  • Generator/Engine Control Unit

    Features

    Microprocessor Based Design Universal LED Graphic Interface, Displays Generator Status and Failures Modular Design, Quick InstallationWith Annunciator Output * Selectable MPU Signal for Speed SensingSuitable for Pump Engine control With Lamp Test Function for All Front Panel LEDs and Annunciator Lamps Provide IDLE control For Elec. GovernorsFive Adjustable Time Delay PotentiometersSix DIP Switches For Specification Setting

    Adjustable Timers SpecificationsEngine Pre-Heat 2 ~ 30 Seconds Starter Cranking time 1 ~ 15 Seconds Energize to STOP 1 ~ 15 Seconds Engine Idle (Governor) 0 ~ 300 Seconds Engine Cool-down 0 ~ 300 Seconds

    DC Supply 9.0 to 36 VDCAlternator Input Range 5 ~ 300VAC

    50/60 HzMPU Signal Input Range 2V to 70V PeakRated MPU Frequency 100 Hz ~ 10,000 HzFuel Solenoid Signal Output 10 Amp @ 12/24VDC

    Protection & Alarm Status Indicators Start Signal Output 10 Amp @ 12/24VDC Start Failure High Water Temperature Low Oil Pressure Overspeed

    Underspeed No Speed Signal Extra Prog. Input

    Annunciator Output 300mA @ 12/24VDCPower Consumption Under 3VA on AutoOperating Temperature -20 ~ 70Relative Humidity < 90 %Weight 200 gram

    Mechanical Specifications (mm/Inch) Installing Panel

    * Together with RA-20 Annunciator Module

    ???????????????????????

    ????????

    ???????????

    ?????????????????????????????????

    ???????????????????????

    ?????????????

    ??????????

    ????????????????

    ?????????????

    GCU-20

    C

  • ?Remote Annunciator Module Together with GCU-20 Module or other ECU with Annunciator output

    Features Works Up to 1500 Meters from The Host Module Using 18 AWG

    Cable (@12/24VDC)

    Universal LED Graphic Interface, Displays Generator Status and

    Failures

    Modular Design, Quick Installation

    Circuits are Finger Safe with UL94-V0 Epoxy Protection

    Simplify All Wiring with Pluggable Terminal Block

    Easy Assembly & Maintenance with No Chance of Wiring Mistakes

    Icon Reference TableIcon Description Icon? Description

    Low Oil Pressure Alarm Wrong speed Alarm

    Auxiliary Alarm (Flashing) No Speed Signal Alarm (Flashing)

    High Water Temperature Alarm Engine Running Indicator

    Engine IDLE Indicator (Flashing)

    Over Crank Alarm Common Alarm Indicator

    Specifications?Rated Input Voltage 9.0 to 36 VDC Operating Temperature -20~+70 ?

    Working Distance from Host ECU 1500 Meters Relative Humidity Maximum 95%

    Standard Cable 18 AWG Dimensions 88.0 (L) x 88.0 (W) x 37.5 (H) mm

    Terminal Block Capacity 300 VAC / 15A Weight 150 gram

    Power Consumption AV 0.1 rednU

    Mechanical Specifications (Unit : mm[inch] ) Installing Panel

  • Universal 16 Amp 1/2 Wave Self Excited Automatic Voltage Regulator Can Be Used In Parallel Operation Compatible with Marelli Motori M40FA640A-MARK I and Caterpillar AVR(*1)

    Features

    < 0.5% Regulation Suitable for brushless type generator Sensing Input

    170~510 VAC Can be used in Parallel Operation 16 ADC Current Output Suitable Frequency 50/60 Hz Soft Start Voltage Ramping Load CT Current Compensation, Analogue Voltage Input

    Specifications Sensing Input Voltage 170~510 VAC Single Phase 2 wire Voltage Build-up Residual volts at AVR terminal > 5 VAC

    zH 06/05 ycneuqerF External Volts Adjustment 5% with 2 K 1 watt trimmer

    Power Input Voltage 60~300 VAC Single Phase 2 wire CT Current Compensation Input 1A or 5A (Selectable)

    Max. 90 VDC @ 240 VAC input Analogue Input 5 VDC 10% AC @ 3 VDC

    Output Unit Power Dissipation Max. 10 Watt Current Continuous 16A,

    Intermittent 20A for 10 Sec. Thermal Drift 0.03% per change in AVR ambient

    Resistance Min. 6 @ 35 VDC

    Voltage Regulation < 0.5% (with 4% engine governing)

    Under Frequency Protection 55 Hz @ 60 Hz , 45 Hz @ 55 Hz

    (Adjustable)

    EnvironmentVibration 3.3G @ 100~2 KHz Relative Humidity Maximum 95%

    Operation Temperature -40~70 Storage Temperature -40~85

    Mechanical Specifications Unit : mm AVR Control Function VOLT Voltage Adjustment

    STAB Stability Adjustment

    U/F To Set the U/F(*2) Knee Point

    DROOP To Adjust Droop

    TRIM Analogue Input Adjustment

    Physical Specification Dimension 156.0 (L) x 106.0 (W) x 41.0 (H) mm

    Weight 450 g 2%

    156

    88

    138

    106 41

    X5

    Notes (*) : 1. Use for reference purpose only and not a genuine, Marelli Motori and Caterpillar

    product. 2. U/F : Under Frequency protection

  • Built as a Mid Level voltage regulator foruse on a Marathon* generator with PMG Self Excited Automatic Voltage Regulatorusing IGBT Insulated Gate Bipolar Transistors

    Features< 1% Regulation110 / 220 / 400 VAC InputPMG input Frequency 40 to 500HzPMG Voltage input from 25~300VAC

    Under Frequency ProtectionTwo-stage For STAB Adjusting Range

    SpecificationsSensing Input Terminal 0-110V 95 ~ 140V

    Terminal 0-240V 185 ~ 250V Full Load PMG 5 VACOutput Voltage 90VDC @ 220VAC Under Frequency Protection U/F Range 42 ~ 62Hz

    Current Continuous 8A External Voltage Adjustment 10% with1K Ohm

    Intermittent 12A for 10sec EMI Suppression Internal Electromagnetic Interference FilteringResistence 10 to 100 Ohms Voltage Regulation < 1% (with 4% engine governing)

    EnvironmentVibration 1.5G @ 5 ~ 30 Hz 5.0G @ 30 ~ 500 Hz Relative Humidity < 95%

    Operating Temperature -40 to 60 Degree C. Storage Temperature -40 ~ 85?

    Mechanical SpecificationsAVR Controls Functions

    VOLT Voltage Adjustment

    STAB Stability Adjustment

    U/F UFRO Knee point setDROOP Droop Adjustment

    TRIM Analogue Input Adjustment

    U/F DIP U/V Rate Set

    Physical Specifications

    Dimension 150.0 (L) x 135.0 (W) x 55.3 (H) mm

    Weight 480 g 2%

    UNIT : mm

    PMG can be single and 3 phase

    * This is not a Marathon ProductsThe Marathon Name is use forReference purpose only

  • 8 Amp With Full Harmonic (Compounding Winding) AVR or Harmonic + Auxiliary Winding or PMG Automatic Voltage Regulator PWM Output Compatible with Leroy Somer R438 * regulators *All manufacturer names, numbers, symbols and descriptions are used for reference purpose only and do not imply that any part is the product of these manufacturer.

    Features < 1% Regulation 110 / 220 / 380 VAC Programmable Input Harmonic Frequency 40~500 Hz Harmonic Voltage 25~300 VAC Under Frequency Protection Two-stage For STAB Adjusting Range PWM Output

    Specifications Sensing Input Terminal 0-110V = 95~135V Volts Regulation < 1% (with 4% engine governing)

    Terminal 0-220V = 180~250V Voltage Build-up Harmonic residual volt. > 5 VAC

    Terminal 0-380V = 360~515V External Volts Adjustment 10% @ 1K

    Frequency 50/60 Hz single phase EMI Suppression Internal electromagnetic Interference

    Filtering

    Output Voltage 150 VDC @ 220 VAC Under Frequency Protection U/F range 42~62 Hz

    Current Continuous 8A Droop Current Transformer N:5A or N:1A

    CAV 04 > .ces 01 rof A21 tnettimretnI Unload Harmonic + Auxiliary

    Winding

    Resistance 10~100 zH 005~04 esahP elgniS CAV 052 < Full Load Harmonic + Auxiliary

    Winding

    EnvironmentOperation Temperature -40~+60 Relative Humidity Maximum 95%

    Storage Temperature -40~+85 Vibration 1.5G @ 5~30 Hz / 5.0G @ 30~500 Hz

    Mechanical Specifications (Unit : mm)

    AVR Control Function VOLT Voltage Adjustment

    STAB Stability Adjustment

    U/F UFRO Knee point set

    DROOP Droop Adjustment

    TRIM Analogue Input Adjustment

    U/F DIP U/V Rate Set

    Physical SpecificationDimensions 150.0 (L) x 135.0 (W) x 55.3 (H) mm

    Weight 480 g 2%

    UF ON

    1

    380

    UFRO

    Z1X1 X2

    LAMSTAB DROOP

    0VF+Z2 F- 110 220

    S2

    TRIMVOLT

    A2A1

    VR

    VRS1

    S3

  • AMF Controller Interface Module With Pluggable Terminal Block to AMF Controller*1 & BTS*1

    Features For use in Electrical Operation and Mechanical Maintenance Transfer Switch connecting to Assorted Brand AMF Controller Available on the Market Simplify All Wiring with Pluggable Terminal Block Easy Assembly & Maintenance with No Chance of Wiring Mistakes Circuits are Finger Safe with UL94-V0 Epoxy Protection Built-In 3 Phase Fuses to Protect Mains & Generator Circuits Build-In Adjustable Transfer Delay Time for Mains and Generator (10~15 Seconds)

    Specifications Item Function Current Fuse Capacity

    F1 Protect Normal Power Circuit 6.3A 50 KA @ 500 VAC

    F2 Protect Normal Power Circuit 6.3A 50 KA @ 500 VAC

    F3 Protect Normal Power Circuit 6.3A 50 KA @ 500 VAC

    F4 Protect Emergency Power Circuit 6.3A 50 KA @ 500 VAC

    F5 Protect Emergency Power Circuit 6.3A 50 KA @ 500 VAC

    F6 Protect Emergency Power Circuit 6.3A 50 KA @ 500 VAC

    Item Function Capacity

    TB1 Connect to Transfer Switch 300VAC / 15A

    TB2 A51 / CAV003 rellortnoC FMA ot tcennoC

    Mains "ON" A7 / CAV052 sniaM ot rotareneG morf refsnarT

    Generator "ON" A7 / CAV052 rotareneG ot sniaM morf refsnarT

    Mechanical Specifications (Unit : mm)

    Physical SpecificationDimensions 150.0 (L) x 135.0 (W) x 45.5 (H) mm

    Weight 260 g 2%

    U N I T : m m

    *1 BTS : Basic Transfer Switch *2 AMF : Automatic Mains Failure Controller

  • Part NO Length Rated Volt Housing600VAC

    600VAC

    870 mm

    1500 mm

    AMP 770022-1

    AMP 770022-1

    HU-087

    HU-150A

    Description : Harness for use with CM0900Usage : Connect CM0900 Control to Transfer Switch--Two Extra wires for Remote Start Connection terminal

  • DoubleThrow Heavyduty ATSwith CenterOff125Amps 0.7 PF 90 to600VACrated 3 pole

    ? ?

    Features ?Compact design -- easy installation & programmingElectrically operated, mechanically held with manualoverr ide(Open Transition) with adjustable time in neutralComprehensive LED digital displayNormal & Emergency OV and UV Monitor ingManufactures with high quali ty UL 94V-0 Plastic

    ?

    One time Exercise in 1 to 4 weeks interval with and without LoadRecommended for use, by the Cell -Phone Industry, Home and Industrial applications

    TS3P125 Specifications TC-V2 SpecificationsRated Voltage 600VAC Over Volt Setting 110 to 530 VAC (adjustable)

    Rated Current 125A Over Volt Reset Below 10VAC of the OV setting

    Rated Frequency 50/60 HZ Under Volt Setting 80 to 470VAC (adjustable)

    Transfer DoubleThrow Type Under Volt Reset Exceed10VAC of the UV setting

    Operating Current 2.0A @ 220V AdjustableTime Delay TDEN 0~90 Sec.

    Poles 3P TDNE 0~90 Sec.

    Rated Short-Time Current 3.0 KA/1 Sec@ 250VAC TDEC 0~90 Sec.

    Shor t Circuit Peak Value 7.5 KA TDES 0~30 Sec.

    Utili zation Category AC-33A* TDOFF 1~20 Sec.

    L ife > 6000Times/ With Load Normal ON Capacity 7A @ 250VAC Max

    Rated Coil Operating

    Voltage

    TCS3P125-11 / 90~140VAC Standby ON Capacity 7A @ 250VAC Max

    TCS3P125-22 /180~270VAC Remote Start Capacity 6A @ 277 VAC / 6A @ 28 VDC Max

    Class PC Power Consumption < 1W

    Connection Front Panel Cut-Out 47.0 0.5 mm x 1620.5 mm

    Mechanical Specifications Unit : mm General SpecificationsTemperature -10~70?

    Humidity < 95%

    Dimensions 167.0(H) x 172.0(W) x 85.0(D) mm

    Weight 1.8 Kg 2%

    * IEC60947-6 Util ization Category AC-33A :1. Frequent operations.

    2. Motor loadsor mixed loads including motors, resistive loads

    and up to 30% incandescent lamp.

    Patent Number: U.S. Pat. No. 7,557,683

  • Double Throw ATS With Neutral OFFRated Current 125 Amps Voltage 220/120 VACFeaturesBuilt-in control with choice of installation either on the side Electrically operated mechanically held type ATSManual Emergency Override handleDelay on OFF position (Adjustable from 0 to 18 sec.)

    Compact size

    Switch and connection indicator lightsChecks for normal source over and under voltages Built-in 7-Days exerciser -- with or without load Adjustable TDEN, TDNE, TDES, TDEC timersDesigned for the cell-phone industry, industrial & home use

    TS125 SpecificationsRated Voltage 120/240 VAC Overvoltage Trip 270VAC (Factory Set) Rated Current 125 A Overvoltage Reset 260VAC Rated Frequency 50/60 Hz Undervoltage Trip 170VAC (Factory Set) Transfer Double Throw Type Undervoltage Reset 180VAC Operating Current 2.6A @ 220V Adjustable Time Delay TDEN 0 ~ 30 Sec. 10% Poles 2P TDNE 0 ~ 30 Sec. 10% Rated Short-Time Current 10 KA/one sec. @ 250 VAC TDEC 0 ~ 120 Sec. 10% Short Circuit Peak Value 25 KA

    TDES 0 ~ 90 Sec. 10% Utilization Category AC-33A* TD OFF 0 ~ 18 Sec. 10% Life >6000 Times With Load

    Remote Start Dry Contact Capacity 6A @ 277 VAC / 6A @ 28 VDC Max Class PCPower Consumption < 1W

    Mechanical Specifications

    Connection FrontPlastic UL94V-0 Door Mount Cut-Out 47.0 0.5 mm Wide x 162 0.5 mm

    General Specifications

    Temperature -10 ~ 70 Degree C Humidity < 97% Weight 1.6 KG / 3.5 lbs Dimensions H*W*D=168.0*151.5*85.0mm

    H*W*D= 6.6 x 6 x 3.35

    Note: IEC60947-6 Utilization Category AC-33A1. Frequent operations 2. Motor loads or mixed loads including motors, resistive

    loads and up to 30% incandescent lamp

    UNIT: mm

    Model Number TSC2P125-22

    1.8 Inches wide x 6.4 Inches High

    of the switch or separately on the enclosure door

  • Assembles using the ATS-01TSP-15 Logic boards andPlated Cooper Buss Bars

  • Universal Electronic Engine Governor Controller with Smoke Limiting, & Idle Speed. Works with Built-in & Non-Built-in PTs Pumps, also can be used

    with Low Current, Electric over Hydraulic Oil Pumps Type

    Governor Actuators

    Features

    Works on a wide ranges of MPU/flywheel frequencies

    15Amp Max Output

    Suitable for all types of diesel and Gas engines

    High Sensitivity and stable at Low Frequency Variations

    Moisture, vibration, and rust protected, Epoxy encapsulated

    electronics

    For Use With Isochronous Generators & Automatic Paralleling

    PLC controls

    Idle Speed Adjustment and connections for a Remote Speed

    POT

    Operating Voltage 12/24 VDC Auto Select Ramp Time 3 to 20 Sec. Adjustable

    Output Current From 20ma to 15Amp Operation Environment Vibration 3G @ 100~2KHz

    Frequency Range 600Hz~9500Hz (PMG Signal) Relative Humidity Maximum 95%

    Idle Speed Frequency Adjustable From 30~85% of normal Operation Temp. -40~85

    Speed Band 0.25% at Steady State Storage Temp. -40~85

    Temp. Stability Dimension 147.0 (L) x 114.0 (W) x 40.0 (H) mm Between -40~85 Better than 0.5%

    neewteb Weight 700g 2%

    Remote Speed Adjustment Range

    (2 mode)

    Adjustable Range 5% with 5

    K potentiometer

    Mechanical Specifications Unit : mm DIP Switch Description SW1 ON 600~1200Hz

    SW2 ON 1200~2500Hz

    SW3 ON 2500~5000Hz

    SW4 ON 5000~9500Hz

    Governor ControlsDROOP Droop rate Adjustment

    GAIN MPU Output Gain Adjustment

    Int. Engine Stability Adjustment

    RAMP TIME Soft Start Adjustment

    IDLE

    1 2 3ACT

    4 5 6 7 MPU9ILS

    8 10 11

    ~+

    REMOTESPEED POT RUN SPEED

    IDLE SPEED

    SW1-ON 600~1200HZSW2-ON 1200~2500HZ

    SW4-ON 5000~9500HZSW3-ON 2500~5000HZ

    POWER : DC12/24V

    DROOP INT. GAIN RAMP-TIME

    SW

    SPEED Speed Adjustment

    IDLE Idle Speed Adjustment

    Specifications

  • Magnetic Pickups (MPU)

    Is a measuring device for monitoring the speed of the driving force. When a ferromagnetic object (Usually the generators flywheel gear) passes by the tip of the MPU, it produces a magnetic field, the MPU induced a voltage signal internally, and the frequency of the voltage as the input to the speed control signal and accurately measure the prime mover speed.

    Specifications EnvironmentDC Resistance 95 3% Operating Temperature -40~+100

    Output Signal 12 VAC (P-P) @ 5 KHz Vibration 3G @ 100~2 KHz

    Clearance 0.5 mm

    Mechanical Specifications (Unit : mm[inch] )

    Installation Reference (Unit : mm[inch] )

    TYPE : EM81

    TYPE : EM121

  • Model SS3524 Intelligent Switch Mode Battery ChargerIs an easy to install compact charger specially intended foruse in gensets. It's wide input voltage range allows the charger to be used in many different countries.The charger is designed for permanent connection to automotive batteries. It maintains the battery fully charged,without overcharging or gassing. The charger is protectedfrom reverse polarity, short circuit and overloads. Emergency Charge Fail Alarm is conveniently built in.Multiple units may be connected in parallel in order to obtain higher current ratings.

    1. Use on a 2 x 12V Lead Acid Battery only2. With Line power disconnected, connect Battery terminals

    "+/-" to battery leads "+/-"3. Connect Line voltage to battery charger on lines L1 & L2,

    form 100 to 240 Vac 50/60 Hz4. Charging voltage should be 27.6+/-0.2VDC and the

    indicate LED marked "ON" should illuminated when power is ON

    Caution! Crimp and property secure terminal lugs on to power wires to avoid shorts

    6. With Power ON check charge current LED bar. The current decreases as the battery charges.

    7. "0 A" indicates the battery is fully charged.9. Charger can remains connected during engine cranking

    and running. 10. Voltage sensing circuit automatically disconnect power

    when the battery is fully charged.11. Emergency Charge Fail Alarm Relay Available for use

    as part of a charge fail engine protection alarm.

    1. Danger: Potentially lethal voltages are present inside the charger. Do not open case and attempt to adjust or repair this unit.

    2. Ventilate battery enclosure, batteries generate explosive hydrogen gas.

    3. Avoid flames and sparks near batteries4. Avoid high humidity and corrosive gases near charger 5. Minimum battery voltage must higher than 10 VDC or

    the charger will automatically disconnect.6. This is not a power supply. Use only as a battery

    charging.

    Automatic Battery Charger for GeneratorsGENERAL INFORMATION

    SPECIFICATIONS

    INSTALLATION INSTRUCTIONS OUTLINE DRAWING

    DANGERPower supply : 100 ~ 240V, 45 ~ 65 Hz DC Output : 27.6VDC 3ADC (continuously)Charge Mode : FloatDC Voltage Regulation : 80% @full loadOperating Temperature : 0 C ~ 40 CHumidity : 0 ~ 90% Relative HumidityVibration & Shock : 5 ~ 50Hz 2mm pk - pk 50 ~ 100 Hz 1mm pk - pk 100 mm drop onto chassis faceContact Capacity : 0.5A @240VACProtection : current limiting protection short circuit protection reverse polarity protectionWeight : 0.72 Kgs (1.6 lbs) Powder Coated Aluminum

    24V AUTOMATIC BATTERY CHARGERModelSS3524

    Output

    +L1 L2

    Power In : 100 to 240Output : 27.6 Vdc 3 Adc

    Charging Current (A)ON 0.7 1.5 2.2 3.0

    TM

    Power100 to

    Charge Fail Relay

    AttentionBattery Low

    2.9"

    4.43

    "

    2.61

    4.72"

    McPhersonControls

    TM

    [email protected]

    1.800-541-7677

    27.6VDC 3AInternational Model

    The SS3524 battery chargers

    use computer technology to

    sense the battery condition and maintain the

    correct charge and maintenance levels

    Page 41

  • Model SS3512 Intelligent Switch Mode Battery ChargerIs an easy to install compact charger specially intended foruse in gensets. It's wide input voltage range allows the charger to be used in many different countries.The charger is designed for permanent connection to automotive batteries. It maintains the battery fully charged,without overcharging or gassing. The charger is protectedfrom reverse polarity, short circuit and overloads. Emergency Charge Fail Alarm is conveniently built in.Multiple units may be connected in parallel in order to obtain higher current ratings.

    1. Use on a 12V Lead Acid Battery only2. With Line power disconnected, connect Battery terminals

    "+/-" to battery leads "+/-"3. Connect Line voltage to battery charger on lines L1 & L2,

    form 100 to 240 Vac 50/60 Hz4. Charging voltage should be 13.8+/-0.2VDC and the

    indicate LED marked "ON" should illuminated when power is ON

    Caution! Crimp and property secure terminal lugs on to power wires to avoid shorts

    6. With Power ON check charge current LED bar. The current decreases as the battery charges.

    7. "0 A" indicates the battery is fully charged.9. Charger can remains connected during engine cranking

    and running. 10. Voltage sensing circuit automatically disconnect power

    when the battery is fully charged.11. Emergency Charge Fail Alarm Relay Available for use

    as part of a charge fail engine protection alarm.

    1. Danger: Potentially lethal voltages are present inside the charger. Do not open case or attempt to adjust or repair this unit.

    2. Ventilate battery enclosure, batteries generate explosive hydrogen gas.

    3. Avoid flames and sparks near batteries4. Avoid high humidity and corrosive gases near charger 5. Minimum battery voltage must higher than 5 VDC or

    the battery charger will automatically disconnect.6. This is not a power supply. Use only as a battery

    charging.

    13.8VDC 5AInternational Model

    Automatic Battery Charger for GeneratorsGENERAL INFORMATION

    SPECIFICATIONS

    INSTALLATION INSTRUCTIONS OUTLINE DRAWING

    DANGERPower supply : 100 ~ 240V, 45 ~ 65 Hz DC Output : 13.8VDC 5ADC (continuously)Charge Mode : FloatDC Voltage Regulation : 80% @full loadOperating Temperature : 0 C ~ 40 CHumidity : 0 ~ 90% Relative HumidityVibration & Shock : 5 ~ 50Hz 2mm pk - pk 50 ~ 100 Hz 1mm pk - pk 100 mm drop onto chassis faceContact Capacity : 0.5 @240VACProtection : current limiting protection short circuit protection reverse polarity protectionWeight : 0.72 Kgs (1.6 lbs) Powder Coated Aluminum

    12V AUTOMATIC BATTERY CHARGERModelSS3512

    Output

    +L1 L2

    Power In : 100 to 240Output : 13.8 Vdc 5 Adc

    Charging Current (A)ON 1.2 2.5 3.7 5.0

    TM

    Power100 to

    Charge Fail Relay

    AttentionBattery Low

    2.9"

    4.43

    "

    2.61

    4.72"

    McPhersonControls

    TM

    [email protected]

    1.800-541-7677

    The SS3512 battery chargers

    use computer technology to

    sense the battery condition and maintain the

    correct charge and maintenance levels

    Page 42

  • Automatic Float Battery Charger12 and 24 volt 10 Amps Low RippleFeatures

    Specifications

    Adjustable for Lead Acid and NiCad BatteriesFloat Charge Factory Det For Lead AcidBattery, Charger Will Supply Current UntilBattery voltage is Equal to Set VoltageOver-Voltage ProtectionCurrent Limiting ProtectionFor Use in 120 and 240 Volt Inputs

    AC Power Input

    Final Charge

    Output Current

    1 Phase 120Vac +/- 10%1 Phase 240Vac +/- 10%

    13.8 Vdc for CH191227.6 Vdc for CH1924

    10Adc Mx for CH191210Adc Vdc for CH1924

    Power Input Fuse 5 Amp / 250 Vac

    Unit Power Dissipation 230 W Max

    Weight 5.4 Kg --- 12 lbs

    Protection Reverse PolarityOver VoltageShort CircuitCurrent Limiting

    Dimencion 12 Inches Wide7 Inches High5.5 Inches Deep

  • CH1712

    CH1724 Automatic Battery Charger

    Wall Mountable 20Amp Features Low Ripple Voltage ( Below +/- 3% )

    Float / Equalize Charge Mode

    Adjustable Equalize Charging Time

    Voltage Detector and Over Voltage Protection

    No Current Drain When Input Power Is Off

    Set Any Charge Current Up To 20 Amp with

    Over Current Protection

    Selectable 110 / 220 VAC Input

    Specifications

    AC Power Input Voltage 1 Phase 100 / 220 VAC 10% Charge Mode Float Charge and Equalize Charge

    Frequency 50 / 60 Hz 5% Cooling Forced Fan Cooling

    Equalize Charge Output Voltage CH1712 Charge 12 VDC Battery at 14.5 VDC Efficiency 80% @ Full Load CH1724 Charge 24 VDC Battery at 28.8 VDC Ripple 3%

    Float Charge Output Voltage CH1712 Charge 12 VDC Battery at 13.8 VDC Protection Short circuit, over current,

    CH1724 Charge 24 VDC Battery at 27.6 VDC charge fail alarm, over voltage

    Equalize Charge Voltage Range 12 VDC 13.5VDC ~ 16.0VDC Adjustment no current drain when input power is off

    24 VDC 27.0VDC ~ 31.0VDC Adjustment Dimension 400 (L) x 300 (W) x 295 (H) mm

    Float Charge Voltage Range 12 VDC 13.0VDC ~ 14.5VDC Adjustment Weight CH1712 24.6 Kg 2 24 VDC 25.8VDC ~ 28.0VDC Adjustment CH1724 30.0 Kg 2 Output Current Range 0.5 ADC ~ 20.0 ADC Operation Temp. -10 ~ 40 Output Voltage Regulation < 1% Storage Temp. -20 ~ 40 Equalize Charging Time 61224 Hours setting Relative Humidity < 90 %

    Mechanical Specifications

    FRONT VIEW AND ILLUSTRATIONS

    DC Voltage Meter DC Current Meter Power LED Float Charge LED Equalize Charge LED Equalize Charge Setting Button Input Power MCCB Output Power MCCB Adjustable Equalize Voltage Adjustable Charge Voltage Adjustable Float Charge Current

    UNIT: mm

  • CA

    E

    F

    D

    B

    A B C D E F2

    2.53

    456

    www.mcphersoncontrols.com

    71/8

    83/4

    147/8

    8

    9

    133/8

    131/2

    149/16

    109/16

    147/8

    167/8

    167/8

    241/4

    251/4

    151/2 151/2

    151/2

    193/8 193/8

    193/8 193/8

    151/2

    133/8

    9

    16

    16

    231/8

    253/8

    313/822

    2ID

    2.5ID

    3ID

    4ID

    5ID

    6ID

    Compact muffler systems de-signed to supply high-quality intake and exhaust sound attenuation to the industrial engine and compressor market.

    We also designed, engineered and manufacture to meet OEM customer specifications.

  • MCPHERSON HEAVY DUTY FILTER & WATER SEPARATORSMcPherson Controls preassembles filter kits are intended for easy installation on the vacuum side of the engine fuel pump. These assemblies protect the engine injection system from water, tank rust, dirt, algae, and varnishes. Contaminated diesel fuels can no longer harm your engine.Similar to the RACOR* Model 1000FH this assemblies can be fitted with a large number of aftermarket filter cartridges including; RACOR*, Baldwin*, Donaldson*, Fleet-Guard*, Luber-Finer*, etc. they can in 2, 10, and 20 micron.

    Model WS1000-1A Similar to RACOR* 1000FHMax Flow Rate: 180 gphSize 11.5 High, 5.8 Wide, 4.8 DepthPort Size 3/4-16UNFWt 10 lbs

    Model WS1000-2A Similar to RACOR* 75/1000FHXMax Flow Rate: 360 gphSize 22 High,18.75 Wide, 11 DepthPort Size 7/8-14UNFWT 31 lbs

    Model WS1000-2A Similar to RACOR* 79/1000FHVMax Flow Rate: 540 gphSize 22 High,21.5 Wide, 12 DepthPort Size 3/4-NPTWt 53 lbs

    4501 NW 27 aveMiami FL 33142Ph 305-634-1511Fax 305-634-1461

    * For reference purpose only, not a genuice RACOR, Baldwin*, Donaldson*, Fleet-Guard*, Luber-Finer* product