Catalogue АТ24 2015 05

download Catalogue АТ24 2015 05

of 67

Transcript of Catalogue АТ24 2015 05

  • 8/16/2019 Catalogue АТ24 2015 05

    1/67

    Catalogue05.2015

    Triol АТ24Low-voltage variable frequency drives

    www.triolcorp.com

  • 8/16/2019 Catalogue АТ24 2015 05

    2/67

  • 8/16/2019 Catalogue АТ24 2015 05

    3/67

    1

    Contents

    Triol АТ24

    Low voltagevariable frequency drive

    Introduction ........................................................

    Review of lines ....................................................

    Line 1 ....................................................................

    Line 2 ....................................................................

    Line 3 ....................................................................

    Line 4 ....................................................................

    Line C ....................................................................

    Line E ....................................................................

    Line Н (380 V) .......................................................

    Line Н (660 V) .......................................................

    Line К ....................................................................

    Line 5 ....................................................................

    Line 7 ....................................................................

    Line 9 ....................................................................

    Line А ....................................................................

    Line М ...................................................................

    Support documentation review ........................

    Additional equipment .......................................

    Services ................................................................

    Intro

    RL

    1

    2

    3

    4

    Н/660 V

    K

    5

    A

    C

    E

    Н/380 V

    М

    SD

    AE

    S

    7

    9

  • 8/16/2019 Catalogue АТ24 2015 05

    4/67

    2

    Introduction

    Dear customers!

    This catalogue presents low voltage variable frequency drive Triol AT24. For your

    convenience the document is divided into several sections that contain informationabout separate product lines. Whole Triol AT24 product range is shown in the table,containing the products described in the catalogue (lines for lifts (elevators), pumps,cranes, HVAC, multidrive and industrial application).

    All information about each line is presented in such sections: application, Key func-tions and features, mechanical and protection parameters, technical characteristics,connection diagram, overall dimensions and VFD congurations.

    Variable speed drives Triol AT24 are successfully operating in a wide range of areas:fuel and energy sector, housing and utilities infrastructure, mining industry, construc-tion industry, cement production and metallurgy.

    We are constantly analyzing our performance results and looking for opportunitiesto improve our products.

    We invite everybody to consolidate our eorts to achieve together outstandingresults.

    We appreciate our Partners and Customers and are always open for cooperation!

    Intro

  • 8/16/2019 Catalogue АТ24 2015 05

    5/67

    3

    Review of lines

    АТ24-ХХХ-ХХХ-ХХХХХХ  1 2 3 4 5 6 7 8 9

    1 Variable frequency drive (VFD) series name  АТ24 – Low voltage variable frequency drive.

    2 VFD power in accordance with power range  For instance, 5K5 — 5,5 kW; 90K — 90 kW, M25 — 250 kW or 0,25 MW.

    3 Rated input voltage  380 V  660 V

    4 Triol АТ24 line type

      In accordance with the line types descriptions following below. 5 Built-in power units  0 — Without built-in blocks,  1 — Built-in choke,  2 — Brake module,  3 — EMI lter,  4 — Sinewave lter.

    6 Input-output modules  0 — Without built-in input-output modules,

      1 — Extension board – Module EXT1;  2 — Extension board – Module EXT2 Termo;  3 — Extension board – Module EXT3 Relay;  4 — Reserve;  А — Multipump (used for a simultaneous control of several pumps).

    7 Interface module  0 — Without built-in interface modules,  1 — Reserve,  2 — Module Anet_CAN (CanOpen),  3 — Module Anet_Probus (Probus DP),  4 — Module Anet_LAN (Ethernet IP)  5 — Module Anet2_RS485 (Modbus RTU, 2 link channels are available).

    8 Encoder module  0 — Without built-in units,  1 — Incremental encoder module ENCO2,  2 — Absolute encoder module ENCO3. 9 Lodgement (locating block) module  0 — Without built-in units;

      1 — Wi-Fi adapter;  2 — USB-host adapter;  3 — USB-device adapter.

    RL

  • 8/16/2019 Catalogue АТ24 2015 05

    6/67

    4

    Line type Application Power range Supply voltage Enclosure

    Line 1 Lift (Elevator)  5.5 kW ... 37 kW 380 V plastic, IP20

    Line 2 HVAC 5,5 kW ... 55 kW 380 V plastic, IP20

    Line 3 HVAC 75 kW ... 400 kW 380 V metal, IP20

    Line 4 HVAC 370 W ... 4 kW 380 V plastic, IP20

    Line 5 Industrial 5,5 kW ... 400 kW 380 V metal, IP54

    Line 7 Industrial 5,5 kW ... 400 kW 380 V metal, IP54

    Line 9 Industrial 5,5 kW ... 400 kW 380 V metal, IP54

    Line А Lift (Elevator) 5,5 kW ... 37 kW 380 V metal, IP54

    Line B HVAC 5,5 kW ... 400 kW 380 V metal, IP54

    Line С Pump 5,5 kW ... 55 kW 380 V plastic, IP20

    Line Е Pump 75 kW ... 400 kW 380 V metal, IP20

    Line H Pump 5,5 kW ... 400 kW 380 V metal, IP54Line H Pump 75 kW ... 1200 kW 660 V metal, IP54

    Line K Crane 5,5 kW ... 400 kW 380 V metal, IP54

    Line М Multidrive 5,5 kW ... 2 MW 380 V metal, IP20

    RL

  • 8/16/2019 Catalogue АТ24 2015 05

    7/67

    1.1

    Line 1

     Application

    Triol AT24 VFD Line 1 is an optimized solution for every elevator. This line is spe-cially designed to provide safety and reliability of the lift mechanisms operation.The equipment features are state-of-the-art technical solutions and functionalitysuitable for the most critical applications.

    Key functions

    • start, stop and control of motor rotation frequency;• acceleration and deceleration ramps including S-shaped ramps;• reversal;• acceleration, decreasing, stop;• protection of the motor overcurrent, overload protection• lift operation at xed speeds, capability of universal setting to the lift VSD (variable speed

    drives) and integration with lift control systems used for an old housing stock;• saving control conguration of motor;• dynamic braking of motor;• operation mode «Evacuation»;• operation mode «Short oor»;• operation mode «Inspection»;• braking unit control support;• motor contactor control;• vector control with and without speed feedback.

    1

  • 8/16/2019 Catalogue АТ24 2015 05

    8/67

    1.2

    Mechanical parameters

    • plastic enclosure, IP20;• forced cooling (fans, air ow direction from the bottom upwards);

    • operation temperature -20 °C ... + 40 °C;• simple connection of input and output cables ;• convenient demountable control panel with graphic display;• possibility of VFD installation in small-size cabinets or in conned space;• resistance to continuous sinewave vibration 0.5 G in three planes.

    Protection functions

    • protection against overheating of power modules;• motor protection against overheating using motor temperature sensor;• overvoltage and under voltage protection in DC-link of VFD;• short-circuit at VFD output protection;• protection against increasing currents at VFD output;• desaturation protection;• input single-phasing protection;

    • «Emergency stop» command from emergency stop circuit.

    1

  • 8/16/2019 Catalogue АТ24 2015 05

    9/67

    1.3

    Line 1

    Power cables connection diagram (  АТ24-5К5...7К5 )

    М

    L1   L2 L3

    R/L1   S/L2 T/L3

    U/T1 V/T2 W/T3

    + R b  

    +  U d  

    Built-in

    EMC filter 

    of Class C2

    +Rb and –Rb terminalsare used only for 

    connecting brake resistor 

    dU/dt filter 

    AT24-5K5…7K5-380-1*****

    variable-frequency drive

    PE

    -R b  

    -DC and +Rb terminals

    are used for connecting

    regeneration unit

    *

                *

    For variable-frequency drives w/o any 

    built-in chokes in DC-link 

    Grounding plate

    -D C 

    + L   d  +Ld and +Ud terminals

    are used for 

    connecting the DC-link

    external choke

     АС DC 

    DC  АС 

    Line-disconnection 1

  • 8/16/2019 Catalogue АТ24 2015 05

    10/67

    1.4

    Technical characteristicsSupply voltage 3x380 V (-15 % .. +10 %)

    Supply frequency 50 Hz (-15 % .. +10 %)

    EMC lter built-in

    DC reactor built-in

    Control panel graphic, 160Х160 pixels, 3’’

    Braking resistor external

    PWM frequency / PWM carrierfrequency

    2 — 10 kHz/5 kHz

    Output frequency 0 — 400 Hz

    Frequency range for dierentmotors

    0 — 400 Hz

    Speed range1:1000 in a closed-loop system with a speed sensor1:100 in an open-loop system

    Fixed speed accuracy (static) in

    vector control mode, withoutspeed sensor

    < 5 % at rated load of motor shaft and rated motor speed

    Fixed speed accuracy (static) invector control mode, with speedsensor

    < 2 % at rated load of motor shaft and rated motor speed

    Torque accuracy+/- 5 % in a closed-loop system+/- 10 % in an open-loop system

    Overload characteristics200 % — for 2 seconds, 150 % — for 60 seconds withan ambient temperature 50 °С

    Asynchronousmotor control prole

    • vector control in a closed-loop system with a speed feed-back

    • vector control in open-loop system without a speed feed-back

    • voltage / frequency U/F ratio control (scalar control)

    Cycle adjustment setting the operating mode — MODBUS, digital inputs

    Slip compensation implemented

    Local signaling run, ready, fault — green, yellow and red LEDs

    Insulation• isolated control circuits• insulated custom circuits

    Supply 10 V DC, +/- 2 % current not exceeding 30 mA, 24 V, 60 mA

    Number of analog inputs 2Analog input type programmable 4..20 mA, 0..5 mA, 0..10 V

    Sampling period 4 ms

    Number of analog outputs 1

    Type analog output programmable 4..20 mA, 0..5 mA, 0..10 V

    Number of digital outputs 4 relay outputs

    Type of digital output• 2 outputs are switching type• 2 outputs are normally open type

    Number of digital inputs 8

    Type of digital inputs

    • 24 V, input resistance: about 4 kOhm

    • PTC sensor, resistance switch 3 kOhm/1,8 kOhm• emergency stop

    1

  • 8/16/2019 Catalogue АТ24 2015 05

    11/67

    1.5

    The logic of the digital input 2 digital inputs arbitrary polarity

    Acceleration and deceleration S-shaped acceleration / deceleration, linear adjustable

    Type of protection

    • power switch (U, V, W, T)

    • OCP hardware (U, V, W) / OCP software (U, V, W)• temperature of switches• Ud max/ Ud min• loss of one or more phases• overheating of the braking resistor• motor overload /motor overheating

    Dielectric strengthfor power circuits and auxiliary circuits having electrical com-munication with the power circuit — 2500 V

    Insulation resistance > 1 MOhm

    Output frequency discreteness 0,1 Hz

    Communication protocol Modbus

    Physical interface 2-wire RS-485 for Modbus

    Frame transmission RTU for Modbus

    Data transfer rate• 115200 bps• 1200 — 250000 bps• up to 1 bps

    Data format 8 bit, 1 stop bit , no parity

    Addresses number 1.. 255 addresses for Modbus

    Access method slave

    Control options Bluetooth module or Wi-Fi module

    Electromagnetic compatibility• EN 55011 class A, group 2, IEC/EN 61800-3, category С2•with the additional EMC lter, EN 55011 class В, group 1,IEC/EN 61800-3, category С1

    Relative humidity 95 %

    The ambient temperature duringoperation / storage

    -20 .. +40 °C / -40 .. +50 °C (humidity-controlled)

    Operating altitude up to 1000 m

    StandardsGOST 24607-88, GOST 13109-97, GOST 15150-69, GOST 14254-96,GOST 17516.1-90, GOST 12.1.044-89, EN 61800-3:2004, EN 55011,ЕN 61000-6 3/4

    Line 1

    1

  • 8/16/2019 Catalogue АТ24 2015 05

    12/67

    1.6

    Model range Line 1

    Triol AТ24 modelRated motorpower, kW

    Rated currentof power circuit, A

    Total VFD outputpower, kVA

    АТ24-5К5-380-1***** 5,5 11 7,5

    АТ24-7К5-380-1***** 7,5 15 10АТ24-11К-380-1***** 11,0 22 15

    АТ24-15К-380-1***** 15,0 30 18

    АТ24-18К-380-1***** 18,0 36 22

    АТ24-22К-380-1***** 22,0 45 28

    АТ24-30К-380-1***** 30,0 60 38

    АТ24-37К-380-1***** 37,0 75 45

    Mounting dimensions

    Triol AТ24 model L, mm H, mm D, mm

    АТ24-5К5-380-1*****

    190 283

    6

    АТ24-7К5-380-1*****

    АТ24-11К-380-1*****

    АТ24-15К-380-1*****

    254 345АТ24-18К-380-1*****

    АТ24-22К-380-1*****

    АТ24-30К-380-1*****291 535

    АТ24-37К-380-1*****

    4 holes ØD

    1

  • 8/16/2019 Catalogue АТ24 2015 05

    13/67

    1.7

    Overall dimensions

    Triol AТ24 model Width, mm Height, mm Depth, mmVFD weight,

    kg

    АТ24-5К5-380-1*****216,5 360 187 14

    АТ24-7К5-380-1*****

    АТ24-11К-380-1*****

    280 444 257 32АТ24-15К-380-1*****

    АТ24-18К-380-1*****

    АТ24-22К-380-1*****

    АТ24-30К-380-1*****325 615 285 47

    АТ24-37К-380-1*****

    Dimensional outlineАТ24-5К5-380-1*****, АТ24-7К5-380-1*****

    Line 1

    1

  • 8/16/2019 Catalogue АТ24 2015 05

    14/67

    1.8

    Dimensional outlineAТ24-30К-380-1*****, AТ24-37К-380-1*****

    Dimensional outlineАТ24-11К-380-1*****, АТ24-15К-380-1*****,АТ24-18К-380-1*****, АТ24-22К-380-1*****

    1

  • 8/16/2019 Catalogue АТ24 2015 05

    15/67

    2.1

    Line 2

     Application

    Triol AT24 VFD Line 2 is a reliable solution for heating, ventilation and air conditioningapplications. This product combines simplicity of management, operational reliability andhigh performance eciency.

    Key functions

    • start, stop and control of motor rotation frequency;• acceleration and braking ramps including S-shaped ramps;• reversal;• acceleration, decreasing, stop;• protection of the motor overcurrent, overload protection;• motor control by external 2-wire and 3-wire sensors;• saving control conguration of motor;• dynamic braking of motor;

    • simultaneous control of ve motors («Cascade controller» macros);• automatic control of technology process by closed-loop system principle using built-in

    PID-controller;• operation of asynchronous motor by custom preset diagram in automatic or manual

    mode.

    2

  • 8/16/2019 Catalogue АТ24 2015 05

    16/67

    2.2

    Mechanical parameters

    • plastic enclosure, IP20;• forced cooling (fans, air ow direction from the bottom upwards);• operation temperature -20 °С ... + 50 °С;• simple connection of input and output cables;• convenient demountable control panel with graphic display;• possibility of installation in small-size cabinets or in conned space;• resistance to continuous sinewave vibration 0.5 G in three plans.

    Protection functions

    • closedown under fuse blowing;• variable frequency drive emergency tripping in case:

    ◊ temperature exceeds critical values◊ increasing of voltage in DC-link◊decreasing of voltage in DC-link◊short-circuit at VFD output◊ by a signal («Power switch» emergency)◊ output current exceed preset values

    • blocking of asynchronous motor reverse;• disabling of VFD continuous duty under resonant frequencies for prevent an executive

    unit’s damages;• disabling of start-up after coast stop during specied time;• after emergency, for protection against start-up of rotating motor;• blocking of start-up after emergency tripping.

    2

  • 8/16/2019 Catalogue АТ24 2015 05

    17/67

    2.3

    Line 2

    Power cables connection diagram (  АТ24-5К5...11К  )

    М

    L1 L2 L3

    R/L1 S/L2 T/L3

    U/T1 V/T2 W/T3

    + R  b  

    +  U  d  

    Line-disconnection

    Built-in

    EMC filter 

    of Class C2

     

    +Rb and -Rb terminals

    are used onlyfor connecting

    brake resistor 

    dU/dt filter 

     AT24-5K5 . . .11K-380-2*****

    variable-frequency drive

    PE

    -R  b  

    -DC and +Rb terminals

    are used

    for connecting

    regeneration unit

    *

                 *

    For variable-frequency drives w/o any 

    built-in chokes in DC-link 

    Grounding plate

    -D  C 

    + L   d  +Ld and +Ud terminals

    are used for 

    connecting

    the DC-link external choke

     АС DC 

    DC  АС 

    2

  • 8/16/2019 Catalogue АТ24 2015 05

    18/67

    2.4

    Technical characteristicsSupply voltage 3х380 V (-15 % ..+10 %)

    Supply frequency 50 Hz (-15 %..+10 %)

    EMC lter built-in

    Discrete change of frequency

    assignments0,1 Hz

    Power factor > 0,95

    Eciency 96 ... 97 %

    Starting current not higher than the calculated input current

    Control laws• linear dependence U/f • quadratic dependence U/f • the programmable U/f 

    Current limit in motoring and generative modes

    Permissible cable lengthto the motor

    max 30 m (shielded)/max 50 m (unshielded)

    Braking • DC braking• combined braking

    DC reactor built-in

    Control panel graphic, 160X160 pixels, 3’’

    Output frequency 0 — 400 Hz

    Braking resistor external

    PWM frequency / PWM carrierfrequency

    2 — 10 kHz/5 kHz

    Frequency range for dierentmotors

    0 — 400 Hz

    Speed range 1:1000 in a closed-loop system with a speed sensor1:100 in an open-loop system

    Fixed speed accuracy (static) invector control mode, withoutspeed sensor

    < 5 % at rated load of motor shaft and rated motor speed

    Fixed speed accuracy (static) invector control mode, with speedsensor

    < 2 % at rated load of motor shaft and rated motor speed

    Torque accuracy+/- 5 % in a closed-loop system+/- 10 % in an open-loop system

    Overload characteristics150 % — for 2 seconds, 120 % —  for 60 seconds withan ambient temperature 50 °С

    Asynchronousmotor control prole

    • vector control in a closed-loop system with a speed feedback• vector control in open-loop system without a speed feedback• voltage / frequency U/F ratio control (scalar control)

    Cycle adjustment PID-controller

    Slip compensation implemented

    Local signaling run, ready, fault — green, yellow and red LEDs

    Insulation• isolated control circuits• insulated custom circuits

    Supply 10 V DC, +/- 2 % current not exceeding 30 mA, 24 V, 60 mA

    Number of analog inputs 2

    2

  • 8/16/2019 Catalogue АТ24 2015 05

    19/67

    2.5

    Type analog input programmable 4..20 mA, 0..5 mA, 0..10 V

    Sampling period 4 ms

    Number of analog outputs 1

    Type of analog output programmable 4..20 mA, 0..5 mA, 0..10 V

    Number of digital outputs 4 relay outputs

    Type of digital outputs• 2 outputs are switching type• 2 outputs are normally open type

    Number of digital inputs 8

    Type of digital inputs• 24 V, input resistance: about 4 kOhm• PTC sensor, Resistance switch 3 kOhm/1,8 kOhm• emergency stop

    The logic of the digital input 2 digital inputs arbitrary polarity

    Acceleration and deceleration S-shaped acceleration / deceleration, linear adjustable

    Type of protection

    • power switch (U, V, W, T)• OCP hardware (U, V, W) / OCP software (U, V, W)• temperature of switches• Ud max/ Ud min• loss of one or more phases• overheating of the braking resistor• motor overload /motor overheating

    Dielectric strengthfor power circuits and auxiliary circuits having electrical com-munication with the power circuit — 2500 V

    Insulation resistance > 1 MOhm

    Output frequency discreteness 0,1 HzCommunication protocol Modbus

    Physical interface 2-wire RS-485 for Modbus

    Frame transmission RTU for Modbus

    Data transfer rate• 115200 bps• 1200 — 250000 bps• up to 1 bps

    Data format 8 bit, 1 stop bit , no parity

    Addresses number 1 .. 255 addresses for Modbus

    Access method slave

    Control options Bluetooth module or Wi-Fi module

    Electromagnetic compatibility• EN 55011 class A, group 2, IEC/EN 61800-3, category С2•with the additional EMC lter, EN 55011 class В, group 1,IEC/EN 61800-3, category С1

    Relative humidity 95 %

    The ambient temperature duringoperation / storage

    -20….+50 °C / -40….+50 °C (humidity-controlled)

    StandardsGOST 24607-88, GOST 13109-97, GOST 15150-69, GOST 14254-96,GOST 17516.1-90, GOST 12.1.044-89, EN 61800-3:2004, EN 55011,ЕN 61000-6 3/4

    Line 2

    2

  • 8/16/2019 Catalogue АТ24 2015 05

    20/67

    2.6

    Model range Line 2

    Triol AТ24 modelRated motorpower, kW

    Rated currentof power circuit, A

    Total VFD outputpower, kVA

    АТ24-5К5-380-2***** 5,5 11 7,5

    АТ24-7К5-380-2***** 7,5 15 10АТ24-11К-380-2***** 11,0 22 15

    АТ24-15К-380-2***** 15,0 30 18

    АТ24-18К-380-2***** 18,0 36 22

    АТ24-22К-380-2***** 22,0 45 28

    АТ24-30К-380-2***** 30,0 60 38

    АТ24-37К-380-2***** 37,0 75 45

    АТ24-45К-380-2***** 45,0 90 56

    АТ24-55К-380-2***** 55,0 110 72

    Mounting dimensions

    Triol AТ24 model L, mm H, mm D, mm

    АТ24-5К5-380-2*****

    190 283

    6

    АТ24-7К5-380-2*****

    АТ24-11К-380-2*****

    АТ24-15К-380-2*****

    254 345АТ24-18К-380-2*****

    АТ24-22К-380-2*****АТ24-30К-380-2*****

    АТ24-37К-380-2*****

    291 535АТ24-45К-380-2*****

    АТ24-55К-380-2*****

    4 holes ØD

    2

  • 8/16/2019 Catalogue АТ24 2015 05

    21/67

    2.7

    Overall dimensions

    Triol AТ24 model Width, mm Height, mm Depth, mmVFD weight,

    kg

    АТ24-5К5-380-2*****216,5 360 187 14АТ24-7К5-380-2*****

    АТ24-11К-380-2*****

    АТ24-15К-380-2*****

    280 444 257 32АТ24-18К-380-2*****

    АТ24-22К-380-2*****

    АТ24-30К-380-2*****

    АТ24-37К-380-2*****

    325 615 285 47АТ24-45К-380-2*****

    АТ24-55К-380-2*****

    Dimensional outlineАТ24-5К5-380-2*****, АТ24-7К5-380-2*****, АТ24-11К-380-2*****

    Line 2

    2

  • 8/16/2019 Catalogue АТ24 2015 05

    22/67

    2.8

    Dimensional outlineAТ24-37К-380-2*****, AТ24-45К-380-2*****, AТ24-55К-380-2*****

    Dimensional outlineАТ24-15К-380-2*****, АТ24-18К-380-2*****,АТ24-22К-380-2*****, АТ24-30К-380-2*****

    2

  • 8/16/2019 Catalogue АТ24 2015 05

    23/67

    3.1

    Line 3

     Application

    Triol AT24 VFD Line 3 is specially designed for heating, ventilation and air conditioningsystems. Metal enclosure with IP20 protection degree allows avoiding VFD’s installation inthe boxes and long cable routing. A large number of security and service functions makesthis VFD multipurpose solution.

    Key functions

    • start, stop and control of motor rotation frequency;• acceleration and braking ramps including S-shaped ramps;• reversal;• acceleration, decreasing, stop;• protection of the motor overcurrent, overload protection;• motor control by external 2-wire and 3-wire sensors;• saving control conguration of motor;• dynamic braking of motor;

    • simultaneous control of ve motors («Cascade controller» macros);• automatic control of technology processes by closed-loop system principle using

    built-in PID-controller;• operation of asynchronous motor by custom preset diagram in automatic or manual mode.

    3

  • 8/16/2019 Catalogue АТ24 2015 05

    24/67

    3.2

    Mechanical parameters

    • plastic enclosure, IP20;• forced cooling (fans, air ow direction from the bottom upwards);• operation temperature -20 °С ... + 50 °С;• simple connection of input and output cables;• convenient demountable control panel with graphic display;• possibility of installation in small-size cabinets or in conned space;• resistance to continuous sinewave vibration 0.5 G in three plans.

    Protection functions

    • closedown under fuse blowing;• variable frequency drive emergency tripping in case:

    ◊ temperature exceed critical values◊ increasing of voltage in DC-link◊decreasing of voltage in DC-link◊short-circuit at VFD output◊ by a signal («Power switch» emergency)◊ output current exceed preset values

    • blocking of asynchronous motor reverse;• disabling of VFD continuous duty under resonant frequencies for prevent an executive

    units damages;• disabling of start-up after coast stop during specied time;• after emergency, for protection against start-up of rotating motor;• blocking of start-up after emergency tripping.

    3

  • 8/16/2019 Catalogue АТ24 2015 05

    25/67

    3.3

    Line 3

    Power cables connection diagram

    Line-disconnection

    Panel for fixing ground cables

    and connecting cable shields

    Terminal

    «Protective earthing» (PE)

    -DC and +Rb terminals

    are used

    for connecting

    regeneration unit

    +Rb and -Rb terminals

    are used only

    for connecting

    brake resistor 

     AT24-75K . . .M11-380-3A****

    variable-frequency drive

    dU/dt filter 

                 *

    Note. In VFD AT24-75K...M11-380-31****

    «-Rb» terminal do not used; it is reserve

    3

  • 8/16/2019 Catalogue АТ24 2015 05

    26/67

    3.4

    Technical characteristicsSupply voltage 3х380 V (-15 % ..+10 %)

    Supply frequency 50 Hz (-15 %..+10 %)

    EMC lter built-in

    Discrete change of frequency

    assignments0,1 Hz

    Power factor > 0,95

    Eciency 96 ... 97 %

    Starting current not higher than the calculated input current

    Control laws• linear dependence U/f • quadratic dependence U/f • the programmable U/f 

    Current limit in motoring and generative modes

    Permissible cable lengthto the motor

    max 30 m (shielded)/max 50 m (unshielded)

    Braking • DC braking• combined braking

    DC reactor built-in

    Control panel graphic, 160X160 pixels, 3’’

    Output frequency 0 — 400 Hz

    Braking resistor external

    PWM frequency / PWM carrierfrequency

    2 — 10 kHz

    Frequency range for dierentmotors

    0 — 400 Hz

    Speed range 1:1000 in a closed-loop system with a speed sensor1:100 in an open-loop system

    Fixed speed accuracy (static) invector control mode, withoutspeed sensor

    < 5 % at rated load of motor shaft and rated motor speed

    Fixed speed accuracy (static) invector control mode, with speedsensor

    < 2 % at rated load of motor shaft and rated motor speed

    Torque accuracy+/- 5 % in a closed-loop system+/- 10 % in an open-loop system

    Overload characteristics150 % — for 2 seconds, 120 % —  for 60 seconds withan ambient temperature 50 °С

    Asynchronousmotor control prole

    • vector control in a closed-loop system with a speed feedback• vector control in open-loop system without a speed feedback• voltage / frequency U/F ratio control (scalar control)

    Cycle adjustment PID-controller

    Slip compensation implemented

    Local signaling run, ready, fault — green, yellow and red LEDs

    Insulation• isolated control circuits• insulated custom circuits

    Supply 10 V DC, +/- 2 % current not exceeding 30 mA, 24 V, 60 mA

    Number of analog inputs 2

    3

  • 8/16/2019 Catalogue АТ24 2015 05

    27/67

    3.5

    Type analog input programmable 4..20 mA, 0..5 mA, 0..10 V

    Sampling period 4 ms

    Number of analog outputs 1

    Type analog output programmable 4..20 mA, 0..5 mA, 0..10 V

    Number of digital outputs 4 relay outputs

    Type of digital output• 2 outputs are switching type• 2 outputs are normally open type

    Number of digital inputs 8

    Type of digital input• 24 V, input resistance: about 4 kOhm• PTC sensor, Resistance switch 3 kOhm/1,8 kOhm• emergency stop

    The logic of the digital input 2 digital inputs arbitrary polarity

    Acceleration and deceleration S-shaped acceleration / deceleration, linear adjustable

    Type of protection

    • power switch (U, V, W, T)• OCP hardware (U, V, W) / OCP software (U, V, W)• temperature of switches• Ud max/ Ud min• loss of one or more phases• overheating of the braking resistor• motor overload /motor overheating

    Dielectric strengthfor power circuits and auxiliary circuits having electrical com-munication with the power circuit — 2500 V

    Insulation resistance > 1 MOhm

    Output frequency discreteness 0,1 HzCommunication protocol Modbus

    Physical interface 2-wire RS-485 for Modbus

    Frame transmission RTU for Modbus

    Data transfer rate• 115200 bps• 1200 — 250000 bps• up to 1 bps

    Data format 8 bit, 1 stop bit , no parity

    Addresses number 1 .. 255 addresses for Modbus

    Access method slave

    Control options Bluetooth module or Wi-Fi module

    Electromagnetic compatibility• EN 55011 class A, group 2, IEC/EN 61800-3, category С2•with the additional EMC lter, EN 55011 class В, group 1,IEC/EN 61800-3, category С1

    Relative humidity 95 %

    The ambient temperature duringoperation / storage

    -20….+50 °C / -40….+50 °C (humidity-controlled)

    StandardsGOST 24607-88, GOST 13109-97, GOST 15150-69, GOST 14254-96,GOST 17516.1-90, GOST 12.1.044-89, EN 61800-3:2004, EN 55011,ЕN 61000-6 3/4

    Line 3

    3

  • 8/16/2019 Catalogue АТ24 2015 05

    28/67

    3.6

    Model range Line 3

    Model of Triol AT24Rated motorpower, kW

    Rated currentof power circuit, A

    Total VFD outputpower, kVA

    АТ24-75К-380-3***** 75 155 100

    АТ24-90К-380-3***** 90 185 120АТ24-М11-380-3***** 110 216 145

    АТ24-М13-380-3***** 130 260 175

    АТ24-М16-380-3***** 160 320 210

    АТ24-М20-380-3***** 200 400 260

    АТ24-М25-380-3***** 250 500 330

    Mounting dimensions

    Triol AТ24 model L, mm H, mm D, mmАТ24-75К-380-3*****

    490 821,5

    9

    АТ24-90К-380-3*****

    АТ24-М11-380-3*****

    АТ24-М13-380-3*****

    598АТ24-М16-380-3*****

    АТ24-М20-380-3*****

    АТ24-М25-380-3*****

    4 holes ØD

    3

  • 8/16/2019 Catalogue АТ24 2015 05

    29/67

    3.7

    Overall dimensions

    Triol AТ24 model Width, mm Height, mm Depth, mmVFD weight,

    kg

    АТ24-75К-380-3*****

    528,5 803,5 334 85АТ24-90К-380-3*****

    АТ24-М11-380-3*****

    АТ24-М13-380-3*****

    650 1312 490 230АТ24-М16-380-3*****

    АТ24-М20-380-3*****

    АТ24-М25-380-3*****

    Dimensional outlineАТ24-75К-380-3*****, АТ24-90K-380-3*****, АТ24-М11-380-3*****

    Line 3

    3

  • 8/16/2019 Catalogue АТ24 2015 05

    30/67

    3.8

    Dimensional outlineАТ24-М13-380-3*****, АТ24-М16-380-3*****,АТ24-М20-380-3*****, АТ24-М25-380-3*****

    3

  • 8/16/2019 Catalogue АТ24 2015 05

    31/67

    4.1

    Line 4

     Application

    Triol AT24 VFD Line 4 is known for its multifunctional performance and exibility in suchspheres of application as ventilation and air conditioning. Due to its optimal constructionthis VFD allows realization of a big variety of tasks. This makes the VFD universal solution.This line can be identied by high quality, easiness of access and simplicity of operation.

    Key functions

    • start/reversal/stop of motor with assigned rates;• changing and autonomic presetting an acceleration / deceleration time;• connecting regenerative unit is available;• frequency mode of motor deceleration;• permit of resonant frequencies.

    4

  • 8/16/2019 Catalogue АТ24 2015 05

    32/67

    4.2

    Mechanical parameters

    • plastic enclosure, IP20;• forced cooling (fans, air ow direction from the bottom upwards);• operation temperature -10 °С ... + 40 °С;• simple connection of input and output cables;• convenient demountable control panel with 7-segment indicator;• it is allowable an installation in small-size cabinets or in conned space;• resistance to continuous sinewave vibration 0.5 G in three plans.

    Protection functions

    • closedown under fuse blowing;• variable frequency drive emergency tripping in case:

    ◊ temperature exceed critical values◊ increasing of voltage in DC-link◊decreasing of voltage in DC-link◊short-circuit at VFD output◊ by a signal («Power switch» emergency)◊ output current exceed preset values

    • blocking of asynchronous motor reverse;• disabling of VFD continuous duty under resonant frequencies for prevent an executive

    units damages;• disabling of start-up after coast stop during specied time;• after emergency, for protection against start-up of rotating motor;• blocking of start-up after emergency tripping.

    4

  • 8/16/2019 Catalogue АТ24 2015 05

    33/67

    4.3

    Line 4

    Power cables connection diagram

    external brakingconverter 

    external DC breaker external braking resistor 

    Supply 380 V50/60 Hz

    Terminals

    Input

    Supply for carrier frequency

    Multifunctionalanalog input

    Relay output 2

    Relay output 1

    High-speedimpulse output

     Analog output 1 Analog output 10 — 10 V

    0 — 20 mA

     Analog output 2

    0 — 10 V

    0 — 20 mA

     AT24-37K...4K0-380-4XXXXX

    +10V

    VCT

    CCI

    4

  • 8/16/2019 Catalogue АТ24 2015 05

    34/67

    4.4

    Technical characteristicsSupply voltage 3х380 V (-15 % ..+10 %)

    Supply frequency 50 Hz (-15 %..+10 %)

    EMC lter built-in

    Discrete change of frequency

    assignments0,1 Hz

    Power factor > 0,95

    Eciency 96 ... 97 %

    Starting current not higher than the calculated input current

    Control laws• linear dependence U/f • quadratic dependence U/f • the programmable U/f 

    Current limit in motoring and generative modes

    Permissible cable lengthto the motor

    max 30 m (shielded)/max 50 m (unshielded)

    Braking • DC braking• combined braking

    DC reactor external, optional

    Control panel graphic

    Output frequency 0 — 400 Hz

    Braking resistor external

    PWM frequency / PWM carrierfrequency

    1...15 kHz

    Frequency range for dierentmotors

    0 — 400 Hz

    Speed range 1:1000 in a closed-loop system with a speed sensor1:100 in an open-loop system

    Fixed speed accuracy (static) invector control mode, withoutspeed sensor

    < 5 % at rated load of motor shaft and rated motor speed

    Fixed speed accuracy (static) invector control mode, with speedsensor

    < 2 % at rated load of motor shaft and rated motor speed

    Torque accuracy+/- 5 % in a closed-loop system+/- 10 % in an open-loop system

    Overload characteristics 120 % — for 60 seconds with an ambient temperature 45 °С

    Motor control prole vector/scalar

    Cycle adjustment PID-controller

    Slip compensation implemented

    Local signaling run, ready, fault — green, yellow and red LEDs

    Insulation• isolated control circuits• insulated custom circuits

    Supply 10 V DC, +/- 2 % current not exceeding 30 mA, 24 V, 60 mA

    Number of analog inputs 1

    Type analog input programmable 0..20 mA, 0..10 V

    Sampling period 4 ms

    4

  • 8/16/2019 Catalogue АТ24 2015 05

    35/67

    4.5

    Number of analog outputs 2

    Type analog output programmable 0..20 mA, 0..10 V

    Number of digital outputs 6

    Type of digital output• 2 outputs are normally close type• 2 outputs are normally open type

    Number of digital inputs 2

    Type of digital input • 24 V, input resistance: about 4 kOhm

    Acceleration and deceleration time 0,1...3600 s

    Type of protection

    • OCP hardware (U, V, W) / OCP software (U, V, W)• Ud max/ Ud min• loss of one or more phases• indicator of DC-link charge

    Dielectric strengthfor power circuits and auxiliary circuits having electrical

    communication with the power circuit — 2500 VInsulation resistance > 1 MOhm

    Output frequency discreteness 0,1 Hz

    Communication protocol Modbus

    Physical interface 2-wire RS-485 for Modbus

    Frame transmission RTU for Modbus

    Data transfer rate• 115200 bps• 1200 — 250000 bps• up to 1 bps

    Data format 8 bit, 1 stop bit , no parity

    Addresses number 1 .. 255 addresses for Modbus

    Access method slave

    Control options Bluetooth module or Wi-Fi module

    Electromagnetic compatibility • EN 55011 class A, group 2, IEC/EN 61800-3, category С3

    Relative humidity 95 %

    The ambient temperature duringoperation / storage

    -10….+45 °C

    StandardsGOST 24607-88, GOST 13109-97, GOST 15150-69, GOST 14254-96,GOST 17516.1-90, GOST 12.1.044-89, EN 61800-3:2004, EN 55011,

    ЕN 61000-6 3/4

    Line 4

    4

  • 8/16/2019 Catalogue АТ24 2015 05

    36/67

    4.6

    Model range Line 4

    Model of Triol AT24Rated motorpower, kW

    Rated currentof power circuit, A

    Total VFD outputpower, kVA

    АТ24-К75-380-4**** 0,75 1,5 1,0

    АТ24-1К5-380-4***** 0,15 3,0 2,0АТ24-2К2-380-4***** 0,22 4,5 3,0

    АТ24-4К0-380-4***** 4,00 8,0 5,3

    Mounting dimensionsTriol AТ24 model L, mm H, mm D, mm

    АТ24-К75-380-4****

    74 162 4,5АТ24-1К5-380-4*****

    АТ24-2К2-380-4*****

    АТ24-4К0-380-4***** 110 255 7

    Overall dimensions

    Triol AТ24 model Width, mm Height, mm Depth, mmVFD weight,

    kg

    АТ24-К75-380-4****

    92 174 132 1.5АТ24-1К5-380-4*****

    АТ24-2К2-380-4*****

    АТ24-4К0-380-4***** 135 265 165 4

    Dimensional outlineАТ24-К75...4К0-380-4*****

     

    W

    W1

    D

    D1

          H      1

          H      2

          H

    2- d

          D      2

    4

  • 8/16/2019 Catalogue АТ24 2015 05

    37/67

    C.1

    Line C 

     Application

    Triol AT24 VFD Line C is the best solution to increase the pumps productivity. This lineis characterized by a robust construction, multifunctionality and exibility. This drive isa great option to ensure smooth operation of equipment, increasing its life period thanksto the exibility and modernity of the technical solutions.

    Key functions

    • start, stop and control the rotation frequency of pump’s motor;• acceleration and braking with assigned rates;• reversal;• acceleration, decreasing, stop;• protection of the motor against overcurrent, overload protection;• motor control by external 2-wire and 3-wire sensors;• saving control conguration of motor;

    • dynamic braking of motor;• control ve motors at the same time («Cascade controller» macros);• automatic control of technology processes by closed-loop system principle using built-in

    PID-controller;• automatically restart asynchronous motor after supply voltage failure or after special

    emergencies of motor (customized emergencies);• operation of asynchronous motor by custom preset diagram in automatic or manual mode.

    С

  • 8/16/2019 Catalogue АТ24 2015 05

    38/67

    C.2

    Mechanical parameters

    • plastic enclosure, IP54;• forced cooling (fans, air ow direction from the bottom upwards);• operation temperature -20 oС ... + 40 °С;• simple connection of input and output cables;• convenient demountable control panel with graphic display;• it is allowable an installation in small-size cabinets or in conned space;• resistance to continuous sinewave vibration 0.5 G in three plans.

    Protection functions

    • closedown under fuse blowing;• variable frequency drive emergency tripping in case:

    ◊ temperature exceed critical values◊ increasing of voltage in DC-link◊decreasing of voltage in DC-link◊short-circuit at VFD output◊ by a signal («Power switch» emergency)◊ output current exceed preset values

    • blocking of asynchronous motor reverse;• disabling of VFD continuous duty under resonant frequencies for prevent an executive

    units damages;• disabling of start-up after coast stop during specied time;• after emergency, for protection against start-up of rotating motor;• blocking of start-up after emergency tripping.

    С

  • 8/16/2019 Catalogue АТ24 2015 05

    39/67

    C.3

    Line C 

    Power cables connection diagram (  АТ24-5К5...11К  )

     AT24-5K5 . . .11K-380-C*****

    variable-frequency drive

    Line-disconnection

    Grounding plate

    +Rb and -Rb terminals

    are used only

    for connecting

    brake resistor 

    -DC and +Rb terminals

    are used

    for connecting

    regeneration unit

    +Ld and +Ud terminals

    are used for 

    connecting

    the DC-link external choke

    dU/dt filter 

    For variable-frequency drives w/o any 

    built-in chokes in DC-link 

                 *

    С

  • 8/16/2019 Catalogue АТ24 2015 05

    40/67

    C.4

    Power cables connection diagram (  АТ24-15К...30К  )

    Line-disconnection

    Grounding plate

    +Rb and -Rb terminalsare used only

    for connecting

    brake resistor 

    +DC and -DC terminals

    are used

    for connecting

    regeneration unit

     AT24-15K . . .30K-380-C*****

    variable-frequency drive

    dU/dt filter 

    +DC and -DC terminals are brought out

    in variable speed drives w/o built-in braking unit;

    +Rb and -Rb terminals are brought out

    in variable speed drives with built-in braking unit

                 *

                 *

    С

  • 8/16/2019 Catalogue АТ24 2015 05

    41/67

    C.5

    Line C 

    Power cables connection diagram (  АТ24-37К...55К  )

    Line-disconnection

    Grounding plate

     AT24-37K . . .55K-380-C*****

    variable-frequency drive

    -DC and +Rb terminals

    are used

    for connecting

    regeneration unit

    +Rb and -Rb terminals

    are used only

    for connecting

    brake resistor 

    dU/dt filter 

    С

  • 8/16/2019 Catalogue АТ24 2015 05

    42/67

    C.6

    Technical characteristicsSupply voltage 3х380 V (-15 % ..+10 %)

    Supply frequency 50 Hz (-15 %..+10 %)

    EMC lter external

    DC reactor built-in

    Control panel graphic, 160X160 pixels, 3’’

    Output frequency 0 — 400 Hz

    Discrete change of frequencyassignments

    0,1 Hz

    Power factor > 0,93

    Eciency 96 ... 97 %

    Starting current not higher than the calculated input current

    Current limit in motoring and generative modes

    Control laws

    • linear dependence U/f 

    • quadratic dependence U/f • the programmable U/f 

    Acceleration and deceleration time 0 ... 4000 s

    Permissible cable lengthto the motor

    max 30 m (shielded)/max 50 m (unshielded)

    Braking• DC braking• combined braking

    Braking resistor external

    PWM frequency / PWM carrierfrequency

    2 — 10 kHz

    Frequency range for dierentmotors 0 — 400 Hz

    Speed range1:1000 in a closed-loop system with a speed sensor1:100 in an open-loop system

    Fixed speed accuracy (static) invector control mode, withoutspeed sensor

    < 5 % at rated load of motor shaft and rated motor speed

    Fixed speed accuracy (static) invector control mode, with speedsensor

    < 2 % at rated load of motor shaft and rated motor speed

    Torque accuracy+/- 5 % in a closed-loop system

    +/- 10 % in an open-loop systemOverload characteristics 120 % from rated value for 120 s, averaging time —10 min

    Asynchronousmotor control prole

    • vector control in a closed-loop system with a speed feedback• vector control in open-loop system without a speed feedback• voltage / frequency U/F ratio control (scalar control)

    Cycle adjustment PID-controller

    Slip compensation implemented

    Local signaling run, ready, fault — green, yellow and red LEDs

    Insulation• isolated control circuits• insulated custom circuits

    Supply 10 V DC, +/- 2 % current not exceeding 30 mA, 24 V, 60 mANumber of analog inputs 2

    С

  • 8/16/2019 Catalogue АТ24 2015 05

    43/67

    C.7

    Type analog inputs programmable 4..20 mA,, 0..5 mA,, 0..10 V

    Sampling period 4 ms

    Number of analog outputs 1

    Type analog output programmable 4..20 mA, 0..5 mA, 0..10 V

    Number of digital outputs 4 relay outputs

    Type of digital output• 2 outputs are normally close type• 2 outputs are normally open type

    Digital outputs with custom logic(PNP or NPN)

    6

    Number of digital inputs 8

    Type of digital input• 24 V, input resistance: about 4 kOhm• PTC sensor, Resistance switch 3 kOhm/1,8 kOhm• emergency stop

    Acceleration and deceleration S-shaped acceleration / deceleration, linear adjustable

    Type of protection

    • power switch (U, V, W, T)• OCP hardware (U, V, W) / OCP software (U, V, W)• temperature of switches• Ud max/ Ud min• loss of one or more phases• overheating of the braking resistor• motor overload /motor overheating

    Dielectric strengthfor power circuits and auxiliary circuits having electricalcommunication with the power circuit — 2500 V

    Insulation resistance > 1 MOhm

    Communication protocol Modbus

    Physical interface 2-wire RS-485 for Modbus

    Frame transmission RTU for Modbus

    Data transfer rate• 115200 bps• 1200 — 250000 bps• up to 1 bps

    Data format 8 bit, 1 stop bit , no parity

    Addresses number 1 .. 255 addresses for Modbus

    Access method slave

    Control options Bluetooth module or Wi-Fi module

    Electromagnetic compatibility• EN 55011 class A, group 2, IEC/EN 61800-3, category С3•with the additional EMC lter, EN 55011 class В, group 1,IEC/EN 61800-3, category С1

    Relative humidity 80 % at a temperature of +20 °С (with no condensation)

    Optional unit «ЕХТ1» unit, for expand numbers of input / output

    StandardsGOST 24607-88,GOST 13109-97, GOST 15150-69, GOST 14254-96,GOST 17516.1-90, GOST 12.1.044-89, EN 61800-3:2004, EN 55011,ЕN 61000-6 3/4

    Line C 

    С

  • 8/16/2019 Catalogue АТ24 2015 05

    44/67

    C.8

    Model range Line C 

    Model of Triol AT24Rated motor pow-

    er, kWRated current

    of power circuit, ATotal VFD output

    power, kVA

    АТ24-5К5-380-C***** 5,5 11 7,5

    АТ24-7К5-380-C***** 7,5 15 10АТ24-11К-380-C***** 11,0 22 15

    АТ24-15К-380-C***** 15,0 30 18

    АТ24-18К-380-C***** 18,0 36 22

    АТ24-22К-380-C***** 22,0 45 28

    АТ24-30К-380-C***** 30,0 60 38

    АТ24-37К-380-C***** 37,0 75 45

    АТ24-45К-380-C***** 45,0 90 56

    АТ24-55К-380-C***** 55,0 110 72

    Mounting dimensions

    Triol AТ24 model L, mm H, mm D, mm

    АТ24-5К5-380-С*****190 283

    6

    АТ24-7К5-380-С*****

    АТ24-11К-380-С*****

    АТ24-15К-380-С*****

    254 344

    АТ24-18К-380-С*****

    АТ24-22К-380-С*****

    АТ24-30К-380-С*****

    АТ24-37К-380-С*****

    АТ24-45К-380-С*****291 535

    АТ24-55К-380-С*****

    4 holes ØD

    С

  • 8/16/2019 Catalogue АТ24 2015 05

    45/67

    C.9

    Line C 

    Overall dimensions

    Triol AТ24 model Width, mm Height, mm Depth, mmVFD weight,

    kg

    АТ24-5К5-380-C*****

    220 310 190 14АТ24-7К5-380-C*****

    АТ24-11К-380-C*****

    АТ24-15К-380-C*****

    280 380 260 32

    АТ24-18К-380-C*****

    АТ24-22К-380-C*****

    АТ24-30К-380-C*****

    АТ24-37К-380-C*****

    АТ24-45К-380-C*****330 540 290 47АТ24-55К-380-C*****

    Dimensional outlineАТ24-5К5-380-С*****, АТ24-7К5-380-С*****, АТ24-11К-380-С***** С

  • 8/16/2019 Catalogue АТ24 2015 05

    46/67

    C.10

    Dimensional outline

    АТ24-37К-380-С*****, АТ24-45К-380-С*****, АТ24-55К-380-С*****.

    Dimensional outlineАТ24-15К-380-С*****, АТ24-18К-380-С*****,АТ24-22К-380-С*****, АТ24-30К-380-С*****

    С

  • 8/16/2019 Catalogue АТ24 2015 05

    47/67

    Е.1

    Line Е 

     Application

    Triol AT24 line E is specially designed in accordance with many exploitation specics forpumps and fans control. Application of such a VFD provides reduced power consumptionand smooth operation of the equipment. Such a multifunctional and reliable solution willnot only implement the current tasks, but also prolong the equipment lifetime.

    Key functions

    • start, stop and control the rotation frequency of pump’s motor;• acceleration and braking with assigned rates;• reversal;• acceleration, decreasing, stop;• protection of the motor against overcurrent, overload protection;• motor control by external 2-wire and 3-wire sensors;• saving control conguration of motor;

    • dynamic braking of motor;• control ve motors at the same time («Cascade controller» macros);• automatic control of technology processes by closed-loop system principle using built-in

    PID-controller;• automatically restart asynchronous motor after supply voltage failure or after special

    emergencies of motor (customized emergencies);• operation of asynchronous motor by custom preset diagram in automatic or manual mode.

    Е

  • 8/16/2019 Catalogue АТ24 2015 05

    48/67

    Е.2

    Е

    Mechanical parameters

    • metal enclosure, IP20;• forced cooling (fans, air ow direction from the bottom upwards);• operation temperature -20 °С ... + 40 °С;• simple connection of input and output cables;• convenient demountable control panel with graphic display;• it is allowable an installation in small-size cabinets or in conned space;• resistance to continuous sinewave vibration 0.5 G in three plans.

    Protection functions

    • closedown under fuse blowing;• variable frequency drive emergency tripping in case:

    ◊ temperature exceed critical values◊ increasing of voltage in DC-link◊decreasing of voltage in DC-link◊short-circuit at VFD output◊ by a signal («Power switch» emergency)◊ output current exceed preset values

    • blocking of asynchronous motor reverse;• disabling of VFD continuous duty under resonant frequencies for prevent an executive

    units damages;• disabling of start-up after coast stop during specied time;• after emergency, for protection against start-up of rotating motor;• blocking of start-up after emergency tripping.

  • 8/16/2019 Catalogue АТ24 2015 05

    49/67

    Е.3

    Е

    Line Е 

    Power cables connection diagram (  АТ24-75К..М11 )

    Terminal

    «Protective earthing» (PE)

    Line-disconnection

    Panel for fixing ground cables

    and connecting cable shields

     AT24-75K . . .M11-380-EA****

    variable-frequency drive

    +Rb and -DC terminals

    are used

    for connecting

    regeneration unit

    +Rb and -Rb terminals

    are used only

    for connecting

    brake resistor 

    dU/dt filter 

  • 8/16/2019 Catalogue АТ24 2015 05

    50/67

    Е.4

    Е

    Technical characteristicsSupply voltage 3х380 V (-15 % ..+10 %)

    Supply frequency 50 Hz (-15 %..+10 %)

    EMC lter external

    DC reactor built-in

    Control panel graphic, 160X160 pixels, 3’’

    Output frequency 0 — 400 Hz

    Discrete change of frequencyassignments

    0,1 Hz

    Power factor > 0,93

    Eciency 96 ... 97 %

    Starting current not higher than the calculated input current

    Current limit in motoring and generative modes

    Control laws

    • linear dependence U/f 

    • quadratic dependence U/f • the programmable U/f 

    Acceleration and deceleration time 0 ... 4000 s

    Permissible cable lengthto the motor

    max 30 m (shielded)/max 50 m (unshielded)

    Braking• DC braking• combined braking

    Braking resistor external

    PWM frequency / PWM carrierfrequency

    2 — 10 kHz

    Frequency range for dierentmotors 0 — 400 Hz

    Speed range1:1000 in a closed-loop system with a speed sensor1:100 in an open-loop system

    Fixed speed accuracy (static) invector control mode, withoutspeed sensor

    < 5 % at rated load of motor shaft and rated motor speed

    Fixed speed accuracy (static) invector control mode, with speedsensor

    < 2 % at rated load of motor shaft and rated motor speed

    Torque accuracy+/- 5 % in a closed-loop system

    +/- 10 % in an open-loop systemOverload characteristics 120 % from rated value for 120 s, averaging time —10 min

    Asynchronousmotor control prole

    • vector control in a closed-loop system with a speed feedback• vector control in open-loop system without a speed feedback• voltage / frequency U/F ratio control (scalar control)

    Cycle adjustment PID-controller

    Slip compensation implemented

    Local signaling run, ready, fault — green, yellow and red LEDs

    Insulation• isolated control circuits• insulated custom circuits

    Supply 10 V DC, +/- 2 % current not exceeding 30 mA, 24 V, 60 mANumber of analog inputs 2

  • 8/16/2019 Catalogue АТ24 2015 05

    51/67

    Е.5

    Е

    Type analog inputs programmable 4..20 mA,, 0..5 mA,, 0..10 V

    Sampling period 4 ms

    Number of analog outputs 1

    Type analog output programmable 4..20 mA, 0..5 mA, 0..10 V

    Number of digital outputs 4 relay outputs

    Type of digital output• 2 outputs are switching type• 2 outputs are normally open type

    Digital outputs with custom logic(PNP or NPN)

    6

    Number of digital inputs 8

    Type of digital input• 24 V, input resistance: about 4 kOhm• PTC sensor, Resistance switch 3 kOhm/1,8 kOhm• emergency stop

    Acceleration and deceleration S-shaped acceleration / deceleration, linear adjustable

    Type of protection

    • power switch (U, V, W, T)• OCP hardware (U, V, W) / OCP software (U, V, W)• temperature of switches• Ud max/ Ud min• loss of one or more phases• overheating of the braking resistor• motor overload /motor overheating

    Dielectric strengthfor power circuits and auxiliary circuits having electricalcommunication with the power circuit — 2500 V

    Insulation resistance > 1 MOhm

    Communication protocol Modbus

    Physical interface 2-wire RS-485 for Modbus

    Frame transmission RTU for Modbus

    Data transfer rate• 115200 bps• 1200 — 250000 bps• up to 1 bps

    Data format 8 bit, 1 stop bit , no parity

    Addresses number 1 .. 255 addresses for Modbus

    Access method slave

    Control options Bluetooth module or Wi-Fi module

    Electromagnetic compatibility• EN 55011 class A, group 2, IEC/EN 61800-3, category С3•with the additional EMC lter, EN 55011 class В, group 1,IEC/EN 61800-3, category С1

    Relative humidity 80 % at a temperature of +20 °С (with no condensation)

    Optional unit «ЕХТ1» unit, for expand numbers of input / output

    StandardsGOST 24607-88,GOST 13109-97, GOST 15150-69, GOST 14254-96,GOST 17516.1-90, GOST 12.1.044-89, EN 61800-3:2004, EN 55011,ЕN 61000-6 3/4

    Line Е 

  • 8/16/2019 Catalogue АТ24 2015 05

    52/67

    Е.6

    Е

    Model range Line Е 

    Model of Triol AT24Rated

    motor power, kWRated current

    of power circuit, ATotal VFD output

    power, kVA

    АТ24-75К-380-Е***** 75 150 100

    АТ24-90К-380-Е***** 90 180 175АТ24-М11-380-Е***** 110 220 14

    Mounting dimensions

    Overall dimensions

    Triol AТ24 model Width, mm Height, mm Depth, mmVFD weight,

    kgАТ24-75К-380-Е*****

    394 740 260

    57

    АТ24-90К-380-Е*****58

    АТ24-М11-380-Е*****

    Triol AТ24 model L, mm H, mm D, mm

    АТ24-75К-380-Е*****

    232 718 9АТ24-90К-380-Е*****

    АТ24-М11-380-Е*****

    4 holes ØD

  • 8/16/2019 Catalogue АТ24 2015 05

    53/67

    Е.7

    Е

    Line Е 

    Dimensional outlineАТ24-75-380-Е*****, АТ24-90К-380-Е*****, АТ24-М11-380-Е****

  • 8/16/2019 Catalogue АТ24 2015 05

    54/67

    Е.8

  • 8/16/2019 Catalogue АТ24 2015 05

    55/67

    Н.1

    Line H

     Application

    Triol AT24 VFD Line H is a multifunction system that provides control of asynchronouselectric pumps for various purposes. This Line can be used to solve multiple issues thatrequire use of equipment in dicult conditions with maximum protection.

    Key functions

    • start, stop and control the rotation frequency of pump’s motor;• acceleration and braking with assigned rates;• reversal;• acceleration, decreasing, stop;• protection of the motor against overcurrent, overload protection;• motor control by external 2-wire and 3-wire sensors;• saving control conguration of motor;

    • dynamic braking of motor;• control ve motors at the same time («Cascade controller» macros);• automatic control of technology processes by closed-loop system principle using built-in

    PID-controller;• automatically restart asynchronous motor after supply voltage failure or after special

    emergencies of motor (customized emergencies);• operation of asynchronous motor by custom preset diagram in automatic or manual mode.

    Н/380 V

  • 8/16/2019 Catalogue АТ24 2015 05

    56/67

    Н.2

    Н/380 V

    Mechanical parameters

    • metal enclosure, IP54;• forced cooling (fans, air ow direction from the bottom upwards);• operation temperature -20 °С ... + 40 °С;• simple connection of input and output cables;• convenient demountable control panel with graphic display;• it is allowable an installation in small-size cabinets or in conned space;• resistance to continuous sinewave vibration 0.5 G in three plans.

    Protection functions

    • closedown under fuse blowing;• variable frequency drive emergency tripping in case:

    ◊ temperature exceed critical values◊ increasing of voltage in DC-link◊decreasing of voltage in DC-link◊short-circuit at VFD output◊ by a signal («Power switch» emergency)◊ output current exceed preset values

    • blocking of asynchronous motor reverse;• disabling of VFD continuous duty under resonant frequencies for prevent an executive

    units damages;• disabling of start-up after coast stop during specied time;• after emergency, for protection against start-up of rotating motor;• blocking of start-up after emergency tripping.

  • 8/16/2019 Catalogue АТ24 2015 05

    57/67

    Н.3

    Н/380 V

    Line H

    Power cables connection diagram (  АТ24-5К5...55К  )

    Line-disconnection

    Choke in DC link

    +Rb and -Rb terminals

    are used only

    for connecting

    brake resistor 

    dU/dt filter 

     AT24-5K5...55K-380-H*****

    variable frequency drive

  • 8/16/2019 Catalogue АТ24 2015 05

    58/67

    Н.4

    Н/380 V

    Technical characteristicsSupply voltage 3х380 V (-15 % ..+10 %)

    Supply frequency 50 Hz (-15 %..+10 %)

    EMC lter external

    DC reactor built-in

    Control panel graphic, 160X160 pixels, 3’’

    Output frequency 0 — 400 Hz

    Discrete change of frequencyassignments

    0,1 Hz

    Power factor > 0,93

    Eciency 96 ... 97 %

    Starting current not higher than the calculated input current

    Current limit in motoring and generative modes

    Control laws

    • linear dependence U/f 

    • quadratic dependence U/f • the programmable U/f 

    Acceleration and deceleration time 0 ... 4000 s

    Permissible cable lengthto the motor

    max 30 m (shielded)/max 50 m (unshielded)

    Braking• DC braking• combined braking

    Braking resistor external

    PWM frequency / PWM carrierfrequency

    2 — 10 kHz

    Frequency range for dierentmotors 0 — 400 Hz

    Speed range1:1000 in a closed-loop system with a speed sensor1:100 in an open-loop system

    Fixed speed accuracy (static) invector control mode, withoutspeed sensor

    < 5 % at rated load of motor shaft and rated motor speed

    Fixed speed accuracy (static) invector control mode, with speedsensor

    < 2 % at rated load of motor shaft and rated motor speed

    Torque accuracy+/- 5 % in a closed-loop system

    +/- 10 % in an open-loop systemOverload characteristics 120 % from rated value for 120 s, averaging time —10 min

    Asynchronousmotor control prole

    • vector control in a closed-loop system with a speed feedback• vector control in open-loop system without a speed feedback• voltage / frequency U/F ratio control (scalar control)

    Cycle adjustment PID-controller

    Slip compensation implemented

    Local signaling run, ready, fault — green, yellow and red LEDs

    Insulation• isolated control circuits• insulated custom circuits

    Supply 10 V DC, +/- 2 % current not exceeding 30 mA, 24 V, 60 mANumber of analog inputs 2

  • 8/16/2019 Catalogue АТ24 2015 05

    59/67

    H.5

    Line H

    Н/380 V

    Type analog inputs programmable 4..20 mA,, 0..5 mA,, 0..10 V

    Sampling period 4 ms

    Number of analog outputs 1

    Type analog output programmable 4..20 mA, 0..5 mA, 0..10 V

    Number of digital outputs 4 relay outputs

    Type of digital output• 2 outputs are switching type• 2 outputs are normally open type

    Digital outputs with custom logic(PNP or NPN)

    6

    Number of digital inputs 8

    Type of digital input• 24 V, input resistance: about 4 kOhm• PTC sensor, Resistance switch 3 kOhm/1,8 kOhm• emergency stop

    Acceleration and deceleration S-shaped acceleration / deceleration, linear adjustable

    Type of protection

    • power switch (U, V, W, T)• OCP hardware (U, V, W) / OCP software (U, V, W)• temperature of switches• Ud max/ Ud min• loss of one or more phases• overheating of the braking resistor• motor overload /motor overheating

    Dielectric strengthfor power circuits and auxiliary circuits having electricalcommunication with the power circuit — 2500 V

    Insulation resistance > 1 MOhm

    Communication protocol Modbus

    Physical interface 2-wire RS-485 for Modbus

    Frame transmission RTU for Modbus

    Data transfer rate• 115200 bps• 1200 — 250000 bps• up to 1 bps

    Data format 8 bit, 1 stop bit , no parity

    Addresses number 1 .. 255 addresses for Modbus

    Access method slave

    Control options Bluetooth module or Wi-Fi module

    Electromagnetic compatibility• EN 55011 class A, group 2, IEC/EN 61800-3, category С3•with the additional EMC lter, EN 55011 class В, group 1,IEC/EN 61800-3, category С1

    Relative humidity 80 % at a temperature of +20 °С (with no condensation)

    Optional unit «ЕХТ1» unit, for expand numbers of input / output

    StandardsGOST 24607-88,GOST 13109-97, GOST 15150-69, GOST 14254-96,GOST 17516.1-90, GOST 12.1.044-89, EN 61800-3:2004, EN 55011,ЕN 61000-6 3/4

  • 8/16/2019 Catalogue АТ24 2015 05

    60/67

    H.6

    Н/380 V

    Model range Line H

    Model of Triol AT24Rated

    motor power, kWRated current

    of power circuit, ATotal VFD output

    power, kVA

    АТ24-5К5-380-H***** 5,5 11 7,5

    АТ24-7К5-380-H***** 7,5 15 10АТ24-11К-380-H***** 11,0 22 15

    АТ24-15К-380-H***** 15,0 30 18

    АТ24-18К-380-H***** 18,0 36 22

    АТ24-22К-380-H***** 22,0 45 28

    АТ24-30К-380-H***** 30,0 60 38

    АТ24-37К-380-H***** 37,0 75 45

    АТ24-45К-380-H***** 45,0 90 56

    АТ24-55К-380-H***** 55,0 110 72

    АТ24-75К-380-H***** 75,0 150 100АТ24-90К-380-H***** 90,0 180 175

    АТ24-М11-380-H***** 110,0 220 145

    АТ24-М13-380-H***** 130,0 260 175

    АТ24-М16-380-H***** 160,0 320 210

    АТ24-М20-380-H***** 200,0 400 260

    АТ24-М25-380-H***** 250,0 500 330

    АТ24-М32-380-H***** 315,0 640 400

    Mounting dimensions4 holes ØD

  • 8/16/2019 Catalogue АТ24 2015 05

    61/67

    H.7

    Line H

    Н/380 V

    Overall dimensions

    Triol AТ24 model Width, mm Height, mm Depth, mm VFD weight,kg

    АТ24-5К5-380-H*****

    215 449,5 224 12,4АТ24-7К5-380-H*****

    АТ24-11К-380-H*****

    АТ24-15К-380-H*****

    284 557 280

    18АТ24-18К-380-H*****

    АТ24-22К-380-H*****

    АТ24-30К-380-H*****29

    АТ24-37К-380-H*****АТ24-45К-380-H*****

    268,5 619,5 301,5 47АТ24-55К-380-H*****

    АТ24-75К-380-H*****

    420 855 334

    72

    АТ24-90К-380-H*****75

    АТ24-М11-380-H*****

    АТ24-М13-380-H***** 1

    670 1400

    417

    143

    АТ24-М16-380-H***** 1 144

    АТ24-М20-380-H***** 1 150

    АТ24-М25-380-H*****1

    770 1856 164АТ24-М32-380-H***** 1 170

    Triol AТ24 model L, mm H, mm D, mm

    АТ24-5К5-380-H*****

    145 422

    8

    АТ24-7К5-380-H*****

    АТ24-11К-380-H*****

    АТ24-15К-380-H*****

    183 520

    АТ24-18К-380-H*****

    АТ24-22К-380-H*****

    АТ24-30К-380-H*****

    АТ24-37К-380-H*****

    АТ24-45К-380-H*****183 596

    АТ24-55К-380-H*****

    АТ24-75К-380-H*****

    360 825АТ24-90К-380-H*****

    АТ24-М11-380-H*****

    АТ24-М13-380-H***** 1

    610 1350АТ24-М16-380-H***** 1

    АТ24-М20-380-H***** 1

    АТ24-М25-380-H***** 1710 1850

    АТ24-М32-380-H***** 1

    1 — variations in dimensions are permissible

  • 8/16/2019 Catalogue АТ24 2015 05

    62/67

    H.8

    Н/380 V

    Dimensional outlineАТ24-15К-380-Н***** — АТ24-37К-380-Н*****

    Dimensional outlineАТ24-5К5-380-Н*****, АТ24-7К5-380-Н*****, АТ24-11К-380-Н*****

  • 8/16/2019 Catalogue АТ24 2015 05

    63/67

    H.9

    Line H

    Н/380 V

    Dimensional outlineАТ24-45К-380-Н*****, АТ24-55К-380-Н*****

    Dimensional outlineАТ24-75К-380-Н*****, АТ24-М11-380-Н*****

  • 8/16/2019 Catalogue АТ24 2015 05

    64/67

    H.10

    Н/380 V

    Dimensional outlineAT24-М25-380-Н*****1, АТ24-М32-380-Н*****1

    Dimensional outlineAT24-М13-380-Н*****1, АТ24-М16-380-Н*****1, АТ24-М20-380-Н*****1

  • 8/16/2019 Catalogue АТ24 2015 05

    65/67

    1

    Supporting documentation review 

    Supporting documents include:• Design manual — contains the detailed information needed for the VFD assembly and

    its next operation;

    • Operation manual — gives information about the VFD installation, commissioning,maintenance and technical parameters;

    • Programming manual — describes Triol AT24 functions and parameters, capabilities ofcontrol panel as well as programming and operational aspects;

    • Additional units manual — presents detailed technical characteristics of additional units,schemes for connection, mounting and adjustment instructions;

    • Quick Operating Manual — contains most necessary information for mechanicalinstallation and quick setup of VFD parameters.

    SD

  • 8/16/2019 Catalogue АТ24 2015 05

    66/67

    2

     Additional equipment 

    This chapter contains information about the following additional units:• unit for connection an incremental encoder Triol ENCO2;• unit for connection an absolute encoder Triol ENCO3.

    Triol ENCO2 unit is intended for connection of incremental angular converters (encoders)to Triol AT24 VFD’s.

    Plug-in unit Triol ENCO2 also can be applied to improve the operation safety ofmechanics by controlling:• exceeding of preset speed;• backspin rotation.

    Triol ENCO2 unit provides:• resistance to interferences with the use of built-in electrically isolated supply unit of

    encoder — 5 V 200 mA;

    • support of operation with dierent output signals types of encoder (open collector,open emitter, standard TTL and HTL, dierential pair);

    • capability of work with dierent levels of output encoder signals.

    Triol ENCO3 unit is intended for connection of incremental angular converters(encoders) to Triol AT24 VFD’s of all the lines, except pump application (vector control ofasynchronous motor is not used).

    Triol ENCO3 unit provides:• resistance to interference with the use of built-in electrically isolated supply unit of

    encoder — 5 V 200 mA;• support of operation with absolute encoders via EnDat v2.0 and EnDat v2.1 protocols;

    • adjustment of interface long-haul line with the use of built-in 120 Ohm resistors.

    AE

  • 8/16/2019 Catalogue АТ24 2015 05

    67/67

    Services

    Triol Corporation is a leading developer and manufacturer of electric equipment. That’swhy it pays considerable attention to the oered products service support. We conducttrainings for exploiting personnel of our Customers and Partners.

    Triol Corporation’s service support is carried out in collaboration with our Partners andincludes:• Warranty repair and spare parts;• Post-warranty repair and spare parts;• Diagnosis and Troubleshooting;• Online Technical support ;• Specialist on-site visit to the Customer;• Preventative service;• Personnel trainings.

    We have spare parts warehouse and service support through our partners. It allows usto immediately respond to your requests and allows our Partners and Customers to feel

    condent in the future.

    S