange dimensions - according to EN 1092-2 PN 16, n = number of drilled holes

Page 102: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

102 Subject to change 09/2008 WILO SE

Standard pumpsSingle in-line pumps, double in-line pumps

Series overview

Standard pumps Single in-line pumps, double in-line pumps Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroLine-IPL

>DesignGlanded pump in in-line design with screwed connection or flange connection

>ApplicationFor pumping heating water (according to VDI 2035), water-glycol mixtures and cool-ing and cold water without abrasive sub-stances in heating, cold water and cooling water systems

Series: Wilo-CronoLine-IL

>DesignGlanded pump in in-line design with flange connection

>ApplicationFor pumping heating water (according to VDI 2035), water-glycol mixtures and cool-ing and cold water without abrasive sub-stances in heating, cold water and cooling water systems

H[m

]

Q[m³/h]14080604020 120 16010000

2

4

6

8

Wilo-VeroLine-IPLn = 1450 1/min

IPL 100

IPL 80

IPL 50IPL 65

IPL 40

IPL 32

H[m

]

Q[m³/h]4020 60 80 120100005

10

20

30

4540

15

25

35

Wilo-VeroLine-IPLn = 2900 1/min

IPL 80

IPL 50

IPL 65IPL 40IPL 32

IPL 30IPL 25

210

543

876

109

IL 200

1000 200 300 400 500Q[m³/h]

H[m

]

Wilo-CronoLine-ILn = 960 1/min

IL 250

00

10

20

3040

60

50

8070

1 10 30 100 300Q[m³/h]

H[m

]

5

IL 125

IL 32 IL 40IL 50 IL 65 IL80

IL 100

IL 150

IL 200

Wilo-CronoLine-IL n=1450 1/min

H[m

]

100110

IL50

IL40

IL80 IL100

90807060504030201002 4 12 24 80 320Q[m³/h]

IL65

IL32

Wilo-CronoLine-ILn = 2900 1/min

Page 103: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

103

Standard pumpsSingle in-line pumps, double in-line pumps

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series overview

Standard

pum

ps

Standard pumps Single in-line pumps, double in-line pumps Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroLine-IPL

> Special features/product benefits• High corrosion protection due to cataphoretic coating• Standard condensate drainage holes in the motor housings and lanterns• Series version: Motor with one-piece shaft• Version N: Standard motor B5 or V1 with stainless steel plug shaft• Bidirectional mechanical seal with forced flushing• Easy to install due to feet with threaded holes on pump housing

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . . • Wilo Control pump management systems . . . . . . . . . . . . . . . . . . . . . . . . .

Page7106108110118119216

248

Series: Wilo-CronoLine-IL

> Special features/product benefits• Reduced life cycle costs due to optimised efficiency• Standard condensate drainage holes in the motor housings• Can be used flexibly in air-conditioning and cooling systems, with application benefits due di-rect draining of condensate via optimised lantern design (patented)

• High corrosion protection due to cataphoretic coating• Easy to install due to feet with threaded holes on pump housing• Bidirectional mechanical seal with forced flushing• High degree of availability due to worldwide obtainability of standard motors (in accordance

with Wilo specifications) and mechanical seals

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . . • Wilo Control pump management systems . . . . . . . . . . . . . . . . . . . . . . . . .

Page7106123126138140216

248

Page 104: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

104 Subject to change 09/2008 WILO SE

Standard pumpsSingle in-line pumps, double in-line pumps

Series overview

Standard pumps Single in-line pumps, double in-line pumps Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroTwin-DPL

>DesignGlanded double pump in in-line design with flange connection

>ApplicationFor pumping heating water (according to VDI 2035), water-glycol mixtures and cool-ing and cold water without abrasive sub-stances in heating, cold water and cooling water systems

Series: Wilo-CronoTwin-DL

>DesignGlanded double pump in in-line design with flange connection

>ApplicationFor pumping heating water (according to VDI 2035), water-glycol mixtures and cool-ing and cold water without abrasive sub-stances in heating, cold water and cooling water systems

H[m

]

Q[m³/h]8040 120 160 20000

2

4

6

10

8

Wilo-VeroTwin-DPLn = 1450 1/min

+

DPL 100DPL 50

DPL 40DPL

32

DPL 80

DPL 65

H[m

]

Q[m³/h]8040 120 160 200005

10

20

30

4540

15

25

35

Wilo-VeroTwin-DPLn = 2900 1/min

+

DPL 80DPL 50

DPL 65DPL 40DPL 32

H[m

]

Q[m³/h]400200 600 800 100000

40

30

20

10

Wilo-CronoTwin-DLn = 1450 1/min

+

DL 80DL 100

DL 125 DL 150 DL 200DL 50 DL 65D

L 40DL 32

H[m

]

Q[m³/h]20010050 300150 25000

60

50

30

40

20

10

Wilo-CronoTwin-DLn = 2900 1/min

+

DL 80 DL 100DL 50

DL 65DL 40

DL 32

Page 105: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

105

Standard pumpsSingle in-line pumps, double in-line pumps

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series overview

Standard

pum

ps

Standard pumps Single in-line pumps, double in-line pumps Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroTwin-DPL

> Special features/product benefits• Reduction of space required and installation costs due to double pump design• Main/standby mode or peak-load operation (by means of auxiliary external device)• Standard condensate drainage holes in the motor housings and lanterns• High corrosion protection due to cataphoretic coating• Series version: Motor with one-piece shaft• Version N: Standard motor B5 or V1 with stainless steel plug shaft• Bidirectional mechanical seal with forced flushing

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . . • Wilo Control pump management systems . . . . . . . . . . . . . . . . . . . . . . . . .

Page7106147149162163216

248

Series: Wilo-CronoTwin-DL

> Special features/product benefits• Reduced life cycle costs due to optimised efficiency• Reduction of space required and installation costs due to double pump design• Main/standby mode or peak-load operation (by means of external auxiliary device)• Peak-load operation (by means of external auxiliary device)• Standard condensate drainage holes in the motor housings• Can be used flexibly in air-conditioning and cooling systems, with application benefits due to direct draining of condensate via optimised lantern design (patented)

• High corrosion protection due to cataphoretic coating• Bidirectional mechanical seal with forced flushing• High worldwide availability of standard motors (according to Wilo specifications) and standard mechanical seals

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . . • Wilo Control pump management systems . . . . . . . . . . . . . . . . . . . . . . . . .

Page7106167168187189216

248

Page 106: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

106 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Technical dataStandard pumps Single pumps (heating, air-conditioning, cooling and industry) Technical data Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo- VeroLine-IPL Wilo- Crono-Line-IL

Wilo- VeroTwin-DPL

Wilo- CronoTwin-DL

Approved fluids (other fluids on request)

Heating water (in accordance with VDI 2035) • • • • •Water-glycol mixtures (for 20-40 vol.% glycol and fluid temperature � 40 °C) • • • • •

Cooling and cold water • • • • •Heat transfer oil Special version at additional charge

Permitted field of application

Standard version for operating pressure, pmax [bar]

10

13 (up to +140°C)16 (up to +120°C)

10

13 (up to +140°C)16 (up to +120°C)

Special version for operating pressure, pmax [bar] 16 25 (on request) 16 25 (on request)

Temperature range [°C] - 10 to + 120 - 10 to + 120 - 20 to + 140 - 10 to + 120 - 20 to + 140

Max. ambient temperature [°C] 40 40 40 40 40

Installation in closed buildings • • • • •Outdoor installation Special version at additional charge

Pipe connections

Threaded connection RP 1 - RP 11/4 – – – –

Nominal connection diameters DN 32 -100 32 - 250 32 -100 32 - 200

Flanges (according to EN 1092-2)–

PN 16 (in accordance

with EN 1092-2)PN 16

PN 16 (in accordance

with EN 1092-2)

PN 16 (in accordance

with EN 1092-2)

Flange with pressure-measurement connections – R 1/8 R 1/8 R 1/8 R 1/8

Materials

Pump housingEN-GJL-250

EN-GJL-250 (EN-GJS-400 on

request)EN-GJL-250

EN-GJL-250 (EN-GJS-400 on

request)

LanternEN-GJL-250

EN-GJL-250 (EN-GJS-400 on

request)EN-GJL-250

EN-GJL-250 (EN-GJS-400 on

request)

Impeller (standard)PP, fibreglass-reinforced/

EN-GJL-200 (depending on type) EN-GJL-200

PP, fibreglass-reinforced/EN-GJL-200 (depending on type)

EN-GJL-200

Impeller (special version) - G-CuSn10 - G-CuSn10

Pump shaft 1.4021 1.4122 1.4021 1.4122

Mechanical seal AQEGG

Other mechanical seals On request (at additional charge)

Electrical connection

Mains connection3~400 V, 50 Hz

3~400 V, 50 Hz (others on re-

quest)3~400 V, 50 Hz

3~400 V, 50 Hz (others on re-

quest)

Page 107: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

107

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Technical data

Standard

pum

ps

Speed range [rpm] 1450/2900 960/1450/29001450-2900 1450/2900 1450/2900

1450-2900

Motor/electronics

Integrated full motor protection Special version with PTC thermistor sensor (TRS) at additional charge

Protection class IP 55 IP 55 IP 55 IP 55 IP 55

Insulation class F F F F F

Speed control Wilo control system

Motor winding up to 3 kW 230 V �/400 V Y, 50 Hz

Motor winding from 4 kW 400 V �/690 V Y, 50 Hz

Installation options

Pipe installation (� 15 kW motor power) • • • • •Support-bracket mounting • • • • •

• = available, - = not available

Wilo- VeroLine-IPL Wilo- Crono-Line-IL

Wilo- VeroTwin-DPL

Wilo- CronoTwin-DL

Page 108: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

108 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-VeroLine-IPL

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroLine-IPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignGlanded pump in in-line design with screwed connection or flange connection

ApplicationFor pumping heating water (according to VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cooling water systems

Scope of delivery• Pump• Installation and operating instructions

Type key

Technical data• Permissible temperature range -10°C to +120°C• Mains connection 3~400 V, 50 Hz• Protection class IP 55• Nominal diameter Rp 1 to DN 100• Max. operating pressure 10 bar (special version: 16 bar)

Special features/product benefits• High corrosion protection due to cataphoretic coating• Standard condensate drainage holes in the motor housings and lan-terns

• Series version: Motor with one-piece shaft• Version N: Standard motor B5 or V1 with stainless steel plug shaft• Bidirectional mechanical seal with forced flushing• Easy to install due to feet with threaded holes on pump housing

Materials• Pump housing and lantern: EN-GJL-250• Impeller: PP fibreglass-reinforced /

EN-GJL-200 (depending on pump type)• Shaft: 1.4021 (version N: 1.4404)

• Mechanical seal: AQ1EGG;other mechanical seals on request

Description/designSingle-stage, low-pressure centrifugal pump in in-line design with

• Mechanical seal • Flange connection with pressure measuring connection R 1/8• Motor with one-piece shaft

Example IPL 40/160-4/2

IPL In-line pump

40 Nominal diameter DN of the pipe connection

160 Nominal impeller diameter

4 Nominal motor power P2 in kW

2 Number of poles

Page 109: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

109

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-VeroLine-IPL

Standard

pum

ps

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroLine-IPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Q[m³/h]0 40 120 1608020 100 14060 18030 110 1507010 90 13050 170

H[m]

0

1

2

3

4

5

6

7

8

9Wilo-VeroLine-IPLn = 1450 1/min

IPL 100IPL 80IPL 50 IPL 65

IPL 40IPL 32

Q[m³/h]0 10 20 30 40 50 60 70 80 90 100 120 130110

H[m]

0

5

45

50

40

35

30

25

20

15

10

Wilo-VeroLine-IPLn = 2900 1/min

IPL 80

IPL 50

IPL 65

IPL 40IPL 32

IPL 30IPL 25

Page 110: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

110 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroLine-IPL

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-VeroLine-IPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IPL 32/110-0,25/4 - 32/160-0,25/4

Speed 1450 rpm

Wilo-VeroLine-IPL 40/80-0,09/4 - 40/110-0,12/4

Speed 1450 rpm

Wilo-VeroLine-IPL 40/130-0,25/4 - 40/160-0,37/4

Speed 1450 rpm

Wilo-VeroLine-IPL 50/110-0,25/4

Speed 1450 rpm

0 2 4 6 8

0 2 4 6 8

0 2 4 6 8 Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]0 0,5 1,0 1,5 2,0

H[m]

0

1

2

3

4

5

6

7

8

00,5

2,0

1,01,5

P2[kW]

00,040,080,12

ηp[%]

010203040

IPL 32/110-0,25/4

Ø 155

Ø 155

Ø 155

Ø114

IPL 32/160-0,25/4

NPS

H [m

]

QminWilo-VeroLine-IPL 32/160 -Wilo-VeroLine-IPL 32/110

0 2 4 6 8 10

0 0,5 1,0 1,5 2,0 2,5 3,0

0

0,5

1,0

1,5

2,0

2,5

3,0

3,5

12

12

12

012

0 2 4 6 8 100

0,020,040,060,08

0 2 4 6 8 100

20

40

60

345

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Wilo-VeroLine-IPL 40/110 -Wilo-VeroLine-IPL 40/80

Ø 106

Ø 106

Ø 79

Ø 106

IPL 40/80-0,09/4

IPL 40/110-0,12/4

Qmin

0 5 10 15 20 25

0 2

0

1

2

3

4

5

6

7

8

0123

0 5 10 15 20 250

0,10,20,3

0 5 10 15 20 250

204060

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Wilo-VeroLine-IPL 40/160 -Wilo-VeroLine-IPL 40/130

Ø 151

IPL 40/160-0,37/4

IPL 40/130-0,25/4

45

Ø 151

Ø 133

Ø 151

Qmin

0 4 8 12 16

0 1 2

0

0,5

1,0

1,5

2,0

2,5

3,0

3,5

4,0

00,40,81,2

0 4 8 12 160

0,04

0,08

0,12

0 4 8 12 160

204060

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Wilo-VeroLine-IPL 50/110

IPL 50/110-0,25/4

Ø 107

Ø 107

Ø 107

1,62,02,4

Qmin

Page 111: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

111

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroLine-IPL

Standard

pum

ps

Wilo-VeroLine-IPL 50/130-0,37/4 - 50/160-0,55/4

Speed 1450 rpm

Wilo-VeroLine-IPL 65/120-0,25/4 - 65/150-0,75/4

Speed 1450 rpm

Wilo-VeroLine-IPL 80/130-0,75/4 - 80/150-1,1/4

Speed 1450 rpm

Wilo-VeroLine-IPL 100/135-1,1/4 - 100/175-3/4

Speed 1450 rpm

0 5 10 15 20 25 30

0 2 4 6 8

0

1

2

3

4

5

6

7

0123

0 5 10 15 20 25 300

0,2

0,4

0 5 10 15 20 25 300

204060

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

IPL 50/130-0,37/4N

PSH

[m]

Wilo-VeroLine-IPL 50/160 -Wilo-VeroLine-IPL 50/130

Ø 156

Ø 127

Ø 156

Ø 156

IPL 50/160-0,55/4

456

Qmin

0 10 20 30 40 50

0 4 8 1 6

0

1

2

3

4

5

6

7

8

0123

0 10 20 30 40 500

0,20,40,6

0 10 20 30 40 500

204060

456

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

IPL 65/150-0,75/4

NPS

H [m

]

Wilo-VeroLine-IPL 65/150 -Wilo-VeroLine-IPL 65/120

Ø 149

Ø 140

Ø 149

Ø 149

IPL 65/140-0,55/4IPL 65/130-0,37/4IPL 65/120-0,25/4

Ø 127Ø 115

Qmin

0 20 40 6 0

0 5 10 15 20

0

1

2

3

4

5

6

7

8

01234

0 20 40 6 00

0,4

0,8

0 20 40 6 00

204060

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

IPL 80/150-1,1/4

NPS

H [m

]

Wilo-VeroLine-IPL 80/150 -Wilo-VeroLine-IPL 80/130

Ø 155

Ø 135

Ø 155

Ø 155

IPL 80/130-0,75/4

567

Qmin

0 40 80 120 160 200

0 10 20 30 40 50

0

2

4

6

8

10

0

2

4

0 40 80 120 160 2000

1

2

3

0 40 80 120 160 2000

20406080

6

8

H[m]

P2[kW]

ηp[%]

IPL 100/175-3/4

NPS

H [m

]

Wilo-VeroLine-IPL 100/175 -Wilo-VeroLine-IPL 100/135

Qmin

Ø 175

Ø 165

Ø 175

IPL 100/165-2,2/4

IPL 100/145-1,5/4

IPL 100/135-1,1/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

Ø 175

Ø 145Ø 135

Page 112: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

112 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroLine-IPL

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-VeroLine-IPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IPL 25/70-0,12/2 - 25/90-0,25/2

Speed 2900 rpm

Wilo-VeroLine-IPL 30/70-0,12/2 - 30/90-0,25/2

Speed 2900 rpm

Wilo-VeroLine-IPL 32/90-0,37/2 - 32/160-1,1/2

Speed 2900 rpm

Wilo-VeroLine-IPL 32/165-3/2 - 32/175-4/2

Speed 2900 rpm

8 1

8 1

8 1 Q[m³/h]

Q[m³/h]

Q[m³/h]

0 2 4 6 0

Q[l/s]0 0,5 1,0 1,5 2,0 2,5

H[m]

0

2

4

6

8

10

12

0123456

0 2 4 6 0

P2[kW]

00,050,100,150,20

0 2 4 6 0

ηp[%]

0

20

40

60

NPS

H [m

]

Wilo-VeroLine-IPL 25/90 -Wilo-VeroLine-IPL 25/70

IPL 25/90-0,25/2IPL 25/80-0,12/2

IPL 25/70-0,12/2

Qmin

IPL 25/85-0,18/2

Ø 89

Ø 89

Ø 89

Ø 81Ø 78

Ø 70

8 1

8 1

8 1 Q[m³/h]

Q[m³/h]

Q[m³/h]

0 2 4 6 0

Q[l/s]0 0,5 1,0 1,5 2,0 2,5

H[m]

0

2

4

6

8

10

12

0123456

0 2 4 6 0

P2[kW]

00,050,100,150,20

0 2 4 6 0

ηp[%]

0

20

40

60

NPS

H [m

]

Wilo-VeroLine-IPL 30/90 -Wilo-VeroLine-IPL 30/70

IPL 30/90-0,25/2IPL 30/80-0,12/2

IPL 30/70-0,12/2

Qmin

IPL 30/85-0,18/2

Ø 89

Ø 89

Ø 89

Ø 81Ø 78

Ø 70

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 2 4 6 8 10 12 14 16

Q[l/s]0 2 4

H[m]

0

4

8

12

16

20

24

28

0

2

4

6

8

0 2 4 6 8 10 12 14 16

P2[kW]

0

0,4

0,8

1,2

0 2 4 6 8 10 12 14 16

ηp[%]

0

20

40

IPL 32/160-1,1/2

IPL 32/130-1,1/2

IPL 32/110-0,75/2

IPL 32/100-0,55/2

IPL 32/90-0,37/2

Ø155

Ø92

Ø155

Ø102

Ø128Ø114

Ø155

Wilo-VeroLine-IPL 32/160 -Wilo-VeroLine-IPL 32/90

NPS

H [m

]

Qmin

0 5 10 15 20 25

0 1 2 3 4 5 6 7 8

0

5

10

15

20

25

30

35

40

45

02468101214

0 5 10 15 20 250123

0 5 10 15 20 25

30

30

300

20

40

60

NPS

H [m

]

Wilo-VeroLine-IPL 32/175 -Wilo-VeroLine-IPL 32/165Qmin

IPL 32/175-4/2IPL 32/165-3/2

Ø173

Ø173

Ø173

Ø157

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Q[m³/h]

Q[m³/h]

Page 113: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

113

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroLine-IPL

Standard

pum

ps

Wilo-VeroLine-IPL 40/70-0,12/2

Speed 2900 rpm

Wilo-VeroLine-IPL 40/90-0,37/2 - 40/115-0,55/2

Speed 2900 rpm

Wilo-VeroLine-IPL 40/120-1,5/2 - 40/160-4/2

Speed 2900 rpm

Wilo-VeroLine-IPL 40/165-4/2 - 40/175-5,5/2

Speed 2900 rpm

3 4 5

0 4 8 12 16

0 1 2

0

0,5

1,0

1,5

2,0

2,5

3,0

3,5

4,0

4,5

012345

0 4 8 12 160

0,04

0,08

0,12

0 4 8 12 160

20

40

60

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

IPL 40/70-0,12/2N

PSH

[m]

Wilo-VeroLine-IPL 40/70Qmin

Ø 66

Ø 66

Ø 66

4

0 2 4 6 8 10 12 14 16 18 20

0 2

0

2

4

6

8

10

12

14

02468

0 2 4 6 8 10 12 14 16 18 200

0,2

0,4

0,6

0 2 4 6 8 10 12 14 16 18 200

20

40

6

60

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

IPL 40/115-0,55/2IPL 40/90-0,37/2Ø106

Ø106

Ø86

Ø106

Wilo-VeroLine-IPL 40/115Wilo-VeroLine-IPL 40/90

0 10 20 30 40 50

0 4 8 12 16

0

5

10

15

20

25

30

35

048121416

0 10 20 30 40 5001234

600 10 20 30 40 500

20406080

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Wilo-VeroLine-IPL 40/160 -Wilo-VeroLine-IPL 40/120Qmin

Ø147Ø156

Ø156

Ø156

Ø124Ø133

IPL 40/160-4/2

IPL 40/130-2,2/2

IPL 40/150-3/2

IPL 40/120-1,5/2

60

60 0 5 10 15 20 25 30 35 40 45

0 5 10

0

5

10

15

20

25

30

35

40

45

02468101214

0 5 10 15 20 25 30 35 40 450

2

4

0 5 10 15 20 25 30 35 40 450

204060

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]Qmin

IPL 40/175-5,5/2IPL 40/165-4/2

Ø168

Ø168

Ø155

Ø168

Wilo-VeroLine-IPL 40/175-Wilo-VeroLine-IPL 40/165

Page 114: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

114 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroLine-IPL

Wilo-VeroLine-IPL 40/195-7,5/2

Speed 2900 rpm

Wilo-VeroLine-IPL 50/115-0,75/2

Speed 2900 rpm

Wilo-VeroLine-IPL 50/120-1,5/2 - 50/150-4/2

Speed 2900 rpm

Wilo-VeroLine-IPL 50/155-4/2

Speed 2900 rpm

Q[m³/h]

Q[l/s]

0 5 10 15 20 25 30 35

0 1 2 3 4 5 6 7 8 9 10 11

0

5

10

15

20

25

30

35

40

45

50

55

60

0246810

0 5 10 15 20 25 30 350246

0 5 10 15 20 25 30 350

20

40

60

Q[m³/h]

Q[m³/h]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

IPL 40/195-7,5/2

Ø195

Ø195

Ø195

Wilo-VeroLine-IPL 40/195

0 4 8 12 16 20 24 28 32

0 4 8

0

2

4

6

8

10

12

14

0

2

4

6

0 4 8 12 16 20 24 28 320

0,20,40,60,8

0 4 8 12 16 20 24 28 320

20406080

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

Ø107

Ø107

Ø107

IPL 50/115-0,75/2

Wilo-VeroLine-IPL 50/115

0 5 10 15 20 25 30 35 40 45 50 55

0 5 10 15

02468

10121416182022242628

0246810

0 5 10 15 20 25 30 35 40 45 50 550

1,6

3,2

0 5 10 15 20 25 30 35 40 45 50 550

204060

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

IPL 50/140-3/2IPL 50/120-1,5/2

IPL 50/150-4/2IPL 50/130-2,2/2

Ø145

Ø145

Ø145

Ø123Ø112

Ø134

Wilo-VeroLine-IPL 50/150 -Wilo-VeroLine-IPL 50/120

0 5 10 15 20 25 30 35 40 45 50

0 5 10 15

0

5

10

15

20

25

30

0246810

0 5 10 15 20 25 30 35 40 45 50012

0 5 10 15 20 25 30 35 40 45 50

55

55

550

20406080

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

IPL 50/155-4/2

Ø145

Ø145

Ø145

34

Wilo-VeroLine-IPL 50/155

Page 115: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

115

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroLine-IPL

Standard

pum

ps

Wilo-VeroLine-IPL 50/165-5,5/2 - 50/175-7,5/2

Speed 2900 rpm

Wilo-VeroLine-IPL 50/185-7,5/2

Speed 2900 rpm

Wilo-VeroLine-IPL 65/115-1,5/2

Speed 2900 rpm

Wilo-VeroLine-IPL 65/120-2,2/2 - 65/140-4/2

Speed 2900 rpm

0 10 20 30 40 50 60 70

0 2 4 6 8 10 12 14 16 18 20 22

0

5

10

15

20

25

30

35

40

45

0

4

8

12

0 10 20 30 40 50 60 7002468

0 10 20 30 40 50 60 700

20

40

60

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

IPL 50/165-5,5/2

IPL 50/175-7,5/2

IPL 50/175-5,5/2

Ø167

Ø167Ø157

Ø167

Wilo-VeroLine-IPL 50/175-Wilo-VeroLine-IPL 50/165

0 5 10 15 20 25 30 35 40 45 50

0 5 10 15

0

5

10

15

20

25

30

35

40

45

50

0246810

0 5 10 15 20 25 30 35 40 45 500246

8

0 5 10 15 20 25 30 35 40 45 500

20406080

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Wilo-VeroLine-IPL 50/185Qmin

IPL 50/185-7,5/2

Ø184

Ø184

Ø184

0 10 20 30 40 50

0 2 4 6 8 10 12 14 16

0

2

4

6

8

10

12

14

16

060

60

60

24681012

0 10 20 30 40 500

0,40,81,21,6

0 10 20 30 40 500

2040

6080

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

Ø116

Ø116

Ø116

IPL 65/115-1,5/2

Wilo-VeroLine-IPL 65/115

0 2

0 10 20 30 40 50 60 70 80 90

0 1 0

0

4

8

12

16

20

24

0

2

46

8

0 10 20 30 40 50 60 70 80 9001234

0 10 20 30 40 50 60 70 80 900

20406080

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]Qmin

Ø135

Ø135

Ø124Ø135

Ø114

IPL 65/130-3/2

IPL 65/140-4/2IPL 65/120-2,2/2

Wilo-VeroLine-IPL 65/140 -Wilo-VeroLine-IPL 65/120

Page 116: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

116 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroLine-IPL

Wilo-VeroLine-IPL 65/145-5,5/2 - 65/155-7,5/2

Speed 2900 rpm

Wilo-VeroLine-IPL 65/165-5,5/2 - 65/175-7,5/2

Speed 2900 rpm

Wilo-VeroLine-IPL 80/115-2,2/2

Speed 2900 rpm

Wilo-VeroLine-IPL 80/130-3/2 - 80/140-4/2

Speed 2900 rpm

0 3

0 10 20 30 40 50 60 70 80 90 100 110

0 10 2 0

0

5

10

15

20

25

30

0

5

10

15

20

0 10 20 30 40 50 60 70 80 90 100 11002468

0 10 20 30 40 50 60 70 80 90 100 110

120

120

1200

20406080

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Wilo-VeroLine-IPL 65/155 -Wilo-VeroLine-IPL 65/145Qmin

IPL65/155-7,5/2IPL 65/145-5,5/2

IPL 65/155-5,5/2

Ø140

Ø140

Ø140

Ø126

0 20 40 60 80 100

0 5 10 15 20 25

0

5

10

15

20

25

30

35

0246810

0 20 40 60 80 1000246

0 20 40 60 80 1000

204060

8

80

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

IPL 65/175-7,5/2IPL 65/165-5,5/2

IPL 65/175-5,5/2

Ø152

Ø152

Ø152

Ø134

Wilo-VeroLine-IPL 65/175 -Wilo-VeroLine-IPL 65/165

0 2

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 10 20 30 40 50 60 70 80

Q[l/s]0 1 0

H[m]

0

4

8

12

16

0

4

8

12

0 10 20 30 40 50 60 70 80

P2[kW]

0

0,8

1,6

2,4

0 10 20 30 40 50 60 70 80

ηp[%]

020406080

Ø119

Ø119

Ø119

IPL 80/115-2,2/2

Wilo-VeroLine-IPL 80/115

NPS

H [m

]

Qmin

0 10 20 30 40 50 60 70 80 90 100 110 120

0 10 20 30

0

2

4

6

8

10

12

14

16

18

20

22

0

2

4

6

8

0 10 20 30 40 50 60 70 80 90 100 110 12001234

0 10 20 30 40 50 60 70 80 90 100 110 120

130

130

1300

20406080

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

IPL 80/140-4/2

IPL 80/130-3/2 Ø135

Ø135

Ø135

Ø119

Wilo-VeroLine-IPL 80/140 -Wilo-VeroLine-IPL 80/130

Page 117: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

117

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroLine-IPL

Standard

pum

ps

Wilo-VeroLine-IPL 80/145-5,5/2 - 80/155-7,5/2

Speed 2900 rpm

0 4

0 20 40 60 80

0 20 40 60 80

0 20 40 60 80

100 120 140

0 10 20 3 0

0

2

4

6

8

10

12

14

16

18

20

22

2426

024681012

100 120 1400246

100 120 1400

204060

8

80

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

IPL 80/155-7,5/2IPL 80/145-5,5/2

Ø134

Ø134

Ø134

Ø122

Wilo-VeroLine-IPL 80/155 -Wilo-VeroLine-IPL 80/145

Page 118: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

118 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Terminal diagram, motor data Wilo-VeroLine-IPL

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-VeroLine-IPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagramsStar switching Y Delta switching �

Motor protection switch required onsite. Check the direction of rota-tion.To change the direction of rotation, swap any two phases.

P2 � 3 kW 3~400 V Y3~230 V �

P2 4 kW 3~690 V Y3~400 V �

After removing the bridges, Y-� starting is possible.

L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1 L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1

MMotor data (1450 rpm)

Wilo-VeroLine-IPL ... Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

0.09 kW 0.37 0.69 0.51

0.12 kW 0.45 0.67 0.58

0.25 kW 0.86 0.74 0.61

0.37 kW 1.10 0.75 0.65

0.55 kW 1.70 0.69 0.70

0.75 kW 1.95 0.76 0.73

1.1 kW 2.90 0.78 0.74

1.5 kW 3.35 0.82 0.79

2.2 kW 4.70 0.83 0.82

3 kW 6.40 0.83 0.83

Observe motor name plate data

Motor data (2900 rpm)

Wilo-VeroLine-IPL ... Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

0.12 kW 0.35 0.74 0.67

0.18 kW 0.53 0.77 0.68

0.25 kW 0.70 0.76 0.66

0.37 kW 1.00 0.84 0.68

0.55 kW 1.40 0.82 0.70

0.75 kW 2.00 0.86 0.68

1.1 kW 2.60 0.84 0.79

1.5 kW 3.25 0.81 0.80

2.2 kW 4.60 0.87 0.81

3 kW 6.10 0.86 0.84

4 kW 8.20 0.86 0.85

5.5 kW 10.50 0.90 0.84

7.5 kW 14.30 0.90 0.86

Observe motor name plate data

Page 119: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

119

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-VeroLine-IPL

Standard

pum

ps

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-VeroLine-IPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing A

Note:Housing with feet for installation on a base, brackets on request; II Pressure measuring connection R1/8; III Ventilation R1/8

Dimension drawing B

Note:Housing with feet for installation on a base, brackets on request; II Pressure measuring connection R1/8; III Ventilation R1/8

Dimension drawing C

III Ventilation R1/8

Øg

DNØ18

Ød

Øk

ØD

III

3 x o

IIII

x

a

c

p

c

1060

l 1

b1

b2

bm

ax

l 0

p1

em

n x d L

f

ef

50

50

II

a l1

Ø g

p 1

2 x

o

p

x

b2

bmax

b1

fem

l o

Ø d

Ø k

Ø D

DNnxd L

II

III

Øg

b1

p 1

b2

l 1

l 0

bmax

G

a t x

III

Rp

Page 120: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

120 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-VeroLine-IPL

Dimensions, weights (1450 rpm with flange connection)

Wilo-VeroLine-IPL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Im-pel-ler*

Weight approx.

Di-men-sion draw-ing

DN l0 A b1 b2 bmax c e f Ø g l1max m o p p1 x – M –

– [mm] – [mm] – [kg] –

32/110-0.25/4 32 260 70 101 106 207 90 40 50 143 295 130 M10 20 120 150 CI 20 A

32/160-0.25/4 32 260 70 101 106 207 90 40 50 143 295 130 M10 20 120 150 CI 20 A

40/80-0.09/4 40 250 65 68 78 146 – 110 110 125 272 125 M10 20 107 150 CI 13 B

40/110-0.12/4 40 250 90 80 90 170 90 40 50 143 294 125 M10 20 120 150 CI 18 B

40/130-0.25/4 40 320 75 113 121 234 90 40 50 143 289 160 M10 20 120 150 CI 21 A

40/160-0.37/4 40 320 75 113 121 234 90 40 50 143 289 160 M10 20 120 150 CI 22 A

50/110-0.25/4 50 280 83 91 101 192 90 40 50 143 300 140 M10 20 120 150 CI 22 A

50/130-0.37/4 50 340 86 116 131 247 104 40 50 143 291 170 M10 20 120 150 CI 25 A

50/160-0.55/4 50 340 86 116 131 247 104 40 50 185 327 170 M10 20 128 150 CI 27 A

65/120-0.25/4 65 340 93 119 138 257 135 40 55 143 297 170 M10 20 120 150 CI 26 A

65/130-0.37/4 65 340 93 119 138 257 135 40 55 143 297 170 M10 20 120 150 CI 27 A

65/140-0.55/4 65 340 93 119 138 257 135 40 55 185 333 170 M10 20 128 150 CI 30 A

65/150-0.75/4 65 340 93 119 138 257 135 40 55 185 333 170 M10 20 128 150 CI 31 A

80/130-0.75/4 80 360 105 125 153 278 135 40 55 185 339 180 M10 20 128 150 CI 34 A

80/150-1.1/4 80 360 105 125 153 278 135 40 55 185 339 180 M10 20 128 150 CI 35 A

100/135-1.1/4 100 500 120 159 197 356 200 226 60 176 398 250 M12 20 148 150 CI 69 A

100/145-1.5/4 100 500 120 159 197 356 200 226 60 176 423 250 M12 20 148 150 CI 69 A

100/165-2.2/4 100 500 120 159 197 356 200 226 60 196 450 250 M12 20 155 150 CI 76 A

100/175-3/4 100 500 120 159 197 356 200 226 60 196 450 250 M12 20 155 150 CI 77 A

Note concerning l1For version N (standard motor), the dimensions depend on the motor version*impeller material: CI grey cast iron; P plastic

Dimensions, weights

Wilo-VeroLine-IPL ... Thread

Screwed con-nection

Over-all

lengthDimensions Impel-

ler*Weight approx.

Dimen-sion draw-ing

G Rp l0 A b1 b2 bmax Ø g l1 p1 t x – M –

– [mm] – [kg] –

25/70-0.12/2 1½ 1 180 34 66 57 123 106 247 76 48 100 CI 6.5 C

25/80-0.12/2 1½ 1 180 34 66 57 123 106 247 76 48 100 CI 6.5 C

25/85-0.18/2 1½ 1 180 52 69 68 137 125 251 107 44 100 CI 8.0 C

25/90-0.25/2 1½ 1 180 52 69 68 137 125 251 107 44 100 CI 8.6 C

30/70-0.12/2 2 1¼ 180 34 66 57 123 106 254 76 55 100 CI 6.5 C

30/80-0.12/2 2 1¼ 180 34 66 57 123 106 254 76 55 100 CI 6.5 C

30/85-0.18/2 2 1¼ 180 52 69 68 137 125 251 107 44 100 CI 8.0 C

30/90-0.25/2 2 1¼ 180 52 69 68 137 125 251 107 44 100 CI 8.6 C

*impeller material: CI grey cast iron; P plastic

Page 121: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

121

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-VeroLine-IPL

Standard

pum

ps

Dimensions, weights

Wilo-VeroLine-IPL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Im-pel-ler*

Weight approx.

Di-men-sion drawing

DN l0 A b1 b2 bmax c e f Ø g l1max m o p p1 x – M –

– [mm] – [mm] – [kg] –

32/90-0.37/2 32 260 70 101 106 207 90 40 50 143 295 130 M10 20 120 150 CI 20 A

32/100-0.55/2 32 260 70 101 106 207 90 40 50 143 295 130 M10 20 120 150 CI 20 A

32/110-0.75/2 32 260 70 101 106 207 90 40 50 143 295 130 M10 20 120 150 CI 22 A

32/130-1.1/2 32 260 70 101 106 207 90 40 50 185 331 130 M10 20 128 150 CI 24 A

32/160-1.1/2 32 260 70 101 106 207 90 40 50 185 331 130 M10 20 128 150 CI 24 A

32/165-3/2 32 320 100 112 124 236 120 132 68 217 396 155 M10 20 160 150 CI 43 A

32/175-4/2 32 320 100 112 124 236 120 132 68 220 412 155 M10 20 168 150 CI 50 A

40/70-0.12/2 40 220 65 75 84 159 – 95 95 106 259 110 M10 20 76 150 CI 11 B

40/90-0.37/2 40 250 90 80 90 170 90 40 50 143 294 125 M10 20 120 150 CI 19 A

40/115-0.55/2 40 250 90 80 90 170 90 40 50 143 294 125 M10 20 120 150 CI 19 A

40/120-1.5/2 40 320 75 113 121 234 90 40 50 185 325 160 M10 20 128 150 CI 30 A

40/130-2.2/2 40 320 75 113 121 234 90 40 50 193 353 160 M10 20 151 150 CI 32 A

40/150-3/2 40 320 75 113 121 234 90 40 50 217 388 160 M10 20 160 150 CI 37 A

40/160-4/2 40 320 75 113 121 234 90 40 50 232 421 160 M10 20 168 150 CI 44 A

40/165-4/2 40 340 82 113 129 242 130 149 58 220 426 170 M10 20 168 150 CI 54 A

40/175-5.5/2 40 340 82 113 129 242 130 149 58 232 446 170 M10 20 168 150 CI 55 A

40/195-7.5/2 40 440 110 145 149 294 180 172 78 279 520 190 M10 20 188 150 CI 84 A

50/115-0.75/2 50 280 83 91 101 192 90 40 50 143 300 140 M10 20 120 150 CI 24 A

50/120-1.5/2 50 340 86 116 131 247 104 40 50 185 327 170 M10 20 128 150 CI 33 A

50/130-2.2/2 50 340 86 116 131 247 104 40 50 193 349.5 170 M10 20 151 150 CI 35 A

50/140-3/2 50 340 86 116 131 247 104 40 50 217 390 170 M10 20 160 150 CI 40 A

50/150-4/2 50 340 86 116 131 247 104 40 50 232 423 170 M10 20 168 150 CI 47 A

50/155-4/2 50 340 105 102 119 232 140 130 40 232 463 150 M10 20 168 150 CI 60 A

50/165-5.5/2 50 340 103 120 138 279 164 143 48 279 526 170 M10 20 188 150 CI 76 A

50/175-5.5/2 50 340 103 120 138 279 164 143 48 279 526 170 M10 20 188 150 CI 76 A

50/175-7.5/2 50 340 103 120 138 279 164 143 48 279 526 170 M10 20 188 150 CI 84 A

50/185-7.5/2 50 440 120 145 150 295 160 170 70 279 521 190 M10 20 188 100 CI 86 A

65/115-1.5/2 65 340 93 100 118 218 104 40 50 193 360.5 170 M10 20 151 150 CI 34 A

65/120-2.2/2 65 340 93 119 138 257 135 40 55 193 356 170 M10 20 151 150 CI 37 A

65/130-3/2 65 340 93 119 138 257 135 40 55 217 396 170 M10 20 160 150 CI 42 A

65/140-4/2 65 340 93 119 138 257 135 40 55 232 429 170 M10 20 168 150 CI 49 A

65/145-5.5/2 65 340 120 112 134 279 140 140 60 279 531 160 M12 20 188 150 CI 78 A

65/155-5.5/2 65 340 120 112 134 279 140 140 60 279 531 160 M12 20 188 150 CI 78 A

65/155-7.5/2 65 340 120 112 134 279 140 140 60 279 531 160 M12 20 188 150 CI 86 A

65/165-5.5/2 65 430 110 126 146 279 180 195 60 279 532 215 M12 20 188 150 CI 80 A

65/175-5.5/2 65 430 110 126 146 279 180 195 60 279 532 215 M12 20 188 150 CI 81 A

65/175-7.5/2 65 430 110 126 146 279 180 195 60 279 532 215 M12 20 188 150 CI 89 A

80/115-2.2/2 80 360 100 110 135 245 135 40 55 193 378 180 M10 20 151 150 CI 40 A

80/130-3/2 80 360 105 125 153 278 135 40 55 217 402 180 M10 20 160 150 CI 46 A

80/140-4/2 80 360 105 125 153 278 135 40 55 232 435 180 M10 20 168 150 CI 53 A

80/145-5.5/2 80 400 105 123 151 279 180 173 57 279 548 200 M12 20 188 150 CI 85 A

Page 122: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

122 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-VeroLine-IPL

80/155-7.5/2 80 400 105 123 151 279 180 173 57 279 548 200 M12 20 188 120 CI 93 A

Note concerning l1For version N (standard motor), the dimensions depend on the motor version*impeller material: CI grey cast iron; P plastic

Dimensions, weights

Wilo-VeroLine-IPL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Im-pel-ler*

Weight approx.

Di-men-sion drawing

DN l0 A b1 b2 bmax c e f Ø g l1max m o p p1 x – M –

– [mm] – [mm] – [kg] –

Flange dimensions

Wilo-VeroLine-IPL ... Nominal flange diame-ter Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

32... 32 140 78 100 4 x 19

40... 40 150 88 110 4 x 19

50... 50 165 102 125 4 x 19

65... 65 185 122 145 4 x 19

80... 80 200 138 160 8 x 19

100... 100 220 156 180 8 x 19

Pump flange dimensions - drilled according to EN 1092-2 PN 16, n = number of drilled holes

Page 123: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

123

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-CronoLine-IL

Standard

pum

ps

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoLine-IL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignGlanded pump in in-line design with flange connection

ApplicationFor pumping heating water (according to VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cooling water systems

Scope of delivery• Pump• Installation and operating instructions

Type key

Technical data• Permissible temperature range -20°C to +140°C• Mains connection 3~400 V, 50 Hz• Protection class IP 55• Nominal diameter DN 32 to DN 250• Max. operating pressure 16 bar (25 bar on request)

Special features/product benefits• Reduced life cycle costs due to optimised efficiency• Standard condensate drainage holes in the motor housings• Can be used flexibly in air-conditioning and cooling systems, with application benefits due direct draining of condensate via optimised lantern design (patented)

• High corrosion protection due to cataphoretic coating• Easy to install due to feet with threaded holes on pump housing• Bidirectional mechanical seal with forced flushing• High degree of availability due to worldwide obtainability of standard motors (in accordance with Wilo specifications) and mechanical seals

Materials• Pump housing and lantern: Standard: EN-GJL-250; optionally sphe-roidal cast iron EN-GJS-400-18-LT

• Impeller: Standard: EN-GJL-200; Special version: Red brass G-CuSn10

• Shaft: 1.4122• Mechanical seal: AQ1EGG; other mechanical seals on request

Description/designSingle-stage, low-pressure centrifugal pump in in-line design with

• Mechanical seal • Flange connection with pressure measuring connection R 1/8• Lantern• Coupling • IEC standard motor

Example IL 40/160-4/2

IL In-line pump

40 Nominal diameter DN of the pipe connection

160 Nominal impeller diameter

4 Nominal motor power P2 in kW

2 Number of poles

Page 124: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

124 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-CronoLine-IL

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoLine-IL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

0 100 200 300

IL 200

400 500 Q[m³/h]

H[m]

8

9

10

11

7

6

5

4

3

2

1

0

Wilo-CronoLine-ILn=960 1/min

H[m]

0

80

90

0 1

IL 32

5 10 30 100 300

IL 250

IL 125IL 50

IL 65

IL 80IL 100 IL 200

IL 150

IL 40

Q[m³/h]

70

60

50

40

30

20

10

Wilo-CronoLine-IL n=1450 1/min

Page 125: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

125

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-CronoLine-IL

Standard

pum

ps

Q[m³/h]2 4 12 24 80 320

H[m]

0

70

60

50

100

110

120

90

80

40

30

20

10

Wilo-CronoLine-ILn = 2900 1/min

IL 32

IL 40

IL 50

IL 65

IL 80

IL 100

Page 126: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

126 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoLine-IL

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoLine-IL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-CronoLine-IL 200/240-7,5/6 - 200/270-11/6

Speed 960 rpm

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 100 200 300 400 500

Q[l/s]0 40 80 120

H[m]

0

2

4

6

8

10

12

0

4

8

12

0 100 200 300 400 500

P2[kW]

02468

0 100 200 300 400 500

ηp[%]

0204060

IL 200/260-7,5/6IL 200/240-7,5/6

IL 200/270-11/6

Ø 272

Ø 272

Ø 272

Ø 262Ø 240

Wilo-CronoLine-IL 200/270 -Wilo-CronoLine-IL 200/240

NPS

H [m

]

Qmin

Page 127: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

127

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoLine-IL

Standard

pum

ps

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoLine-IL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-CronoLine-IL 32/140-0,25/4 - 32/170-0,55/4

Speed 1450 rpm

Wilo-CronoLine-IL 40/140-0,25/4 - 40/170-0,75/4

Speed 1450 rpm

Wilo-CronoLine-IL 40/210-1,1/4 - 40/220-1,5/4

Speed 1450 rpm

Wilo-CronoLine-IL 50/150-0,55/4 - 50/170-1,1/4

Speed 1450 rpm

6 2

6 2

6 2

Ø 175

Ø 175

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 4 8 12 1 0

Q[l/s]0 1 2 3 4 5 6

H[m]

0

2

4

6

8

10

12

01234

0 4 8 12 1 0

P2[kW]

0

0,2

0,4

0 4 8 12 1 0

ηp[%]

0

20

40

Wilo-CronoLine-IL 32/170 -Wilo-CronoLine-IL 32/140

IL 32/170-0,55/4IL 32/150-0,37/4IL 32/140-0,25/4

Ø 175

NPS

H [m

]

Qmin

Ø 157Ø 138

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 5 10 15 20 25

Q[l/s]0 2 4 6 8

H[m]

0

2

4

6

8

10

12

01234

0 5 10 15 20 25 30

30

30

P2[kW]

00,20,40,6

0 5 10 15 20 25

ηp[%]

0204060

IL 40/170-0,75/4

IL 40/140-0,25/4

IL 40/160-0,55/4IL 40/150-0,37/4

Ø 175

Ø 175

Ø 175

Ø 129

Ø 160Ø 145

Wilo-CronoLine-IL 40/170 -Wilo-CronoLine-IL 40/140

NPS

H [m

]

Qmin

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 5 10 15 20 25

Q[l/s]0 1 2 3 4 5 6 7 8

H[m]

0

2

4

6

8

10

12

14

16

18

20

01234

0 5 10 15 20 25

P2[kW]

00,40,81,2

0 5 10 15 20 25

ηp[%]

0

20

40

60

IL 40/220-1,5/4IL 40/210-1,1/4

Ø 220

Ø 205Ø 220

Ø 220

Wilo-CronoLine-IL 40/220 -Wilo-CronoLine-IL 40/210

NPS

H [m

]

Qmin

0 4

0 4

0 1

0 4 Q[m³/h]

Q[m³/h]

Q[m³/h]

0 10 20 3 0

Q[l/s]0 2 4 6 8 1 2

H[m]

0

2

4

6

8

10

12

01

2

3

0 10 20 3 0

P2[kW]

0

0,4

0,8

1,2

0 10 20 3 0

ηp[%]

0204060

IL 50/170-1,1/4

IL 50/150-0,55/4

IL 50/160-0,75/4

Ø 174

Ø 174

Ø 150Ø 164

Ø174

Wilo-CronoLine-IL 50/170 -Wilo-CronoLine-IL 50/150

NPS

H [m

]Qmin

Page 128: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

128 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoLine-IL

Wilo-CronoLine-IL 50/200-1,5/4 - 50/220-2,2/4

Speed 1450 rpm

Wilo-CronoLine-IL 50/260-3/4 - 50/270-4/4

Speed 1450 rpm

Wilo-CronoLine-IL 65/150-0,75/4 - 65/170-1,5/4

Speed 1450 rpm

Wilo-CronoLine-IL 65/210-2,2/4 - 65/220-3/4

Speed 1450 rpm

0 5

0 5

8 1

0 5 Q[m³/h]

Q[m³/h]

Q[m³/h]

0 10 20 30 4 0

Q[l/s]0 4 2

H[m]

0

2

4

6

8

10

12

14

16

18

012345

0 10 20 30 4 0

P2[kW]

00,51,01,5

0 10 20 30 4 0

ηp[%]

0204060

Wilo-CronoLine-IL 50/220 -Wilo-CronoLine-IL 50/200

NPS

H [m

]

Qmin

IL 50/220-2,2/4IL 50/200-1,5/4

Ø 211

Ø 201

Ø 211

Ø 211

0 5

0 5

8 1

0 5 Q[m³/h]

Q[m³/h]

Q[m³/h]

0 10 20 30 4 0

Q[l/s]0 4 2

H[m]

0

4

8

12

16

20

24

28

32

048121620

0 10 20 30 4 0

P2[kW]

0123

0 10 20 30 4 0

ηp[%]

0

20

40

IL 50/270-4/4

IL 50/270-3/4

IL 50/260-3/4

Ø 268

Ø 255Ø 268

Ø 268

Wilo-CronoLine-IL 50/270 -Wilo-CronoLine-IL 50/260

NPS

H [m

]

Qmin

I

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 10 20 30 40 50 60

Q[l/s]0 4 8 12 16

H[m]

0

2

4

6

8

10

12

0

1

2

3

0 10 20 30 40 50 60

P2[kW]

00,40,81,2

0 10 20 30 40 50 60

ηp[%]

0204060

Wilo-CronoLine-IL 65/170 -Wilo-CronoLine-IL 65/150

NPS

H [m

]

Qmin

IL 65/150-0,75/4

IL 65/170-1,1/4

IL 65/170-1,5/4

IL 65/160-1,1/4

Ø 173

Ø 173

Ø 159Ø 173

Ø144

S

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 10 20 30 40 50 60

Q[l/s]0 4 8 12 16

H[m]

0

4

8

12

16

20

012345

0 10 20 30 40 50 60

P2[kW]

0

1

2

0 10 20 30 40 50 60

ηp[%]

0204060

IL 65/220-2,2/4

IL 65/210-2,2/4

IL 65/220-3/4

Ø 225

Ø 225

Ø 225

Ø208

Wilo-CronoLine-IL 65/220 -Wilo-CronoLine-IL 65/210

NPS

H [m

]

Qmin

Page 129: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

129

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoLine-IL

Standard

pum

ps

Wilo-CronoLine-IL 65/250-3/4 - 65/270-5,5/4

Speed 1450 rpm

Wilo-CronoLine-IL 80/145-1,1/4 - 80/170-2,2/4

Speed 1450 rpm

Wilo-CronoLine-IL 80/210-3/4 - 80/220-4/4

Speed 1450 rpm

Wilo-CronoLine-IL 80/270-5,5/4

Speed 1450 rpm

0 8

0 8

0 8 Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 6 0

Q[l/s]0 5 10 15 20

H[m]

0

4

8

12

16

20

24

28

0246

0 20 40 6 0

P2[kW]

0

2

4

6

0 20 40 6 0

ηp[%]

0

20

40

60

Wilo-CronoLine-IL 65/270 -Wilo-CronoLine-IL 65/250

NPS

H [m

]

Qmin

IL 65/270-4/4

IL 65/270-5,5/4IL 65/250-4/4

IL 65/250-3/4

Ø 263

Ø 247Ø 263

Ø 263

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100

Q[l/s]0 5 10 15 20 25 30

H[m]

0

2

4

6

8

10

12

0

1

2

3

4

0 20 40 60 80 100

P2[kW]

00,51,01,52,0

0 20 40 60 80 100

ηp[%]

020406080

IL 80/170-2,2/4

IL 80/150-1,1/4IL 80/145-1,1/4

IL 80/160-1,5/4

Ø 175

Ø 146

Ø 175Ø 158

Ø 135

Ø 175

Wilo-CronoLine-IL 80/170 -Wilo-CronoLine-IL 80/145

NPS

H [m

]

Qmin

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100

Q[l/s]0 5 10 15 20 25 30

H[m]

0

4

8

12

16

20

0123456

0 20 40 60 80 100

P2[kW]

0123

0 20 40 60 80 100

ηp[%]

0204060

IL 80/210-3/4

IL 80/220-4/4

Ø 222

Ø 215Ø 222

Ø 222

Wilo-CronoLine-IL 80/220 -Wilo-CronoLine-IL 80/210

NPS

H [m

]

Qmin

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100

Q[l/s]0 5 10 15 20 25

H[m]

0

4

8

12

16

20

24

0

24

0 20 40 60 80 100

P2[kW]

0

2

4

6

0 20 40 60 80 100

ηp[%]

0204060

IL 80/270-5,5/4

Ø 250

Ø 250

Ø 250

Wilo-CronoLine-IL 80/270N

PSH

[m]

Qmin

Page 130: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

130 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoLine-IL

Wilo-CronoLine-IL 100/145-1,1/4 - 100/170-3/4

Speed 1450 rpm

Wilo-CronoLine-IL 100/200-3/4 - 100/220-5,5/4

Speed 1450 rpm

Wilo-CronoLine-IL 100/250-5,5/4 - 100/270-11/4

Speed 1450 rpm

Wilo-CronoLine-IL 125/190-4/4 - 125/220-7,5/4

Speed 1450 rpm

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 40 80 120 160 200

Q[l/s]0 10 20 30 40 50

H[m]

0

2

4

6

8

10

012345678

0 40 80 120 160 200

P2[kW]

0

1

2

0 40 80 120 160 200

ηp[%]

0204060

IL 100/170-3/4

IL 100/170-2,2/4

IL 100/150-1,5/4

IL 100/160-2,2/4IL 100/145-1,1/4

Ø 171

Ø 171

Ø 171

Ø 134Ø 142

Ø158

Wilo-CronoLine-IL 100/170 -Wilo-CronoLine-IL 100/145

NPS

H [m

]

Qmin

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 40 80 120 160

Q[l/s]0 10 20 30 40

H[m]

0

2

4

6

8

10

12

14

16

18

012345

0 40 80 120 160

P2[kW]

0

2

4

6

0 40 80 120 160

ηp[%]

0204060

IL 100/220-5,5/4IL 100/200-4/4

IL 100/200-3/4

IL 100/220-4/4

Ø 212

Ø 212

Ø 212

Ø 197

Wilo-CronoLine-IL 100/220 -Wilo-CronoLine-IL 100/200

NPS

H [m

]

Qmin

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 40 80 120 160 200

Q[l/s]0 10 20 30 40 50

H[m]

0

4

8

12

16

20

24

28

048121620

0 40 80 120 160 200

P2[kW]

0

4

8

12

0 40 80 120 160 200

ηp[%]

0204060

IL 100/270-11/4

IL 100/260-11/4

IL 100/260-7,5/4

IL 100/250-7,5/4

IL 100/250-5,5/4

Ø 266

Ø 266

Ø 266Ø 251Ø 241

Wilo-CronoLine-IL 100/270 -Wilo-CronoLine-IL 100/250

NPS

H [m

]

Qmin

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 40 80 120 160 200

Q[l/s]0 10 20 30 40 50

H[m]

0

2

4

6

8

10

12

14

16

18

012345

0 40 80 120 160 200

P2[kW]

0246

0 40 80 120 160 200

ηp[%]

0204060

IL 125/220-5,5/4

IL 125/210-5,5/4IL 125/190-4/4

IL 125/220-7,5/4

Ø 216

Ø 216

Ø 216

Ø 184Ø 197

Wilo-CronoLine-IL 125/220 -Wilo-CronoLine-IL 125/190

NPS

H [m

]

Qmin

Page 131: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

131

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoLine-IL

Standard

pum

ps

Wilo-CronoLine-IL 125/250-11/4 - 125/270-15/4

Speed 1450 rpm

Wilo-CronoLine-IL 125/300-15/4 - 125/340-30/4

Speed 1450 rpm

Wilo-CronoLine-IL 150/190-5,5/4 - 150/220-11/4

Speed 1450 rpm

Wilo-CronoLine-IL 150/250-15/4 - 150/270-18,5/4

Speed 1450 rpm

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 50 100 150 200 250

Q[l/s]0 20 40 60

H[m]

0

4

8

12

16

20

24

28

046810

0 50 100 150 200 250

P2[kW]

048

12

0 50 100 150 200 250

ηp[%]

0204060

IL 125/250-11/4

IL 125/270-15/4

IL 125/270-11/4

Ø 272

Ø 272

Ø 272Ø 248

Wilo-CronoLine-IL 125/270 -Wilo-CronoLine-IL 125/250

NPS

H [m

]

Qmin

L

I

0 50 100 150 200 250 300

Q[l/s]0 20 40 60 80

H[m]

0

5

10

15

20

25

30

35

40

45

02468101214

0 50 100 150 200 250 300

P2[kW]

0

10

20

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 50 100 150 200 250 300

ηp[%]

0204060

IL 125/300-18,5/4

IL 125/300-15/4

IL 125/320-18,5/4IL 125/320-22/4

IL 125/340-22/4

IL 125/340-30/4

Ø 335

Ø 335

Ø 335

Ø 312Ø 296

Wilo-CronoLine-IL 125/340 -Wilo-CronoLine-IL 125/300

NPS

H [m

]

Qmin

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 50 100 150 200 250 300

Q[l/s]0 10 20 30 40 50 60 70 80 90

H[m]

0

2

4

6

8

10

12

14

16

18

012345

0 50 100 150 200 250 300

P2[kW]

02468

10

0 50 100 150 200 250 300

ηp[%]

0204060

IL 150/200-7,5/4

IL 150/220-11/4

IL 150/190-5,5/4

Ø 224

Ø 224

Ø 224

Ø 186Ø 201

Wilo-CronoLine-IL 150/220 -Wilo-CronoLine-IL 150/190

NPS

H [m

]

Qmin

IL

L

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 100 200 300 400

Q[l/s]0 20 40 60 80 100 120

H[m]

0

4

8

12

16

20

24

28

02468

0 100 200 300 400

P2[kW]

05

101520

0 100 200 300 400

ηp[%]

0204060

Wilo-CronoLine-IL 150/270 -Wilo-CronoLine-IL 150/250

NPS

H [m

]Qmin

IL 150/260-15/4IL 150/250-15/4

IL 150/260-18,5/4

IL 150/270-22/4

IL 150/270-18,5/4

Ø 272

Ø 272

Ø 272Ø263

Ø 252

Page 132: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

132 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoLine-IL

Wilo-CronoLine-IL 150/290-30/4 - 150/310-37/4

Speed 1450 rpm

Wilo-CronoLine-IL 150/320-30/4 - 150/340-45/4

Speed 1450 rpm

Wilo-CronoLine-IL 200/230-11/4 - 200/270-30/4

Speed 1450 rpm

Wilo-CronoLine-IL 200/310-37/4 - 200/340-55/4

Speed 1450 rpm

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 100 200 300 400

Q[l/h]0 20 40 60 80 100 120

H[m]

0

5

10

15

20

25

30

35

04810

0 100 200 300 400

P2[kW]

0102030

0 100 200 300 400

ηp[%]

0204060

IL 150/310-30/4

IL 150/310-37/4

IL 150/290-30/4

Ø 314

Ø 290

Ø 314Ø 305

Ø 314

Wilo-CronoLine-IL 150/310 -Wilo-CronoLine-IL 150/290

NPS

H [m

]

Qmin

IL 150/300-30/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 100 200 300 400 500

Q[l/s]0 40 80 120

H[m]

0

5

10

15

20

25

30

35

40

45

02468101214

0 100 200 300 400 500

P2[kW]

010203040

0 100 200 300 400 500

ηp[%]

0204060

IL 150/320-37/4

IL 150/320-30/4

IL 150/340-37/4

IL 150/330-45/4

IL 150/330-37/4 IL 150/340-45/4

Ø 343

Ø 343

Ø 343Ø 333

Ø 323

Wilo-CronoLine-IL 150/340 -Wilo-CronoLine-IL 150/320

NPS

H [m

]

Qmin

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 100 200 300 400 500 600

Q[l/s]0 40 80 120 160

H[m]

0

4

8

12

16

20

24

28

0481216

0 100 200 300 400 500 600

P2[kW]

0

10

20

30

0 100 200 300 400 500 600

ηp[%]

0204060

IL 200/230-11/4

IL 200/270-30/4

Ø 272

Ø 272

Ø 272

Ø 243Ø 252

Ø 222

Ø 262

Ø 233

NPS

H [m

]

Qmin

IL 200/265-22/4IL 200/265-30/4

IL 200/260-22/4

IL 200/250-18,5/4

Wilo-CronoLine-IL 200/270 -Wilo-CronoLine-IL 200/230

IL 200/240-15/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 100 200 300 400 500 600

Q[l/s]0 40 80 120 160

H[m]

0

5

10

15

20

25

30

35

40

02468

0 100 200 300 400 500 600

P2[kW]

0

20

40

60

0 100 200 300 400 500 600

ηp[%]

0204060

IL 200/340-45/4IL 200/340-55/4IL 200/310-37/4

Ø 330

Ø 330

Ø 330

Ø 314Ø 297

Ø 322

Wilo-CronoLine-IL 200/340 -Wilo-CronoLine-IL 200/310

NPS

H [m

]

Qmin

IL 200/330-45/4

IL 200/330-55/4

IL 200/320-45/4

IL 200/320-37/4

Page 133: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

133

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoLine-IL

Standard

pum

ps

Wilo-CronoLine-IL 250/360-75/4 - 250/400-90/4

Speed 1450 rpm

Wilo-CronoLine-IL 250/410-90/4 - 250/440-132/4

Speed 1450 rpm

Wilo-CronoLine-IL 250/460-132/4 - 250/480-200/4

Speed 1450 rpm

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 200 400 600 800

Q[l/s]0 50 100 150 200

H[m]

0

10

20

30

40

50

05101520

0 200 400 600 800

P2[kW]

020406080

0 200 400 600 800

ηp[%]

0204060

IL 250/400-75/4

IL 250/370-75/4IL 250/360-75/4

Ø346

Ø380

Ø333

Ø360Ø370

Ø380

Ø380

IL 250/400-90/4

Wilo-CronoLine-IL 250/400 -Wilo-CronoLine-IL 250/360

NPS

H [m

]

Qmin

IL 250/390-75/4IL 250/390-90/4

IL 250/380-75/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 200 400 600 800

Q[l/s]0 50 100 150 200

H[m]

0

10

20

30

40

50

60

70

051015202530

0 200 400 600 800

P2[kW]

0

40

80

0 200 400 600 800

ηp[%]

0204060

IL 250/430-132/4IL 250/410-110/4

IL 250/410-90/4

IL 250/440-132/4

IL 250/440-110/4

Ø 420

Ø 420

Ø 420

Ø 402Ø 411

Ø 391

Wilo-CronoLine-IL 250/440 -Wilo-CronoLine-IL 250/410

NPS

H [m

]

Qmin

IL 250/420-90/4

IL 250/420-110/4

IL 250/430-110/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 200 400 600 800

Q[l/s]0 50 100 150 200 250

H[m]

0

20

40

60

80

100

0510152025

0 200 400 600 800

P2[kW]

050

100150

0 200 400 600 800

ηp[%]

0204060

IL 250/480-200/4

IL 250/480-160/4

IL 250/470-200/4

Ø 485

Ø 452

Ø 485

Ø 485Ø 468

Wilo-CronoLine-IL 250/480 -Wilo-CronoLine-IL 250/460

NPS

H [m

]

Qmin

IL 250/460-132/4

IL 250/470-160/4

IL 250/460-160/4

Page 134: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

134 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoLine-IL

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoLine-IL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-CronoLine-IL 32/140-1,5/2 - 32/170-4/2

Speed 2900 rpm

Wilo-CronoLine-IL 40/140-2,2/2 - 40/170-5,5/2

Speed 2900 rpm

Wilo-CronoLine-IL 40/200-7,5/2 - 40/220-11/2

Speed 2900 rpm

Wilo-CronoLine-IL 50/110-1,5/2 - 50/140-4/2

Speed 2900 rpm

IL 32/150-2,2/2IL 32/140-1,5/2

IL 32/170-3/2

IL 32/160-3/2

IL 32/160-2,2/2

IL 32/170-4/2

Ø 173

Ø 173

Ø143Ø 157

Ø 127

0 5 10 15 20 25 30

Q [l/s]0 2 4 6 8

H[m]

0

10

20

30

40

50

048

12

0 5 10 15 20 25 30

P2 [kW]

01234

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 5 10 15 20 25 30

ηp[%]

0

20

40

60

NPS

H [m

]

Wilo-CronoLine-IL 32/170 -Wilo-CronoLine-IL 32/140

Qmin

Ø 173

8 1

0 5

0 5

0 5

IL 40/160-4/2

IL 40/170-5,5/2

IL 40/140-2,2/2

IL 40/150-3/2

Ø 168

Ø 168

Ø 168

Ø 122Ø 138

Ø 150

0 10 20 30 4 0

Q[l/s]0 4 2

H[m]

0

5

10

15

20

25

30

35

40

45

0

4

8

0 10 20 30 4 0

P2[kW]

0

2

4

6

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 10 20 30 4 0

ηp[%]

0204060

Wilo-CronoLine-IL 40/170 -Wilo-CronoLine-IL 40/140

NPS

H [m

]

Qmin

IL 40/220-11/2

IL 40/200-7,5/2

Ø 215

Ø 215

Ø 195

Ø 215

0 5 10 15 20 25 30 35 40 45

Q[l/s]0 5 10

H[m]

0

10

20

30

40

50

60

70

80

0

5

10

15

20

0 5 10 15 20 25 30 35 40 45

P2[kW]

02468

10

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 5 10 15 20 25 30 35 40 45

ηp[%]

0

20

40

60

Wilo-CronoLine-IL 40/220 -Wilo-CronoLine-IL 40/200

NPS

H [m

]

Qmin

IL 50/140-3/2

IL 50/130-3/2

IL 50/120-2,2/2

IL 50/140-4/2

IL 50/110-1,5/2

Ø 138

Ø 138

Ø 101Ø 111

Ø 126

Ø 138

0 10 20 30 40 50 60

Q[l/s]0 4 8 12 16

H[m]

0

4

8

12

16

20

24

28

0481216

0 10 20 30 40 50 60

P2[kW]

0123

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 10 20 30 40 50 60

ηp[%]

0204060

NPS

H [m

]

Wilo-CronoLine-IL 50/140 -Wilo-CronoLine-IL 50/110Qmin

Page 135: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

135

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoLine-IL

Standard

pum

ps

Wilo-CronoLine-IL 50/160-5,5/2 - 50/170-7,5/2

Speed 2900 rpm

Wilo-CronoLine-IL 50/180-7,5/2 - 50/220-15/2

Speed 2900 rpm

Wilo-CronoLine-IL 50/250-18,5/2 - 50/270-30/2

Speed 2900 rpm

Wilo-CronoLine-IL 65/110-3/2 - 65/140-7,5/2

Speed 2900 rpm

0 10 20 30 40 50 60 70

Q[l/s]0 2 4 6 8 10 12 14 16 18 20 22

H[m]

0

5

10

15

20

25

30

35

40

45

0

5

10

15

0 10 20 30 40 50 60 70

P2[kW]

0246

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 10 20 30 40 50 60 70

ηp[%]

0

20

40

60

Ø 167

Ø 167

Ø 167

Ø 157

IL 50/170-7,5/2IL 50/160-5,5/2

IL 50/170-5,5/2

NPS

H [m

]

Wilo-CronoLine-IL 50/170 -Wilo-CronoLine-IL 50/160Qmin

0 8

0 8

0 8

0 20 40 6 0

Q[l/s]0 5 10 15 20

H[m]

0

10

20

30

40

50

60

70

0

10

20

0 20 40 6 0

P2[kW]

048

12

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 6 0

ηp[%]

0204060

NPS

H [m

]

Wilo-CronoLine-IL 50/220 -Wilo-CronoLine-IL 50/180Qmin

Ø 211

IL 50/180-7,5/2

IL 50/210-11/2

IL 50/220-15/2

IL 50/220-11/2

Ø 211

Ø 184Ø 201

Ø 211

0 20 40 60 80 100

Q[l/s]0 5 10 15 20 25

H[m]

0

20

40

60

80

100

120

0481216

0 20 40 60 80 100

P2[kW]

0

10

20

30

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100

ηp[%]

0

20

40

60

NPS

H [m

]

Wilo-CronoLine-IL 50/270 -Wilo-CronoLine-IL 50/250

Qmin

Ø 265

Ø 265

Ø 250

Ø 265

IL 50/270-30/2

IL 50/250-22/2

IL 50/250-18,5/2

IL 50/270-22/2

I

I

L

0 20 40 60 80 100

Q[l/s]0 5 10 15 20 25 30

H[m]

0

4

8

12

16

20

24

28

32

0481216

0 20 40 60 80 100

P2[kW]

0246

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100

ηp[%]

0204060

Ø 140

IL 65/140-7,5/2

IL 65/140-5,5/2

IL 65/130-4/2IL 65/130-5,5/2

IL 65/120-3/2

IL 65/110-3/2

IL 65/120-4/2

Ø 140

Ø 140

Ø 117Ø 126

Ø 108

Qmin

Wilo-CronoLine-IL 65/140 -Wilo-CronoLine-IL 65/110

NPS

H [m

]

Page 136: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

136 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoLine-IL

Wilo-CronoLine-IL 65/150-5,5/2 - 65/170-11/2

Speed 2900 rpm

Wilo-CronoLine-IL 65/200-11/2 - 65/220-22/2

Speed 2900 rpm

Wilo-CronoLine-IL 65/240-30/2 - 65/260-37/2

Speed 2900 rpm

Wilo-CronoLine-IL 80/120-4/2 - 80/140-7,5/2

Speed 2900 rpm

S

0 20 40 60 80 100

Q[l/s]0 5 10 15 20 25

H[m]

0

5

10

15

20

25

30

35

40

45

02468

0 20 40 60 80 100

P2[kW]

0

4

8

12

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100

ηp[%]

0204060

NPS

H [m

]

Wilo-CronoLine-IL 65/170 -Wilo-CronoLine-IL 65/150Qmin

IL 65/150-5,5/2

IL 65/170-11/2

IL 65/160-5,5/2IL 65/160-7,5/2

Ø 168

Ø 168

Ø 168

Ø 134Ø 152

L

I

0 20 40 60 80 100 120

120

120

Q[l/s]0 5 10 15 20 25 30 35

H[m]

0

10

20

30

40

50

60

70

80

04812

0 20 40 60 80 100

P2[kW]

05

101520

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100

ηp[%]

0204060

NPS

H [m

]

Wilo-CronoLine-IL 65/220 -Wilo-CronoLine-IL 65/200Qmin

IL 65/200-11/2IL 65/210-18,5/2

IL 65/220-18,5/2IL 65/220-22/2

IL 65/210-15/2

IL 65/200-15/2

Ø 217

Ø 217

Ø 194Ø 206

Ø 217

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100 120

Q[l/s]0 10 20 30

H[m]

0

20

40

40

60

80

100

0481216

0 20 40 60 80 100 120

P2[kW]

0102030

0 20 40 60 80 100 120

ηp[%]

0

20

40

60

NPS

H [m

]

Wilo-CronoLine-IL 65/260 -Wilo-CronoLine-IL 65/240Qmin IL 65/260-30/2

IL 65/260-37/2IL 65/240-30/2

Ø 252

Ø 252

Ø 252

Ø 233

0 40 80 120 160

Q[l/s]0 10 20 30 40

H[m]

0

4

8

12

16

20

24

024681012

0 40 80 120 160

P2[kW]

0246

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 40 80 120 160

ηp[%]

0204060

NPS

H [m

]

Wilo-CronoLine-IL 80/140 -Wilo-CronoLine-IL 80/110Qmin

IL 80/120-4/2

IL 80/130-5,5/2

IL 80/110-3/2

IL 80/140-7,5/2

Ø 134

Ø 134

Ø 134Ø 122

Ø 105Ø 112

Page 137: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

137

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoLine-IL

Standard

pum

ps

Wilo-CronoLine-IL 80/150-7,5/2 - 80/170-15/2

Speed 2900 rpm

Wilo-CronoLine-IL 80/190-15/2 - 80/220-30/2

Speed 2900 rpm

Wilo-CronoLine-IL 100/145-11/2 - 100/170-30/2

Speed 2900 rpm

Wilo-CronoLine-IL 100/190-30/2 - 100/210-37/2

Speed 2900 rpm

0 40 80 120 160

Q[l/s]0 10 20 30 40

H[m]

0

5

10

15

20

25

30

35

40

02468

0 40 80 120 160

P2[kW]

048

12

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 40 80 120 160

ηp[%]

020406080

NPS

H [m

]

Wilo-CronoLine-IL 80/170 -Wilo-CronoLine-IL 80/150Qmin

IL 80/170-11/2IL 80/170-15/2IL 80/160-11/2

IL 80/150-7,5/2

Ø 173

Ø 173

Ø 173

Ø 155Ø 140

L

L

/

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 40 80 120 160 200

Q[l/s]0 10 20 30 40 50

H[m]

0

10

20

30

40

50

60

70

80

0510152025

0 40 80 120 160 200

P2[kW]

0

10

20

30

0 40 80 120 160 200

ηp[%]

0204060

NPS

H [m

]

Wilo-CronoLine-IL 80/220 -Wilo-CronoLine-IL 80/190Qmin

IL 80/190-18,5/2

IL 80/190-15/2 IL 80/200-22/2

IL 80/200-18,5/2

IL 80/220-22/2IL 80/220-30/2

IL 80/210-30/2

Ø 220

Ø 220

Ø 220

Ø203Ø194

Ø 212

L

/

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 50 100 150 200 250 300

Q[l/s]0 20 40 60 80

H[m]

0

5

10

15

20

25

30

35

40

45

048121620

0 50 100 150 200 250 300

P2[kW]

0

10

20

30

0 50 100 150 200 250 300

ηp[%]

0204060

NPS

H [m

]

Wilo-CronoLine-IL 100/170 -Wilo-CronoLine-IL 100/145

Qmin

IL 100/170-22/2IL 100/170-30/2

IL 100/145-11/2

IL 100/165-22/2

IL 100/160-18,5/2

IL 100/160-15/2

IL 100/150-15/2

Ø 175

Ø 175

Ø 175

Ø 168

Ø 140Ø 150

Ø 158

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 50 100 150 200 250

Q[l/s]0 20 40 60

H[m]

0

10

20

30

40

50

60

02468

0 50 100 150 200 250

P2[kW]

0102030

0 50 100 150 200 250

ηp[%]

0204060

NPS

H [m

]

Wilo-CronoLine-IL 100/210 -Wilo-CronoLine-IL 100/190Qmin

IL 100/210-30/2 IL 100/210-37/2IL 100/190-30/2

Ø 204

Ø 204

Ø 204Ø 192

Page 138: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

138 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Terminal diagram, motor data Wilo-CronoLine-IL

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-CronoLine-IL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagramsStar switching Y Delta switching �

Motor protection switch required onsite. Check the direction of rota-tion.To change the direction of rotation, swap any two phases.

P2 � 3 kW 3~400 V Y3~230 V �

P2 4 kW 3~690 V Y3~400 V �

After removing the bridges, Y-� starting is possible.

L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1 L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1

MMotor data (960 rpm)

Wilo-CronoLine-IL ... Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

7.5 kW 16.00 0.79 0.86

11 kW 24.00 0.77 0.88

Observe motor name plate data

Motor data (1450 rpm)

Wilo-CronoLine-IL ... Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

0.25 kW 0.77 0.78 0.60

0.37 kW 1.06 0.78 0.65

0.55 kW 1.44 0.82 0.67

0.75 kW 1.91 0.81 0.72

1.1 kW 2.55 0.81 0.77

1.5 kW 3.40 0.81 0.79

2.2 kW 4.70 0.82 0.82

3 kW 6.40 0.82 0.83

4 kW 8.20 0.83 0.85

5.5 kW 11.40 0.81 0.86

7.5 kW 15.20 0.82 0.87

11 kW 21.50 0.84 0.89

15 kW 28.50 0.84 0.90

18.5 kW 35.50 0.83 0.91

22 kW 41.50 0.84 0.91

30 kW 55.00 0.86 0.92

37 kW 66.00 0.87 0.93

45 kW 80.00 0.87 0.93

55 kW 100.00 0.85 0.94

75 kW 136.00 0.85 0.94

90 kW 160.00 0.86 0.95

110 kW 198.00 0.85 0.95

132 kW 235.00 0.85 0.95

160 kW 280.00 0.86 0.96

Page 139: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

139

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram, motor data Wilo-CronoLine-IL

Standard

pum

ps

200 kW 340.00 0.88 0.96

Observe motor name plate data

Motor data (1450 rpm)

Wilo-CronoLine-IL ... Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

Motor data (2900 rpm)

Wilo-CronoLine-IL ... Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

1.5 kW 3.25 0.85 0.79

2.2 kW 4.55 0.85 0.82

3 kW 6.10 0.85 0.84

4 kW 7.80 0.86 0.86

5.5 kW 10.40 0.89 0.86

7.5 kW 13.80 0.89 0.88

11 kW 20.00 0.88 0.90

15 kW 26.50 0.90 0.90

18.5 kW 32.00 0.91 0.91

22 kW 39.50 0.88 0.92

30 kW 53.00 0.89 0.92

37 kW 65.00 0.89 0.93

Observe motor name plate data

Page 140: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

140 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-CronoLine-IL

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-CronoLine-IL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing

II Pressure measuring connection R1/8; III Ventilation R1/8

Ø18

Øg

Ød

Øk

ØD

50

p 1

b 3

b 1

b 2

l 0

l 1

50

c

ax

60

10

p

II III

II

e

DN

f

q

n x

d L

f e m

3 x o

DDimensions, weights (960 rpm)

Wilo-CronoLine-IL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q x M

– [mm] – [mm] [kg]

200/240-7.5/6 200 800 245 281 362 – 330 270 165 323 869 370 M16 25 250 – 140 345

200/260-7.5/6 200 800 245 281 362 – 330 270 165 323 869 370 M16 25 250 – 140 345

200/270-11/6 200 800 245 281 362 – 330 270 165 370 912 370 M16 25 250 – 140 345

Dimensions, weights (1450 rpm)

Wilo-CronoLine-IL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q x M

– [mm] – [mm] [kg]

32/140-0.25/4 32 320 100 112 124 118 120 132 68 145 398 155 M10 20 – 118 150 39

32/150-0.37/4 32 320 100 112 124 118 120 132 68 145 398 155 M10 20 – 118 150 40

32/170-0.55/4 32 320 100 112 124 124 120 132 68 188 423 155 M10 20 – 124 150 43

40/140-0.25/4 40 340 82 113 129 118 130 149 58 145 412 170 M10 20 – 118 95 43

40/150-0.37/4 40 340 82 113 129 118 130 149 58 145 412 170 M10 20 – 118 95 45

40/160-0.55/4 40 340 82 113 129 124 130 149 58 188 437 170 M10 20 – 124 95 46

40/170-0.75/4 40 340 82 113 129 124 130 149 58 188 437 170 M10 20 – 124 95 48

40/210-1.1/4 40 440 110 145 149 – 180 172 78 193 471 190 M10 20 151 – 100 51

40/220-1.5/4 40 440 110 145 149 – 180 172 78 193 471 190 M10 20 151 – 100 55

50/150-0.55/4 50 340 103 120 138 124 164 143 48 188 443 170 M10 20 – 124 100 48

50/160-0.75/4 50 340 103 120 138 124 164 143 48 188 443 170 M10 20 – 124 100 50

50/170-1.1/4 50 340 103 120 138 145 164 143 48 193 483 170 M10 20 – 145 100 53

50/200-1.5/4 50 440 120 145 150 – 160 170 70 193 472 190 M10 20 151 – 100 57

Page 141: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

141

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-CronoLine-IL

Standard

pum

ps

50/220-2.2/4 50 440 120 145 150 – 160 170 70 217 516 190 M10 20 160 – 100 67

50/260-3/4 50 440 122 178 174 – 200 200 70 217 542 220 M10 20 160 – 120 80

50/270-3/4 50 440 122 178 174 – 200 200 70 217 542 220 M10 20 160 – 120 80

50/270-4/4 50 440 122 178 174 – 200 200 70 232 620 220 M10 20 178 – 120 87

65/150-0.75/4 65 430 110 126 146 124 180 195 60 188 449 215 M12 20 – 124 120 53

65/160-1.1/4 65 430 110 126 146 145 180 195 60 193 489 215 M12 20 – 145 120 56

65/170-1.1/4 65 430 110 126 146 145 180 195 60 193 489 215 M12 20 – 145 120 57

65/170-1.5/4 65 430 110 126 146 149 180 195 60 193 489 215 M12 20 – 149 120 60

65/210-2.2/4 65 475 130 150 168 – 200 225 50 217 525 245 M12 20 160 – 110 73

65/220-2.2/4 65 475 130 150 168 – 200 225 50 217 525 245 M12 20 160 – 110 73

65/220-3/4 65 475 130 150 168 – 200 225 50 217 525 245 M12 20 160 – 110 76

65/250-3/4 65 475 140 187 174 – 200 215 80 217 546 235 M12 20 160 – 120 85

65/250-4/4 65 475 140 187 174 – 200 215 80 232 624 235 M12 20 178 – 120 91

65/270-4/4 65 475 140 187 174 – 200 215 80 232 624 235 M12 20 178 – 120 91

65/270-5.5/4 65 475 140 187 174 – 200 215 80 279 680 235 M12 20 188 – 120 103

80/145-1.1/4 80 440 120 136 162 145 180 173 72 193 487 200 M12 20 – 145 120 63

80/150-1.1/4 80 440 120 136 162 145 180 173 72 193 487 200 M12 20 – 145 120 63

80/160-1.5/4 80 440 120 136 162 149 180 173 72 193 487 200 M12 20 – 149 120 70

80/170-2.2/4 80 440 120 136 162 156 180 173 72 217 531 200 M12 20 – 156 120 81

80/210-3/4 80 500 145 157 182 – 220 208 62 217 533 230 M12 20 160 – 120 85

80/220-4/4 80 500 145 157 182 – 220 208 62 232 611 230 M12 20 178 – 120 91

80/270-5.5/4 80 500 125 180 202 – 240 223 102 279 667 245 M12 20 188 – 115 114

100/145-1.1/4 100 500 120 159 197 145 200 226 60 193 522 250 M12 20 – 145 135 79

100/150-1.5/4 100 500 120 159 197 149 200 226 60 193 522 250 M12 20 – 149 135 82

100/160-2.2/4 100 500 120 159 197 156 200 226 60 217 565 250 M12 20 – 156 135 93

100/170-2.2/4 100 500 120 159 197 156 200 226 60 217 565 250 M12 20 – 156 135 93

100/170-3/4 100 500 120 159 197 156 200 226 60 217 565 250 M12 20 – 156 135 96

100/200-3/4 100 550 155 173 202 – 220 231 99 217 543 255 M12 20 160 – 120 98

100/200-4/4 100 550 155 173 202 – 220 231 99 232 621 255 M12 20 178 – 120 104

100/220-4/4 100 550 155 173 202 – 220 231 99 232 621 255 M12 20 178 – 120 105

100/220-5.5/4 100 550 155 173 202 – 220 231 99 279 677 255 M12 20 188 – 120 118

100/250-5.5/4 100 550 180 188 214 – 240 236 114 279 677 260 M12 20 188 – 120 132

100/250-7.5/4 100 550 180 188 214 – 240 236 114 323 718 260 M12 20 188 – 120 138

100/260-7.5/4 100 550 180 188 214 – 240 236 114 323 718 260 M12 20 188 – 120 138

100/260-11/4 100 550 180 188 214 – 240 236 114 323 800 260 M12 20 250 – 120 174

100/270-11/4 100 550 180 188 214 – 240 236 114 323 800 260 M12 20 250 – 120 174

125/190-4/4 125 620 175 177 212 – 280 266 54 232 633 280 M16 25 178 – 120 118

125/210-5.5/4 125 620 175 177 212 – 280 266 54 279 689 280 M16 25 188 – 120 134

125/220-5.5/4 125 620 175 177 212 – 280 266 54 279 689 280 M16 25 188 – 120 134

125/220-7.5/4 125 620 175 177 212 – 280 266 54 323 730 280 M16 25 188 – 120 142

125/250-11/4 125 620 200 232 264 – 250 254 125 323 813 280 M16 25 250 – 130 201

Dimensions, weights (1450 rpm)

Wilo-CronoLine-IL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q x M

– [mm] – [mm] [kg]

Page 142: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

142 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-CronoLine-IL

125/270-11/4 125 620 200 232 264 – 250 254 125 323 813 280 M16 25 250 – 130 201

125/270-15/4 125 620 200 232 264 – 250 254 125 370 856 280 M16 25 250 – 130 213

125/300-15/4 125 700 185 238 270 – 280 315 140 370 882 340 M16 25 250 – 140 264

125/300-18.5/4 125 700 185 238 270 – 280 315 140 370 924 340 M16 25 294 – 140 274

125/320-18.5/4 125 700 185 238 270 – 280 315 140 370 924 340 M16 25 294 – 140 274

125/320-22/4 125 700 185 238 270 – 280 315 140 370 952 340 M16 25 294 – 140 284

125/340-22/4 125 700 185 238 270 – 280 315 140 370 952 340 M16 25 294 – 140 284

125/340-30/4 125 700 185 238 270 – 280 315 140 415 1012 340 M16 25 306 – 140 330

150/190-5.5/4 150 700 200 202 249 – 260 284 116 279 702 310 M16 25 188 – 130 166

150/200-7.5/4 150 700 200 202 249 – 260 284 116 323 743 310 M16 25 188 – 130 174

150/220-11/4 150 700 200 202 249 – 260 284 116 323 825 310 M16 25 250 – 130 209

150/250-15/4 150 700 230 278 320 – 288 304 146 370 887 330 M16 25 250 – 135 281

150/260-15/4 150 700 230 278 320 – 288 304 146 370 887 330 M16 25 250 – 135 281

150/260-18.5/4 150 700 230 278 320 – 288 304 146 370 929 330 M16 25 294 – 135 309

150/270-18.5/4 150 700 230 278 320 – 288 304 146 370 929 330 M16 25 294 – 135 309

150/270-22/4 150 700 230 278 320 – 288 304 146 370 957 330 M16 25 294 – 135 319

150/290-30/4 150 770 230 300 337 – 300 344 150 415 1025 370 M16 25 306 – 145 392

150/300-30/4 150 770 230 300 337 – 300 344 150 415 1025 370 M16 25 306 – 145 392

150/310-30/4 150 770 230 300 337 – 300 344 150 415 1025 370 M16 25 306 – 145 392

150/310-37/4 150 770 230 300 337 – 300 344 150 456 1061 370 M16 25 327 – 145 446

150/320-30/4 150 770 230 300 337 – 300 344 150 415 1025 370 M16 25 306 – 145 399

150/320-37/4 150 770 230 300 337 – 300 344 150 456 1061 370 M16 25 327 – 145 446

150/330-37/4 150 770 230 300 337 – 300 344 150 456 1061 370 M16 25 327 – 145 446

150/330-45/4 150 770 230 300 337 – 300 344 150 456 1125 370 M16 25 327 – 145 472

150/340-37/4 150 770 230 300 337 – 300 344 150 456 1061 370 M16 25 327 – 145 446

150/340-45/4 150 770 230 300 337 – 300 344 150 456 1125 – M16 – 327 – – 472

200/230-11/4 200 800 245 281 362 – 330 270 165 323 869 370 M16 25 250 – 140 335

200/240-15/4 200 800 245 281 362 – 330 270 165 370 912 370 M16 25 250 – 140 335

200/250-18.5/4 200 800 245 281 362 – 330 270 165 370 954 370 M16 25 294 – 140 364

200/260-22/4 200 800 245 281 362 – 330 270 165 370 982 370 M16 25 294 – 140 374

200/265-22/4 200 800 245 281 362 – 330 270 165 370 982 370 M16 25 294 – 140 374

200/265-30/4 200 800 245 281 362 – 330 270 165 415 1042 370 M16 25 306 – 140 419

200/270-30/4 200 800 245 281 362 – 330 270 165 415 1042 370 M16 25 306 – 140 419

200/310-37/4 200 820 245 322 370 – 360 370 180 456 1086 400 M16 25 327 – 155 486

200/320-37/4 200 820 245 322 370 – 360 370 180 456 1086 400 M16 25 327 – 155 486

200/320-45/4 200 820 245 322 370 – 360 370 180 456 1150 400 M16 25 327 – 155 512

200/330-45/4 200 820 245 322 370 – 360 370 180 456 1150 400 M16 25 327 – 155 512

200/330-55/4 200 820 245 322 370 – 360 370 180 495 1230 400 M16 25 392 – 155 665

200/340-45/4 200 820 245 322 370 – 360 370 180 456 1150 400 M16 25 327 – 155 512

200/340-55/4 200 820 245 322 370 – 360 370 180 495 1230 400 M16 25 392 – 155 665

Dimensions, weights (1450 rpm)

Wilo-CronoLine-IL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q x M

– [mm] – [mm] [kg]

Page 143: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

143

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-CronoLine-IL

Standard

pum

ps

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-CronoLine-IL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing

II Pressure measuring connection R1/8; III Ventilation R1/8

gxx

l 1

p1

b1

l 2 l 3

l 0

b2

b 4

b 5bm

ax

4 x d

m

D

d

K

DNG

n x

dL

II IIIII

Maße, Gewichte (1450 rpm)

Wilo-CronoLine-IL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b4 b5 bmax Ø g l1max l2 l3 m p1 x M

– [mm] [kg]

250/360-75/4 250 1150 321 369 454 340 180 932 764 1850 700 150 550 478 190 1137

250/370-75/4 250 1150 321 369 454 340 180 932 764 1850 700 150 550 478 190 1137

250/380-75/4 250 1150 321 369 454 340 180 932 764 1850 700 150 550 478 190 1137

250/390-75/4 250 1150 321 369 454 340 180 932 764 1850 700 150 550 478 190 1137

250/390-90/4 250 1150 321 369 454 340 180 932 764 1900 700 150 550 478 190 1182

250/400-75/4 250 1150 321 369 454 340 180 932 764 1850 700 150 550 478 190 1137

250/400-90/4 250 1150 321 369 454 340 180 932 764 1900 700 150 550 478 190 1182

250/410-90/4 250 1150 321 369 454 340 180 932 764 1900 700 150 550 478 190 1182

250/410-110/4 250 1150 321 369 454 340 180 1001 834 2150 700 150 550 547 190 1347

250/420-90/4 250 1150 321 369 454 340 180 932 764 1900 700 150 550 478 190 1182

250/420-110/4 250 1150 321 369 454 340 180 1001 834 2150 700 150 550 547 190 1347

250/430-110/4 250 1150 321 369 454 340 180 1001 834 2150 700 150 550 547 190 1347

250/430-132/4 250 1150 321 369 454 340 180 1001 834 2150 700 150 550 547 190 1427

250/440-110/4 250 1150 321 369 454 340 180 1001 834 2150 700 150 550 547 190 1347

250/440-132/4 250 1150 321 369 454 340 180 1001 834 2150 700 150 550 547 190 1427

250/460-132/4 250 1200 308 386 451 340 180 998 834 2150 700 175 575 547 190 1500

250/460-160/4 250 1200 308 386 451 340 180 998 834 2150 700 175 575 547 190 1637

250/470-160/4 250 1200 308 386 451 340 180 998 834 2150 700 175 575 547 190 1637

250/470-200/4 250 1200 308 386 451 340 180 998 834 2150 700 175 575 547 190 1742

250/480-160/4 250 1200 308 386 451 340 180 998 834 2150 700 175 575 547 190 1637

250/480-200/4 250 1200 308 386 451 340 180 998 834 2150 700 175 575 547 190 1742

Page 144: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

144 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-CronoLine-IL

Standard pumps Single pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-CronoLine-IL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing

II Pressure measuring connection R1/8; III Ventilation R1/8

Ø18

Øg

Ød

Øk

ØD

50

p 1

b 3

b 1

b 2

l 0

l 1

50

c

ax

60

10

p

II III

II

e

DN

f

q

n x

d L

f e m

3 x o

DDimensions, weights (2900 rpm)

Wilo-CronoLine-IL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q x M

– [mm] – [mm] [kg]

32/140-1.5/2 32 320 100 112 124 145 120 132 68 193 463 155 M10 20 – 145 150 48

32/150-2.2/2 32 320 100 112 124 149 120 132 68 193 463 155 M10 20 – 149 150 50

32/160-2.2/2 32 320 100 112 124 149 120 132 68 193 448 155 M10 20 – 149 90 50

32/160-3/2 32 320 100 112 124 156 120 132 68 217 506 155 M10 20 – 156 150 60

32/170-3/2 32 320 100 112 124 156 120 132 68 217 506 155 M10 20 – 156 90 60

32/170-4/2 32 320 100 112 124 168 120 132 68 232 584 155 M10 20 – 168 150 67

40/140-2.2/2 40 340 82 113 129 149 130 149 58 193 477 170 M10 20 – 149 95 55

40/150-3/2 40 340 82 113 129 156 130 149 58 217 520 170 M10 20 – 156 95 64

40/160-4/2 40 340 82 113 129 168 130 149 58 232 598 170 M10 20 – 168 95 71

40/170-5.5/2 40 340 82 113 129 182 130 149 58 279 644 170 M10 20 – 182 95 82

40/200-7.5/2 40 440 110 145 149 – 180 172 78 279 649 190 M10 20 188 – 100 96

40/220-11/2 40 440 110 145 149 – 180 172 78 323 772 190 M10 20 250 – 100 125

50/110-1.5/2 50 340 105 102 119 145 140 130 40 193 463 150 M10 20 – 145 100 53

50/120-2.2/2 50 340 105 102 119 149 140 130 40 193 463 150 M10 20 – 149 100 56

50/130-3/2 50 340 105 102 119 156 140 130 40 217 510 150 M10 20 – 156 100 68

50/140-3/2 50 340 105 102 119 156 140 130 40 217 510 150 M10 20 – 156 100 68

50/140-4/2 50 340 105 102 119 168 140 130 40 232 588 150 M10 20 – 168 100 75

50/160-5.5/2 50 340 103 120 138 182 164 143 48 279 651 170 M10 20 – 182 100 86

50/170-5.5/2 50 340 103 120 138 182 164 143 48 279 651 170 M10 20 – 182 100 86

50/170-7.5/2 50 340 103 120 138 182 164 143 48 279 651 170 M10 20 – 182 100 94

50/180-7.5/2 50 440 120 145 150 – 160 170 70 279 650 190 M10 20 188 – 100 99

50/210-11/2 50 440 120 145 150 – 160 170 70 323 773 190 M10 20 250 – 100 128

50/220-11/2 50 440 120 145 150 – 160 170 70 323 773 190 M10 20 250 – 100 128

50/220-15/2 50 440 120 145 150 – 160 170 70 323 773 190 M10 20 250 – 100 139

50/250-18.5/2 50 440 122 178 174 – 200 200 70 370 824 220 M10 20 250 – 120 182

Page 145: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

145

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-CronoLine-IL

Standard

pum

ps

50/250-22/2 50 440 122 178 174 – 200 200 70 370 866 220 M10 20 294 – 120 213

50/270-22/2 50 440 122 178 174 – 200 200 70 370 866 220 M10 20 294 – 120 204

50/270-30/2 50 440 122 178 174 – 200 200 70 415 971 220 M10 20 306 – 120 249

65/110-3/2 65 340 120 112 134 156 140 140 60 217 524 160 M12 20 – 156 110 66

65/120-3/2 65 340 120 112 134 156 140 140 60 217 524 160 M12 20 – 156 110 66

65/120-4/2 65 340 120 112 134 168 140 140 60 232 602 160 M12 20 – 168 110 73

65/130-4/2 65 340 120 112 134 168 140 140 60 232 602 160 M12 20 – 168 110 73

65/130-5.5/2 65 340 120 112 134 – 140 140 60 279 654 160 M12 20 188 – 110 84

65/140-5.5/2 65 340 120 112 134 – 140 140 60 279 654 160 M12 20 188 – 110 84

65/140-7.5/2 65 340 120 112 134 – 140 140 60 279 654 160 M12 20 188 – 110 92

65/150-5.5/2 65 430 110 126 146 182 180 195 60 279 657 215 M12 20 – 182 120 90

65/160-5.5/2 65 430 110 126 146 182 180 195 60 279 657 215 M12 20 – 182 120 90

65/160-7.5/2 65 430 110 126 146 182 180 195 60 279 657 215 M12 20 – 182 120 100

65/170-11/2 65 430 110 126 146 – 180 195 60 323 788 215 M12 20 250 – 120 124

65/200-11/2 65 475 130 150 168 – 200 225 50 323 782 245 M12 20 250 – 110 134

65/200-15/2 65 475 130 150 168 – 200 225 50 323 782 245 M12 20 250 – 110 145

65/210-15/2 65 475 130 150 168 – 200 225 50 323 782 245 M12 20 250 – 110 145

65/210-18.5/2 65 475 130 150 168 – 200 225 50 370 825 245 M12 20 250 – 110 158

65/220-18.5/2 65 475 130 150 168 – 200 225 50 370 825 245 M12 20 250 – 110 158

65/220-22/2 65 475 130 150 168 – 200 225 50 370 867 245 M12 20 294 – 110 181

65/240-30/2 65 475 140 187 174 – 200 215 80 415 975 235 M12 20 306 – 120 253

65/260-30/2 65 475 140 187 174 – 200 215 80 415 975 235 M12 20 306 – 120 253

65/260-37/2 65 475 140 187 174 – 200 215 80 415 975 235 M12 20 306 – 120 276

80/110-3/2 80 400 105 123 151 156 180 173 57 217 541 200 M12 20 – 156 120 74

80/120-4/2 80 400 105 123 151 168 180 173 57 232 619 200 M12 20 – 168 120 80

80/130-5.5/2 80 400 105 123 151 – 180 173 57 279 671 200 M12 20 188 – 120 91

80/140-7.5/2 80 400 105 123 151 – 180 173 57 279 671 200 M12 20 188 – 120 99

80/150-7.5/2 80 440 120 136 162 182 180 173 72 279 655 200 M12 20 – 182 120 109

80/160-11/2 80 440 120 136 162 – 180 173 72 323 786 200 M12 20 250 – 120 134

80/170-11/2 80 440 120 136 162 – 180 173 72 323 786 200 M12 20 250 – 120 134

80/170-15/2 80 440 120 136 162 – 180 173 72 323 786 200 M12 20 250 – 120 147

80/190-15/2 80 500 145 157 182 – 220 208 62 323 790 230 M12 20 250 – 120 154

80/190-18.5/2 80 500 145 157 182 – 220 208 62 370 833 230 M12 20 250 – 120 167

80/200-18.5/2 80 500 145 157 182 – 220 208 62 370 833 230 M12 20 250 – 120 167

80/200-22/2 80 500 145 157 182 – 220 208 62 370 875 230 M12 20 294 – 120 190

80/210-30/2 80 500 145 157 182 – 220 208 62 415 963 230 M12 20 306 – 120 245

80/220-22/2 80 500 145 157 182 – 220 208 62 370 875 230 M12 20 294 – 120 190

80/220-30/2 80 500 145 157 182 – 220 208 62 415 963 230 M12 20 306 – 120 245

100/145-11/2 100 500 120 159 197 – 200 226 60 323 821 250 M12 20 250 – 135 147

100/150-15/2 100 500 120 159 197 – 200 226 60 323 821 250 M12 20 250 – 135 160

100/160-15/2 100 500 120 159 197 – 200 226 60 323 821 250 M12 20 250 – 135 160

Dimensions, weights (2900 rpm)

Wilo-CronoLine-IL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q x M

– [mm] – [mm] [kg]

Page 146: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

146 Subject to change 09/2008 WILO SE

Standard pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-CronoLine-IL

100/160-18.5/2 100 500 120 159 197 – 200 226 60 370 864 250 M12 20 250 – 135 177

100/165-22/2 100 500 120 159 197 – 200 226 60 370 906 250 M12 20 294 – 135 192

100/170-22/2 100 500 120 159 197 – 200 226 60 370 906 250 M12 20 294 – 135 192

100/170-30/2 100 500 120 159 197 – 200 226 60 415 994 250 M12 20 306 – 135 247

100/190-30/2 100 550 155 173 202 – 220 231 99 415 973 255 M12 20 306 – 120 258

100/210-30/2 100 550 155 173 202 – 220 231 99 415 973 255 M12 20 306 – 120 258

100/210-37/2 100 550 155 173 202 – 220 231 99 415 973 255 M12 20 306 – 120 281

Dimensions, weights (2900 rpm)

Wilo-CronoLine-IL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q x M

– [mm] – [mm] [kg]

Flange dimensions

Wilo-CronoLine-IL ... Nominal flange diameter Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

32... 32 140 76 100 4 x 19

40... 40 150 84 110 4 x 19

50... 50 165 99 125 4 x 19

65... 65 185 118 145 4 x 19

80... 80 200 132 160 8 x 19

100... 100 220 156 180 8 x 19

125... 125 250 184 210 8 x 19

150... 150 285 211 240 8 x 23

200... 200 340 266 295 12 x 23

250... 250 405 319 355 12 x 28

Pump flange dimensions - according to EN 1092-2 PN 16, n = number of drilled holes

Page 147: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

147

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-VeroTwin-DPL

Standard

pum

ps

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroTwin-DPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignGlanded double pump in in-line design with flange connection

ApplicationFor pumping heating water (according to VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cooling water systems

Scope of delivery• Pump• Installation and operating instructions

Type key

Technical data• Permissible temperature range -10°C to +120°C• Mains connection 3~400 V, 50 Hz• Protection class IP 55• Nominal diameter DN 32 to DN 100• Max. operating pressure 10 bar (special version: 16 bar)

Special features/product benefits• Reduction of space required and installation costs due to double pump design

• Main/standby mode or peak-load operation (by means of auxiliary external device)

• Standard condensate drainage holes in the motor housings and lan-terns

• High corrosion protection due to cataphoretic coating• Series version: Motor with one-piece shaft• Version N: Standard motor B5 or V1 with stainless steel plug shaft• Bidirectional mechanical seal with forced flushing

Materials• Pump housing and lantern: EN-GJL-250• Impeller: PP fibreglass-reinforced /

EN-GJL-200 (depending on pump type)

• Shaft: 1.4021 (version N: 1.4404)• Mechanical seal: AQ1EGG;other mechanical seals on request

Description/designSingle-stage, low-pressure double pump in in-line design with

• Switchover valve• Mechanical seal • Flange connection with pressure measuring connection R 1/8• Motor with one-piece shaft

Example DPL 40/160-4/2

DPL In-line double pump

40 Nominal diameter DN of the pipe connection

160 Nominal impeller diameter

4 Nominal motor power P2 in kW

2 Number of poles

Page 148: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

148 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-VeroTwin-DPL

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroTwin-DPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Q[m³/h]0 40 120 1608020 100 14060 200 210 230220180 19030 110 1507010 90 13050 170

H[m]

0

1

2

3

4

5

6

7

8

9Wilo-VeroTwin-DPLn = 1450 1/min

+

DPL 100

DPL 80DPL 50

DPL 65DPL 40DPL

32

Q[m³/h]0 40 120 1608020 100 14060 200 210 220180 19030 110 1507010 90 13050 170

H[m]

0

5

10

15

20

25

30

35

40

45

50Wilo-VeroTwin-DPLn = 2900 1/min

+

DPL 80

DPL 50

DPL 65

DPL 40DPL 32

Page 149: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

149

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroTwin-DPL

Standard

pum

ps

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-VeroTwin-DPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DPL 32/110-0,25/4 - 32/160-0,25/4

Speed 1450 rpm - individual operation

Wilo-VeroTwin-DPL 32/110-0,25/4 - 32/160-0,25/4

Speed 1450 rpm - parallel operation

Wilo-VeroTwin-DPL 40/130-0,25/4 - 40/160-0,37/4

Speed 1450 rpm - individual operation

Wilo-VeroTwin-DPL 40/130-0,25/4 - 40/160-0,37/4

Speed 1450 rpm - parallel operation

0

0

1

2

3

4

5

6

7

8

0

1

0

0,10

0,15

0,05

010203040

2

3

9

0,5 1,0 1,5

0 2 4 6

0 2 4 6

0 2 4 6

Ø 155

DPL 32/160-0,25/4

Ø 114

DPL 32/110-0,25/4

Ø 155

Ø 155

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 32/160 -Wilo-VeroTwin-DPL 32/110

NPS

H [m

]

Qmin

R

0 2 4 6 8 10 12

0 1 2 3 4

0

1

2

3

4

5

6

7

8

0

1

0 2 4 6 8 10 120

0,1

0,2

0,3

0 2 4 6 8 10 120

10203040

2

3

9

Ø 155

DPL 32/160-0,25/4

Ø 114

DPL 32/110-0,25/4

Ø 155

Ø 155

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 32/160 -Wilo-VeroTwin-DPL 32/110

NPS

H [m

]

Qmin

+

0

1

2

3

4

5

6

7

0

1,0

2,0

0

0,2

0,4

0

20

40

60

3,0

4,0

8

0 2 4 6

10 20 251550

10 20 251550

10 20 251550

1 3 5 7

Ø 151

DPL 40/160-0,37/4

Ø 133

DPL 40/130-0,25/4

Ø 151

Ø 151

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 40/160 -Wilo-VeroTwin-DPL 40/130

NPS

H [m

]

Qmin

0

1

2

3

4

5

6

7

0

1,0

2,0

00,20,40,60,8

0

20

40

60

3,0

4,0

0 10 20 30 40

0 10 20 30 40

0 10 20 30 40

8

0 2 4 6 8 10 12

Ø 151

DPL 40/160-0,37/4

Ø 133

DPL 40/130-0,25/4

Ø 151

Ø 151

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 40/160 -Wilo-VeroTwin-DPL 40/130

NPS

H [m

]Qmin

+

Page 150: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

150 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DPL

Wilo-VeroTwin-DPL 50/110-0,25/4

Speed 1450 rpm - individual operation

Wilo-VeroTwin-DPL 50/110-0,25/4

Speed 1450 rpm - parallel operation

Wilo-VeroTwin-DPL 50/130-0,37/4 - 50/160-0,55/4

Speed 1450 rpm - individual operation

Wilo-VeroTwin-DPL 50/130-0,37/4 - 50/160-0,55/4

Speed 1450 rpm - parallel operation

0

0,5

1,0

1,5

2,0

2,5

3,0

3,5

00,40,81,2

0

0,05

0,10

0

20

40

60

4,0

1,62,0

0 10 155

0 10 155

0 10 155

0 2 41 3

Ø 107

DPL 50/110-0,25/4

Ø 107

Ø 107

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

QminWilo-VeroTwin-DPL 50/110

0 5 10 15 20 250

0,5

1,0

1,5

2,0

2,5

3,0

3,5

0

0,40,81,2

0 5 10 15 20 250

0,050,100,15

0 5 10 15 20 250

20

40

60

0,20

4,0

1,62,0

4 620

Ø 107

DPL 50/110-0,25/4

Ø 107

Ø 107

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/110

NPS

H [m

]

Qmin +

0

1

2

3

4

5

6

7

0

1

2

0

0,4

0,2

0,6

0

20

40

60

8

3

4

4 80 2 6

0 10 20 30

0 10 20 30

0 10 20 30

Ø 156

DPL 50/160-0,55/4

Ø 127

DPL 50/130-0,37/4

Ø 156

Ø 156

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/160 -Wilo-VeroTwin-DPL 50/130

NPS

H [m

]

Qmin

0

1

2

3

4

5

6

7

0

1

2

0 10 20 30 4 00

0,4

0,8

1,2

0 10 20 30 4 00

20

40

60

8

3

4

4 8 120

0 10 20 30 4 0

Ø 156

DPL 50/160-0,55/4

Ø 127

DPL 50/130-0,37/4

Ø 156

Ø 156

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/160 -Wilo-VeroTwin-DPL 50/130

NPS

H [m

]

Qmin

+

Page 151: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

151

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroTwin-DPL

Standard

pum

ps

Wilo-VeroTwin-DPL 65/120-0,25/4 - 65/150-0,75/4

Speed 1450 rpm - individual operation

Wilo-VeroTwin-DPL 65/120-0,25/4 - 65/150-0,75/4

Speed 1450 rpm - parallel operation

Wilo-VeroTwin-DPL 80/130-0,75/4 - 80/150-1,1/4

Speed 1450 rpm - individual operation

Wilo-VeroTwin-DPL 80/130-0,75/4 - 80/150-1,1/4

Speed 1450 rpm - parallel operation

20 40 5030100

20 40 5030100

20 40 5030100

0

1

2

3

4

5

6

7

0

2

4

0

0,4

0,2

0,6

020406080

6

8

8

5 10 12,57,52,50 15

Ø 149

DPL 65/150-0,75/4

Ø 140

DPL 65/140-0,55/4

Ø 149

Ø 149

Ø 127Ø 115

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 65/150 -Wilo-VeroTwin-DPL 65/120

NPS

H [m

]

Qmin

DPL 65/130-0,37/4

DPL 65/120-0,25/4

0 20 40 6 00

1

2

3

4

5

6

7

0

2

4

0 20 40 6 00

0,40,81,21,6

0 20 40 6 00

20406080

6

8

8

0 5 10 15 20

Ø 149

DPL 65/150-0,75/4

Ø 140

DPL 65/140-0,55/4

Ø 149

Ø 149

Ø 127Ø 115

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

DPL 65/130-0,37/4DPL 65/120-0,25/4

Wilo-VeroTwin-DPL 65/150 -Wilo-VeroTwin-DPL 65/120

+

0

1

2

3

4

5

6

7

0

1

2

0

0,5

1,0

0

20

40

60

3

4

8

20 40 600

5 100

20 40 600

20 40 600

20

Ø 154

DPL 80/150-1,1/4

Ø 135

DPL 80/130-0,75/4

Ø 154

Ø 154

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

QminWilo-VeroTwin-DPL 80/150 -Wilo-VeroTwin-DPL 80/130

0 20 40 60 80 100 120

0 10 20 30

0

1

2

3

4

5

6

7

0

1

2

0 40 60 80 100 1200

0,51,01,52,0

0 20 40 60 80 100 1200

20

40

60

3

4

8

0 2

Ø 154

DPL 80/150-1,1/4

Ø 135

DPL 80/130-0,75/4

Ø 154

Ø 154

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]Qmin

Wilo-VeroTwin-DPL 80/150 -Wilo-VeroTwin-DPL 80/130

+

Page 152: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

152 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DPL

Wilo-VeroTwin-DPL 100/135-1,1/4 - 100/175-3/4

Speed 1450 rpm - individual operation

Wilo-VeroTwin-DPL 100/135-1,1/4 - 100/175-3/4

Speed 1450 rpm - parallel operation

50 100 12575250

50 100 12575250

50 100 12575250

200 10 30

0

2

4

6

8

10

0246

0

1

3

0204060

81012

2

Ø 175

DPL 100/175-3/4

Ø 165

DPL 100/165-2,2/4

Ø 175

Ø 175

DPL 100/145-1,5/4

DPL 100/135-1,1/4

Ø 145Ø 135

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 100/175 -Wilo-VeroTwin-DPL 100/135

NPS

H [m

]

Qmin

0 50 100 150 200 250

0 20 4 0

0

2

4

6

8

10

0246

0 50 100 150 200 2500

2

4

6

0 50 100 150 200 2500

204060

81012

Ø 175

DPL 100/175-3/4

Ø 165

DPL 100/165-2,2/4

Ø 175

Ø 175

DPL 100/145-1,5/4

DPL 100/135-1,1/4

Ø 145Ø 135

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 100/175 -Wilo-VeroTwin-DPL 100/135

NPS

H [m

]

Qmin

+

Page 153: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

153

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroTwin-DPL

Standard

pum

ps

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-VeroTwin-DPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroTwin-DPL 32/90-0,37/2 - 32/160-1,1/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 32/90-0,37/2 - 32/160-1,1/2

Speed 2900 rpm - parallel operation

Wilo-VeroTwin-DPL 32/165-3/2 - 32/175-4/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 32/165-3/2 - 32/175-4/2

Speed 2900 rpm - parallel operation

5 10 12,57,52,50

5 10 12,57,52,50

5 10 12,57,52,50

0

4

8

12

16

20

24

28

0

4

0

0,5

0102030

8

2

6

1012

1,0

32

10 2 3 4

DPL 32/160-1,1/2DPL 32/130-1,1/2DPL 32/110-0,75/2

Ø 155

Ø 128Ø 114

DPL 32/100-0,55/2

Ø 92Ø 102

DPL 32/90-0,37/2

Ø 155

Ø 155

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 32/160 -Wilo-VeroTwin-DPL 32/90

NPS

H [m

]

Qmin

0 5

0 5 10 15 20 25

0 2

0

4

8

12

16

20

24

28

0246

0 5 10 15 20 250

0,51,01,5

10 15 20 250

102030

81012

2,0

32

DPL 32/160-1,1/2DPL 32/130-1,1/2DPL 32/110-0,75/2

Ø 155

Ø 155Ø 128

Ø 114

DPL 32/100-0,55/2

Ø 92Ø 102

Ø 155

DPL 32/90-0,37/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 32/160 -Wilo-VeroTwin-DPL 32/90

NPS

H [m

]

Qmin+

0

5

10

15

20

25

30

35

40

0

10

0

2

4

010203040

20

30

45

0

10

2 4 6

20 251550

10 20 251550

10 20 251550

DPL 32/175-4/2DPL 32/165-3/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 32/175 -Wilo-VeroTwin-DPL 32/165

NPS

H [m

]

Qmin

Ø173

Ø173

Ø173

Ø157

0 10 20 30 40 50

0 4 8 1 6

0

5

10

15

20

25

30

35

40

0

10

0 10 20 30 40 500246

0 10 20 30 40 500

10203040

20

30

45

DPL 32/175-4/2

DPL 32/165-3/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 32/175 -Wilo-VeroTwin-DPL 32/165

NPS

H [m

]Qmin

+

Q[l/s]

Ø173

Ø173

Ø173

Ø157

Page 154: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

154 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DPL

Wilo-VeroTwin-DPL 40/90-0,37/2 - 40/115-0,55/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 40/90-0,37/2 - 40/115-0,55/2

Speed 2900 rpm - parallel operation

Wilo-VeroTwin-DPL 40/120-1,5/2 - 40/160-4/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 40/120-1,5/2 - 40/160-4/2

Speed 2900 rpm - parallel operation

0

2

4

6

8

10

12

0

0,2

0,4

0,6

0

20

40

60

14

246810

00 5 10 15

0 5 10 15

0 5 10 15

1 2 3 40

DPL 40/115-0,55/2

Ø 106

Ø 106

Ø 86

Ø 106

DPL 40/90-0,37/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 40/115 -Wilo-VeroTwin-DPL 40/90

NPS

H [m

]

Qmin

0 5 10 15 20 25

0 2 4 6 8

0

2

4

6

8

10

12

0 5 10 15 20 250

0,4

0,8

1,2

0 5 10 15 20 250

20

40

60

14

246810

0

DPL 40/115-0,55/2

Ø 106

Ø 106

Ø 86

Ø 106

DPL 40/90-0,37/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 40/115-Wilo-VeroTwin-DPL 40/90

NPS

H [m

]

Qmin+

0

5

10

15

20

25

30

0

84

0

2

4

0

20

40

60

12

35

0 10 20 30 40

0 10 20 30 40

0 10 20 30 40

12840

DPL 40/160-4/2

Ø 156

Ø 156

Ø 156

DPL 40/130-2,2/2

DPL 40/150-3/2

Ø 147Ø 133Ø 124

DPL 40/120-1,5/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 40/160 -Wilo-VeroTwin-DPL 40/120Qmin

NPS

H [m

]

0 10 20 30 40 50 60

0 4 8 12 16

0

5

10

15

20

25

30

0

84

0 10 20 30 40 50 600246

0 10 20 30 40 50 600

20

40

60

12

35

DPL 40/160-4/2

Ø 156

Ø 156

Ø 156

DPL 40/150-3/2

Ø 147Ø 133

Ø 124

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 40/160-Wilo-VeroTwin-DPL 40/120

NPS

H [m

]

Qmin+

DPL 40/130-2,2/2

DPL 40/120-1,5/2

Page 155: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

155

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroTwin-DPL

Standard

pum

ps

Wilo-VeroTwin-DPL 40/165-4/2 - 40/175-5,5/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 40/165-4/2 - 40/175-5,5/2

Speed 2900 rpm - parallel operation

Wilo-VeroTwin-DPL 40/195-7,5/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 40/195-7,5/2

Speed 2900 rpm - parallel operation

20 40 5030100

20 40 5030100

20 40 5030100

5 10 12,57,52,50

0

5

10

15

20

25

30

35

40

0

10

20

0

2

4

6

0

20

40

60

45

30

40

DPL 40/175-5,5/2

Ø 168

Ø 168

DPL 40/165-4/2

Ø 150

Ø 168

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 40/175 -Wilo-VeroTwin-DPL 40/165

NPS

H [m

]

Qmin

0 20 40 60 80 1000

5

10

15

20

25

30

35

40

0

10

20

0 20 40 6 00

4

8

12

0 20 40 60 800

20

40

60

45

30

40

100

0 5 10 15 20 25

DPL 40/175-5,5/2

Ø 168

Ø 168

DPL 40/165-4/2

Ø 150

Ø 168

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 40/175 -Wilo-VeroTwin-DPL 40/165

NPS

H [m

]

Qmin

+

5 7,5

0

10

20

30

40

50

60

0

10

20

0

4

8

010203040

30

0 10 20 30

0 10 20 30

0 10 20 30

2,50

DPL 40/195-7,5/2

Ø 195

Ø 195

Ø 195

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 40/195

NPS

H [m

]

Qmin

0 5 10 15 20

0

10

20

30

40

50

60

0

10

20

048

12

010203040

30

0 20 40 60 80

0 20 40 60 80

0 20 40 60 80

DPL 40/195-7,5/2

Ø 195

Ø 195

Ø 195

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]Qmin

Wilo-VeroTwin-DPL 40/195+

Page 156: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

156 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DPL

Wilo-VeroTwin-DPL 50/115-0,75/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 50/115-0,75/2

Speed 2900 rpm - parallel operation

Wilo-VeroTwin-DPL 50/120-1,5/2 - 50/150-4/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 50/120-1,5/2 - 50/150-4/2

Speed 2900 rpm - parallel operation

0

2

4

6

8

10

12

0

0,4

0,8

0

20

40

60

0

4

8

12

14

0 10 20 30

0 10 20 30

0 10 20 30

0 4 82 6

DPL 50/115-0,75/2

Ø107

Ø 107

Ø 107

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/115

NPS

H [m

]

Qmin

0 10 20 30 40 50

0 4 8 1 6

0

2

4

6

8

10

12

0 10 20 30 40 500

0,40,8

0 10 20 30 40 500

20

40

60

1,2

0

4

8

12

14

DPL 50/115-0,75/2

Ø107

Ø 107

Ø 107

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/115

NPS

H [m

]

+Qmin

20 40 5030100

20 40 5030100

20 40 5030100

5 10 12,57,52,50

0

4

8

12

16

20

24

0

2

4

6

0

20

40

60

28

0481216

DPL 50/150-4/2

DPL 50/140-3/2

Ø 134

DPL 50/130-2,2/2DPL 50/120-1,5/2

Ø 145

Ø 123Ø 112

Ø 145

Ø 145

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/150 -Wilo-VeroTwin-DPL 50/120

NPS

H [m

]

Qmin

0 20 40 6 0

0 5 10 15 20

0

4

8

12

16

20

24

0 40 6 00246

0 20 40 6 00

20

40

60

28

0481216

DPL 50/150-4/2

Ø 145

DPL 50/140-3/2

Ø 134

DPL 50/130-2,2/2

DPL 50/120-1,5/2

Ø 145

Ø 123Ø 112

Ø 145

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/150 -Wilo-VeroTwin-DPL 50/120

NPS

H [m

]

+Qmin

Page 157: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

157

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroTwin-DPL

Standard

pum

ps

Wilo-VeroTwin-DPL 50/155-4/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 50/155-4/2

Speed 2900 rpm - parallel operation

Wilo-VeroTwin-DPL 50/165-5,5/2 - 50/175-5,5/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 50/165-5,5/2 - 50/175-5,5/2

Speed 2900 rpm - parallel operation

0

4

8

12

16

20

24

28

0

4

8

2

4

0204060

12

16

32

0

20 40 5030100

20 40 5030100

20 40 5030100

5 12,5 15102,50

DPL 50/155-4/2

Ø 141

Ø 141

Ø 141

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/155

NPS

H [m

]

Qmin

0 20 40 60 80

0 5 10 15 20 25

0

4

8

12

16

20

24

28

0

4

8

0 20 40 60 80 100

246

0 20 40 60 80 1000

204060

12

16

32

0

DPL 50/155-4/2

Ø 141

Ø 141

Ø 141

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/155

NPS

H [m

]

+Qmin

0 20 40 60

0 20 40 60

0 20 40 60

0

5

10

15

20

25

30

35

40

048

4

2

6

0

20

40

60

45

121620

0

0

105 15

DPL 50/175-7,5/2

Ø 167

Ø 167

Ø 167

DPL 50/165-5,5/2

Ø 157

DPL 50/175-5,5/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/175 -Wilo-VeroTwin-DPL 50/165Qmin

NPS

H [m

]

0 20 40 60 80 1000

5

10

15

20

25

30

35

40

048

0 20 40 60 80 100

4

8

12

0 40 60 80 1000

20

40

60

45

121620

0 5

0

0 2

10 15 20 25

DPL 50/175-7,5/2

Ø 167

Ø 157

Ø 167

DPL 50/165-5,5/2

Ø 157

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/175 -Wilo-VeroTwin-DPL 50/165

NPS

H [m

]Qmin

+

Page 158: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

158 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DPL

Wilo-VeroTwin-DPL 50/185-7,5/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 50/185-7,5/2

Speed 2900 rpm - parallel operation

Wilo-VeroTwin-DPL 65/115-1,5/2 - 65/140-4/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 65/115-1,5/2 - 65/140-4/2

Speed 2900 rpm - parallel operation

20 40 5030100

20 40 5030100

20 40 5030100

5 10 12,57,52,50

0

10

20

30

40

50

048

0

4

8

20

40

60

0

DPL 50/185-7,5/2

Ø 184

Ø 184

Ø 184

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/185

NPS

H [m

]

Qmin

L

0 20 40 60 80 100

0 5 10 15 20 25

0

10

20

30

40

50

04812

0 20 40 60 80 100048

12

0 20 40 60 80 100

20

40

1620

60

0

DPL 50/185-7,5/2

Ø 184

Ø 184

Ø 184

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 50/185

NPS

H [m

]

Qmin +

0

4

8

12

16

20

24

0246

0

2

4

0204060

81012

10 1550

400 20 60

400 20 60

400 20 60

DPL 65/140-4/2

Ø 135

DPL 65/130-3/2

Ø 124

DPL 65/120-2,2/2

DPL 65/115-1,5/2

Ø 135

Ø 116Ø 114

Ø 135

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 65/140 -Wilo-VeroTwin-DPL 65/115

NPS

H [m

]

Qmin

0 40 80 120 160

0 10 20 30 40

0

4

8

12

16

20

24

0246

0 40 80 120 1600246

0 40 80 120 1600

204060

81012

DPL 65/140-4/2

Ø 135

DPL 65/130-3/2

Ø 124

DPL 65/120-2,2/2

DPL 65/115-1,5/2

Ø 135

Ø 116Ø 114

Ø 135

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 65/140 -Wilo-VeroTwin-DPL 65/115

NPS

H [m

]

+Qmin

Page 159: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

159

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroTwin-DPL

Standard

pum

ps

Wilo-VeroTwin-DPL 65/145-5,5/2 - 65/155-7,5/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 65/145-5,5/2 - 65/155-7,5/2

Speed 2900 rpm - parallel operation

Wilo-VeroTwin-DPL 65/165-5,5/2 - 65/175-7,5/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 65/165-5,5/2 - 65/175-7,5/2

Speed 2900 rpm - parallel operation

0

4

8

12

16

20

24

04

0

4

0204060

81216

28

40 80 10060200

40 80 10060200

30 50 10040200

10 20 251550 30

2

6

Ø 140

DPL 65/155-7,5/2

Ø 126

DPL 65/145-5,5/2

Ø 140

Ø 140

DPL 65/155-5,5/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 65/155 -Wilo-VeroTwin-DPL 65/145

NPS

H [m

]

Qmin

LN

0 40 80 120 160 200

0 10 20 30 40 50

0

4

8

12

16

20

24

04

0 40 80 120 160 200048

12

0 40 80 120 160 2000

204060

81216

28

Ø 140

DPL 65/155-7,5/2

Ø 126

DPL 65/145-5,5/2

Ø 140

Ø 140

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 65/155 -Wilo-VeroTwin-DPL 65/145

NPS

H [m

]

+Qmin

0

5

10

15

20

25

30

0

4

0204060

35

0

8

16

20

0 5 10 15

4020 600

4020 600

4020 600

2

6

Ø 152

DPL 65/175-7,5/2

Ø 134

DPL 65/165-5,5/2

Ø 152

Ø 152

DPL 65/175-5,5/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 65/175 -Wilo-VeroTwin-DPL 65/165

NPS

H [m

]

Qmin

0 40 80 120 160

0 10 20 30 40

0

5

10

15

20

25

30

0 40 80 120 160048

12

0 40 80 120 1600

204060

35

0

8

16

20Ø 152

DPL 65/175-7,5/2

Ø 134

DPL 65/165-5,5/2

Ø 152

Ø 152

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 65/175 -Wilo-VeroTwin-DPL 65/165

NPS

H [m

]+

Qmin

Page 160: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

160 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-VeroTwin-DPL

Wilo-VeroTwin-DPL 80/115-2,2/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 80/115-2,2/2

Speed 2900 rpm - parallel operation

Wilo-VeroTwin-DPL 80/130-3/2 - 80/140-4/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 80/130-3/2 - 80/140-4/2

Speed 2900 rpm - parallel operation

0 20 40 60

20 40 60

20 40 60

0

2

4

6

8

10

12

14

16

0

4

0

1

2

00

204060

8

12

0

0 5 1510

18

Ø 119

DPL 80/115-2,2/2

Ø 119

Ø 119

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 80/115

NP

SH

[m

]

Qmin

0 20 40 60 80 1000

2

4

6

8

10

12

14

16

18

0

4

0 20 40 60 80 100

1234

0 20 40 60 80 1000

204060

8

12

0

0 5 10 15 20 25 30

Ø 119

DPL 80/115-2,2/2

Ø 119

Ø 119

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 80/115

NP

SH

[m

]

+Qmin

0

4

8

12

16

20

0246

0

1

2

3

20

40

81012

0

0 20 40 60 80 100

0 20 40 60 80 100

0 40 60 80 100

0 5

0 2

10 15 20 25

Ø 135

DPL 80/140-4/2

Ø 119

DPL 80/130-3/2

Ø 135

Ø 135

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 80/140 -

Wilo-VeroTwin-DPL 80/130

NPS

H [m

]

Qmin

0 40 80 120 160 200

0 10 20 30 40 50

0

4

8

12

16

20

0246

0 40 80 120 160 2000246

0 80 120 160 200

20

40

81012

0 40

Ø 135

DPL 80/140-4/2

Ø 119

DPL 80/130-3/2

Ø 135

Ø 135

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 80/140 -

Wilo-VeroTwin-DPL 80/130

NPS

H [m

]

+Qmin

Page 161: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

161

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroTwin-DPL

Standard

pum

ps

Wilo-VeroTwin-DPL 80/145-5,5/2 - 80/155-7,5/2

Speed 2900 rpm - individual operation

Wilo-VeroTwin-DPL 80/145-5,5/2 - 80/155-7,5/2

Speed 2900 rpm - parallel operation

4

8

12

16

20

24

048

0

4

6

204060

121620

0

0

50 100 12575250

20 30100

50 100 12575250

50 100 12575250

2

Ø 134

DPL 80/155-7,5/2

Ø 122

DPL 80/145-5,5/2

Ø 134

Ø 134

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 80/155-Wilo-VeroTwin-DPL 80/145

NPS

H [m

]

Qmin

0 50 100 150 200 250

4

8

12

16

20

24

048

0 50 100 150 200 250048

12

0 50 100 150 200 250

204060

121620

0 20 40 60

0

0

Ø 134

DPL 80/155-7,5/2

Ø 122

DPL 80/145-5,5/2

Ø 134

Ø 134

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-VeroTwin-DPL 80/155-Wilo-VeroTwin-DPL 80/145

NPS

H [m

]

+Qmin

Page 162: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

162 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Terminal diagram, motor data Wilo-VeroTwin-DPL

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-VeroTwin-DPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagramsStar switching Y Delta switching �

Motor protection switch required onsite. Check the direction of rota-tion.To change the direction of rotation, swap any two phases.

P2 � 3 kW 3~400 V Y3~230 V �

P2 4 kW 3~690 V Y3~400 V �

After removing the bridges, Y-� starting is possible.

L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1 L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1

MMotor data (1450 rpm)

Wilo-VeroTwin-DPL ...

Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

0.25 kW 0.86 0.74 0.61

0.37 kW 1.10 0.75 0.65

0.55 kW 1.70 0.69 0.70

0.75 kW 1.95 0.76 0.73

1.1 kW 2.90 0.78 0.74

1.5 kW 3.35 0.82 0.79

2.2 kW 4.70 0.83 0.82

3 kW 6.40 0.83 0.83

Observe motor name plate data

Motor data (2900 rpm)

Wilo-VeroTwin-DPL ...

Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

0.37 kW 1.00 0.84 0.68

0.55 kW 1.40 0.82 0.70

0.75 kW 2.00 0.86 0.68

1.1 kW 2.60 0.84 0.79

1.5 kW 3.25 0.81 0.80

2.2 kW 4.60 0.87 0.81

3 kW 6.10 0.86 0.84

4 kW 8.20 0.86 0.85

5.5 kW 10.50 0.90 0.84

7.5 kW 14.30 0.90 0.86

Observe motor name plate data

Page 163: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

163

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-VeroTwin-DPL

Standard

pum

ps

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-VeroTwin-DPL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing

Note:Housing with feet for installation on a base, brackets on request; II Pressure measuring connection R1/8; III Ventilation R1/8

Øg

Ø18

III IIIII

II

3 x o

p

ef

m

1060

la

1

l 0

b2b1

bmax

p1

DN

Ød

Øk

ØD

n x d L

x

s

c

50

50

ef

Dimensions, weights (1450 rpm)

Wilo-VeroTwin-DPL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Im-pel-ler*

Weight ap-prox.

DN l0 A b1 b2 bmax c e f Ø g l1max m o p p1 s x – M

– [mm] – [mm] – [kg]

32/110-0.25/4 32 260 70 101 105 410 225 56 106 143 295 136 M10 20 120 205 150 CI 34

32/160-0.25/4 32 260 70 101 105 410 225 56 106 143 295 136 M10 20 120 205 150 CI 34

40/130-0.25/4 40 320 75 113 119 456 240 45 135 143 289 167 M10 20 120 224 150 CI 41

40/160-0.37/4 40 320 75 113 119 456 240 45 135 143 289 167 M10 20 120 224 150 CI 43

50/110-0.25/4 50 280 83 95 101 390 228 50 107 143 300 155 M10 20 120 194 150 CI 38

50/130-0.37/4 50 340 86 120 130 500 240 48 132 143 291 190 M10 20 120 250 150 CI 45

50/160-0.55/4 50 340 86 120 130 500 240 48 132 185 327 190 M10 20 128 250 150 CI 50

65/120-0.25/4 65 340 93 125 135 550 240 43 137 143 297 185 M10 20 120 290 150 CI 50

65/130-0.37/4 65 340 93 125 135 550 240 43 137 143 297 185 M10 20 120 290 150 CI 52

65/140-0.55/4 65 340 93 125 135 550 240 43 137 185 333 185 M10 20 128 290 150 CI 57

65/150-0.75/4 65 340 93 125 135 550 240 43 137 185 333 185 M10 20 128 290 150 CI 59

80/130-0.75/4 80 360 103 134 147 601 240 30 150 185 339 192 M10 20 128 320 150 CI 62

80/150-1.1/4 80 360 103 134 147 601 240 30 150 185 339 192 M10 20 128 320 150 CI 63

100/135-1.1/4 100 500 180 173 188 801 580 80 250 176 373 226 M12 20 148 440 150 CI 135

100/145-1.5/4 100 500 180 173 188 801 580 80 250 176 398 226 M12 20 148 440 150 CI 135

100/165-2.2/4 100 500 180 173 188 801 580 80 250 196 425 226 M12 20 155 440 150 CI 147

100/175-3/4 100 500 180 173 188 801 580 80 250 196 425 226 M12 20 155 440 150 CI 150

Note concerning l1For version N (standard motor), the dimensions depend on the motor version*impeller material: CI grey cast iron; P plastic

Page 164: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

164 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-VeroTwin-DPL

Dimensions, weights (2900 rpm)

Wilo-VeroTwin-DPL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Im-pel-ler*

Weight approx.

DN l0 A b1 b2 bmax c e f Ø g l1max m o p p1 s x – M

– [mm] – [mm] – [kg]

32/90-0.37/2 32 260 70 101 105 410 225 56 106 143 295 136 M10 20 120 205 150 CI 35

32/100-0.55/2 32 260 70 101 105 410 225 56 106 143 295 136 M10 20 120 205 150 CI 36

32/110-0.75/2 32 260 70 101 105 410 225 56 106 143 295 136 M10 20 120 205 150 CI 38

32/130-1.1/2 32 260 70 101 105 410 225 56 106 185 331 136 M10 20 128 205 150 CI 44

32/160-1.1/2 32 260 70 101 105 410 225 56 106 185 331 136 M10 20 128 205 150 CI 44

32/165-3/2 32 320 100 117 122 539 360 43 137 217 393 155 M10 20 160 300 150 CI 85

32/175-4/2 32 320 100 117 122 539 360 43 137 220 409 155 M10 20 168 300 150 CI 99

40/90-0.37/2 40 250 75 85 91 350 225 35 97 143 294 135 M10 20 120 174 150 CI 37

40/115-0.55/2 40 250 75 85 91 350 225 35 97 143 294 135 M10 20 120 174 150 CI 39

40/120-1.5/2 40 320 75 113 119 456 240 45 135 185 325 167 M10 20 128 224 150 CI 59

40/130-2.2/2 40 320 75 113 119 456 240 45 135 193 353 167 M10 20 151 224 150 CI 63

40/150-3/2 40 320 75 113 119 456 240 45 135 217 388 167 M10 20 160 224 150 CI 73

40/160-4/2 40 320 75 113 119 456 240 45 135 232 421 167 M10 20 168 224 150 CI 87

40/165-4/2 40 340 100 120 127 587 400 52 145 220 413 170 M10 20 168 340 150 CI 104

40/175-5.5/2 40 340 100 120 127 587 400 52 145 232 433 170 M10 20 168 340 150 CI 104

40/195-7.5/2 40 440 110 145 147 692 500 38 192 279 515 220 M10 20 188 400 150 CI 175

50/115-0.75/2 50 280 83 95 101 390 228 50 107 143 300 155 M10 20 120 194 150 CI 41

50/120-1.5/2 50 340 86 120 130 500 240 48 132 185 327 190 M10 20 128 250 150 CI 60

50/130-2.2/2 50 340 86 120 130 500 240 48 132 193 350 190 M10 20 151 250 150 CI 64

50/140-3/2 50 340 86 120 130 500 240 48 132 217 390 190 M10 20 160 250 150 CI 74

50/150-4/2 50 340 86 120 130 500 240 48 132 232 423 190 M10 20 168 250 150 CI 88

50/155-4/2 50 340 105 108 116 532 360 52 148 232 463 170 M10 20 168 300 150 CI 101

50/165-5.5/2 50 340 120 126 136 619 360 50 130 279 503 180 M10 20 188 340 150 CI 148

50/175-5.5/2 50 340 120 126 136 619 360 50 130 279 503 180 M10 20 188 340 150 CI 148

50/175-7.5/2 50 340 120 126 136 619 360 50 130 279 503 180 M10 20 188 340 150 CI 164

50/185-7.5/2 50 440 120 145 148 693 500 50 200 279 521 220 M10 20 188 400 150 CI 172

65/115-1.5/2 65 340 93 103 117 432 225 25 137 193 361 185 M10 20 151 212 150 CI 66

65/120-2.2/2 65 340 93 125 135 550 240 43 137 193 356 185 M10 20 151 290 150 CI 72

65/130-3/2 65 340 93 125 135 550 240 43 137 217 396 185 M10 20 160 290 150 CI 82

65/140-4/2 65 340 93 125 135 550 240 43 137 232 429 185 M10 20 168 290 150 CI 96

65/145-5.5/2 65 340 120 121 130 619 400 50 150 279 521 170 M12 20 188 340 150 CI 153

65/155-5.5/2 65 340 120 121 130 619 400 50 150 279 521 170 M12 20 188 340 150 CI 154

65/155-7.5/2 65 340 120 121 130 619 400 50 150 279 521 170 M12 20 188 340 150 CI 170

65/165-5.5/2 65 430 153 134 144 679 440 55 185 279 521 215 M12 20 188 400 150 CI 169

65/175-5.5/2 65 430 153 134 144 679 440 55 185 279 521 215 M12 20 188 400 150 CI 169

65/175-7.5/2 65 430 153 134 144 679 440 55 185 279 521 215 M12 20 188 400 150 CI 185

80/115-2.2/2 80 360 100 113 132 480 240 43 137 193 378 205 M10 20 151 235 150 CI 76

80/130-3/2 80 360 103 134 147 601 240 30 150 217 402 192 M10 20 160 320 150 CI 85

80/140-4/2 80 360 103 134 147 601 240 30 150 232 435 192 M10 20 168 320 150 CI 99

80/145-5.5/2 80 400 155 134 146 630 400 62 178 279 528 200 M12 20 188 350 150 CI 168

Page 165: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

165

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-VeroTwin-DPL

Standard

pum

ps

80/155-7.5/2 80 400 155 134 146 630 400 62 178 279 528 200 M12 20 188 350 150 CI 184

Note concerning l1For version N (standard motor), the dimensions depend on the motor version*impeller material: CI grey cast iron; P plastic

Dimensions, weights (2900 rpm)

Wilo-VeroTwin-DPL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions

Im-pel-ler*

Weight approx.

DN l0 A b1 b2 bmax c e f Ø g l1max m o p p1 s x – M

– [mm] – [mm] – [kg]

Flange dimensions

Wilo-VeroTwin-DPL ...

Nominal flange diameter Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

32... 32 140 78 100 4 x 19

40... 40 150 88 110 4 x 19

50... 50 165 102 125 4 x 19

65... 65 185 122 145 4 x 19

80... 80 200 138 160 8 x 19

100... 100 220 156 180 8 x 19

Pump flange dimensions - drilled according to EN 1092-2 PN 16, n = number of drilled holes

Page 166: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

166 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-CronoTwin-DL

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoTwin-DL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignGlanded double pump in in-line design with flange connection

ApplicationFor pumping heating water (according to VDI 2035), water-glycol mixtures and cooling and cold water without abrasive substances in heating, cold water and cooling water systems

Scope of delivery• Pump• Installation and operating instructions

Type key

Technical data• Permissible temperature range -20°C to +140°C• Mains connection 3~400 V, 50 Hz• Protection class IP 55• Nominal diameter DN 32 to DN 200• Max. operating pressure 16 bar

Special features/product benefits• Reduced life cycle costs due to optimised efficiency• Reduction of space required and installation costs due to double pump design

• Main/standby mode or peak-load operation (by means of external auxiliary device)

• Peak-load operation (by means of external auxiliary device)• Standard condensate drainage holes in the motor housings• Can be used flexibly in air-conditioning and cooling systems, with application benefits due to direct draining of condensate via opti-mised lantern design (patented)

• High corrosion protection due to cataphoretic coating• Bidirectional mechanical seal with forced flushing• High worldwide availability of standard motors (according to Wilo specifications) and standard mechanical seals

Materials• Pump housing and lantern: Standard: EN-GJL-250• Impeller: Standard: EN-GJL-200; Special version: Red brass G-CuSn10

• Shaft: 1.4122• Mechanical seal: AQ1EGG; other mechanical seals on request

Description/designSingle-stage, low-pressure double pump in in-line design with

• Switchover valve• Mechanical seal • Flange connection with pressure measuring connection R 1/8• Lantern• Coupling • IEC standard motor

Example DL 40/160-4/2

DL In-line double pump

40 Nominal diameter DN of the pipe connection

160 Nominal impeller diameter

4 Nominal motor power P2 in kW

2 Number of poles

Page 167: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

167

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-CronoTwin-DL

Standard

pum

ps

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Series description Wilo-CronoTwin-DL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Q[m³/h]0 100 200 300 400 500 600 700 800 900 1000 1100

H[m]

0

5

40

35

30

25

20

15

10

Wilo-CronoTwin-DLn = 1450 1/min

+

DL 80

DL 100

DL 125 DL 150 DL 200

DL 50

DL 65

DL 40

DL 32

Q[m³/h]0 50 125 175 225 275 325 37525 75 100 150 200 250 300 350

H[m]

0

5

40

50

60

30

20

10

45

55

65

35

25

15

Wilo-CronoTwin-DLn = 2900 1/min

+

DL 80 DL 100

DL 50

DL 65

DL 40

DL 32

Page 168: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

168 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoTwin-DL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-CronoTwin-DL 32/140-0,25/4 - 32/170-0,55/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 32/140-0,25/4 - 32/170-0,55/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 40/140-0,25/4 - 40/170-0,75/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 40/140-0,25/4 - 40/170-0,75/4

Speed 1450 rpm - parallel operation

2 4

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 5 10 15

0 5 10 15

0 5 10 15

Q[l/s]0

H[m]

0

2

4

6

8

10

12

0

2

4

6

8

P2[kW]

0

0,2

0,4

0,6

ηp[%]

010203040

DL 32/150-0,37/4

DL 32/170-0,55/4DL 32/140-0,25/4

Ø 175

Ø 175

Ø 175

Ø 157Ø 138

Wilo-CronoTwin-DL 32/170 -Wilo-CronoTwin-DL 32/140

NPS

H [m

]

Qmin

4 6

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 5 10 15 20 25

Q[l/s]0 2

H[m]

0

2

4

6

8

10

12

0

2

4

6

8

0 5 10 15 20 25

P2[kW]

00,20,40,60,8

0 5 10 15 20 25

ηp[%]

010203040

DL 32/150-0,37/4

DL 32/170-0,55/4

DL 32/140-0,25/4 Ø 175

Ø 175

Ø 175

Ø 157Ø 138

Wilo-CronoTwin-DL 32/170 -Wilo-CronoTwin-DL 32/140

NPS

H [m

]

Qmin +

0

2

2 40 6

4

6

8

10

12

0

0,4

0,8

0

20

40

60

0246810

0 10 155 20 25

155 25

155 25

0 10 20

0 10 20

DL 40/170-0,75/4

Ø 175

DL 40/160-0,55/4DL 40/150-0,37/4

DL 40/140-0,25/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 40/170 -Wilo-CronoTwin-DL 40/140

Qmin

NPS

H [m

]

Ø 175Ø 160

Ø 145Ø 129

Ø 175

0

2

4

6

8

10

12

00,40,81,2

0

20

40

60

0 10 20 30 4 00246810

0 4 2

0 10 20 30 4 0

0 10 20 30 4 0

DL 40/170-0,75/4

Ø 175

DL 40/160-0,55/4

DL 40/150-0,37/4

DL 40/140-0,25/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 40/170 -Wilo-CronoTwin-DL 40/140

NPS

H [m

]

Ø 175Ø 160

Ø 145Ø 129

Ø 175

Qmin

Page 169: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

169

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoTwin-DL

Standard

pum

ps

Wilo-CronoTwin-DL 40/210-1,1/4 - 40/220-1,5/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 40/210-1,1/4 - 40/220-1,5/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 50/150-0,55/4 - 50/170-1,1/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 50/150-0,55/4 - 50/170-1,1/4

Speed 1450 rpm - parallel operation

4

8

12

16

20

0

2

4

0

1,0

0,5

1,5

0

20

40

60

6

8

0

0 10 20

0 10 20

Ø 220

DL 40/220-1,5/4

DL 40/210-1,1/4

Ø 220Ø 205

Ø 220

0 10 20

0 4 62

5 15 25

5 15 25

5 15 25

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Qmin

NPS

H [m

]

Wilo-CronoTwin-DL 40/220 -Wilo-CronoTwin-DL 40/210

0 10 20 30 4 0

0 4 2

4

8

12

16

20

0

2

4

0 10 20 30 4 00

1

2

3

0 10 20 30 4 00

20

40

60

6

8

0

Ø 220

DL 40/220-1,5/4DL 40/210-1,1/4

Ø 220Ø 205

Ø 220

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Qmin

NPS

H [m

]

Wilo-CronoTwin-DL 40/220 -Wilo-CronoTwin-DL 40/210

+

0

2

4

6

8

10

12

024

0

0,5

1,0

0

20

40

60

6810

4 8

10 20 30

10 20 30

10 20 30

DL 50/160-0,75/4

DL 50/170-1,1/4DL 50/150-0,55/4

Ø 174

Ø 174Ø 164

Ø 150

Ø 174

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Wilo-CronoTwin-DL 50/170 -Wilo-CronoTwin-DL 50/150

Qmin

0 10 20 30 40 50 60

0 4 8 12 16

0

2

4

6

8

10

12

024

0 10 20 30 40 50 600

0,51,01,52,0

0 10 20 30 40 50 600

20

40

60

6810

DL 50/160-0,75/4

DL 50/170-1,1/4DL 50/150-0,55/4 Ø 174

Ø 174

Ø 164

Ø 150

Ø 174

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]Qmin

Wilo-CronoTwin-DL 50/170 -Wilo-CronoTwin-DL 50/150

+

Page 170: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

170 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL

Wilo-CronoTwin-DL 50/200-1,5/4 - 50/220-2,2/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 50/200-1,5/4 - 50/220-2,2/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 50/260-3/4 - 50/270-4/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 50/260-3/4 - 50/270-4/4

Speed 1450 rpm - parallel operation

D

0

4

8

12

0

2

10 30 50

4

6

8

10

12

14

16

18

5 10

0

1

2

0

20

40

60

0 20 40

10 30 500 20 40

10 30 500 20 40

DL 50/220-2,2/4

Ø 217

Ø 217

Ø 217

DL 50/200-1,5/4

Ø 201

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 50/220 -Wilo-CronoTwin-DL 50/200

NPS

H [m

]

Qmin

0

4

8

12

0 20

2

4

6

8

10

12

14

16

18

0 40 6 0

0 5 10 15 20

01234

0 20 40 6 0

0

20

40

60

0 20 40 6 0

DL 50/220-2,2/4

Ø 217

Ø 217Ø 201

Ø 217

DL 50/200-1,5/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 50/220 -Wilo-CronoTwin-DL 50/200

NPS

H [m

]

Qmin +

10 15

0

4

10 30 50

10 30 50

10 30 50

8

12

16

20

24

28

32

0

10

20

0

2

4

0

20

40

60

30

40

5

20 40

20 40

20 40

DL 50/270-4/4

Ø 268

DL 50/260-3/4

Ø 268Ø 255

Ø 268

DL 50/270-3/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 50/270 -Wilo-CronoTwin-DL 50/260

NPS

H [m

]

Qmin

0 20 40 6 0

0 5 10 15 20 25

0

4

8

12

16

20

24

28

32

0

10

20

0 20 40 6 002468

0 20 40 6 00

20

40

60

30

40

DL 50/270-4/4

Ø 268

DL 50/260-3/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 50/270 -Wilo-CronoTwin-DL 50/260

NPS

H [m

]

Ø 268Ø 255

Ø 268

Qmin

Page 171: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

171

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoTwin-DL

Standard

pum

ps

Wilo-CronoTwin-DL 65/150-0,75/4 - 65/170-1,5/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 65/150-0,75/4 - 65/170-1,5/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 65/210-2,2/4 - 65/220-3/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 65/210-2,2/4 - 65/220-3/4

Speed 1450 rpm - parallel operation

0

2

4

6

8

10

12

0

2

0

1,0

0,5

1,5

0

4

6

10 155

0 20 40 60

0 20 40 60

0 20 40 60

20406080

DL 65/170-1,5/4

DL 65/170-1,1/4

Ø 173

Ø 173Ø 159

Ø 173

DL 65/160-1,1/4DL 65/150-0,75/4

Ø 144

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 65/170 -Wilo-CronoTwin-DL 65/150Qmin

NPS

H [m

]

0 20 40 6 0

0 5 10 15 20

0

2

4

6

8

10

12

0

2

0 20 40 6 00

1

2

3

0 20 40 6 00

20406080

4

6

DL 65/170-1,5/4

Ø 173

Ø 173Ø 159

Ø 173

DL 65/160-1,1/4

Ø 144

DL 65/150-0,75/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 65/170 -Wilo-CronoTwin-DL 65/150

Qmin

NPS

H [m

]

0

4

8

12

16

20

1

2

3

020406080

0

5 10 15

2010 40 5030

10 5030

10 5030

0

20 400

20 400

DL 65/220-3/4

Ø 225

DL 65/210-2,2/4

Ø 225

Ø 225

Ø 208

DL 65/220-2,2/4

0

4

8

12

16

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 65/220 -Wilo-CronoTwin-DL 65/210

Qmin

NPS

H [m

]

0 20 40 60 80 1000

4

8

12

16

20

0 20 40 60 80 100

2

4

6

0 40 60 80 1000

0 2

0

0 5 10 15 20 25 30

20406080

DL 65/220-3/4

Ø 225

DL 65/210-2,2/4

Ø 225

Ø 225

Ø 208

0

4

8

12

16

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 65/220 -Wilo-CronoTwin-DL 65/210

NPS

H [m

]Qmin

Page 172: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

172 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL

Wilo-CronoTwin-DL 65/250-3/4 - 65/270-5,5/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 65/250-3/4 - 65/270-5,5/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 80/150-1,1/4 - 80/170-2,2/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 80/150-1,1/4 - 80/170-2,2/4

Speed 1450 rpm - parallel operation

0 20 40 60

0 20 40 60

0 5 10 15 20

0 0

4

8

12

16

20

24

28

0

4

6

2

0

20

40

4

8

12

0 20 40 60

60

DL 65/270-5,5/4

Ø 263

DL 65/250-4/4

Ø 263

Ø 247

Ø 263

DL 65/250-3/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 65/270 -Wilo-CronoTwin-DL 65/250

NPSH

[m]

Qmin

L

00 20 40 60 80 100 120

0 10 2 0

0

4

8

12

16

20

24

28

0 20 40 60 80 100 1200

4

8

12

0 20 40 60 80 100 1200

20

40

60

4

8

12

DL 65/270-5,5/4

Ø 263

DL 65/250-4/4

Ø 263Ø 247

Ø 263

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 65/270 -Wilo-CronoTwin-DL 65/250

NPS

H [m

]

Qmin

0

2

4

6

8

10

12

0

2

4

0

1

2

0204060

6

8

DL 80/170-2,2/4

Ø 175

DL 80/160-1,5/4

DL 80/150-1,1/4

Ø 175

Ø 158Ø 146

Ø 175

0 10 20 30

40 6020 80 100

6020 100

6020 100

0

40 800

40 800

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 80/170 -Wilo-CronoTwin-DL 80/150

NPS

H [m

]

Qmin

0 40 80 120 160

500 10 20 30 40

0

2

4

6

8

10

12

0

2

4

0 40 80 120 1600123

0 40 80 120 1600

204060

6

8

DL 80/170-2,2/4

Ø 175

DL 80/160-1,5/4

DL 80/150-1,1/4

Ø 175

Ø 158Ø 146

Ø 175

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 80/170 -Wilo-CronoTwin-DL 80/150

+

NPS

H [m

]

Qmin

Page 173: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

173

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoTwin-DL

Standard

pum

ps

Wilo-CronoTwin-DL 80/210-3/4 - 80/220-4/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 80/210-3/4 - 80/220-4/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 80/270-5,5/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 80/270-5,5/4

Speed 1450 rpm - parallel operation

20 40 60 80 1000

0 10 20

0

2

4

6

8

10

12

14

16

18

0

8

16

0204060

24

0

234

1

20 40 60 80 1000

20 40 60 80 1000

DL 80/220-4/4

Ø 222

Ø 222

Ø 222

DL 80/210-3/4

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

Q[m³/h]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 80/220 -Wilo-CronoTwin-DL 80/210

NPS

H [m

]

Qmin

Ø 215

0 40 80 120 160 200

0 10 20 30 40 50 60

0

2

4

6

8

10

12

14

16

0

8

16

0 40 80 120 160 2000246

0 40 80 120 160 2000

204060

24

18

DL 80/220-4/4

Ø 222

Ø 222Ø 215

Ø 222

DL 80/210-3/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 80/220 -Wilo-CronoTwin-DL 80/210

+

NPS

H [m

]

Qmin

0

4

20 60 100

20 60 100

20 60 100

8

12

16

20

24

0

4

6

2

0204060

4

2

00 40 80

0 40 80

0 40 80

0 10 20 30

8

6

DL 80/270-5,5/4

Ø 250

Ø 250

Ø 250

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 80/270

NPS

H [m

]

Qmin

0 80 120 160

0 20 30 40 50

0

4

8

12

16

20

24

0 40 80 120 1600

4

8

12

0 80 120 1600

204060

0 1

0 4

4

2

00 4

8

6

DL 80/270-5,5/4

Ø 250

Ø 250

Ø 250

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 80/270+

NPS

H [m

]Qmin

Page 174: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

174 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL

Wilo-CronoTwin-DL 100/145-1,1/4 - 100/170-3/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 100/145-1,1/4 - 100/170-3/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 100/200-3/4 - 100/220-5,5/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 100/200-3/4 - 100/220-5,5/4

Speed 1450 rpm - parallel operation

0

4

0

2

4

6

8

10

0

1

2

3

020406080

8

12

2010 300

20 40 60 80 1200 100

20 40 60 80 1201000

20 40 60 80 1200 100

DL 100/170-3/4

Ø 171

Ø 171

DL 100/160-2,2/4DL 100/150-1,5/4

DL 100/145-1,1/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 100/170 -Wilo-CronoTwin-DL 100/145

NPS

H [m

]

Qmin

Ø 171Ø 158

Ø 142Ø 134

0

4

0

2

4

6

8

10

0 50 100 150 200 250

0 100 150 200 2500

2

4

6

0204060

0 50 100 150 200 250

0 20 40 60

0 5

8

12

Ø 171

Ø 171Ø 158

Ø 142

Ø 134

Ø 171

DL 100/170-3/4

DL 100/160-2,2/4

DL 100/150-1,5/4

DL 100/145-1,1/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 100/170 -Wilo-CronoTwin-DL 100/145

+

NPS

H [m

]

Qmin

1000

2

4

6

8

10

12

14

16

04812

0

4

6

2

0204060

1620

0 5025 75 125

25 75 125

25 75 1251000 50

2010 300

1000 50

DL 100/220-5,5/4DL 100/200-4/4

Ø 212

Ø 197

Ø 212

Ø 212

DL 100/200-3/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 100/220 -Wilo-CronoTwin-DL 100/200

Qmin

NPS

H [m

]

0 50 100 150 200 250

0 20 40 60

0

2

4

6

8

10

12

14

16

04812

0 50 100 150 200 2500

4

8

12

0 50 100 150 200 2500

204060

1620

Ø 212

DL 100/220-5,5/4DL 100/200-4/4

Ø 212Ø 197

Ø 212

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 100/220 -Wilo-CronoTwin-DL 100/200

NPS

H [m

]

Qmin

Page 175: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

175

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoTwin-DL

Standard

pum

ps

Wilo-CronoTwin-DL 100/250-5,5/4 - 100/270-11/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 100/250-5,5/4 - 100/270-11/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 125/190-4/4 - 125/220-7,5/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 125/190-4/4 - 125/220-7,5/4

Speed 1450 rpm - parallel operation

0

4

8

12

16

20

24

28

0

5

10

0204060

048

1612

50 100 1500

50 100 1500

50 100 1500

20 400

Ø 266

DL 100/270-11/4

DL 100/260-11/4

DL 100/250-7,5/4

Ø 266Ø 251

Ø 241

Ø 266

DL 100/250-5,5/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 100/270 -Wilo-CronoTwin-DL 100/250

NPS

H [m

]

Qmin

0

4

8

12

16

20

24

28

05

1015

0204060

0 50 100 150 200 250 300

0 20 40 60 80

0 50 100 150 200 250 300

0 50 100 150 200 250 300

048

1612

Ø 266

DL 100/270-11/4

DL 100/260-11/4DL 100/250-7,5/4

Ø 266Ø 251

Ø 241

Ø 266

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 100/270 -Wilo-CronoTwin-DL 100/250

NPS

H [m

]

Qmin

0

2

4

6

8

10

12

14

16

0123

4

8

0

4

0 50 100 150

0 50 100 150

0 50 100 150

0 20 40

0

20406080

Ø 216

DL 125/220-7,5/4DL 125/210-5,5/4DL 125/190-4/4

Ø 216Ø 197

Ø 184

Ø 216

DL 125/220-5,5/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 125/220 -Wilo-CronoTwin-DL 125/190

NPS

H [m

]

Qmin

0 20 40 6 0

0

0 50 100 150 200 2500

2

4

6

8

10

12

14

16

0123

0 50 100 150 200 250

48

1216

0 50 100 150 200 250

300

300

3000

2040

456

6080

Ø 216

DL 125/220-7,5/4DL 125/210-5,5/4DL 125/190-4/4

Ø 216Ø 197

Ø 184

Ø 216

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 125/220 -Wilo-CronoTwin-DL 125/190

NPS

H [m

]Qmin

Page 176: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

176 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL

Wilo-CronoTwin-DL 125/250-11/4 - 125/270-15/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 125/250-11/4 - 125/270-15/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 125/300-18,5/4 - 125/340-30/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 125/300-18,5/4 - 125/340-30/4

Speed 1450 rpm - parallel operation

0 50 150 250100 200

0 50 150 250100 200

0 4020 60

50 150 250100 20000

4

8

12

16

20

24

0

10

15

5

0

0

4

8

12

28

20406080

Ø 272

DL 125/270-15/4DL 125/250-11/4

Ø 272

Ø 248

Ø 272

DL 125/270-11/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 125/270 -Wilo-CronoTwin-DL 125/250

NPS

H [m

]

Qmin

0 100 200 300 400

0 20 40 60 80 100 120

0

4

8

12

16

20

24

0 100 200 300 4000

10

20

0 100 200 300 4000

20406080

0

4

8

12

30

28

Ø 272

DL 125/270-15/4DL 125/250-11/4

Ø 272

Ø 248

Ø 272

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 125/270 -Wilo-CronoTwin-DL 125/250

NPS

H [m

]

Qmin

0

5

10

15

20

25

30

35

40

45

0

20

020406080

0

8

16

0 100 200 300

0 100 200 300

0 100 200 300

0 40 80 10020 60

DL 125/340-30/4

Ø 335

DL 125/320-22/4DL 125/300-18,5/4

Ø 312Ø 296

Ø 335

DL 125/320-18,5/4

Ø 335

0

10

30

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 125/340 -Wilo-CronoTwin-DL 125/300

NPS

H [m

]

Qmin

0

5

10

15

20

25

30

35

40

0

20

40

0

60

0 100 200 300 400 500 600

0 100 200 300 400 500 600

0

8

16

24

0 100 200 300 400 500 600

0 40 80 120 160 200

45

20406080

DL 125/340-30/4

Ø 335

DL 125/320-22/4

DL 125/300-18,5/4

Ø 335

Ø 312

Ø 296

Ø 335

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 125/340 -Wilo-CronoTwin-DL 125/300

NPS

H [m

]

Qmin

Page 177: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

177

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoTwin-DL

Standard

pum

ps

Wilo-CronoTwin-DL 150/190-5,5/4 - 150/220-11/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 150/190-5,5/4 - 150/220-11/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 150/250-15/4 - 150/270-22/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 150/250-15/4 - 150/270-22/4

Speed 1450 rpm - parallel operation

0

2

4

6

8

10

12

14

16

5

10

204060

0

2

4

6

0

0

0 50 150 250100 200

0 50 150 250100 200

0 4020 60

50 150 250100 2000

80

18

DL 150/220-11/4

Ø 224

DL 150/200-7,5/4DL 150/190-5,5/4

Ø 224

Ø 201Ø 186

Ø 224

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 150/220 -Wilo-CronoTwin-DL 150/190

NPS

H [m

]

Qmin

0 100 200 300 400

0 20 40 60 80 100 120

0

2

4

6

8

10

12

14

16

0 100 200 300 400

51015

0 100 200 300 400

204060

20

0

2

4

6

0

0

80

18

DL 150/220-11/4

Ø 224

DL 150/200-7,5/4DL 150/190-5,5/4

Ø 224

Ø 201Ø 186

Ø 224

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 150/220 -Wilo-CronoTwin-DL 150/190

NPS

H [m

]

Qmin

0 100 200 3000

4

8

12

16

20

24

0

8

0 100 200 3000

10

0 100 200 3000

20406080

16

24

20

28

40 80 100200 60

Ø 272

DL 150/270-22/4DL 150/260-18,5/4DL 150/250-15/4

Ø 272

Ø 272

Ø 263Ø 252

DL 150/270-18,5/4

DL 150/260-15/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 150/270 -Wilo-CronoTwin-DL 150/250

NPS

H [m

]

Qmin

0 100 200 300 400 500 600

0 40 80 120 160 200

0

4

8

12

16

20

24

0

8

0 100 200 300 400 500 6000

1020304050

0 100 200 300 400 500 6000

16

24

28

20406080

Ø 272

DL 150/270-22/4

DL 150/260-18,5/4DL 150/250-15/4

Ø 272

Ø 272

Ø 263

Ø 252

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 150/270 -Wilo-CronoTwin-DL 150/250

NPS

H [m

]Qmin

Page 178: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

178 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL

Wilo-CronoTwin-DL 150/300-30/4 - 150/340-45/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 150/300-30/4 - 150/340-45/4

Speed 1450 rpm - parallel operation

Wilo-CronoTwin-DL 200/240-15/4 - 200/270-30/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 200/240-15/4 - 200/270-30/4

Speed 1450 rpm - parallel operation

0 100 300 500200 400

0 100 300 500200 400

100 300 500200 40000

10

20

30

0

5

10

15

20

25

30

35

40

0

20

020406080

40

45

0

Ø 343

DL 150/340-45/4DL 150/320-37/4DL 150/300-30/4

Ø 323Ø 305

Ø 343

Ø 343

DL 150/340-37/4

Q[m³/h]

Q[m³/h]

Q[m³/h]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 150/340 -Wilo-CronoTwin-DL 150/300

NPS

H [m

]

Qmin

0 50 100 150 Q[l/s]

/LL

0

10

20

30

0 200 400 600 800 1000

1000

0 50 100 150 200 250 300

0

5

10

15

20

25

30

35

40

0 200 400 600 800

1000

0204060

200 400 600 8000

80

45

0

20406080

Ø 343

DL 150/340-45/4

DL 150/320-37/4DL 150/300-30/4

Ø 343Ø 323Ø 305

Ø 343

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 150/340 -Wilo-CronoTwin-DL 150/300

NPS

H [m

]

Qmin

0

20

10

30

0 200 400 600

200 400 600

200 400 600

0

4

8

12

16

20

24

048121620

0 100 150 20050

00

00

20406080

DL 200/270-30/4

Ø 272

DL 200/260-22/4DL 200/250-18,5/4DL 200/240-15/4

Ø 272

Ø 233

Ø 252

Ø 272

Ø 243

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 200/270 -Wilo-CronoTwin-DL 200/240

NPS

H [m

]

Qmin

0 200 400 600 800 1000 12000

4

8

12

16

20

24

048121620

0 100 200 300 400

0

20

40

0 200 400 600 800 1000 1200

0 200 400 600 800 1000 12000

20406080

60

DL 200/270-30/4

Ø 272

DL 200/260-22/4DL 200/250-18,5/4DL 200/240-15/4

Ø 272

Ø 233

Ø 252

Ø 272

Ø 243

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

+

Wilo-CronoTwin-DL 200/270 -Wilo-CronoTwin-DL 200/240

NPS

H [m

]

Qmin

Page 179: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

179

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoTwin-DL

Standard

pum

ps

Wilo-CronoTwin-DL 200/310-37/4 - 200/340-55/4

Speed 1450 rpm - individual operation

Wilo-CronoTwin-DL 200/310-37/4 - 200/340-55/4

Speed 1450 rpm - parallel operation

0

40

20

60

0 100 300 500200 400

0 100 300 500200 400

100 300 500200 40000

5

10

15

20

25

30

35

40

048

20406080

121620

45

DL 200/340-55/4

Ø 330

Ø 330

Ø 297Ø 314

Ø 330

DL 200/320-45/4DL 200/310-37/4

0

0 50 100 150 Q[l/s]

Q[m³/h]

Q[m³/h]

Q[m³/h]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 200/340 -Wilo-CronoTwin-DL 200/310

NPS

H [m

]

Qmin

0 200 400 600 800 1000 1200

1200

0 50 100 150 200 250 300 350

0

5

10

15

20

25

30

35

40

048

0 200 400 600 800 1000

1200

0

40

80

0 200 400 600 800 1000

121620

45

120

20406080

DL 200/340-55/4

Ø 330

Ø 330

Ø 297

Ø 314

Ø 330

DL 200/320-45/4DL 200/310-37/4

0

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 200/340 -Wilo-CronoTwin-DL 200/310

NPS

H [m

]

Qmin +

Page 180: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

180 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-CronoTwin-DL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-CronoTwin-DL 32/140-1,5/2 - 32/170-4/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 32/140-1,5/2 - 32/170-4/2

Speed 2900 rpm - parallel operation

Wilo-CronoTwin-DL 40/140-2,2/2 - 40/170-5,5/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 40/140-2,2/2 - 40/170-5,5/2

Speed 2900 rpm - parallel operation

5 15 2510 200

5 15 2510 200

5 15 2510 200

0

10

20

30

40

50

051015

0

1

2

3

0

20

40

60

6420

DL 32/150-2,2/2

Ø173

Ø 173

Ø 143Ø 157

Ø 173

DL 32/170-4/2DL 32/160-3/2

DL 32/140-1,5/2

Ø 127

DL 32/170-3/2

DL 32/160-2,2/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 32/170 -Wilo-CronoTwin-DL 32/140

NPS

H [m

]

Qmin

0 10 20 30 4 00

10

20

30

40

50

051015

0 10 20 30 4 002468

0 10 20 30 4 00

20

40

60

202530

0 4 2

DL 32/150-2,2/2

Ø173

Ø 173

Ø 143Ø 157

Ø 173

DL 32/170-4/2DL 32/160-3/2

DL 32/140-1,5/2

Ø 127

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 32/170 -Wilo-CronoTwin-DL 32/140

NPS

H [m

]

Qmin +

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 30 5010

30 5010

30 5010

40

0 20 40

0 20 40

Q[l/s]0 5 10 15

H[m]

0

5

10

15

20

25

30

35

40

45

0

10

20

30

40

P2[kW]

0

4

2

6

ηp[%]

0

20

40

60

DL 40/170-5,5/2

DL 40/150-3/2

DL 40/160-4/2DL 40/140-2,2/2

Ø 150Ø 138

Ø 168

Ø 168

Ø 168

Ø 122

Wilo-CronoTwin-DL 40/170 -Wilo-CronoTwin-DL 40/140

Qmin

NPS

H [m

]

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100

Q[l/s]0 5 10 15 20 25 30

H[m]

0

5

10

15

20

25

30

35

40

45

0

10

20

30

40

0 20 40 60 80 100

P2[kW]

0

4

8

12

0 20 40 60 80 100

ηp[%]

0

20

40

60

DL 40/170-5,5/2DL 40/150-3/2

DL 40/160-4/2DL 40/140-2,2/2

Ø 150Ø 138

Ø 168

Ø 168

Ø 168

Ø 122

Wilo-CronoTwin-DL 40/170 -Wilo-CronoTwin-DL 40/140

NPS

H [m

]

Qmin

+

Page 181: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

181

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoTwin-DL

Standard

pum

ps

Wilo-CronoTwin-DL 40/200-7,5/2 - 40/220-11/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 40/200-7,5/2 - 40/220-11/2

Speed 2900 rpm - parallel operation

Wilo-CronoTwin-DL 50/110-1,5/2 - 50/140-4/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 50/110-1,5/2 - 50/140-4/2

Speed 2900 rpm - parallel operation

40 50 Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 3010

40 500 20 3010

40 500 20 3010

Q[l/s]0 5 10 15

H[m]

0

10

20

30

40

50

60

70

0

10

20

30

P2[kW]

0

5

10

ηp[%]

0

20

40

60

DL 40/220-11/2DL 40/200-7,5/2

Ø 195

Ø 215

Ø 215

Ø 215

NPS

H [m

]

QminWilo-CronoTwin-DL 40/220 -Wilo-CronoTwin-DL 40/200

0 8

0 8

0 8 Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 6 0

Q[l/s]0 5 10 15 20 25

H[m]

0

10

20

30

40

50

60

70

0

10

20

30

0 20 40 6 0

P2[kW]

05

101520

0 20 40 6 0

ηp[%]

0

20

40

60

DL 40/220-11/2DL 40/200-7,5/2

Ø 195

Ø 215

Ø 215

Ø 215

NPS

H [m

]

Qmin

+

Wilo-CronoTwin-DL 40/220 -Wilo-CronoTwin-DL 40/200

Q[m³/h]0 20 30 5010

30 5010

30 5010

40

0 20 40

0 20 40

Q[l/s]0 5 10 15

H[m]

0

4

8

12

16

20

24

28

32

0

10

20

Q[m³/h]0

2

4

Q[m³/h]0

Ø 111

Ø 126

Ø 138

Ø 138

Ø 101

DL 50/110-1,5/2

DL 50/120-2,2/2

DL 50/140-3/2

DL 50/140-4/2DL 50/130-3/2

Ø 138 NPS

H [m

]

Qmin

Wilo-CronoTwin-DL 50/140 -Wilo-CronoTwin-DL 50/110

P2[kW]

ηp[%]

20406080

Q[m³/h]0 20 40 60 80 100

Q[l/s]0 5 10 15 20 25 30

H[m]

0

4

8

12

16

20

24

28

32

0

10

20

30

Q[m³/h]0 20 40 60 80 100

P2[kW]

02468

Q[m³/h]0 20 40 60 80 100

ηp[%]

020406080

Ø 111Ø 126

Ø 138

Ø 138

Ø 101

DL 50/110-1,5/2

DL 50/120-2,2/2

DL 50/140-4/2DL 50/130-3/2

Ø 138

NPS

H [m

]Qmin +

Wilo-CronoTwin-DL 50/140 -Wilo-CronoTwin-DL 50/110

Page 182: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

182 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL

Wilo-CronoTwin-DL 50/160-5,5/2 - 50/170-7,5/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 50/160-5,5/2 - 50/170-7,5/2

Speed 2900 rpm - parallel operation

Wilo-CronoTwin-DL 50/180-7,5/2 - 50/220-15/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 50/180-7,5/2 - 50/220-15/2

Speed 2900 rpm - parallel operation

L

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60

0 20 40 60

0 20 40 60

Q[l/s]0 5 10 15 20

H[m]

0

5

10

15

20

25

30

35

40

45

048121620

P2[kW]

0

4

6

2

ηp[%]

0

20

40

60

DL 50/160-5,5/2

DL 50/170-7,5/2

Ø 167

Ø 167

Ø 167

Ø 157

NP

SH

[m

]

Qmin

Wilo-CronoTwin-DL 50/170 -

Wilo-CronoTwin-DL 50/160

DL 50/170-5,5/2 L

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100

Q[l/s]0 5 10 15 20 25 30

H[m]

0

5

10

15

20

25

30

35

40

45

048121620

0 20 40 60 80 100

P2[kW]

0

4

8

12

0 20 40 60 80 100

ηp[%]

0

20

40

60

DL 50/160-5,5/2

DL 50/170-7,5/2

Ø 167

Ø 167

Ø 167

Ø 157

NP

SH

[m

]

Qmin

+

Wilo-CronoTwin-DL 50/170 -

Wilo-CronoTwin-DL 50/160

L

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60

0 20 40 60

0 20 40 60

Q[l/s]0 10 15 205

H[m]

0

10

20

30

40

50

60

70

01020

P2[kW]

0

10

15

5

ηp[%]

0

20

40

60

DL 50/180-7,5/2

DL 50/210-11/2

DL 50/220-15/2

Ø 211

Ø 211

Ø 211

Ø 184Ø 201

NPS

H [m

]

Qmin

Wilo-CronoTwin-DL 50/220 -Wilo-CronoTwin-DL 50/180

DL 50/220-11/2

L

D

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 20 40 60 80 100 120

Q[l/s]0 10 20 30 40

H[m]

0

10

20

30

40

50

60

70

010203040

0 20 40 60 80 100 120

P2[kW]

0

10

20

30

0 20 40 60 80 100 120

ηp[%]

0

20

40

60

DL 50/180-7,5/2

DL 50/210-11/2

DL 50/220-15/2

Ø 211

Ø 211

Ø 211

Ø 184Ø 201

NPS

H [m

]

Qmin+

Wilo-CronoTwin-DL 50/220 -Wilo-CronoTwin-DL 50/180

Page 183: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

183

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoTwin-DL

Standard

pum

ps

Wilo-CronoTwin-DL 65/110-3/2 - 65/140-7,5/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 65/110-3/2 - 65/140-7,5/2

Speed 2900 rpm - parallel operation

Wilo-CronoTwin-DL 65/150-5,5/2 - 65/170-11/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 65/150-5,5/2 - 65/170-11/2

Speed 2900 rpm - parallel operation

D

Q[m³/h]0 40 80 10020 60

Q[m³/h]0 40 80 10020 60

Q[m³/h]0 40 80 10020 60

Q[l/s]0 10 20 30

H[m]

0

4

8

12

16

20

24

28

32

01020

0

4

8

0

DL 65/130-5,5/2DL 65/120-4/2

DL 65/140-7,5/2

DL 65/110-3/2

Ø 140

Ø 140

Ø 140

Ø 108

Ø 126Ø 117

NPS

H [m

]

Qmin

Wilo-CronoTwin-DL 65/140 -Wilo-CronoTwin-DL 65/110

DL 65/140-5,5/2

DL 65/120-3/2

P2[kW]

ηp[%]

20406080

D

Q[m³/h]

Q[m³/h]

Q[m³/h]

0 40 80 120 160 200

Q[l/s]0 10 20 30 40 50 60

H[m]

0

4

8

12

16

20

24

28

32

01020304050

0 40 80 120 160 200

P2[kW]

048

1216

0 40 80 120 160 200

ηp[%]

020406080

DL 65/130-5,5/2DL 65/120-4/2

DL 65/140-7,5/2

DL 65/110-3/2Ø 140

Ø 140

Ø 140

Ø 108

Ø 126Ø 117

NPS

H [m

]

Qmin +

Wilo-CronoTwin-DL 65/140 -Wilo-CronoTwin-DL 65/110

20 60 10040 800

20 60 10040 800

20 60 10040 800

5

10

15

20

25

30

35

40

0

10

0

5

10

020406080

20

45

0

0 10 205 15 25 30

DL 65/150-5,5/2

Ø168

Ø 168

Ø 134Ø 152

Ø 168

DL 65/170-11/2DL 65/160-7,5/2

DL 65/160-5,5/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 65/170 -Wilo-CronoTwin-DL 65/150

NPS

H [m

]

Qmin

0 40 80 120 160 200

5

10

15

20

25

30

35

40

0

10

0 40 80 120 160 20005

1015

0 40 80 120 160 2000

20406080

20

30

45

20

0 10 20 30 40 50 60

0

DL 65/150-5,5/2Ø168

Ø 168

Ø 134Ø 152

Ø 168

DL 65/170-11/2

DL 65/160-7,5/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 65/170 -Wilo-CronoTwin-DL 65/150

NPS

H [m

]Qmin

+

Page 184: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

184 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL

Wilo-CronoTwin-DL 65/220-11/2 - 65/220-22/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 65/200-11/2 - 65/220-22/2

Speed 2900 rpm - parallel operation

Wilo-CronoTwin-DL 80/120-4/2 - 80/140-7,5/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 80/120-4/2 - 80/140-7,5/2

Speed 2900 rpm - parallel operation

20 60 10040 800

20 60 10040 800

20 60 10040 800

5 1510 25 300 20

0

10

20

30

40

50

60

70

0

10

0

10

20

0

20

80

DL 65/200-15/2

Ø217

DL 65/220-22/2

DL 65/210-18,5/2

Ø 217Ø 206

Ø 194

Ø 217

DL 65/220-18,5/2

DL 65/210-15/2

DL 65/200-11/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 65/220 -Wilo-CronoTwin-DL 65/200

NPS

H [m

]

Qmin

20406080

D

0 40 80 120 160 200

0 10 20 30 40 50 60

0

10

20

30

40

50

60

70

0

10

0 40 80 120 160 2000

10203040

0 40 80 120 160 2000

20406080

20

30

80

DL 65/200-15/2

Ø217

DL 65/220-22/2DL 65/210-18,5/2

Ø 217Ø 206

Ø 194

Ø 217

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

Wilo-CronoTwin-DL 65/220 -Wilo-CronoTwin-DL 65/200

NPS

H [m

]

Qmin+

0

4

8

12

16

20

24

048

0

4

6

2

020406080

12

3010 200

50 100 12575250

50 100 12575250

50 100 12575250

DL 80/140-7,5/2DL 80/130-5,5/2DL 80/120-4/2

Ø 134

Ø 134

Ø 122Ø 112

Ø 134

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

Wilo-CronoTwin-DL 80/140 -Wilo-CronoTwin-DL 80/120

0 50 100 150 200 250

0 20 4 0

0

4

8

12

16

20

24

048

0 50 100 150 200 250048

1216

0 50 100 150 200 2500

121620

20406080

DL 80/140-7,5/2

DL 80/130-5,5/2

DL 80/120-4/2

Ø 134

Ø 134Ø 122

Ø 112

Ø 134

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

QminWilo-CronoTwin-DL 80/140 -Wilo-CronoTwin-DL 80/120

+

Page 185: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

185

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-CronoTwin-DL

Standard

pum

ps

Wilo-CronoTwin-DL 80/150-7,5/2 - 80/170-15/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 80/150-7,5/2 - 80/170-15/2

Speed 2900 rpm - parallel operation

Wilo-CronoTwin-DL 80/190-15/2 - 80/220-30/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 80/190-15/2 - 80/220-30/2

Speed 2900 rpm - parallel operation

50 100 12575250

50 100 12575250

50 100 12575250

0 10 20 30

10

15

20

25

30

35

40

048

0

10

20406080

12

45

0

5

15

5

0

DL 80/170-15/2

DL 80/160-11/2DL 80/150-7,5/2

Ø 173

Ø 173

Ø 152Ø 140

Ø 173

DL 80/170-11/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

QminWilo-CronoTwin-DL 80/170 -Wilo-CronoTwin-DL 80/150

0 50 100 150 200 250 300

300

0 20 40 6 0

0

5

10

15

20

25

30

35

40

048

0 50 100 150 200 250

300

0

10

20

30

0 50 100 150 200 250

20406080

121620

45

0

DL 80/170-15/2DL 80/160-11/2

DL 80/150-7,5/2

Ø 173

Ø 173

Ø 152Ø 140

Ø 173

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

QminWilo-CronoTwin-DL 80/170 -Wilo-CronoTwin-DL 80/150

+

50 100 1500

10

20

30

40

50

60

0

10

0

20

10

30

0

20

30

70

0 20 40

0

10 30

50 100 1500

50 100 1500

DL 80/220-30/2DL 80/200-22/2

DL 80/190-18,5/2

Ø 220

Ø 220

Ø 203Ø 194

Ø 220

DL 80/200-18,5/2

DL 80/190-15/2

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

Wilo-CronoTwin-DL 80/220 -Wilo-CronoTwin-DL 80/190

20406080

D

0 50 100 150 200 250

0 20 40 6 0

0

10

20

30

40

50

60

0

10

0 50 100 150 200 250

300

3000

20

40

60

0 50 100 150 200 250 3000

20406080

20

30

70

DL 80/220-30/2DL 80/200-22/2DL 80/190-18,5/2

Ø 220

Ø 220Ø 203

Ø 194

Ø 220

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]Qmin

Wilo-CronoTwin-DL 80/220 -Wilo-CronoTwin-DL 80/190

+

Page 186: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

186 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-CronoTwin-DL

Wilo-CronoTwin-DL 100/145-11/2 - 100/170-30/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 100/145-11/2 - 100/170-30/2

Speed 2900 rpm - parallel operation

Wilo-CronoTwin-DL 100/190-30/2 - 100/210-37/2

Speed 2900 rpm - individual operation

Wilo-CronoTwin-DL 100/190-30/2 - 100/210-37/2

Speed 2900 rpm - parallel operation

0 100 200 3000

5

10

15

20

25

30

35

40

0

8

0 100 200 3000

10

20

30

0 100 200 3000

16

24

45

0 20 40 60 80 100

20406080

DL 100/170-30/2DL 100/165-22/2DL 100/160-18,5/2

Ø 175

Ø 175Ø 168

Ø 158

DL 100/150-15/2

DL 100/145-11/2

Ø 140 Ø 150

DL 100/160-15/2

Ø 175

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin Wilo-CronoTwin-DL 100/170 -Wilo-CronoTwin-DL 100/145

D

0 100 200 300 400

0 20 40 60 80 100 120

0

5

10

15

20

25

30

35

40

0

8

0 100 200 300 4000

10203040

0 100 200 300 4000

20406080

16

24

45

DL 100/170-30/2DL 100/165-22/2DL 100/160-18,5/2

Ø 175

Ø 175Ø 168

Ø 175

DL 100/150-15/2DL 100/145-11/2

Ø 140Ø 150

Ø 158

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

QminWilo-CronoTwin-DL 100/170 -Wilo-CronoTwin-DL 100/145

+

50 100 150 200 Q[m³/h]

Q[l/s]

00

50 100 150 200 Q[m³/h]0

50 100 150 200 Q[m³/h]0

0 20 40 60

10

20

30

40

50

60

H[m]

0

20

40

60P2[kW]

020406080

ηp[%]

04812

NPS

H [m

]

DL 100/210-30/2 DL 100/210-37/2DL 100/190-30/2

Wilo-CronoTwin-DL 100/210 -Wilo-CronoTwin-DL 100/190

Ø 204

Ø 204Ø 192

Ø 204

Qmin

LL

0 50 100 150 200 250 300

0 20 40 60 80 100

0 50 100 150 200 250 3000

20

40

60

0 50 100 150 200 250 3000

20406080

0

10

20

30

40

50

60

70

048121620

DL 100/210-37/2

Ø 204

Ø 204

Ø 192

Q[m³/h]

Q[m³/h]

Q[m³/h]

Q[l/s]

H[m]

P2[kW]

ηp[%]

NPS

H [m

]

Qmin

Wilo-CronoTwin-DL 100/210 -Wilo-CronoTwin-DL 100/190

+

DL 100/190-30/2

Ø 204

Page 187: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

187

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram, motor data Wilo-CronoTwin-DL

Standard

pum

ps

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-CronoTwin-DL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagramsStar switching Y Delta switching �

Motor protection switch required onsite. Check the direction of rota-tion.To change the direction of rotation, swap any two phases.

P2 � 3 kW 3~400 V Y3~230 V �

P2 4 kW 3~690 V Y3~400 V �

After removing the bridges, Y-� starting is possible.

L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1 L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1

MMotor data (1450 rpm)

Wilo-CronoTwin-DL ...

Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

0.25 kW 0.77 0.78 0.60

0.37 kW 1.06 0.78 0.65

0.55 kW 1.44 0.82 0.67

0.75 kW 1.91 0.81 0.72

1.1 kW 2.55 0.81 0.77

1.5 kW 3.40 0.81 0.79

2.2 kW 4.70 0.82 0.82

3 kW 6.40 0.82 0.83

4 kW 8.20 0.83 0.85

5.5 kW 11.40 0.81 0.86

7.5 kW 15.20 0.82 0.87

11 kW 21.50 0.84 0.89

15 kW 28.50 0.84 0.90

18.5 kW 35.50 0.83 0.91

22 kW 41.50 0.84 0.91

30 kW 55.00 0.86 0.92

37 kW 66.00 0.87 0.93

45 kW 80.00 0.87 0.93

55 kW 100.00 0.85 0.94

Observe motor name plate data

Motor data (2900 rpm)

Wilo-CronoTwin-DL ...

Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

1.5 kW 3.25 0.85 0.79

2.2 kW 4.55 0.85 0.82

3 kW 6.10 0.85 0.84

4 kW 7.80 0.86 0.86

5.5 kW 10.40 0.89 0.86

7.5 kW 13.80 0.89 0.88

11 kW 20.00 0.88 0.90

Page 188: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

188 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Terminal diagram, motor data Wilo-CronoTwin-DL

15 kW 26.50 0.90 0.90

18.5 kW 32.00 0.91 0.91

22 kW 39.50 0.88 0.92

30 kW 53.00 0.89 0.92

37 kW 65.00 0.89 0.93

Observe motor name plate data

Motor data (2900 rpm)

Wilo-CronoTwin-DL ...

Nominal current (approx.) Power factor Efficiency

IN 3~400 V cos � �M

[A] –

Page 189: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

189

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-CronoTwin-DL

Standard

pum

ps

Standard pumps Double pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-CronoTwin-DL Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing

II Pressure measuring connection R1/8; III Ventilation R1/8

Øg

ØD

Ø18

Øk

Ød

s

ax

60

2

b3

q

III

10

II

b 1b

l 0m

ef

3 x o

p

p 1

c

ef

50

II

50

DN

n x

d L

1l

Dimensions, weights (1450 rpm)

Wilo-CronoTwin-DL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q s x M

– [mm] – [mm] [kg]

32/140-0.25/4 32 320 100 117 122 118 360 43 137 145 395 155 M10 20 – 118 300 90 77

32/150-0.37/4 32 320 100 117 122 118 360 43 137 145 395 155 M10 20 – 118 300 90 80

32/170-0.55/4 32 320 100 117 122 124 360 43 137 188 430 155 M10 20 – 124 300 90 84

40/140-0.25/4 40 340 100 120 127 118 400 52 145 145 399 170 M10 20 – 118 340 95 82

40/150-0.37/4 40 340 100 120 127 118 400 52 145 145 399 170 M10 20 – 118 340 95 84

40/160-0.55/4 40 340 100 120 127 124 400 52 145 188 424 170 M10 20 – 124 340 95 88

40/170-0.75/4 40 340 100 120 127 124 400 52 145 188 424 170 M10 20 – 124 340 95 90

40/210-1.1/4 40 440 110 145 147 – 500 38 192 193 466 220 M10 20 151 – 400 100 111

40/220-1.5/4 40 440 110 145 147 – 500 38 192 193 466 220 M10 20 151 – 400 100 118

50/150-0.55/4 50 340 120 126 136 124 360 50 130 188 420 180 M10 20 – 124 340 100 92

50/160-0.75/4 50 340 120 126 136 124 360 50 130 188 420 180 M10 20 – 124 340 100 95

50/170-1.1/4 50 340 120 126 136 145 360 50 130 193 460 180 M10 20 – 145 340 100 102

50/200-1.5/4 50 440 120 145 148 – 500 50 200 193 472 220 M10 20 151 – 400 100 115

50/220-2.2/4 50 440 120 145 148 – 500 50 200 217 516 220 M10 20 160 – 400 100 134

50/260-3/4 50 440 122 177 174 – 480 50 200 217 542 220 M10 20 160 – 400 120 158

50/270-3/4 50 440 122 177 174 – 480 50 200 217 540 220 M10 20 160 – 400 120 158

50/270-4/4 50 440 122 177 174 – 480 50 200 232 620 220 M10 20 178 – 400 120 172

65/150-0.75/4 65 430 153 134 144 124 440 55 185 188 438 215 M12 20 – 124 400 120 114

65/160-1.1/4 65 430 153 134 144 145 440 55 185 193 478 215 M12 20 – 145 400 120 121

65/170-1.1/4 65 430 153 134 144 145 440 55 185 193 478 215 M12 20 – 145 400 120 122

65/170-1.5/4 65 430 153 134 144 149 440 55 185 193 478 215 M12 20 – 149 400 120 128

65/210-2.2/4 65 475 140 157 166 – 520 45 210 217 525 245 M12 20 160 – 400 110 145

65/220-2.2/4 65 475 140 157 166 – 520 45 210 217 525 245 M12 20 160 – 400 110 145

65/220-3/4 65 475 140 157 166 – 520 45 210 217 525 245 M12 20 160 – 400 110 151

65/250-3/4 65 475 140 184 176 – 500 50 220 217 545 235 M12 20 160 – 400 120 168

Page 190: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

190 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-CronoTwin-DL

65/250-4/4 65 475 140 184 176 – 500 50 220 232 623 235 M12 20 178 – 400 120 180

65/270-5.5/4 65 475 140 184 176 – 500 50 220 279 679 235 M12 20 188 – 400 120 204

80/150-1.1/4 80 440 155 144 160 145 440 62 188 193 483 220 M12 20 – 145 400 120 133

80/160-1.5/4 80 440 155 144 160 149 440 62 188 193 483 220 M12 20 – 149 400 120 140

80/170-2.2/4 80 440 155 144 160 156 440 62 188 217 527 220 M12 20 – 156 400 120 162

80/210-3/4 80 500 145 166 176 – 550 72 228 217 530 250 M12 20 160 – 450 120 169

80/220-4/4 80 500 145 166 176 – 550 72 228 232 608 250 M12 20 178 – 450 120 181

80/270-5.5/4 80 500 125 188 198 – 560 62 233 279 667 245 M12 20 188 – 450 115 234

100/145-1.1/4 100 500 180 173 188 145 580 80 250 193 497 226 M12 20 – 145 440 135 154

100/150-1.5/4 100 500 180 173 188 149 580 80 250 193 497 226 M12 20 – 149 440 135 161

100/160-2.2/4 100 500 180 173 188 156 580 80 250 217 540 226 M12 20 – 156 440 135 183

100/170-3/4 100 500 180 173 188 156 580 80 250 217 540 226 M12 20 – 156 440 135 188

100/200-3/4 100 550 155 183 197 – 560 79 251 217 538 275 M12 20 160 – 450 120 188

100/200-4/4 100 550 155 183 197 – 560 79 251 232 616 275 M12 20 178 – 450 120 200

100/220-5.5/4 100 550 155 183 197 – 560 79 251 279 672 275 M12 20 188 – 450 120 228

100/250-5.5/4 100 550 180 198 210 – 600 54 266 279 677 260 M12 20 188 – 480 120 263

100/250-7.5/4 100 550 180 198 210 – 600 54 266 323 718 260 M12 20 188 – 480 120 275

100/260-11/4 100 550 180 198 210 – 600 54 266 323 800 260 M12 20 250 – 480 120 346

100/270-11/4 100 550 180 198 210 – 600 54 266 323 800 260 M12 20 250 – 480 120 346

125/190-4/4 125 620 180 205 189 – 640 68 283 232 635 312 M16 25 178 – 500 120 225

125/210-5.5/4 125 620 180 205 189 – 640 68 283 279 691 312 M16 25 188 – 500 120 257

125/220-5.5/4 125 620 180 205 189 – 640 68 283 279 691 312 M16 25 188 – 500 120 257

125/220-7.5/4 125 620 180 205 189 – 640 68 283 323 732 312 M16 25 188 – 500 120 273

125/250-11/4 125 620 200 255 267 – 591 86 314 323 813 280 M16 25 250 – 520 130 397

125/270-11/4 125 620 200 255 267 – 591 86 314 323 813 280 M16 25 250 – 520 130 397

125/270-15/4 125 620 200 255 267 – 591 86 314 370 856 280 M16 25 250 – 520 130 421

125/300-18.5/4 125 700 200 277 292 – 800 51 334 370 924 340 M16 25 294 – 550 140 615

125/320-18.5/4 125 700 200 277 292 – 800 51 334 370 924 340 M16 25 294 – 550 140 615

125/320-22/4 125 700 200 277 292 – 800 51 334 370 952 340 M16 25 294 – 550 140 635

125/340-30/4 125 700 200 277 292 – 800 51 334 415 1012 340 M16 25 306 – 550 140 729

150/190-5.5/4 150 700 210 215 241 – 640 91 309 279 695 365 M16 25 188 – 550 130 324

150/200-7.5/4 150 700 210 215 241 – 640 91 309 323 736 365 M16 25 188 – 550 130 340

150/220-11/4 150 700 210 215 241 – 640 91 309 323 818 365 M16 25 250 – 550 130 409

150/250-15/4 150 700 230 293 310 – 696 116 344 370 887 330 M16 25 250 – 600 135 548

150/260-15/4 150 700 230 293 310 – 696 116 344 370 887 330 M16 25 250 – 600 135 548

150/260-18.5/4 150 700 230 293 310 – 696 116 344 370 929 330 M16 25 294 – 600 135 604

150/270-18.5/4 150 700 230 293 310 – 696 116 344 370 929 330 M16 25 294 – 600 135 604

150/270-22/4 150 700 230 293 310 – 696 116 344 370 957 330 M16 25 294 – 600 135 624

150/300-30/4 150 770 230 314 329 – 758 130 374 415 1025 370 M16 25 306 – 650 145 639

150/320-37/4 150 770 230 314 329 – 758 130 374 456 1061 370 M16 25 327 – 650 145 748

150/340-37/4 150 770 230 314 329 – 758 130 374 456 1061 370 M16 25 327 – 650 145 748

Dimensions, weights (1450 rpm)

Wilo-CronoTwin-DL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q s x M

– [mm] – [mm] [kg]

Page 191: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

191

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-CronoTwin-DL

Standard

pum

ps

150/340-45/4 150 770 230 314 329 – 758 130 374 456 1125 370 M16 25 327 – 650 145 800

200/240-15/4 200 800 250 322 347 – 1000 62 400 370 912 370 M16 25 250 – 700 140 688

200/250-18.5/4 200 800 250 322 347 – 1000 62 400 370 954 370 M16 25 294 – 700 140 745

200/260-22/4 200 800 250 322 347 – 1000 62 400 370 982 370 M16 25 294 – 700 140 765

200/270-30/4 200 800 250 322 347 – 1000 62 400 415 1042 370 M16 25 306 – 700 140 856

200/310-37/4 200 820 245 339 361 – 808 129 391 456 1086 400 M16 25 327 – 700 155 1000

200/320-45/4 200 820 245 339 361 – 808 129 391 456 1155 400 M16 25 327 – 700 155 1051

200/340-55/4 200 820 245 339 361 – 808 129 391 495 1230 400 M16 25 392 – 700 155 1359

Dimensions, weights (1450 rpm)

Wilo-CronoTwin-DL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q s x M

– [mm] – [mm] [kg]

Dimensions, weights (2900 rpm)

Wilo-CronoTwin-DL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q s x M

– [mm] – [mm] [kg]

32/140-1.5/2 32 320 100 117 122 145 360 43 137 193 460 155 M10 20 – 145 300 90 94

32/150-2.2/2 32 320 100 117 122 149 360 43 137 193 460 155 M10 20 – 149 300 90 99

32/160-2.2/2 32 320 100 117 122 149 360 43 137 193 460 155 M10 20 – 149 300 90 99

32/160-3/2 32 320 100 117 122 156 360 43 137 217 503 155 M10 20 – 156 300 90 118

32/170-3/2 32 320 100 117 122 156 360 43 137 217 501 155 M10 20 – 156 300 90 118

32/170-4/2 32 320 100 117 122 168 360 43 137 232 581 155 M10 20 – 168 300 90 132

40/140-2.2/2 40 340 100 120 127 149 400 52 145 193 464 170 M10 20 – 149 340 95 104

40/150-3/2 40 340 100 120 127 156 400 52 145 217 507 170 M10 20 – 156 340 95 123

40/160-4/2 40 340 100 120 127 168 400 52 145 232 585 170 M10 20 – 168 340 95 137

40/170-5.5/2 40 340 100 120 127 182 400 52 145 279 631 170 M10 20 – 182 340 95 159

40/200-7.5/2 40 440 110 145 147 – 500 38 192 279 644 220 M10 20 188 – 400 100 200

40/220-11/2 40 440 110 145 147 – 500 38 192 323 767 220 M10 20 250 – 400 100 258

50/110-1.5/2 50 340 105 108 116 145 360 52 148 193 463 170 M10 20 – 145 300 100 87

50/120-2.2/2 50 340 105 108 116 149 360 52 148 193 463 170 M10 20 – 149 300 100 92

50/130-3/2 50 340 105 108 116 156 360 52 148 217 510 170 M10 20 – 156 300 100 116

50/140-3/2 50 340 105 108 116 156 360 52 148 217 510 170 M10 20 – 156 300 100 116

50/140-4/2 50 340 105 108 116 168 360 52 148 232 588 170 M10 20 – 168 300 100 130

50/160-5.5/2 50 340 120 126 136 182 360 50 130 279 628 180 M10 20 – 182 340 100 168

50/170-5.5/2 50 340 120 126 136 182 360 50 130 279 628 180 M10 20 – 182 340 100 168

50/170-7.5/2 50 340 120 126 136 182 360 50 130 279 628 180 M10 20 – 182 340 100 189

50/180-7.5/2 50 440 120 145 148 – 500 50 200 279 650 220 M10 20 188 – 400 100 197

50/200-11/2 50 440 120 145 148 – 500 50 200 323 773 220 M10 20 250 – 400 100 255

50/220-11/2 50 440 120 145 148 – 500 50 200 323 773 220 M10 20 250 – 400 100 255

50/220-15/2 50 440 120 145 148 – 500 50 200 323 773 220 M10 20 250 – 400 100 278

Page 192: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

192 Subject to change 09/2008 WILO SE

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-CronoTwin-DL

65/110-3/2 65 340 120 121 130 156 400 50 150 217 514 170 M12 20 – 156 340 110 129

65/120-3/2 65 340 120 121 130 156 400 50 150 217 514 170 M12 20 – 156 340 110 129

65/120-4/2 65 340 120 121 130 168 400 50 150 232 592 170 M12 20 – 168 340 110 143

65/130-5.5/2 65 340 120 121 130 – 400 50 150 279 644 170 M12 20 188 – 340 110 166

65/140-5.5/2 65 340 120 121 130 – 400 50 150 279 644 170 M12 20 188 – 340 110 166

65/140-7.5/2 65 340 120 121 130 – 400 50 150 279 644 170 M12 20 188 – 340 110 182

65/150-5.5/2 65 430 153 134 144 182 440 55 185 279 647 215 M12 20 – 182 400 120 188

65/160-5.5/2 65 430 153 134 144 182 440 55 185 279 647 215 M12 20 – 182 400 120 189

65/160-7.5/2 65 430 153 134 144 182 440 55 185 279 647 215 M12 20 – 182 400 120 207

65/170-11/2 65 430 153 134 144 – 440 55 185 323 778 215 M12 20 250 – 400 120 257

65/200-11/2 65 475 140 157 166 – 520 45 210 323 783 245 M12 20 250 – 400 110 267

65/200-15/2 65 475 140 157 166 – 520 45 210 323 783 245 M12 20 250 – 400 110 289

65/210-15/2 65 475 140 157 166 – 520 45 210 323 783 245 M12 20 250 – 400 110 289

65/210-18.5/2 65 475 140 157 166 – 520 45 210 370 826 245 M12 20 250 – 400 110 315

65/220-18.5/2 65 475 140 157 166 – 520 45 210 370 826 245 M12 20 250 – 400 110 315

65/220-22/2 65 475 140 157 166 – 520 45 210 370 868 245 M12 20 294 – 400 110 360

80/120-4/2 80 400 155 134 146 168 400 62 178 232 600 200 M12 20 – 168 350 120 157

80/130-5.5/2 80 400 155 134 146 – 400 62 178 279 652 200 M12 20 188 – 350 120 180

80/140-7.5/2 80 400 155 134 146 – 400 62 178 279 652 200 M12 20 188 – 350 120 196

80/150-7.5/2 80 440 155 144 160 182 440 62 188 279 651 220 M12 20 – 182 400 120 218

80/160-11/2 80 440 155 144 160 – 440 62 188 323 783 220 M12 20 250 – 400 120 267

80/170-11/2 80 440 155 144 160 – 440 62 188 323 783 220 M12 20 250 – 400 120 267

80/170-15/2 80 440 155 144 160 – 440 62 188 323 783 220 M12 20 250 – 400 120 294

80/190-15/2 80 500 145 166 176 – 550 72 228 323 787 250 M12 20 250 – 450 120 307

80/190-18.5/2 80 500 145 166 176 – 550 72 228 370 830 250 M12 20 250 – 450 120 333

80/200-18.5/2 80 500 145 166 176 – 550 72 228 370 830 250 M12 20 250 – 450 120 333

80/200-22/2 80 500 145 166 176 – 550 72 228 370 872 250 M12 20 294 – 450 120 378

80/220-30/2 80 500 145 166 176 – 550 72 228 415 960 250 M12 20 306 – 450 120 489

100/145-11/2 100 500 180 173 188 – 580 80 250 323 796 226 M12 20 250 – 440 135 289

100/150-15/2 100 500 180 173 188 – 580 80 250 323 796 226 M12 20 250 – 440 135 315

100/160-15/2 100 500 180 173 188 – 580 80 250 323 796 226 M12 20 250 – 440 135 315

100/160-18.5/2 100 500 180 173 188 – 580 80 250 370 839 226 M12 20 250 – 440 135 350

100/165-22/2 100 500 180 173 188 – 580 80 250 370 881 226 M12 20 294 – 440 135 379

100/170-30/2 100 500 180 173 188 – 580 80 250 415 969 226 M12 20 306 – 440 135 490

100/190-30/2 100 550 155 183 197 – 560 79 251 415 969 275 M12 20 306 – 450 120 507

100/210-30/2 100 550 155 183 197 – 560 79 251 415 969 275 M12 20 306 – 450 120 507

100/210-37/2 100 550 155 183 197 – 560 79 251 415 969 275 M12 20 306 – 450 120 553

Dimensions, weights (2900 rpm)

Wilo-CronoTwin-DL ...

Nomi-nal

flange diame-ter

Over-all

lengthDimensions Weight

approx.

DN l0 A b1 b2 b3 c e f Ø g l1max m o p p1 q s x M

– [mm] – [mm] [kg]

Page 193: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

193

Standard pumpsDouble pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-CronoTwin-DL

Standard

pum

ps

Flange dimensions

Wilo-CronoTwin-DL ...

Nominal flange diameter Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

32... 32 140 76 100 4 x 19

40... 40 150 84 110 4 x 19

50... 50 165 99 125 4 x 19

65... 65 185 118 145 4 x 19

80... 80 200 132 160 8 x 19

100... 100 220 156 180 8 x 19

125... 125 250 184 210 8 x 19

150... 150 285 211 240 8 x 23

200... 200 340 266 295 12 x 23

Pump flange dimensions - according to EN 1092-2 PN 16, n = number of drilled holes

Page 194: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

194 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Series overview

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroLine-IPS

>DesignGlanded pump in in-line design with screwed connection or flange connection

>ApplicationFor pumping cold and hot water (in accord-ance with VDI 2035) without abrasive sub-stances in heating, cold water and cooling water systems

Series: Wilo-VeroLine-IPH-O

>DesignGlanded pump in in-line design with flange connection

>ApplicationFor pumping heat transfer oil in closed in-dustrial circulation systems

3

4

2

1

00 4 8 12 16 20

Wilo-VeroLine-IPs

IPs 50IPs 40

IPs 25H

[m]

Q[m³/h]

0 10 20 30 40 50 60

25

15

20

30

10

5

0

32/170/-2,2/2

65/140-4/2

65/125-2,2/2

80/140-4/2

65/110-2,2/2

80/110-2,2/2

H[m

]

Q[m³/h]

Wilo-VeroLine-IPH-O/-Wn = 2900 1/min

65/160-4/2

32/125-0,75/2

20/160-1,1/2

0 10 20 30 40

1

2

0

4

5

3

7

8

6

20/160-0,37/4

80/160-1,1/4

80/140-1,1/4

65/160-1,1/4

65/125-1,1/4

32/170-0,37/4

32/125-0,18/4

65/140-1,1/4

H[m

]

Q[m³/h]

Wilo-VeroLine-IPH-O/-Wn = 1450 1/min

Page 195: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

195

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series overview

Special in-line pumps

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroLine-IPS

> Special features/product benefits• Worldwide availability of the standard motors used

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . .

Page7198200201202

248

Series: Wilo-VeroLine-IPH-O

> Special features/product benefits• Bidirectional, self-cooled mechanical seal• Large range of applications due to wide fluid temperature range from -10°C to +350°C and operating pressure range up to 9 bar without additional wearing parts

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . .

Page7198204206208

248

Page 196: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

196 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Series overview

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroLine-IPH-W

>DesignGlanded pump in in-line design with flange connection

>ApplicationFor pumping hot water without abrasive matter in closed industrial circulation sys-tems, district heating, closed heating sys-tems, etc.

Series: Wilo-VeroLine-IP-Z

>DesignGlanded circulation pump in in-line design with threaded connection

>ApplicationFor pumping potable water, cold and hot water (in accordance with VDI 2035) with-out abrasive substances, in heating, cold water and cooling water systems

0 10 20 30 40 50 60

25

15

20

30

10

5

0

32/170/-2,2/2

65/140-4/2

65/125-2,2/2

80/140-4/2

65/110-2,2/2

80/110-2,2/2

H[m

]

Q[m³/h]

Wilo-VeroLine-IPH-O/-Wn = 2900 1/min

65/160-4/2

32/125-0,75/2

20/160-1,1/2

0 10 20 30 40

1

2

0

4

5

3

7

8

6

20/160-0,37/4

80/160-1,1/4

80/140-1,1/4

65/160-1,1/4

65/125-1,1/4

32/170-0,37/4

32/125-0,18/4

65/140-1,1/4

H[m

]

Q[m³/h]

Wilo-VeroLine-IPH-O/-Wn = 1450 1/min

0

1

0 1 2 3 4 5

2

3

4

5

Wilo-VeroLine-IP-Z

IP-Z 25/6IP-Z 25/2

H[m

]

Q[m³/h]

Page 197: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

197

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series overview

Special in-line pumps

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series: Wilo-VeroLine-IPH-W

> Special features/product benefits• Bidirectional, self-cooled mechanical seal• Large range of applications due to wide fluid temperature range from -10 °C to +210°C and operating pressure range up to 23 bar without additional wearing parts

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . .

Page7198205206208209

Series: Wilo-VeroLine-IP-Z

> Special features/product benefits• High resistance to corrosive media, due to stainless steel housing and Noryl impeller• Wide range of applications due to suitability for water with hardness values up to 28°dH• All plastic parts that come into contact with the fluid fulfil KTW recommendations

> More information• Planning guide . . . . . . . . . . . . . . . . . . . • Technical data . . . . . . . . . . . . . . . . . . . • Series description . . . . . . . . . . . . . . . . • Pump curves . . . . . . . . . . . . . . . . . . . . . • Terminal diagrams, motor data . . . . • Dimensions, weights . . . . . . . . . . . . . • Switchgears and control devices . . .

Page7198211213214215216

Page 198: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

198 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Technical dataSpecial in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Technical data Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo- Vero-Line-IPS 25

Wilo- Vero-Line-IPS 40

Wilo- Vero-Line-IPS 50

Wilo- Vero-Line-IPH-O

Wilo- Vero-Line-IPH-W

Wilo- Vero-Line-IP-Z

Approved fluids (other fluids on request)

Heating water (in accordance with VDI 2035) • • • • • •

Water-glycol mixtures (for 20-40 vol.% glycol and fluid temperature � 40 °C) • • • • – •

Cooling and cold water • • • • • •

Hot water – – – – • –

Heat transfer oil Special version at additional charge up to +350 °C –

Potable water and water for food-processing com-panies in accordance with TrinkwV 2001 (drinking water ordinance)

– – – – – •

Permitted field of application

Standard version for operating pressure, pmax [bar] 10 (up to +120°C)8 (up to +140°C)

6 (up to +120°C)5 (up to +140°C)

9 (heat trans-fer oil)

23 (hot wa-ter) 10

Temperature range [°C] -10 to +140 -10 to +350 -10 to +210 -8 to +110

Max. ambient temperature [°C] 40

Installation in closed buildings • • • • • •

Outdoor installation Special version at additional charge

Pipe connections

Threaded connection R1 – – – – G11/2

Flange connection (counter flanges, seals and screws included in the scope of delivery) – • • • • –

Flange versionPN10

PN6 PN16 on request (in accord-ance with DIN EN 1092-2)

n PN10

Nominal connection diameters DN – 40 50 20 - 80 20 - 80 –

Flange with pressure-measurement connections – R 1/8 R 1/8 – – –

Materials

Pump housing EN-GJL-200 1.0625 1.4306

Lantern EN-GJL-200 EN-GJS-400-15 1.4306

Impeller (standard) PP, fibreglass-reinforced EN-GJL-250 Noryl

Pump shaft 1.4021/1.4122 1.4005 1.4571

Mechanical sealBVEGG AQ1VGG AQ1EGG

Ceramic/graphite/EP-

DM

Other mechanical seals On request

Page 199: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

199

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Technical data

Special in-line pumps

Electrical connection

Mains connection

3~400 V, 50 Hz

1~230 V, 50 Hz

3~400 V, 50 Hz

Speed range [rpm] 1450 1450/2900

Motor/electronics

Integrated full motor protection Special version with PTC thermistor sensor (TRS) at additional charge –

Protection class IP 55 IP 55 IP 55 IP 55 IP 55 IP 44

Terminal box protection class IP 54

Insulation class F F F F F F

Motor protection required onsite • • • • • •Speed control Wilo-Control system –

Motor winding up to 3 kW 230 V �/400 V Y, 50 Hz

Motor winding from 4 kW– 230 V �/400

V Y, 50 Hz –

Installation options

Pipe installation (� 15 kW motor power)• •

with horizontal shaft only•

Support-bracket mounting – – – – – –

• = available, - = not available

Wilo- Vero-Line-IPS 25

Wilo- Vero-Line-IPS 40

Wilo- Vero-Line-IPS 50

Wilo- Vero-Line-IPH-O

Wilo- Vero-Line-IPH-W

Wilo- Vero-Line-IP-Z

Page 200: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

200 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-VeroLine-IPS

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroLine-IPS Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignGlanded pump in in-line design with screwed connection or flange connection

ApplicationFor pumping cold and hot water (in accordance with VDI 2035) with-out abrasive substances in heating, cold water and cooling water sys-tems

Scope of delivery• Pump• Installation and operating instructions

Type key

Technical data• Permissible temperature range -10°C to +140°C• Mains connection 3~400 V, 50 Hz• Protection class IP 55• Nominal diameter Rp 1, DN 40 and DN 50• Max. operating pressure, 10 bar or 6 bar for flange connection.

Special features/product benefits• Worldwide availability of the standard motors used

Materials• Pump housing and lantern: EN-GJL-200• Impeller: Plastic• Shaft: 1.4021• Mechanical seal: BVEGG; other mechanical seals on request

Description/designSingle-stage, low-pressure centrifugal pump in in-line design with

• Mechanical seal or stuffing box

• Threaded or flange connection with pressure measuring connection R 1/8

• Standard motor

Example IPS 40 GRD

IPS In-line pump

40 Nominal diameter DN of the pipe connection

GRD Mechanical seal

Page 201: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

201

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroLine-IPS

Special in-line pumps

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-VeroLine-IPS Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IPS 25

Speed 1450 rpm

Wilo-VeroLine-IPS 40

Speed 1450 rpm

Wilo-VeroLine-IPS 50

Speed 1450 rpm

NPS

H[m

]

NPS

H[m

]

NPS

H[m

]

Page 202: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

202 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Terminal diagram, motor data Wilo-VeroLine-IPS

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-VeroLine-IPS Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram

L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1

Mains 3~400 V, 50 Hz

3~230 V, 50 Hz �

(dashed line)

Motor data

Wilo-VeroLine-IPS ... Nominal motor power Nominal current (approx.)

P2 IN 3~400 V IN 3~230 V

[kW] [A]

25 0.12 0.45 0.78

40 0.18 0.60 1.04

50 0.25 0.75 1.30

Observe motor name plate data

Page 203: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

203

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-VeroLine-IPS

Special in-line pumps

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-VeroLine-IPS Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing A

II) Ventilation

Dimension drawing B

I) Pressure measuring connection R1/8II) Ventilation

DDimensions, weights

Wilo-VeroLine-IPS ... Nominal flange diam-

eter

Screwed con-nection

Overall length Dimensions Weight ap-prox.

Dimension drawing

DN Rp l0 A l1 l2 M –

– [mm] [kg] –

25 – 1 180 35 300 234 12 A

40 40 – 250 53 305 – 20 B

50 50 – 280 62 340 – 23 B

Flange dimensions PN6 (DIN EN 1092-2)

Wilo-VeroLine-IPS ... Nominal flange diame-ter

Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

40 40 130 80 100 4 x 14

50 50 140 90 110 4 x 14

n = number of drilled holes

Flange dimensions PN 16 on request (DIN EN 1092-2)

Wilo-VeroLine-IPS ... Nominal flange diame-ter

Pump flange dimensions

DN Ø D Ø d Ø k n x Ø dL

– [mm] [pcs. x mm]

40 40 150 88 110 4 x 19

50 50 165 102 125 4 x 19

n = number of drilled holes

Page 204: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

204 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Series description Wilo-VeroLine-IPH-O

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroLine-IPH-O Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignGlanded pump in in-line design with flange connection

ApplicationFor pumping heat transfer oil in closed industrial circulation systems

Scope of delivery• Pump• Installation and operating instructions

Type key

Technical data• Permissible temperature range -10°C to +350°C at max. 9 bar• Mains connection 3~400 V, 50 Hz• Protection class IP 55• Nominal diameter DN 20 to DN 80

Special features/product benefits• Bidirectional, self-cooled mechanical seal• Large range of applications due to wide fluid temperature range from -10°C to +350°C and operating pressure range up to 9 bar without additional wearing parts

Materials• Pump housing: Cast steel 1.0625 • Lantern: EN-GJS-400-15• Impeller: EN-GJL-250• Shaft: Stainless steel 1.4005• Mechanical seal: AQ1VGG; other mechanical seals on request

Description/designSingle-stage, low-pressure centrifugal pump in in-line design with

• Mechanical seal • Flange connection• Lantern• Motor with special shaft

Example IPH-O 65/125-1.1/4

IPH-O In-line pump for heat transfer oil

65 Nominal diameter DN of the pipe connection

125 Impeller diameter

1.1 Nominal motor power P2 in kW

4 Number of poles

Page 205: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

205

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-VeroLine-IPH-W

Special in-line pumps

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Series description Wilo-VeroLine-IPH-W Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignGlanded pump in in-line design with flange connection

ApplicationFor pumping hot water without abrasive matter in closed industrial circulation systems, district heating, closed heating systems, etc.

Scope of delivery• Pump• Installation and operating instructions

Type key

Technical data• Permissible temperature range -10°C to +210°C at max. 23 bar• Mains connection 3~400 V, 50 Hz• Protection class IP 55• Nominal diameter DN 20 to DN 80

Special features/product benefits• Bidirectional, self-cooled mechanical seal• Large range of applications due to wide fluid temperature range from -10 °C to +210°C and operating pressure range up to 23 bar without additional wearing parts

Materials• Pump housing: Cast steel 1.0625• Lantern: EN-GJS-400-15• Impeller: EN-GJL-250• Shaft: Stainless steel 1.4005• Mechanical seal: AQ1EGG; other mechanical seals on request

Description/designSingle-stage, low-pressure centrifugal pump in in-line design with

• Mechanical seal • Flange connection• Lantern• Motor with special shaft

Example IPH-W 65/125-1.1/4

IPH-W In-line pump for hot water applications

65 Nominal diameter DN of the pipe connection

125 Impeller diameter

1.1 Nominal motor power P2 in kW

4 Number of poles

Page 206: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

206 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Pump curves Wilo-Veroline-IPH-O/-W

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-Veroline-IPH-O/-W Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IPH-O/-W 20/160-0,37/4

Speed 1450 rpm

Wilo-VeroLine-IPH-O/-W 32/125-0,18/4 - 32/170-0,37/4

Speed 1450 rpm

Wilo-VeroLine-IPH-O/-W 65/125-1,1/4 - 65/160-1,1/4

Speed 1450 rpm

Wilo-VeroLine-IPH-O/-W 80/140-1,1/4 - 80/160-1,1/4

Speed 1450 rpm

[m /h]30

2

4

8

6

10

[lgpm]

[l/s]

0 4 52 3

H [

m]

3

5

9

7

1

0 0,2 0,4 0,6 0,8 1,0 1,2 1,40 0,3 0,40,1 0,2

Wilo-VeroLineIPH-O / IPH-W 20/160-0,37/4

0

0,1

0,2

0,3

P2

[ k

W ]

Q

[m /h]3

NPS

H [m

]

Ø 160

20/160 – 0,37/4

NPSH

1

[m/s]

v

0 0,5 0,750,25 1,0 1,25

0 0,2 0,4 0,6 0,8 1,0 1,2 1,4

0

2

4

3

1

[m /h]3

0

0,1

0,2

0,3

0,4

10

9

8

7

6

5

4

3

2

1

0

[lgpm]

[l/s]

0 10 20 30

P2

[ k

W ]

Q

H [

m]

[m/s]

v

00 1 2 3 4 5 6 7 8 9

0,5 1,0 1,5 2,0 2,5

0 0,5 1,0 1,5 2,0 2,5 3,0

[m /h]30 1 2 3 4 5 6 7 8 9

Wilo-VeroLine

IPH-O / IPH-W 32/170-32/125

3,5

4

0

8

32/170 – 0,37/4

32/125 – 0,18/4

Ø 125

Ø 170

NPS

H [m

]

Ø 170

[m /h]3

0

0,4

0,3

0,1

0,2

0,6

0,5

9

8

7

6

5

4

3

2

1

0

[lgpm]

[l/s]

0 20 40 60 80 100 120Q

H [

m]

[m/s]

v

0 2 4 6 8 10

0 0,5 1,0 1,5 2,0 2,5

0 5 10 15 20 25 30 35

[m /h]3

P2

[ k

W ]

Wilo-VeroLine

IPH-O / IPH-W 65/160-65/125

65/125 – 1,1/4

65/140 – 1,1/4

65/160 – 1,1/4

Ø 140

Ø 160

Ø 125

0

4

NPS

H [m

]

2

0 5 10 15 20 25 30 35

Ø 160

[m /h]30

0

0,4

0,6

0,2

1,0

0,8

1

2

3

4

5

6

7

8

[lgpm]

[l/s]

0 40 120 16080Q

H [

m]

[m/s]

v

0 102 124 6 8 14

0 0,5 1,0 1,5 2,0

0 10 20 30 40

0 10 20 30 40 [m /h]3

P2

[ k

W ]

Wilo-VeroLine

IPH-O / IPH-W 80/160-80/140

80/140 – 1,1/4

NPSH

80/160 – 1,1/4

Ø 140

Ø 160

0

8

4

2,5

NPS

H [m

]

Page 207: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

207

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-Veroline-IPH-O/-W

Special in-line pumps

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Pump curves Wilo-Veroline-IPH-O/-W Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IPH-O/-W 20/160-1,1/2

Speed 2900 rpm

Wilo-VeroLine-IPH-O/-W 32/125-0,75/2 - 32/170-2,2/2

Speed 2900 rpm

Wilo-VeroLine-IPH-O/-W 65/110-2,2/2 - 65/160-4/2

Speed 2900 rpm

Wilo-VeroLine-IPH-O/-W 80/110-2,2/2 - 80/140-4/2

Speed 2900 rpm

[m /h]30

10 10

024

86

20

40

30

50

[lgpm]

[l/s]

0 2 4 6 8 10

H [

m]

15

25

45

35

5

0 0,5 1,0 1,5 2,0 2,5 3,00 0,20,1 0,40,3 0,60,5 0,7 0,8

NPS

H [m

]

Wilo-VeroLineIPH-O / IPH-W

20/160-1,1/2

20/160 – 1,1/2

NPSH

0

0,5

1,0

P2

[ k

W ]

Q

[m /h]3

Ø 160

[m/s]

v

0 0,5 1,0 1,5 2,0 2,5

0 0,5 1,0 1,5 2,0 2,5 3,0

[m /h]3

0

0,5

1,0

1,5

2,0

2,5

40

36

32

28

24

20

16

12

8

4

0

[lgpm]

[l/s]

0 10 20 30 40 50 60Q

H [

m]

[m/s]

v

0 2 4 6 8 10 12 140 1 2 3 4 5

0 1 2 3 4 5 6 7

[m /h]3

P2

[ k

W ]

Wilo-VeroLine

IPH-O / IPH-W 32/170 – 32/125

0 2 4 6 8 10 12 14

32/170 – 2,2/2

32/125 – 0,75/2

Ø 170

Ø 125

5

0

10

NPS

H [m

]

Ø 170

[m /h]3

0

3

1

2

4

32

28

24

20

16

12

8

4

0

[lgpm]

[l/s]

0 40 80 120 160 200Q

H [

m]

[m/s]

v

0 10 20 30 40 50 600 2 4 6 8 10 12 14 16 20

0 1 2 3 4

[m /h]3

P2

[ k

W ]

0 10 20 30 40 50 60

65/110 – 2,2/2

65/125 – 2,2/2

65/140 – 4/2

65/160 – 4/2

Ø 140

Ø 160

Ø 160

Ø 110

Ø 125

0

4

8

NPS

H [m

]

Wilo-VeroLine

IPH-O / IPH-W 65/160 – 65/110

[m /h]3

0

1

3

2

4

22

20

18

16

14

12

10

8

6

4

2

0

[lgpm]

[l/s]

0 40 80 120 160 240200Q

H [

m]

[m/s]

v

00 4 8 12 2016

0 1 2 3 4

10 20 30 40 50 60

[m /h]3

70

0 10 20 30 40 50 60 70

P2

[ k

W ]

Ø 140

Ø 110

8

0

4

80/140 – 4/2

Wilo-VeroLine

IPH-O / IPH-W 80/140-80/110

NPS

H [m

]

Ø 140

80/110 – 2,2/2

Page 208: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

208 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Terminal diagram, motor data Wilo-VeroLine-IPH-O/-W

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Terminal diagram, motor data Wilo-VeroLine-IPH-O/-W Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagramsStar switching Y Delta switching �

Motor protection switch required onsite. Check the direction of rota-tion.To change the direction of rotation, swap any two phases.P2 � 3 kW 3~400 V Y

3~230 V �P2 4 kW 3~690 V Y

3~400 V �After removing the bridges, Y-� starting is possible.

L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1 L 2 L3

U1 V1 W1

W2 U2 V2

PEL 1

MMotor data (1450 rpm)

Wilo-VeroLine-IPH-O/-W...

Nominal motor power Nominal current Power factor Efficiency

P2 IN3~400 V cos� �M

[kW] [A] –

20/160-0.37/4 0.37 1.12 0.70 72.00

32/125-0.18/4 0.18 0.62 0.65 62.00

32/170-0.37/4 0.37 1.12 0.70 72.00

65/125-1.1/4 1.10 2.70 0.84 76.80

65/140-1.1/4 1.10 2.70 0.84 76.80

65/160-1.1/4 1.10 2.70 0.84 76.80

80/140-1.1/4 1.10 2.70 0.84 76.80

80/160-1.1/4 1.10 2.70 0.84 76.80

Observe motor name plate data

Motor data (2900 rpm)

Wilo-VeroLine-IPH-O/-W...

Nominal motor power Nominal current Power factor Efficiency

P2 IN3~400 V cos� �M

[kW] [A] –

20/160-1.1/2 1.10 2.60 0.84 78.00

32/125-0.75/2 0.75 1.90 0.87 76.00

32/170-2.2/2 2.20 4.40 0.88 83.60

65/110-2.2/2 2.20 4.40 0.88 83.60

65/125-2.2/2 2.20 4.40 0.88 83.60

65/140-4/2 4.00 8.20 0.85 86.00

65/160-4/2 4.00 8.20 0.85 86.00

80/110-2.2/2 2.20 4.40 0.88 83.60

80/140-4/2 4.00 8.20 0.85 86.00

Observe motor name plate data

Page 209: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

209

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-VeroLine-IPH-O/-W

Special in-line pumps

Special in-line pumps Single pumps (heating, air-conditioning, cooling and industry) Dimensions, weights Wilo-VeroLine-IPH-O/-W Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing

L1 x b1 b2

n x Ø dL

Ø k

DN v2 v4

Ø D

4mm

H1

H

Dimensions, weights (1450 rpm)

Wilo-VeroLine-IPH-O/-W...

Nominal flange diam-

eter

Dimensions Weight ap-prox.

DN b1 b2 H H1 L1 X M

– [mm] [kg]

20/160-0.37/4 20 105 105 290 145 385 300 28

32/125-0.18/4 32 90 87 260 130 370 300 23

32/170-0.37/4 32 110 115 260 130 395 300 30

65/125-1.1/4 65 110 110 370 170 440 300 39

65/140-1.1/4 65 121 107 400 190 440 300 39

65/160-1.1/4 65 121 107 400 190 440 300 39

80/140-1.1/4 80 150 123 430 205 445 300 41

80/160-1.1/4 80 150 123 430 205 445 300 54

Dimensions, weights (2900 rpm)

Wilo-VeroLine-IPH-O/-W...

Nominal flange diam-

eter

Dimensions Weight ap-prox.

DN b1 b2 H H1 L1 X M

– [mm] [kg]

20/160-1.1/2 20 105 105 290 145 417 300 31

32/125-0.75/2 32 90 87 260 130 402 300 26

32/170-2.2/2 32 110 115 260 130 477 300 41

65/110-2.2/2 65 110 110 370 170 467 300 43

65/125-2.2/2 65 110 110 370 170 467 300 43

65/140-4/2 65 121 107 400 190 503 300 61

65/160-4/2 65 121 107 400 190 503 300 61

80/110-2.2/2 80 133 106 400 190 472 300 51

Page 210: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

210 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (heating, air-conditioning, cooling and industry)

Dimensions, weights Wilo-VeroLine-IPH-O/-W

80/140-4/2 80 150 123 430 205 507 300 69

Dimensions, weights (2900 rpm)

Wilo-VeroLine-IPH-O/-W...

Nominal flange diam-

eter

Dimensions Weight ap-prox.

DN b1 b2 H H1 L1 X M

– [mm] [kg]

Flange dimensions

Wilo-VeroLine-IPH-O/-W...

Nominal flange di-ameter

D V2 V4 C Pump flange di-mensions

DN L n x Ø dL

– [mm] [pcs. x mm]

20... 20 105 35 51 75 4 x 14

32... 32 140 50 66 100 4 x 18

65... 65 185 94 110 145 8 x 18

80... 80 200 105 121 160 8 x 18

Pump flange dimensions - according to DIN 2545 PN 25; n = number of drilled holes

Page 211: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

211

Special in-line pumpsSingle pumps (secondary hot water circulation)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-VeroLine-IP-Z

Special in-line pumps

Special in-line pumps Single pumps (secondary hot water circulation) Series description Wilo-VeroLine-IP-Z Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

DesignGlanded circulation pump in in-line design with threaded connection

ApplicationFor pumping potable water, cold and hot water (in accordance with VDI 2035) without abrasive substances, in heating, cold water and cooling water systems

Scope of delivery• Pump• Installation and operating instructions

Type key

Technical data• Permissible temperature range- Potable water up to 28 °dH: max. +65 °C, In short-term operation

(2 h) up to +110 °C-Heating water: -8 °C to +110 °C

• Mains connection 1~230 V, 50 Hz 3~400 V, 50 Hz• Protection class IP 44 motor, IP 54 terminal box• Nominal diameter Rp 1• Max. operating pressure 10 bar

Special features/product benefits• High resistance to corrosive media, due to stainless steel housing and

Noryl impeller• Wide range of applications due to suitability for water with hardness

values up to 28°dH• All plastic parts that come into contact with the fluid fulfil KTW rec-ommendations

Materials• Pump housing and lantern: 1.4306• Impeller: Noryl• Shaft: 1.4571• Mechanical seal: Ceramic/graphite/EPDM

Description/designSingle-stage, low-pressure centrifugal pump in in-line design with

• Mechanical seal • Threaded connection• Motor with one-piece shaft

Example Wilo-Veroline-IP-Z 25/6

IP In-line pump (screw-end pump)

-Z Circulation pump

25/ Nominal connection diameter R/Rp

6 Power capacity in approximation to the maximum delivery head [m]

Page 212: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

212 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (secondary hot water circulation)

Series description Wilo-VeroLine-IP-Z

Special in-line pumps Single pumps (secondary hot water circulation) Series description Wilo-VeroLine-IP-Z Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-Veroline-IP-Z

Q[m³/h]0,1 0,2 0,3 0,4 0,5 0,6 0,8 1,0 2,0 3,0 4,0

H[m]

0

0,5

1,0

1,5

2,0

2,5

3,0

3,5

4,0

4,5

25/625/2

Page 213: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

213

Special in-line pumpsSingle pumps (secondary hot water circulation)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump curves Wilo-VeroLine-IP-Z

Special in-line pumps

Special in-line pumps Single pumps (secondary hot water circulation) Pump curves Wilo-VeroLine-IP-Z Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-VeroLine-IP-Z 25/2 - 25/6

0 1 2 3 v

Q [lgpm]

[l/s]

0

0 0

0,5 1 2 3 4 5 6

5 10 15 20

0,5 1

0

2

1

3

4

5

6

H[m

]

[m/h]

[m3/h]

Wilo-VeroLine-IP-Z 25/2Wilo-VeroLine-IP-Z 25/6

IP-Z 25/2

IP-Z 25/6

Page 214: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

214 Subject to change 09/2008 WILO SE

Special in-line pumpsSingle pumps (secondary hot water circulation)

Terminal diagram, motor data Wilo-VeroLine-IP-Z

Special in-line pumps Single pumps (secondary hot water circulation) Terminal diagram, motor data Wilo-VeroLine-IP-Z Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram A

Single-phase motor 1~230 V, 50 Hz

With attached capacitor

Terminal diagram B

Three-phase motor 3~230/400 V, 50 Hz

continuous line = Ydashed line = �3~400 V Y3~230 V �

L

L1

N

N PE

C1C2

C

L1 L2 L3 PE

W2 U2 V2

U1 V1 W1

Motor data

Wilo-VeroLine-IP-Z ... Mains con-nection

Nominal mo-tor power

Nominal current approx. Nominal cur-rent

Capacity Speed Wiring diagram

– P2 IN1~230 V IN3~230 V IN3~400 V C V –

– [kW] [A] [�F] [rpm] –

25/2 1~230 V 0.1 1.1 – – 4.0 1450 A

25/2 3~400 V 0.09 – 0.5 0.29 – 1460 B

25/6 1~230 V 0.18 1.15 – – 8.0 2750 A

25/6 3~400 V 0.12 – 0.66 0.38 – 2750 B

Observe motor name plate data

Page 215: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

215

Special in-line pumpsSingle pumps (secondary hot water circulation)

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-VeroLine-IP-Z

Special in-line pumps

Special in-line pumps Single pumps (secondary hot water circulation) Dimensions, weights Wilo-VeroLine-IP-Z Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimension drawing A

1~230 V

Dimension drawing B

3~230/400 V

L1

x

H 250

125 90

L4L3

G1½

L2

L

115 H2

G1½ x G2

L1

L2

L

x115 H2

H 250

125 90

L4L4

G1½ x G2

G1½

Dimensions, weights

Wilo-VeroLine-IP-Z ... Mains connec-tion

Nominal flange diame-ter

Dimensions Weight approx.

Dimen-sion

drawing

– DN H H2 L L1 L2 L3 L4 X M –

– [mm] [kg] –

25/2 1~230 V 25 180 148 241 213 136 82 58 92 5.5 A

25/2 3~400 V 25 180 148 241 213 136 – 58 92 4.5 B

25/6 1~230 V 25 180 148 241 213 136 82 58 92 5.5 A

25/6 3~400 V 25 180 148 241 213 136 – 58 92 4.5 B

Page 216: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

216 Subject to change 09/2008 WILO SE

Switchgears and control devicesPlug-in modules, switchgears, motor protection, accessories

Series overview

Switchgears and control devices Plug-in modules, switchgears, motor protection, accessories Series overview Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Control device: Vario control system Wilo-VR-HVAC

>Control device for glandless and glanded pumps(electronically regulated stageless pumps and/or pumps with integrated frequency converter)

• Variable-control system for stageless performance control of pumps of the TOP-E/-ED, Stratos/-D/-Z/-ZD, IP-E/DP-E, IL-E/DL-E, IL-E…BF series

• For the control modes � p-c and � p-v in heating and air-conditioning technology• Pump performance splitting with up to 4 units• Nominal power up to P2 = 22 kW• Speed range between 100 % and 40 %• Includes full motor protection device

Control device: Comfort control system Wilo-CRn

>Control device for glandless and glanded pumps(electronically regulated stageless pumps and/or pumps with integrated frequency converter)

• Comfort-control system for stageless power control of pumps of the series Stratos/-D/-Z/-ZD, IP-E/DP-E, IL-E/DL-E, IL-E...BF

• For all control modes in heating and air-conditioning technology• Pump performance splitting with up to 6 units• Nominal power up to P2 = 22 kW• Speed range between 100 % and 40 %

Control device: Wilo-CC-HVAC System

>Switchgear for glandless and glanded pumps (Standard pumps with fixed speed)

• Comfort control system for continuous performance control of conventional circulation pumps with three-phase motor

• For all control modes in heating and air-conditioning technology• Pump duty splitting with up to 6 units (more units on request)• Nominal power up to P2 = 200 kW (higher power on request)• Speed range between 100 % and 40 %• Incl. motor protection device

Control device: Comfort control system Wilo-CR

>Control device for glandless and glanded pumps(Standard pumps with fixed speeds)

• Comfort control system for stageless performance control of commercially available circula-tion pumps with a three-phase AC motor

• Suitable for all control modes used in heating, air-conditioning and pressure boosting• Pump performance splitting with up to 6 units• Nominal power to P2 = 30 kW (to P2 = 200 kW on request)• Speed range between 100 % and 40 %• Includes full motor protection device

Page 217: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

217

Switchgears and control devicesPlanning guide

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Pump performance control

Switc

hgears

and

control

devices

Pump management

Switchgears and control devices Planning guide Pump performance control Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsPump performance controlLoad-specific excess pump performanceCirculation pumps for central heating and air-conditioning as well as the hydraulic pipe system must be designed to be capable to meet the maximum climatic requirements.These maximum load conditions, however, only exist on a few days during the heating/cooling season. A typical load curve for a central heating system is shown on the diagram. Centralised and decentral-ised control systems intervene continuously in the system's hydrau-lics in order to make adjustments to the actual load situation; in most cases, they cause a reduction of the volume flow while at the same time increasing the pump delivery head. Such operating states are not economical for pump operations, since lower delivery heads would in fact be sufficient, particularly for a low volume flow; in addi-tion, the noise levels that would result must be avoided under all cir-cumstances.

Fig.: Typical load factor of a central heating system during a heating period of roughly 5500 hours

Operating range Heating days

Load

fact

or

The Wilo solution: load-sensitive power adjustment

Control mode Pump type/pump model

Signal/control variable

Controlsystem

Integrated infinitely variable differential-pressure control

Stratos/Stratos-ZStar-E

Star-ZETOP-EIP-E/IL-E

�p Standard equipment

Time-dependent activation/deactivation– single pumps

TOP-Z t SK 601

Star-Z t S1R-h/SK 601

RS t SK 601

Double pump control

Stratos/Stratos-Z/Stratos-D/Stratos-ZD �p, t Stratos IF-Module

TOP-E/-ED �p, t IF-Module

IP-E/DP-E �p, t –

IL-E/DL-E �p, t IF-Module

Glandless and glanded pumps �p, +T, �T, t 3

Infinitely variable performance control– single- and multi-pump systems

Glandless and glanded pumps �p, ±T, �T, t, DDC CR system, CC system,

VR systemMotor protection Glandless pumps – SK 602/SK 622Building automation – – Wilo-Control�p= differential pressure ±T= feed/return temperature �T= differential temperature t = time

Page 218: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

218 Subject to change 09/2008 WILO SE

Switchgears and control devicesPlanning guide

Pump performance control

Switchgears and control devices Planning guide Pump performance control Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsNeed for controlDue to the constant further development of equipment for building services and the growing sensitivity towards energy consumption, three main factors were decisive for the use of controls for heating pumps in the past.

1. Optimisation of functionsAdjustment of the flow rate/heat volume flow to requirements, par-ticularly to stabilise hydraulic conditions and to reduce circulation losses.

2. Economic efficiencyReduction of the electricity consumption and operating costs, partic-ularly during partial or low-load operation (i.e. for more than 80% of the operating time).

3. ComfortAvoiding system noise, in particular flow noise and noise in the ther-mostatic valves.In the context of reducing CO2 emissions and environmental issues, saving electricity plays an ever more important role. It is widely known that generating power from fossil fuels produces significant levels of CO2 emissions. In Germany, engineers use the calculation principle that one kWh of electricity generated in a power station produces about 0.56 kg of CO2 in the form of emissions.The decisive factor for concentrating studies on pumps in particular is their proportionally high share of power consumption in the context of the energy balance of buildings. The causes for this are the high levels of operating hours as well as the familiar phenomenon of over-dimensioning heating pumps during the planning stage, factors which considerably add to the energy balance. Over-dimensioning by a factor of 2 to 5 times is quite frequent.

Pump performance control by speed variationOf the many methods developed and tried in the past to automatical-ly adjust the heating pump output to actual load demands, among them mechanical/hydraulic processes (bypass/throttling circuits etc.), the method of speed control has established itself on a lasting basis. Particularly high efficiency and easy handling have ensured the dominance of speed control, since ideally, the performance parame-ters volume flow, pressure difference and output directly relate to

changes of speed.

n1/n2 = Q1/Q2 (n1/n2 )2 = H1/H2 (n1/n2)3 = P1/P2

For example, when the speed is doubled, the volume flow is increased by a factor of two and the delivery head by a factor of 4 while the in-put power must be about 7 to 8 times greater.

Fig.: Pump curves of a pump during operation at different speeds

Single-family house Large building

Pumps account for 10 –15% of the overall power consumption, because...

Pumps account for 5 – 8% of the overall power consumption

- There are two to four pumps (heating/sec-ondary hot water circulation/accumulator charging, etc.), each pump with about 1500 h to 5000 h operating time per year (de-pending on the application), i.e. with three pumps on average:

- 3 x 65W x approx. 3500 a/h = approx. 700 kWh/a

- By comparison: average, statistical total power consumption for a single-family house = approx. 5000 to 8000 kWh

H (%)

1,2n1,1n

1,0n0,9n0,8n0,7n0,6n

144121

10081644936

1,2n

1,1n

1,0n

0,9n0,8n0,7n0,6n

173

133

10073513421

Q[m³/h]

Q[m³/h]

P (%)

Page 219: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

219

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Performance features

Switc

hgears

and

control

devices

Pump management

Switchgears and control devices Wilo-Vario and Comfort control systems VR, CRn, CR, CC Performance features Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo control device…

VR-HVAC CRn CC-HVAC CR

Applications

Pump versions Glandless/ glanded pumps Glandless/ glanded pumps Glandless/ glanded pumps Glandless/ glanded pumps

Pump typesElectronically controlled

pumpsStandard/

electronically controlled pumps

Standard pumps Standard pumps

Number of pumps 1–4 1–6 1–61) 1–6

Technical data

Complete device • Power supply for pumps required onsite • •

Modular design • • • •Nominal power range P2 0.37–22.0 kW 1.1–200 kW 1.1–200 kW2) 1.1–200 kW

Activation types: Infinitely variable, analo-gue

Infinitely variable, analogue/star-delta opt. direct/star-delta direct/star-delta

Electrical connection standard model

3~400 V, 50 Hz or

1~230 V, 50 Hz

1~230V, 50 HzPower connection of the

pumps onsite

3~400 V, 50 Hz 3~400 V, 50 Hz

Protection class IP 54 IP 00 + IP 42 standard /IP 54 optional IP 54 IP 00 + IP 42 standard/

IP 54 optional

Permitted ambient tempera-ture: 0°C to +40°C 0 °C to +40 °C 0 °C to +40 °C 0 °C to +40 °C

Speed range

Infinitely variable, analogue,

2–10 V, 3–10 V, 4–10 V pre-selectable,

Min. pump speedacc. to name plate up to

100 %

Between 40% and 100% of the nominal motor

speed

Between 40% and 100% of the nominal motor speed

Between 40% and 100% of the nominal motor

speed

Control modes(description on the following pages)

�p-c • • • •�p-c (TA) – • o •�p-q (m2/ h) – • o •�p-v • • • •TA (outside temperature), controller – • o •

T-abs (process temp.), controller – • o •

TF (feed temperature), controller – • o •

TR (return temperature), controller – • o •

�T-c – • o •�T-v – • o •Manual control mode (DDC) – • • •Q-c – • o •

• = available, – = not available, o = optional on request1) Larger number of pumps on request2) Higher nominal motor power values on request

Page 220: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

220 Subject to change 09/2008 WILO SE

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Performance features

Control and signalling functions

Remote speed adjustment (control input) – 0/4 - 20 mA

0/2 - 10 V0/4 - 20 mA (standard)

0/2 - 10 V (opt. on request)0/4 - 20 mA0/2 - 10 V

Remote setpoint adjustment – 0/4 - 20 mA0/2 - 10 V

0/4 - 20 mA (standard)0/2 - 10 V (opt. on re-

quest)

0/4 - 20 mA0/2 - 10 V

Run and fault signal visualisation • • • •

Control input "Setpoint switchover" – • • •

"Overriding Off" control input • • • •SBM • • • •SSM • • • •Fault-actuated switchover from frequency converter to mains operation

– – • •

Fault-actuated switchover from duty pump to standby pump

• • • •

Status display for pumps and frequency converters – • • •

Equipment features

Motor protection Integrated in pump WSK / SSM, integrated in pump

WSK / TS (PTC)/ TSA ETA / TS (PTC) / WSK

Graphic displayMenu navigation/ symbol

displayMenu navigation/ plain

text displayMenu navigation / plain

text display/symbol display

Menu navigation/ plain text display

User-oriented menunavigation with multilingual plain text display

– • • •

Manual control panel Manual /0 /Auto Manual /0 /Auto Manual /0 /Auto Manual /0 /Auto

Fault memory 9 messages 35 messages 35 messages 35 messages

Fault-actuated switchover • • • •Pump kick • • • •Run-time optimisation / pump cycling

Only time-dependent pump cycling • • •

Pump duty splitting up to 4 pumps up to 6 pumps up to 6 pumps1) up to 6 pumps

PID controller • • • •Integrated real time clock with summer/winter time change – • • •

Integrated individual/total operating hours counter • • • •

Service life optimisation for multi-pump systems – • • •

Conductivity testing of the actual value section • • • •

Wilo control device…

VR-HVAC CRn CC-HVAC CR

• = available, – = not available, o = optional on request1) Larger number of pumps on request2) Higher nominal motor power values on request

Page 221: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

221

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Performance features

Switc

hgears

and

control

devices

Pump management

"Mains - Emergency - Opera-tion" service selector switch for maintenance purposes

– • • •

Night reduction to minimum speed and/or second controlled level via internal clock timer

– • • •

Remote acknowledgement of collective fault signal

– •(with DDC board)

o •(with DDC board)

Pilot pump function – • • •Clock timer – • • •Switchover to second setpoint level

– •(with DDC board)

•(max. 3)

•(with DDC board)

Individual run and fault signals for pumps and converters

•(with options board)

•(with signal board) o •

(with signal board)

Manual / automatic switchover with external switch

– •(with control board) o •

(with control board)

Connection option for a repair switch (potential-free contact)

– •(with control board) o •

(with control board)

Accessories

Differential-pressure sensor, DDG • • • •

Temperature boards, KTY / PT 100 – • – •

Temperature module, PT 100 – – o –

Temperature sensor, TSG – • – •Outdoor temperature sensor, KTY – • – •

Outdoor temperature sensor, PT 100 –

•(to be provided by the

customer)o

•(to be provided by the

customer)

PTC thermistor triggering relay –

•(to be taken into account during the selection of the

pump)

o(to be taken into account during the selection of the

pump)

•(to be taken into account during the selection of

the pump)

Control board – • – •

Signal board •(with options board)

• – •

DDC board – • – •

Volume-flow transmitter–

(to be provided by the cus-tomer)

•(to be provided by the

customer)

–(to be provided by the cus-

tomer)

•(to be provided by the

customer)

Wilo control device…

VR-HVAC CRn CC-HVAC CR

• = available, – = not available, o = optional on request1) Larger number of pumps on request2) Higher nominal motor power values on request

Page 222: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

222 Subject to change 09/2008 WILO SE

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Performance features

Special features

DPM (dual pump management)

not required for DPM with: Stratos/-D /-Z/-ZD,

TOP-E /-ED, VeroLine IP-E, VeroTwin DP-E,

CronoLine IL-E, CronoTwin DL-E

not required for DPM with: Stratos/-D /-Z/-ZD,

TOP-E /-ED, VeroLine IP-E, VeroTwin DP-E,

CronoLine IL-E, CronoTwin DL-E

not required for DPM with the following series: Stratos/-D /-Z/-ZD,

TOP-E /-ED,VeroLine IP-E, VeroTwin

DP-E, CronoLine IL-E, CronoTwin

DL-E

not required for DPM with: Stratos/-D /-Z/-ZD,

TOP-E /-ED, VeroLine IP-E, VeroTwin DP-E, CronoLine IL-E, CronoTwin DL-E

Wilo control device…

VR-HVAC CRn CC-HVAC CR

• = available, – = not available, o = optional on request1) Larger number of pumps on request2) Higher nominal motor power values on request

Page 223: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

223

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Control modes

Switc

hgears

and

control

devices

Pump management

Switchgears and control devices Wilo-Vario and Comfort control systems VR, CRn, CR, CC Control modes Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Differential pressure - constant (�p - c)

The differential pressure setpoint to be adjust-ed at the control devices is kept constant across the entire volume flow range. That means that any reduction of the volume flow (Q) caused by the throttling of the hydraulic control units will in turn adjust the pump out-put to actual system requirements by reducing the speed of the pump. Along with the change in speed, the power consumption is reduced to below 50% of the nominal power. The applica-tion of the differential pressure control re-quires a variable volume flow in the system. Peak-load operation, e.g. in conjunction with a double pump, is performed automatically and according to the load by the control system. If the controlled base-load pump is no longer able to supply the required load, the second pump is automatically cut in. The variable speed pump is then run down until the preset differential pressure setpoint value is reached.

Required accessories:Differential pressure sensor, DDG(see also "Performance features" table)

Fig.: Pump curve behaviour for infinitely variable constant differential pressure control (�p - c)

Δp-level = constant

Control range

Flow volume Q [%]

Q [%]

Delivery

head

H [%]

Power

requirement [%]

Control / savings range

Flow volume

approx. ± 2% Linearity/hysteresis

Page 224: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

224 Subject to change 09/2008 WILO SE

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Control modes

Switchgears and control devices Wilo-Vario and Comfort control systems VR, CRn, CR, CC Control modes Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Differential pressure - variable (�p - v)

When upgrading existing systems it is not al-ways possible to evaluate the index circuit which. Original installations have been com-pleted years ago and now, after installing ther-mostatic valves, noise problems have devel-oped. The index circuit of the system is not known or it is not possible to integrate the new sensor lines that are required. An extension of the control range is nevertheless possible using the �p-v control mode (recommended for sin-gle-pump systems). A processor unit of the control system adapts the differential pressure setpoint value to a preset variable differential-pressure curve by means of a comparison of the setpoint /actual value. In parallel operation, the differential pressure is kept constant at the design level after the first peak-load pump has been cut in.

Required accessories:Differential pressure sensor, DDG(also see "Performance features" table)

Fig.: Pump curve behaviour with infinitely variable differential pressure control (�p - v)

Del

iver

y he

ad H

[m]

Pow

er r

equi

rem

ent

P [%

]

36

16

100

n = 60%

n = 40%

n = 100%

25

12

100

Δp = constant

Control range

Control range / savings potential

n = 100%

n = 40%

Q [%]

Q [%]

n = 60%

Page 225: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

225

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Control modes

Switc

hgears

and

control

devices

Pump management

Switchgears and control devices Wilo-Vario and Comfort control systems VR, CRn, CR, CC Control modes Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Differential pressure - delivery-superimposed (�p - q)

In order to avoid the time and expenses associ-ated with index circuit evaluation (extensive and expensive cable routing, amplifiers, etc.), it is possible to override the differential pressure setpoint value directly with a signal propor-tional to delivery. Using this method, it is pos-sible, even with multi-pump systems, to achieve a control-range extension in spite of central measured-value acquisition (differen-tial pressure sensor at the pump).This method requires, in addition to the differ-ential pressure sensor which is to be fitted di-rectly on the pump system, the heating-circuit output or the input of the consumer rail, the provision by the customer of a volume-flow transmitter (0/4– 20 mA) to be installed in the system's main feed pipe.The use of the �p-q control is recommended for such systems whose index circuit or system performance are not known or in such cases where long signal distances cannot be bridged, particularly for such systems where volume-flow transmitters are already available.

Required accessories:Differential pressure sensor, DDGVolume-flow transmitter (provided by the cus-tomer)(also see "Performance features" table)

Fig.: Pump curve behaviour of a multi-pump system with infinitely variable delivery-superimposed differen-tial pressure control (�p - q)

Del

iver

y he

adH

[%

] Po

wer

requ

irem

ent

P [%

]

Flow volume Q [%]

Dp = constantDp = delivery-

superimposed

Key:

Pu H = main pumpPu S = peak load pumpQ V = full-load flow volumeQ T = part-load capacityP 1V = full-load power

consumptionP 1T = part-load power

consumption

Page 226: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

226 Subject to change 09/2008 WILO SE

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Control modes

Switchgears and control devices Wilo-Vario and Comfort control systems VR, CRn, CR, CC Control modes Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Differential pressure - temperature superimposed (�p - T)

The operational performance of the hydraulic system can be further optimised by adapting the differential pressure setpoint value for pump output control according to a superim-posed reference variable (e.g. outdoor temper-ature). The differential pressure setpoint value and thus the pump output is reduced with ris-ing outdoor temperatures, it is increased with falling outdoor temperatures.

Required accessories:Differential-pressure sensor, DDGTemperature board, KTY 10or Temperature board, PT 100CC temperature module, PT 100(also see "Performance features" table)Process temperature sensor or outdoor tem-perature sensor, PT 100 or KTY

Fig.: Differential pressure setpoint variation according to a temperature

Temperature T[C]

Diff

eren

tial

pre

ssur

e se

tpoi

nt

p [m

]

max.

min.

+ 50 - 20

Page 227: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

227

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Control modes

Switc

hgears

and

control

devices

Pump management

Switchgears and control devices Wilo-Vario and Comfort control systems VR, CRn, CR, CC Control modes Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Differential temperature control (�T)

Heating/air-conditioning systems vary in terms of their cooling/heating requirements accord-ing to outdoor temperature fluctuations. A number of installations are installed without actuating units or the option of controlling the volume flow (single-pipe heating systems, pri-mary circuits, etc.). Moreover, pure throttling or bypass controls are highly uneconomical. The secondary power consumption (electricity) for the pump drive is also unnecessarily high during the transition period.The differential-temperature control �T is one option for maintaining a constant difference between feed and return temperatures as a re-sult of weather- and usage-dependent tem-perature spread. The heat flow becomes varia-ble due to the changes in flow rates and the transferred heating/cooling capacity can be controlled independently of feed or return temperatures. Differential-temperature con-trols should therefore only be used with indi-vidual consumers or with systems with a known control time constant to be able to use them in a straightforward manner.

Required accessories:Temperature board, KTY 10or Temperature board, PT 100CC temperature module, PT 100(also see "Performance features" table)Temperature sensor, TSG or PT 100(provided by the customer)

Fig.: Volume flow variation according to the temperature spread

Tem

pera

ture

T[C

]

Q [%]

Feed temperature

Return temperature

25

20

90

70

100

T

Page 228: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

228 Subject to change 09/2008 WILO SE

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Control modes

Switchgears and control devices Wilo-Vario and Comfort control systems VR, CRn, CR, CC Control modes Subject to change 09/2008 WILO SE Wilo Catalogue A2A2 - 50 Hz - Glanded pumps

Temperature control (±T)

With the case of pump control according to the temperature, the control signal (±T) results in a variation of pump output, but there is no ad-justment of the variation or its results by means of feedback of the comparison of the setpoint/actual value.Fixed motor speeds have been assigned to the pump for specific feed /return temperatures according to an empirically predetermined pump curve.A falling feed temperature (+T) or a rising re-turn temperature (-T) will result in automatic speed reduction and thus the reduction of the pump performance input.Temperature control ±T can only be applied to single pump operation. Feed or return temper-ature-sensitive peak-load operation is techni-cally not feasible.

Required accessoriesTemperature board, KTY 10or Temperature board, PT 100CC temperature module, PT 100(also see "Performance features" table)Temperature sensor, TSG or PT 100(provided by the customer)

Fig.: System diagram of the infinitely variable temperature control

Heating curves, basic temperature

Min. boundary

Delivery

head

Po

wer

consumptionP

1[%]

Outside temperature

Pump performance diagram Q/H

Pump performance diagram Q/P

Flow volume Q [%]

Return

temperature

–T [C]

H [%]

Feed

temperature

+T [C]

TA [C]

Control range, adjustable from 5°C to 50°C, e.g. 30°C

Max. boundary

Flow volume Q [%]

Control range

max. n = 100 %

min. n = 60 %

max. n = 100 %

min. n = 60 %

Energy savin

gs

Page 229: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

229

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Control modes

Switc

hgears

and

control

devices

Pump management

Switchgears and control devices Wilo-Vario and Comfort control systems VR, CRn, CR, CC Control modes Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Variable differential temperature (�T - v)

The �T-v control function is particularly suita-ble for pump output control in single-pipe heating systems, district heatings, systems with condensing boiler technology and cooling systems. The �T-v control mode ensures that the differ-ential temperature is spread variably according to another temperature, e.g. the outdoor tem-perature. This means that only the water quan-tity required for heat transfer is circulated. This leads to significant energy savings on the drive side. Furthermore, the return temperature can also be drastically reduced. The large tempera-ture spread improves the efficiency of boilers or heat exchangers, and limits the return tem-perature, as required e.g. in most district heat-ing networks.

Required accessories:Temperature board, KTY 10orTemperature board, PT 100CC temperature module, PT 100(also see "Performance features" table)Temperature sensor, TSG or PT 100(provided by the customer)Process temperature sensor or outdoor temperature sensor, PT 100 or KTY

Fig.: Differential temperature according to the process or outdoor temperature

Fig.: Effect on the differential temperature

Diff

eren

tial

tem

pera

ture

ΔT

[°K]

Outside, process temperature [°C]

ΔT

Feed temperature

Return temperature

Tmin Tmax

Outside, process temperature [°C]

Controller influence

negative positive

Diff

eren

tial

tem

pera

ture

– s

etpo

int [

°C]

Page 230: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

230 Subject to change 09/2008 WILO SE

Switchgears and control devicesWilo-Vario and Comfort control systems VR, CRn, CR, CC

Control modes

Switchgears and control devices Wilo-Vario and Comfort control systems VR, CRn, CR, CC Control modes Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Constant volume flow control (Q - c)

The volume flow which is set at the CR device is kept constant. If the volume flow Q de-creases, the speed of the pump system is increased until the set volume flow is reached again. If the volume flow increases, the speed is reduced so that only the required rate is pumped.

The Q-c control function is applied practically in such cases where a constant, adjustable vol-ume flow is to be pumped. Such cases are for example cooling systems, cooling towers, test stands or systems for water supply, water treatment and sewage disposal. Flow rates of 2 – 2000 m3/h can be controlled.

Examples of the application of flow rate con-trols:Mixing of chemically different well waters in an elevated tank for establishing a consistent wa-ter qualityDelivery of cold and cooling water according to the connected cooling towers or consumersMixing sewage (municipal and industrial appli-cations) for achieving a defined untreated sewage composition, adapted to the sewage treatment in a sewage treatment plantDosing of chemicals in chemical and environ-mental engineeringAgricultural irrigation

Required accessories:Flow rate meter provided by the customer Monitoring of limit values is to be implemented onsite (system protection)

Fig.: Principle of the constant volume flow control

Pressure - constant (p - c)

The constant pressure control mode (p - c) is suitable for use in conjunction with open pipe systems, e.g. water supply and pressure boost-ing applications.The pump output is adapted according to wa-ter requirements (pressure-dependent) along a setpoint level. Multi-pump systems require the activation and deactivation of base-load and peak-load pumps according to requirements. Fluid hammers caused by premature deactiva-tion and immediate reactivation are thus fully eliminated.In a pressure boosting system, the base-load pump is deactivated via the control system at Q = 0(also see "Performance features" table)

Fig.: Constant pressure control (p - c) using a 3-pump system as an example

Qmin Qmax

Del

iver

y he

ad H

[m]

Delivery rate Q [m³]

Qset

Del

iver

y he

adH

[m

] Switch-off pressure levelpeak-load pumppOff

Pipe network parabola

Set pointlevel

Pump 3Switch-onpressure levelpeak-load pump p On

Pump 1 Pump 2

Flow rate Q

Page 231: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

231

Switchgears and control devicesSwitchgears

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-VR-HVAC system

Switc

hgears

and

control

devices

Pump management

Switchgears and control devices Switchgears Series description Wilo-VR-HVAC system Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsVR-HVAC systemDigitally-controlled, infinitely variable Vario control system for elec-tronically controlled glandless and glanded pumps of the Stratos, TOP-E, VeroLine-IP-E and CronoLine-IL-E series, for mounting sin-gle-pump and multiple-pump systems.

Typical field of application of the Wilo-VR-HVAC system is water cir-culation in heating, ventilation, cooling and air-conditioning systems of large buildings such as hospitals, hotels, schools, department stores, industrial systems, residential, commercial and public build-ings. Latest pump technology and digital control electronics fulfil all requirements of the Wilo-VR-HVAC system for new installations and retrofitting:

- For all glandless and glanded pumps with integrated power electron-ics up to P2 = 22 kW nominal power.

- For pump duty splitting with up to 4 units (to make best use of the low-power split units in low-load operation).

- Prevention of flow or cavitation noise.- Reduction of operating costs due to energy savings.

Operating principleThe control device is for controlling and regulating circulation pumps with electronic control or integrated pump output electronics. The differential pressure of a system is controlled according to the load with appropriate signal transmitters. The controller affects the fre-quency converter which has an effect on the pump speed. A modifi-cation of the speed changes the delivery head and thus the power output of the single pumps. According to load requirements, pumps are activated or deactivated. The control device can control up to 4 pumps.

Equipment features- PID controller- Lockable main switch-Graphical LC display for the indication of all values and operating states

- Red-button technology (one-button operation)- LEDs for indicating operation standby, pump(s) in operation, faulty pump(s)

- Circuit breakers and output terminals for the power supply of pump(s)

- Integrated signal board (option)-Automatic pump cycling

- Emergency operation as an option- Selection of a standby pump

Infinitely variable speed controlAn electronic Wilo DDG differential pressure sensor delivers the actu-al differential pressure value as 4 - 20 mA current signal. Then the controller maintains the differential pressure at a constant level by means of the comparison of the setpoint/actual values. If there is no "External Off" signal and no fault, at least one pump is running. The pump speed depends on the load. If the required output cannot be covered by this pump (base-load pump), another pump is cut in, the speed of which is then controlled according to the reduction to the setpoint. Pumps, which are already running, keep operating at maxi-mum speed (peak-load pumps). If the demand decreases to such an extent that the controlling pump runs at its lowest output range and is not needed to cover the demand, this pump is deactivated and the control function is assigned to another pump which has previously been running at maximum speed.Control modes �p-c and �p-v can be preselected in the menu. Only the first pump is controlled in �p-v mode. If more pumps are cut in, these are adjusted according to the �p-c curve.

Control modesThe following control modes can be preselected on the Wilo-VR-HVAC system for electronic performance control:

- For variable-delivery systems (e.g. heating systems with thermostat-ic valves):

- Constant differential pressure control (�p-c)-Variable differential pressure control (�p-v)

Control and signalling functionsThe standard Wilo-VR-HVAC system has an extensive range of con-trol inputs/outputs for integration into external monitoring units to be provided by the customer:

-Analogue output, �pout (0 - 10 VDC), for indicating the actual value of the differential pressure sensor

-Activation/deactivation via external potential-free contact- SSM collective fault signal as potential-free changeover contact - SBM collective run signal as potential-free changeover contact- IFS individual fault signal for each pump as potential-free changeover contact (optional)

- IRS individual run signal as potential-free changeover contact (op-tional)

Page 232: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

232 Subject to change 09/2008 WILO SE

Switchgears and control devicesSwitchgears

Series overview Wilo-VR-HVAC system

Switchgears and control devices Switchgears Series overview Wilo-VR-HVAC system Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Dimensions, weights Wilo-VR-HVAC system

Switchbox Dimensions Weight approx.

Width x height x depth M

[mm] [kg]

VR-HVAC 1x0.37WM 400 x 300 x 120 8.5

VR-HVAC 2x0.37WM 400 x 300 x 120 9.0

VR-HVAC 3x0.37WM 400 x 300 x 120 9.5

VR-HVAC 4x0.37WM 400 x 300 x 120 10.0

VR-HVAC 1x0.55WM 400 x 300 x 120 8.5

VR-HVAC 2x0.55WM 400 x 300 x 120 9.0

VR-HVAC 3x0.55WM 400 x 300 x 120 9.5

VR-HVAC 4x0.55WM 400 x 300 x 120 10.0

VR-HVAC 1x0.75WM 400 x 300 x 120 8.5

VR-HVAC 2x0.75WM 400 x 300 x 120 9.0

VR-HVAC 3x0.75WM 400 x 300 x 120 9.5

VR-HVAC 4x0.75WM 400 x 300 x 120 10.0

VR-HVAC 1x1.1WM 400 x 300 x 120 8.5

VR-HVAC 2x1.1WM 400 x 300 x 120 9.0

VR-HVAC 3x1.1WM 400 x 300 x 120 9.5

VR-HVAC 4x1.1WM 400 x 300 x 120 10.0

VR-HVAC 1x1.5WM 400 x 300 x 120 8.5

VR-HVAC 2x1.5WM 400 x 300 x 120 9.0

VR-HVAC 3x1.5WM 400 x 300 x 120 9.5

VR-HVAC 4x1.5WM 400 x 300 x 120 10.0

VR-HVAC 1x2.2WM 400 x 300 x 120 8.5

VR-HVAC 2x2.2WM 400 x 300 x 120 9.0

VR-HVAC 3x3.3WM 400 x 300 x 120 9.5

VR-HVAC 4x2.2WM 400 x 300 x 120 10.0

VR-HVAC 1x3.0WM 400 x 300 x 120 8.5

VR-HVAC 2x3.0WM 400 x 300 x 120 9.0

VR-HVAC 3x3.3WM 400 x 300 x 120 9.5

VR-HVAC 4x3.0WM 400 x 300 x 120 10.0

VR-HVAC 1x4.0WM 400 x 300 x 120 8.5

VR-HVAC 2x4.0WM 400 x 300 x 120 9.0

VR-HVAC 3x4.0WM 400 x 300 x 120 9.5

VR-HVAC 4x4.0WM 400 x 300 x 120 10.0

VR-HVAC 1x5.5WM 400 x 300 x 120 8.5

VR-HVAC 2x5.5WM 400 x 300 x 120 9.0

VR-HVAC 3x5.5WM 400 x 300 x 120 9.5

VR-HVAC 4x5.5WM 400 x 300 x 120 10.0

VR-HVAC 1x7.5WM 400 x 300 x 120 8.5

VR-HVAC 2x7.5WM 400 x 300 x 120 9.0

VR-HVAC 3x7.5WM 400 x 400 x 120 11.5

VR-HVAC 4x7.5WM 400 x 400 x 120 12.0

VR-HVAC 1x11WM 400 x 400 x 120 10.5

Page 233: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

233

Switchgears and control devicesSwitchgears

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series overview Wilo-VR-HVAC system

Switc

hgears

and

control

devices

Pump management

VR-HVAC 2x11WM 400 x 400 x 120 11.0

VR-HVAC 3x11WM 600 x 600 x 250 34.5

VR-HVAC 4X11WM 600 x 600 x 250 35.0

VR-HVAC 1x15WM 400 x 400 x 120 10.5

VR-HVAC 2x15WM 400 x 400 x 120 11.0

VR-HVAC 3x15WM 600 x 600 x 250 35.0

VR-HVAC 4x15WM 600 x 600 x 250 35.5

VR-HVAC 1x18.5WM 400 x 300 x 120 10.5

VR-HVAC 2x18.5WM 400 x 300 x 120 11.0

VR-HVAC 3x18.5WM 600 x 600 x 250 35.0

VR-HVAC 4x18.5WM 600 x 600 x 250 35.5

VR-HVAC 1x22WM 400 x 300 x 120 10.5

VR-HVAC 2x22WM 400 x 300 x 120 11.0

VR-HVAC 3x22WM 600 x 600 x 250 35.5

VR-HVAC 4x22WM 600 x 600 x 250 36.0

Dimensions, weights Wilo-VR-HVAC system

Switchbox Dimensions Weight approx.

Width x height x depth M

[mm] [kg]

Page 234: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

234 Subject to change 09/2008 WILO SE

Switchgears and control devicesSwitchgears

Terminal diagrams Wilo-VR-HVAC system

Switchgears and control devices Switchgears Terminal diagrams Wilo-VR-HVAC system Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram VR-HVAC 3~400 V Terminal diagram VR-HVAC 1~230 V

L1 L2 L3 PE

1 42...

1 42...

U V W PE

+24

V

SSM SBMExt.OFF

Sensor

IN

0...1

0 V

SSM

L1 N PE L1 N PE

1 42...

1 42...

+24

V

SSM SBMExt.OFF

Sensor

IN

0...1

0 V

SSM

Page 235: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

235

Switchgears and control devicesWilo-Comfort control systems CR, CRn, CC

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-CR, Wilo-CRn, Wilo-CC

Switc

hgears

and

control

devices

Pump management

Switchgears and control devices Wilo-Comfort control systems CR, CRn, CC Series description Wilo-CR, Wilo-CRn, Wilo-CC Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsWilo-Comfort control systems CR, CRn and CCDigitally controlled, infinitely variable Comfort control systems for glandless and glanded pumps of all makes, single-pump and multi-pump systems.CR version for conventional pumps with fixed speed.CRn version for infinitely variable, electronically controlled pumps or pumps with integrated frequency converter.CC version for conventional pumps with fixed speed.

Typical fields of application of the Wilo-Comfort control devices CR, CRn and CRn are water circulation and water supply (e.g. pressure boosting)

- In residential, commercial and public buildings, hotels, hospitals, de-partment stores and for industrial buildings. Most up-to-date digital control electronics fulfil all requirements of the Wilo-Comfort control systems for new installations and retrofitting:

- For CR version for all glandless and glanded pumps with three-phase motors with a nominal power up to P2 = 30 kW (higher output values and other voltages on request)

- For CRn version independent of the power via analogue control sig-nals 0 / 2 – 10 V or 0 / 4 – 20 mA

- For CC version for all glandless and glanded pumps with three-phase motors with a nominal power up to P2 = 200 kW (higher output val-ues and other voltages on request)

- For pump duty splitting with up to 6 units (to make best use of the low-power individual units in low-load operation)

- Prevention of flow or cavitation noise- Lower operating costs due to energy savings- Speed control range between 100% and 40% of the nominal power.

Operating principleThe Wilo-Comfort control systems allow the infinitely variable elec-tronic adjustment of the pump output to meet the continuously var-ying operating conditions in the hydraulic system according to the control variables: pressure (p), volume flow (Q), temperature (T).

Equipment features- PID controller- Integrated real-time clock with summertime/wintertime change- Integrated individual/total operating hours counter- Service life optimisation for multi-pump systems-Motor protection due to connection of WSK, PTC TS and TSA (for CR

version)-Motor protection due to connection of WSK and SSM (for CRn ver-sion)

-Motor protection due to connection of WSK, PTC TS and TSA (for CC version)

- Touch display with multi-colour backlight for CC version-Alphanumerical LCD display for the CR and CRn versions (4-line) with

backlight- Status display for drives (e.g. pumps and frequency converters)-User-oriented menu navigation with multi-language plain text dis-play and/or symbol navigation

- Storage and display of extensive operating data-Defined display of fault signals and storage in the history memory- Conductivity test of the transmitter paths

Infinitely variable speed controlInfinitely variable speed control must be regarded as the ideal solu-tion to the problem of achieving 100% harmonious adjustment of the pump output to the actual operating states of the system.Unfortunately, its particular inherent capability of reducing the speed right down to a very low level – about 10–20% of the residual speed – cannot be implemented in practice in heating applications. Speed reductions in the range below 60% residual speed and the resulting drop in delivery head (delivery head as a quadratic function of speed) may result in malfunctions and sometimes to a breakdown in water distribution. In this case, the �p measuring point must be installed on what is called the index circuit of the system, i.e. the line or consumer with the greatest pressure losses. Extremely low speeds below 40%

Sensor connection

DDG - or

TSG

Mains connectionMotor connection

Return Return sensor

Outside temperature sensor

Ext. offSSM0-10 Volt

6

Feed

Feed sensor

Mains supply connection

Mains supplyconnection

Mains connect

Page 236: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

236 Subject to change 09/2008 WILO SE

Switchgears and control devicesWilo-Comfort control systems CR, CRn, CC

Series description Wilo-CR, Wilo-CRn, Wilo-CC

of the nominal speed can also lead to thermal and mechanical over-loading of the electric motors.

Control modesThe following control modes can be preselected for electronic pump output control with Wilo-Comfort control systems (also see "Per-formance features" table)

• For variable-delivery systems (e.g. heating systems with thermostat-ic valves):

-Constant differential pressure control (�p-c)-Variable differential pressure control (�p-v)-Variable-delivery differential pressure control (�p-q)-Temperature-superimposed differential pressure control (�p-T)-Constant pressure control (p-c) for pressure boosting systems-Constant flow rate control (Q-c)• For constant-volume systems (e.g. cooling systems with heat ex-changers):

-Differential temperature control (�T)- Process temperature control (±T)-Variable temperature control (�T-v)

Control and signalling functionsThe Wilo-Comfort control systems provide extensive control inputs and outputs as standard equipment for integration in external moni-toring units provided by the customer (see also "Performance fea-tures" table)

-Remote setpoint adjustment (0 – 10 V/10 – 20 mA) preselectable (with CR and CRn)

-Remote setpoint adjustment (4 – 20 mA) preselectable (with CC)-Activation/deactivation via external potential-free contact-Activation of frost protection via external potential-free contact

(only for heating/air-conditioning) via digital input- Low water cut-out switch via external potential-free contact (only

for pressure boosting) via digital input-Collective fault signal/collective run signal as potential-free change-over contact

- "Mains – Emergency – Operation" service selector switch for mainte-nance personnel

- Switchover to second setpoint level (with CR and CRn)- Switchover to second/third setpoint level (with CC)

The following optional control inputs and outputs are available:-Remote acknowledgement of the collective fault signal- Switchover to manual control mode- Individual run and fault signals for pumps and converters-Manual/automatic switchover- Signalling contact connection of repair switches

Type key, CR control device (example: CR 1.1-2 WM)

CR Comfort control technology

1.1 Maximum nominal motor power P2 of pump to be controlled in kW

2 Number of pumps to be controlled(1–6 pumps)

WM Device version

WM = wall-mounted installation IP 42 (IP 54 on request)

FM = floor model IP 42 (IP 54 on request)

SE = control-panel installation

Type key, CRn control system (example: CRn 1-2 TP WM)

CRn Comfort control technology, new

1-2 Number of pumps that can be connected:1–23–45–6

TP, TK Control mode:T = temperatureP = PT 100 sensorK = KTY sensor

WM Device version

WM = wall-mounted installation IP 42 (IP 54 on request)

SE = control-panel installation

Type key, CC control device (example: CC 2x1.1 FC WM)

CC Comfort Controller

2 Number of pumps to be controlled(1–6 pumps)

1.1 Maximum nominal motor power P2 of pump to be controlled in kW

FC Installation with frequency converter and sine filter

WM Device version

WM = wall-mounted installation, IP 54

BM = floor model, IP 54

Type key, CR control device (example: CR 1.1-2 WM)

Page 237: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

237

Switchgears and control devicesWilo-Comfort control systems CR, CRn, CC

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Technical data Wilo-CR, Wilo-CRn, Wilo-CC

Switc

hgears

and

control

devices

Pump management

Switchgears and control devices Wilo-Comfort control systems CR, CRn, CC Technical data Wilo-CR, Wilo-CRn, Wilo-CC Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsWilo-Comfort control system CR• Automatic, load-sensitive, infinitely variable speed control of gland-ed and glandless pumps with three-phase motor.

• For heating /air-conditioning according to the differential pressure �p, feed/return temperature (±T) or differential temperature (�T) in-cluding free adjustment of the duty point by means of the advance

correction of the full-load pump output. For pressure boosting ac-cording to the pressure (p).

• Device version-Wall-mounted installation (WM) available only up to 4 kW- Floor models (FM) available above 5.5 kW-Control-panel installation (SE)

Wilo-Comfort control system CRn• Automatic load-sensitive, infinitely variable speed control of gland-less and glandless pumps with integrated or external frequency con-verter.

• For heating/air-conditioning according to the differential pressure �p, feed/return temperature (±T) or differential temperature (�T) in-

cluding free adjustment of the duty point by means of the advance correction of the full-load pump output.

• Device version-Wall-mounted installation-Control-panel installation

Wilo-Comfort control system CC• Automatic, load-sensitive, infinitely variable speed control of gland-ed and glandless pumps with three-phase motor.

• For heating /air-conditioning according to the differential pressure �p, feed / return temperature (±T) or differential temperature (�T) in-cluding free adjustment of the duty point by means of the advance

correction of the full-load pump output. For pressure boosting ac-cording to the pressure (p).

• Device version-Wall-mounted installation -Control-panel installation

Connection data Wilo-CR

Device grading: Max. nominal motor power P2 [kW]3~400 V/ 50 Hz / 60 Hz

1.1 2.2 3.0 4.0 5.5 7.5 11.0 15.0 22.0 30.0

Maximum output current I [A] 2.8 5.6 7.6 9.7 13.0 16.0 24.0 32.0 44.0 61.0

Power factor cos ˆ > 0.90

Efficiency:- for Pmax- within the permitted partial load range

> 0.93> 0.85

Electrical connection 3~400 V/ N / 50 Hz / 60 HzOutput voltage [V] 3 x 130 V – 400 VOutput frequency [Hz] (10 Hz) 12 Hz – 50 Hz / 60 HzControl range (% nominal motor speed) 40% – 100%Permitted ambient temperature 0 °C to +40 °C

Connection data Wilo-CRn

Electrical connection 1~230 V (shock-proof plug) / N/ PE / 50 Hz / 60 Hzpower connection of the pumps onsite

Output signals 0/2 – 10 V0/4 – 20 mA

Permitted ambient temperature 0 °C to +40 °C

Connection data Wilo-CC

Device grading:Max. nominal motor power P2 [kW]3~400 V/ 50 Hz / 60 Hz

1.1 1.5 2.2 3.0 4.0 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.5 45.0 55.0

Max. permissible nominal pump current I [A] 3.0 3.7 5.2 7.0 9.0 13.0 16.0 24.0 32.0 37.5 43.1 61.0 72.4 89.6 106.0Power factor cos ˆ > 0.90

Efficiency: - for Pmax- within the permitted partial load range

> 0.93> 0.85

Page 238: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

238 Subject to change 09/2008 WILO SE

Switchgears and control devicesWilo-Comfort control systems CR, CRn, CC

Technical data Wilo-CR, Wilo-CRn, Wilo-CC

Electrical connection 3~400 V/ PE Hz / 50 HzOutput voltage [V] 3 x 130 V – 400 VOutput frequency [Hz] (10 Hz) 12 Hz – 50 Hz / 60 HzControl range (% nominal motor speed) 40% – 100%Permitted ambient temperature 0 °C to +40 °C

Connection data Wilo-CC

Accessories for Wilo-Comfort control systems CR, CRn and CC

Accessories

Sensors

Differential pressure sensor, DDG (4 – 20mA) (observe the measurement ran-ge)

Terminal diagram:base board, CC /CRn system

Outdoor temperature sensor, KTY or PT 100

Temperature signal transmitter, TSG (included in the scope of delivery of the temperature board)

Terminal diagram:temperature board, KTY 10

Temperature boardAutomatic, infinitely variable speed control according to the feed or return temperature or according to the dif-ference between feed and return tempera-tures

Temperature board, KTY 10: Heating system with large temperature spread (Tmax: +140 °C, �Tmin 10 K, �Tmax: 100 K), 2 TSG temperature transmitters included in the scope of delivery

Terminal diagram:temperature board, KTY 10

Temperature board, PT 100: Cooling/air-conditioning systems with small temperature spread (Tmax: +140 °C, �Tmin K, �Tmax: 100 K)

Terminal diagram:temperature board, PT 100

CC temperature mod-ule, PT 100

Temperature range -200 °C to +500 °C, connection of PT 100, PT 1000 and Ni 1000 sensors

Terminal diagram:temperature module, PT 100

CR/CRncontrol board

Deactivation of each pump (up to 2 pumps) by repair switch onsite and remote adjustment of operating mode (mains / automatic) for each pump (up to 2 pumps) 3 control boards are required for 6 pumps

Terminal diagram:control board

CR/CRnDDC board

Load adjustment of the pump system (comparison of setpoint-actual values) via external controller, pump activation and deactivation, pump cycling, set-point switchover, switch-over to remote speed control and acknowledgement of the collective fault signal via external potential-free contact

Terminal diagram:DDC board

CR/CRnsignal board 1 – 2

Potential-free individual operation/individual fault signal for pumps 1 – 2 and frequency converter, status signals to the digital inputs DIG2 or DIG3 (e.g. low water, antifreeze), actual speed value or actual transmitter value (can be prese-lected)

Terminal diagram:signal board 1-2

CR/CRn signal board 3 – 6

Potential-free individual operation/individual fault signal for pumps 3 – 6 Terminal diagram:signal board 3-6

Dimensions and weights Wilo-CR system

Nominal power Number of pumps

WM / FM SE

P2 W H D Weight W H Req. instal-lation depth

Weight

[kW] [mm] [kg] [mm] [kg]

1.1 – 4.01-4-fold 620 770 265 50 550 730 190 30

5-6-fold 780 770 315 70 704 730 200 45

5.5 – 7.51-2-fold 600 1900 415 195 499 1696 210 95

3-4-fold 800 1900 415 205 699 1696 210 105

5-6-fold 1000 1900 415 215 899 1696 210 115

11.0 – 22.01-2-fold 800 1900 515 270 699 1696 310 140

3-4-fold 1200 1900 515 350 1099 1696 310 1601) Control system consists of 2 switch rails.

Page 239: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

239

Switchgears and control devicesWilo-Comfort control systems CR, CRn, CC

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Technical data Wilo-CR, Wilo-CRn, Wilo-CC

Switc

hgears

and

control

devices

Pump management

11.0 – 15.0 5-6-fold 1200 1900 515 365 1099 1696 310 175

225-6-fold1) 1200 1900 515 – 1099 1696 310 –

600 1900 515 520 499 1696 310 230

30

1-2-fold 1200 1900 515 390 1099 1696 310 200

3/4-fold1) 1200 1900 515 – 1099 1696 310 –

600 1900 515 560 499 1696 310 270

5-6-fold1) 1200 1900 515 – 1099 1696 310 –

1200 1900 515 640 1099 1696 310 320Section dimensionCR controller andoperating unit

– – – – – 186 138 82 –

Dimensions and weights Wilo-CR system

1) Control system consists of 2 switch rails.

Dimensions and weights Wilo-CRn system

Temperature sensorsNumber of pumps

WM SE

Dimensions (W x H x D) Weight Dimensions (W x H x D) Weight

[pcs.] [mm] [kg] [mm] [kg]PT 100 1 – 2 400 x 400 x 200 12.5 360 x 380 x 120 5.0PT 100 3 – 4 400 x 400 x 200 12.5 360 x 380 x 120 5.0KTY 1 – 2 400 x 400 x 200 13.0 360 x 380 x 120 5.5KTY 3 – 4 400 x 400 x 200 13.0 360 x 380 x 120 5.5

Dimensions and weights Wilo-CC system

Nominal power P2 Number of pumps Dimensions (W x H x D) Weight

[kW] [pcs.] [mm] [kg]

0.75 – 4.01–4 600 x 760 x 250 50

5–6 760 x 760 x 250 70

5.5 – 7.51–2 600 x 1900 x 500 175

3–4 800 x 1900 x 500 205

5–6 1000 x 1900 x 400 230

11.0 – 15.01–2 800 x 1900 x 500 220

3–4 1000 x 1900 x 400 27011.0 5–6 1000 x 1900 x 400 30015.0 5–6 1200 x 1900 x 500 360

18.5 – 22.01–2 800 x 1900 x 500 250

3–4 1000 x 1900 x 400 320

5–6 1800 x 1900 x 500 500

301–2 800 x 1900 x 500 270

3–4 1200 x 1900 x 500 380

5–6 2000 x 1900 x 500 580

Page 240: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

240 Subject to change 09/2008 WILO SE

Switchgears and control devicesWilo-Comfort control systems CR, CRn, CC

Terminal diagrams Wilo-CR, Wilo-CRn, Wilo-CC

Switchgears and control devices Wilo-Comfort control systems CR, CRn, CC Terminal diagrams Wilo-CR, Wilo-CRn, Wilo-CC Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagram, CR system base board

DDG1 2 3

Actu

al v

alue

Eart

hSe

nsor

Shie

ld

Sign

alEa

rth

Sens

orSh

ield

External setpoint

or actual value 2

Ext.off

MPI MPI

SSM SBM

Pot.-freemessages

P

J

Bridgeor

Ea

rth

Off

On

X1 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24SSM SBMSensor Analog IN 1 Ext. off WM

Electroderelais

or

Frost-guard

or

Waterlevel-reglulator

Terminal diagram drives CR system (P2 � 4 kW) Terminal diagram drives CR system (P2 5.5 kW)

X4 10 11 12 13 14 X5 15 16 17 18 19

U V W U V W

WSK WSK

Pump 1/3/5

Bridge or ther- mistor or

Pump 2/4/6

Bridge or ther- mistor or

Bridge

orTher-

mistor

or

WSK

X2 1 2

3 ~

X1 PE PE 1 2 3 PE PE 4 5 6 PE

102

U1V1W1

W2U2V2

Pump 1...6P = ...kWI = ...A

TTerminal diagram base board CRn system (for pump drives 1�230 V)

Bridgeor

SSM

Pump 1...4P = ...kWI = ...A

TOP-E or

openor

WSKor

Pot.-freeNC contact

SSM Pump orStart relay

In0.......10V

Stratos0.......10V

1 ~M

L N PE

1)

On+ -

CR-IPG X3 / X4

CR-IPE X1 / X2

Required for Stratos IF-Modul with 0...10 V input(IF-Modul Stratos SBM, Stratos Ext. Min, Stratos Ext. Aus)

On-sitepower supply

Setpoint 1)

Page 241: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

241

Switchgears and control devicesWilo-Comfort control systems CR, CRn, CC

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Terminal diagrams Wilo-CR, Wilo-CRn, Wilo-CC

Switc

hgears

and

control

devices

Pump management

Terminal diagram expansion board CRn system (for pump drives 3�400 V)

Bridgeor

SSM

orPump 1...6P = ...kWI = ...A

openor

Setpoint inputsof the pump,see table

WSK or

Pot.-freeNC contact

SSMPump or

Startrelayor

3 ~M

L1 L2 L3 PE

SetpointOn+ -

CR-IPG X3 / X4

CR-IPE X1 / X2

On-sitepower supply

Star-delta starter

Terminal diagram CC-HVAC, direct starting, with frequency converter

L1X0

Mains

Feed Pumps(Output)

X1 X2 X3L2 L3 654321

L1 L2 L3 WVUWVU

Sensor ...

X498765432

Extern

On/

Off

Anti-

freeze

Sensor

(+)

Sensor

(IN

)

Analogue

In (+

)Analogue

In (I

N)

Actual

value

(+)

Act.

value

(GND

)f (

+)

f (G

ND

)

GND

1X5

4321654321

Pump 1 Pump 2Pump 1 Pump 2

Pumps(WSK)

Analogueinputs

4321

SBM

Pot.-freesignals

SSM

SBM SSM

Terminal diagram CC-HVAC, �-�-starting, with frequency converter

L1X0

Netz Pump 1 Pump 2

Feed Pumps(Output)

X1 X2 X3L2 L3 121110987654321

L1 L2

1X9

Ventilator

2

L NL3 V2U2W2W1V1U1V2U2W2W1V1U1

Sensor ...

X498765432

Exte

rn O

n/O

ff

Ant

i-fr

eeze

Sens

or (+

)Se

nsor

(IN

)

Ana

logu

e In

(+)

Ana

logu

e In

(IN

)

Actu

al v

laue

(+)

Act.

val

ue (G

ND

)f (

+)

f (G

ND

)

GN

D

1X5

4321654321

Pump 1 Pump 2

Pumps(WSK)

Analogueinputs

4321

SBM

Pot.-freesignals

SSM

SBM SSM

Page 242: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

242 Subject to change 09/2008 WILO SE

Switchgears and control devicesWilo-Comfort control systems CR, CRn, CC

Terminal diagrams Wilo-CR, Wilo-CRn, Wilo-CC

Switchgears and control devices Wilo-Comfort control systems CR, CRn, CC Terminal diagrams Wilo-CR, Wilo-CRn, Wilo-CC Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-CRn system, assignment of the setpoint outputs: 1. at the CRn control device / 2. at the pump to be controlled

Pump type Analoguecontrol signal

1. Setpoint outputs, CRn:

+ -

2. Setpoint inputs, pump:

IL-E...BF R1 (from year of construction 08/2002 to 02/2003) 0 - 10 V 2 4 GND

IL-E...BF R1 (from year of construction 08/2002 to 02/2003) 0 – 20 mA 2 4 GND

IL-E...BF R1 (from year of construction 03/2003) 0 - 10 V 2 7 GNDIL-E...BF R1 (from year of construction 03/2003) 0 – 20 mA 2 7 GNDIL-E... R1 (from year of construction 01/2003) 0 - 10 V 1 (0 - 10 V) 2 (GND)IL-E... R1 (from year of construction 01/2003) 0 – 20 mA 4 – 20 mA 2 (GND)IP-E – 0 - 10 V 1 2IP-E – 4 – 20 mA 1 2

Page 243: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

243

Switchgears and control devicesSwitchgears

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Signal transmitters and accessories

Switc

hgears

and

control

devices

Pump management

Switchgears and control devices Switchgears Signal transmitters and accessories Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo DDG signal transmitter

(Dimensions in mm), fastening elements onsite

Signal transmitter for wall-mounted instal-lation for infinitely variable speed control according to the differential pressure.With built-in pressure-surge throttles, 2 DIN 3862, � 6 mm cutting-ring unions, 5m connection cable to the switchgear1) (3 x 0.75mm2), 2 angle cutting-ring unions R 1/8 x � 6 mm.1) Longer distances to be extended by cus-tomer up to 25 m: x 0.75 mm2, shielded, up to 250 m: 3 x 1.5 mm2, shielded

Top view

DDG 10 to 100 (DDG 2 without illustration)

Maximum operating voltage: 15 – 30 VDCCurrent output: 4 – 20 mAMaximum load resistance: 500 Pressure measurement ranges:2) 3)DDG 2:DDG 10:DDG 20:DDG 40:DDG 60:DDG 100:

000000

totototototo

0.2 bar*1.0 bar2.0 bar4.0 bar6.0 bar

10.0 bar*2)Other pressure measurement ranges on request3)Selection of pressure measurement range according to the pump duty point* not with VR-HVAC

Power consumption: 1.5 WProtection class: IP 54Maximum pressure rating:

25 bar

Fluid temperature: 0 °C to +70 °CAmbient temp.: 0 °C to +40 °C

DDG transducer

- +24V=

~

CR4-20 mA 4-20 mA

9 10

4 2

7 1

+

-

+

-

1

2

+

+

>

230V 50HzMeasuring transformer DDG

230V 50Hz

Transformer DDG

Wilo-signaltransmitter DDG

123

max. 250 m (2 x 1.5 mm2) max. 750 m (2 x 1.5 mm2)

Transducer for wall-mounted installation for amplifying signals from the Wilo DDG signal transmitter for cable lengths in excess of 250m.Delivery incl. DDG power supply unit.

Signal cable

Operating voltage: 230 V/50 HzCurrent input/output: 0 – 20 mAMax. back-up fuse: 10 AMaximum input resistance: 50 Maximum load resistance: � 600

Maximum power con-sumption:

5 VA

Protection class: IP 54Ambient temperature: 0°C to + 40°C

Input: 2 x 1.5 mm2, 250 m max. length, shielded

Output: 2 x 1.5 mm2, 750 m maximum length, shielded

Page 244: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

244 Subject to change 09/2008 WILO SE

Switchgears and control devicesSwitchgears

Signal transmitters and accessories

DDG power supply unit

Fastening elements onsite

Power supply unit for wall-mounted instal-lation for power supply of the DDG signal transmitter.

Operating voltage: 230 V/ 50 HzOutput voltage: 24 V DCOutput current: 0 – 20 mA

Protection class: IP 54Ambient temperature: 0°C to +40°C

Outdoor temperature sensor KTY/PT 100

Signal transmitter for wall-mounted instal-lation for outdoor temperature measure-ment.

Required: Connection line (provided by the customer)up to 25 m: 3 x 0.75 mm2, shieldedup to 100 m: 3 x 1.50 mm2, shieldedup to 250 m: 3 x 2.50 mm2, shielded

>Technical data38

4,2

5365

35

50

M16

65

Protection class: IP 65Temperature range: –25°C to +80°C

KKTY 10 temperature board

Terminal diagram, KTY 10 temperature board

Additional board for upgrading Wilo-CR/CRn system switchgear series for use of the con-trol modes

• Differential temperature control (�T)• Feed/return temperature control (±T)• Differential pressure – temperature-super-imposed (�p-T)

3 analogue inputs for TSG temperature sen-sors:

• Feed temperature (+T)• Return temperature (–T)• Temperature setpoint (T)

Fixation material, CAN bus cable and 2 TSG temperature signal transmitters are included in the scope of delivery.

>Technical data

Feed

tem

pera

ture

Retu

rnte

mpe

ratu

re

Exte

rnal

tem

pera

ture

X3 1 2 3 4 5 6+ - + - + -

T (feed) T (return) T (external)

Measurement range: ±T: - 20 ... +150°C�T: 10 K

Resolution: 10 bitsAccuracy: 0.2% of upper limit

+ transmitter toler-ance

Ambient temperature:

0 °C to +40 °C

Dimensions: 100 mm x 120 mmWeight: approx. 0.5 kg

Page 245: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

245

Switchgears and control devicesSwitchgears

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Signal transmitters and accessories

Switc

hgears

and

control

devices

Pump management

TSG signal transmitter

Signal transmitter for pipe attachment for temperature measurement included in the scope of delivery of the KTY 10 temperature board. With 2 spring fasteners for attach-ment to pipes up to DN 100, 1 tube of ther-mal conducting glue, 5 m connecting cable for switchgear 1) (2 x 0.75 mm2, shielded)

70

15

1) Longer distances to be extended by customer

up to 25 m: 3 x 0.75 mm2, shielded, up to 100 m: 3 x 1.50 mm2, shielded, up to 250 m: 3 x 2.50 mm2, shielded

KTY 10 PTC thermistor- at +25 °C: 2 k - at +90 °C: 3.09 k Max. current: 2 mA

Protection class: IP 43Temperature range: 0°C to +150°C

Temperature board PT 100

Terminal diagram, PT 100 temperature board

Additional board for upgrading switchgears of the Wilo-CR/CRn system series for use of the control modes

• Differential temperature control (�T)• Feed/return temperature control (±T)• Differential pressure – temperature-super-imposed (�p-T)

3 analogue inputs for PT 100 temperature sensors in 2-/3- and 4-conductor technol-ogy to be provided by the customer:

• Feed temperature (+T)• Return temperature (–T)• Temperature setpoint (T)

Fixation material and CAN bus cable are in-cluded in the scope of delivery.

> Technical data

Feed

te

mpe

ratu

re

Retu

rn

tem

pera

ture

Exte

rnal

tem

pera

ture

X3 1 2 3 4 5 6 7 8 9

T (feed) T (return) T (process) + - + - + -

Two-wire circuit

Three-wire circuit

Measurement range: ±T: - 20 ... +150 °C�T: 5 K

Accuracy: ± 2 K (in relation to standard values in accordance with DIN IEC 751)+ transmitter toler-ance

Ambient temperature:

0 °C to +40 °C

Dimensions: 100 mm x 120 mmWeight: approx. 0.5 kg

DDC board

Terminal diagram, DDC board

Additional board for upgrading switchgears of the Wilo-CR/CRn system series for re-mote control by external monitoring units (e.g. BA or DDC substation).

1 analogue input for external correcting var-iable (speed adjustment for DDC operation)8 digital inputs for connection of an external potential-free button for

• Peak-load cut-in• Peak-load deactivation• Pump cycling• Setpoint changeover• Acknowledgement of the collective fault signal

• Parameter record switching• Control input, 0/ 2 -10 V or 0 / 4 - 20 mA• Signal input DIG 3

Fixation material and CAN bus cable are in-cluded in the scope of delivery.

S1

0/4…20 mA

0…10 V

UI

SL- SL- PT SW External Param. Analogue ZU AB 1/2 Quit 2 IN 2

Peak

-loa

d cu

t-in

Peak

-loa

d de

acti

vati

on

Pum

p D

uty

Cyc

ling

Setp

oint

ch

ange

over

Exte

rnal

faul

t co

nfirm

atio

n

Cha

nge

of

para

met

er re

cord

Ana

logu

e, e

xter

nal

X3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

1617

1819

In – +

DIG

.3Re

s.2 Analogue input: Correcting variable:

Measurement ran-ge:

0 – 10 V,0 / 4 – 20 mA(= min.- max. speed)

Input resistance: 10k or 50 Resolution: 10 bitsAccuracy: 0.2% of upper limit

+ transmitter tole-rance

Digital inputs:Input level: 24 VDC / 1 mADielectric strength: 250 VACMaximum cable length:

100 m

Terminal cross-sections:

1.5 mm2

Ambient temp.: 0 °C to +40 °CDimensions: 100 mm x 120 mmWeight: approx. 0.5 kg

Page 246: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

246 Subject to change 09/2008 WILO SE

Switchgears and control devicesSwitchgears

Signal transmitters and accessories

Control board

Terminal diagram, control board

Additional board for upgrading switchgears of the Wilo-CR/CRn system series for Manu-al – 0 – Automatic operating mode selec-tion for a maximum of 2 pumps (e.g.: 5-pump system requires 3 control boards). Switchover for each pump via potential-free control switches provided by the customer.

Manual – 0 – Automatic switchover via po-tential-free two-way NO contacts provided by the customer with "Off" middle position for each pump.Operating mode:

Connection for repair switches provided by the customer with auxiliary contact:

Fixation material and CAN bus cable are in-cluded in the scope of delivery.

Signal board 1 – 2

Terminal diagram, signal board 1 – 2

Additional board for upgrading switchgears of the Wilo-CR/CRn system series for indi-vidual run and single fault signals for single and double pump systems.

• Potential-free signalling contacts for opera-tion (NO contact) and fault (NC contact) of: pump 1, pump 2, frequency converter

• Signals for the digital inputs DIG2 or DIG3, e.g. frost (heating) or low water (pressure boosting)

• Analogue output for actual speed value or actual value transmitter (can be preselect-ed)Fixation material and CAN bus cable are in-cluded in the scope of delivery.

Pump 1/3/5 Pump 2/4/6

Pump 1/3/5 Pump 2/4/6

Man

ual

oper

atio

n

Rele

ase

Con

trol

func

tion

Man

ual

oper

atio

n

Rele

ase

Con

trol

func

tion

X3 1 2 3 4 5 6 7 8 9 10 11 12

Man

ual

Rele

ase

Con

trol

func

tion

Man

ual

Rele

sae

Con

trol

fu

ncti

on

– Manual: Pump in mains operation– 0: Pump Off– Automatic: Pump enabled for control

mode

– closed: Pump enabled– open: Pump disabled

Selector switch: P1 / P2, P3 / P4, P5 / P6

Control inputs: 2 x repair switches (On / Off for each pump)2 x control switches (Manual – 0 – Au-tomatic for each pump)

Input level: 24 VDC / 1 mADielectric strength: 250 VACMaximum cable length:

100 m

Terminal cross-sec-tions:

1.5 mm2

Ambient temp.: 0 °C to +40 °CDimensions: 100 mm x 120 mmWeight: approx. 0.5 kg

Pump 1 Pump 2 Transformer WM Analog OUT

Pump 1 Pump 2 FU

Ope

rati

ng

Dis

turb

ance

X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Ope

rati

ng

disb

urba

nce

Ope

rati

ng

dist

urba

nce

Low

wat

er

+ -

DD

G

or

spee

d

Analogue output: Actual valueMeasurement ran-ge:

0 – 10 V, 0/4 – 20mA (speed or transmit-ter)

Input resistance: 10 k or 50 Resolution: 10 bitsAccuracy: 0.2% of upper limit

+ transmitter tole-rance

Signalling contactsRating: max. 250 VAC/2 A

min. 12 VDC/10mAMaximum cable length:

100 m

Terminal cross-sec-tions:

1.5 mm2

Ambient temp.: 0 °C to +40 °CDimensions: 120 mm x 120 mmWeight: approx. 0.5 kg

Page 247: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

247

Switchgears and control devicesSwitchgears

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Signal transmitters and accessories

Switc

hgears

and

control

devices

Pump management

Signal board 3 – 6

Additional board for upgrading switchgears of the Wilo-CR/CRn series for individual run/single fault signals for three-pump to six-pump systems (signal board 1 – 2 also re-quired).

• Potential-free signalling contacts for opera-tion (NO contact) and fault (NC contact) of: pump 3, pump 4, pump 5, pump 6Fixation material and CAN bus cable are in-cluded in the scope of delivery.

Terminal diagram, signal board 3 – 6

Pump 3 Pump 4 Pump 5 Pump 6

Pump 3 Pump 4 Pump 5 Pump 6

Ope

rati

ng

dist

urba

nce

X1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Ope

rati

ng

dist

urba

nce

Ope

rati

ng

dist

urba

nce

Ope

rati

ng

dist

urba

nce

Signalling contactsRating: max. 250 VAC/2 A

min. 12 VDC/10mATerminal cross-sec-tions:

1.5 mm2

Ambient temp.: 0 °C to +40 °CDimensions: 120 mm x 120 mmWeight: approx. 0.5 kg

Page 248: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

248 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsPump control

Series overview Wilo interface modules

Wilo-Control pump management systems Pump control Series overview Wilo interface modules Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-IF-Modul PLR

• Retrofit plug-in module for pump types with IR interface-Wilo-TOP-E/ED-Wilo-VeroLine-IP-E-Wilo-VeroTwin-DP-E-Wilo-CronoLine-IL-E-Wilo-CronoTwin-DL-E

• Serial digital PLR interface for connection to BA building automation via:-Wilo interface converter or- company-specific coupling modules

• Communication-capable dual pump management (according to time, load and fault, only TOP-E/-ED and IL-E/DL-E)

Wilo-IF-Modul LON

• Retrofit plug-in module for LON-compatible pump types with infrared interface-Wilo-TOP-E/ED-Wilo-VeroLine-IP-E-Wilo-VeroTwin-DP-E-Wilo-CronoLine-IL-E-Wilo-CronoTwin-DL-E

• Serial digital LON interface for connection to BA building automation via LONWorks networks:- LONTalk protocol- LONMark conformity

• Communication-capable dual pump management (according to time, load and fault, only TOP-E/-ED and IL-E/DL-E)

Page 249: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

249

Wilo-Control pump management systemsPump control

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series overview operating and service devices

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Pump control Series overview operating and service devices Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-IR-Module

• Remote control with infrared interface for electronically controlled Wilo pumps• Commissioning and diagnostic instrument/tool• Adaptable into the SDIO slot of a Pocket PC (PDA)• Wilo software is compatible with Microsoft Windows mobile operating system• Extension of pump functions• Enables the export, storage and printout of pump data records

Wilo-Dia-Log

• The complete package for commissioning, service, maintenance and documentation of elec-tronically controlled Wilo pumps with infrared interface, consisting of:-Wilo-IR-Module, complete- Pocket PC, preconfigured with the Microsoft Windows Mobile™ Version 5.0 operating system and "IR-Module" user software, including power supply unit

-Data transfer cable from the Pocket PC to a computer (USB interface)- Portable printer, including power supply unit and paper roll (for roll width of 58 mm)-Documentation and software

Wilo-IR-Monitor

• Remote control with infrared interface for electronically controlled Wilo pumps• Commissioning and diagnostic instrument/tool• Extension of pump functions• Rotation test unit for all pump motors and standard motors

Page 250: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

250 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsPump control

Series overview building automation (BA)

Wilo-Control pump management systems Pump control Series overview building automation (BA) Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-Control AnaCon

• Analogue interface converter for the universal connection of communication-capable Wilo pumps with serial, digital PLR interface to onsite monitoring units in accordance with VDI 3814.

Wilo-Control DigiCon

• Digital interface converter for the connection of communication-capable Wilo pumps with se-rial digital PLR interface to onsite monitoring units with digital RS 485 interface.

Wilo-Control DigiCon-A (manual oper-ation level)

• Manual control panel for Wilo-Control DigiCon for the extended connection communication-capable Wilo pumps with serial digital PLR interface to operating levels onsite in accordance with VDI 3814.The Wilo-Control DigiCon-A manual control panel allows the overriding control of pumps con-nected to the Wilo-Control DigiCon interface converter.

Wilo-Control bus-Box

• Junction box or distribution box for setting up a CAN bus system with connection of the nodes via short spur lines.

Page 251: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

251

Wilo-Control pump management systemsPump control

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Building automation planning guide

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Pump control Building automation planning guide Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsBuilding automation (BA)Automatically controlled processes have become essential in modern buildings. This particularly applies to all building and technical sys-tems in the fields of:

• Heating systems• Cooling systems• Ventilation systems• Heating pumps• Combined heat and power plants • Water supply• Sewage disposal etc.

The BA is responsible for controlling the dependencies between the various sections involved in the technical building equipment (TGA). It is in particular facility management that requires the intersectional exchange of information and data in order to run the building or es-tates with optimum efficiency and economy. As field devices, pumps are to be seen as components with high power consumption that are indispensable for operations in the TGA. The operational reliability and economic efficiency of pumps and pump systems are ensured by their central availability and monitoring.Due to technical progress in the fields of electrical engineering/elec-tronics, potential-free contacts and analogue unit signals are being successively replaced by bus systems.

Fig.: Building automation - diagram

M M MM

Operating station /

operating unit

Network

Net

wor

k

Network

Network

Programmingunit

Data interfaceunit

Data processingapparatus /

server station

Operating unit Communications unit / controller /

ASR

Application-specificcontrol and

regulatory unit

Controller / automation station /

ASR

Data interfaceunit

Systemfor special

applications

Systemfor special

applications

Programmingunit

Operating station /

operating unit

Data interfaceunit

Space / operating unit

Local overridingoperating units

Systemfor special

applications

Au

tom

ati

on

Ma

na

ge

me

nt

Fie

ld

Venetian blinds / protection against sunlight

Light / dimming

Connections within the functional levels

Connections between the functional levels

Page 252: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

252 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsPump control

Building automation planning guide

Integration into the building automationDepending on the nature and extent of a BA system, different com-munications connections are required to transfer the signals, control commands and data to the pump system to be monitored.The design and functions of BA a system are defined precisely in VDI 3814. The scope of communication is decisive for determining whether potential-free contacts or analogue signals (2 control cables are required for each piece of information) or bus systems (all data via one bus line) are used for data transmission.Wilo pumps as well as their optional accessories are equipped with control terminals at which internal relay signals are available in ac-cordance with VDI 3814 requirements.

Functional principle of a collective fault/collective run signal*:

It is also possible to implement external control functions such as Overriding Off and Overriding Min. via potential-free contacts pro-vided by the customer.For this, there are the following combination options:

• Overriding Off:- Stratos/Stratos-Z/Stratos-D/Stratos-ZD with IF-Modules- TOP-E/-ED (P2 350 W)- CronoLine-IL-E/CronoTwin-DL-E-VeroLine-IP-E/VeroTwin-DP-E

• Overriding Min.:- Stratos/Stratos-Z/Stratos-D/Stratos-ZD with IF-Modules

• Overriding Off, Overriding Max and Overriding Min:- Stratos/Stratos-Z/Stratos-D/Stratos-ZD with Stratos IF-Modules PLR and analogue interface converter

- TOP-E/-ED with PLR IF-Modules and WILO-Control AnaCon-VeroLine-IP-E/Vero-Twin-DP-E with PLR IF-Module and Wilo-Control AnaCon

- CronoLine-IL-E/CronoTwin-DL-E with IF-Modules PLR and Wilo-Control AnaCon

In addition to these functions, the new pumps with communication capabilities feature the option of specifying an extensive number of actual physical values. The latest sensor technology records hydraulic and electrical pump data and provides it via a PLR or LON serial digital interface of the BA. This entire information can be exchanged be-tween a pump with communication capability (accessory modules re-quired) and another BA unit via a 2-wire cable. Pumps with communication capability are:

• Stratos/Stratos-Z/Stratos-D with IF-Modules• TOP-E/-ED with IF-Modules • CronoLine-IL-E/CronoTwin-DL-E with IF-Modules• VeroLine-IP-E/VeroTwin-DP-E with IF-Modules

System integrationThe demands in terms of communication capabilities and functions are guided through ever more complex hierarchies of building auto-mation as a result of the rising demands for technical building equip-ment (TGA) in large building projects. This leads to a situation where components at the field level are becoming increasingly technically sophisticated, because - among other things - they also fulfil func-tional requirements at the automation level. In order to reduce instal-lation costs and thus investment costs of technical building equip-ment, and thus also those associated with pump systems while at the same time increasing their economic efficiency and reliability, it is necessary to use systems with "open communication" and "distribut-ed intelligence".

The Wilo-Control automation and control system offers:• Monitoring and control in accordance with VDI 3814 with- Potential-free contacts-Analogue signals

• Serial digital PLR interface (Wilo-specific hardware and protocol) of pumps with communication capability is connected in a star shape via a 2-wire cable to a Wilo interface converter or a company-specific coupling module (I/O module). This connection permits transmission lines of up to 1000 m. Additional advantages are:- Twisting protection- Resistance to interference

Mains volt-age

Collective fault signalSSM

Collective run signalSBM

Relay Contact Relay Contact

Off1) 0 closed 0 open

On 0 closed 1 closed

On, pump faulty

1 open 0 open

Mains voltage

Control in-put "Ext. Off"

Collective fault sig-nal SSM

Collective run signal SBM

Relay Contact Relay Contact

Off1) closedopen

00

closedclosed

00

openopen

On closedopen

00

closedclosed

10

closedopen

On, pump faulty

closedopen 1

1 open 00

openopen

0 = relay not active (without current)1 = relay activeSBM = collective run signalSSM = collective fault signal1) Failure of the control electronics is equivalent to the "Mains off" state

* Functional principle according to works setting

Input NO contact SPDT contact

Fault signal in compliance

with VDI 3814

Run signal incompliance

with VDI 3814 Connection

optional

Illustration:De-energised idle state (relay not active)

Page 253: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

253

Wilo-Control pump management systemsPump control

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Building automation planning guide

Switc

hgears

and

control

devices

Pump management

- Small cross-sections (0.75 mm2)- EMC protection at both ends-Galvanic isolation- Interference voltage resistance up to 250 VAC

• Serial bus-capable RRS 485 interface (standard hardware, Wilo-spe-cific protocol) with digital interface converter for communication with digital monitoring units. The data protocol is to be coordinated with the respective BA manufacturer.

• Serial bus-capable LLON interface with LONTalk protocol and FTT10A transceiver type for connecting electronically controlled LON-capa-ble Wilo pumps with infrared interfaces to LONWorks networks. The LONWorks technology offers installation advantages such as:-Twisting protection-Resistance to interference- Small cross-sections (0.75 mm2)- EMC protection at both ends-Galvanic isolation- Interference voltage resistance up to 250 VAC- Freely selectable topology.

LON is an open, non-manufacturer-specific system which enables open, intersectional communication between different components and systems. It thus offers advantages to planning engineers, install-ers and operators, such as:

• Intersectional integration• Is non-manufacturer-specific• Creation of functional added values• Avoidance of installation and planning errors due to standardised da-ta interface (prerequisite: no varying transmission media)

• Reduction of installation expenses compared to stand-alone systems• Reduced investment costs due to multiple use of sensors• No expensive gateway solutions are required for data exchange be-tween stand-alone systems

• Flexibility in the event of modifications and retrofitting• Reduced operating costs due to intelligent energy management• Efficiency and operational reliability due to hydraulic load manage-ment in heating/ventilation/air-conditioning installations

• Overall transparency due to centralised displays, interventions and monitoring

• Standardised and transparent operation of equipment and technical systems

• LONWorks enables 2 directions of communication:-Vertical communication between components at the field level and automation stations at the automation level

- Horizontal communication between components of the field level.

Horizontal communication in particular allows decentralised struc-tures to be set up, which operate without higher-level automation station. It has thus become possible to implement previously ex-pensive control tasks with significantly lower installation expenses, e.g. a controlled pump with communication capability can ex-change data directly via LON with a valve, a differential-pressure sensor or a boiler control system and conduct control tasks. At the same time, the pump is able to send electrical and hydraulic operat-ing data, for statistical evaluation, and, if necessary, any fault and run signals to the higher-level primary control unit or receive over-riding commands from this primary control unit.

Communication takes place according to the standardised LONTalk protocol and uses the defined network variables of the LONMark functional profile "Pump Controller Object for HVAC Applications" (8120_10.pdf).

• Serial bus-capable CAN interface as the new Wilo standard for con-nection to a CAN bus system. The protocol meets the CANopen standard (EN 50325-4). Compared to the data items of the LONTalk protocol, the CAN protocol uses newly defined data items, such as e.g.-Times for pump kick, pump cycling, fault shutdown delay-Adjustment of the SSM/SBM performance, pump management for up to 127 pumps

-Histogram (statistics), and much more:The complete list of parameters can be downloaded from the WILO website.

• The data items of these two bus protocols are nevertheless compara-ble at the functional level (selection of control mode, setpoint speci-fication, etc.). With its high transmission speed (125 kBit/s), however, CAN does offer a few advantages compared to the LON field bus sys-tem:- Integration into any CAN bus system, since the protocol complies

with the CANopen standard (EN 50325-4).-Communication options with CAN-capable third-party products-Communication options with Wilo I/O modules and Wilo gateways; due to the line structure of the CAN bus system, the amount of ca-bles required is reduced to a minimum.

• The following aspects are to be observed when planning and install-ing a CAN bus line:-A maximum of 127 consumers can be connected to and addressed on a CAN bus line.

-With 64 pumps and 32 I/O modules, simplified addressing and con-nection options are possible.

-When there are more than 64 pumps on a CAN bus line, the pumps must be configured with a commercially available CANopen config-uration program.

-A special, shielded CAN bus cable is used for cabling. This shield is to be placed carefully on both sides in order to avoid communica-tion disruptions on the bus. This is done at the pumps with EMC ca-ble connections which are enclosed with the Stratos CAN IF-Mod-ule. Cable clips that enclose the braided shield are to be used in the switch cabinet.

- For the configuration of the various bus topologies, the maximum line lengths are to be taken into account (cf. fig. 1, fig. 2, fig. 3):

• Nodes may be structural elements and components (including ones from third-party sources) such as:- Single pumps, double pumps, pump systems with CAN interface

Maximum line lengths with different bus topologies

Max. overallline length Lt

Max. line length of an individual spur line L

d

Max. cumulative length of all spur

lines

[m] [m] [m]

200 10 50

Page 254: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

254 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsPump control

Building automation planning guide

- Pressure sensors, differential pressure sensors, temperature sensors- External controllers- Routers, repeaters, gateways- I/O modules

• The bus must be sealed off at the last node of the bus line with ap-propriate resistances. The Stratos CAN IF-Module with two DIP switches is possible with the pumps.

• The use of CAN bridges with interface in accordance with ISO11898-2 is recommended for extending the bus length. The use of repeaters is not recommended.

Operating data management by BAOperating data management by the BA system allows the recording and storage of cyclic and event-specific data, e.g.:

• Maximum output data for �p and Q• Minimum output data for �p and Q• Current power consumption P1• Operating hours• Cumulative power consumption• Status signals• Fault signals with specification of date, time and cause.

The multitude of listed information and functions enables specific energy and maintenance management and thus contributes to re-ducing costs. Overall efficiency values and performance figures can thus be determined, e.g. by performance and work values in relation to the heating load to be measured.

Fig. 1: Line structure with connection of all nodes via short spur lines

Fig. 2: Line structure with connection of individual nodes via short spur lines

Fig. 3: Pure line structure

Node 3Node 2 Node n

Node 1 Node 127Bus-Box

Bus-Box

Bus-Box

Lt

Ld

Node 3

Node 2

Node nNode 1 Node 127Bus-Box

Ld

Lt

Node 3Node 2 Node nNode 1 Node 127

Lt

Page 255: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

255

Wilo-Control pump management systemsPump control

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-IR-Module

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Pump control Series description Wilo-IR-Module Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsWilo-IR-Module

Fig.: Wilo-IR-Module: Operating and service unit for pump monitoring

ApplicationThe Wilo-IR-Module is, in conjunction with a commercially available PDA or Pocket-PC, a modern operating and service unit for wireless, convenient remote control of the electronically controlled Wilo pumps with infrared interface of the series Wilo- ...

- Stratos/Stratos-Z/Stratos-D/Stratos-ZD- TOP-E/-ED-VeroLine-IP-E-VeroTwin-DP-E- CronoLine-IL-E- CronoTwin-DL-E

The extensive pump functions can be adjusted via the IR-Module by wireless remote control using the PDA/Pocket-PC. The pumps send back detailed operation and status data which are displayed in a readily comprehensible and clearly legible fashion on the monitor of the PDA/Pocket-PC. A program created by Wilo guarantees a clear structure for all operation functions. Pump-specific data sets can be saved and archived as text (file format .rtf) or as tables (file format .xls), together with information regarding installation site, date and time.The user continues to have access to all of the functions and pro-grammes that a PDA/Pocket-PC offers. The analysis and adjustment possibilities of the IR-Module are guaranteed to installers, planners and operators that electronically controlled pumps of the above-named series can be adjusted in optimum fashion in heating, ventila-tion and air-conditioning systems and that they can be documented throughout their entire life cycles.

VersionA PDA or Pocket PC is required to operate the IR-Module that must meet certain requirements:

- SDIO-capable cart slot-Windows Mobile version 5.0 operating system or higher- 5 MB free memory (minimum)- Bluetooth interface for printer (optional)- CPU with 300 MHz pulse frequency- 64 MB ROM- 32 MB RAM-Display: 240 x 320 pixels

Updating the programThe current software for the IR-Module and the PDA/Pocket PC is available for download at the website: www.wilo.com.

Automatic connection setupInformation is exchanged between IR-Module and pump(s) in wire-less fashion via an infrared interface with 33 kHz or 455 kHz. The slow transmission with 33 kHz guarantees the compatibility of all ex-isting electronically controlled pumps with infrared interfaces. In the event of installation conditions in narrow spaces (e.g. a number of pumps installed closely side-by-side), an automatic connection set-up prevents the simultaneous activation of different pumps and thus initiates the correct data exchange between the desired pump and the IR-Monitor. No manual addressing of the individual pumps is re-quired for IR communication.

Data storageOperating data recorded immediately prior to a fault is stored in the pump and can be further used for diagnostic purposes with the IR-Module and the PDA/Pocket PC.

Statistical functionsThe hydraulic duty point of the relevant pump can be viewed with the IR-Module in a statistical histogram. The hydraulic load of the pump can thus be monitored during a definable operating period.

Technical data

Wilo-IR-Module

Protection class IP 43

Vibration resistance DIN EN 60068-2-6

Operating temperature -10 °C to +40 °C

Storage temperature -20 °C to +70 °C

Transmission and reception range max. 8 m, 15 °C

Display 50 x 50 mm,with backlight that can be swit-ched on

Power supply provided viaPDA/Pocket PC

Service life depends on the selected PDA/Pocket PC

Data buffer EEPROM

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Page 256: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

256 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsPump control

Series description Wilo-IR-Module

Main menuThe main menu of the IR-Module provides access to ten function menus.

Function menu 1: "Communication"This function menu automatically establishes a con-nection between the IR-Module and the pump. All of the pumps detected in a single group (e.g. distributor) can be activated selectively here.

Function menu 2: "Display/Operating data"Hydraulic and electrical operating data is displayed in this function menu. Status signals and information on the pump mode can be accessed.

Function menu 3: "Operation"Operating data and status information are displayed in this function menu. Settings such as the selection of the control mode and setpoint changes can be defined at the same time.

Function menu 4: "Statistics"Statistical data is displayed in this function menu, which can also be reset here. A histogram shows the distribution in percent of the volume flow throughout the operating time. This makes the hydraulic load of the pump transparent.

Page 257: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

257

Wilo-Control pump management systemsPump control

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-IR-Module

Switc

hgears

and

control

devices

Pump management

Function menu 5: "Service"This function menu enables detailed fault diagnostics with the stored operating data that was available prior to the last fault that occurred. The fault memory (FIFO principle) of the pump is read out and various self-tests can be carried out at the pump.

Function menu 6: "Settings"This function menu allows you to select a specific lan-guage and international or US units for displaying op-erating data. In addition, the IR-Module software ver-sion can be updated.

Function menu 7: "Print"Data records of pumps can be printed out in this func-tion menu. Data transfer to a mobile printer is imple-mented by means of a Bluetooth interface. The printer must be configured separately.

Function menu 8: "Open"Saved data records for pumps are opened in this func-tion menu.

Page 258: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

258 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsPump control

Series description Wilo-IR-Module

Wilo-Dia-Log

Fig.: Wilo-Dia-Log

• The complete package for commissioning, service, maintenance and documentation of electronically controlled Wilo pumps with infrared interface, consisting of:-Wilo-IR-Module, complete- Pocket PC, preconfigured with the Microsoft Windows Mobile™

Version 5.0 operating system and "IR-Module" user software, in-cluding power supply unit

-Data transfer cable from the Pocket PC to a computer (USB inter-face)

- Portable printer, including power supply unit and paper roll (for roll width of 58mm)

-Documentation and software

Function menu 9: "Save"Pump data records are saved using this function menu along with details concerning installation-specific designations. The date and time are automatically re-corded in file names, so that multiple storage of a data record results in a chronological order.The files are saved to the PDA and can be transferred to the PC.

Function menu 10: "Snap shot"Important data of the pump (from the CAN version) or the pump system can be displayed in summarised form here.

Page 259: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

259

Wilo-Control pump management systemsPump control

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Series description Wilo-IR-Monitor

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Pump control Series description Wilo-IR-Monitor Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsWilo-IR-Monitor

Fig.: Wilo-IR-Monitor; operating and service unit for pump monitoring

ApplicationModern operating and servicing equipment for user-friendly remote control of the electronically controlled Wilo pumps with infrared in-terface of the following Wilo series:

- Stratos/Stratos-Z/Stratos-D/Stratos-ZD- TOP-E/-ED-VeroLine-IP-E-VeroTwin-DP-E- CronoLine-IL-E- CronoTwin-DL-E

The IR-Monitor can be used in conjunction with all conventional glandless and glanded pumps without IR interfaces. It is capable of checking the direction of rotation, the rotating-field frequency and the current operating status of each pump and standard motor with the IR-Monitor.The extensive pump functions can be remotely monitored by wireless control with the IR-Monitor. All operating steps and status reports are clearly graphically displayed by a LC display.The functionality of the IR-monitor is closely linked with the proper-ties of the high-efficiency and/or energy-saving pumps. The opera-tion of the IR-Monitor is similar to operating the pump; that is, changes and confirmations of newly set values is done by turning and pressing the red operating button (single button operation).The functional capacity has mainly been tailored for the use by con-tractors and service personnel.

VersionIndustrial standard due to its sturdy and robust plastic casing and the scratch-resistant monitor screen. A carrying case for additional pro-tection is also included in the scope of delivery.

Automatic connection setupThe information exchange between the IR-Monitor and the pump is wireless via infrared light. In the event of installation conditions in narrow spaces (e.g. a number of pumps installed closely side-by-side), an automatic connection setup prevents the simultaneous ac-tivation of different pumps and thus initiates the correct data ex-change between the desired pump and the IR-Monitor. Manual cod-ing of the individual pumps is not required.

Data storageAny operating data recorded immediately prior to a fault is saved in the pump and can be made further use of for data diagnostic purpos-es with the IR-Monitor.

Statistical functionsThe hydraulic output (volume flow) of the relevant pump can be viewed with the IR-Monitor in a statistical histogram.The load profile of the hydraulic system is thus perceivable during the course of a defined operating period.A non-fading data storage medium (EEPROM) is available for buffer-ing preset values.

Battery monitoringThe state of the (rechargeable) batteries is monitored on a continu-ous basis. A warning is displayed on the monitor when the capacity fades.

Technical data

Wilo-IR-Monitor

Protection class IP 43

Vibration resistance DIN EN 60068-2-6

Operating temperature -10 °C to +40 °C

Storage temperature -20 °C to +70 °C

Transmission and reception range max. 8 m

Display 50 x 50 mm,with backlight that can be swit-ched on

Power supply 2 Mignon alkaline battery cells 1.5 V size AA (included in the scope of delivery)

Service life approx. 24 hrs. when on and illu-minated

Data buffer EEPROM

Emitted interference EN 61000-6-3

Interference resistance EN 61000-6-2

Technical data

Page 260: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

260 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsPump control

Series description Wilo-IR-Monitor

Main menuThe main menu of the IR-Monitor is divided into 6 function menus:

Menu 1: "Communication"This menu initiates the automatic setup of a connec-tion between the IR-Monitor and the pump. The se-lective activation of individual pumps within a group of pumps � 1000 W is also possible here.

Menu 2: "Display"System data can be read here, e.g. actual electrical and hydraulic values, operating status, operating mode, fault messages.The display always distinguishes clearly between "Sin-gle pump" and "Double pump".

Menu 3: "Operation"Data can be both displayed (current setpoint) and changed in this menu, e.g. control mode, setpoint, pump ON/OFF, disabling the manual control panel at the pump (pump ON/OFF, Ext. Off and SSM are still ac-tive).

Menu 4: "Statistics"The Statistics menu provides a clear histogram of the hydraulic output (volume flow Q) for the analysis of operating periods. This makes the load conditions of the hydraulic system visible over a definable operating period. This menu also has an operating hours and op-erating data counter.

Menu 5: "Service"The service menu gives the user the option of fault di-agnostics, fault statistics, function tests of the pump, the IR-Monitor and the serial digital interface, as well as monitoring the direction of rotation and measuring the frequency of the rotating field.These two measurements can also be conducted with all conventional pumps without IR interface.

Menu 6: "Adjust"Language selection, contrast and time-out settings, changing and activating the personal password are available to adjust the IR-Monitor to suit individual re-quirements.

Page 261: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

261

Wilo-Control pump management systemsPump control

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Function overview Wilo-IP-E/IL-E and DP-E/DL-E with Wilo-IF-Modules

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Pump control Function overview Wilo-IP-E/IL-E and DP-E/DL-E with Wilo-IF-Modules Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

• Integrated electronic performance control for operation at constant/variable differential pressure- Simplifies pump configuration-Can be adjusted to the duty point-Reduces noise and saves electricity

• Integrated full motor protection• Thermal insulation as standard• Retrofit IF-Modules for functional extension

• Integrated electronic performance control for operation at constant/variable differential pressure- Simplifies pump configuration-Can be adjusted to the duty point-Reduces noise and saves electricity

• Integrated full motor protection• Double pump switchover valve• Retrofit IF-Modules for functional extension

Wilo-VeroLine-IP-E/CronoLine-IL-E Wilo-VeroTwin-DP-E/CronoTwin-DL-E

Function table Wilo-IP-E/IL-E and DP-E/DL-E

Function VeroLine-IP-E CronoLine-IL-E VeroTwin-DP-E CronoTwin-DL-E

Electrical connection

3~400 V/50 Hz • • • •3~380 V/60 Hz • • • •Manual function

Pump On/Off • • • •Control mode setting (�p - c, �p-v, controller) • • • •Differential pressure setpoint setting • • • •Speed setting (manual control mode) • • • •

• = available, - = not available1) with 1 x IF-Module, PLR2) with 2 x IF-Modules, PLR/PLR3) with 1 x IF-Module, LON4) with 2 x IF-Modules, LON/PLR5) with 1 x IF-Module, CAN

Page 262: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

262 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsPump control

Function overview Wilo-IP-E/IL-E and DP-E/DL-E with Wilo-IF-Modules

Automatic function

Infinitely variable performance control �p-c • • • •Infinitely variable performance control �p-v • • • •Full motor protection with fault trip • • • •External control function

Overriding Off control input • • • •Control input, 0 - 10 V (remote speed adjustment) • • • •Signal and display function

Collective fault signal • • • •Collective run signal • • • •Fault signal light • • • •IR communication run signal light • • • •Fault code • • • •LC display for indicating pump data • • • •Data exchange

Infrared interface for wireless data exchange with the operating and service unit, Wilo-IR-Module/ IR-Monitor

• • • •

Serial digital PLR interface for connection to BA via Wilo interface converter or company-specific coupling modules

•1) •1) •1) •2)

Serial digital LON interface for connection to a LON-Works network •3) •3) •3) •4)

Serial digital CAN interface for connection to a CAN bus system •5) – •5) –

Dual pump management(2 x single pumps or 1 x double pump)

Main/standby mode(automatic fault-actuated switchover/time-de-pendent pump cycling)

• • • •

Parallel operation(peak load activation and deactivation) • • • •

Function table Wilo-IP-E/IL-E and DP-E/DL-E

Function VeroLine-IP-E CronoLine-IL-E VeroTwin-DP-E CronoTwin-DL-E

• = available, - = not available1) with 1 x IF-Module, PLR2) with 2 x IF-Modules, PLR/PLR3) with 1 x IF-Module, LON4) with 2 x IF-Modules, LON/PLR5) with 1 x IF-Module, CAN

Page 263: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

263

Wilo-Control pump management systemsPump control

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-IF-Modules for single pumps

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Pump control Wilo-IF-Modules for single pumps Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps1 x Wilo-IF-Module PLRPlug-in module for single pumps of the Wilo-TOP-E and Wilo-Vero-Line-IP-E/CronoLine-IL-E series with infrared interface

Additional functions• Serial digital PLR interface for connection to BA building automation

via-Wilo interface converter or- Company-specific coupling modules

• Transfer of the following data items as control commands to the pump:-Control mode �p-c -Delivery head/speed setpoint- Pump On/Off- Setback operation

• Transfer of the following data items as signals from the pump:-Actual delivery head value-Actual volume flow value-Actual consumption value-Actual output value-Actual motor current value-Operating hours-Actual speed value-Detailed fault signals- Status signals

• Double pump DP interface for integrated dual pump management of 2 x single pumps or 1 x double pump (see Wilo-IF-Modules for double pumps)

PLR

DP L N PE SSM1~230 V

Wilo-TOP-EWilo-IF module PLR

Wilo interface converter orcompany specific coupling module

0...10V In

Ext.off P1 ≥ 500 W (P2 ≥ 350 W)

+24V

Wilo-IF-module PLR

Wilo interface converter orcompany speci�c coupling module

0/4...20 mAAux, no function

2

HL MP

3 +24 V PE L1 L2 L33~400V

1 0...10 V

Ext.off

Wilo-IP-E

DP

PLR

SBM

SSM

Wilo-IF-module PLR

Wilo interface converter orcompany speci�c coupling module

0/4...20 mAAux, no function

23 +24 V

PE L1 L2 L33~400V

1 0...10 V

Ext.off

Wilo-IL-E

DP

PLR

SBM

SSM

Page 264: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

264 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsPump control

Wilo-IF-Modules for single pumps

Wilo-Control pump management systems Pump control Wilo-IF-Modules for single pumps Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps1 x Wilo-IF-Module LONPlug-in module for LON-capable single pumps of the Wilo-TOP-E and Wilo-VeroLine-IP-E/CronoLine-IL-E series with infrared inter-face

Additional functions• Serial digital LLON interface for connection to LONWorks networks• Transfer of the following data items as control commands to the pump:-Operating mode- Setpoint-Data from external sensors

• Transfer of the following data items as signals from the pump:-Hydraulic operating data- Electrical operating data- Status signals- Fault signals

• Double pump DP interface for integrated dual pump management of 2 x single pumps or 1 x double pump (see Wilo-IF-Modules for double pumps)

Standards• LONMark Application Layer Interoperability Guidelines Version 3.2• LONMark Layers 1-6 Interoperability Guidelines 3.0• LONMark Functional Profile "Pump Controller Object for HVAC Appli-cations" (8120_10.pdf)

Delivery statusThe LON IF-Module is supplied as "Application unconfigured" in ac-

cordance with the LONMark Application Layer Interoperability Guide-lines.

DocumentationThe following documentation is available to you on our homepage www.wilo.com (/Products/Wilo building automation):LONMark Functional Profile "Pump Controller Object for HVAC Appli-cations" (8120_10.pdf)

• Download application via network: *.NXE / *.APB• External interface files: *.XIF / *.XFB• Device resource files: *.ENU / *.FMT / *.FPT / *.TYP

LON

DP L N PE SSM1~230 V

Wilo-TOP-EWilo-IF module LON*

LONWorks network

0...10V In

Ext.off+24V

* The picture does not showthe actual position of the terminals

P1 500 W (P2 350 W)

Wilo-IF-module LON*

0/4...20 mAAux, no function

2

HL MP

3 +24 V PE L1 L2 L33~400V

1 0...10 V

Ext.off

Wilo-IP-E

DP

LON

SBM

SSM

* The picture does not showthe actual position of the terminals

LONWorks network

Wilo-IF-module LON*

* The picture does not showthe actual position of the terminals

LONWorks network

0/4...20 mAAux, no function

23 +24 V

PE L1 L2 L33~400V

1 0...10 V

Ext.off

Wilo-IL-E

DP

LON

SBM

SSM

Page 265: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

265

Wilo-Control pump management systemsPump control

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-IF-Modules for double pumps

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Pump control Wilo-IF-Modules for double pumps Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps2 x Wilo-IF-Modules PLRPlug-in modules for double pumps of the Wilo-TOP-ED and Wilo-TOP-E series (2 pc.) and Wilo-CronoTwin-DL-E and CronoLine-IL-E (2 x) with infrared interface

Additional functions• Serial digital PLR interface for connection to BA building automation

via-Wilo interface converter or- company-specific coupling modules

• Transfer of the following data items as control commands to the pump:-Control mode -Delivery head/speed setpoint- Pump ON/OFF- Setback operation

• Transfer of the following data items as signals from the pump:-Actual delivery head value-Actual volume flow value-Actual consumption value-Actual output value-Actual motor current value-Operating hours-Actual speed value-Detailed fault signals- Status signals

• Double pump DP interface for optional integration of a dual pump management system of 1 x double pump or 2 x single pumps, option-ally with the following functions:

-Main/standby mode for automatic fault-actuated switchover to the standby pump and automatic pump cycling after 24 hrs Operating time

- Parallel operation for efficiency-optimised (TOP-ED) and/or (DL-E) activation and deactivation of the peak-load pump according to re-quirements and automatic fault-actuated switchover to standby pump

• Included in the IF-Module PLR scope of delivery for TOP-ED/-E: 2-core connecting cable, 670 mm long

• Included in the IF-Module PLR scope of delivery for DL-E/-IL-E: 2-core connecting cable, 1800 mm long

PLR

DP L N PE 1~230 V

0...10 V In

PLR

DP L N PE

1~230 V

0...10 V In

SSMSSM

Wilo-IF module PLR Wilo-TOP-ED/-E Wilo-IF module PLR

Wilo interface converter or a company-specific coupling module.

P1 � 500 W (P2 � 350 W) P1

� 500 W (P2 � 350 W)

Ext.offExt.off+24V

+24VMA (Master) SL (Slave)

Wilo-TOP-ED/-E

Connecting cable, min. 2 x 0.75 mm2, cannot be confused

Master Slave

3 +24 V21 0...10V

0/4...20mAAux, no function

23 +24 V

0/4...20mA

PE L1 L2 L3 PE L1 L2 L33~400V 3~400V

DP

PLR

DP

PLR

SBM

SSM

SBM

SSM

1 0...10V

Connecting cable, min. 2 x 0.75 mm2, cannot be confused

Wilo-IF module PLR Wilo-DL-E/IL-E Wilo-IF-module PLR

Wilo interface converter or a company-specific coupling module.

Wilo-DL-E/IL-E

Ext.offExt.off

Aux, no function

Page 266: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

266 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsPump control

Wilo-IF-Modules for double pumps

Wilo-Control pump management systems Pump control Wilo-IF-Modules for double pumps Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsWilo-IF-Modules 1 x LON and 1 x PLRPlug-in modules for LON-capable double pumps of the Wilo-TOP-ED and Wilo-TOP-E series (2 x) and Wilo-CronoTwin-DL-E and Crono-Line-IL-E (2 x) with infrared interface. For dual pump management, a PLR module is required in addition to the LON function module.The functions of the LON module apply to the entire double pump.

Additional functions• Serial digital LLON interface for connection to LONWorks networks. In the LONWorks network, data items are transmitted for the double pump as a complete unit; there is no differentiation between master and slave.

• Transfer of the following data items as control commands to the pump:-Operating mode- Setpoint-Data from external sensors

• Transfer of the following data items as signals from the pump:-Hydraulic operating data- Electrical operating data- Status signals- Fault signals

• Double pump DP interface for the optional integration of a dual pump management system of 1 x double pump or 2 x single pumps, option-ally with the following functions:-Main/standby mode

for automatic fault-actuated switchover to the standby pump and

automatic pump cycling after 24 hrs operating time- Parallel operation

for the efficiency-optimised activation and deactivation of the peak-load pump and automatic fault-actuated switchover to standby pump

• Included in the IF-Module PLR scope of delivery for TOP-ED/-E: 2-core connecting cable, 670mm long;

• Included in the IF-Module PLR scope of delivery for DL-E/-IL-E: 2-core connecting cable, 1800 mm long

Standards• LONMark Application Layer Interoperability Guidelines Version 3.2• LONMark Layers 1-6 Interoperability Guidelines 3.0• LONMark Functional Profile "Pump Controller Object for HVAC Appli-cations" (8120_10.pdf)

Delivery statusThe LON IF-Module is supplied as "Application unconfigured" in ac-cordance with the LONMark Application Layer Interoperability Guide-lines.

DocumentationWe provide you with the following documentation on our homepage www.wilo.com (/Products/Wilo building automation): LONMark Functional Profile "Pump Controller Object for HVAC Appli-cations" (8120_10.pdf)

• Download application via network: *.NXE /*.APB• External interface files: *.XIF / *.XFB• Device resource files: *.ENU /*.FMT /*.FPT /*.TYP

LON

DP L N PE SSM

1~230 V

Wilo-TOP-ED/-EWilo-IFmodule LON*

LONWorks network

0...10 V In

Ext.off+24V

PLR

DP L N PE SSM

1~230 V

0...10 V Ext.off

Connecting cable, min. 2 x 0,75 mm2, lock-protected

Wilo-IF module PLR Wilo-TOP-ED/-E

MA (Master) SL (Slave)

* Illustration does not reflect the actual position of the terminals

In

+24V

P1� 500 W (P2� 350 W) P1� 500 W (P2� 350 W)

LON

DP

PE L1 L2 L33~400 V

Wilo-DL-E/-IL-E

Wilo-IFmoduleLON*

LONWorks network

SBM

SSM

3 +24 V21 0...10 V

0/4...20mAAux,without function

Ext.offMaster

PLR

DP

PE L1 L2 L33~400 V

Wilo-IF module PLR

SBM

SSM

3 +24 V21 0...10 V

0/4...20mAAux, without function

Ext.offSlave

Connecting cable, min. 2 x 0,75 mm2, lock-protected

Wilo-DL-E/-IL-E

* Illustration does not reflect the actual position of the terminals

Page 267: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

267

Wilo-Control pump management systemsControl technology

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-Control AnaCon

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Control technology Wilo-Control AnaCon Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

I 0 Bus Controller

EIB

Bus Controller

CAN

Bus Controller

AnaCon AnaCon

TOP-E Stratos

LON

I 0 I 0

Sensor

Sensor

Sensor

Sensor

Sensor

Front view Dimension drawing

ma

0-10V off max min on 24V ssm ebm-ma ebm-sl

+-

mode

p-cp-v

n-c

set pointAn

aC

on

100%

0%

0-10V disable

set

sl 0/0/0

power

+-

pump rs 23224 V

DC

50m

A

1446 90

87 33

58

15 10

148

8

Page 268: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

268 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsControl technology

Wilo-Control AnaCon

Wilo-Control pump management systems Control technology Wilo-Control AnaCon Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsWilo-Control AnaConThe Wilo-Control AnaCon interface converter is suitable for the uni-versal connection of communications-capable pumps with the PLR interface to onsite control and monitoring units with conventional input/output channels. It is installed on a top-hat rail (DIN EN 50 02235) in a switch cabinet in the immediate vicinity of the monitor-ing unit. The Wilo-Control AnaCon interface converter converts the two-wire connection of the serial digital PLR interface into a parallel interface with analogue signals and potential-free contacts.

1 single or double pump of the following Wilo series is connected to the BA via the Wilo-Control AnaCon interface converter:

• TOP-E/-ED (with IF-Module PLR)• Stratos/-D/-Z series (with Stratos IF-Module PLR)• VeroLine-IP-E/-DP-E (with IF-Module PLR)• CronoLine-IL-E/-DL-E (with IF-Module PLR)

Bidirectional communication between the pumps and the monitoring unit (BA) enables the remote control of:

• Pump OFF• Pump ON in control mode• Max. speed• Min. speed (setback operation)• Setpoint for differential pressure or speed (analogue In 0 - 10 V con-trol input)

Bidirectional communication between the pumps and the monitoring unit (BA) enables the remote querying of:

• Collective fault signal• MA individual run signal or single pump• SL individual run signal (double pump only)

In addition to remote control and remote querying, the Wilo-Control AnaCon interface converter also enables the local adjustment of:

• �p-c for constant differential pressure• �p-v for variable differential pressure• n-c for constant speed• Setpoint for differential pressure or speed• Enabling of the analogue In 0 - 10 V control input

The Wilo-Control AnaCon interface converter is equipped with LEDs for:

• AnaCon operational standby• Communication with the pump• Communication with RS 485 interface• Collective fault signal• MA individual run signal or single pump• SL individual run signal (double pump only)

Technical data• Contact load- Collective fault signal (potential-free changeover contact: max. 250 VAC, 1 A

-MA individual run signal (potential-free NO contact) max. 250 VAC, 1 A

- SL individual run signal (potential-free NO contact) max. 250 VAC, 1 A

- Potential-free NO contact for "Pump Off" function: 24 VDC, 2.4 mA

- Potential-free NO contact for "Control On" function: 24 VDC, 2.4 mA

- Potential-free NO contact for "Maximum speed" function: 24 DC, 2.4 mA

- Potential-free NO contact for "Min. speed" function: 24 VDC, 2.4 mA

• Supply voltage-Operating voltage: 24 VDC ± 25 %- Current consumption: 40mA

• Electromagnetic compatibility- Emitted interference: DIN EN 61000-6-3- Interference resistance: DIN EN 61000-6-2

• Analogue In 0 - 10 V control input- Input resistance: > 200 kW- Input protection: max. +/- 48 VDC

• PLR interface- Point-to-point interface with Wilo-specific hardware and Wilo-specific protocol

- Two-core connection with interchangeable wires (no shielded cable necessary)

-Maximum cable length: 1000m

Manual operation of the pump by means of the red button is not pos-sible if the pump is connected to the AnaCon.A temporary disruption of the interface connection to electronically controlled pumps with IR interface is possible with the IR-Monitor. Operation can then be controlled with the IR-Monitor. Interface communication is automatically restored after the IR connection is disconnected.

Page 269: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

269

Wilo-Control pump management systemsControl technology

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-Control DigiCon

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Control technology Wilo-Control DigiCon Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

I 0 Bus Controller

RS 485

Bus Controller

CAN

Bus Controller

DigiCon

Stratos-D Stratos

DigiCon

IP-E IL-ETOP-E TOP-ED

LON

I 0 I 0

Front view Dimension drawing

ma

0-10V off max min on 24V ssm ebm-ma ebm-sl

0-10V off max min on 24V ssm ebm-ma ebm-sl

+ -

+ -

Dig

iCo

n-

A

0-10V disable

0-10V disable

sl

1 1 1

ma sl

2 2 2

1446 90

87 33

58

15 10

148

8

Page 270: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

270 Subject to change 09/2008 WILO SE

Wilo-Control pump management systemsControl technology

Wilo-Control DigiCon

Wilo-Control pump management systems Control technology Wilo-Control DigiCon Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsWilo-Control DigiConThe Wilo-Control DigiCon interface converter is suitable for the uni-versal connection of communication-capable pumps with the PLR in-terface on the onsite control and monitoring units with RS 485 digital serial interface. It is installed on a top-hat rail (DIN EN 50 02235) in a switch cabinet in the immediate vicinity of the monitoring unit. The Wilo-Control DigiCon interface converter transforms the two-wire connection of the serial digital PLR interface into a bus-compatible RS 485 serial digital interface.

A maximum of 4 single or double pumps of the following Wilo series can be connected to the BA by means of the Wilo-Control DigiCon interface converter:

• TOP-E/-ED (with IF-Module PLR)• Stratos/-D/-Z series (with Stratos IF-Module PLR)• VeroLine-IP-E (with IF-Module PLR)• VeroTwin-DP-E (with IF-Module PLR)• CronoLine-IL-E (with IF-Module PLR) CronoTwin-DL-E (with IF-

Module PLR)

Bidirectional communication between the pumps and the monitoring unit (BA) makes it possible to select between the following types of regulation and control modes:

• �p-c for constant differential pressure• �p-v for variable differential pressure• �p-T for temperature-controlled differential pressure• n-c for constant speed

Bidirectional communication between the pumps and the monitoring unit (BA) allows the remote control of:

• Pump OFF• Pump ON in control mode• Max. speed• Min. speed (setback operation)• Setpoint for the preselected regulation or control mode

Bidirectional communication between the pumps and the monitoring unit (BA) enables the remote query of:

• Current operating mode• Collective fault signal• Detailed fault signal• Individual run signal MA or single pump• Individual run signal SL (only double pump)as well as the following pump operating parameters:

• Actual delivery head and current volume flow• Motor current• Power consumption• Operating hours• Cumulative power consumption• Speed• Fluid temperature (only Stratos/-D/-Z/-ZD)

In addition to remote control and remote querying, the Wilo-Control DigiCon interface converter also enables the local adjustment of:

• �p-c for constant differential pressure• �p-v for variable differential pressure• n-c for constant speed• Setpoint for differential pressure or speed

The Wilo-Control DigiCon interface converter is equipped with LEDs for:

• DigiCon operation standby• Communication with the pump• Communication with RS 485 interfaceA maximum of 64 Wilo-Control DigiCon interface converters can be switched in series via the RS 485 interface.

Technical data• Supply voltage-Operating voltage: 24 VDC ± 25 %- Current consumption: 70 mA- Terminal cross-section: 1.5mm2

• Electromagnetic compatibility- Emitted interference: DIN EN 61000-6-3- Interference resistance: DIN EN 61000-6-2

• PLR interface- Point-to-point interface with Wilo-specific hardware and Wilo-specific protocol

- Two-wire connection with interchangeable cores (no shielded cable necessary)

-Maximum cable length: 1000m-Cable type: e.g. J-Y(St)Y 2x2x0.8- Terminal cross-section: 1.5 mm2

• Interface RS 485 Bus-capable interface with hardware in accordance with the RS 485 standard and the Wilo-specific protocol. The protocol is to be coordi-nated with the respective BA manufacturer.-Addressing of a maximum of 64 DigiCons (maximum of 256 pumps)-Maximum total length of the bus line: 1000m-Cable type: e.g. J-Y(St)Y 2x2x0.8, shielded- Terminal cross-section: 1.5 mm2

Documentation of the Wilo-specific protocol is stored on the CD in-cluded in the scope of delivery. The software provided on this CD also enables communication between the pumps and a conventional PC.Manual operation of the pump by means of the red button is not pos-sible if the pump is connected to the Wilo-Control DigiCon. A tempo-rary disruption of the interface connection to electronically control-led pumps with IR interface is possible with the IR-Monitor. Operation can then be controlled with the IR-Monitor. Interface communication is automatically restored after the IR connection is disconnected.

AccessoriesManual control panel Wilo-Control DigiCon-A for a maximum of 2 pumps

Page 271: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

271

Wilo-Control pump management systemsControl technology

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-Control DigiCon-A

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Control technology Wilo-Control DigiCon-A Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

I 0 Bus Controller

RS 485

Bus Controller

CAN

Bus Controller

DigiCon DigiCon-A DigiCon-A

Stratos-D Stratos

DigiCon DigiCon-A DigiCon-A

IP-E IL-ETOP-E TOP-ED

LON

I 0 I 0

Front view Dimension drawing

ma

0-10V off max min on 24V ssm ebm-ma ebm-sl

0-10V off max min on 24V ssm ebm-ma ebm-sl

+ -

+ -

Dig

iCo

n-

A

0-10V disable

0-10V disable

sl

1 1 1

ma sl

2 2 2

1446 90

87 33

58

15 10

148

8

Page 272: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

272 Subject to change 09/2008 Wilo SE

Wilo-Control pump management systemsControl technology

Wilo-Control DigiCon-A

Wilo-Control pump management systems Control technology Wilo-Control DigiCon-A Subject to change 09/2008 Wilo SE Wilo Catalogue A2 - 50 Hz - Glanded pumpsWilo-Control DigiCon-AThe Wilo-Control DigiCon-A manual control panel allows the over-riding control of pumps connected to the Wilo-Control DigiCon in-terface converter.The manual control panel is installed on a top-hat rail (DIN EN 50 02235) and is contacted via a lateral plug system to the Wilo-Control DigiCon interface converter. 2 manual control panels for the higher-level control of no more than one single or double pump can be con-nected to a Wilo-Control DigiCon.

The Wilo-Control DigiCon-A manual control panel enables overriding remote control via potential-free control contacts and an analogue signal for simultaneous bus communication of:

• Pump OFF• Pump ON in control mode• Max. speed• Min. speed (setback operation)• Setpoint for differential pressure or speed (analogue In 0 - 10 V con-trol input)

The Wilo-Control DigiCon-A manual control panel enables remote querying via potential-free signalling contacts for simultaneous bus communication of:

• Collective fault signal• MA individual run signal or single pump• SL individual run signal (double pump only)

In addition to remote control and remote querying, the Wilo-Control DigiCon-A manual control panel also allows:

• Enabling of the analogue In 0 - 10 V control input

The Wilo-Control DigiCon-A manual control panel is equipped with LEDs for:

• DigiCon-A operational standby• Collective fault signal (for each pump)• MA individual run signal or single pump (for each pump)• SL individual run signal (double pump only) (for each pump)

Technical data• Contact load- Collective fault signal

(potential-free changeover contact): max. 250 VAC, 1 A-MA individual run signal

(potential-free NO contact) max. 250 VAC, 1 A- SL individual run signal

(potential-free NO contact) max. 250 VAC, 1 A- Potential-free NO contact

for "Pump Off" function: 24 VDC, 2.4 mA- Potential-free NO contact

for "Control On" function: 24 VDC, 2.4 mA- Potential-free NO contact

for "Maximum speed" function: 24 VDC, 2.4 mA- Potential-free NO contact

for "Min. speed" function: 24 VDC, 2.4 mA

• Supply voltage-Operating voltage: The DigiCon-A manual control panel is powered

via the lateral DigiCon plug system.- Current consumption: 40mA

• Electromagnetic compatibility- Emitted interference: DIN EN 61000-6-3- Interference resistance: DIN EN 61000-6-2

• Analogue In 0 - 10 V control input- Input resistance: > 200 kW- Input protection: max. +/- 48 VDC

• PLR interface- Point-to-point interface with Wilo-specific hardware and Wilo-specific protocol

- Two-core connection with interchangeable wires (no shielded cable necessary)

-Maximum cable length: 1000m

Manual operation of the pump by means of the red button is not pos-sible if the pump is connected to the Wilo-Control DigiCon.A temporary disruption of the interface connection to electronically controlled pumps with IR interface is possible with the IR-Monitor. Operation can then be controlled with the IR-Monitor. Interface communication is automatically restored after the IR connection is disconnected.

Page 273: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

273

Wilo-Control pump management systemsControl technology

Wilo Catalogue A2 - 50 Hz - Glanded pumps

Accessories

Switc

hgears

and

control

devices

Pump management

Wilo-Control pump management systems Control technology Accessories Subject to change 09/2008 WILO SE Wilo Catalogue A2 - 50 Hz - Glanded pumps

Wilo-Control bus boxJunction box or distribution box for setting up a CAN bus system with connection of the nodes via short spur lines. The Wilo-Control bus box does not require any external power supply.

• Threaded cable connection (3x): M16x1.5• Dimensions (without threaded cable connection); 95x95x60mm• Fixation elements: to be provided by the customer

Technical dataProtection class: IP 44

Fig.: Wilo-Control bus box

Wilo-Control CAN bus cable• Shielded CAN bus cable 1x2x0.5; available in the lengths:-10 m-100 m

• The cable is suitable for permanent installation inside buildings.

Technical data• Number of wires: 2• Nominal cross-section: 0.5mm2

• Characteristic impedance 120W• Loop resistance: max. 37 /km• Operating capacity: 50 pF/m

Page 274: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

1 Änderungen vorbehalten. WILO AG 09/2007

Heating, air-conditioning, coolingCirculation pumpsGlandless pumps and accessories, package heat exchanger assembly

Heating, air-conditioning, coolingGlanded pumpsPumps with in-line design and accessories

Heating, air-conditioning, cooling, water supplyMonobloc and norm pumps, axial split case pumpsPumps and accessories

Water supply Domestic water supply, rainwater utilisationPumps, systems and accessories

Water supply Borehole pumps, 3" to 24"Pumps and systems for building services, domestic, municipal and industrial water supply

Water supply High-pressure multistage centrifugal pumpsPumps and accessories

Water supply Pressure boosting systemsSingle-pump and multi-pump systems in dry well installations

Water supply Sprinkler pumps with VdS approvalBorehole pumps and accessories

Drainage and sewageDrainage pumpsSubmersible pumps, self-priming pumps and accessories

Drainage and sewageSewage pumps, DN 32 to DN 600Submersible pumps and accessories for building services, municipal and industrial applications

Drainage and sewageWastewater and sewage lifting units, pumps stationsPump systems and accessories

Drainage and sewageSubmersible mixersMixers, re-circulation pumps, jet cleaners, grit collector pumps and acces-sories for municipal application in water treatment systems

Catalogue A1

Catalogue A2

Catalogue A3

Catalogue B1

Catalogue B2

Catalogue B3

Catalogue B4

Catalogue B5

Catalogue C1

Catalogue C2

Catalogue C3

Catalogue C4

UMETechnologie

UMETechnologie

UMETechnologie

UMETechnologie

Heat

ing,

air-

cond

ition

ing,

cool

ing

Wat

ersu

pply

Dra

inag

ean

dse

wag

e

Wilo Catalogue Edition 2009

UMETechnologie

Page 275: Catalogue Heating, Air-conditioning Cooling Glanded Pumps Pumps - 2009.pdf · Pumps in In-line Design and Accessories Catalogue Heating, Air-conditioning Cooling Glanded Pumps Catalogue

WILO SENortkirchenstraße 10044263 DortmundGermanyT +49 231 4102-0F +49 231 [email protected]

AlgeriaBad Ezzouar, Dar El BeidaT +213 21 [email protected]

Armenia375001 YerevanT +374 10 [email protected]

Bosnia and Herzegovina71000 Sarajevo T +387 33 [email protected]

Georgia0179 TbilisiT +995 32 [email protected]

Macedonia1000 SkopjeT +389 2 [email protected]

Mexico07300 MexicoT +52 55 [email protected]

Moldova2012 ChisinauT +373 2 [email protected]

Rep. MongoliaUlaanbaatarT +976 11 [email protected]

Tajikistan734025 DushanbeT +992 37 [email protected]

Turkmenistan744000 AshgabadT +993 12 [email protected]

Uzbekistan100015 TashkentT +998 71 [email protected]

March 2009

Wilo – International (Subsidiaries)

Wilo – International (Representation offices)

ArgentinaWILO SALMSONArgentina S.A.C1295ABI CiudadAutónoma de Buenos AiresT+ 54 11 4361 [email protected]

AustriaWILO PumpenÖsterreich GmbH1230 WienT +43 507 [email protected]

AzerbaijanWILO Caspian LLC1065 BakuT +994 12 [email protected]

BelarusWILO Bel OOO220035 MinskT +375 17 [email protected]

BelgiumWILO SA/NV1083 GanshorenT +32 2 [email protected]

BulgariaWILO Bulgaria Ltd.1125 SofiaT +359 2 [email protected]

CanadaWILO Canada Inc.Calgary, Alberta T2A 5L4T +1 403 [email protected]

ChinaWILO China Ltd.101300 BeijingT +86 10 [email protected]

CroatiaWILO Hrvatska d.o.o. 10090 ZagrebT +38 51 [email protected]

Czech RepublicWILO Praha s.r.o.25101 CestliceT +420 234 [email protected]

DenmarkWILO Danmark A/S2690 KarlslundeT +45 70 [email protected]

EstoniaWILO Eesti OÜ12618 TallinnT +372 [email protected]

FinlandWILO Finland OY02330 EspooT +358 [email protected]

FranceWILO S.A.S.78390 Bois d'ArcyT +33 1 [email protected]

Great BritainWILO (U.K.) Ltd.DE14 2WJ Burton-Upon-TrentT +44 1283 [email protected]

GreeceWILO Hellas AG14569 Anixi (Attika)T +302 10 [email protected]

HungaryWILO Magyarország Kft2045 Törökbálint(Budapest)T +36 23 [email protected]

IrelandWILO Engineering Ltd.LimerickT +353 61 [email protected]

ItalyWILO Italia s.r.l.20068 PeschieraBorromeo (Milano)T +39 [email protected]

KazakhstanWILO Central Asia050002 AlmatyT +7 727 [email protected]

KoreaWILO Pumps Ltd. 621-807 GimhaeGyeongnamT +82 55 [email protected]

LatviaWILO Baltic SIA1019 RigaT +371 67 [email protected]

LebanonWILO SALMSONLebanon12022030 El MetnT +961 4 [email protected]

LithuaniaWILO Lietuva UAB03202 VilniusT +370 5 [email protected]

The NetherlandsWILO Nederland b.v.1551 NA WestzaanT +31 88 9456 [email protected]

NorwayWILO Norge AS0975 OsloT +47 22 [email protected]

PolandWILO Polska Sp. z.o.o.05-090 RaszynT +48 22 [email protected]

PortugalBombas Wilo-SalmsonPortugal Lda.4050-040 PortoT +351 22 [email protected]

RomaniaWILO Romania s.r.l.077040 Com. ChiajnaJud. IlfovT +40 21 [email protected]

RussiaWILO Rus ooo123592 MoscowT +7 495 [email protected]

Saudi ArabiaWILO ME - RiyadhRiyadh 11465T +966 1 [email protected]

Serbia and MontenegroWILO Beograd d.o.o.11000 BeogradT +381 11 [email protected]

SlovakiaWILO Slovakia s.r.o.82008 Bratislava 28T +421 2 [email protected]

SloveniaWILO Adriatic d.o.o.1000 LjubljanaT +386 1 [email protected]

South AfricaSalmson South Africa1610 EdenvaleT +27 11 [email protected]

SpainWILO Ibérica S.A.28806 Alcalá de Henares(Madrid)T +34 91 [email protected]

SwedenWILO Sverige AB35246 VäxjöT +46 470 [email protected]

SwitzerlandEMB Pumpen AG4310 RheinfeldenT +41 61 [email protected]

TaiwanWILO-EMU Taiwan Co. Ltd.110 TaipehT +886 227 [email protected]

TurkeyWILO Pompa Sistemleri San. ve Tic. A.S.34530 IstanbulT +90 216 [email protected]

UkrainaWILO Ukraina t.o.w.01033 KiewT +38 044 [email protected]

VietnamPompes Salmson VietnamHo Chi Minh-Ville VietnamT +84 8 [email protected]

United Arab EmiratesWILO ME - DubaiDubaiT +971 4 [email protected]

USAWILO-EMU USA LLCThomasville, Georgia 31792T +1 229 [email protected]

USAWILO USA LLC Melrose Park, Illinois 60160T +1 708 [email protected]

Subject to change without prior notice. In appliance of our General Terms of Delivery and Service (see www.wilo.com)

2100995/2T/0809/MP